Assembly and operating instructions Power System Module

image

Contents

1. 1 L1L2L3 N PE L1L2L3 N PE L1L2L3 N PE L1L2L3 N PE Circuit 1 Circuit 3 Circuit 4 Circuit 2 400V 400V 400V 400V Fig 5 PSM Plus wiring diagram 14 PSM Power System Module 8 Metered PSM Power System Module with measuring function Model No DK 7856 016 2 infeeds 16A Model No DK 7856 003 1 infeed 32A Designed in accordance with DIN EN 60950 1 VDE 0805 2003 03 Ks 3 Danger AN b An electrical test must be performed after the completion of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked Warning To prevent damage to the Rittal Metered PSM ensure that N and L for the infeed are not interchanged Note A power pack is required if the Metered PSM is not connected to the CMC TC Processing Unit Model number for the required power pack DK7201 210 connection cable is also required see Chapter 15 8 1 Scope of supply 1 x bus bar 1 x operating instructions 1 x cable bracket incl assembly parts 2 x female connection 7856 016 1 x Connection cable wit CE Plug 856 003 multipoint strip 32A 8 2 Features The principal feat
2. 38 8 1 SCOPE OF SUPPLY 15 17 1 MOUNTING IN THE RITTAL FLEXRACK I 40 8 2 FEATURES Ip NGA ME ee 15 17 2 MOUNTING IN RITTAL TS ENCLOSURES 41 8 89 CONFIGURATION cene 15 17 2 1 Mounting in Rittal TS enclosures 8 4 OPTIONAL ACCESSORIES 222222222222 16 base and roof frames 42 8 5 DESCRIPTION 16 17 2 2 Mounting Rittal TS enclosures 9 6 CONFIGURATION OF THE METERED PSM 18 punched mounting sections 43 8 7 CONNECTION TO THE CMC TC 19 17 3 MOUNTING IN RITTAL TE ENCLOSURES 43 8 7 1 Associated documents 19 17 4 MOUNTING THE PLUG IN MODULES 44 8 7 2 Commissioning 19 17 5 INFEED STRAIN RELIEF SUGGESTION 45 8 8 WIRING DIAGRAM 22 17 6 ALTERNATIVE POSSIBILITIES FOR MOUNTING OF THE CABLE CLAMP 46 9 PSM Version 32 A Single Phase 23 17 7 ALTERNATIVE POSSIBILITIES FOR MOUNTING sa 4 aaa 2 OF THE CABLE CLAMP BRACKET 46 9 3 CONFIGURATION aed kaaa 23 18 Electrical Connection of the Bus bar 47 9 4 OPTIONAL ACCESSORIES 23 18 1 TECHNICAL DATA OF THE INFEEDS 47 9 5 FUNCTION PRINCIPLE 24
3. Observe the correct fuse values Refer to the notes on the rating plate Cr The plug in modules can now be clipped onto the bus bar in the desired positions The modules are locked into place using the lugs on the end faces A module can only be released from the bus bar after it has been unlocked PSM Power System Module PSM Power System Module To unlock a module the lugs on the end faces must be pressed down at the same time at both ends The module can then be pulled off the bus bar The connection direction of the modules is used to select infeed or Condition All infeeds must be connected by the customer For information about assembly and connection of the bus bar please see Chapters 17 and 18 All important operating parameters such as application limit temperature and humidity allowed voltage supply back up fuses etc are described in more detail in Chapter 16 1 5 4 Optional accessories Cr Note Article numbers see Chapter 15 over voltage protection Various country specific plug in modules DK 7856 025 or DK 7856 026 connection cable PSM Power System Module 7 PSM Power System Module 5 5 Function principle The diagram shows circuit A and circuit B of a 2000 mm strip A oo em Fig 1 Function principle The red arrow on the PSM module points up B infeed For single phase 32 A infeed the B circuit must be protected using a 16 A class C circ
4. Fig 10 Tab 15 PSM Power System Module 21 Metered PSM 8 8 Wiring diagram 7856 016 7856 003 111213 PEN L3 L2 L1 Circuit 1 Circuit 2 00V Fig 11 Metered PSM wiring diagram 22 PSM Power System Module PSM Version 32 A Single Phase 9 PSM Version 32 A Single Phase Model No DK 7856 321 Model No DK 7856 043 with integrated RCD Danger electrical test must be performed after the completion of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked 9 1 Scope of supply 1 x bus bar with CEKON connection cable and connection plug 1 x operating instructions 1 x cable bracket incl assembly parts 9 2 Features The principal features of the Rittal PSM are 1 infeed with connection cable and CEE connection plug 32 A current are available Integrated protection using a 16 A class C circuit breaker The Model 7856 043 has two integrated RCDs Residual Current protectiv Devices and allows the application in areas as described in DIN VDE 0100 410 Six plug in modules be inserted on 2 metre bus bar this corresponds to 36 IEC 60320 appliance sockets Shock hazard protected design i e it is not necessary to configure the whole bus bar at once Various country modules UK USA F B earthing pin plug IEC 320 1
5. max current 1 x 32A 16 A circuit breaker characteristic Integrated fusing 7256 043 offers additionally two RCDs residual current 30mA Fusing installed by Back up fuse installed by the customer 32 A per phase the customer Observe the data on the bus bar rating plate Max cable length 50 observe the cable cross section and backup fuse 32 A blue 32 A plug single phase Connection plug of the infeed Cable cross section 3G6mm 36 PSM Power System Module Technical Specifications 16 6 Technical specifications PSM 32 A 3 phase Model No DK 7856 323 Potential Me Yes equalisation Farthin Yes separate housing earthing point 6 3 mm flat pin 3 connector min 2 5 mm cross section category Temperature 5 C to 45 C temperature range 4 F to 140 F connection Power supply Power supply 3 400 VAC N PE max current 3 x 32 A icin Back up fuse installed by the customer 32 A per phase 9 Observe the data on the bus bar rating plate 50 m observe the cable cross section and backup fuse Max cable length Connection plug of 3x32 A variant with red CEKON 32 A plug 3 phase the infeed Cable Cross section 5G6mm PSM Power System Module 37 Assembly Instructions 17 Assembly Instructions The Rittal PSM system must be installed in an enclosure or case system which also provides protection against external influences The length of lines should not exce
6. 008 7856 010 7856 015 7856 016 7856 020 55 CONEIGUBATION 6 7856 043 7856 321 AND 7856 323 30 54 OPTIONAL ACCESSORIES 7 15 4 7856 010 7856 016 7856 020 7856 008 5 5 FUNCTION PRINCIPLE 8 ei 5 6 WIRING DIAGRAM 9 16 Technical Specifications 32 6 PSM with fixed infeed 10 Ev TECHNICAL SPECIFICATIONS PSM BUS BAR 62 FEATURES nn g 16 2 TECHNICAL SPECIFICATIONS PSM WITH 541 22 10 FIXED INFEED eeeeeeeee ener nnns 33 6 4 OPTIONAL ACCESSORIES 11 16 3 TECHNICAL SPECIFICATIONS PSM PLUS WITH 4 WAY 0000 34 d PSM PIUS NN 12 16 4 TECHNICAL SPECIFICATIONS PSM BUS BAR SCOPE OF SUPPLY 12 WITH 3 PHASE CURRENT MEASUREMENT 35 7 2 FEATURES 12 16 5 TECHNICAL SPECIFICATIONS PSM 32 A 7 3 222222222424 5 12 36 7 4 OPTIONAL ACCESSORIES 13 16 6 TECHNICAL SPECIFICATIONS PSM 32 A 3 7 5 WIRING DIAGRAM 0 44 14 PHASE 37 8 Metered 15 17 Assembly Instructions
7. 1 Infeed 2 Fig 7 Metered PSM The angled plug connectors permit a parallel routing of the connection cable to the Metered PSM bus bar Cr Note The Model DK 7856 003 has a fixed infeed with DIN Bolting and a 32A CE Plug PSM Power System Module 17 Metered PSM 8 6 Configuration of the Metered PSM Select infeed by turning and confirm by pressing Select parameters by turning and confirm by pressing Only the measured Use Exit to values are displayed m return to start for the Total display display Select parameters Disp by turning and confirm by parameters pressing Set high and low setpoint for voltage or current by turning and confirm by pressing Use Exit to leave the menu em Use Exit to return item to start display Configuration of the display Press Jog Dial for more than 3 sec then release to reach the configuration menu change the value and confirm by pressing Use Exit to leave th menu item Sequence diagram 1 Configuration of the Metered PSM Turn Jog Dial to Use Exit to return to start display 18 PSM Power System Module 8 7 Connection to the CMC TC 8 7 1 Associated documents The guide for the CMC TC Processing Unit DK 7320 100 and its safety notes also apply together with this guide You can download the German version of the guide from http www rimatrix5 de service support downlo ads asp Pow
8. 19 2 JBABRLIHING namna WA a AD 48 9 6 WIRING DIAGRAM 2 2 25 18 3 INFEED CONNECTION PLUG DATA AND ASSIGNMENT aaa 49 10 oo System Module with a 32 A Infeed 18 4 TERMINAL ASSIGNMENT 49 SCOPEOFSUPPLY ANN 26 10 2 FEATURES a a a aa 26 10 3 CONFIGURATION 26 10 4 OPTIONAL ACCESSORIES 26 10 5 WIRING 27 2 PSM Power System Module empty page PSM Power System Module 3 Documentation Notes 1 Documentation Notes The audience for this guide is the technical specialists familiar with the assembly installation and operation of the Rittal PSM e You should read this operating guide prior to the commissioning and store the guide so it is readily accessible for subsequent use Rittal cannot accept any liability for damage and operational malfunctions that result from the non observance of this guide 1 1 Retention of the documents This guide and all associated documents are part of the product They must be given to the operator of the unit and must be stored so they are available when needed 1 2 Used symbols The following safety and other notes are used in this guide Symbol for a handling instruction e This bullet point indicates that you should perform an action Safety and other notes Danger Immediate danger to li
9. Model No DK 7856 015 Designed in accordance with DIN EN 60950 1 VDE 0805 2003 03 Danger electrical test must be performed after the completion ofthe assembly installation and maintenance work ry All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked 7 1 Scope of supply 1 x bus bar 1 x operating instructions 1 x cable bracket incl assembly parts 7 2 Features The principal features of the Rittal PSM Plus are Four separate 3 infeeds redundant configurations permitting 192 Acurrent available 48 A per infeed Six plug in modules can be accommodated on a 2000 mm bus bar which corresponds to 36 IEC 320 C13 appliance sockets IEC 60320 C13 IEC 60320 C19 plug in modules and earthing pin plug Shock hazard protected design i e it is not necessary to configure the whole bus bar at once Modular design for simple installation Optimised cable management Full compatibility with Rittal enclosure systems 7 3 Configuration The vertical bus bar is an H shaped aluminium section The power distribution for the individual plug in modules is realised in the rear concealed section The bus bar can be clipped directly into the vertical enclosure frame members of Rittal flexRack i or else retrofitted to other existing racks To upgrade TS enclosures you require the DK 7856 022 or DK 7856 023 mo
10. PSM offers revolutionary power management for IT racks The modular power supply system realises power input via a vertical mounting rail bus bar with a three phase infeed The individual Power System Modules are simply clipped to this rail The Metered PSM bus bar provides the possibility to measure the voltage current power and energy per infeed and per phase The mains frequency can also be measured per infeed The Metered PSM bus bar also provides the possibility to set the upper and lower threshold values for voltage and current for each phase I O port connection on the CMC TC or power pack Jog Dial LCD display Fig 6 Metered PSM The Jog Dial is used to configure the Metered PSM bus bar and to navigate through the display menu represented in the LCD display The connection to the CMC TC allows all parameters of the bus bar to be queried using a Web interface The inclusion in a network management system using SNMP is also possible If the Metered PSM bus bar is operated directly with a power pack all values can be read from the display The power pack is connected to the port A remote configuration administration is not possible for operation with power pack for the Metered PSM bus bar PSM Power System Module Metered PSM If the threshold value of the Metered PSM bus bar is undershot or overshot the display flashes and the error message will be displayed at the lower edge Infeed
11. a strain relief PSM Power System Module Cr Note The mounting of the strain relief may vary according to the specific installation situation the enclosure Warning The strain relief for the connection cable must be made the immediate vicinity of the connection plug of the PSM bus bar If the strain relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket Note Where gland plates are fitted the cable can also be tied directly to the base frame 45 Assembly Instructions 17 6 Alternative possibilities for mounting of the cable clamp bracket Fig 35 Side view 2 from outside 17 7 Alternative possibilities for mounting of the cable clamp bracket For the PSM bus bars DK 7856 321 and DK 7856 323 the strain relief on the bus bar is made using a PG screwed cable gland It may be necessary to use cable ties to attach the infeed line s to a mounting bracket Fig 33 Top view 1 outside from above Fig 36 Side view 3 from outside Fig 34 Side view 2 from inside 46 PSM Power System Module Electrical Connection of the Bus bar 18 Electrical Connection of the Bus bar The 7856 010 and 7856 020 bus bars can be used to provide a redundant power supply system for IT enclosures To achieve this the Rittal PSM has two separate infeed possibilities infeed infeed Il see Section 5 6 For
12. consumers will be lost if the plug in module is unlocked Warning When the modules mounted there must be no consumers in the power sockets First mount the modules on the bus bar and then connect the corresponding consumers Warning To remove a plug in module C should first remove consumers connected to the module concerned Note The plug in modules C can also be mounted and removed while the bus bar A is in operation Note The module is mounted correctly if all four retaining lugs D at the end faces have locked into the bus bar Note When doing so ensure that the module is not tilted Note If the modules are equipped with miniature circuit breaker it can be reset after being activated by pressing the yellow pin Warning A possible short circuit must be corrected beforehand PSM Power System Module Assembly Instructions 17 5 Infeed strain relief suggestion For model number DK 7856 010 020 016 e he strain relief for the connection cable must be realised using the provided bracket C To do this attach the bracket C with the supplied screws D to the base frame E e The connecting cable F is then fastened to the cable bracket C with the enclosed cable ties G This configuration provides for adequate strain relief Fig 30 Example for the installation of a strain relief Fig 31 Example for the installation of
13. in more detail in Chapter 16 5 9 4 Optional accessories Cr Note Article numbers see Chapter 15 Over voltage protection Various country specific plug in modules 23 PSM Version 32 A Single Phase 9 5 Function principle The diagram shows circuit A and circuit B of a 2000 mm strip A 2 Fig 12 Function principle The red arrow on the PSM module The black arrow on the PSM module points up points up F1 fuse F2 fuse For single phase 32 A infeed the B For single phase 32 A infeed the A circuit F1 fuse is tapped after the circuit F2 fuse is tapped after the 16 A class circuit breaker 16 A class circuit breaker 24 PSM Power System Module PSM Version 32 A Single Phase 9 6 Wiring diagram 1 9 L1 NPE 230V Fig 13 PSM 32 A single phase A x Note The Model 856 043 has additionally to the two fuses two integrated RCDs PSM Power System Module 25 Power System Module with a 32 A Infeed 10 Power System Module with a 32 A Infeed Model No DK 7856 323 VDE Reg No A592 Tested and certified in accordance with DIN EN 60950 VDE 0805 2000 12 j N Danger Ae An electrical test must be A performed after the completion of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked r 10 1 Scope of supp
14. m observe the cable cross section and backup fuse Power supply Max cable length Tension spring terminal plug type Number of poles 5 cross section mm 4 Max cross section AWG 12 Connection plug of EN rated voltage 500 V the infeed Rated peak voltage 6 kV Level of contamination 3 Rated current 16A Bared length mm 8 Bared length inch 0 33 32 PSM Power System Module Technical Specifications 16 2 Technical specifications PSM with fixed infeed Model No DK 7856 005 2000 mm enclosure height with one infeed Model No DK 7856 006 2000 mm enclosure height with two infeeds equalisation Yes separate housing earthing point 6 3 mm flat pin Earthing connector 2 5 mm cross section econ IP 20 to EN 60529 category Temperature 5 C to 45 C range 41 F to 104 F temperature range 4 F to 140 F connection Bue Infeed 3 400 VAC N PE max current 3 x 16 A Pp y Infeed Il 3 400 VAC N PE max current 3 x 16A Pa Back up fuse installed by the customer 16 A per phase 9 Observe the data on the bus bar rating plate 50 m observe the cable cross section and backup fuse Max cable length 3 phase circuit with neutral conductor and PE separate neutral conductor Connection plug of PE the infeed max current 3x16 A per infeed PSM Power System Module 33 Technical Specifications 16 3 Technical specifications PSM Plus with 4
15. modules can now be clipped onto the bus bar in the desired positions They are locked into place by way of the lugs on the end faces A module can only be released from the bus bar after it has been unlocked To unlock a module the lugs on the end faces must be pressed down at the same time at both ends The module can then be pulled off the bus bar For information about assembly and connection of the bus bar please see Chapters 17 and 18 All important operating parameters such as application limit temperature and humidity allowed voltage supply back up fuses etc are described in more detail in Chapter 16 6 10 4 Optional accessories Cr Note Article numbers see Chapter 15 over voltage protection Various country specific plug in modules PSM Power System Module Power System Module with a 32 A Infeed 10 5 Wiring diagram w Circuit L1L2L3 N PE 40 Fig 14 PSM 32 A 3 phase wiring diagram PSM Power System Module 27 Mounting of the Lockout 11 Mounting of the Lockout for DK7856 321 and DK 7856 323 The DK 7856 321 and DK 7856 323 PSM bus bars provide a possibility to prevent the unintentional activation of the circuit breakers by the installation of the supplied lockout Cr Note The installation of the lockout does not affect the actual operation of the line circuit breaker Fig 18 Correct installation of the lockout Opening for l
16. relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket Note Observe the correct fuse values Refer to the notes on the rating plate Cr PSM Power System Module The plug in modules can now be clipped onto the bus bar in the desired positions The modules are locked into place using the lugs on the end faces A module can only be released from the bus bar after it has been unlocked To unlock a module the lugs on the end faces must be pressed down at the same time at both ends The module can then be pulled off the bus bar The connection direction of the modules is used to select infeed or Il redundancy see Section 5 5 Condition All infeeds must be connected by the customer Cr Note Model DK 7856 005 only got one infeed So it does not matter in which direction you put in the modules For information about assembly and connection of the bus bar please see Chapters 17 and 18 All important operating parameters such as application limit temperature and humidity allowed voltage supply back up fuses etc are described in more detail in Chapter 16 2 6 4 Optional accessories Cr Note Article numbers see Chapter 15 over voltage protection Various country specific plug in modules PSM Power System Module PSM with fixed infeed PSM Plus 7 PSM Plus Power System Module with 4 Infeeds
17. the rating plate on the bus bar Fig 37 Separate earthing point in the vicinity of the infeed for bus bars with plug in infeed 48 18 2 Earthing A Cr Warning The bus bar possesses a housing earthing point in the area of the infeed marked with the symbol A conductive connection must be made from this earthing point to the enclosure frame Sep housing earthing point min cross section 2 5 mm The PE conductor of both power circuits is brought to a common housing potential in the bus bar Note The connection of separate protective conductor is not required for DK 7856 321 and DK 7856 323 PSM Power System Module 18 3 Infeed connection plug data and assignment 1 conductor female multi point conductor with side mounted locking 5 pole for insertion in the base terminal block The following conductors can be used Single wire Multi wire Fine wire with tinned single cores Max cross section 4 mm Max cross section 12 AWG Bared length 8 mm Bared length 0 33 inch Compacted strands with wire end ferrule or pin type cable socket crimped gas tight Cr Note When wire end ferrules are used the next smaller cross section must be chosen Danger The connection plug does not serve as an on load isolator 18 4 Terminal assignment PE Fig 38 Terminal assignment PSM Power System Module 49 empty page 50 PSM Power System Module S
18. way infeed Model No DK 7856 015 Potential Y Ss es equalisation Yes separate housing earthing point 6 3 flat pin connector 9 2 5 mm cross section categor range 41 F to 104 F 5 to 95 relative humidity non condensing temperature range 4 F to 140 F Ene Wa connection Circuit 3 400 VAC 230 VAC N PE max current 3 x 16 A Circuit Il 34400 VAC 230 VAC N PE max current x 16 A Circuit 3 400 VAC 230 VAC N PE max current x 16 A Circuit IV 3 400 VAC 230 VAC N PE max current 3 x 16 A Power supply Back up fuse installed by the customer 16 A per phase Observe the data on the bus bar rating plate Max cable length 50 m observe the cable cross section and backup fuse 4x Wieland GST 18 connection plug 3 phase circuit with neutral conductor and PE separate neutral conductor common PE Connection plug of the infeed max current 3x16 A per infeed 34 PSM Power System Module Technical Specifications 16 4 Technical specifications PSM bus bar with 3 phase current measurement Model No DK 7856 016 Model No DK 7856 003 Aluminium anodised Height for enclosure height 2000 mm Width approx 60 mm Depth approx 55 mm Weight approx 5 kg without packing without modules Potential Y aes es equalisation Earthi Yes separate housing earthing point 6 3 mm flat pin connector arthing min 2 5 mm cross section 2
19. 0 to EN 60529 category Temperature 5 C to 40 C range 41 F to 104 F temperature range 4 F to 140 F connection _ FT connection 7856 016 Circuit 400 VAC N PE 7856 003 Power supply max current 3 x 16 A Circuit 230V 50Hz 60Hz Circuit Il 400 VAC N PE max current 3 x 16A Back up fuse installed by the customer 16 A per phase Fusing 7856 016 respectively 32 A 7856 003 Observe the data on the bus bar rating plate Max cable length 50 m observe the cable cross section and backup fuse 2 7856 003 Tension spring terminal plug CE Connection plug 32 A type Number of poles 5 Max cross section 2 4 Connection plug of Max cross section AWG 12 the infeed EN rated voltage 500 V Rated peak voltage 6 kV Level of contamination 3 Rated current 16A Bared length mm 8 Bared length inch 0 33 PSM Power System Module 35 Technical Specifications 16 5 Technical specifications PSM 32 A single phase Model No DK 7856 321 Model No DK 7856 043 Potential ee es equalisation Earthin Yes separate housing earthing point 6 3 mm flat pin 9 connector min 2 5 mm cross section IP protection IP 20 to EN 60529 categor Temperature 5 C to 45 C range 41 F to 113 F Humidity range 5 to 95 relative humidity non condensing Storage 20 C to 60 C temperature range 4 F to 140 F Power connection Power supply Power supply 1 200 230 VAC N PE
20. 15 1 7856 003 7856 005 7856 006 DK 7856 240 PSM plug in module 7856 008 7856 010 7856 020 earthing pin plug red 7856 01 6 7856 043 7856 321 Dk 7856 170 Over voltage protection 7856 323 Optional power pack for DK 7201 210 DK 7856 016 with DK 7200 210 D F B connection cable Model No PSM 6 way IEC320 plug DK 7856 070 lin module with fuse PSM 6 way IEC320 plug DK 7856 080 lin module without fuse DK 7200 211 connection cable DK 7856 082 IEC320 C13 6 way red DK 7200 213 CH connection cable PSM 4 way earthing pin DK 7856 090 plug in module with fuse 15 2 7856 015 Model No 6 way C13 module with DI 7200 09 2x16 A inputs 2 way earthing pin plug DK 7856 101 module with 2x16 inputs 4 way C19 module with m 2x16 A inputs DK 7856 170 Over voltage protection 3 phase mains DK 7856 018 connection cable EN 60 309 DK 7856 017 Extension cable 15 3 7856 003 7856 005 7856 006 7856 008 7856 010 7856 015 7856 016 7856 020 7856 043 7856 321 and 7856 323 Model No PSM 4 way earthing pin DK 7856 100 plug in module without fuse PSM 4 way French plug DK 7856 110 in module with fuse PSM 4 way French plug DK 7856 120 lin module without fuse PSM 4 way USA plug in DK 7856 130 module with fuse PSM 4 way USA plug in DK 7856 140 module without fuse PSM 4 way UK plug in DK 7856 150 module with fuse PSM 4 way UK plug in DK 7856 160 module without fuse PSM
21. 3 19 appliance sockets PSM Power System Module Integrated fuses Modular design for simple installation Optimised cable management Complete compatibility with Rittal enclosure systems 9 3 Configuration The vertical bus bar is an H shaped aluminium section The power distribution for the individual plug in modules is realised in the rear concealed section The bus bar can be clipped directly into the vertical enclosure frame members of Rittal flexRack i or else retrofitted to other existing racks To upgrade TS enclosures you require the DK 7856 022 or DK 7856 023 mounting kit and for TE enclosures the DK 7000 684 PSM adaptor Cr Note Observe the correct fuse values Refer to the notes on the rating plate The plug in modules can now be clipped onto the bus bar in the desired positions They are locked into place by way of the lugs on the end faces A module can only be released from the bus bar after it has been unlocked To unlock a module the lugs on the end faces must be pressed down at the same time at both ends The module can then be pulled off the bus bar The connection direction of the modules is used to select circuit fusing 1 or circuit fusing B F2 For information about assembly and connection of the bus bar please see Chapters 17 and 18 All important operating parameters such as application limit temperature and humidity allowed voltage supply back up fuses etc are described
22. 321 and DK 7856 323 are exceptions Warning If the bus bar is connected via the CEKON CEE connecting cable the corresponding CEKON CEE supply socket must be as close as possible to the bus bar Warning If the bus bar is not connected via a CEKON CEE connector but is instead installed permanently a suitable mains power disconnection device must be provided Risk of death The bus bar and the plug in modules must not be opened Risk of death If for some reason work needs to be performed on the bus bar all circuits must be disconnected from the mains and protected against being switched on again Risk of death A clear label must be provided at the disconnecting device of both power circuits describing how the equipment is to be properly disconnected from the power supply Warning The cable strain relief bracket enclosed in the package should be used at the infeed 47 Electrical Connection of the Bus bar Warning Observe all warnings and rating plates attached to the bus bar Danger An electrical test must be performed after the completion of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked Warning When connecting the bus bar ensure that an appropriate fuse is provided Observe the regulations of the local power supply company as well as
23. 4 way CH plug in DK 7856 180 module with fuse PSM 4 way CH plug in DK 7856 190 module without fuse DK 7856 201 Active PSM 8 way individually switchable DK 7856 210 PSM light module DK 7000 684 PSM adaptor for TE rack DK 7856 022 TS mounting kit for static installation DK 7856 023 ITS mounting kit mobile 30 PSM Power System Module Accessories for PSM Bus bars 15 4 7856 010 7856 016 7856 020 7856 008 Designation Connection cable 3 16A 6A Connection cable 1 1 Connection cable UPS 1 phase C14 X Com PSM Power System Module 31 Technical Specifications 16 Technical Specifications 16 1 Technical specifications PSM bus bar Model No DK 7856 010 1200 mm enclosure height Model No DK 7856 020 2000 mm enclosure height Model No DK 7856 008 for 2200mm Racks Weight approx 1 5 kg without packing without modules Potential equalisation Yes separate housing earthing point 6 3 mm flat pin Earthing connector 2 5 mm cross section 20 to EN 60529 category Temperature 5 C to 45 C range 41 F to 113 F Humidity range 5 to 95 relative humidity non condensing Storage 20 C to 60 C temperature range 4 F to 140 F Power connection Infeed 3 400 VAC N PE max current x 16 A Infeed Il 3 400 VAC N PE max current 3 x 16 A Bein Back up fuse installed by the customer 16 A per phase 9 Observe the data on the bus bar rating plate 50
24. Power System Module PSM FRIEDHELM LOH GROUP 7856 003 7856 005 7856 006 7856 008 7856 010 7856 015 7856 016 7856 020 7856 043 7856 321 7856 323 We reserve all rights for this technical documentation Without our previous consent it must neither be reproduced nor made available for third parties Nor must it be put to any other misuse by the receiver or third parties Any violation of the above obliges the violating party to pay compensation and may lead to penal action Microsoft Windows is a registered trademark of Microsoft Corporation Acrobat Reader is a registered trademark of Adobe Systems Incorporated Table of Contents 11 Mounting of the Lockout 28 12 Maintenance 29 1 Documentation 1 1 4 1 1 RETENTION OF THE DOCUMENTS A 13 Glennie ARR 29 1 2 USED 5 5 4 4 2 04000024 2 d Wa DISDOSS am PERI 29 2 Safety NOTES AP PA 4 15 Accessories for PSM Bus bars 30 3 ANTCOCUCTION an aa Ega A AG man Gan 5 15 1 7856 003 7856 005 7856 006 7856 008 7856 010 7856 020 7856 016 7856 043 4 Service and Service Address 5 7856 321 AND 7856 323 30 19 2 90 0 1 30 9 Un d LOU Module 15 3 7856 003 7856 005 7856 006 7856
25. ail Info RITTAL de Cr Note Please indicate always the item number in the reference line Support Tel 49 0 2772 505 9052 Complaints 49 0 2772 505 1855 Fax 49 0 2772 505 2319 Further information concerning the Rittal PSM can be downloaded from the RimatriX5 homepage www rimatrix5 com PSM Power System Module 5 PSM Power System Module Model No DK 7856 010 Model No DK 7856 020 Model No DK 7856 008 for 2200mm Racks VDE Reg No A592 Tested and certified in accordance with DIN EN 60950 VDE 0850 2000 12 Danger AN electrical test must be performed after the completion 1 of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked 5 1 Scope of supply 1 x bus bar 2 x female multipoint connection strip 1 x operating instructions 1 x cable bracket incl assembly parts 5 2 Features The principal features of the Rittal PSM are Two separate 3r infeeds redundant configurations permitting 96A current in total i e 48 A per infeed Four plug in modules can be accommodated on a 1200 mm bus bar which corresponds to 24 IEC 320 C13 appliance sockets Seven plug in modules be accommodated on a 2000 mm bus bar which corresponds to 42 IEC 320 C13 appliance sockets Fight plug in modules can be accommodated on a 2200mm bis bar
26. any changes to the Rittal PSM that are not described in this guide or in the associated guides The operational safety of the unit is guaranteed only for its approved use The limit values stated in the technical specifications see Chapter 16 may not be exceeded under any circumstances In particular this applies to the permitted ambient temperature range and to the permitted IP protection category When used with a higher required IP protection category the Rittal PSM must be installed PSM Power System Module in a housing or enclosure with a higher IP protection category Operation of the Rittal PSM system in direct contact with water aggressive media or inflammable gases and fumes is prohibited In addition to these general safety notes also observe any special safety notes listed for the specific tasks in the individual sections The strain relief for the connection cable must be made in the immediate vicinity of the connection plug of the PSM bus bar If the strain relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket 3 Introduction The stable flow of information and production is the lifeline of an enterprise Loss of data failure of function and production causes extensive and in many cases life threatening damage Therefore it is the declared company objective to ensure a maximum of safety and reliability Rittal
27. at 1828384 Accept Reset B P3 BE Lokales Intranet 2 Fig 8 Tab 1 PSM Power System Module Metered PSM The name of the Metered PSM bus bar is alSo used to send SNMP traps Notification text Upper and lower threshold value Alarm management see CMC TC PU manual 19 Metered PSM Tabs 1 to 12 are constructed identically Tabs 1 to 3 represent the L1 L2 and L3 voltages of infeed 1 Tabs 4 to 6 represent the current of infeed 1 Tabs 7 to 12 provide the values for infeed 2 Tab 13 provides the values for the power and the energy of infeed 1 Tab 14 provides this information for infeed 2 gt CMC TC Processing Unit Microsoft Internet Explorer P Datei Bearbeiten Ansicht Favoriten Extras gt A A Asuchen XgFavorten meden lt 4 Ge S B Lr Adresse 4 192 168 115 131 Unit Name MeteredPSM Serialnr Software 00001 V1 1 Circuit 1 Total kWh 1234 5 kWh Total kW 50 0 kW Frequency 50 0 Hz Values per Phase Circuit 1 Power 1 1 Power 1 2 Power 1 3 Energy 1 1 Energy 1 2 Energy 1 3 3 ah HUG _ 7 ca Fig 9 Tab 13 20 PSM Power System Module Metered PSM Tab 15 provides an overview for the voltage and current values of both infeeds and all phases 3 CMC TC Processing Unit Microsoft Internet Explorer x id hn gt 192 168 115 131 Unit Name Serialnr Software 00001 V1 1 Status Setup
28. ate vicinity of the connection plug of the PSM bus bar If the strain relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket Mounting in flexRack i also see 17 1 Mounting in TS enclosures also see 17 2 Mounting in TE enclosures also see 17 3 Cr Cr Note In the case of enclosures with a swing frame mounting is only possible on the side of the enclosure where the swing frame hinges are fitted Otherwise the swing radius of the swing frame will be impaired Note In 600 mm wide enclosures the rear 482 6 mm 19 level may be slightly obstructed by the PSM bus bar This must be taken into account when assembling the enclosure PSM Power System Module Cr Note The DK 7856 022 023 mounting kit is required to assemble the TS enclosure The two mounting brackets are screwed to the end covers of the PSM The two fastening holes in the brackets permit mounting at various depths It must be ensured however that the PSM remains readily accessible for installed punched section 39 Assembly Instructions 17 1 Mounting in the Rittal flexRack i Fig 20 flexRack i Fig 21 flexRack i with installed PMS bus bar 40 With Rittal flexRack i the Rittal PSM can be clipped into the vertical frame members of the enclosure e To this end the bus bar A is placed up against the side of the vertical se
29. both infeeds the supplied accessories contain the required connection plugs to attach a fixed connection cable As an alternative you can use a preassembled connection lead with plug see Chapter 15 This plug connector is described in Section 18 4 It is used to connect a permanently installed connection cable to the bus bar Within the bus bar the two three phase circuits are completely independent of each other i e they each make available L1 L2 L3 N and PE The protective conductors of the two circuits are placed together in the bus bar and connected to the bus bar housing The Rittal PSM Plus provides four separate infeed possibilities infeed 1 to infeed 4 see Section 7 5 The Rittal Metered PSM provides two separate infeed possibilities infeed 1 to infeed 2 see Section 8 8 Rittal PSM Version 32 single phase provides one infeed possibility Each module slot is protected with its own circuit breaker see Section 9 6 Given the appropriate selection of the backup fusing load distribution and group formation of loads a redundancy can be provided Rittal PSM Version 32 A three phase provides an infeed possibility separated into two circuits using two circuit breakers see Section 9 6 The modules do not need to be turned PSM Power System Module 18 1 Technical data of the infeeds Note Note that the product uses a multi infeed bus bar DK 7856 005 DK 7856 007 DK 7856
30. chaltschrank Systeme Industrial Enclosures Coffrets et armoires lectriques Kastsystemen Apparatskapssystem Armadi per quadri di comando Sistemas de armarios LI O0 Stromverteilung Power Distribution Distribution de courant Stroomverdeling atr mf rdelning Distribuzione di corrente Distribuci n de corriente MEATA Elektronik Autbau Systeme Electronic Packaging Electronique Electronic Packaging Systems Electronic Packaging Contenitori per elettronica Sislemas para la electr nica TL 2 FEZ22Z ITY FATA System Klimatisierung system Climate Control Climatisation Systeemklimatisering Systemklimatisering Soluzioni di climalizzaziones Climatizacion de sistemas SREB VATA IT Solutions IT Solutions Solutions IT IT Solutions IT l sningar Soluzioni per IT Soluciones Tl Communication Systems Communication Systems Armoires outdoor Outdoor behuizingen Communication Systems Soluzioni outdoor sistemas de comunicaci n Je Ya AT 01 11 A38653 11 IT74 RITTAL Rittal GmbH amp Co KG Postfach 1662 D 35726 Herborn Telefon 49 0 2772 505 0 Telefax 49 0 2772 505 2319 eMail infoGrittal de www rittal de Hii
31. ckets B are fastened to the end covers at the top and bottom of the bus bar The bus bar A with the mounted brackets is then fastened to the appropriate roof and base frame elements using the enclosed screws and washers C 7 Fig 25 Installed PSM bus bar in the TS 8 enclosure 42 PSM Power System Module Assembly Instructions 17 2 2 Mounting in Rittal TS enclosures punched mounting sections Cr Note lf the punched mounting sections are used the bus bars can also be fitted in enclosures of different heights It is also possible to realise a combination of punched section and roof or base frame mounting Warning The strain relief for the connection cable must be made the immediate vicinity of the connection plug of the PSM bus bar If the strain relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket Fig 26 Installation on punched mounting section PSM Power System Module Fig 27 Installation on punched mounting section To accommodate varying heights of enclosure or Rittal PSM another mounting variant 15 possible To do this the punched mounting section must be fitted in the enclosure at the height of the bus bar end covers When doing so observe the assembly instructions of the enclosure type concerned Here too the mounting brackets are fastened to the two end covers of the bus ba
32. ction B Ensure that the bus bar sits in the side groove over the whole length The two parts are then clipped together by pressing the other side of the bus bar to overcome the resistance of the mounting lugs This requires a certain amount of force IN Cr Cr Warning Once the two parts are locked together they cannot be separated again without causing damage to one or both parts Note The 24 U bus bar should not be installed in the 42 U enclosures The length of the bus bar can cause it to shift in the frame section Note View of the snapped in bus bar with vertical enclosure frame PSM Power System Module Assembly Instructions 17 2 Mounting in Rittal TS enclosures E T BP Fig 22 Installation start Fig 23 PSM bus bar with mounting bracket PSM Power System Module The two mounting brackets from the mounting kit must be used These brackets are screwed to the plastic end covers of the bus bar with the enclosed screws Cr Note The depth at which the bus bar is mounted in the enclosure can be varied by screwing the mounting brackets to the plastic covers the other way round 41 Assembly Instructions 17 2 1 Mounting in Rittal TS enclosures base and roof frames e For retrofitting the Rittal PSM can also be fastened to the base and roof frames D The two mounting brackets B from the mounting kit must be used The 90 angled bra
33. ed the lengths specified in the technical data for preventing losses caused by unnecessary line lengths In addition the allowed ambient temperature and humidity ranges must be complied with just as the IP protection category as required for the specific application The corresponding details are contained in Chapter 16 Compliance with a higher required protection category can be achieved by installation into an enclosure having the required protection category General notes to be observed when installing the PSM Warning When using accessories in connection with the Rittal PSM the installation and operating instructions for the accessories and for the Rittal PSM must be observed Note The Rittal PSM can either be clipped into the vertical enclosure frame members of the Rittal or else retrofitted to other enclosures using the corresponding Rittal mounting kit Cr Note During installation the existing national and regional regulations of the country in which the Rittal PSM is to be installed and operated must be observed Electrical shock danger No objects must be inserted into the socket receptacles of the plug in modules nor into the connectors on the bus bar as high electrical voltages may be present and may even result in the death of the persons involved 38 Warning It is imperative to disconnect any device operated via the plug in modules o
34. er must be specified as product group Here you find software updates for the metered PSM as well To view the guide you require the Acrobat Reader program Acrobat Reader can be downloaded from www adobe com 8 7 2 Commissioning The Metered PSM bus bar can be managed completely using the CMC TC PU The Metered PSM bus bar is connected directly with the sensor unit input of the PU The bus bar is recognised automatically and immediately operational after confirmation of the changed configuration on the PU Processing Unit Microsoft Internet Explorer u m ni Datei Bearbeiten Ansicht Favoriten Extras KI zur ck gt G 2 A suchen Favoriten Medien C4 F lye Adresse 4 http 192 168 115 131 gt wechseln zu Links gt Name Testunit Location FuE IT E 7445 RITTAL Contact info rittal de DRIVING IT PEREQRNITANCE Setup Sensorunit 3 PSM_M Uni F p PSM_ 192 168 115 131 Serialnr Software 00001 V1 1 1 2 3 4 5 6 7 8 9101112131415 Type Voltage Circuit 1 Phase 1 Sensor Status 230 1 V OK Message Text Voltage Status 1 1 Setpoint High 253 0 V Range 110 0 250 0v Step 0 5 Setpoint Low 207 0 V Range 90 0 240 0V Step 0 5 Alarm Relay C Disable Enable Alarm Beeper C Disable Enable Alarm Reset Auto Manual Trap Receiver 1 2 RITTAL GmbH 2006 Scheduled Alarm Off 11 21 37 4 Send SMS Form
35. f Rittal PSM from the power supply e g by pulling the mains connection cable before commencing any maintenance or repair work Warning In the case of plug in modules with built in circuit breakers it must be ensured that the module concerned is disconnected from the power supply before resetting the circuit breaker This is achieved for example by pulling the mains connection cable Electrical shock danger Existing safety devices must not be made ineffective Electrical shock danger The Rittal PSM may only be operated with a PE connection The PE connection is made at the terminal strip The prerequisite here is that the connecting cable is connected with a PE terminal on the mains side Warning The voltage of the electrical connection must correspond to the nominal values specified on the rating plate and in Chapter 16 Electrical shock danger Before commencing any work on the Rittal PSM it must always be disconnected from the power supply and secured to prevent inadvertent reconnection Warning The Rittal PSM must not be modified in any way The internal wiring and connections made by the manufacturer must not be altered PSM Power System Module Assembly Instructions Warning Cables are gathered and secured by fitting the enclosed cable brackets in the case or enclosure Note See Chapter 18 Warning The strain relief for the connection cable must be made the immedi
36. fe and limb Warning Possible danger for the product and the environment Note Useful features information and special 2 Safety Notes Observe the subsequent general safety notes for the installation and commissioning of the unit Assembly and installation of the Rittal PSM in particular for wiring the enclosures with mains power may be performed only by a trained electrician Other tasks associated with the Rittal PSM such as the assembly and installation of system components with tested standard connectors and the operation and configuration of the Rittal PSM may be performed only by instructed personnel Observe the valid regulations for the electrical installation for the country in which the unit is installed and operated and the national regulations for accident prevention Also observe any company internal regulations work operating and safety regulations Prior to working at the Rittal PSM system it must be disconnected from the power supply protected against being switched on again An electrical test must be performed after the completion of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked Use only genuine or recommended parts and accessories see Chapter 15 The use of other parts can void the liability for any resulting consequences Do not make
37. itting redundant configurations Cr Note Model DK 7856 005 only got ONE 3 infeed 96 A current in total i e 48 A per infeed Cr Note Model DK 7856 005 48A current in total Seven plugin modules be accommodated on a 2000 mm bus bar which corresponds to 42 IEC 320 C13 appliance sockets Various country modules UK USA F B earthing pin plug IEC 320 13 19 appliance sockets Shock hazard protected design i e it is not necessary to configure the whole bus bar at once Modular design for simple installation Optimised cable management Complete compatibility with Rittal enclosure systems 6 3 Configuration The vertical bus bar is an H shaped aluminium section The power distribution for the individual plug in modules is realised in the rear concealed section The bus bar can be clipped directly into the vertical enclosure frame members of Rittal flexRack i or else retrofitted to other existing racks To upgrade 5 enclosures you require the DK 7856 022 or DK 7856 023 mounting kit and for TE enclosures the DK 7000 684 PSM adaptor The models 7856 005 and 7856 006 did have a fixed connection from the power cable to the bus bar so it is no more possible to disconnect the plug on the bar and there is no need for a cable bracket Warning The strain relief for the connection cable must be made the immediate vicinity of the connection plug of the PSM bus bar If the strain
38. ly 1 x bus bar with connection cable 2 x female multipoint connection strip 1 x operating instructions 1 x cable bracket incl assembly parts 10 2 Features The principal features of the Rittal PSM are One 3 infeed 96 available 32 per phase Six plug in modules can be accommodated on a 2000 mm bus bar which corresponds to 36 IEC 320 appliance sockets Various country modules UK USA F B earthing pin plug IEC 320 C13 appliance sockets Shock hazard protected design i e it is not necessary to configure the whole bus bar at once Modular design for simple installation Optimised cable management Complete compatibility with Rittal enclosure systems 26 10 3 Configuration The vertical bus bar is an H shaped aluminium section The power distribution for the individual plug in modules is realised in the rear concealed section The bus bar can be clipped directly into the vertical enclosure frame members of Rittal flexRack i or else retrofitted to other existing racks To upgrade 5 enclosures you require the DK 7856 022 or DK 7856 023 mounting kit and for TE enclosures the DK 7000 684 PSM adaptor Once the bus bar is fitted in the enclosure a voltage supply must be provided in a suitable form The six slots for the modules are each assigned their own fuse See Section 10 5 Cr Note Observe the correct fuse values Refer to the notes on the rating plate The plug in
39. nent wiring Connecting lines are available as Rittal accessories Cr Note Observe the correct fuse values Refer to the notes on the rating plate Metered PSM Pa Warning The strain relief for the connection cable must be made in the immediate vicinity of the connection plug of the PSM bus bar If the strain relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket The plug in modules can now be clipped onto the bus bar in the desired positions They are locked into place by way of the lugs on the end faces A module can only be released from the bus bar after it has been unlocked To unlock a module the lugs on the end faces must be pressed down at the same time at both ends The module can then be pulled off the bus bar Condition for the redundancy All infeeds must be connected by the customer For information about assembly and connection of the bus bar please see Chapters 17 and 18 All important operating parameters such as application limit temperature and humidity allowed voltage supply back up fuses etc are described in more detail in Chapter 16 4 8 4 Optional accessories Cr Note Article numbers see Chapter 15 DK 7856 025 or DK 7856 026 connection cable over voltage protection Various plug in modules Connection to the CMC TC 8 5 Description The Power System Module Metered
40. ock or chain Fig 15 Lockout Press Press Fig 19 Installation examples The removal of the lockout can be prevented by raising the plastic cap and Fig 16 1 Installation steps inserting a lock or a chain n E 55 NEL i vU The lockout must be inserted in these openings Fig 17 Openings for the installation of the lockout 28 PSM Power System Module 12 Maintenance The Rittal PSM is a maintenance free system that does not need to be opened for the purposes of installation or operation Opening the housing or any accessory components will void any warranty and liability claims 13 Cleaning The Rittal PSM system can be cleaned using a dry cloth The use of aggressive substances like cleanser s solvent acids etc will destroy the system 14 Disposal Because the Rital PSM comprises predominantly of aluminium plastic materials it should be sent for proper disposal and recycling when it is no longer needed The infeed cables should be removed before disposal PSM Power System Module Maintenance 29 Accessories for PSM Bus bars 4 Active PSM 6 way 4x 15 Accessories for PSM Bus bars DK 7856 203 carthing pin plug 22 2 Active PSM 6 way with Cr Note DK 7856 204 4x C19 The accessories are sorted IEC320 Power System according to the use with PSM bus 7 DK 7856 220 Module individually fused 2 GT IEC 320 C19 PSM plug
41. offers support to achieve this By means of universal competence in effective prevention comprehensive safety and centralised organisation i e teamwork for IT safety and reliability This result is optimum combination of power management administration enclosure monitoring server administration and climate control components The solution for the power management is the Rittal PSM Power System Module This concept includes complete power distribution of the enclosure i e power supply distribution and protection The PSM offers a revolutionary energy management for IT racks The modular power supply system permits the power supply using a vertical bus bar on which the power system modules are simply clipped The system is made complete by its sophisticated modular structure A basic installation can be implemented in next to no time When demands then grow over time the original system can simply be expanded with further plug in modules also available in PSM Power System Module Introduction various country specific versions Rittal does not accept any warranty for any other uses of PSM buses 4 Service and Service Address If you have any questions concerning technical or other issues related to our product range Rittal will be pleased to provide any required support You may contact us at the address indicated below Rittal GmbH amp Co KG Auf dem Stuetzelberg D 35745 Herborn Germany E m
42. r The bus bar can then be mounted on the punched sections 17 3 Mounting in Rittal TE enclosures The PSM adaptor DK7000 684 is required for installation in the Rittal TE enclosure Cr Note The associated assembly manual accompanies the PSM adaptor DK 7000 684 43 Assembly Instructions The plug in module C is placed centred on the two connectors B and locked into place with a gentle push If a plug in module needs to be removed 17 4 Mounting the plug in modules Cr Note It is only possible to use original Hittal plug in modules with Rittal PSM The use of any other parts will render all warranty claims void Depending on the type a maximum of seven modules or four modules can be inserted in a 2000 mm or 1200 mm respectively It is not necessary to mount always the full possible number of modules as the bus bar is designed with shock hazard protection Cr Note Important to ensure a redundant configuration for DK 7856 010 DK 7856 020 DK 7856 015 DK 7856 016 all infeeds must be connected For 7856 321 the backup fusing and the load distribution must be taken into consideration See Chapter 18 and Sections 5 6 7 5 8 8 9 6 10 5 yee Fig 29 Installed plug in module 44 release all four retaining lugs D at the same time and carefully withdraw the module Warning Caution when consumers connected to a module the power to all these
43. uit breaker The black arrow on the PSM module points up A infeed For single phase 32 A infeed the A circuit must be protected using a 16 A class C circuit breaker PSM Power System Module PSM Power System Module 5 6 Wiring diagram The diagram shows infeed and infeed of a 2000 mm and a 1200 mm strip Modul Modul1 11213 N PE PE N L3 L2 L1 Circuit1 Circuit2 400V 400V Fig 3 Wiring diagram Rittal PSM 1200 mm aaa aaa ee eS eS i C7 gt Kao JL I m o BH o e The wiring of the 2200mm Model has the same plan with one extra Cr Note 11212 N PE PE N L3 L2 L1 Slot for a PSM Module Circuit 1 Circuit 2 400V 400V Fig 2 Wiring diagram Hittal PSM 2000 mm PSM Power System Module 9 PSM with fixed infeed 6 PSM with fixed infeed Model No DK 7856 005 with one infeed Model No DK 7856 006 with two infeeds VDE Reg No A592 Tested and certified accordance with DIN EN 60950 VDE 0850 2000 12 Danger electrical test must be performed after the completion of the assembly installation and maintenance work All protective conductor terminals and the voltages at all connection plugs and at each individual module slot must be checked 6 1 Scope of supply 1 x bus bar with fixed infeeds 1 x operating instructions 1 x assembly parts 6 2 Features The principal features of the Rittal PSM are Two separate 3 infeeds perm
44. unting kit and for TE enclosures the DK 7000 684 PSM adaptor Once the bus bar is fitted in the enclosure a voltage supply must be provided in a suitable form This can be done either by way of a three phase connector e g IEC309 16 A or with permanent wiring Connecting lines are available as Rittal accessories Cr Note Observe the correct fuse values Refer to the notes on the rating plate The plug in modules can now be clipped onto the bus bar in the desired positions They are locked into place by way of the lugs on the end faces A module can only be released from the bus bar after it has been unlocked To unlock a module the lugs on the end faces must be pressed down at the same time at both ends The module can then be pulled off the bus bar Condition for the redundancy All infeeds must be connected by the customer see Section 7 5 For information about assembly and connection of the bus bar please see Chapters 17 and 18 All important operating parameters such as application limit temperature and humidity allowed voltage supply back up fuses etc are described in more detail in Chapter 16 3 PSM Power System Module 7 4 Optional accessories Cr Note Article numbers see Chapter 15 DK 7856 018 connection cable over voltage protection IEC 60320 C13 IEC 60320 C19 plug in modules and earthing pin plug PSM Power System Module PSM Plus PSM Plus 7 5 Wiring diagram
45. ures of Rittal Metered PSM are Two separate 3 infeeds redundant configurations permitting 96A current available 48 A per infeed PSM Power System Module Metered PSM Cr Note The Model DK 7856 003 has just one singlephase Infeed and offers max 32A Six plug in modules be inserted on a 2 metre bus bar this corresponds to 36 IEC 320 appliance sockets Shock hazard protected design i e it is not necessary to configure the whole bus bar at once IEC 60320 C13 IEC 60320 C19 plug in modules and earthing pin plug Modular design for simple installation Optimised cable management enclosure Full compatibility with Rittal systems Connection to the CMC TC Measurement and display on the current voltage power work energy frequency display 8 3 Configuration The vertical bus bar is an H shaped aluminium section The power distribution for the individual plug in modules is realised in the rear concealed section The bus bar can be clipped directly into the vertical enclosure frame members of Rittal flexRack i or else retrofitted to other existing racks To upgrade 5 enclosures you require the DK 7856 022 or DK 7856 023 mounting kit and for TE enclosures the DK 7000 684 PSM adaptor Once the bus bar is fitted in the enclosure a voltage supply must be provided in a suitable form This can be done either by way of a three phase connector e g IEC309 16 A or with perma
46. which corresponds to 48 IEC 320 C13 appliance sockets Various country modules UK USA F B earthing pin plug IEC 320 13 19 appliance sockets Shock hazard protected design i e it is not necessary to configure the whole bus bar at once Modular design for simple installation Optimised cable management Complete compatibility with Rittal enclosure systems 5 3 Configuration The vertical bus bar is an H shaped aluminium section The power distribution for the individual plug in modules is realised in the rear concealed section The bus bar can be clipped directly into the vertical enclosure frame members of Rittal flexRack i or else retrofitted to other existing racks To upgrade 5 enclosures you require the DK 7856 022 or DK 7856 023 mounting kit and for TE enclosures the DK 7000 684 PSM adaptor Once the bus bar is fitted in the enclosure a voltage supply must be provided in a suitable form This can be done either by way of a three phase connector e g IEC309 16 A or with permanent wiring to the plug in terminal strips provided on the bus bars Connecting lines are available as Rittal accessories Warning The strain relief for the connection cable must be made the immediate vicinity of the connection plug of the PSM bus bar If the strain relief bracket cannot be attached to the base frame a suitable punched section must be installed for the mounting of the strain relief bracket Note