Home
        Rheem Performance XP75T06PV76U0 Instructions / Assembly
         Contents
1.               Figure 1    There are vent piping configurations  when  combined with certain environmental conditions that  can produce enough condensate to require collection  and disposal  When a slope away from the water  heater cannot be achieved and condensate handling  is required in a horizontal vent system  the vent pipe  should be sloped toward the water heater as shown  in Figure 2        Slope Toward    Drain Port  vA yo      ie Drain Ul       D                         Figure 2    e Remove drain port cap     e Connect flexible condensate drain tube to the  blower drain port     e Loop the drain tube so that it has a circular trap   See Figure 3     e     Secure the top and bottom of the loop with wire  ties or plastic zip ties as shown     e DONOT restrict any portion of the circular drain  tube     e Loop must be smooth and not collapse the tube     e Fill circular drain tube with water to make sure  combustion gases cannot vent into the room     e Condensation collected must be discharged per  local codes     e DO NOT drain over public way or walkway     e Refer to local codes for any condensate  requirements             Water    Filled  From Drain  Port  Wire or Zip  Ties  To Drain  f C  Figure 3    If the venting system is vertical and condensation  handling is required  then the blower coupling  drain port and tube must be used as described  previously  Any horizontal portion of the vent pipe  must slope toward the water heater at a minimum  of 1 8 inch per foo
2.        gt     To gas supply              gt    Union    Sediment trap          Cap  Gas Control  thermostat  Jacket door    Flammable Vapor Sensor       Auxiliary drain pan    Drain Pan Pipe  to suitable drain     75 Gallon Shown                       pressure increase in the water heater and  system piping  This rapid pressure increase can  quickly reach the safety setting of the relief  valve  causing it to operate during each heating  cycle  Thermal expansion  and the resulting  rapid  and repeated expansion and contraction  of components in the water heater and piping  system can cause premature failure of the relief  valve  and possibly the heater itself  Replacing  the relief valve will not correct the problem     The suggested method of controlling thermal  expansion is to install an expansion tank in the  cold water line between the water heater and  the check valve  see illustration below   The  expansion tank is designed with an air cushion  built in that compresses as the system pressure  increases  thereby relieving the over pressure  condition and eliminating the repeated operation  of the relief valve  Other methods of controlling  thermal expansion are also available  Contact  your installing contractor  water supplier or  plumbing inspector for additional information  regarding this subject     for servicing if necessary  The HOT and COLD  water connections are clearly marked on all  water heaters  Install a shut off valve in the cold  water line near the wate
3.       The control will verify the blower vacuum  switch has closed  ensuring that the blower  is functioning properly and that the venting  system is not blocked     The control will then proceed through a  sequence of self diagnostics before initiating  a trial for ignition     During the trial for ignition  the hot surface  ignitor will warm up     Once the hot surface ignitor warms up  the  main gas valve will open allowing gas to  flow to the main burner     Once the main burner ignites  the control  will verify that the burner flame is present  through the flame sense circuit  The hot  surface ignitor will then turn off     The main burner will remain lit throughout  the heat cycle until the water temperature  setting is reached     Once the water temperature setting is  reached  the control will close the main gas  valve which will extinguish the main burner  flames        The blower motor will stay energized for   an additional 30 seconds after the control  verifies that the burner flame is extinguished  in order to clear combustion gases from the  water heater     After the post purge sequence  the control  will de energize the blower motor and go  into a stand by mode awaiting the next call  for heat     This water heater is equipped with a  flammable vapor sensor that is monitored  continuously by the electronic control in all  modes of operation     In the event that flammable vapors are  detected  the control will automatically shut  down the water heater and prev
4.    31  Extended Shut Down        32  Troubleshooting Tips  Before You Call   KONS CRVIC EAT 33 34    Gas Valve LED Codes       35    Customer Service  Parsist a EETA  36  If You Need Service         40    FOR YOUR RECORDS  Write the model and serial numbers here            You can find them on a label on the appliance           Staple sales slip or cancelled check here     Proof of the original purchase date is needed to obtain service under  the warranty     READ THIS MANUAL    Inside you will find many helpful hints on how to use and maintain    your water heater properly  A little preventive care on your part can  save you time and money over the life of your water heater     You   ll find many answers to common problems in the  Troubleshooting Guide  If you review the chart of Troubleshooting  Tips first  you may not need to call for service     READ THE SAFETY INFORMATION    Your safety and the safety of others are very important  There    are many important safety messages in this manual and on your  appliance  Always read and obey all safety messages     as an indication of Important Safety Information   This symbol alerts you to potential hazards that can  kill or hurt you and others     h This is the safety alert symbol  Recognize this symbol    All safety messages will follow the safety alert symbol and  either the word    DANGER        WARNING        CAUTION    or     NOTICE        These words mean     A DANGER An imminently hazardous situation  that will result in
5.    M i H c ECO activated  1  Replace gas control valve    V ABC   One of the temperature adjust but  1  Press and release each of the buttons once     O     OO   tons stuck closed  2  Replace gas control valve    V ABC   Water temperature sensor is either open 1  Check that all wiring is correct and secure     0     O   orshort circuited  2  Replace gas control valve    VABC 1  Check for correct wiring to FV sensor    0 0   O       Unit shuts down  2  Check for open circuits to FV sensor    3  Replace FV sensor    VABC 1  FV sensor detected presence of flammable vapors      000 O       Unit shuts down and in lockout  2  Contact a service agency           CAUTION  Label all wires prior to disconnection when servicing controls  Wiring errors can cause improper and  dangerous operation  VERIFY PROPER OPERATION AFTER SERVICING        CAUTION  For your safety DO NOT attempt repair of gas piping  remote control  burners  vent system or other    safety devices  Refer repairs to qualified service personnel        Replacement Parts    For 75 gallon models using Natural or LP gas     Instructions For Placing a Parts Order    All parts orders should include     4  The model and serial number of the  water heater from the rating plate     2  Specify type of gas  natural or LP   as marked on the rating plate     3  Part description  as noted below  and  number of parts desired     4 Refer to page 36     Blower Exhaust  Coupling              Blower  Assembly        Heat Trap Nipple     Hea
6.    Maximum unsupported length is  recommended to be no more than 4 ft     It is very important that the first hanger  be located on the horizontal length  immediately near to the first 90 degree  elbow from the vertical rise of vent pipe  connected to the appliance     The support method used should isolate  the vent pipes from floor joists or other  structural members to help prevent the  transmission of noise and vibration     DO NOT support  pin or otherwise secure  the vent system in a way that restricts the  normal thermal expansion and contraction  of the chosen venting material     If the appliance is being installed as a  replacement for an existing power vent  appliance  a thorough inspection of the  existing vent systems must be performed  prior to any installation work     1  Verify that the correct materials as  specified in this manual have been used  and the minimum or maximum vent  lengths and terminal location as detailed in  this manual are met     2  Carefully inspect the entire vent system  for any signs of cracks or fractures   particularly at the joints between elbows  or other fittings and the straight length of  vent pipe     3  Check the vent for signs of sagging or  other stresses in the joints as a result of  misalignment of any components in the  system     4  If any of the conditions above   are found  they must be corrected in  accordance with the instructions in this  manual before completing the installation  and putting the appliance into servi
7.    port for vent     4  Four  4  ft  from any gable  dormer or other roof structure  with building interior access  i e   vent  window  etc       5  Ten  10  ft  from any forced air inlet to the building  Any  fresh or make up air inlet such as a dryer or furnace area is  considered to be a forced air inlet     6  Maintain a minimum distance from the vent terminal of  not less than 12 in  above grade or average snowfall  which   ever is greater     Read these instructions thoroughly and make sure you un   derstand all steps and procedures before proceeding with the  installation     Determine the locations for the vent terminal then make a  hole through the roof and interior ceiling s  to accommodate  the vent pipe     Assemble the vent pipe assembly     Install the vent system and attach it to the blower exhaust  coupling on the water heater   s blower assembly     Optional      2  x 2  Sheet Metal Shield on  Brick or Masonry Walls        Terminals with 1 2  Mesh  Protective Screens Inside and  Termination Restrictors Inside     Note  Termination Restrictors         Condensate used on 75 Gallon  Management Drain models ONLY   Port     Rear of termination  4  from outside  wall to back of        elbow   Inside of Outside of  Building Building        See Condensate Management Sec   tion for additional information about  optional piping     Horizontal lengths of the vent system must slope towards the  water heater a minimum of 1 8 in  per foot  10 mm per m      e Support vertic
8.   61 cm  from the  center line of the terminal    E   Clearance to unventilated soft  F   Clearance to outside corner  G   Clearance to inside comer    H   Clearance to each side of centerline    extended above meter regulator assembly    J   Clearance to nonmechanical air supply in    4 ft   1 2 m  below or to side of opening  1 ft  30 cm  above  let to building or the combustion air inlet   opening  to any other appliance  K   Clearance to a mechanical air supply 3 ft   91 cm  above if within 10 ft   3 m  horizontally  inlet    L   Clearance above paved sidewalk or    paved driveway located on public prop   erty  M   Clearance under veranda  porch  deck     or balcony    1 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code     For clearances not specified in ANSI Z223 1  NFPA 54 the following statement shall be included     Clearance in accordance with local installation codes and the requirements of the gas supplier and the manfacture s installation  instructions        15    Installing the water heater       NOTICE  All pipe  fittings  solvent cement  primers and procedures must conform to American National  Standards Institute and American Society for Testing and Materials  ANSI ASTM  standards     Additional Vent Location Considerations               ae aN S    _    Rising moisture will  collect under eaves                                         esl al                         If soffit vent is too   close  block off and  install new vent at 6    
9.   Use only standard  and or long bend elbows  See examples     Additional PVC Fittings Considerations    Do Not Use    Short Sweep 90   Elbow    Standard 90   Elbow    Good Best    Long Sweep 90   Elbow    13    Installing the water heater    Vent Pipe Connections    3 in  eet   7 6 cm   lt     pipe diameter                                  g   Ha  5  lt  4in   f  10 2 cm                                pipe diameter                                          4   Min  2 1 2 in   Figure 1    6 4cm to    6 in   15 2 cm     A Max  Spacing                                                                               Figure 2    Table 1  From Sea level through 2000 ft   609m  Above Sea level    Vent System   Min  Allowed Equivalent Vent   Max  Allowed Equivalent Vent  Model Diameter Lengths  Each Pipe Run  Lengths  Each Pipe Run  Vent System    Termination s     ae 50   Elbow  allon  90   Elbow    From 2000 ft   609m  Above Sea Level through 7700 ft   2 347m  Above Sea Level    se Gallen       14    Vent Terminal Clearances   US    Vent Terminal Q Air Supply Inlet NY Area Where Terminal Is Not Permitted  US Installations     A   Clearance above grade  veranda  porch 12 in   30 cm   deck or balcony    B   Clearance to window or door that may be   4 ft   1 2 m  below or to side of opening  1 ft  300 m  above  opened opening    C   Clearance to permanently closed window    D   Vertical clearance to ventilated soffit    located above the terminal within a hori   zontal distance of 2 feet
10.   water heater can be installed at elevation  up to 2000 feet without any change or  modification     The water heater must be isolated from  the gas supply piping system by closing  its individual manual gas shutoff valve  during any pressure testing of the gas  supply at test pressures equal to or less  than 1 2 psi  3 5 kPa      For installation between 2000 and 7700  feet  refer to the Venting Information tables  on page 14 for maximum equivalent vent  lengths     Installations above 7700 feet are not  authorized     Contact the local gas supplier for more  information     11    Installing the water heater    The water heater must be installed with the factory installed blower assembly in place     ADANGER  Failure to  install the blower assembly  and properly vent the water  heater to the outdoors as  outlined in the Venting section  of this manual will result in  unsafe operation of the water  heater causing bodily injury   explosion  fire or death     To avoid the risk of fire   explosion  or asphyxiation  from carbon monoxide   NEVER operate the water  heater unless it is properly  vented and has adequate air  supply for proper operation  as outlined in the Venting  section of this manual     The vent pipe must overlap   a minimum of      in  on each  connection  It is important  that the vent pipe engages  fully into any pipe fitting and  be kept in that position until  the adhesive has fully cured   DO NOT drill or punch holes  in the plastic pipe or fittings     NO
11.  2  Check that the water heater is securely connected  to earth ground   V ABC   Pressure switch remained closed 1  Pressure switch wiring is incorrect    oe000 Roe after the call 2  Replace pressure switch   YV ABC   Pressure switch remained open lon  1  Pressure switch wiring is incorrect   000000 gor than 5 seconds after the combus    2  Pressure switch tubing is not connected correctly   1on blower was energized  3  Air intake or exhaust obstructed   V ABC   Error in the hot surface ignitor cir  1  Check that all wiring is correct and secure    0 0 e6   cuit  2  Replace hot surface ignitor   V ABC   System in lockout  1  Gas supply is off or too low to operate   cone eo 2  Hot surface ignitor not positioned  correctly   3  Low voltage to the water heater   4  Electric polarity to unit is incorrect   test and cor   rect   5  Combustion shut off device tripped  contact ser   vice agency   VABC i i i 1  Turn power to the water heater off for 10 seconds  eo0o0o00 0   a in the gas valve driver cir  and then back on   2  Replace gas control valve   VABC 1  Turn power to the water heater off for 10 seconds    0            Problem with the internal circuit  and then back on   2  Replace gas control valve   VABC 1  Turn power to the water heater off for 10 seconds                Problem with the internal circuit  and then back on     2  Replace gas control valve                             V ABC   Flame signal sensed out of proper 1  Replace gas control valve    000  O0   sequence
12.  DANGER  Hotter  water increases the  potential for Hot Water  SCALDS     Display Burns on Adult Skin  VABC    Temperature Setting                               WARM   approx  70  F  21  C  e00000    e  Y   approx  120  F  49  C  oo0oeo0oo0oo0 More than 5 minutes  A   approx  130  F  54  C  O00  00 About 30 seconds  B   approx  140  F  60  C  OoO000eOo Less than 5 seconds  C   approx  150  F  66  C  O0000 6 About 1 1 2 seconds  C Flashing   approx  160  F  71  C  OCO0000  About 1 2 seconds          IMPORTANT SAFETY INFORMATION  READ ALL INSTRUCTIONS BEFORE USING    ADANGER     LIQUEFIED PETROLEUM  LP     PROPANE OR BUTANE   AND NATURAL GAS MODELS    LP and Natural gas have an odorant added to aid in detecting a gas leak  Some people  may not physically be able to smell or recognize this odorant  If you are unsure or  unfamiliar with the smell of LP or natural gas  ask the gas supplier  Other conditions   such as    odorant fade     which causes the odorant to diminish in intensity  can also hide or       camouflage a gas leak     Water heaters utilizing LP gas are  different from natural gas models  A  natural gas water heater will not function  safely on LP gas and vice versa     No attempt should ever be made to  convert the water heater from natural  gas to LP gas  To avoid possible  equipment damage  personal injury or  fire  do not connect the water heater to a  fuel type not in accordance with the unit  data plate  LP for LP units  Natural gas  for natural gas units  Th
13.  Do not  smoke  Avoid skin or eye  contact  Observe all cautions  and warnings on material  containers     ACAUTION   For proper installation     DO NOT use solvent cement  that has become curdled   lumpy or thickened     DO NOT thin solvent  cement  Observe shelf  precautions printed on the  containers     For applications below 32  F  use only low temperature  type solvent cement     Appropriate solvent and  cleaner must be used for the  type of vent pipe used  PVC   CPVC or ABS      Cementing Joints    All joints in the vent piping must be  properly sealed and the following  materials are recommended     PVC materials should use ASTM D2564  grade cement     CPVC materials should use ASTM F493  grade cement     ABS materials should use ASTM D2235  grade cement     Cleaner Primer and Medium Body  Solvent Cement     4  Cut pipe end square  remove jagged  edges and burrs  Chamfer end of pipe   then clean fitting socket and pipe joint  area of all dirt  grease or moisture     2 After checking pipe and socket for  proper fit  wipe socket and pipe with  cleaner primer  Apply a liberal coat of  primer to inside surface of socket and  outside of pipe  Do not allow primer  to dry before applying cement     3  Apply a thin coat of cement evenly in  the socket  Quickly apply a heavy  coat of cement to the pipe end and  insert pipe into fitting with a slight  twisting motion until it bottoms out     NOTICE  Cement must be fluid  if not   recoat     4  Hold the pipe fitting for 30 secon
14.  another location                         Inside  corner                         Caulk 6    caulk zone           6    caulk  zone or to edge of window  etc   starting within 6 ft     i Q H     y 2    sq  sheet metal plate on  brick or masonary surface is recommended     Caulk                                                                                        WARNING  Moisture in the flue gas will condense as it  leaves the vent terminal  In cold weather this condensate can  freeze on the exterior wall  under the eaves and on  surrounding objects  Some discoloration to the exterior of the  building is to be expected  However  improper location or  installation can result in severe damage to the structure or  exterior finish of the building    Horizontal Vent Terminal Installation    2  x 2  Sheet  Metal Shield on    gs 1 So 4 Brick or Masonry  sasad Walls      16   Vent Terminal with   een Mesh Protective   From       Water Heater       Screen Inside  qn    4  10 cm   lt    __        Q8     TIA  SOG a Sod       SEG  z    LUNAS    12     Pipe Coupling 680 cm     Outside of Building Wall    Read these instructions thoroughly and make sure you  understand all steps and procedures before proceeding with the  installation     Determine the locations for the vent terminal then make a hole  through the exterior wall to accommodate the pipe     Insert lengths of vent pipe through the wall as shown     Allow sufficient length of pipe to extend beyond the exterior  wall of the buildi
15.  can  cause a banging noise heard in a water  pipe  Strategically located risers in the  water pipe system or water hammer  arresting devices can be used to minimize  the problem     The anode rod should be removed from  the water heater   s tank annually for  inspection and replaced when more than 6  in  of core wire is exposed at either end of  the rod     Make sure the cold water supply is turned  off before removing anode rod     This water heater incorporates a  combustion shut off device that shuts   the operation of the water heater down   if undesirable combustion conditions  occur  such as the presence of flammable  vapors or blockage of the combustion air  inlet openings  Please contact a Qualified  Service Technician if this occurs     ADANGER   Combustible materials   such as clothing  cleaning  materials  or flammable  liquids  etc   must not be  placed against or next to  the water heater           Proper burner flame pattern       Housekeeping    Visually inspect the hot surface  ignitor     To ensure sufficient ventilation  and combustion air supply  proper  clearances must be maintained     When installed in a closet  DO NOT  block or obstruct any of the combustion  air inlet openings located around the  perimeter of the water heater  A minimum  of 1 in  is required between these  combustion air inlet openings and any  obstruction     Venting System Inspection    Inspect the vent system  Make certain  that all joints are secure and the vent  system supports a
16.  death or serious  injury    A WARNING A potentially hazardous situation that  could result in death or serious injury  and or damage to property     A CAUTION A potentially hazardous situation that  may result in minor or moderate  injury     Notice  Attention is called to observe a  specified procedure or maintain  a specific condition     IMPORTANT SAFETY INFORMATION  READ ALL INSTRUCTIONS BEFORE USING    Be sure to read and understand the entire Use and Care Manual before attempting to install or  operate this water heater  It may save you time and money  Pay particular attention to the Safety  Instructions  Failure to follow these warnings could result in serious bodily injury or death  Should  you have problems understanding the instructions in this manual  or have any questions  STOP  and  get help from a qualified service technician  or the local gas utility        NOTICE  This water heater is equipped with a flammable vapor sensor that will automatically  shut down the water heater in the presence of gasoline vapors and some other flammable vapors   If the flammable vapor sensor shuts down the water heater  contact a qualified service technician   Clear any hazardous materials and ventilate the area around the water heater  Do not turn off the  appliance or adjust the ON OFF switch in any way  DO NOT tamper with the flammable vapor  sensor  DO NOT submerse the flammable vapor sensor in water  DO NOT allow the flammable  vapor sensor to come into contact with any subs
17.  inlet  water line  Check with your local water utility  company  It may have been installed in the cold  water line as a separate back flow preventer    or it may be part of a pressure reducing valve   water meter or water softener  A check valve  located in the cold water inlet line can cause  what is referred to as a    closed water system      A cold water inlet line with no check valve or  back flow prevention device is referred to as an     open    water system     As water is heated  it expands in volume and  creates an increase in the pressure within the  water system  This action is referred to as     thermal expansion     In an    open    water  system  expanding water which exceeds the  capacity of the water heater flows back into  the city main where the pressure is easily  dissipated     A    closed water system     however  prevents  the expanding water from flowing back into the  main supply line  and the result of    thermal  expansion    can create a rapid and dangerous    Water Supply Connections    Refer to the illustration below for suggested  typical installation  The installation of unions  or flexible copper connectors is recommended  on the hot and cold water connections so that  the water heater may be easily disconnected    Typical Installation    Vent connector    Union  Heat trap See  6    minimum CeO  Hot water outlet to  fixtures Q oF     CS e223    Water Heater Jacket QB    Temperature and  pressure relief valve    Manual gas shut off valve    _
18.  on water heater jacket        Not enough combustion or  ventilation air supplied to  the water heater location     Unable to light  the main burner    Air in gas line     Proper operation of the water heater requires air for  combustion and ventilation  See the Combustion and  Ventilation Air information in the    Installing The  Water Heater    section of this manual     Contact a qualified service technician to purge the air  from the gas line        Blocked Exhaust     Contact a qualified service technician to evaluate vent  pipe for blockage        Pressure Switch     Make sure the pressure switch hose is not  kinked         Wire Connections not fully  secured     Contact a qualified service technician to confirm wire  connections        Combustion Shut off Device  tripped     Combustion shut off device should be inspected by a  qualified service technician        Gas Control Problem     Main burner does not  stay lit    Gas Controls  Thermostat   s   single use gas shut off device  has opened     Contact a qualified service technician     The gas control  thermostat  should be replaced by a  qualified service technician        Combustion Shutoff Device  Tripped     The combustion shutoff device should be inspected  by a qualified service technician        CAUTION  Label all wires prior to disconnection when servicing controls  Wiring errors can cause improper and dangerous  operation  VERIFY PROPER OPERATION AFTER SERVICING        CAUTION  For your safety DO NOT attempt
19.  repair of gas piping  gas control  thermostat   burners  vent system or other    safety devices  Refer repairs to qualified service personnel     33    Before You Call For Service       Troubleshooting Tips    Save time and money  Review the charts on the following pages first and you may not need to call for    service     This water heater incorporates a combustion shut off device that shuts the operation of the water heater  down if undesirable combustion conditions occur  such as the presence of flammable vapors or blockage of  the combustion air inlet openings  Please contact a Qualified Service Technician if this occurs     Problem    Rumbling noise    Relief valve  producing popping  noise or draining    Not enough or  no hot water    Water is too hot    Possible Causes    Scale and sediment    Pressure build up  caused by thermal  expansion to a  closed system     Water usage may have  exceeded the capacity  of the water heater     Low gas pressure     What To Do    Drain the water heater to remove scale and sediment  from the tank  Refer to the top of page 30     This is an unacceptable condition and must be  corrected  Contact the water supplier or plumbing  contractor on how to correct this  Do not plug the  relief valve outlet     Wait for the water heater to recover after an  abnormal demand     Check gas supply pressure and manifold pressure        The gas control  thermostat   may be set too low     See the    Water Temperature Setting    of The Water  Heater 
20.  the button  will not continue to lower or raise   the temperature setting  The button  must be pressed and released for each  temperature change desired     A condition known as    stacking    or     layering    can occur when a series of  short and frequent hot water draws are  taken     The hottest temperature water will be at    Time Temperature Relationship in Scalds                      Temperature Setting    the top of the tank  closest to the outlet  pipe delivering hot water to the home     Stacking can cause this top layer of water  to be hotter than the water toward the  bottom of the tank near the gas control   thermostat   Therefore  always remember  to test the water temperature with your  hand before use and remember that hotter  water increases the risk of scald injury     Also  always supervise young children or  others who are incapacitated     The gas control  thermostat  is constructed  with a built in safety shut off device  designed to shut off the gas supply to the  burner if the main burner is extinguished  for any reason     The gas control  thermostat  is also  equipped with a single use gas shut off  device that will shut off the gas supply   to the burner if the water heater exceeds  normal operating temperatures  Refer to  the Before You Call For Service section of  this manual  or contact your dealer     A WARNING  Should overheating  occur or the gas supply fail to shut off   turn off the manual gas shutoff valve to  the appliance     If the wat
21.  venting instructions  and or all venting design instructions shall  remain with the appliance or equipment at the completion of the installation   3  After NFPA 54 section 10 10 4 2 add a new section 10 10 4 3 as follows    When more than four gas appliances are to be vented through a common gas vent  or common horizontal vent manifold  a plan of the proposed vent installation   shall be submitted to the Inspector and the serving gas supplier for review and  approval     
22.  water return line  from heating unit  not  supplied with water  heater     Gas Fired  Water Heater          Combustion Air Inlet  Openings    6    Air Gap    PA cae   lt  O        y 3 4  Shut Off Valve  Typ      2 Gallon Thermal  Expansion Tank  if   required not supplied  with water heater     3 4  HWS  amp  HWR  to Heating Coil      not supplied with    Vacuum Relief Valve   Not Supplied     Pressure Gauge  3 4  Check Valve with 1 8  Hole  3 4  Shut Off Valve  Typ       lt  3 4  cold water supply  IG  a          AT   gt     ot water  to space heater    LI A  Hot water coil    All bronze pump     internal in pump     Akt bleed valve     1       Check valve          Water Sample Tap     To HVAC Unit   FAN  ON    Air Handler    ag       X        Electronically controlled pump timer   Activates every 6 hours for 60 seconds   Wire to bronze pump     If required  install per local codes  and valve manufacturer   s    instructions     25    Lighting the water heater       Before operating this water heater  be sure to read and follow the instructions on the label pictured  below and all other labels on the water heater  as well as the warnings printed in this manual  Failure  to do so can result in unsafe operation of the water heater resulting in property damage  personal  injury  or death  Should you have any problems reading or following the instructions in this manual   STOP  and get help from a qualified person     FOR YOUR SAFETY READ BEFORE OPERATING       WARNING  If you 
23. Combination Potable Space Heating Installation    Nominal 3 4  size mixing or tempering valve     refer to warning above   Follow mixing or    tempering valve manufacturer   s instructions for    installation of the valve     Spring loaded check valve in heating unit  hot water supply line and cold water return  line  not supplied with water heater     NOTE  This check valve is incorporated  in some heating units  Refer to the  installation instructions supplied with  specific heating unit to determine if it is  required     See diagrams above for proper  pipe application for vertical  or horizontal supply lines     Isolation valve in hot water supply line  to heating unit  not supplied with water  heater     Temperature and Pressure Relief  Valve  tie to location approved by  local code    Gas line to water heater           valve discharge line    Gas Control  Thermostat     Temperature and pressure relief    Lg    Water Heater drain pan installed  in accordance with the Local and  State Code    Water Heater to be in accordance  am the Local and State Energy  ode    All water piping shall be insulated in  eal with Local and State Energy  ode           Minimum of 2  developed length of  3 4  pipe     3 4  Tempered  domestic hot water  supply to house                     6    Min   amp   Y a     Dr a A      3 4  Shut     Off Valve   Typ    Gas Direct Vent discharge  must comply with Local  and State Codes       Air vent    Drain valve    water heater   Isolation valve in  cold
24. NIC  CONTROL    6 PINCONNECTOR    BK  Oz    L2    IGNITER AND  FLAME PROBE       L1    ON OFF  SWITCH    TEMPERATURE PRESSURE  SWITCH SWITCH       BK   BLACK  BL   BLUE   G   GREEN  R   RED  W   WHITE  Y  YELLOW    120 V 60 Hz Less than 5 amps       CAUTION  Label all wires prior to disconnection when servicing controls  Wiring errors can cause improper  and dangerous operation  VERIFY PROPER OPERATION AFTER SERVICING     21    Installing the water heater       AWARNING  If local  codes require external  application of insulation  blanket kits the  manufacturer   s  instructions included  with the kit must be  carefully followed     NOTICE  If pipe  insulation is used   ensure that the thickness  does not exceed 1    in   Insulation thicker than  Y  in  can interfere with  the Blower Assembly  Dilution Air Holes     22    Insulation Blankets    Insulation blankets  available to the  general public  for external use on gas  water heaters are not necessary  The  purpose of an insulation blanket is to  reduce the standby heat loss encountered  with storage tank heaters  This water  heater meets or exceeds the National  Appliance Energy Conservation Act  standards with respect to insulation and  standby loss requirements making an  insulation blanket unnecessary     The manufacturer   s warranty does not  cover any damage or defect caused by  installation  attachment or use of   any type of energy saving or other  unapproved devices  other than those  authorized by the manufactur
25. ON    position       Set the thermostat to the lowest setting   by pressing the COOLER   and HOTTER  buttons at the same time and holding   them for  1  second  Depress the COOLER   button until only the WARM indicator  light is lit      Toggle the    ON OFF    switch located on the  blower assembly to the    OFF    position      Turn off all electrical power to the appliance      This appliance is equipped with a Hot  Surface Ignition System which auto   matically lights the burner  Do NOT open  the inner door of this appliance and try to  light the burner by hand      Wait five  5  minutes to clear out any gas   If you smell gas  STOP  Follow   B   in the  safety information above on this label  If    you do not smell gas  go ahead to the next step     8  9    10       Turn on all electrical power to the appliance     Toggle the    ON OFF    switch located on the    blower assembly to the   ON    position     Set thermostat to the desired temperature  setting by pressing the COOLER  and  HOTTER buttons at the same time and  holding them for  1  second  Depress the  HOTTER   button until the desired  temperature display setting is lit  The  preferred starting point for temperature  setting is indicated by Von the thermostat       Ifthe appliance will not operate  follow    the instructions   TO TURN OFF GAS TO  APPLIANCE    and call your service  technician or gas supplier      O 066 b  s    can Q    roren    O  0 TURN GAS OFF TO THE N O    1  Set the thermostat to the lowes
26. TICE  This unit is  equipped with a Flammable  Vapor Sensor  Do not apply  power until enough time has  passed to allow the vapors  from the primer and cement  to dissipate     12    Venting    This appliance must be vented to the  outdoors as described in these instructions   DO NOT connect this appliance to   an existing vent or chimney   it must   be vented separately from all other  appliances     NOTICE  This appliance is approved to  use the following materials for pipe of  the vent system     PVC  DWV  ASTM D2665 or CSA  B181 2     PVC  Schedule 40  ASTM D1785 or  CSA B137 3     CPVC  CPVC 4120  ASTM D2846 or  CSA B137 6     CPVC  Schedule 40  ASTM F441 or  CSA B137 3     ABS  Schedule 40  DWV  ASTM D2661  or CSA B181 1     This appliance is approved to use the  following materials for the fittings of the  vent and combustion air intake systems     PVC  Schedule 40 DWV  ASTM D2665   CPVC  Schedule 40  ASTM F438     ABS  Schedule 40 DWV  ASTM D2661     DO NOT mix ABS pipe and fittings with  PVC or CPVC pipe fittings  Note  It is  acceptable to interchange PVC and CPVC  pipe and fittings     NOTICE  This appliance may be  installed in attics provided ambient  temperatures do not exceed 125  F and  CPVC or ABS pipe and fittings are used  for the entire vent system     The vent system must be adequately  supported along both vertical and  horizontal lengths     The vent system of this appliance may be  installed horizontally through a wall or  vertically through the roof  
27. Use  amp  Care Manual    With Installation Instructions for the Installer       FVIR Compliant  75 Gallon Models    The purpose of this manual is twofold  one  to provide the installer with the basic  directions and recommendations for the proper installation and adjustment of the water  heater  and two  for the owner   operator  to explain the features  operation  safety  precautions  maintenance and troubleshooting of the water heater  This manual also  includes a parts list     It is very important that all persons who are expected to install  operate or adjust this  water heater read the instructions carefully so they may understand how to perform  these operations  If you do not understand these instructions or any terms within it  seek  professional assistance     Any questions regarding the operation  maintenance  service or warranty of this water  heater should be directed to the seller from whom it was purchased  If additional  information is required  refer to the section on    If you need service        Do not destroy this manual  Please read carefully and keep in a safe place for future  reference                       Recognize this symbol as an indication of Important Safety Information     California Proposition 65 Warning  This product contains chemicals known to  the State of California to cause cancer  birth defects or other reproductive harm        WARNING  If the information in these instructions is not followed exactly  a fire or  explosion may result cau
28. age nearby casused by condensate     Inspect dilution air inlet and combustion  air inlet openings  Make certain no  blockage exists  Clean any lint  dirt or oil  accumulation that may exist     At least once a year  lift and release the  lever handle on the temperature pressure  relief valve  located near the top of the  water heater  to make certain the valve  operates freely  Allow several gallons to  flush through the discharge line to an open  drain     NOTICE  If the temperature and  pressure relief valve on the water heater  discharges periodically  this may be due  to thermal expansion in a closed water  system  Contact the water supplier or  your plumbing contractor on how to  correct this  DO NOT plug the relief  valve outlet     A water heater   s tank can act as a settling  basin for solids suspended in the water  It  is therefore not uncommon for hard water  deposits to accumulate in the bottom of the  tank  If allowed to accumulate  these solids  can cover the gas control  thermostat   sensors  causing the sensors to operate  erratically  Because accumulated solids  can prevent the gas control  thermostat   sensors from accurately reading the water  temperature  the water at the fixture can   be hotter than the gas control  thermostat   setting  It is suggested that a few quarts of  water be drained from the water heater   s  tank every month to clean the tank of these  deposits     Rapid closing of faucets or solenoid valves  in automatic water using appliances
29. al and horizontal lengths of the vent system  as previously mentioned     Determine the vent terminal height and cut the pipe accord   ingly     e Insert lengths of vent pipe through the ceiling wall as  shown     e Install adequate flashing where the vent pipe passes  through the roof     e Place the supplied mesh metal screen inside the vent ter   minal then connect a short piece of pipe approximately 3 in   between the terminal and elbow     NOTICE  For cold climates the screen may be removed     NOTICE  This water heater is supplied with a vent ter   mination restrictor  The restrictor helps the water heater  achieve peak efficiency when the water heater is installed  using 3 in  diameter pipe at the minimum equivalent vent  length of 10 ft     IMPORTANT  DO NOT install the termination restric   tor in equivalent vent lengths longer than 10 ft  or on any  other Power Vent model     17    Installing the water heater       Terminals with 1 2 in   1 3 cm  Mesh Terminals with 1 2  Mesh  Protective Screens and Termination Protective Screens Inside   Restrictors Inside    Note  Termination Restrictors used on    75 Gallon models ONLY Exhaust Vent    Elbow      Min  12 in    30 5 cm  Above Roof  or Anticipated Snow  Level  which  ever is highest    Exhaust Vent             3  Piece of Pipe             y and    Max  24 in   61 cm   Above Roof     Min  12in  Without Additional 9s   se eee eee eeeee   30 5 cm  Above Roof Support   or Anticipated Snow   Level  which    ever is highe
30. appliance as practical at the  time of the appliance installation  The  sediment trap shall be either a tee fitting  with a capped nipple in the bottom outlet  or other device recognized as an effective  sediment trap     DO NOT use excessive force  over 31 5  ftelbs    42 70 Nem  in tightening the pipe  joint at the Combination Gas Control   Thermostat  inlet  particularly if Teflon  pipe compound is used  as the valve body  may be damaged     The inlet gas pressure to the water heater  must not exceed 14 in  w c  for natural gas   or 14 in  w c  for LP gas  For purposes of  input adjustment  the minimum inlet gas  pressure  with main burner on  is shown on  the water heater rating plate  If high or low  gas pressures are present  contact your gas  supplier for correction     leaks at all connections and fittings   Bubbles indicate a gas leak that must  be corrected     The factory connections to the gas control   thermostat  should also be leak tested after  the water heater is placed in operation     Pressure Testing the Gas Supply System    The water heater and its individual shutoff  valve must be disconnected from the gas  supply piping system during any pressure  testing of that system at test pressures in  excess 1 2 psi  3 5 kPa      High Altitude    Input rating of this water heater is based on  sea level operation  At higher elevations  the actual input rate may be lower than the  value listed on the rating label due to the  derating of natural gas and LP gas  This
31. ard  for Temperature Actuated Mixing Valves  for Hot Water Distribution Systems  ASSE  1017 be installed  See page 4 for more  details and contact a licensed plumber or  the local plumbing authority for further  information     The chart on the next page may be used  as a guide in determining the proper water  temperature for your home     27    Operating the water heater    28    Water Temperature Setting    Maximum water temperatures occur just  after the burner has shut off  To determine  the water temperature  turn on a hot water  faucet and place a thermometer in the  water stream     To avoid any unintentional changes in  water temperature settings  the gas control   thermostat  has a tamper resistant feature  for changing the temperature setting  To  change the temperature setting follow  these instructions     1   Wake Up  the temperature indicators  by holding down both  COOLER  and   HOTTER  temperature adjustment  buttons at the same time for one  second  see Figure below  One or two  of the temperature indicators will light  up  These indicators will only remain  on for 30 seconds if no further buttons  are pressed  After 30 seconds the  control will go back to  sleep  mode     2  Release both of the temperature buttons     a  To decrease the temperature press  and release the  COOLER  button  until the desired setting is reached     b  To increase the temperature press  and release the  HOTTER  button  until the desired setting is reached     NOTICE  Holding down
32. at the drain valve is closed   then open the shut off valve in the cold  water supply line     Open each hot water faucet slowly to allow  the air to vent from the water  heater and piping     Condensation    Condensation can form on the tank when  it is first filled with water  Condensation  might also occur with a heavy water  draw and very cold inlet water  temperatures     Drops of water falling on the burner can  produce a sizzling or pinging sound     The discharge line must be no smaller   than the outlet of the valve and must   pitch downward from the valve to allow  complete drainage  by gravity  of the relief  valve and discharge line     The end of the discharge line should not   be threaded or concealed and should be  protected from freezing  No valve of any  type  restriction  or reducer coupling should  be installed in the discharge line     A steady flow of water from the hot water  faucet s  indicates a full water heater     Do not allow the flammable vapor sensor  to become submerged in water     This condition is not unusual  and will  disappear after the water becomes heated   If  however  the condensation continues   examine the piping and fittings for possible  leaks     AWARNING  DO NOT attempt to convert this water heater for use with a different type of gas other than the type  shown on the rating plate  Such conversion could result in hazardous operating conditions     AWARNING  Never use  an open flame to test for  gas leaks  as property  damage  per
33. ating of all  the appliances in the enclosure  If ducts  are used  the minimum dimensions of  rectangular air ducts shall not be less than  3in      NOTICE  If the duct openings which  supply combustion and ventilation air  are to be covered with a protective  screen or grill  the net free area   openings in the material  of the  covering material must be used in  determining the size of the openings   Protective screening for the openings  MUST NOT be smaller than 1 4in mesh  to prevent clogging by lint or other  debris     will shorten the life of any gas burning  appliance     Propellants from common spray cans  or gas leaks from A C and refrigeration  equipment are highly corrosive after  passing through a flame     The water heater warranty is voided when  failure of the heater is due to operation in  a corrosive atmosphere     IMPORTANT  Do  not apply heat to the  HOT or COLD water  connections  If sweat  connections are   used  sweat tubing to  adapter before fitting  adapter to the cold  water connections   on heater  Any heat  applied to the cold  water supply fittings  will permanently  damage the dip tube  and heat traps     NOTICE  The  National Fuel Gas  Code  NFGC   mandates a manual  gas shut off valve   See  NFGC    for complete  instructions    Local codes or  plumbing authority  requirements   may vary from   the instructions   or diagrams  provided and take  precedent over these  instructions     Thermal Expansion    Determine if a check valve exists in the
34. ble Vapor Sensor     Q DON   T operate the water heater if the    sight glass or igniter assembly grommet is  damaged or broken  see to the left      23    Installation Checklist  A  Water Heater Location    Q Close to area of vent   Q Drain pan installed     Q Indoors and protected from freezing  temperatures     U Proper clearance from combustible surfaces  observed and water heater not installed on  carpeted floor     Q Sufficient fresh air supply for proper  operation of water heater        Q Air supply free of corrosive elements and  flammable vapors     B  Water Supply    Q Water heater completely filled with water        Q Air purged from water heater and piping     C  Gas Supply    Q Gas line equipped with shut off valve  union  and sediment trap        Q Approved pipe joint compound used     D  Relief Valve    Q Temperature and Pressure Relief Valve  properly installed and discharge line run to  open drain     E  Venting  Q Water Heater vented separately from all  other appliances     Q Flue baffle properly hung in top of heater   s  flue     Q Blower assembly properly installed     Q Proper materials and techniques used in the  installation of the vent assembly        Q Vent pipe properly secured to blower exhaust  coupling on the blower assembly     F  Wiring       Correct power supply  120 V         Q Electrical connections tight     24    U Provisions made to protect area from water  damage     Q Sufficient room to service heater        Q Combustible materials  s
35. ce     Ambient Temperature Installation  Requirements    Rheem recommends this appliance be  installed in locations where the ambient  temperatures do not exceed 100  F     DO NOT install the ats ina  location where it may be subjected to  ambient temperatures exceeding 125  F     The appliance should be installed so as to  minimize the length of plastic pipe and the  number of vent and combustion Air Inlet  connection fittings required     Vent pipe materials must be chosen based  upon the ambient temperature where the  appliance is installed and the location  within the vent system     Additional installation information for  The Commonwealth of Massachusetts is  located on the back page of this manual     Maximum and Minimum Vent Lengths    Ambient Installation Temperatures and Vent System Material Specifications    Below 100  F 100  F to 125  F  Models    Equivalent Vent  System Length    CPVC or ABS    0 to 10 ft  10 ft  to Max 0 to 20 ft  20 ft  to Max  75 Gallon    Read these instructions thoroughly and make sure you  understand all steps and procedures before proceeding  with the installation     1  Connect the vent system piping to the blower as   sembly using the already installed 3 in  diameter blower  exhaust coupling and clamps     2  For vent terminal use the 3 in  diameter  Schedule  40  PVC  90    1 4 standard bend elbow supplied with  the appliance  See Figure 1      This appliance may also be installed with 4 in  diameter  pipe and fittings for the vent syst
36. do not follow these instructions and the Use  amp  Care  Manual instructions exactly  a fire or explosion may result causing property  damage  personal injury or loss of life     A  This appliance does not have a pilot  It is  equipped with an ignition device which auto   matically lights the burner  Do NOT try to light  the burner by hand     BEFORE PUTTING THIS APPLIANCE INTO   SERVICE   Smell all around the appliance   area for gas  Be sure to smell next to the   floor because some gas is heavier than air   and will settle on the floor    WHAT TO DO IF YOU SMELL GAS   e Do not try to light any appliance    e Do not touch any electric switch  do  not use any phone in your building    e Immediately call your gas supplier  from a neighbor s phone  Follow the    gas supplier s instructions     e Ifyou cannot reach your gas  supplier  call the fire department     C  Use only your hand to push in the gas  control buttons  Never use tools  If the  control buttons will not push in  don   t try  to repair them  call a qualified service  technician  Force or attempted repair  may result in fire or explosion       Do not use this appliance if any part has  been under water  Immediately call a  qualified installer or service agency to  replace a flooded water heater  Do not  attempt to repair the unit  It must be  replaced     OPERATING INSTRUCTIONS      STOP  Read the safety information above  on this label      Toggle the   ON OFF    switch located on the  blower assembly to the    
37. dress   1241 Carwood Court  Montgomery  Alabama 36117  Phone  1 866 279 4566    When contacting the manufacturer  the following information will be requested   a  Model and serial number of the water heater as shown on the rating plate attached to the jacket of the heater     meae o    Address where the water heater is located and physical location    Name and address of installer and any service agency who performed service on the water heater   Date of original installation and dates any service work was performed    Details of the problems as you can best describe them    List of people  with dates  who have been contacted regarding your problem     Important Instructions for the Commonwealth of Massachusetts    The Commonwealth of Massachusetts requires compliance with regula   tion 5 08  Modifications to NFPA 54  Chapter 10   248 CMR 4 00  and 5 00 for installation of through     the     wall vented gas appliances as  follows      1  Revise NFPA 54 section 10 5 4 2 by adding a second exception as fol   lows    Existing chimneys shall be permitted to have their use continued when a gas  conversion burner is installed  and shall be equipped with a manually reset  device that will automatically shut off the gas to the burner in the event of a  sustained back draft     2  Revise 10 8 3 by adding the following additional requirements     a  For all side wall horizontally vented gas fueled equipment installed in  every dwelling  building or structure used in whole or in part f
38. ds to  prevent the tapered socket from  pushing the pipe out of the fitting     5 Wipe all excess cement from the joint  with a rag  Allow 15 minutes before  handling  Cure time will vary  according to fit  temperature and  humidity     NOTICE  Stir the solvent cement  frequently while using  Use a natural  bristle brush or the dauber supplied  with the can  The proper brush size is  one inch     NOTICE  This unit is equipped with  a Flammable Vapor Sensor  DO NOT  apply power until enough time has  passed to allow the vapors from the  primer and cement to dissipate     Wiring    If local codes permit  the water heater may The water heater must be electrically    be connected to electric service with the grounded in accordance with local   power cord provided  DO NOT use an codes  or  in the absence of local codes   extension cord   A grounding receptacle is in accordance with latest edition of the  required  National Electric Code ANSI NFPA No  70     Refer to the figures below for water heater    If local codes do not permit the use of cord a  internal wiring     connections  a 120 V  50 60 Hz power  supply  with suitable disconnecting means   must be connected to the black and white  leads in the heater control enclosure     A knock out hole is provided to permit use  of conduit or metal clad cable connectors     CONNECTION DIAGRAM SCHEMATIC    ON   OFF  SWITCH       SENSOR        IGNITER    FV SENSOR          PRESSURE  SWITCH    TEMPERATURE  SWITCH    G            ELECTRO
39. e  or building   until the service call has been made  the  leak is corrected and a qualified agency  has determined the area to be safe     IMPORTANT SAFETY INFORMATION  READ ALL INSTRUCTIONS BEFORE USING    A WARNING     For your safety  the information in this manual must be followed to minimize the risk of  fire or explosion  electric shock  or to prevent property damage  personal injury  or loss of  life     FOR INSTALLATIONS IN THE STATE OF CALIFORNIA    California Law requires certain water heaters must be braced  anchored or strapped   to resist falling or horizontal displacement due to earthquake motions  For the affected  water heaters up to 52 gallon capacity  a brochure with generic earthquake bracing  instructions can be obtained from  Office of the State Architect  1102 Q Street  Suite 5100   Sacramento  CA 95814 or you may call 916 445 8100 or ask a water heater dealer     However  applicable local codes shall govern installation  For affected water heaters of  a capacity greater than 52 gallons  consult the local building jurisdiction for acceptable  bracing procedures     SAFETY PRECAUTIONS    Have the installer show you the location of the gas shut off valve and how to shut it off  if necessary  Turn off the manual shut off valve if the water heater has been subjected to  overheating  fire  flood  physical damage or if the gas supply fails to shut off        Read this manual entirely before installing DO NOT attempt to repair or replace   or operating the wa
40. e water  heater can be regulated by pressing the  buttons on the front of the gas control   thermostat      Safety and energy conservation are factors  to be considered when selecting the water  temperature setting of the water heater   s  gas control  thermostat s    The lower the  temperature setting  the greater the savings  in energy and operating costs     To comply with safety regulations  the gas  control  thermostat  was set at its lowest  setting before the water heater was shipped  from the factory  The recommended  starting point temperature is 120  F     Water temperatures above 125  F can  cause severe burns or death from scalding     the hot surface ignitor should heat up  then  the gas valve should open and the main  bumer ignite  After the main burner ignites   replace the outer door  If no main burner  flame is established  the gas control will go  through three trials for ignition before going  into a lock out  A waming light will alert  the user of this lock out condition  If this  happens  refer to    Troubleshooting Guide        TO SHUT OFF WATER HEATER   Turn  switch on the blower assembly to the    OFF     position     Be sure to read and follow the warnings  outlined in this manual and on the label  located on the water heater near the gas  control thermostat     Mixing valves are recommended for  reducing point of use water temperature  by mixing hot and cold water in branch  water lines  It is recommended that a  mixing valve complying with the Stand
41. ed terminal is flush with the  outside wall surface     Complete the installation of the remainder of the vent system  and attach it to the blower exhaust coupling on the water  heater   s blower assembly     Horizontal lengths of the vent system must slope downward  a minimum of 1 8 in  per foot     IMPORTANT  When the vent system cannot be sloped  away from the water heater or  if the vent system has  vertical section s   then all horizontal sections must slope  upwards a minimum of 1 8 in  per foot     DO NOT use unequal diameters of pipe and fittings for the  vent system except as defined previously    Support vertical and horizontal lengths of the vent systems as  previously mentioned     NOTICE  This water heater is supplied with a vent  termination restrictor  The restrictor helps the water heater  achieve peak efficiency when the water heater is installed  using 3 in  diameter pipe at the minimum equivalent vent  length of 10 ft     IMPORTANT  DO NOT install the termination restrictor  in equivalent vent lengths longer than 10 ft  or on any other  Power Vent model        Slope horizontal pipe downward 1 8     per foot  10 mm per m  min                  Horizontal Vent Terminal Installation    Vertical Vent Terminal Installation    The location of the vent terminal depends on the following  minimum clearances and considerations     1  Minimum 12 in  above roof   2  Minimum 12 in  above anticipated snow level     3  Maximum 24 in  above roof level without additional sup
42. em     To connect the vent system piping    e Install a 12 in  length of 3 in  diameter pipe verti   cally to the blower exhaust coupling on the blower  assembly    e Followed by a 3 in  to 4 in  diameter pipe increaser   fitting  See Figure 2      For vent terminal   e Use 4 in  diameter  Schedule 40  PVC  90    1 4 stan   dard bend elbows  not supplied      DO NOT use unequal diameters of pipe and fittings for  the vent system except as defined previously     Equivalent Vent  System Length    PVC CPVC or ABS       Equivalent Vent  System Length    Equivalent Vent  System Length    CPVC or ABS PVC CPVC or ABS    IMPORTANT  Ensure that all the coupling clamps  are tight before allowing the appliance to operate     When using ABS  US only  or CPVC pipe and fittings   use 90   elbows of the corresponding size and material  for the vent terminal     Screens for the 3  amp  4 in  vent terminals have been sup   plied with the appliance     The minimum and maximum equivalent lengths for the  vent system are shown in Table 1     e Maintain a minimum vertical height of 1 ft  of pipe   including pipe increasers  if used   from the blower  exhaust coupling before transitioning into any elbow        The vent termination is not included in the equiva   lency calculations     NOTICE  A 90    1 4 standard bend or long bend  elbow is equivalent to 5 ft  of straight pipe  A 45    1 8  standard bend or long bend elbow is equivalent to  2 5 ft  of straight pipe     DO NOT use short bend elbows
43. ent the water  heater from being started again     The following is a list of materials that will  cause the Flammable Vapor Sensor to shut  down the water heater     Vapors of Gasoline     Vapors of certain flammable paints   stains  and thinners     Vapors of vent pipe Cement  amp  Solvents     Bleach  direct contact with flammable  vapor sensor      Some other flammable materials and their  vapors     If the flammable vapor sensor shuts down  the water heater  then the electronic control  will display the appropriate error code   and you should then promptly contact a  qualified service technician     Refer to the    NOTICE    on page 3 for  additional information     29    Care and cleaning of the water heater          ADANGER  Before  manually operating the  relief valve  make certain  no one will be exposed to  the danger of the hot water  released by the valve  The  water may be hot enough to  create a scald hazard  The  water should be released  into a suitable drain to  prevent injury or property  damage     ADANGER  Hotter water  increases the potential for  Hot Water Scalds        ADANGER  Failure to  perform the recommended  Routine Preventative  Maintenance can harm the  proper operation of this  water heater  which can  cause carbon monoxide  dangers  excessive hot  water temperatures and  other potentially hazardous  conditions     30    Draining the Water Heater    ACAUTION  Shut off gas to the water  heater at the manual gas shut off valve  before draining wa
44. er  into  onto  or in conjunction with the water heater   The use of unauthorized energy saving  devices may shorten the life of the water    heater and may endanger life and property     The manufacturer disclaims any  responsibility for such loss or injury  resulting from the use of such  unauthorized devices     ACAUTION  If local codes require the  application of an external insulation  blanket to this water heater  pay careful  attention to the following so as not to  restrict the proper function and  operation of the water heater     DO NOT cover the operating or  warning labels attached to the water  heater or attempt to relocate them on  the exterior of insulation blanket     DO NOT apply insulation to the top  of the water heater  This will interfere  with the safe operation of the blower   assembly     DO NOT cover the burner access door   jacket door  gas control  thermostat  gas  valve or pressure and temperature relief  valve     DO NOT apply insulation to the  bottom of the water heater or the area  where the combustion air inlet openings  and Flammable Vapor Sensor are  located  This area must be unobstructed  so as not to restrict combustion air flow  to the burner or operation of the sensor     Inspect the insulation blanket frequently  making certain it has not sagged   and it is not restricting the air flow   to the combustion air inlet openings   perforation holes  or the Flammable  Vapor sensor located around the lower  perimeter of the water heater jacke
45. er heater has been subjected to  fire  flood or physical damage  turn off the  manual gas control  shut off  valve  and  do not operate the water heater again until  is has been checked by a qualified service  technician     NOTICE  DO NOT use this appliance if  any part has been under water  Immediately  call a qualified installer or service agency   to replace a flooded water heater  DO   NOT attempt to repair the unit  It must be  replaced     VACATION       AOOO OOK    COOLER 9  S  HOTTER       Burns on Adult Skin                             Water Temperature Time To Produce a Serious Burn     120  F More than 5 minutes   125  F 1  2 to 2 minutes   130  F About 30 seconds   135  F About 10 seconds   140  F Less than 5 seconds   145  F Less than 3 seconds   150  F About 1  2 seconds   155  F About 1 second       Table courtesy of Shriners Burn Institute                   WARM   approx  70  F  21  C  e00000  ort  Vv   approx  120  F  49  C  O0 000 More than 5 minutes  A  approx  130  F  54  C  O008e00 About 30 seconds  B   approx  140  F  60  C  CO000e  O Less than 5 seconds  C   approx  150  F  66  C  O0000 e About 1 1 2 seconds  C Flashing   approx  160  F  71  C  O0000e About 1 2 seconds       Sequence of Operation    During initial start up or a call for heat  the  control will verify the vacuum switch is  open     Once the control verifies the blower vacuum  switch is open  the control will energize the  blower motor for the pre purge sequence   approximately 5 seconds
46. ese units are not  certified for any other fuel type     LP appliances should not be installed  below grade  for example  in a basement   if such installation is prohibited by  federal  state and or local laws  rules   regulations or customs     LP gas must be used with great caution   It is heavier than air and will collect first  in lower areas making it hard to detect at  nose level     Before attempting to light the water  heater  make sure to look and smell for  gas leaks  Use a soapy solution to check  all gas fittings and connections  Bubbling  at a connection indicates a leak that must  be corrected  When smelling to detect a  gas leak  be sure to sniff near the floor  also     Gas detectors are recommended in LP   amp  natural gas applications and their  installation should be in accordance  with the detector manufacturer   s  recommendations and or local laws   rules  regulations or customs     It is recommended that more than one  method  such as soapy solution  gas  detectors  etc   be used to detect leaks in  gas applications        DANGER  If a gas leak is present or  suspected     DO NOT attempt to find the cause  yourself     DO NOT try to light any appliance   DO NOT touch any electrical switch   DO NOT use any phone in your building     Leave the house immediately and make  sure your family and pets leave also     Leave the doors open for ventilation  and contact the gas supplier  a qualified  service agency or the fire department     Stay away from the hous
47. he air must be supplied through two  permanent openings of equal area  One is  to be located within 12in  above the floor  and the other is to be located within 12in   from the ceiling     Corrosive Atmospheres    The air in beauty shops  dry cleaning  establishments  photo processing   labs  and storage areas for liquid and  powdered bleaches or swimming pool  chemicals often contain such halogenated  hydrocarbons     An air supply containing halogenated  hydrocarbons may be safe to breathe   but when it passes through a gas flame  corrosive elements are released that    The minimum net free area of each opening  must not be less than one square inch   per 1000 Btuh of the total input rating   of all the appliances in the enclosure    but not less than 100 square inches   if  each opening communicates with other  unconfined areas inside the building     Buildings of unusually tight construction  shall have the combustion and ventilation  air supplied from outdoors  or a freely  ventilated attic or crawl space     If air is supplied from outdoors  directly or  through vertical ducts  there must be two  openings located as specified above and  each must have a minimum net free area  of not less than one square inch per 4000  Btuh of the total input rating of all the  appliances in the enclosure     If horizontal ducts are used to  communicate with the outdoors  each  opening must have a minimum net free  area of not less than one square inch per  2000 Btuh of the total input r
48. heater if cold water supply    shut off valve is closed     O DO NOT allow combustible materials such as  newspaper  rags or mops to accumulate near water    heater     A DANGER  Hotter water  increases the Potential for Hot  Water SCALDS  Households  with small children   disabled  or elderly persons  may require a 120  F or  lower gas control   thermostat  setting to  prevent contact with HOT  water     for ventilation  and all gas burning appliances in the    vicinity should be shut off including their pilot    burners  to avoid vapors lighting     NOTICE  Flammable vapors can be drawn by air    currents from surrounding areas to the water heater     fF  If there is any difficulty in understanding or following    the Operating Instructions or the Care and Cleaning  section  it is recommended that a qualified person or  serviceman perform the work     Operating Procedure    This heater is equipped with a hot surface  ignitor to light the main burner  There is   no pilot light to be lit  but on initial start    up  it is recommended that the outer door   be removed  leave inner door in place for  safety  to determine if the hot surface ignitor  and main burner are operating properly     Once filled with water  it is only necessary  to plug the power cord in and make sure the     ON OFF    switch located on the blower  assembly is in the    ON    position to put the  water heater into operation  Within seconds    Water Temperature Setting    The temperature of the water in th
49. lt in serious injury or death     A Do not store or use gasoline or other flammable vapors and liquids  in the vicinity of this or any other appliance  Storage of or use of gasoline  or other flammable vapors or liquids in the vicinity of this or any other  appliance can result in serious injury or death                 IMPORTANT SAFETY INFORMATION  READ ALL INSTRUCTIONS BEFORE USING    ADANGER     WATER TEMPERATURE SETTING       Safety and energy conservation are factors to be considered when selecting the water  temperature setting of a water heater   s gas control  Water temperatures above 125  F  can cause severe burns or death from scalding  Be sure to read and follow the warnings  outlined on the label pictured below  This label is also located on the water heater     A DANGER    Water temperature over 125   F  can cause severe burns  instantly or death from scalds     Children  disabled and elderly are  at highest risk of being scalded     See instruction manual before  setting temperature at water  heater     Feel water before bathing or  showering     Temperature limiting valves are  available  see manual        NOTICE  Mixing valves are recommended for reducing  point of use water temperature by mixing hot and   cold water in branch water lines  It is recommended   that a mixing valve complying with the Standard for  Temperature Actuated Mixing Valves for Hot Water  Distribution Systems  ASSE 1017 be installed  See page  27 for more details and contact a licensed pl
50. ly to From HOT ADANGER  When this system requires in an application intended to supply domestic  beating outlet on water for space heating at elevated hot water needs and hot water for space    water heater    Tee fitting for vertical hot  water supply lines     Hot water From HOT  supply to outlet on  house water heater    _  lt           lt     Hot water supply  to heating unit         Tee fitting for horizontal hot  water supply lines     temperatures  above 125  F  52  C     a mixing  valve complying with the Standard for  Temperature Actuated Mixing Valves for Hot  Water Distribution Systems  ASSE 1017 must  be installed in the hot water supply line to the  house in order to reduce the scald hazard  potential     ADANGER  Any piping or components used  in the installation of this water heater in a  combination potable and space heating  application must be suitable for use with  drinking water     heating purposes  do not connect the heater  to an existing heating unit or components of a  heating system that have previously been  used with a non drinking water system  Toxic  chemicals such as those used for boiler  treatment may be present and will  contaminate the drinking water supply  causing possible health risks  Never  introduce toxic chemicals  such as those used  for boiler treatment  into this system     50 ft  maximum distance from water  heater to fan coil  developed length  is    required for Massachusetts State           Typical 75 Gallon Piping Diagram for 
51. ner   from the water heater  A vacuum  cleaner can be used on the burner and  floor shield inside the water heater   The burner can also be cleaned by  scrubbing with mild detergent     31    Care and cleaning of the water heater       NOTICE  Refer to the  Hydrogen Gas Caution in  the Operating Instructions     NOTICE  Do not remove  the anode rod from the  water heater   s tank  except  for inspection and or  replacement  as operation  with the anode rod removed  will greatly shorten the   life of the glass lined tank  and will exclude warranty  coverage     32    Vacation and Extended Shut Down    If the water heater is to remain idle for an  extended period of time  the power and  water to the appliance should be turned  off to conserve energy and prevent a  build up of dangerous hydrogen gas     The water heater and piping should be  drained if they might be subjected to  freezing temperatures     Anode Rod    This water heater is equipped with an  anode rod designed to prolong the life  of the glass lined tank  The anode rod is  slowly consumed  thereby eliminating or  minimizing corrosion of the glass lined  tank     After a long shut down period  the   water heater   s operation and controls  should be checked by qualified service  personnel  Make certain the water heater  is completely filled again before placing it  in operation     Water sometimes contains a high sulfate  and or mineral content and together with  cathodic protection process can produce a  hydrogen 
52. ng for attachment of the vent terminal     Place the supplied mesh metal screen inside the vent terminal  fitting     NOTICE  For cold climates the screen may be removed     16    1  DO NOT install the vent terminal under any patio or deck        To help prevent moisture from freezing on walls and under eaves   do not locate the vent terminal on the side of a building with  prevailing winter winds     3 When terminating the vent pipes through brick or masonry  surfaces  the installation of a rust resistant sheet metal backing  plates behind the vent terminal is recommended     4  DO NOT locate the vent terminal too close to shrubbery  as flue  gasses may damage them        Caulk all cracks  seams and joints within 6 ft  of the vent  terminal     6  Insulate vent pipe exposed to cold conditions  attics  crawl  spaces  etc   with inflammable material to help prevent moisture  from accumulating in the vent pipe     7  Support horizontal sections of the vent pipe every 4 ft  DO NOT  rigidly secure the vent system  Provisions must be made to allow  for expansion and contraction of the vent system     g  DO NOT install the vent terminal less than 1 ft  above grade or  average snowfall whichever is greater     g  Permanently seal annular openings around the vent system  penetration using approved materials to prevent entry of  combustion products into the building     Connect the terminal to the vent pipe which is extending out of  the building     Ensure that the back of the suppli
53. nge specified on the  rating plate        Q DO provide adequate air for combustion  and ventilation as discussed in the Use  and Care Manual and the National Fuel  Gas Code     LU DO maintain proper clearances to  combustibles as specified on the rating  plate        Q DO allow enough time for joint cement  vapors to dissipate BEFORE applying  power to the water heater     Q DO ensure that the venting system  complies with the guidelines found in the  Use and Care Manual and National Fuel  Gas Code     Q DO contact a qualified service technician  if the main burner will not stay lit  The  burner chamber is designed to be sealed  utilizing a gasket and tamper resistant  screws        Ignitor Assembly Sight Glass    Grommet  Flammable  Vapor Sensor    DON   T    L DON   T block or restrict Combustion Air  Inlet Openings or the Flammable Vapor  Sensor located around the lower portion  of the water heater jacket     L DON   T block or restrict the Blower  Assembly Dilution Air holes  see diagram  to the left      Q DON   T remove the Burner Access Door  unless absolutely necessary  This should  only be done by a qualified service  technician  A new burner access door  gasket must be installed on any burner  access door that has been removed     L  DON   T install this water heater where  standing water may occur  The base of the  water heater is meant to be mounted on a  dry surface     L  DON   T allow cleaners  solvents  or other  materials to come into contact with the  Flamma
54. on  air inlet openings and any obstruction     DO NOT obstruct or block the Flammable  Vapor Sensor     Because of natural air movement in a room  or other enclosed space  flammable vapors  can be carried some distance from where  liquids which give off flammable vapors are  to be used or stored  The open flame of the  water heater   s main burner can ignite these  vapours and create a shutdown condition of  the water heater which will not allow the  water heater to ignite until examined by a  Qualified Service Technician     FVIR certified gas water heaters can be  installed on a residential garage floor without  the use of an 18 inch stand in accordance with  the National Fuel Gas Code  NFPA 54  ANSI  2223 1  unless otherwise directed by State and  Local code requirements  The water heater  must be located so it is not subject to physical  damage  for example  by moving vehicles  area  flooding  etc     We recommend this water heater be  installed in locations where the ambient  temperatures DO NOT exceed 100  F     IMPORTANT  Do not install the water  heater in a location where it may be    subjected to ambient temperatures  exceeding 125  F     The water heater should be installed so as  to minimize the length of plastic vent pipe  and the number of vent connection fittings  required  See the  Venting Section  for vent  system requirements     Long hot water lines should be insulated to  conserve water and energy     The water heater and water lines should  be protected f
55. onfused  with combustible or  flammable products and  materials  Combustible  and or flammable products  and materials should never  be stored in the vicinity of  this or any gas appliance     Location    The water heater should not be located in   an area where leakage from the tank or  connections will result in damage to the area  adjacent to the heater or to lower floors of the  structure     When such areas cannot be avoided it is  recommended that a suitable drain pan   adequately drained  must be installed under the  water heater     The water heater must be centered in the drain  pan     The drain pan must not restrict air flow to the  combustion air inlet openings  perforation  openings  located around the lower perimeter  of the water heater     Drain pan kits are available from the store  where the water heater was purchased  or any  water heater distributor     Make certain the floor underneath the water  heater is strong enough to sufficiently support  the weight of the water heater once it is filled  with water     A gas fired water heater or any other appliance  should not be installed in a space where liquids  which give off flammable vapors are to be  used or stored  Such liquids include gasoline   LP gas  butane or propane   paint or adhesives  and their thinners  solvents or removers     DO NOT block or obstruct any of the  combustion air inlet openings located around  the perimeter of the water heater  A minimum  of 1 in  is required between these combusti
56. or residential  purposes  including those owned or operated by the Commonwealth and  where the side wall exhaust vent termination is less than seven  7  feet above  finished grade in the area of the venting  including but not limited to decks  and porches  the following requirements shall be satisfied    1  INSTALLATION OF CARBON MONOXIDE DETECTORS  At the time  of installation of the side wall horizontal vented gas fueled equipment  the  installing plumber or gasfitter shall observe that a hard wired carbon monox   ide detector with an alarm and battery back up is installed on the floor level  where the gas equipment is to be installed  In addition  the installing plumber  or gasfitter shall observe that a battery operated or hard wired carbon mon   oxide detector with an alarm is installed on each additional level of the dwell   ing  building or structure served by the side wall horizontal vented gas fueled  equipment  It shall be the responsibility of the property owner to secure the  services of qualified licensed professionals for the installation of hard wired  carbon monoxide detectors   a  In the event that the side wall horizontally vented gas fueled equipment is  installed in a crawl space or an attic  the hard wired carbon monoxide detec   tor with alarm and battery back up may be installed on the next adjacent floor  level    b  In the event that the requirements of this subdivision can not be met at the  time of completion of installation  the owner shall have a 
57. period of thirty  30   days to comply with the above requirements  provided  however  that during  said thirty  30  day period  a battery operated carbon monoxide detector with  an alarm shall be installed    2  APPROVED CARBON MONOXIDE DETECTORS  Each carbon  monoxide detector as required in accordance with the above provisions shall  comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified    3  SIGNAGE  A metal or plastic identification plate shall be permanently  mounted to the exterior of the building at a minimum height of eight  8  feet  above grade directly in line with the exhaust vent terminal for the horizon     40    tally vented gas fueled heating appliance or equipment  The sign shall read   in print size no less than one half  1 2  inch in size   GAS VENT DIRECTLY  BELOW  KEEP CLEAR OF ALL OBSTRUCTIONS     4  INSPECTION  The state or local gas inspector of the side wall horizon   tally vented gas fueled equipment shall not approve the installation unless   upon inspection  the inspector observes carbon monoxide detectors and  signage installed in accordance with the provisions of 248 CMR 5 08 2  a 1  through 4     b  EXEMPTIONS  The following equipment is exempt from 248 CMR  5 08 2  a 1 through 4    1  The equipment listed in Chapter 10 entitled  Equipment Not Required To  Be Vented  in the most current edition of NFPA 54 as adopted by the Board   and   2  Product Approved side wall horizontally vented gas fueled equipment in   stalled in a room or st
58. r heater     1 4    per ft  max  slope up or  down for horizontal venting     Blower assembly    Anode    Union   Optional     Shut off 7 U  valve    Shut off valve    ex To cold water supply    Thermal expansion tank   if required     Relief valve discharge line  to suitable open drain     Combustion Air  Inlet Openings    6    Air gap    Installing the water heater    A new combination temperature and pressure relief valve  complying with the Standard for Relief Valves  for Hot Water Supply Systems  ANSI Z21 22  is factory installed and must remain in the opening provided  and marked for the purpose on the water heater  No valve of any type should be installed between the  relief valve and the tank  Local codes shall govern the installation of relief valves     AWARNING  The tank  must be full of water before  heater is turned on  The  water heater warranty does  not cover damage or failure  resulting from operation  with an empty or partially  empty tank     10    Relief Valve    The pressure rating of the relief valve must  not exceed 150 psi  the maximum working  pressure of the water heater as marked on  the rating plate     The Btuh rating of the relief valve must  equal or exceed the Btuh input of the water  heater as marked on its rating plate     Position the outlet of the relief valve above  a suitable open drain to eliminate potential  water damage  Piping used should be of a  type approved for hot water distribution     To Fill the Water Heater    Make certain th
59. re all in place     Check the vent system terminal to see  that it is free from obstructions and  there is no damage nearby caused by  condensate     Inspect dilution air holes  Make  certain no blockage exists  Clean any  lint  dirt or oil accumulation that may  exist     Burner Inspection    Visually inspect the hot surface  ignitor and main burners periodically     Through the sight glass  inspect the  hot surface ignitor with the main  burner off and inspect the main  burner while firing     If any unusual burner operation is  noted  the water heater should be shut  off until qualified service assistance  can be obtained        DO NOT obstruct or block the  Flammable Vapor Sensor  The sensor  does not require any maintenance   or cleaning  DO NOT expose to  cleaning agents     Test for spillage at the dilution air  holes after 5 minutes of burner  operation  Place a blown out match or  candle close to the dilution air holes   The smoke from the candle or match  should be drawn into the dilution air  holes  If the smoke is pushed away  from the dilution air holes  the blower  or vent system may be blocked   Contact qualified service personnel     ACAUTION  For your safety   cleaning of the burner must be  performed only by qualified service  personnel  as it involves the  disconnection of gas piping and  leak testing  The burner chamber is  a Sealed area  If the burner access  door is removed  the burner access  door gasket must be replaced     For cleaning  remove the bur
60. rom exposure to freezing  temperatures     DO NOT install the water heater in  bathrooms  bedrooms  any occupied rooms  normally kept closed  or in unprotected  outdoor areas     Minimum clearance from combustible  construction     Pe tetele       Front  Clearance dimension is measured  from the water heater jacket to the closet door            Top  clearance dimension is measured  from the jacket top of the water heater to the  ceiling    If the clearances stated on the Instruction   Warning Label  located on the front of the  heater differ  install the water heater according  to the clearances stated on the label     If the water heater is installed in an alcove  or closet  the entire floor must be covered  by a wood or metal panel    A minimum of 24 in  clearance from   the front and top should be available for  adequate inspection and servicing     The water heater may be installed on  combustible floors  but not directly on  carpeting  If the water heater must be  installed on carpeting  place a metal or wood  panel beneath the water heater  extending  beyond its full width and depth at least 3 in   in all directions     NOTICE  For proper operation and  maintenance  a minimum clearance of 1 5  in  must be provided from the combination  temperature and pressure relief valve to any  wall or object  7    Installing the water heater    NOTICE  Do not install the  water heater in attics where  the temperature may exceed  100  F  This water heater is  equipped with a temperat
61. ructure separate from the dwelling  building or structure  used in whole or in part for residential purposes     c  MANUFACTURER REQUIREMENTS   GAS EQUIPMENT VENTING  SYSTEM PROVIDED  When the manufacturer of Product Approved side  wall horizontally vented gas equipment provides a venting system design or  venting system components with the equipment  the instructions provided   by the manufacturer for installation of the equipment and the venting system  shall include    1  Detailed instructions for the installation of the venting system design or  the venting system components  and   2  A complete parts list for the venting system design or venting system     d  MANUFACTURER REQUIREMENTS   GAS EQUIPMENT VENTING  SYSTEM NOT PROVIDED  When the manufacturer of a Product Approved  side wall horizontally vented gas fueled equipment does not provide the parts  for venting the flue gases  but identifies  special venting systems   the fol   lowing requirements shall be satisfied by the manufacturer    1  The referenced  special venting system  instructions shall be included with  the appliance or equipment installation instructions  and   2  The  special venting systems  shall be Product Approved by the Board   and the instructions for that system shall include a parts list and detailed  installation instructions     e  A copy of all installation instructions for all Product Approved side wall  horizontally vented gas fueled equipment  all venting instructions  all parts  lists for
62. section of this manual        Leaking or open hot  water faucets     Make sure all faucets are closed        Check valve error codes     Refer to gas control  thermostat  status code table on next  page           ON OFF    switch turned off     Turn    ON           Blower unplugged     Plug in  Verify power supply  120VAC         Combustion Shutoff System  tripped     The gas control  thermostat   is set too high     Contact a qualified service technician     See the    Water Temperature Setting    of The Water  Heater section of this manual        Gas Control  Thermostat   Defective     Contact a qualified service technician to replace the  gas control  thermostat         CAUTION  Label all wires prior to disconnection when servicing controls  Wiring errors can cause improper and dangerous  operation  VERIFY PROPER OPERATION AFTER SERVICING        CAUTION  For your safety DO NOT attempt repair of gas piping  gas control  thermostat   burners  vent system or other  safety devices  Refer repairs to qualified service personnel     34    LED Status    VABC   ooe eood    Problem    An open earth ground circuit to the  ignition system     Gas Control  Thermostat  Status Codes       Solution  1  Check that the earth ground connection is properly  connected   2  Check that the ground conductor on the water  heater is properly connected                             VABC 1  Check proper connection of line  Oe ex Wiring error or a high resistance to neutral and hot wires   earth ground 
63. sing property damage  personal injury or death     A FOR YOUR SAFETY         Do not store or use gasoline or other If you cannot reach your gas supplier  call the  flammable vapors or liquids or other fire department     combustible materials in the vicinity of this or Do not return to your home until authorized    any other appliance  To do so may result in an by the gas supplier or fire department   explosion or fire  3            Improper installation  adjustment  alteration         WHAT TO DO IF YOU SMELL GAS service or maintenance can cause property  damage  personal injury  or death  Refer to  this manual  Installation and service must be  performed by a qualified installer  service  agency or the gas supplier     Do not try to light any appliance     Do not touch any electrical switch  do not  use any phone in your building     Immediately call your gas supplier from a  neighbor   s phone  Follow the gas supplier   s  instructions        AP17509  01 15     Safety Information  Safety Precautions        3 6  RGasilViocdel Sie eee 5    Installation Instructions  ocat omt ea eee E T    Water Supply Connections    9    GaS SUPPIV E T 11  Ventine E 13 20  Wiring Diagram            21  Pipe Insulation          22 23  nea lllita pS ree eee 28   Installation Checklist        24    Potable Space Heating      25    Operating Instructions  Lighting Instructions       26  Water Temperature       27 28    Care and Cleaning    Vent System Inspection     31    Burner Inspection       
64. sonal injury   or death could result     AWARNING  Failure to  install a water heater  suitable for the altitude at  the location it is intended  to serve  can result in  improper operation of the  appliance resulting in  property damage and or  producing carbon  monoxide gas  which  could result in personal  injury  or death     Gas Supply    The branch gas supply line to the water  heater should be clean 1 2 in  black steel  pipe or other approved gas piping material     A union or ANSI design certified semi   rigid or flexible gas appliance connector  should be installed in the gas line close to  the water heater  The National Fuel Gas  Code  NFGC  mandates a manual gas  shut off valve  See  NFGC  for complete  instructions     If flexible connectors are used  the  maximum length shall not exceed 36 in   and must meet the requirements in ANSI  Z21 24 Connectors for Gas Appliances     Compound used on the threaded joints of  the gas piping must be of the type resistant  to the action of LP gas  Use compound  sparingly on male threads only     Where a sediment trap is not incorporated  as part of the appliance  a sediment trap  shall be installed downstream of the    Leak Testing    The water heater and its gas connections  must be leak tested at normal operating  pressures before it is placed in operation     q  Turn on the manual gas shut off valve  near the water heater     3  Use a soapy water solution to test for    equipment shutoff valve as close to the  inlet of the 
65. st    Slope 1 8 in  per foot   10 mm per m  towards  the water heater          and  pea A in  Ae cm  Optional   Condensate  ove Roo     Without Additional Management Drain  Support  Port    Optional   Condensate  Management Drain             Alternate Vent Pipe Through Roof          Exhaust Vent Pipe Through Roof     See Condensate Management Section for additional information about optional piping     18       NOTICE  Vent  riser fittings   and pipe must  be included in  the total vent  length calcula   tion as described  in the manual     ACAUTION   Make sure  drain port cap  is securely in  place     NOTICE  Some  models are not  supplied with   a drainable  coupling  If  condensation is  required  please  contact the  service depart   ment listed on  the back of this  manual     Condensate Management and Vent Risers    There is no condensate collection and disposal  required for Rheem water heaters under most  conditions  Installations where the vent run is  short or it runs through conditioned space in the  home  such as basements or interior walls  do not  typically cause condensation and will not require  any condensation disposal methods regardless of  vent pipe slope  Figure 1 shows the recommended  vent pipe slope of no less than 1 8 inch per foot  away from the water heater  Any condensation   in the venting system will drain toward the vent  termination  The blower pipe coupling features a  capped drain port which is not needed in this case     Slope ie           
66. sulfide  or rotten egg odor in the  heated water  Chlorination of the water  supply should minimize the problem     Before You Call For Service       Troubleshooting Tips    Save time and money  Review the charts on the following pages first and you may not need to call for service     down if undesirable combustion conditions occur  such as the presence of flammable vapors or blockage of      This water heater incorporates a combustion shut off device that shuts the operation of the water heater    the combustion air inlet openings  Please contact a Qualified Service Technician if this occurs     Problem Possible Causes    Condensation This usually happens when  a new water heater is    filled for the first time     What To Do    This is normal  After the water in the tank warms  up  the condensation will disappear  If  however  the  condition persists  examine the piping and fittings  for possible leaks        Moisture from the products  of combustion condensing  on the tank surface     This is normal and will disappear in time  Excessive  condensation can cause main burner outage        An undersized water  heater will cause  condensation     Yellow flame Scale on top of the burner     Use a water heater size that meets the requirements  of your needs     Contact a qualified service technician to remove scale        or soot 7    Vent System or Combustion air    inlet openings are restricted     Remove obstruction or debris from vent system or  combustion air inlet openings
67. t   This could result in an unsafe operating  condition     Hot and Cold Pipe Insulation Installation       Typical vertical piping arrangement    For increased energy efficiency  some  water heaters have been supplied with  two 24    sections of pipe insulation        Typical horizontal piping arrangement    Please install the insulation  according   to the illustrations above  that best meets  your requirements  Blower assembly not  shown        T amp P Insulation Installation    For increased energy efficiency  this water heater has been supplied with a 2 3 8 in   section of T amp P insulation  Please install the insulation as shown below        Typical Side Connect T  amp  P Arrangement     Heat Traps    For increased energy efficiency  some water  heaters have been supplied with factory  installed 1 in  NPT heat traps in the hot  outlet line and cold water inlet line     Slip the insulation cover over the T amp P  Valve through the center hole and align  the hole in the side with the opening of the  T amp P Valve     Ensure the T amp P Valve opening is not  obstructed by the insulation     Blower Assembly not shown     These heat traps may require a minimum  of one  1  90   1 in  NPT elbow and may  require an additional 90   1 in  NPT elbow  or a 1 in  coupling depending on your  installation needs  See llustration of nipples  and heat traps on pages 36     During Installation of this water heater    DO    Q DO check inlet gas pressure to ensure  that it is within the ra
68. t setting by first depressing the COOLER  and HOTTER  buttons atthe same time and holding for  1  second  Depress the COOLER button    until only the WARM indicator lightis lit     2  Toggle the   ON OFF    switch located on the blower assembly to the    OFF    position     3  Turn off all electrical power to the appliance        Operating the water heater          CAUTION  Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a  long period of time  generally two weeks or more   HYDROGEN GAS IS EXTREMELY FLAMMABLE   To dissipate such  gas and to reduce risk of injury  it is recommended that the hot water faucet be opened for several minutes at the kitchen sink  before using any electrical appliance connected to the hot water system  If hydrogen is present  there will be an unusual sound  such as air escaping through the pipe as the water begins to flow  DO NOT smoke or use an open flame near the faucet at the  time it is open     Safety Precautions    A  DO turn off manual gas shut off valve if water heater E DO NOT store or use gasoline or other flammable    has been subjected to over heating  fire  flood   physical damage or if the gas supply fails to shut off     DO NOT turn on water heater unless it is completely    vapors and liquids  such as adhesives or paint thinner   in vicinity of this or any other appliance  If such  flammables must be used  open doors and windows    filled with water        DO NOT turn on water 
69. t so a water trap is not created   See Figures 4  amp  5 as examples of a vertical instal   lations with condensation removal tube and trap                                                     aaa    ny  O L D  Figure 4 Figure 5    A vent riser is used when the vent termination can   not be located above grade or snow lines  Power  vented water heaters installed with a vent riser  should have a slope toward the water heater if the  venting is long and passes through unconditioned  spaces  It is recommended that these installa   tions have the condensate collection and disposal  method defined previously  Figure 6 shows a  condition where a vent riser is necessary to meet  the minimum clearance  Note that the vent pipe  must slope back to the water heater so that a water  trap is not created at the outside 90 degree elbow     Side View              Q       pim    Termination Openings    5 12 in   30 5 cm  min  above  grade or anticipated snow level    y      Clearance is 4  from back of elbow to wall                          gt     lt                       Figure 6  19    Installing the water heater    20    NOTICE  All pipe  fittings  solvent cement  primers and procedures must conform to American  National Standards Institute and American Society for Testing and Materials  ANSI ASTM  standards     AWARNING  DANGER  OF FIRE OR BODILY  INJURY   Solvent cements  and primers are highly  flammable  Provide  adequate ventilation and do  not assemble near heat  source or open flame 
70. t z A es wf Flue baffle and hanger  Trap T  Nipple f              a Dip tube  I  lt        Dip tube gasket       Anode rod        Temperature and pressure  relief valve    Flammable Vapor Sensor     Burner Access Door Gasket           Burner orifice   Tgniter        Burner Access Door j     Combustion Shut off Device  enlarged view                          A      T             Located inside the combustion chamber     36       CAUTION  For your safety  DO  NOT attempt repair of gas piping    gas control  thermostat   burners    vent connectors or other safety devices   Refer repairs to qualified service  personnel     Use only original equipment  replacement parts       Burner Assembly Kit       The kit provides extra speed clips  and tamper resistant screws        May differ in actual appearance     Jacket Door     Hot Surface Igniter Assembly Grommet    Notes     37    Notes     Notes     39    IF YOU NEED SERVICE    1  Should you have any questions about your new water heater  or if it requires adjustment  repair  or routine    maintenance  it is suggested that you first contact your installer  plumbing contractor or previously agreed upon  service agency  In the event the firm has moved  or is unavailable  refer to the telephone directory  commercial  listings or local utility for qualified service assistance     2  Should your problem not be solved to your complete satisfaction  you should then contact the Manufacturer   s National  Service Department at the following ad
71. tances such as bleach or cleaners  See the    Gas  Valve LED Error Code    Section of this manual for a list of error codes     ADANGER   INSTALL THE BLOWER ASSEMBLY AND PROPERLY VENT  T THE WATER HEATER    Failure to install the blower assembly and properly vent the water heater to the outdoors   as outlined in the Venting Section of the Installation Instructions in this manual can result   in unsafe operation of the water heater  To avoid the risk of fire  explosion  or asphyxiation  from carbon monoxide  never operate this water heater unless it is properly vented and has  an adequate air supply for proper operation  Be sure to inspect the vent system for proper  installation at initial start up  and at least annually thereafter  Refer to the Care and Cleaning  section of this manual for more information regarding vent system inspection     A AWARNING     Gasoline  as well as other flammable materials and liquids  which include but are not limited to  adhesives  solvents  paint thinners etc    and the vapors they produce are extremely dangerous   DO NOT handle  use or store gasoline or other flammable or combustible materials anywhere  near or in the vicinity of a water heater or any other appliance  Be sure to read and follow  warning label pictured below and other labels on the water heater  as well as the warnings  printed in this manual  Failure to do so can result in property damage  bodily injury or death        Flammable Vapors    FIRE AND EXPLOSION HAZARD  Can resu
72. ter     ADANGER  Before manually operating  the temperature and pressure relief  valve  make certain no one will be  exposed to the hot water released by the  valve  The water drained from the tank  may be hot enough to present a scald  hazard and should be directed to a  suitable drain to prevent injury or  damage     Before turning off the cold water supply to  the water heater  open a hot water faucet  allowing sufficient cold water into the  tank to prevent the risk of a scald injury  while draining the water heater  Once the  water in the tank is no longer hot  turn off  the cold water supply to the water heater   Open a hot water faucet or lift the handle  on the relief valve to admit air to the tank     Attach a garden hose to the drain valve on  the water heater and direct the stream of  water to a drain  Open the valve     Routine Preventative Maintenance    Properly maintained  your water heater  will provide years of dependable trouble   free service     It is recommended that a periodic  inspection of the gas control  thermostat    burner  relief valve and venting system  should be made by service personnel  qualified in gas appliance repair     It is suggested that a routine preventative  maintenance program be established and  followed by the user     Inspect plastic vent pipe  Make certain  that all joints are secure and that vent  pipe supports are all in place  Check the  outdoor vent terminal to see that it is  free of obstructions  and that there is no  dam
73. ter heater  any part of your water heater unless it is  specifically recommended in this manual   All other servicing should be referred to a  qualified technician     Use this appliance only for its intended  purpose as described in this Use and Care  Manual     Be sure your appliance is properly installed  in accordance with local codes and the  provided installation instructions     v    READ AND FOLLOW THIS SAFETY INFORMATION  1 CAREFULLY        ON    SAVE THESE INSTRUCTIONS    Installing the water heater       This water heater must be installed in accordance with these instructions  local codes  utility company  requirements  and or in the absence of local codes  use the latest edition of the American National  Standard National Fuel Gas Code  A copy can be purchased from either the American Gas Association   400 N  Capitol Street NW  Washington  DC 20001 as ANSI standard Z223 1 or National Fire Protection  Association  1 Batterymarch Park  Quincy  MA 02269 as booklet NFPA 54     Combustion Air Inlet  Openings       Flammable  gt   Vapor   Diameter of  Sensor le    water heater    plus 2    min     The auxiliary drain pan  installation MUST conform  to local codes     NOTICE  DO NOT allow  the drain pan to obstuct  the flammable vapor  sensor     NOTICE  DO NOT  allow the flammable  vapor sensor to become  submerged in water   Make sure the drain pan  is properly drained     A WARNING  Combustible  construction refers to  adjacent walls and ceilings  and should not be c
74. uch as clothing   cleaning materials  rags  etc  clear of the base  of the heater     Q Clearances of 1 in  from combustion air inlet  openings observed       Q Flammable vapor sensor is not blocked     Q Water connections tight and free of leaks     L  Soap and water solution used to check all  connections and fittings for possible gas  leak     L  Gas Company inspected installation  if  required           Discharge line protected from freezing     L  Vent system supported at required intervals   U Appropriate minimum clearances observed     Q Precautions taken to prevent moisture  damage around vent termination        Q Vapors from vent pipe cement and primer  have dissipated prior to applying electrical  power        Heater properly grounded and proper  polarity observed     Supplemental instructions for gas water heaters installed in  potable water space heating applications    Local codes or plumbing authority requirements may vary from the instructions or diagrams provided in this  manual and take precedent over these instructions                                   Hot water Combination Potable Water and Space Heating Application  t uppi    Tee fitting must be installed as shown  This NOTICE  Suitable for  potable  water  ensures that any air in the water lines will be heating and space heating applications  DO     purged through the domestic water faucets and NOT use for space heating application only   Hot water showers  ADANGER  If this water heater is installed  supp
75. umber or the  local plumbing authority for further information     4    Time Temperature Relationship in Scalds                                Water Temperature Time To Produce a Serious Burn     120  F More than 5 minutes   125  F 1  2 to 2 minutes   130  F About 30 seconds   135  F About 10 seconds   140  F Less than 5 seconds   145  F Less than 3 seconds   150  F About 1  2 seconds   155  F About 1 second       Table courtesy of Shriners Burn Institute    The chart shown above may be used as a guide in  determining the proper water temperature for your home     ADANGER  Households with small children   disabled  or elderly persons may require a 120  F  or lower gas control  thermostat  setting to prevent  contact with    HOT    water     Maximum water temperatures occur just after the burner  has shut off  To find water temperature being delivered   turn on a hot water faucet and place a thermometer in the  water stream and read the thermometer   See page 27 for  more details      The temperature of the water in the heater can be  regulated by pressing the temperature buttons on the front  of the gas control  thermostat   To comply with safety  regulations the gas control thermostat  was set at its  lowest setting before the water heater was shipped from the  factory     The illustration below details  he approximate water  emperature for each mark on  he Gas Control  Thermostat   emperature Dial         VACATION    WV a B c     OOOO 00   COOLER 9 S  HOTTER    A warnine  A
76. ure  sensing device that will   shut off the water heater   if the maximum allowable  vent pipe temperature is  exceeded     NOTICE  The water heater  should not be installed near  an air supply containing   halogenated hydrocarbons     Inspect Shipment    Inspect the water heater for possible damage  Check the markings on the rating plate of  the water heater to be certain the type of gas supplied corresponds to the water heater    requirements     Combustion and Ventilation Air    Ventilation  ambient  air temperature  must be 100  F or less  Proper operation  of the water heater requires air for  combustion and ventilation  Provisions  for combustion and ventilation air  must comply with referenced codes and  standards     DO NOT block or obstruct any of the  combustion air inlet openings located  around the perimeter of the water  heater  A minimum of lin  is required  between these combustion air inlet  openings and any obstruction     NOTICE  If the water heater is  installed in an unconfined space within a  building of conventional frame  masonry  or metal construction  infiltration   air is normally adequate for proper  combustion and ventilation  If the   water heater is installed in a confined  space  provisions for combustion and  ventilation air must be made     DO NOT obstruct or block the  Flammable Vapor Sensor     A confined space is one having a volume  of less than 50 cubic feet per 1000 Btuh  of the aggregate input of all appliances  within that space     T
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
User manual - Australian Leisure Facilities Association  HDR-TG1  GE WWA6600R User's Manual  AVVERTENZA AVVERTENZA AVVERTENZA    Copyright © All rights reserved. 
   Failed to retrieve file