Home

Kelvinator JS4BE-048KA Installation Guide

image

Contents

1. 128 264 127 286 265 131 287 287 Table 3 Charging Table 1 5 Ton Units OUTDOOR TEMPERATURE F TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS 259 131 299 346 146 368 149 390 152 412 155 10 258 137 301 259 140 280 139 281 143 303 142 304 146 Table 4 Charging Table 2 Ton Units NOTES LEGEND HUA Shaded boxes indicate flooded conditions 1 All pressures are listed psig and all temperatures in F EE Rated design values The suction pressure 2 Discharge temperatures GREATER than charted values will be lower than design value if indoor air indicate an UNDERCHARGED system flow entering dry bulb or entering wet bulb 3 Discharge temperatures LESS than charted values indicate an OVERCHARGED system temperatures are lower than design OUTDOOR TEMPERATURE F TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS 243 132 137 142 266 140 308 145 144 148 Table 5 Charging Table 2 5 Ton Units OUTDOOR TEMPERATURE F TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS EE
2. ELECTRICAL WIRING Pre Electrical Checklist Line Voltage Connecting Refrigerant Tubing Between the Indoor amp Outdoor Unit Grounding Thermostat Connections START UP amp ADJUSTMENTS Pre Start Check List Start Up Procedures Air Circulation Indoor Blower System Cooling System Heating optional AIR CONDITIONER MAINTENANCE REFRIGERANT CHARGING Charging the Unit in AC mode Charging Charts amp Application Notes Figure 2 Charging Chart 1 5 Ton Models Figure 3 Charging Chart 2 Ton Models Figure 4 Charging Chart 2 5 Ton Models Figure 5 Charging Chart 3 Ton Models Table 3 Charging Table 1 5 Ton Units Table 4 Charging Table 2 Ton Units Table 5 Charging Table 2 5 Ton Units Table 6 Charging Table 3Ton Units WIRING DIAGRAMS Figure 6 W D for 1 5 2 2 5 amp 3 Ton Models Figure 7 W D for 3 Ton Models INSTALLATION PERFORMANCE CHECKLIST REPLACEMENT PARTS IMPORTANT SAFETY INFORMATION INSTALLER Please readall instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate
3. Charging Chart 1 5 Ton Models S4BE 024KB Charging Chart Cooling Remove refrigerant when above curve Add refrigerant when below curve 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Figure 3 Charging Chart 2 Ton Models 2 a 2 5 a he A 2 3 3 Liquid Pressure psig S4BE 030KB Charging Chart Cooling Remove refrigerant when above curve Add refrigerant when below curve 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Figure 4 Charging Chart 2 5 Ton Models S4BE 036KB Charging Chart Cooling Remove refrigerant when above curve Add refrigerant when below curve 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Figure 5 Charging Chart 3 Ton Models LEGEND E Shaded boxes indicate flooded conditions tE Rated design values The suction pressure NOTES will be lower than design value if indoor air flow entering dry bulb or entering wet bulb temperatures are lower than design indicate an UNDERCHARGED system indicate an OVERCHARGED system OUTDOOR TEMPERATURE F 1 All pressures are listed psig and all temperatures in F 2 Discharge temperatures GREATER than charted values 3 Discharge temperatures LESS than charted values TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS TEMP PRESS 124
4. Charts amp Application Notes This equipment s cooling system contains refrigerant under high pressure Always use safe and environmentally sound methods when handling refrigerant handling or servicing the unit Review the factory literature and safety warnings prior to servicing When repairing system leaks always use a nitrogen inert gas to protect the refrigerant system and pressure check the repair before re charging Always replace the filter dryers when performing any repair to the refrigeration system with one capable of acid removal After completing the repairs evacuate the system to 350 500 microns and weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging charts Figure 2 page 8 Figure 3 page 8 Figure 4 page 9 amp Figure 5 page 9 are applicable only to matched assemblies of NORDYNE equipment and listed airflows for the indoor coil NOTE Before using these charts make sure the unit is in a stable operating mode As shown in the charts the ideal system sub cooling can vary over the range of operation Reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit efficiency EER or rated Coefficient of Performance COP in heating mode Table 3 page 10 Table 4 page 10 Table 5 page 11 or Table 6 page 11 are valid for a variety of indoor return air cond
5. Inspect for loose connections Line Voltage A wiring diagram is located on the inside cover of the electrical box of the outdoor unit The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit Anelectrical disconnect must be located within sight of and readily accessible to the unit This switch shall be capable of electrically de energizing the outdoor unit Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit Incoming field wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed onthe outdoor unit data label Any other wiring methods must be acceptable to authority having jurisdiction The outdoor unit requires both power and control circuit electrical connections Refer to the wiring diagram schematic for identification and location of outdoor unit field wiring interfaces See Figure 6 and Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits Provide power supply for the unit in accordance with the unit wiring diagram and
6. equipment access control panels are in place y Verify air filters are cleaned and properly installed y Verify duct work is sealed to prevent air leakage y Verify line voltage power leads are securely connected and the unit is properly grounded y Verify low voltage wires are securely connected to the correct leads on the low voltage terminal strip y Verify power supply branch circuit overcurrent protection is sized properly y Verify the thermostat is wired correctly Start Up Procedures The thermostat s function mode should be set to OFF and the fan mode should be set to AUTO Close all electrical disconnects to energize the system Air Circulation Indoor Blower 1 Set the thermostat system mode on OFF and the fan mode to ON 2 Verify the blower runs continuously Check the air delivery at the supply registers and adjust register openings for balanced air distribution If insufficient air is detected examine ductwork for leaks or obstructions 3 Set the thermostat fan mode to AUTO and verify the blower stops running System Coolin 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for an
7. letretien to H on 2 Employez uniquement des conducteurs capacitor en cuivre RED 3 Ne convient pas aux installations de plus de 150 volt a la terre to T2 on_ BLACK capacitor STAR YELLOW ORANGE S OUTDOOR START BLUE FAN MOTOR CAPAC l to C on capacitor YELLOW q GROUNDING SCREW l l l l l L 1__L2 GND CRANKCASE HEATER OPTIONAL SEE NOTE 6 7114520 8 14 Figure 7 W D for 3 Ton Models 13 14 15 INSTALLATION PERFORMANCE CHECKLIST INSTALLATION ADDRESS CITY STATE o o o UNIT MODEL UNIT SERIAL INSTALLER NAME CITY Unit Installed Minimum clearances shown on page 3 Has the owner s information been N reviewed with the customer O Bie Hong Package been left m Stage 1 Suction Pressure low side PROPOSITION 65 WARNING WARNING This product contains chemicals known to the state of California to cause cancer WARNING This product contains chemicals known to the state of California to cause birth defects or other reproductive harm AR CERTIFIED www ahridirectory org Cc US Listed Intertek Unitary Small AC AHRI Standard 210 240 Certification applies only when the complete system is listed with AHRI We Encourage Professionalism o i Tan exe YOUR ENVIRONMENT OUR EXPERTISE v MEMBER COMPANY Rs ENCE Through Technician Certification by NATE ELECTRICAL SYST
8. personal injury or death e The installer must comply with all local codes and regulations which govern the installation of this type of equipment Local codes and regulations take precedence over any recommendations contained in these instructions Consult local building codes and the National Electrical Code ANSI Cl for special installation requirements All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code Part 1 CSA C 22 1 This equipment contains liquid and gaseous refrigerant under high pressure DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment Fully annealed refrigerant grade copper tubing should be used when installing the system Refrigerant suction line tubing should be fully insulated Installation of equipment may require brazing operations Installer must comply with safety codes and wear appropriate safety equipment safety glasses work gloves fire extinguisher etc when performing brazing operations Follow all precautions in the literature on tags and on labels provided with the equipment Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of
9. 2 GND SCREW CONNECTIONS CRANKCASE WIRE NUT HEATER LEGEND SEE NOTE6 OPTIONAL CC Contactor Coil FIELD WIRING CCH Crankcase Heater HPS High Pressure Switch ance Vor Ge 711 0050 Figure 6 W D for 1 5 2 amp 2 5 Ton Models WIRING DIAGRAM Split System Air Conditioner Outdoor Section NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 deg C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40ca class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 8 DO NOT use a Hard Start Kit on a model with a PTCR installed lt lt 208 230 mu L1 CCH OPTIONAL COMPRESSOR CONTACT Sm OUTDOOR FAN MOTOR 24 VOLT FIELD CONNECTIONS LEGEND FIELD WIRING LOW VOLTAGE HIGH VOLTA G Es CC Contactor Coil CCH Crankcase Heater HPS High Pressure Switch YELLOW BLACK WIRE NUT Single Phase 1 Couper le courant avant de faire
10. B B BA O O O O00 O00 w Wire Size based on N E C for 60 type copper conductors Table 1 Copper Wire Size THERMOSTAT WIRE GAUGE MAXIMUM RECOMMENDED THERMOSTAT WIRE LENGTH FT Table 2 Thermostat Wire Gauge Thermostat Connections Thermostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment The outdoor unit is designed to operate from a 24 VAC Class II control circuit The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA 70 and with applicable local codes having jurisdiction The low voltage wires must be properly connected to the units low voltage terminal block Recommended wire gauge and wire lengths for typical thermostat connections are listed in Table 2 The thermostat should be mounted about 5 feet above the floor on an inside wall DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s instruction sheet for detailed mounting and installation information START UP amp ADJUSTMENTS Pre Start Check List y Verify the indoor unit is level and allows proper condensate drainage y Verify the outdoor coil and top of the unit are free from obstructions and debris and all
11. EE 125 128 133 268 133 311 137 137 z 141 Table 6 Charging Table 3Ton Units 12 WIRING DIAGRAMS WIRING DIAGRAM Split System Air Conditioner Outdoor Section Single Phase NOTES Ta For ampacities and overcurrent protection see unit rating plate Connect to 24 vac 40ca class 2 circuit See furnace airhandler installation toT2on BLACK Disconnetall power before servicing 1 Couper le courant avant de faire letretien For supply connections use copper conductors only 4 2 3 Not suitable on systems that exceed 150 volts to ground 4 5 6 2 Employez uniquement des conducteurs to H on en cuivre capacitor 3 Ne convient pas aux installations RED de plus de 150 volt a la terre For replacement wires use conductors suitable for 105 deg C instructions for control circuit and optional relay transformer kits capacitor Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as shown using BLACK manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 START DO NOT use a Hard Start Kit on a model with a PTCR installed YELLOW OUTDOOR L1 l ORANGE q h CCH OPTIONAL COMPRESSOR CONTACTS CAPACITOR YELLOW ASCT SEE NOTE 7 OUTDOOR FAN MOTOR YELLOW BLACK GROUNDING 24VOLT FIELD l i L
12. EM YES YES zZ O Electrical connections tight zZ O Line voltage polarity correct Rated Voltage L1 L2 Volts L1 L3 Volts L2 L3 Volts Avg Volts Max deviation of voltage from avg volts Volt imbalance Blower Motor HP Sheave Setting YES YES REPLACEMENT PARTS Replacement parts are available through all Nordyne distributors Please have the complete model and serial number of the unit when ordering replacement parts Has the thermostat been calibrated Is the thermostat level Is the heat anticipator setting correct If Applicable Electrical e Capacitors e Temperature Limit Switches e Compressors e Thermostats e Contactors Time Delay Relays Pressure Switches e Transformers e Relays Motors e Blower Motor e Fan Motor Components Blower Assembly Fan Grille e Cabinet Panels Filter Driers Expansion Valves NORDYNE COMPLETE COMFORT GENUINE VALUE Specifications amp illustrations subject to change without notice or incurring obligations 09 14 Bg 7096660 NEW
13. SPLIT SYSTEM AIR CONDITIONER 14 SEER SINGLE PHASE MODELS INSTALLATION INSTRUCTIONS S4BE 018KB 024KB 030KB 036KB 1 5 2 2 5 amp 3 TON SERIES IMPORTANT ATTENTION INSTALLERS It is your responsibility to know this product better than your customer This includes being able to install the product according to strict safety guidelines and instructing the customer on howto operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installation service personnel for this type of equipment Please read all instructions carefully before starting the installation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY amp KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION AIR CONDITIONER INSTALLATION General Information Before You Install this Unit Locating the Air Conditioner Packaging Removal Ground Level Roof Mount
14. e finalizing the full system refrigerant charge e S4BE outdoor units with non AHRI listed indoor coils are not recommended Deviations from rated airflows or non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation Referto Table 3 page 10 Table 4 page 10 Table 5 page 11 or Table 6 page 11 to determine the ideal amount of sub cooling for a given liquid pressure The refrigerant charge can be checked and adjusted through the service ports provided external to the outdoor unit Use only gage line sets which have a Schrader depression device present to actuate the valve A high pressure switch is factory installed and located in the liquid line internal to the outdoor unit The switch is designed to protect the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the liquid pressure rises above 575 psig then the switch will open and de energize the outdoor unit The switch will close again once the liquid pressure decreases to 460 psig Please note that the switch interrupts the thermostat inputs to the unit Thus when the switch opens and then closes there may be a 5 minute short cycling delay before the outdoor unit will energize A low pressure switch select models only is factory installed and located in the suction line internal to the outdoor unit The switch i
15. e the following Inspect and clean or replace air filters at the beginning of each heating and cooling season or more frequently if required Inspect the condensate drain and outdoor coil at the beginning of each cooling season Remove any debris Clean the outdoor coil and louvers as necessary using a mild detergent and water Rinse thoroughly with water Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary A CAUTION The unit should never be operated without a filter inthe return air system Replace disposable filters with the same type and size e e e Donotattemptto add additional oil to motors unequipped with oil tubes The compressor is hermetically sealed at the factory and does not require lubrication o REFRIGERANT CHARGING Ax WARNING S4BE Split System Air Conditioners are shipped charged with R410A refrigerant and ready for installation If repairs make it necessary for evacuation and charging it should only be attempted by qualified trained personnel thoroughly familiar with this equipment Under no circumstances should the owner attempt to install and or service this equipment Failure to comply with this warning could resultin property damage personal injury or death After refrigerant line connections are completed it is required that you leak check and evacuate the indoor section and all line connections using proper methods befor
16. er must be installed in strict accordance with the manufacturer s installation instructions Optional equipment such as liquid line solenoid valves low ambient etc shouldbe installed in strict accordance with the manufacturer s installation instructions e e e e e ELECTRICAL WIRING Ax WARNING ELECTRICAL SHOCK OR FIRE HAZARD To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Label all wires prior to disconnection when servicing the unit Wiring errors can cause improper and dangerous operation All electrical connections must be in compliance with all applicable local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes Pre Electrical Checklist y Verify that the voltage frequency and phase of the supply source match the specifications on the unit rating plate y Verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment Refer to the unit wiring label for proper voltage wiring y Verify factory wiring is in accordance with the unit wiring diagram See Figure 6 page 12 and Figure 7 page 13
17. frigerant tubing Refer to the indoor unit s installation instructions for installation details All units are securely packed at the time of shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site Verify coil fins are straight If necessary comb fins to remove flattened or bent fins Claims for damage apparent or concealed should be filed immediately with the carrier y Please consult your dealer for maintenance information and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ventilated areas and areas subject to accumulation of debris should be avoided Consideration should be given to availability of electric power service access noise and shade Packaging Removal NOTE To prevent damage to the tubing connections carefully remove the carton and user s manual from the equipment Discard the shipping carton Ground Level Ground level installations must be located according to local building codes or ordinances and these requirements e Clearances must be in accordance with those sho
18. injury or property damage A WARNING Shut off all electrical power to the unit before performing any maintenance or service on the system Failure to comply may result in personal injury or death A WARNING Unless noted otherwise in these instructions only factory authorized parts or accessory kits may be used with this product Improper installation service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage A WARNING S4BE Split System Air Conditioners are shipped charged with R410A refrigerant and ready for installation If repairs make it necessary for evacuation and charging it should only be attempted by qualified trained personnel thoroughly familiar with this equipment Under no circumstances should the owner attempt to install and or service this equipment Failure to comply with this warning could resultin property damage personal injury or death A CAUTION This unit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit A WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious
19. itions and are most influenced by the outdoor ambient temperature outdoor fan operation and the unit operating voltage Before using these tables make sure the unit is in a stable operating mode The ideal system sub cooling can vary over the range of operation Reference the tables to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit efficiency EER or rated Coefficient of Performance COP in heating mode Toinspecta systems operation using quality instruments match the measured liquid temperature to the units table The measured liquid pressure reading should be within 3 of the table value for most installations For systems that are operating with more than a 5 deviation inspect the unit for the proper voltage and phase balance and the refrigeration system for leaks Units that are operating at less then 95 of the nominal voltage or with a 2 phase imbalance may see a more significant deviation than the amount stated above DO NOT use the charts in systems that have a fan cycling under low ambient control Refer to the low ambient kit instructions for more information If applicable D 2 5 a 0 e a 3 5 3 Liquid Pressure psig S4BE 018KB Charging Chart Cooling Remove refrigerant when above curve Add refrigerant when below curve 90 95 100 105 110 115 120 125 130 Liquid Temperature F Figure 2
20. s designed to protect the compressor from a loss of charge Under normal conditions the switch is closed If the suction pressure falls below 5 psig then the switch will open and de energize the outdoor unit The switch will close again once the suction pressure increases above 20 psig Please note that the switch interrupts the thermostat inputs to the unit When the switch opens and then closes there will be a 5 minute short cycling delay before the outdoor unit will energize Charging the Unit in AC mode At outdoor temperatures above 55 F for optimized sub cooling of 10 F 12 F 1 With the system operating at steady state measure the liquid refrigerant pressure in psig at the outdoor unit service valve 2 Measure the liquid refrigerant temperature in Fahrenheit at the service valve 3 Determine the required liquid refrigerant pressure from Table 3 page 10 Table 4 page 10 Table 5 page 11 or Table 6 page 11 e f the pressure measured in Step 1 is greater than the required liquid refrigerant pressure determined in Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged Charging
21. the equipment Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure AIR CONDITIONER INSTALLATION General Information The S4BE series air conditioner is designed only for outdoor rooftop or ground level installations This unit has been tested for capacity and efficiency in accordance with AHRI Standards and will provide many years of safe and dependable comfort providing it is properly installed and maintained Abuse improper use and or improper maintenance can shorten the life of the appliance and create unsafe hazards Toachieve optimum performance and minimize equipment failure it is recommended that periodic maintenance be performed on this unit The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools Before You Install this Unit V The cooling load of the area to be conditioned must be calculated and a system ofthe proper capacity selected It is recommended that the area to be conditioned be completely insulated and vapor sealed V Check the electrical supply and verify the power supply is adequate for unitoperation The system mustbe wired and provided with circuit protection in accordance with local building codes Ifthere is any question concerning the power supply contact the local power company V The indoor section air handler furnace etc should be installed before routing the re
22. the unit rating plate Connect the line voltage leads to the terminals on the contactor inside the control compartment Use only copper wire for the line voltage power supply to this unit as listed in Table 1 Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Use of rain tight conduit is recommended 208 230 Volt units are shipped from the factory wired for 230 volt operation For 208V operation remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided with the equipment e Grounding A WARNING The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur Do not use gas piping as an electrical ground This unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit COPPER WIRE SIZE AWG 1 VOLTAGE DROP SUPPLY WIRE LENGTH FEET SUPPLY CIRCUIT AMPACITY 150 100 o N iN N O O a a RIOD NjojOo O a a ajo j o 00
23. ts together it is recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing If precise forming of refrigerant lines is required a copper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation Tubing should be kept clean of foreign debris during installation Every effort should be made by the installer to ensure thatthe field installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity The maximum recommended interconnecting refrigerant line lengths is 75 ft and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 ft NOTE For installations exceeding these conditions please refer to the Application Guidelines for Refrigerant Lines Addendum A filter dryer is provided with the unit and must be installed in the liquid line of the system If the installation replaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dry
24. wn in Figure 1 e A suitable mounting pad Figure 1 must be provided and separate from the building foundation The pad must be level and strong enough to support the weight of the unit The slab height must be a minimum of 2 5 cm above grade and with adequate drainage Roof Mount The method of mounting should be designed so that it does not overload roof structures or transmit noise to the interior of the structure The roof must be structurally capable of handling the weight of the unit e Full perimeter support is required under the unit Support must be made of weather resistant materials and installed prior to unit installation e The support must be built to raise the unit 6 above the roof 6 from Building or Structure 24 for Service Access DONOT NS OBSTRUCT TOP OF UNIT NOTE Units require full perimeter clearances Installer must maintain 18 between two units or 12 between single unit and structure y2 Mounting Pad XA Figure 1 Clearance Requirements Connecting Refrigerant Tubing Between the Indoor amp Outdoor Unit A CAUTION When servicing cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants After outdoor and indoor unit placement has been determined route refrigerant tubing between the equipmentin accordance with sound installation practices When connecting refrigerant linese
25. y unusual noises If unusual sounds occur determine the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allow the system to operate for several minutes and then set the temperature selector above room temperature Verify the fan and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to the ON position System Heating optional 1 Set the thermostat s system mode to HEAT and the temperature mode above room temperature 2 Verify the optional heating equipment furnace or electric heat and indoor blower energize Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature Listen for any unusual noises If unusual sounds occur determine the source of the noise and correct as necessary AIR CONDITIONER MAINTENANCE A WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Proper maintenance is important to achieve optimum performance from the air conditioner The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools If you do not possess these skills contact your dealer for maintenance Consult your local dealer about the availability of maintenance contracts Routine maintenance should includ

Download Pdf Manuals

image

Related Search

Related Contents

Piranha ES 12k User Manual  User manual  Excitador La vaca Manual de usuario  Manual de reparación EXCLUSIVAMENTE para personal técnico  OCZ Technology Fatal1ty 1000W  2015-Present BoXXer Team  ASUS CP220 User's Manual  Murray 11052x4NC User's Manual  Cardio 60 のみ - BrytonSport  Synology Cube Station Series CS407 CS407e  

Copyright © All rights reserved.
Failed to retrieve file