Home

Operating Instructions

image

Contents

1. Pressing the key several times in the SHIFT mode green LED in shift key alight shows the outflow temperature limitation the correction limitation and the control parameters Xp Tn and Tv on the display in L2 YAUE0005 25 03 02 36 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 6 2 8 6 3 Example L2 Tio 120 C Ti L2 Td 30 Ti L2 Ap Ob Ti L2 Tn 12 0s Ti L2 Tv _ 20s Ti In order to use control parameters other than those found by auto adaptation see Item 8 4 1 the values can be entered in the appropriate display after switching off the O SHIFT SHIFT function pressing LED off Example for Xp 0 0 1 0 if the required value is 1 0 C For values above 200 0 C or 200 0 sec the message L2 OUT OF RANGE appears Recommendations for the control parameters In most cases satisfactory control results are obtained with the following control parameters bath liquid water oil XP 0 5 C 1 C Tn 10s 25s TV 2s 5s Bath temperature limitation The limitation of the bath temperature is an additional warning and switch off function switching off the heating at a selectable value i e the heating output is set to 0 This protects the unit from a continuous cutoff via the safety circuit especially during external control at certain operating cond
2. 8 8 3 8 8 4 8 8 5 Programme test After the input of the programme it is advisable to check that the programme buffer PROGR TEST contains the correct data This is done with the key L in the SHIFT mode Pressing the key repeatedly produces the same sequence as during the input of the programme Changing the programme data Select the data line to be changed as in programme test SHIFT OFF This resets the data of the indicated segment Then the data can be input as usual LOCAL Enter the new data with Si each Programme start interruption and abort It is convenient to bring the operating temperature of the thermostat to the programme start temperature Tstart before starting the programme or to automatize it by the tolerance range function Start the programme sequence with L2 in the SHIFT mode The programme sequence can be followed by the indication of the setpoint TS L1 shows the segment number on the right and L2 shows as a setpoint source a P for programme on the right The keys 1 to 9 are blocked while the programme is running The programme sequence can be stopped with SHIFT L2 and then be re started with PROGR ON OFF SHIFT L2 During the interruption of the programme the display shows a W wait on ESC ON OFF the right in L2 The programme can be aborted with and then SHIFT Ka within 2 sec Afterwards the programme can only be started with segment 1 YAUE0005 25 03 02 44 LAUDA Ultra Kr
3. non 60 4120 Siliconeol_ 5 a4at soc gt 160 12B 121 Lze 221 oer Kryo 85 Ultra 85 30 Silicone oil 1 76 17 at 80 C gt 56 LZB 113 LZB 213 LZB 313 Therm XLT At higher temperatures gt Evaporation losses gt Use bath covers gt Section 10 Accessories Rs Distilled water or fully deionised water must only be used with the addition of 0 1g sodium carbonate Na2CO3 I water otherwise gt danger of corrosion 1 Water content falls after prolonged operation at higher temperatures gt mixture becomes flammable flash point 128 C gt Check the mixture ratio with a densitometer When selecting bath liquids it should be noted that performance must be expected to worsen at the lower limit of the operating temperature range due to increasing viscosity The full operating range should only be utilised if really necessary The operating ranges of the bath liquids and tubing represent general data which may be limited by the operating temperature range of the unit Silicone oil causes pronounced swelling of Silicone rubber gt never use Silicone oil with Silicone tubing Ethyl alcohol Ethyl alcohol is frequently used for operating temperatures below 60 C Warning As the fire point of ethyl alcohol is 12 C the user works outside the standard specifications see Item 4 2 It is essential that the unit is being operated under continuous supervision boiling point 78 C fire p
4. rene i Temperaturkalibrierung Temperature Calibration Calibrage temperature 8 5 Neutralkontakt Sammelst rung Neutral contact Overall fault Contact neutre Perturbation g n ral Analoge Ein Ausg nge Analogue inputs outputs Entr es sorties analogique Netzspannungs ausgang Mains supply output Sortie tension secteur YAUE0005 25 03 02 Parameterebene Parameter menue Menu des param tres 8 4 Ubertemperatur Overtemperature Surtemperature 8 3 4 Displayumschaltung Display selection S lection d affichage 8 3 2 Sollwert Setpoint Valeur de consigne 8 3 6 Kontakteingang St rung Input contact Fault Entree Perturbation TOP zem 12N E WN KA GS ES Ee ES Pt100 T1 JDO ER 535 amp Gi as a a ss Ys fs Eh eh Cf 3 Pt 100 T2 RS 232 C LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 3 3 1 3 2 3 3 3 4 General construction and technical description Operating principle LAUDA Ultra Kryomats with Electronics P are bath circulation thermostats They differ in bath volume bath depth pump type and output as well as in cooling capacity and
5. response time 1 5 sec Overall length approx 120 mm 4 wire circuit Fig 3 Pt 100 70 stainless steel protection tube 4 mm dia Temp range 200 300 C 50 response time 1 5 sec Overall length approx 290 mm 4 wire circuit Fig 3 Pt 100 92 stainless steel protection tube 4 mm dia with attached Silicone cable 2 m long and plug Temp range 100 200 C 50 response time 3 sec Overall length approx 250 mm 4 wire circuit Fig 4 Connecting cable Lemo Lemo for external control on all units with Lemo connector using Pt 100 stainless steel except Pt 100 94 length 2 5 m Connection cable as above length as specified Screw clamp fitting stainless steel with Teflon pressure ring for Pt 100 resistance thermometer 4 mm dia Fig 5 YAUE0005 25 03 02 64 ETP 050 ETP 009 ETP 051 UK 246 UK 247 HX 078 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Fig 1 Fig 2 NS 14 29 DIN 122 42 Pt 100 42 A Pt 100 90 80 Pt 100 70 250 A B Pt 100 44 300 135 Pt 100 66 410 245 32 YAUE0005 25 03 02 65 Notes for trouble shooting for LAUDA Thermostats with P electronics Each repair requiring the opening of the control part by means of tools and each work at the electronic part may only be
6. 03 02 34 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 5 At the PAR level display select L1 Analogue outp Cal L2 Chan 1 1 Chan2 2 Input SHIFT OFF 1 E or 2 for channel 2 Depending on the selected configuration of the analogue outputs see Item 8 11 the socket 52 S analogue signals see Item 8 9 pin 2 carries a voltage signal of approx 95 or 9 5 V or pin 5 the corresponding current signal of approx 19 mA in case of current configuration for channel 1 With a precision multimeter or e g a temperature recorder set the output signal to 9 V 4 or 18 mA or the corresponding temperature by the repeated operation of the key ESC SHIFT ON Pressing leaves the menu and the most recent value setting is ESC entered lf the value was selected too low leave the PAR level with and make a new selection The calibration of channel 2 is similar Connect the measuring instrument to pin 1 voltage signal only Calibration of the temperature measurement circuits With the calibration function the indications of the three temperature measuring points bath temperature Ti external Pt 100 probe T1 and external Pt 100 probe T2 can be set to a known accurate value The resulting correction is processed additively over the entire temperature range Make sure that a sufficiently accurate re
7. 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 1 8 2 8 3 8 3 1 DUPLEX pumps can of course also be used for the connection of closed external systems They then offer the advantage of the liquid flowing through the external system at virtually no pressure important for thin walled glass vessels When operating with closed external systems or when used as bath thermostat the bath should be filled to the highest possible level up to 1 cm below the cover plate The circulating pumps have a control lever for continuous flow adjustment pump output through the external system between 0 and maximum Starting up Filling Fill the unit with bath liquid to suit the operating temperature see Section 5 The filling volume is given under Technical data In general the thermostat has to be filled up to max 1 cm below the cover plate When filling an external system by the pump additional liquid may have to be added during start up Connection to supply Connect the unit only to an earthed socket PE Compare the details on the label with the mains voltage see Item 4 4 2 When working without external system ensure that the pump connections are linked together metal hose link Cat No LZM 045 or LZM 056 Basic functions Supply switch on Switch on the main switch ZE on the left of the control unit except RUL 80 D RUL 90 D the green signal lamp lights up Switch on the power switch The green indicating lamp lights up The
8. D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 2 Technical data to DIN 58966 Type RUL 80 RUL 90 RUK 50 RUK 50 W RUK 90 RUK 90 W RUL 80 D RUL90 D RUK50 D RUK50W D RUK90 D RUK 90 W D Working temperature range C 80 100 90 100 50 100 50 100 90 100 90 100 Ambient temperature range C 5 35 5 35 5 35 5 35 5 35 5 35 Condenser cooling Air Air Air Water Air Water Temperature setting C membrane keypad with 16 keys setpoint input with 0 01 C resolution resolution Bath temperature built in digital thermometer with 0 01 C resolution accuracy and stability of measurement measurement electronics without probe better than 0 05 0 05 K Temperature probe Pt 100 to DIN IEC 751 Class B can be calibrated additively at each measurement point Display back lit LCD matrix display 2 lines with 16 signs each 10 mm character height External temperature 2 separate temperature measurement circuits for external Pt 100 to DIN IEC 751 in measurement 4 wire circuit accuracy and stability of measurement better than 0 05 0 05 K can be calibrated additively at each measurement point One probe produces the measurement for external control Temperature control modified PID PI controller with automatic structure selection Control parameters through auto
9. E E E E TE 50 8 12 1 Be e 51 8 12 2 Adjustable overtemperature limiter 0 2 eee e cece ee eect ee eeeeaeeeeeeeaeeeseeaaeeeseeaaeeeseeaaeeeeneaeeeeeaas 51 8 12 3 Connection potential free contact Combined fault 12 N Alarm out 53 8 13 Serial interface RS 232 C sacs sc csccscecceetececactcvendrencetececedescereedece cast p aeos aana dokaa eeraa cadat aata ED aSa aatia eE 53 8 13 1 Data of the RS 232 C interface istae cecccessceceeeceeeeeeeaaeeeeneeceeeeeeeaeeeeaaesgeeeeceaeeseaaeseeaaesseneeseresaas 53 YAUE0005 25 03 02 4 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 13 2 General Principles narinaa ana a i a aaea aeaa e 8 13 3 Output commands sises isora aada Acie ed aada aa adian 8 13 4 Requesting data from the thermostat ec ce ceeeceeeeenneeeeeeeaeeeeeeaeeeeeeaeeesenaes 8 13 5 Error messages on the COMPUTED eee eeeeeeceeeenteeeeeeneeeeeeaeeeseesaeeeeeeaeeeeeenaes 8 14 Tmipg elocktfupetlott eege secede te aa iania eaaa 8 14 1 Setting and indication of date and gme rennes mt bg rulle Keilen e BEE 8 14 3 Activating the timing FUNCTION 00 eee eee eee enneeeeeeaeeeeeeaaeeeeeeaaeeeeeeaaeeseeaeeeenenaes H MAINTENANCE g tt gur cevaceacdetecesscevacececaviceascataceasteviceaccavacetscaviceascatacausteds 9 1 Safety notes in Case Of repairs ecccceeeeeee
10. Fill in bath liquid see operating instructions 5 2 3 Level in the vessel is close to Either reduce the amount of overflow thermal liquid or install an other heater switches off vessel Attention HOT Admissible working temperature Bath liquid is accepted no other range of bath liquid exceeds steps necessary unit limitations operating temperature range of valid the unit Motor chamber temperature gt 55 C Switch setpoint selection to l Internal Check setpoint selection see right side of display L2 P Programme A Analogue R RS 232 RAM defective Unit has to be switched on once again set date and time once again see operating instructions if necessary replace RAM page 2 of 4 Notes for trouble shooting for LAUDA Thermostats with P electronics Display Double Pt 100 for bath Interruption short circuit or Replace double Pt 100 for bath Internal Pt 100 temperature or safety temperature deviation of bath temperature defective temperature temperature probes too important For USH 400 6 please check both single Pt 100 Display Tried to switch over to external Continue to work with internal Ext Pt 100 not control without connecting an control or connect external Pt 100 connected external Pt 100 for T1 or T2 look at display for control variables I 1 or 2 check display for T1 or T2 Tried to calibrate Pt 100 being not connected Display Important deviation of Pt Value input differing from
11. LUK 210 LUK 211 LUK 212 Units with different voltages may have a different loading see unit label see item 4 3 Technical changes reserved YAUE0005 25 03 02 11 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW RUK 50 P RUK 50 W P RUL 80 RUL 90 RUK 50 RUK 50 gg g D RUK 40S RUK 40 SW RUK 90S RUK 90 SW RUK 90 P RUK 90 W P RUK 90 D RUK 90 W D ULTRA KRYOMAT YAUE0005 25 03 02 12 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Programmgeber Programmer Programmateur 8 8 Extern Regelung Extern control R gulation externe 8 7 Regelparameter Control parameter Parametr s de r glage 8 6 Analoge Ein Ausgange Analogue inputs outputs Entr es sorties analogique 8 10 8 11 Schaltuhr Timer Horloge 8 14 Entsperren Reset R armement 8 3 4 8 12 Ti 300 00 C H LAUDA t Ts 300 00N C Ti I Ge PROGR lide H eo Tid PCs
12. RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Type RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P Working temperature range C 40 100 40 100 80 100 80 100 Ambient temperature range C 5 35 5 35 5 35 5 35 Condenser cooling Air Water Air Water E Co membrane keypad with 16 keys setpoint input with 0 01 C resolution Bath temperature measurement built in digital thermometer with 0 01 C resolution accuracy and stability of measurement electronics without probe better than 0 05 0 05 K Temperature probe Pt 100 to DIN IEC 751 Class B can be calibrated additively at each measurement point Display back lit LCD matrix display 2 lines with 16 signs each 10 mm character height External temperature 2 separate temperature measurement circuits for external Pt 100 to DIN IEC measurement 751 in 4 wire circuit accuracy and stability of measurement better than 0 05 0 05 K can be calibrated additively at each measurement point One probe produces the measurement for external control Temperature control modified PID PI controller with automatic structure selection Control parameters through auto adaptation or manual input With external control a cascade controller operates on the measurement of one of the external circuits T1 or T2 Temperature variation at 10 C C 0 02 0 05 0 02 0 05
13. SHIFT OFF lass u Input TS 20 C press ZO The display shows Li Ti 60 00 C C L2 TO 65 00 C Ti YAUE0005 25 03 02 51 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW lass u1 If TU is shown in L2 press CO again Now input 0 5 8 0 0 a The switch off point of the overtemperature limiter is now 2 K below the bath temperature Ti The display shows the message L1 TEMPERATURE L2 TOO HIGH with a beep Heating pump and refrigeration unit are switched off on all poles To restart the unit press the reset key L2 The display shows the standard display lass u Now press H and set To to a value above the bath temperature e g 70 C utr LOCAL Input 0 7 0 0 O Fa Then press the key LO once more The unit returns to normal operation In order to reduce the switching frequency of the refrigeration compressor a number of time delays have been incorporated Therefore the refrigeration unit restarts with a considerable delay Note The overtemperature switch off point has to be set at least 25K below the fire point of the bath liquid used according to EN 61010 Caution In case of any malfunction in Items 8 12 1 and 8 12 2 the unit has to be taken out of use immediately and checked by an engineer otherwise its safety is no longer ensured YAUE0005 25 03 0
14. adaptation or manual input With external control a cascade controller operates on the measurement of one of the two external circuits T1 or T2 Temperature variation C 0 02 0 05 0 02 0 05 0 02 0 05 0 02 0 05 0 02 0 05 0 02 0 05 at 10 C Heating rating max kW 1 2 1 2 2 0 2 0 2 0 2 0 Cooling capacity 20 C KW 1 0 1 2 2 5 3 0 1 7 2 0 eff with Ethanol at 0 C 0 8 1 15 2 2 2 5 1 4 1 6 20 C ambient 10 C 0 7 1 1 2 0 2 2 1 3 1 5 temperature 20 C 0 6 1 0 1 4 1 4 1 2 1 4 40 C 0 5 0 4 0 4 1 1 1 2 50 C 0 45 0 8 0 15 0 15 1 0 1 1 60 C 0 4 0 6 0 8 0 9 80 C 0 1 0 25 0 25 0 25 85 C SE 0 13 Kc Kee See See 90 C 0 06 0 06 Safety system Overtemperature protection with selectable switch off point low levelprotection to EN 61010 FL DIN 12879 Class 2 Additionally 10 stage level indication on the display Simplex pump Pump output against zero head l min 22 22 22 22 22 22 max pump pressure bar 0 5 0 5 0 5 0 5 0 5 0 5 Duplex pump D Pump output pressure suction l min 20 15 20 15 20 15 20 15 20 15 20 15 max pump pressure bar 0 5 0 33 0 5 0 33 0 5 0 33 0 5 0 33 0 5 0 33 0 5 0 33 pressure suction YAUE0005 21 06 02 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK
15. as anti freeze protection and of course as setpoint limitation Setpoint input loss 12 Press the key SHIFT LED off L2 shows L2 Ts _ 20 00 C Ti The setpoint TS can be input within the unit temperature range but not higher than the LOCAL current overtemperature switch off point When the input is too high pressing does not enter the value but instead produces the message L2 TS gt gt TO Input Ts with the number keys and the negative sign SHIFT OFF e g for 25 03 C LOCAL input 2 5 0 3 Ba Or for 1 93 C input 0 0 1 9 3 After the last digit the cursor returns to the first digit again so that corrections can easily be made Parameter level PAR Pressing the key L 5 several times in the SHIFT mode green LED in SHIFT key alight leads successively to the input functions described below YAUE0005 25 03 02 31 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 4 1 Auto adaptation Here it is possible to start the controller auto adaptation by input of 1 SHIFT OFF and pressing the ENTER key There should be the largest possible difference between the bath temperature and the setpoint to be entered subsequently i e the time to reach the setpoint has to be longer than 5 min preferably 10 min In addition auto adaptation is obviously possible only during a
16. display shows consecutively Fa LAUDA P Thermostat Type RUK 50 depending on type V 2 XX Date and software version L1 Ti 20 00 C H K other values depending on L2 Ts 10 00 C N Ti l bath temperature and setpoint Check the direction of the pump rotation RUK P and RUK S units only YAUE0005 25 03 02 27 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 3 2 The pump motor has to rotate anticlockwise When looking at the coupling at the motor shaft end through the cut out for the pump control lever or pump connection the side facing the observer has to rotate anticlockwise If this is not the case the rotation of the 3 phase current connection is incorrect The pump does not achieve its full capability Remedy by interchanging two phases in the supply by a qualified electrician Direction of rotation of condenser fan on air cooled units without W in the type designation except RUL 80 D RUL 90 D While the refrigerating system is operating the fan draws in air at the front and discharges it at the back If the pump rotates in the correct direction the fan usually also rotates in the correct direction Standard display Top line L1 Ti bath temperature i internal D or l or t indication of the level in the thermostatic bath crossbeam shows the filling height in th
17. done by a trained technician Malfunction Fait Reason Remedy Green signal lamp of Control fuse has actuated Replace fuse on PCB mains switch not alight MP Mains 5 x 20 F4A Overload on PCB Replace PCB MP Mains Display Bath level too low Evaporation external Fill in bath liquid press reset Level too low consuming device not refilled button twice Leakage in hose connections Check hoses and their connection if necessary replace them fill in bath liquid press reset button twice Level detector Check level detector plugs and hall sensors if necessary replace them check their function carefully For USH 400 6 fill in bath liquid up to the level mark Display Temperature probe Temperature difference between Replace bath temperature probe Temperature too high two probes gt 15 C double Pt 100 For USH 400 6 please check both single Pt 100 Temperature of bath liquid Overtemperature switch off point Press reset button adjust above over temperature To set too low overtemp switch off point To at switch off point To an higher value press reset button Triac or triggering Replace triac or PCB MP Mains Display Contact input 14 N Fault Pins 1 2 not connected Reason for malfunction caused by External fault is used external system No signal transmitter connected Switch off function Contact input to socket 14 N though selection Fault at PAR level see
18. from the type of product being thermostated e g a shift above or below certain temperature levels or a fracture of the container and a reaction with the thermostatic liquid etc It is impossible to cover all possible causes and they remain largely within the decision and responsibility of the user Values for temperature variation and indication accuracy apply under normal conditions according to DIN 58966 In special cases high frequency electromagnetic fields may lead to less favourable values There is no loss of safety Units are in accordance with EMC directive EN 61326 1 class A Units are only suitable for use in industrial areas as disturbing voltage fluctuations might occur Notice only valid for EU countries YAUE0005 06 06 02 20 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 4 4 4 4 1 4 4 2 4 4 3 Warning The units must only be used according to the descriptions indicated in these Operating Instructions This includes operation by properly qualified and instructed personnel The units are not designed for operation under medical conditions according to EN 60601 1 or IEC 601 1 Warning notes Temperatures The outflow and return pipes of the pumps reach the operating temperature i e even temperatures above 70 C Touching them is dangerous because o
19. heating or cooling phase which is actively influenced by the energy sources available Example 1 intended operating temperature approx 70 C 1 Set the setpoint to 70 C 2 Within 1 minute start auto adaptation at the PAR level e g at a bath temperature corresponding to the ambient temperature On reaching the setpoint the auto adaptation switches off automatically and its result can be indicated at the control parameter level see Item 8 6 Example 2 it is required to operate at approx 20 C with controlled cooling 1 Set the setpoint to 20 C 2 Start auto adaptation at the PAR level 8 4 2 Output limitation Normally the maximum heating or cooling output is available For special applications it is possible to set a limit for both heating and cooling output At the PAR level display select L1 Output L2 in per cent_ 100 4 Using the display can be switched from e g 100 i e heating output limitation to cooling output limitation with a negative sign By the input of e g 0 0 5 8 Ba SHIFT OFF a heating output limitation of 58 can be set With e g 0 9 3 a a cooling output limitation of 93 is entered The action can be recognised by the symbols i and H flashing even at large control deviations YAUE0005 25 03 02 32 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RU
20. of the set overtemperature and low temperature switch off point Read out of the fault signal Transfer of ramp segments and their processing Status signal Read out of the control parameter and transfer O ON EE ae S External controller status and start YAUE0005 25 03 02 53 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 13 2 8 13 3 General principles The interface operates with two stop bits no parity bit and with 8 data bits The transfer rate can be set to 4800 baud or 9600 baud see Item 8 4 5 Values from the computer can be transferred directly to the thermostat i e transmitted e g OUT SEG and START commands or data can be transmitted from the thermostat to the computer on request with an IN command An OUT SEG or START command if transmitted correctly is always acknowledged by the thermostat with the message OK followed by LF and CR This message like any other response has to be requested by the computer Any output command OUT SEG START STOP switches the thermostat to remote operation This can be recognized by an R setpoint source RS 232 on the right in L2 Poise 1 loss 12 Then all the keys are locked except for the functions SHIFT ZOU and SHIFT Ea If no output command follows from the connected computer the keyboard can be LOCAL CO ac
21. operating at PAR level is activated instructions Display Wrong inputs Setpoint adjusted above Adjust overtemperature switch off Ts gt To overtemperature switch off point point To at an higher To temperature pay attention to bath liquid flash point etc Overtemperature switch off point First adjust setpoint Ts at a lower adjusted below setpoint Ts value then set requested overtemperature switch off point Display Wrong input Setpoint adjusted below low Adjust low temperature switch off Ts lt Tu temperature switch off point point Tu at a lower value Tu Low temperature switch off point First adjust setpoint at an higher adjusted above setpoint temperature then set requested Ts low temperature switch off point Tu G Therm Service Fehler Fehlpe1 doc 04 12 98 page 1 of 4 Notes for trouble shooting for LAUDA Thermostats with P electronics Setpoint Ts is not adjustable but will disappear Sound signal appears when a button is pressed Operating error Display Tu Cursor flashes acoustic signal switches compressor off after 1 min Display Out of range Wrong input Wrong input Tu or To is not adjustable Out of range Display TA only for USH 400 6 Display 4 only for USH 400 6 RUL and RUK Display T only for USH 400 6 RUL and RUK Display Upper limitation of oil gt limitation of unit cancelled beginning with
22. piece of hose The pump control lever should be set to open this improves the circulation inside the bath As a permanent arrangement the hose link Cat No LZM 045 or LZM 056 is the best and safest solution Connection of external systems Connection to closed external systems Additional liquid must be poured in after the thermostat has been switched on until the liquid in the bath remains at the correct level approx 2 cm below the plastic cover plate For suitable tubing materials please see Section 5 With external systems at a higher level it may happen even in closed systems that the external volume drains down and the thermostat bath overflows if the pump is stopped and air enters the thermostated system Connection to open external systems baths Hang the hoses into the external bath protect them against slipping out preferably at two opposite sides The suction hose should have a notch at its end so that it cannot attach itself by suction to the wall or bottom Before switching on the unit the external bath has to be filled with liquid up to the required level If the Kryomat and external bath are not at the same level the connecting hoses have to be vented by pulling them out after the Kryomat has been switched off in order to prevent overflowing Always ensure the maximum possible flow area in the external system nipples tubing system This results in a larger flow and therefore improved thermostatic control Alway
23. software version 1 06 Setpoint cannot be selected by means of keyboard Display Clock does not run External fault clock stop G Therm Service Fehler Fehlpe1 doc 04 12 98 Setpoint is determined by the Switch off analogue input analogue input see right side of display L2 A Another function blocks the keybord e g programme runs RS 232 active Parameter etc Leave the function or press ESC RS 232 R appears on the right side of display L2 Stop access and press the button Local Set low temperature switch off point Tu at a lower value Actual value is lt Tu resp setpoint adjusted too close to low temperature switch off point Tu bath temperature Ti falls below Tu Tried to enter values being out of admissible ranges Ts To Tu being out of operating temp Choose the right values taking into consideration their limitations check bath liquid or configuration after having switched on the unit Programme input out of Enter admissible values operating temperature range of the unit Value for Xp Tn Tv above Enter admissible values 199 9 Input values are outside of temperature limits of the type of unit or initialization does not fit to the type of unit Reinitialize type of unit see operating instructions Maintenance may also return Default values Surrounding temperature of the part of the thermostat may be too high see operating instructions 5 2 8 Level too low
24. value Td is exceeded the heating or cooling output is set to 0 When this function is activated the time for heating up or cooling down may be extended To enter the difference value Td proceed as described in Item 8 6 1 and switch the display to input and indication Example L2 Td _30 C Change the value by entering the figures with a resolution of 1 LOCAL Enter the new value by pressing ES YAUE0005 25 03 02 38 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 7 8 7 1 It is possible to select values within the temperature range from 5 C to 150 C If this range has not been respected the display shows L2 Td OUT OF RANGE and there is an acoustic signal This function can be switched off by entering L2 Td 000 C External control External measurement inputs and external controller The units have two Pt 100 temperature measurement inputs whose measurements can be indicated T1 T2 You can connect external Pt 100 T1 T2 at the rear connectors 10 S in 4 wire circuit Use shielded connecting cables Connect the shielding to the plug case Cover the unused connectors with protective caps Pin connections sockets 10 S Pt 100 pin 1 current path 2 U voltage path D 3 UU voltage path Pt 100 4 current path DIN IEC 751 Plug 4 pin Lemosa for Pt 100 conn
25. 0 02 0 05 0 02 0 05 Heater rating max kW 2 0 2 0 2 0 2 0 Cooling capacity 20 C KW 2 3 2 8 1 5 1 8 eff 0 C 2 0 2 3 1 2 1 4 with ethanol at 20 C 10 C 1 8 2 0 1 1 1 3 ambient temperature 20C 1 2 1 2 1 0 1 2 40 C 0 2 0 2 0 9 1 0 50 C 0 8 0 9 60 C 0 6 0 7 80 C 0 1 0 1 Safety system Overtemperature protection with selectable switch off point low level protection to EN 61010 FL DIN 12879 Class 2 Simplex pump Pump output against zero head l min 50 50 50 50 max pump pressure bar 0 8 0 8 0 8 0 8 Pump connections M 19x1 5 M 19x1 5 M 19x1 5 M 19x1 5 Nipples 15 Nipples 15 Nipples 15 Nipples 15 Filling volume max L 19 27 19 27 19 27 19 27 Bath opening W x D mm 282x257 282x257 282x257 282x257 Bath depth mm 220 220 220 220 Usable liquid depth mm 180 180 180 180 Height to top of bath mm 900 900 900 900 Floor area WxD mm 550x735 550x735 1000x735 1000x735 H 1250 1250 1250 1250 Weight Kg 175 175 295 300 Supply V Hz 230 400 3 N PE 50 Protection class 1 to VDE 106 Loading kW 4 1 3 9 5 5 5 3 Units conform to EU Guideline 89 336 EWG EMC and 73 23 EWG low voltage and carry the CE mark 50 Hz units Cat No LUK 231 LUK 227 LUK 229 LUK 230 Units with different voltages may have a different loading see unit label see item 4 3 Technical changes reserved YAUE0
26. 005 25 03 02 10 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Type RUK 40S RUK 40 SW RUK 90S RUK 90 SW Working temperature range C 40 100 40 100 90 100 90 100 Ambient temperature range C 5 35 5 35 5 35 5 35 Condenser cooling Air Water Air Water Temperature setting resolution C membrane keypad with 16 keys setpoint input with 0 01 C resolution Bath temperature measurement built in digital thermometer with 0 01 C resolution accuracy and stability of measurement electronics without probe better than 0 05 0 05 K Temperature probe Pt 100 to DIN IEC 751 Class B can be calibrated additively at each measurement point Display back lit LCD matrix display 2 lines with 16 signs each 10 mm character height External temperature 2 separate temperature measurement circuits for external Pt 100 to DIN IEC measurement 751 in 4 wire circuit accuracy and stability of measurement better than 0 05 0 05 K can be calibrated additively at each measurement point One probe produces the measurement for external control Temperature control modified PID PI controller with automatic structure selection Control parameters through auto adaptation or manual input With exte
27. 1 IN_ NR 70 INPUT 1 A 80 LOCATE 12 5 PRINT SPC 50 90 LOCATE 12 5 PRINT Response of the thermostat A 100 TI TIMER 1 110 IF TI gt TIMER THEN 110 120 GOTO 30 130 END The isolation of the status data may be as follows LEFT A 1 overtemperature fault MID A 2 1 low level fault MID A 3 1 programme segment running MID A 4 1 control by Ti T1 or T2 MID A 5 1 analogue input on off MID A 6 1 external Pt 100 T1 connected RIGHT A 1 external Pt 100 T2 connected 8 13 5 Error messages on the computer The following error messages can be reported from the thermostat to the computer during operation ERR 2 invalid inputs e g overflow of the input buffer ERR 3 invalid command ERR 5 invalid command when switching the control variable for the controller e g external controller OUT_RT2 Other command than OUT_RTI OUT RI OUT_RT2 ERR 6 temperature value cannot be set ERR 7 syntax error in channel number ERR 8 channel does not exist YAUE0005 25 03 02 58 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 14 Timing clock function The unit is equipped with a clock indicating day month year weekday hours and minutes and provides these for the timing function The clock is backed for approx 10 years by a bu
28. 2 52 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 12 3 8 13 8 13 1 Connection potential free contact Combined fault 12 N Alarm out 3 pin flange connector conforms to NAMUR recommendation NE 28 1 n o make 2 common 3 n c break 1 2 are linked when unit operation is OK Use shielded connecting cables Connect the shielding to the plug case Cover the unused connectors with protective caps Coupling socket 3 pin Cat No EQD 047 Serial interface RS 232 C 9 pin sub D socket 53 S Data of the RS 232 C interface Cables used computer end Computer Thermostat 25 pin 9 pin 9 pin 3 RxD 2 2 T x D transmitted data 2 TxD 3 R x D received data 7 SG 5 5 signal ground 6 DSR 6 6 DTR data terminal ready 4 RTS 7 7 CTS clear to send 5 CTS 8 8 RTS request to send Use shielded connecting cables Connect the shielding to the plug case Cover the unused connectors with protective caps Using this interface it is possible to transfer the following data from or to a computer with a suitable interface 1 Transfer of the setpoint from the computer to the thermostat 2 Read out of the bath temperature Ti the external temperature T1 the external temperature T2 and the setpoint on the unit Transfer of the low temperature and overtemperature switch off point Read out
29. 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Type RUL 80 RUL 90 RUK 50 RUK 50 W RUK 90 RUK 90 W RUL 80 D RUL90 D RUK50 D RUK50W D RUK90 D RUK 90 W D Pump connections M 16x1 M 16x1 M 16x1 M 16x1 M 16x1 M 16x1 Nipples 13 Nipples 13 Nipples 13 Nipples 13 Nipples 13 Nipples 13 Filling volume max L 9 14 13 18 19 27 19 27 19 27 19 27 Bath opening W x D mm 250x175 250x175 282x257 282x257 282x257 282x257 Bath depth mm 180 220 220 220 220 220 Usable liquid depth mm 140 180 180 180 180 180 Height to top of bath mm 900 900 900 900 900 900 Floor area Wx D mm 550x735 550x735 550x735 1000x735 1000x735 1000x735 H 1250 1250 1250 1250 1250 1250 Weight Kg 185 195 175 175 295 300 Supply V Hz 230 50 230 50 230 400 3 N PE 50 Protection class 1 to VDE 106 Loading kW 3 2 3 5 3 9 3 7 5 3 5 1 Units conform to EU Guideline 89 336 EWG EMC and 73 23 EWG low voltage and carry the CE mark 50 Hz units Cat Nr Simplex Pump LUK 117 LUK 137 LUK 201 LUK 203 LUK 205 LUK 207 Duplex Pump LUK 118 LUK 138 LUK 202 LUK 204 LUK 206 LUK 208 Units with different voltages may have a different loading see unit label see item 4 3 Technical changes reserved YAUE0005 21 06 02 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P
30. A Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 4 5 8 4 6 8 4 7 Connections contact input Fault 14 N alarm in 3 pin flange socket to NAMUR recommendation NE 28 1 n o close 2 common 3 not used Connector plug 3 pin Cat No EQS 048 Use shielded connecting cables Connect the shielding to the plug case Cover the unused connectors with protective caps Baud rate RS 232 On the display at the PAR level L1 Ser Int RS 232 L2 Baud Rate 9600 LC H is possible to switch with between 9600 and 4800 With ENTER SHIFT OFF the indicated baud rate is entered Menu language On the display at the PAR level L1 Lang Germ 0 L2 Engl 1 French 2 the menu language can be selected Enter the corresponding code numbers 0 1 or 2 with Es on SHIFT OFF Calibrating the analogue output channels The 90 values of the analogue voltage outputs channel 1 and 2 or the analogue current output of channel 1 can be calibrated separately for channel 1 voltage or current and channel 2 voltage The factory calibration on channels 1 and 2 for 0 10 V 100 400 C is performed at 9 V 350 C In special cases e g to correct scaling deviations of instruments connected to the output or if channel 1 is to be a current output the output can be calibrated by the user YAUE0005 25
31. AUDA Thermostats with P electronics Malfunction Fault Reason Remedy Unit does not work at Wrong control parameters Enter new values or start adjusted setpoint adjusted autoadaption Temperature control by Thermal contact of bath liquid Improve circulation through means of external and external measuring point external consuming device or controller not stable not sufficient thermal contact to ext Pt 100 Unit does not cool down Controller output limitation at Adjust higher value at PAR level PAR level too small e g 100 Compressor defective Replace refrigeration unit by refrigeration engineer Leakage in refrigeration Clear leakage fill in refrigerant system by refrigeration engineer Compressor does not run Compressor without tension Eliminate line interruption Triggering defective Replace PCB MP Mains Unit does not cool down Compressor does not run Pressure switch has actuated Unscrew grid clean condenser blow through compressed air improve ventilation Solenoid valves do not Triggering defective Replace PCB MP Mains work correctly Compressor switches ON Condensation pressure too Fan defective Replace fan motor and OFF in regular Fan speed only RK Check speed or speed controller periods temperature constancy very bad Condenser dirty Unscrew grid from the back side blow compressed air or nitrogen through condenser Ventilation disturbed Enlarge distance to nea
32. CTION OF EXTERNAL GVGTEMS ee ERR EEEEEEEn 26 7 1 Connection to closed external SYSteMS cccssccesseeeeeeeeeeseeseneeeeneeeeeeaeeseseeeeneeaeseaeseseaeeenseeeseneseaees 26 YAUE0005 25 03 02 3 E LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 7 2 Connection to open external systems baths sccsseceseeeeeeeeseseeeeneeneeseeseseeeeeeeeeeseeeseneneeeneeeeneas 26 753 Circulating PUMPS inciscesectcacscvsedcescetee ced ty cove seetceceeden veteenceee au Seeuuiebnedetuectaeti soci svautivensdusveleevbeed sduevetaseteeud 26 g ag al el 27 e WE ll VE 27 B52 CONNECTION 1O SUP IY ona eege eege ege ar aa aaea ara rea aaa aa raen naas 27 8 3 Basic TUNCUONS eege EE SEENEN NEERA EL ASAE 27 CDN We elen Ee EE 27 8 9 2 Standard Ree EE 28 8 3 3 Basic action ON inputs and OUTPUTS 0 eee ae RA ET I NEARNE La AA Raai 29 8 3 4 Overtemperature switch off point 30 8 3 5 Low temperature Switch off point 31 tee d le EE EN 8 4 Parameter level RAR ege eege 31 E Ee Ee ET e EE 32 Cette TTC EE 32 8 4 3 Display resolution Li reirnos erai era iee E a EE EE ENE eraa 33 8 4 4 Contact input Fault AN 33 8 4 5 Baud rate RS 232 wie Weenie el dee inva dete Wil i ded 34 8 4 6 Menu Eine E isin tee eet tae eee Meee a ete eee ge ene 34 8 4 7 Calibrating the analogue output channel 34 8 5
33. Calibration of the temperature measurement Circuits ceeceseceseeeeeeeeee cess seeesnenseeneeseensneeennananes 35 8 6 Control parameters isossa cece ceccece et teestececencerewetneactevenceuetatines sted consti EENEG 36 8 6 1 Indication and input of the Control pDarameterg eee eeeeeeeeeeeeeeeeeeaeeeeeeeaeeeeeaaeeeeeeaaeeeeneaeeeeneas 36 8 6 2 Recommendations for the control parameters cceeeeeseceeeenneeeceeaeeceeaeeeeeeaaeeeseeaeeeseenaeeeeeeaaes 37 8 6 3 Bath temperature limitation sessie iaieiiea ini EAEE atia rien AREA 37 8 6 4 Correction Blue EE 38 8 7 External comtol esines asa aana aaa an i aiaa iiaa a ia 39 8 7 1 External measurement inputs and external controller A 39 8 7 2 Start of external Control 40 tr NORE a ae eke tetas chee E E EA 40 8 8 Operation with programmer ccccscccseeeeeeeeseeeeesneeeneneeeeeneesnaaeenseeeeeesesaeseseeaeseeesessaesenenenseeneeeeeennes 41 88A e tele TE lu Cl e EE 41 8 8 2 Example of a programme seipie aa e ae i NEERA ERE OR 43 8 83 Programme testanneet aai 44 8 8 4 Changing the programme data 44 8 8 5 Programme start interruption and abort AA 44 8 9 Connection for analogue signals socket 52 S sscesseseseeeseeeeeeeeeseeneeeenseensesneesnesseasenaeseensnensneesnes 45 8 10 Analogue DD iesse 46 8 11 Analogue Outputs sarirani eain a ea iaa e 48 8 11 1 Temperature signal channel Thoreida taisne aAa AEE RERA E E 49 8 11 2 Temperature signal channel 2 50 e AA aao a E E
34. Cat No HKO 025 1 m Silicone tubing 11 mm int diameter Cat No LZS 007 2 pces of 1 2 water hose 4 m long each with quick connect coupling only with water cooled units Operating Instructions Standard accessories RUK 50 W P RUK 90 W P RUK 40 S W RUK 90 S W 1 Bath cover Cat No HDQ 050 2 Nipples 15 mm dia fitted Cat No HKA 005 1 m Silicone tubing 14 mm int diameter Cat No LZS 011 2 pces of 1 2 water hose 4 m long each with quick connect coupling only with water cooled units Operating Instructions 6 2 Setting up operation as bath thermostat Set up the unit conveniently so that the control panel is towards the front and ensure that the air circulation for the refrigeration system through the grille in the lower part of the unit is not restricted At air cooled units a minimum spacing of 50 cm between grille and wall is recommended see Item 3 7 1 At water cooled units W in type designation make the hose connections to the water tap and the drain see Item 3 7 2 Protect tubing with hose clips against slipping off Close the drain cock at the back of the bath YAUE0005 25 03 02 25 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 7 1 7 2 7 3 If no external system is connected it is advisable to link together the pump connections with a
35. EI EES D WS EE e aset E EE ES UNE EES AN kas TT TT EC EES ES ERR EE Sees ES DEER E Me E LIT NNN Loes 0 5 10 15 20 2 30 35 40 45 50 55 60 65 70 Bath liquid ethanol LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 3 8 Mains supply output 34 H The 230 V supply voltage is available at the socket 34 H at the back in normal operation and with the unit switched on The maximum current which can be drawn there is 2 A In case of a fault this supply is switched off This output can be used e g to connect a non return fitting Cat No UD 125 Suitable mating plug Cat No EQS 045 3 9 Remote operation FBK option As an option the units can be converted to remote control then the entire electronics with control panel is removed from the unit and used for remote operation An adapter for the cable connections is required on the basic unit and the control panel is placed in an extra housing The conversion is to be carried out by a qualified electrician only All necessary components except the connection cables are supplied as part of the kit Please specify the length of the connecting cables See accessories in the Appendix 4 Safety devices and warning notes 4 1 Safety functions The built in over temperature limiter can be set over the complete operating temperature ra
36. I TIMER 1 IF Tl gt TIMER THEN 110 GOTO 30 END The following values can be transmitted similarly to the thermostat OUT_LXXX XX OUT_HXXX XX OUT_XPXXX XX OUT_TNXXX XX OUT_TVXXX XX OUT_RT1 OUT_RT2 OUT RI SEG_XXX XX_XX XX SEG_ XX _XXX_XX XX YAUE0005 25 03 02 switching point for low temperature usually set to the lower range limit of the thermostat overtemperature switch off point For safety reasons it is essential that after the transfer this value is read back with the command IN_9 and checked setting of the control parameter Xp for the controller setting of the control parameter Tn setting of the control parameter Tv switches the control variable to the source external Pt 100 T1 external control switches the control variable to the source external Pt 100 T2 external control switches the control variable to the source Ti probe in the bath control according to the bath temperature using this programme segment command a segment can be written into the programmer buffer It indicates the target temperature and the segment time hours 2 digits max and minutes 59 max The segment start is formed by the current setpoint i e before the transfer of a programme segment it is useful to transfer a setpoint as a segment start suitable for the subsequent segment using OUT_XXX XX single segment with segment number used when whole temperature programmes are to be loaded from the comput
37. K 90 SW 8 4 3 8 4 4 At thermostats with refrigeration system the activation of refrigeration can be suppressed by entering 000 Only values between 10 and 100 or 10 and 100 can be entered otherwise the display shows the message L1 Output L2 OUT OF RANGE Display resolution L1 At the PAR level display select L1 Display 0 001 1 L resolution 0 01 0 Enter 1 SHIFT OFF Ba Switches all displays in L1 to 0 001 K resolution The temperatures are then displayed with approx 2 digit resolution Input 0 switches all displays in L1 to 0 01 K resolution Normally a resolution of 0 01 K is used Contact input Fault 14 N When using the contact input FAULT 14 N pins 1 and 2 of the socket have to be connected together when there is no fault If this input is not used a blanking plug with a link has to be plugged in The function of the contact input fault can be switched off at the PAR level when the display shows L1 Alarm Inp con 14 N L2 on 1 off 0 by the input of 0 SHIFT OFF A shorting plus is not required If the alarm input has been activated in error by the input of 1 the unit can be restarted by the following inputs Jr Press the key LO Select Alarm Inp con 14 N at the PAR level Input 0 with Ba Press OU again If a fault message has been produced by opening the external signal circuit reset by utr pressing the key LO twice after rectifying the fault YAUE0005 25 03 02 33 LAUD
38. K 90 SW The pump motor is fitted with a temperature monitor which switches off if the motor winding overheats The heater is also switched off simultaneously After the motor winding has cooled down the pump starts up automatically 4 2 Why can a thermostat be dangerous 1 Thermostats are equipped with heaters supplying the necessary heat to the thermostating liquid If the temperature control fails or if the liquid level is too low the heater may reach temperatures which can lead to a fire in the laboratory especially in combination with flammable liquids 2 When using the thermostat as a circulation thermostat a hose may break causing hot liquid to spill and endangering people and goods The safety requirements on thermostats therefore depend on whether o non flammable or flammable liquids are used o operation is with or without supervision The thermostats described in these Operating Instructions are protected against overtemperature and low liquid level when operated according to the regulations FL The units can be operated with non flammable bath liquids and with flammable bath liquids up to 25 C below their fire point EN 61010 on condition that there is a correct adjustment and regular testing see Item 8 12 of overtemperature and low level protection 4 3 Important notes The user is only protected against those hazards which are caused by exceeding the temperature and by low liquid level Further hazards may arise
39. LAUDA Operating Instructions LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW LAUDA DR R WOBSER GMBH amp CO KG P O Box 1251 97912 Lauda K nigshofen from series A 01 Tel 49 0 9343 503 0 software version 2 14 Fax 49 0 9343 503 222 01 02 YAUE0005 E mail info lauda de Internet http www lauda de LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 1 BRIEF OPERATING INSTRUCTIONS Renee Sege see EEN EEN SES 6 1 1 Fitting the tubing to the pump CONNECTIONS 0 ceeceeeeeeee ee eeeeeee ee eeeeeee ee eeeneeseeeeeneeseeeeeneeseeeseneneeeeees 6 k2 MIMPORtan ts ees sess eta sce He cc ieee ace och isco ice head ele aegis hat eel cas 7 1 3 Operating SAlOty acccci ieiunii aenneren roenan a raean eaan desea raana eaaa aSa etaa a cece eutens EEn Enae 7 TFA El e BE 7 2 TECHNICAL DATA TO DIN EE eeneg aerer eech 8 3 GENERAL CONSTRUCTION AND TECHNICAL DESCRIPTION tccccceceeeeeeeeseeeeneees 14 3 1 Operating principle euEeeeegeesegk SEENEN EENEG KEEN set EES 14 3 2 Type SCIOCUON EE 14 BiB COMSUUCTION NEE 14 3 4 Thermostatic bata Zeg 14 3 5 Circulating Dunn py EE 15 3 6 Temperature Control and electronics cc
40. LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 11 2 8 12 Configurable means that the temperature range required to correspond to the voltage range 0 10 V current range 0 20 mA or 4 20 mA can be determined by setting the range start Tmin and the range end Tmax The display shows L1 CONFIGURABLE 1 L2 Tmin _ Example range 20 220 C Input 0 2 0 0 0 Ba The display shows L2 Tmax C LOCAL Input 2 2 0 0 0 E The following fixed scalings are available 200 400 C 0 6 V 10 mV K 0 2 V Code 2 100 400 C 0 10 V or 0 20 mA or 4 20 mA Code 3 0 100 C 0 10 V or 0 20 mA or 4 20 mA Code 4 Then the display shows L2 Ti T1 T2 Ts 0 3_ LOCAL E g to set the bath temperature on channel 1 input 0 Be Similarly for the LOCAL temperature signal of the external Pt 100 T1 input 1 A etc The display then returns to the standard display Temperature signal channel 2 Channel 2 is purely a voltage output at socket 52 S on pin 1 The selection is made as described for channel 1 in Item 8 11 1 except that current ranges can not be selected Safety function The operation of the safety devices of the units has already been described in Item 4 1 After starting up the user should confirm the correct operation of the safety devices If the uni
41. Pressing PS always enters the value on the display It is obviously essential to select a value above the current bath temperature Ti and the current setpoint TS otherwise the equipment is switched off by the safety circuit with L1 TEMPERATURE L2 TOO HIGH or the message L2 TS gt gt TO and the value is not accepted If the unit was switched off in the fault status an audible signal reports the stored fault when switching on qiir itr Press reset key D J Depending on the previous sequence press L9 again y p g p q If necessary check whether the overtemperature switch off point TO is above the current bath temperature and whether the bath is filled sufficiently YAUE0005 25 03 02 30 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 3 5 8 3 6 8 4 Low temperature switch off point lass u1 Press Wt SHIFT OFF to indicate the current low temperature switch off point TU If lass u TO is indicated press the key CO again to bring TU on display L2 TU _ 10 00 C TU low temperature switch off point TU can be set up to 10 K below the working temperature range of the unit If the bath temperature falls below TU TU appears on the display in L2 so that a new value can be input if necessary In addition the refrigeration unit is switched off so that TU can be used e g
42. ack of the unit underneath the back panel the inlet on the left and the discharge to the drain on the right when looking at the unit from the back The cooling water flow is adapted to the demand through the condenser pressure it is between 30 and 400 Uh depending on the unit type and the operating status The temperature of the water should not exceed 25 C 3 7 3 Safety devices of the refrigeration system The compressors are fitted with an over temperature cut out which responds to the compressor temperature and to their current consumption In addition the cooling systems are protected against over pressures by pressure control devices When the refrigeration compressor or both compressors is in operation the green lamp in the control unit is alight If this signal lamp is not alight despite the fact that the controller demands cooling cooling symbol on the right of the display please check whether the finned condenser is dirty air cooled units or whether there is a fault in the water supply or discharge water cooled units YAUE0005 25 03 02 17 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 3 7 4 Cooling diagrams YAUE0005 25 03 02 90 REA gg Eege gt EAE xe 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 SEEEEEES RRB Nfs ees TEE Natasa ie tee ASS SEI R
43. angerous media inside the equipment D autre part nous confirmons que l appareil mentionn ci dessus a t nettoy correctement que les tubulures sont ferm es et qu il n y a aucun produit toxique agressif radioactif ou autre produit nocif ou dangeureux dans la cuve Stempel Datum Betreiber Seal Cachet Date Date Responsible person Personne responsable Formblatt Form Formulaire Unbedenk doc LAUDA DR R WOBSER GmbH amp Co KG Erstellt published tabli LSC PfarrstraBe 41 43 Tel 49 0 9343 503 0 And Stand config level Version 0 1 D 97922 Lauda K6nigshofen Fax 49 0 9343 503 222 Datum date 30 10 1998 Internet http www lauda de E mail info lauda de UNBEDENK DOG
44. atically If T2 is not connected either the thermostat switches to Ti When changing the setpoint for more than 10 C it may be possible to achieve an improved control result by restarting the external control from the control variable Ti with SHIFT LA Notes When operating with external control it is essential to ensure that the probe for the control variable is in good thermal contact with the liquid otherwise a poor control result must be expected or the control may be completely ineffective Proceeding from the control parameters used for bath control the control may have to be adapted either by auto adaptation see Item 8 4 1 or by input of control parameters Important set the overtemperature switch off point TO see Item 8 3 4 sufficiently high since the bath temperature may under certain circumstances become much higher than the setpoint You may possibly activate the bath temperature limitation as well see Item 8 6 3 YAUE0005 25 03 02 40 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 8 Operation with programmer Temperature programmes with up to 99 segments can be stored and processed A segment consists of a target temperature which is to be reached at the end of the segment and the time duration of the segment The time 00 00 for temperature differences is possibl
45. ccceeeeecesseeeeeenseeneeenseeeeeeenseeeeeenseeneeenseeeeesenseeneeseseeneneneneees 16 3 7 Refrigeration SYStOiM ia eege SEENEN NEE EES 16 E ME Meel Ee WE Ee DEE 17 3 7 2 Water cooled version EE 17 3 7 3 Safety devices of the refrigeration System cccecccceeseeeeeceeeeeeeeeeeeeaeeeeaeeseeeeeseaeeeseaeeeeaeeseeeeetaees 17 3 7 4 ee inte Belle TEE 18 3 8 Mains supply output 34 H esc ccc secede ice 2lek ocd oe aces See ca dak hk eee dda ev td ca ded anunn ennnen nnmnnn nnmnnn nnmnnn nnna 19 3 9 Remote operation FBK Option 2 ccccceseeeeeeeeee cece eee eeneeeaeeeeeeeeee enn neeeeeseseeseeaseseneeeeeeeseeeseseeeeeeees 19 4 SAFETY DEVICES AND WARNING NOTES ees EEN 19 4 1 Safety F N CTION S use Eege ENEE EENEG 19 4 2 Why can a thermostat be AanGerouS ccccsccesseeeseeeeeeeeeeseaesesneeeneeeesesaesaseeeeneeaeseesseseeeenseeesenesnanes 20 AES importan le EE 20 4 4 Warning NOIES ee 21 4 41 ul e 21 Ake Mains Connection ice vacate chin ian ee Ata heh ad ten nda aed 21 4 43 CFUMOESXtrACKION DEE 21 5 BATH LIQUIDS AND HOSE CONNECTION KEEN 22 Bel CRL UE 22 5 2 Hose connections continuous lengths ccceseeeeeeee scence en eneeeeeenseeeeeeeeseeeeeenseeeeeeenseeneesnseesnenenseeees 23 6 UNPACKING ASSEMBLY AND SETTING UP KEREN 25 DCL SOM PC KUNG ssc eege eege 25 6 2 Setting up operation as bath thermostat 0 ccccsecesseeeeeeseeeseeeeeseeeeeeneseseaeseeseeeseaeseseaesenseaeeeneseeees 25 7 CONNE
46. col mixture uninsulated Silicone tubing 14 60 100 ecg tae LZS 011 water glycol mixture insulated ext dia 35mm approx Silikonschlauch 14 100 100 waler LZS 012 l water glycol mixture insulated ext dia 55mm approx YAUE0005 25 03 02 EPDM tube not for Ultra 350 and mineral oils Silicone oil causes pronounced swelling of Silicone rubber gt never use Silicone oil with Silicone tubing Protect tubing with hose clips against slipping off 23 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Metal hoses Tube i mm a mm Temperature Length single layer connection range C insulation MC 50 M 16x1 10 LZM 040 MC 100 M 16x1 10 18 10 400 100 LZM 041 MC 150 M 16x1 10 18 10 400 150 LZM 042 MC 200 M 16x1 10 18 10 400 200 LZM 043 Pump link M 16x1 10 18 10 400 20 LZM 044 Metal hoses Tube i mm a mm Temperature Length with insulation connection range C MK 50 M 16x1 150 LZM 052 MK 100 M 16x1 10 44 90 150 100 LZM 053 MK 150 M 16x1 10 44 90 150 150 LZM 054 MK 200 M 16x1 10 44 90 150 200 LZM 055 Pump link M 16x1 10 44 90 150 20 LZM 045 Metal hoses Tube i mm a mm Temperature Length with Insulation connection rang
47. d standard display Numerical inputs are always made with the SHIFT function switched off LED in SHIFT key off After the last digit of a number the cursor returns to the first digit so that corrections can LOCAL easily be made before pressing the key A brief beep on pressing a key means that this input is not possible Error messages are indicated with text notes and accompanied by a beep After approx 5 sec the message disappears and the beep switches off YAUE0005 25 03 02 29 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 3 4 Overtemperature switch off point lass u1 Press the 1 key to indicate the current overtemperature switch off point TO Important The green LED in the key must not be alight If necessary bring the IFT keypad to the basic mode by pressing the e key LED off If TU is indicated press lass u LH again to indicate To L2 TO _95 00 Ti TO overtemperature switch off point TO can be selected within the unit temperature range 5 K ESC Return to the standard display without change with Anew value is input with the number keys SHIFT OFF e g 98 70 C requires 0 9 8 7 0 Ba After the last digit the cursor returns to the first digit again so that any corrections can easily be made LOCAL
48. ding to the plug case The mass for all signals pin 3 must not be connected with ground If a connection to the ground cannot be avoided use a potential free signal bridge in between Cover the unused connectors with protective caps YAUE0005 25 03 02 45 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 10 Analogue inputs A setpoint in the form of an analogue current or voltage signal can be provided by connection to the socket Temp Signal 52 S see Item 8 9 By pressing the key in the SHIFT mode the display shows L1 ANALOGUE INP OUTP L2 INP 0 OFF 1_ Pressing 0 E selects the configuration and scaling of a setpoint input The display shows L1 ANALOG INP OFF 0 L2 ON 1 CONF 2_ LOCAL Input 1 ae switches in a previously configured input as setpoint and L2 shows an A on the right indicating that the setpoint is determined by the analogue input This condition remains stored in case of a fault or after the power is switched off LOCAL Input 0 E switches the setpoint back to the setpoint source internal i e key input Scaling takes place interactively by applying the voltage and current values corresponding to the appropriate temperature range limits to the corresponding input For pin connections for voltage or current input on socket 52 S see Item 8 9 This m
49. e C MGK 50 M 19x1 5 150 LZM 056 MGK 100 M 19x1 5 12 36 90 150 100 LZM 057 MGK 150 M 19x1 5 12 36 90 150 150 LZM 058 MGK 200 M 19x1 5 12 36 90 150 200 LZM 059 Metal hoses Tube Temperature with triple connection range C insualtion MC 50 S M 16x1 10 34 60 350 LZM 046 MC 100 S M 16x1 10 34 60 350 100 LZM 047 MC 150 S M 16x1 10 34 60 350 150 LZM 048 MC 200 S M 16x1 10 34 60 350 200 LZM 049 Further details on thermostatic liquids and hoses can be found in our special publication YAUE0005 25 03 02 24 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 6 Unpacking assembly and setting up 6 1 Unpacking Goods are packed carefully largely preventing transport damage If unexpectedly some damage is visible on the equipment please inform the carrier or the postal authority so that it can be inspected Standard accessories RUL 80 D RUL 90 D 1 Bath cover Cat No HDQ 051 2 Nipples 13 mm dia fitted Cat No HKO 026 2 Nipples 11 mm dia Cat No HKO 025 1 m Silicone tubing 11 mm int diameter Cat No LZS 007 Operating Instructions Standard accessories RUK 50 W D RUK 90 W D 1 Bath cover Cat No HDQ 050 2 Nipples 13 mm dia fitted Cat No HKO 026 2 Nipples 11 mm dia
50. e In connection with the tolerance range monitoring the programme continues not until the target temperature is reached It is useful to prepare a time temperature diagram before programming and to check whether the energy balance enables the programme speed Set the overtemperature switch off point To to a value slightly above the highest bath temperature to be expected see Item 8 3 4 8 8 1 Programme input PROGR INPUT Press the key L J in the SHIFT mode The display shows L1 PROG INP L2 Tata C Enter here the starting temperature of the programme SHIFT OFF automatically e g for 60 00 C input 0 6 0 0 0 Ba The display shows L1 PROG INP SEG 01 L2 Tew Cah Now enter the target temperature and the time for the first segment e g for 140 00 C in LOCAL LOCAL LOCAL the time 2 h 00 min 1 4 0 0 0 then 0 2 then 0 0 E The display shows L1 PROG INP SEG 02 L2 T h Now enter the target temperature and the time for the second segment e g for a phase at a constant temperature of 140 00 C and 1 h 30 min YAUE0005 25 03 02 41 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW LOCAL After the last programme segment press the key once more and the display shows L1 PROG INP L2 NO OF CYCLES _ Input 1 99 is possible With more than one cycle it is conveni
51. e range between min and max filling add additional liquid max filling height heating switches off output in cooling range cooling indication proportional to cooling actuation control C H output in heating range heating indication proportional to heating actuation control Bottom line L2 TS setpoint temperature S setpoint N notice that the level indication acts in the top line L1 Ti control variable is Ti bath temperature can be switched to T1 or T2 ext Pt 100 YAUE0005 25 03 02 28 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 3 3 setpoint source I internal input by keys P programmer R RS 232 C A analogue input socket 52 S lass u The display in line 1 L1 can be switched by pressing the keys W and repeated operation of G i to T1 T2 Ti etc T1 T2 measurements of external Pt 100 probes E boise 12 mp A The display in line 2 L2 can be switched by pressing the keys operation of Jto and repeated Y actual output heating cooling TSi measurement of the safety comparison probe with limited resolution and accuracy Ti T1 T2 TS etc Basic action on inputs and outputs ESC From virtually every display or input function the key aborts and returns to the selecte
52. e selected whether the thermostat should automatically switch on or off at the time to be selected subsequently in Item 8 14 3 Input either 1 or O as appropriate A display to input date and time appears Input here the switching point for the timing function as described in Item 8 14 1 and LOCAL enter it with ES The display returns to the standard display Activating the timing function By pressing the key in the SHIFT mode the display shows the selection menu as described in Item 8 14 1 Activate the timing function with ACTIV 1 by the input of 1 Fal Again the display shows L1 Clock L2 ON 1 OFF 0 LOCAL Normally 1 E is input here to activate the timing function The timing clock symbol now appears in line L1 before the last position If the previous selection was that the thermostat should switch on automatically the thermostat now switches off and starts up at the selected time When the unit has been switched off by the timing function the display shows L2 CLOCK STOP The activated timing function can always be switched off with off 0 i e with 0 E ESC In addition the timing function can be cancelled at any time with YAUE0005 25 03 02 60 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 9 9 1 9 2 Maintenance Safety notes in case of repairs Always pul
53. ection Cat No EQS 022 One probe can be selected for the actual value for external control Then the unit operates with cascade control to this actual value i e the unit controls the temperature at the external measurement point to the selected setpoint by suitably altering the bath temperature Thus the influence of disturbances changes of load or through flow etc can be reduced considerably or eliminated totally YAUE0005 25 03 02 39 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 7 2 8 7 3 Start of external control Connect platinum resistance thermometers to both of the Pt 100 inputs 10 S T1 and T2 It is sensible but not essential to use T1 if only one input is in use LU The external control with the measuring point T1 is switched on with the key in the SHIFT mode pressing the key again switches to T2 as control variable C Pressing the key _4 once more SHIFT ON switches back to the bath control internal Ti In L2 the position before the final one shows the parameter used as control variable L2 Ts 120 35 Ti T1 T2 This setting remains stored in case of a fault or after the power is switched off If T1 is selected but no probe has been connected the message L1 Ext Pt 100 not L2 connected appears The unit then switches the control variable to T2 autom
54. eeeeeeeeeeseeeeeseeseeeeeseseeeseseeceeseseseenenseeeeees 9 2 Repair and re initilisation 0 0 cccccseesseeeee cece eeeeeee scence seen enneneeeeeeeseeeseneeseseeeeeseeeeneees 9 3 Maintenance of the refrigeration SySteIm 0ccceceseeeeeeeeeeeeeeeeeeneeeeeeeeeseeeeeseees 9 4 Cleaning BE 9 5 Transport and etoragg EE EEEEEENEEEEE ENEE enidan eaae ENEE EENS 9 6 Spares Oring r r eege Seeerei EE 10 ACCESSORIES FOR LAUDA ULTRA KRYOMATS ssssssessnnnnnnnnunnnnnnnnnnnnnn YAUE0005 25 03 02 5 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 1 1 Brief Operating Instructions Even if you find these brief instructions initially sufficient please also read the following sections especially Section 4 Safety devices and warning notes For safe operation of the equipment it is essential that the information given in these Operating Instructions is observed Check the Ultra Kryomat and the accessories during unpacking for any transport damage and if necessary inform the carrier or the postal authority Assemble the unit according to Section 6 and add extra items as appropriate Water cooled units marked W in the type designation have to be connected to the mains water supply with the hoses supplied See Section 6 On air cooled units the spacing of the grilles from a
55. ent to have the final temperature and the starting temperature Tstart at the same level Afterwards a tolerance range can be input for monitoring the programme The display shows L1 PROG INP L2 TOL RANGE_ Now you can input a tolerance range value from 0 1 to 9 9 C l e if the control variable bath temperature or external temperature T1 or T2 deviates from the set temperature of the segment by more than the tolerance range value while the programme is running then the programme sequence will be stopped until the control variable is within the tolerance range again At the same time a T appears on the right in L2 The input of 0 0 switches off the tolerance range function YAUE0005 25 03 02 42 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 8 2 Example of a programme Segment 50 Segment No Input Press BS Tstart 03000 1x 1 SC 7000 1x h 02 1x min 00 1x 2 G 7000 1x h 01 1x min 30 1x 3 SC 9000 1x h 02 1x min 00 1x 4 C 8000 1x h 02 1x min 00 1x 5 SC 1000 1x h 02 1x min 30 2x Cycles 1 99 1x Tolerance range C 0 0 0 1 9 9 1x I YAUE0005 25 03 02 43 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW
56. er to the thermostat Thus in contrast to the command SEG_ several segments may be transmitted 55 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW The programme starts with the latest setpoint therefore please check before START whether the setpoint suitable for the first segment is available in the unit OUT_TBX X the tolerance range value is 1 2 of the value of the total range i e is 0 5 is 0 5 K range 0 1 9 9 K 0 0 switches off the tolerance range function OUT_CYXX number of the programme cycles range 1 99 0 switches off the function i e the programme is repeated until it is stopped manually START starts the segment contained in the programme buffer STOP stops the programme segment run With START the programme segment starts again from the beginning YAUE0005 25 03 02 56 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 13 4 Requesting data from the thermostat IN IN 3 IN 3 IN A IN_5 IN_6 IN IN 6 IN 9 IN A IN P IN CG YAUE0005 25 03 02 indication of the bath temperature Ti i e the request of the thermostat to transmit the bath temperature indication of the temperature value at the exte
57. essage signals as well as inputs are indicated as 2 x 16 characters 10 mm high on a liquid crystal display LCD with background illumination The input of the setpoint TS and all other parameters is made by using a membrane keypad with 16 keys and the operator guidance in the LCD display field All inputs are stored even when the thermostat is switched off or if the supply fails The digitizing of the Pt 100 resistance signal is performed in the microprocessor by continuous comparison with the precision resistors The secondary control using a modified PID control algorithm is purely digital Then the tubular heating element for the heating of the bath is operated electronically using a triac with burst firing action The refrigeration units are switched by the electronically controlled auto compressor system The LAUDA proportional cooling system uses low noise solenoid valves to control the cooling action through the PID temperature controller This leads to minimum energy demand and minimum environmental heating in fully automatic operation over the entire working temperature range under variable load conditions 3 7 Refrigeration system The units operate with compressor cooling Types RUK 50 and RUK 40 S have single stage systems types RUL 80 RUL 90 RUK 90 and RUK 90 S have 2 stage systems in cascade The low temperature stage operates with an electronic starting control Depending on the preceding operation the low temperature stage star
58. ethod compensates various scaling errors e g also those of the sources connected Pressing 2 E configures and scales the setpoint input The display shows L1 ANALOG INPUT L2 U 0 Assa Select a voltage range with 0 Ba Voltages in the range 0 10 5 V can be handled A current range is selected with 1 Ka Currents in the range 0 22 mA can be handled The display shows Li ANALOG INPUT L2 Tmin _ YAUE0005 25 03 02 46 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Input the lowest temperature of the range which corresponds to the lowest voltage or current value of the range to be scaled Example range 0 120 C should correspond to 0 10 V approx Input O O 0 0 O Ba The display shows L1 ANALOG INPUT L2 Tmax _ C LOCAL Input the upper limit of the temperature range 1 2 0 0 0 If the current input is selected the programme asks whether 0 20 mA or 4 20 mA is required The display shows L1 CURRENT INPUT L2 0 20 0 4 20 1 LOCAL LOCAL Select 0 Ba or 1 Ba This menu Item is omitted when the voltage input has been selected The display shows L1 INPUT CAL L2 YES 1 NO 0 Here the decision is made whether an automatic calibration procedure is started or whether the voltage or current values from the last calibration procedure are retained LOCAL
59. f very high or low temperatures Mains connection Connect the unit only to mains sockets with protective earth contact PE They must have a fuse according to the unit label Fume extraction Depending on the bath liquid used and the operating method there is a possibility that toxic vapours may be produced In that case it is necessary to provide an appropriate fume extraction Pull out the mains plug before cleaning the bath with solvents Provide appropriate fume extraction Before starting up the unit it is absolutely essential to ensure that the bath contains no explosive mixtures If necessary purge it with nitrogen YAUE0005 06 06 02 21 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 5 Bath liquids and hose connections The operating ranges of the bath liquids and hoses are general information only and may be restricted through the operating temperature range of the units or safety requirements specified in the appropriate standards see Item 4 2 5 1 Bath liquids LAUDA Working Chemical i Viscosity Ref No Designation tem Designation i kin at Quantity perature i Temperature range Former from C at 20 C mm2 s mm2 s 5l 101 201 designation to C water 5 90 deionised water Kryo30 G100 Ka Mono 50 at 25 C LZB 109 LZB 209 LZB 309 ethylene glycol water
60. ference is available otherwise it is better to use the factory calibration which gets lost by overwriting CAL Pressing the key 3 in the SHIFT mode green LED in shift key alight produces the display L1 CALIBRATE L2 Ti 0 T1 1 T2 2 LOCAL The channel to be calibrated is selected with 0 1 or 2 E YAUE0005 25 03 02 35 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 6 8 6 1 When selecting an unused channel e g if Pt 100 is not connected to T2 the display shows L1 Ext Pt 100 not L2 connected For calibration a sufficiently accurate reference temperature measurement should be possible and the measurement point temperature should be constant The display shows L1 IN 61 04 C L2 To The value shown in L1 is the measured value obtained without any correction using probe and electronics without calibration Now enter the real value for the measurement point T1 e g 60 00 C Example 0 6 0 0 0 Ti or T2 can be calibrated in the same way In order to avoid dangerous conditions the correction is limited to 5 K In case of larger corrections the display shows L1 CORRECTION VALUE L2 TOO LARGE and the entered value is not accepted ESC You can leave the calibration level with Control parameters Indication and input of the control parameters par
61. ilt in battery so that the clock continues to operate even when the unit is not connected to the electrical supply 8 14 1 Setting and indication of date and time This function is only required when changing from summer to winter time and vice versa or when the unit is being operated in other time zones Date and time are set at the factory when the unit is started up for the first time By pressing the key in the SHIFT mode the display shows L1 Clock 0 Activ 1 L2 SET 2 FUNCT 3 By the input of 0 ENTER date and time are indicated returns to the standard display The input of 2 SET allows date and time to be altered The display shows L1 DA MOYE H MI L2 Day month year weekday hours and minutes are now input in sequence Weekday code Monday Tuesday Wednesday Thursday Friday Saturday Sunday NOOR OD The hours are input from 0 to 24 factory set to Central European Time Example L2 19 01 98 3 16 05 Terminate the input with E YAUE0005 25 03 02 59 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 14 2 8 14 3 Timing clock function By pressing the key in the SHIFT mode the display shows the menu as described in Item 8 14 1 Select the timing function FUNCT 3 with 3 BS The display shows L1 Thermostat ON 1 L2 OR OFF 0 Here it can b
62. itions To enter the switch off point Tio proceed as described in Item 8 6 1 and switch the display to input and indication Example L2 Tio 120 C Change the value by entering the figures with a resolution of 1 C YAUE0005 25 03 02 37 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 6 4 LOCAL Enter the new value by pressing BS It is possible to select values within a range from 50 C to the selected overtemperature switch off point TO 5 C If this range has not been accepted the display shows the message L2 Tio gt gt To 5 C Of course TiO has to be set above the setpoint TS otherwise the display shows the message L2 TS gt Tio The bath temperature limitation can be switched off by entering L2 Tio 000 If the bath temperature Ti exceeds the selected switch off point the display shows Example L2 Tio 120 C and there is an acoustic signal The heater switches off As soon as the temperature has dropped the unit starts working again Correction limitation During the operation with external control it may be necessary not to exceed the difference between the bath temperature Ti and the measuring point for the external control T1 or T2 e g in order to get a smooth heating of the material or the vessel Such a limit value can be selected by the variable Ta If the
63. l out the mains plug or switch off the main switch for all repair and cleaning operations Repairs on the control unit with cover removed must be carried out by a qualified electrician only Repair and re initilisation LAUDA thermostats are largely free from maintenance Dirty thermostatic liquid should be removed through the drain cock and replaced If the unit should become faulty it may be advisable to return only the faulty module where appropriate When replacing the control unit check whether the new control unit has been programmed for the correct basic unit type If the correct type does not appear after having switched on the mains switch proceed as follows O PAR Mains switch off press the keys and L 6 simultaneously and at the same time switch on the supply Wait until the following display appears SHIFT L1 RK20K 0 K12K 1 L2 Type O PAR 4 Release the keys and 6 and go through the menu with the key until the required type appears Input the code number and enter with ES Example L1 RUK 40 20 RUK 50 21 L2 Type The type designations are shown abbreviated e g RUK 40 instead of RUK 40 S The units are protected by fuse cut outs except RUL 80 RUL 90 These are accessible after removing the back of the control unit The control circuit of the unit has a separate fuse a fuse 5 x 20 F4A is located in the control unit This is accessible after removing the cover When the fuse has blo
64. mps Simplex pumps have a single pressure stage they are used for thermostating closed external systems or when the unit is used mainly as a bath thermostat Duplex pumps have a pressure stage and a suction stage The output of the pressure stage is adjusted by a float in accordance with the bath level so that the two stages have the same output This arrangement permits to thermostate open external baths The pumps are fitted with a lever for flow rate adjustment which can be used to vary the flow rate between zero and the maximum The pumps operate perfectly up to a viscosity of approx 150 mm2 sec with the pump output decreasing rapidly with increasing viscosity Pump characteristics 50 Hz water SIMPLEX pump RUL 80 RUL 90 RUK 50 W RUK 90 W nipple 13 mm dia nipple 11 mm dia measured according to DIN 58966 nipple 13 mm dia nipple 11 mm dia measured according to DIN 58966 YAUE0005 25 03 02 15 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW SIMPLEX pump RUK 50 W P RUK 90 W P RUK 40 S W RUK 90 S W measured according to DIN 58966 5 0 15 20 75 30 35 40 45 50 3 6 Temperature control and electronics The units operate with a Pt 100 resistance thermometer for measuring the bath temperature Ti The bath temperature all other temperature values and m
65. nge The bath temperature is measured by a separate Pt 100 resistance sensor TSi and processed by a separate analogue digital converter This measured value is compared with the measured value of the bath temperature probe Ti continuously If the measurements differ by more than 15 C the thermostat switches off as in the case of a low level or over temperature fault The function of the microprocessor is monitored by an integrated watchdog circuit and an additional counter which operates similarly to a normal watchdog circuit but is also capable of switching off the unit in case of a strobe failure When the set overtemperature switch off point TO is exceeded the unit switches off permanently on all poles A float switch with magnetic coupling acts as a low level cut out and also switches off the unit pump heater and cooling system permanently on all poles In both fault conditions the display shows the corresponding message and additionally an audible signal draws attention to the fault The switch off function of the safety circuit remains stored even during a break in the supply or after having switched off the supply 1f r Reset is possible by pressing the reset key LO but only after having eliminated the toubles YAUE0005 25 03 02 19 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RU
66. ny object which might obstruct the free air flow must be at least 0 5 m Fitting the tubing to the pump connections Without external system link the pump connectors together to ensure better circulation inside the bath using e g EPDM tubing up to 120 C or better the metal tubing With external system connect the tubings to the external system Protect the tubing with hose clips against slipping off Use only softened water or LAUDA bath liquids Section 5 Fill up the bath to a level about 1 cm below the plastic cover plate Check the supply voltage against the details on the label Insert the mains plug On water cooled units turn on the water tap Switch on the supply switch green lamp lights up On 3 phase units the mains switch red yellow has to be switched on first If the unit except RUL 80 D RUL 90 D and RUK xx W D has not previously been operating on this supply check the direction of the rotation of the pump motor in the case of air cooled units without W in the type designation also check the condenser fans see Item 8 3 1 The display shows the software version and the type of the unit followed by the standard display Poise 1 loss 3 Select the required indications using the keys and in the SHIFT mode It is useful to show the setpoint TS in display line 2 L2 see Item 8 3 2 Set the overtemperature switch off point TO slightly above the operating temperature 1f r If there is an err
67. oint 12 C viscosity at 20 C 1 5 mm s freezing point 114 C DIN safety data sheets are available on request YAUE0005 25 03 02 22 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 5 2 Hose connections continuous lengths Tubing type Int dia Temperature Application mm range C EPDM tubing uninsulated For all bath liquids except Ultra 350 and mineral oils RKJ 111 EPDM tubing insulated 10 120 EPDM tubing 12 uninsulated EPDM tubing insulated 60 120 For all bath liquids except Ultra 350 and mineral oils For all bath liquids except Ultra 350 and mineral oils For all bath liquids LZS 019 RKJ 112 LZS 021 T SZ except Ultra 350 and 35mm approx mineral oils Silicone tubing 8 water Ee LZS 001 insulated ext dia gy 30 mm approx Silicone tubing 8 100 100 waten LZS 002 i water glycol mixture insulated ext dia 50 mm approx Silicone tubing VARG RKJ 016 water glycol mixture uninsulated Silicone tubing wates RKJ 059 j water glycol mixture uninsulated Silicone tubing 11 60 100 ware LZS 007 l water glycol mixture insulated ext dia 32 mm approx Silikonschlauch 11 100 100 waon LZS 009 water glycol mixture insulated ext dia 52 mm approx Silikonschlauch 14 10 100 Walls RKJ 070 water gly
68. or message press the key LOJ and perhaps increase To YAUE0005 25 03 02 6 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 1 2 Important TO must be at least 25K below the fire point of the bath liquid used see Item 8 3 4 When connecting up an external system please check that filling this system does not cause the level inside the thermostat to fall more than permitted When the thermostating liquid has reached the setpoint the symbol or i starts to flash in line 1 L1 of the display After the unit has stabilised the bath temperature Ti corresponds to the setpoint TS If the refrigerating system has been out of use for some time it may take up to 20 minutes depending on the ambient temperature and the type of unit until the rated cooling capacity is available 1 3 Operating safety The thermostat must be operated with non flammable bath liquids or with flammable bath liquids up to 25 C below their fire point otherwise there is the possibility that a flammable atmosphere may form see Item 4 2 1 4 Warning The outflow and return pipes of the pumps reach the operating temperature i e even temperatures above 70 C Touching them is dangerous because of very high or low temperatures YAUE0005 25 03 02 sw 7 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50
69. p from rolled sections and fitted with covers on all four sides The unit is mounted on four castors the two front ones of them can be locked Front and rear panels are fitted with large ventilation grills which ensure heat dissipation especially in air cooled units The side panels have recessed hand rails so that the units can be placed side by side The back of the cover plate carries the control unit with pump drive electrical controls connections for temperature probe level probe and heater as well as the control panel with electronics and connection to the supply Thermostatic bath The bath is made of rustfree stainless steel and insulated with polyurethane foam to suit the working temperature Most of the bath area has a free bath opening for thermostating inside the bath All parts in contact with the bath liquid are made from rustfree stainless steel nickel plated copper plastics stable over the working temperature range PETP or PTFE YAUE0005 25 03 02 14 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 3 5 Circulating pump The units are fitted either with a pressure pump type designation without D or with P which we call SIMPLEX pump or with a pressure suction pump with level control type designation with D called DUPLEX pump Both pump types are submersible centrifugal pu
70. rby units or walls Kc Ambient temperature too high Air eee a al room Insufficient cooling in the Bath liquid contaminated by Ee bath liquid to suit bath lower temperature range condensate temperature Cools down to approx 0 C Bath liquid not suitable water Use water glycol mixture only G Therm Service Fehler Fehlpe1 doc 04 12 98 page 4 of 4 BESTATIGUNG CONFIRMATION CONFIRMATION LAUDA An To A LAUDA Dr R Wobser LAUDA Service Center Fax 49 0 9343 503 222 Von From De Firma Company Entreprise Stra e Street Rue Ort City Ville Tel Fax Betreiber Responsible person Personne responsable Hiermit best tigen wir da nachfolgend aufgef hrtes LAUDA Ger t Daten vom Typenschild We herewith confirm that the following LAUDA equipment see label Par la pr sente nous confirmons que l appareil LAUDA voir plaque signal tique Typ Type Type mit folgendem Medium betrieben wurde was used with the below mentioned media a t utilis avec le liquide suivant Dar ber hinaus best tigen wir da das oben aufgef hrte Ger t sorgf ltig gereinigt wurde die Anschl sse verschlossen sind und sich weder giftige aggressive radioaktive noch andere gef hrliche Medien in dem Ger t befinden Additionally we confirm that the above mentioned equipment has been cleaned that all connectors are closed and that there are no poisonous aggressive radioactive or other d
71. re available at the socket Temp Signal 52 S see Item 8 9 They can be set to carry the temperature values Ti bath temperature T1 temperature at ext Pt 100 T1 T2 temperature at ext Pt 100 T2 TS setpoint YAUE0005 25 03 02 48 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 11 1 Temperature signal channel 1 Channel 1 can be configured at the socket 52 S on pin 2 as a voltage output or on pin 5 ANALOG 1 0 as a current output Press the key in SHIFT mode The display shows L1 ANALOG INP OUTP L2 INP 0 OUTP 1 Select the processing of the outputs by pressing 1 Ba The display shows L1 Analog output L2 Chan 1 1 Chan 2 2 Select channel 1 by pressing 1 ES The display shows L1 Analog output L2 USO et Select the current output with 1 Fa The display shows L1 CURRENT OUTPUT L2 0 20 0 4 20 1 LOCAL Select the required current range 0 20 mA or 4 20 mA by pressing 0 or 1 The current range selection is omitted if the voltage range 0 10 V has been selected in the previous menu The display shows the scalings available for selection L1 CONFIGURABLE 1 L2 analog output_ By pressing the key SHIFT ON the pre set scalings are displayed consecutively The selection is made by the input of the appropriate code SHIFT OFF YAUE0005 25 03 02 49
72. rnal control a cascade controller operates on the measurement of one of the external circuits T1 or T2 Temperature variation at 10 C C 0 1 0 5 0 1 0 5 0 1 0 5 0 1 0 5 Heater rating max kW 120 20 20 20 Cooling capacity 20 C KW 4 8 6 0 4 0 4 0 eff 0 C 3 9 4 8 3 6 3 6 with ethanol at 20 C 10 C 3 0 3 8 3 4 3 4 ambient temperature 20 C 20 24 3 2 3 2 40 C 0 7 0 8 2 8 2 8 50 C 2 0 2 0 60 C 0 7 0 7 80 C 0 2 0 2 Safety system Overtemperature protection with selectable switch off point low level protection to EN 61010 FL DIN 12879 Class 2 Simplex pump Pump output against zero head l min 50 50 50 50 max pump pressure bar 0 8 0 8 0 8 0 8 Pump connections M 19x1 5 M 19x1 5 M 19x1 5 M 19x1 5 Nipples 15 Nipples 15 Nipples 15 Nipples 15 Filling volume max L 19 27 19 27 19 27 19 27 Bath opening W x D mm 282x257 282x257 282x257 282x257 Bath depth mm 220 220 220 220 Usable liquid depth mm 180 180 180 180 Height to top of bath mm 900 900 1060 1060 Floor area WxD mm 1000x735 1000x735 1300x735 1300x735 H 1250 1250 1410 1410 Weight Kg 260 260 440 440 Supply V Hz 230 400 3 N PE 50 Protection class 1 to VDE 106 Loading kW 6 1 5 7 9 1 8 7 Units conform to EU Guideline 89 336 EWG EMC and 73 23 EWG low voltage and carry the CE mark 50 Hz units Cat No LUK 209
73. rnal probe T1 indication of the current setpoint TS status signal 7 characters char 1 from the left overtemperature fault 1 no fault 0 char 2 low level fault 1 level OK 0 char 3 programmer segment running 1 programmer segment off 0 char 4 control according to the bath temperature Ti 0 T1 1 7T2 2 char 5 setpoint set by analogue inputs 1 analogue inputs off 0 char 6 indicates whether external Pt 100 T1 is connected 1 or not connected 0 char 7 indicates whether external Pt 100 T2 is connected 1 or not connected 0 invalid invalid indication of the temperature of the external probe T2 indication of the current low temperature switch off point TU indication of the current overtemperature switch off point TO indication of the current value of Xp indication of the current value of Tn indication of the current value of Tv 57 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Examples A BASIC programme used to transfer values from the thermostat to the computer and to display them specifying the channel number e g 1 for IN_1 i e the bath temperature is as follows Note set baud rate to 4800 see Item 8 4 5 10 OPEN COM1 4800 N 8 2 AS 1 20 CLS 30 LOCATE 8 5 PRINT SPC 20 40 LOCATE 8 5 50 INPUT Channel No NR 60 PRINT
74. s 14 18 dia 110 mm immersion UG 072 RE 30 for 14 tubes 24 30 dia 110 mm immersion UG 073 RUL 80 D RUL 90 D 1 rack RF 18 1 for 20 tubes 14 18 dia 80 mm immersion UG 074 RF 18 2 for 20 tubes 14 18 dia 110 mm immersion UG 075 Non return fitting RUL RUK without P and S UD 125 for automatic venting of the connecting hoses when thermostating an open external bath Remote operation FBK LUZ 906 without cable set The electronic control unit is placed separately from the unit and linked to it by cable Cable set for FBC length 5 m UK 235 Cable set for FBC length as specified UK 238 LAUDA Pt 100 platinum resistance thermometers to DIN IEC 751 Class A for external control and other temperature measurement Pt 100 42 all glass version with NS 14 23 ground taper DIN 12242 Temp range 100 300 C 50 response time 0 8 sec Overall length approx 115 mm 4 wire circuit ETP 049 Fig 1 Pt 100 44 all glass version with NS 14 23 ground taper DIN 12242 Temp range 100 300 C 50 response time 0 8 sec Overall length approx 320 mm ETP 007 Fig 2 Pt 100 66 as Pt 100 44 Overall length approx 430 mm ETP 008 Fig 2 YAUE0005 25 03 02 63 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Pt 100 90 stainless steel protection tube 4 mm dia Temp range 100 300 C 50
75. s protect the tubing with hose clips against slipping off or use stainless steel hoses V2A with screwed connections Circulating pumps In principle there is a difference between SIMPLEX pumps e g at RUK 50 RUK 90 W P and DUPLEX pumps at e g RUK 50 D RUK 90 W D SIMPLEX pumps are used for operation with closed external systems They require a pressure tight external system DUPLEX pumps are used mainly with open external systems such as baths In contrast to SIMPLEX pumps they have a pressure and a suction stage as well as a float for level control DUPLEX pumps automatically maintain a constant level in the Kryomat irrespective of the level in the external bath Liquid is poured into the external bath until a level is achieved in the Kryomat at which the pressure and the suction stage have exactly the same output If the difference in level between the open external bath and the Kryomat bath is greater than 0 5 m there is the possibility in certain applications that the control range of the level controller is not sufficient With a higher lower external bath level the suction pressure hose should then be clamped off with a tubing clamp to such an extent that a constant level in the bath is obtained at which the pump float is within its control range YAUE0005 25 03 02 26 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK
76. t operates without supervision we recommend this check to be carried out daily YAUE0005 25 03 02 50 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 12 1 8 12 2 Low level cut out For the correct operation of the low level cut out it is essential that the float switch operates correctly To check this lower the level in the bath by draining away some of the liquid When the bath level falls below the minimum level approx 20 mm above the upper heater winding the pump the heating and the refrigeration unit switch off on all poles The display shows the message L1 LEVEL L2 TOO LOW and there is a warning beep cae To restart fill up the bath and press the reset key Q twice with approx 1 sec interval Adjustable overtemperature limiter To check it the switch off point TO has to be set below the current bath temperature Note that an input of TO below the setpoint TS produces the message L2 TS gt gt TO and the previous value for TO is retained Therefore the setpoint Ts usually has to be lowered by a few degrees first before this test can be carried out Then the overtemperature switch off point can be set e g 1 C below the current bath temperature Example Ti 60 C TS 60 C TO 650 ner 12 To check the operation of the overtemperature limiter press
77. the Check temperature reference Correcting value too 100 from standard values basic value that is indicated by thermometer check Pt 100 high more than 5 K replace PCB CPU Scale of analogue Outputs not correctly calibrated Calibrate the analogue output outputs shows channels discrepancies see operating instructions Unit does not heat Triac Replace triac though heating is indicated Interruption Eliminate Controller output limitation at Enter higher values at PAR level PAR level too small e g 100 Pump does not run Temperature safety cut out Motor blocked Turn propeller of motor if in pump has actuated necessary replace it clean pump Pump stops Viscosity of bath liquid too high Use other bath liquid wait until motor has cooled down Bath temperature rises Controller Replace PCB MP Mains or PCB clearly above adjusted CPU setpoint Ts Heating indication ON Heating indication OFF a a Pee l triac Temperature rises slowly res not sufficient es emission of pump islet cooling water supply or above adjusted setpoint other kind of cooling Heating indication OFF Display shows wrong Temperature probe Replace double Pt 100 or external temperature Ti T1 T2 Pt 100 T1 T2 Display is dark Temperature cut out in Overload caused by short Replace PCBs or control unit transformer has actuated circuit G Therm Service Fehler Fehlpe1 doc 04 12 98 page 3 of 4 Notes for trouble shooting for L
78. tivated until the next output command by pressing the keys ENTER The data requests by the thermostat IN commands only lock the programme keys SHIFT and SHIFT Kal All the other key functions are in operation In the following text the symbol _ will be taken to mean blank no character RS 232 interface and controller are operated by a single processor for optimum control it is therefore advisable to have pauses of at least 100 msec between the interface commands Output commands OUT_XXX XX Setpoint transfer with up to 3 places before the decimal point and up to 3 places behind This includes the negative sign Transfer can take various forms e g for 5 00 C 005 00 05 05 0 005 5 00 A BASIC programme for the IBM PC which can be used to transfer any values between the set upper and lower limits see Items 8 3 4 and 8 3 5 and which displays the response O K or a possible error message may be as follows YAUE0005 25 03 02 54 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW Note set baud rate to 4800 see Item 8 4 5 OPEN COM1 4800 N 8 2 AS 1 CLS LOCATE 8 5 PRINT SPC 70 LOCATE 8 5 INPUT Enter your command without OUT_ VALUE PRINT 1 OUT_ VALUE INPUT 1 A LOCATE 12 5 PRINT SPC 50 LOCATE 12 5 PRINT Response of the thermostat A T
79. ts up 10 sec to 20 min after the refrigeration system has been started up The refrigeration system cools the bath liquid through a heat exchanger mounted inside the bath YAUE0005 25 03 02 16 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 3 7 1 Air cooled version Condenser and motor heat are removed through a finned condenser cooled by a powerful fan Fresh air is drawn in at the front of the unit and discharged towards the back It is essential that there is no restriction to free ventilation Because of this the distance between the ventilation grilles and walls or similar must be at least 0 5 m Furthermore the units should also not be operated close to sources of heat Such as radiators etc The cooling capacity specified under technical data refers to 20 C ambient temperature higher temperatures lead to a reduction in cooling capacity Above 35 C the compressor switches off automatically depending on the loading The heat dissipated to the room air is made up of the heat removed from the bath by cooling together with the energy taken from the electrical supply 3 7 2 Water cooled version The heat of the condenser and of the motor is removed through a water cooled counter flow heat exchanger The connections for inlet from the water tap and outlet to the drain are located at the b
80. urer 9 5 Transport and storage Warning in case of danger of frost e g transport in winter the condenser of water cooled units has to be emptied For this operation warm up the bath to approx 20 C disconnect the water hose from the water tap Set the setpoint to e g 20 C and immediately on start up of the first stage compressor blow compressed air into the water supply hose seen from the back on the left side Set the drain hose as low as possible so that the unit is emptied completely Switch off the unit immediately 9 6 Spares ordering When ordering spares please specify the equipment type and number on the label This avoids queries and prevents the supply of wrong goods We shall always be happy to deal with queries suggestions and complaints LAUDA DR R WOBSER GMBH amp CO KG Postfach 1251 97912 Lauda K6nigshofen Tel 49 0 9343 503 0 Fax 49 0 9343 503 222 E mail info lauda de Internet http www lauda de YAUE0005 25 03 02 62 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 10 Accessories for LAUDA Ultra Kryomats Racks in stainless steel for test tubes centrifuge tubes etc All RUK units up to 3 racks RE 13 for 56 tubes 10 13 dia 80 mm immersion UG 070 RE 18 1 for 33 tubes 14 18 dia 80 mm immersion UG 071 RE 18 2 for 33 tube
81. with input 0 Bal The display returns to the standard display With a new calibration the voltage or current source e g setpoint unit programmer has to be connected up The range limits have to be adjustable The unit may switch to fault if the input signal is not connected If this is the case it is necessary to connect the input utr signal first Then press the reset key U and calibrate in the same way as described above YAUE0005 25 03 02 47 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 11 Select the recalibration with 1 Ba The display shows Li SET Umin L2 YES 1 When the voltage or current corresponding to the lower range limit is applied to the LOCAL input confirm this by the input of 1 ENTER The display shows Ete Ee wait L2 XXXXXXXXXXXXXX The calibration takes approx 20 sec The display then shows L1 SET Umax L2 YES 1 When the voltage or current corresponding to the upper range limit is applied to the input confirm this by the input of 1 E The display shows NNN wait L2 XXXXXXXXXXXXXX The calibration takes approx 60 sec The display then returns to the standard display The calibration is finished Switch on the external setpoint from an analogue input as described in Item 8 10 2 Analogue outputs Two analogue output channels a
82. wn the green lamp in the mains switch does not light up YAUE0005 25 03 02 61 LAUDA Ultra Kryomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 9 3 Maintenance of the refrigeration system The refrigeration system operates largely without maintenance If an air cooled unit is being operated in a dusty atmosphere we recommend to clean the condenser of the refrigeration system at intervals of 4 to 6 months This is best done by blowing compressed air or nitrogen into the ventilation openings for a few minutes Unscrew the front grille if necessary Repair and disposal note The cooling circuit is charged with HFHC refrigerant See the label inside the unit The repair and disposal must be carried out by a qualified refrigeration engineer only 9 4 Cleaning The unit can be cleaned using a cloth moistened with water with the addition of a few drops of domestic detergent No water must find its way into the control unit The user is responsible for any necessary decontamination if dangerous materials have been spilled on or inside the unit This applies in particular if the unit is removed for a different use for repair storage etc The method of cleaning or decontamination is determined by the expertise of the user If the user has any doubts on whether this may damage the unit he is to contact the manufact
83. working temperature range Laboratory thermostats operate with liquids operating medium heat transfer oil which serve for energy transfer to the product to be thermostated The thermostated products can be immersed in the thermostatic bath bath thermostat or placed in an external open bath whose liquid is circulated by the pump of the thermostat When operating as circulator the thermostatic liquid is pumped through an external heat exchanger arranged by the user in which a product is being thermostated jacketed vessels reactors heat exchangers Type selection Ultra Kryomats RUL 80 and RUL 80 D have a working temperature range down to 80 C Ultra Kryomats RUL 90 and RUL 90 D have a working temperature range down to 90 C and are available only with air cooled condenser Series RUK 50 and RUK 90 are more powerful units and are available with both air cooled and water cooled condenser Version RUK P is equipped with a more powerful Simplex pump and has a slightly restricted temperature range Series RUK 40 S and RUK 90 S have an appreciably larger cooling capacity combined with the high power Simplex pump Construction The refrigeration system is mounted in the lower part of the basic unit Above this the rust free stainless steel bath is set into the cover plate On RUL 80 RUL 90 and RUK 90 units a heat exchanger embedded in insulation is located below the cover plate The main constructional element is a frame made u
84. yomats RUL 80 D RUL 90 D RUK 50 D RUK 50 W D RUK 90 D RUK 90 W D RUK 50 P RUK 50 W P RUK 90 P RUK 90 W P RUK 40 S RUK 40 SW RUK 90 S RUK 90 SW 8 9 Connection for analogue signals socket 52 S 6 pin flange socket according to NAMUR recommendation NE 28 Pin 1 voltage output temperature signal channel 2 setpoint TS bath temperature Ti external Pt 100 T1 or T2 can be selected Scaling can be as follows 0 10 V corresponding to a temperature range selected within the working temperature range e g 50 80 C minimum load 4 kOhm or 0 6 V 200 400 C 10 mV K 0 2 V or 0 10 V 100 400 C or 0 10 V 0 100 C Pin 2 voltage output temperature signal channel 1 other data as pin 1 Pin 3 ground for all signals Pin 4 setpoint voltage input scaling can be selected as pin 1 Ri 12 kOhm approx pin 4 pin 3 Pin 5 current output temperature signal channel 1 signal selection as pin 1 Can be configured for 0 20 mA or 4 20 mA Scaling can be 0 20 4 20 mA 100 400 C or 0 20 4 20 mA 0 100 C or 0 20 4 20 mA a temperature range selectable within the working temperature range e g 50 80 C maximum burden 330 Ohm Connect only either pin 2 or pin 5 Pin 6 setpoint current input configuration and scaling as pin 5 Burden 320 Ohm approx Maximum voltage 15 V Connector plug 6 pin Cat No EQS 057 Use shielded connecting cables Connect the shiel

Download Pdf Manuals

image

Related Search

Related Contents

OK LIGHTING OK-5109H Installation Guide  Asrock Fatal1ty Z97M Killer  Manual del usuario - Rockwell Automation  

Copyright © All rights reserved.
Failed to retrieve file