York Sunline 2000 User's Manual
Contents
1. VOLTAGE OUTDOOR SUPPLY MAX MAX MODEL POWER SUP LIMITATIONS COMPRESSOR FAN AIR MINIMUM FUSE HACR BCH PLY SEE NOTE 1 MOTOR BLOWER CIRCUIT SIZE BREAKER MIN MAX RLA LRA FLA MOTOR AMPACITY SEE NOTE 2 SIZE ELA AMPS AMPS 208 230 1 60 187 253 19 0 105 1 7 5 3 34 1 50 50 036 208 230 3 60 187 253 11 9 85 1 7 5 3 21 9 30 30 460 3 60 414 504 5 9 42 1 0 3 1 11 5 15 15 575 3 60 518 630 4 8 34 1 0 3 1 11 1 15 15 208 230 1 60 187 253 25 0 105 2 3 8 6 38 6 60 60 04g 208 230 3 60 187 253 14 7 130 2 3 5 2 25 9 40 40 460 3 60 414 504 7 7 64 1 4 2 6 13 6 20 20 575 3 60 518 630 6 4 52 1 4 2 0 11 4 15 15 208 230 1 60 187 253 32 1 169 2 3 8 6 51 4 80 80 060 208 230 3 60 187 253 19 3 123 23 6 0 32 4 50 50 460 3 60 414 504 10 0 62 1 4 3 0 16 9 25 25 575 3 60 518 630 7 9 50 1 4 2 4 13 7 20 20 NOTES 1 Utilization Range in accordance with ARI Standard 110 2 Dual element time delay type ELECTRICAL DATA Heat Pump with Supplemental Electric Heat Belt Drive HEATER ps ELECTRIC HEATERS MAX B MODEL POWER ACCESSORY BLOWER CIRCUIT FUS HACR2 BCH SUPPLY MODEL TOTAL SIZE MOTOR KW STAGES AMPACITY BREAKER NUMBER FLA AMPS AMPS AMPS 2CE04510506 4 0 1 19 1 58 0 70 70 2CE04510706 5 6 1 27 1 67 9 80 80 208 1 60 2 04511006 8 6 8 0 1 38 3 81 9 90 90 2 04511506 11 9 2 57 4 105 8 110 110 2 04512006 15 9 2 76 6 129 7 150 150 2 04510506 5 3 1 22 1 61 7 70 70 2
2. 5 RET AIR CAP OUTDOOR AIR TEMPERATURE F 72 RH amp KW 10 0 10 20 30 40 50 60 55 MBH 13 1 16 4 23 5 29 1 30 2 41 7 47 0 48 2 KW 2 9 3 0 3 2 3 3 3 5 3 7 3 8 3 9 4750 70 MBH 11 9 15 0 21 5 26 7 27 7 38 2 43 1 44 1 KW 3 0 3 1 3 4 3 4 3 6 3 8 3 9 4 1 80 MBH 10 9 13 6 19 6 24 3 25 2 34 8 39 3 40 2 KW 3 1 3 2 3 4 3 5 3 8 3 9 4 1 4 2 55 MBH 12 4 15 5 22 5 27 7 28 7 39 6 44 7 45 8 KW 2 7 2 9 3 0 3 1 3 3 3 5 3 6 3 7 4400 70 MBH 11 4 14 1 20 3 25 2 26 1 36 1 40 7 41 6 KW 2 9 3 0 3 2 3 3 3 5 3 7 3 8 3 9 80 MBH 10 4 13 1 18 0 23 2 24 2 33 3 37 6 38 5 KW 3 0 3 1 3 2 3 4 3 6 3 8 3 9 4 0 55 MBH 11 8 14 8 21 3 26 5 27 5 37 8 42 7 43 7 KW 2 7 2 8 3 0 3 1 3 3 3 4 3 5 3 6 4200 70 MBH 10 8 13 5 19 4 24 0 24 9 34 4 38 8 39 7 KW 2 9 3 0 3 1 3 3 3 4 3 6 3 7 3 8 80 MBH 9 9 12 4 17 8 22 0 22 9 31 5 35 6 36 5 KW 2 9 3 1 3 2 3 4 3 5 3 7 3 8 3 9 55 MBH 11 2 14 1 20 3 25 2 26 1 35 9 40 6 41 6 KW 2 6 2 7 2 9 3 0 3 3 3 3 3 5 3 5 4050 70 MBH 10 2 12 8 18 5 22 8 23 6 32 7 36 9 37 8 KW 2 8 2 9 3 0 3 2 3 3 3 5 3 6 3 7 80 MBH 9 3 11 7 16 7 20 7 21 5 29 8 33 6 34 4 KW 2 8 3 0 3 1 3 3 3 4 3 6 3 7 3 8 55 MBH 12 3 17 3 22 5 28 2 36 3 44 5 53 8 61 6 KW 3 4 3 5 3 6 3 6 3 8 4 0 4 6 5 2 2000 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 55 MBH 12 1 17 0 22 0 27 7 3
3. COOLING CAPACITIES 4 TON 48 Air Temperature of Air on Outdoor Coil Indoor 85 F 95 F Coil Total Power Sensible Capacity MBH Total Power Sensible Capacity MBH crm WB Cap Input Entering Dry Bulb F Cap Input Entering Dry Bulb F eF MBH KW 86 83 80 77 74 71 68 MBH KW 86 83 80 77 74 71 68 53 4 5 40 35 29 24 2000 51 4 4 46 45 41 35 30 24 46 4 3 46 46 45 41 35 30 24 46 4 3 46 46 46 41 35 30 24 53 4 4 38 33 28 23 1800 51 4 4 44 44 39 34 29 24 47 4 3 47 47 45 40 6 31 26 45 4 2 45 45 45 40 35 30 25 52 4 4 36 32 27 23 1600 50 4 3 44 43 38 34 29 25 45 4 2 45 45 44 40 36 31 27 44 4 1 44 44 44 40 36 31 27 49 4 3 33 29 25 21 1400 47 4 2 42 38 34 30 26 22 43 4 1 43 42 40 36 32 28 24 42 4 1 42 42 40 36 32 28 24 47 4 2 29 25 22 18 1200 45 4 2 37 34 30 27 23 20 40 4 1 40 39 36 32 29 25 22 40 4 0 40 39 36 32 29 25 22 Air On Temperature of Air on Outdoor Coil Indoor 105 F 115 F Coil Total Power Sensible Capacity MBH Total Power Sensible Capacity MBH CFM WB Input Entering Dry Bulb
4. eF MBH KW 86 83 80 77 74 71 68 MBH KW ge 83 80 77 74 71 68 60 6 9 50 43 37 30 350 54 66 54 p 4134 27 49 6 5 49 49 42 35 28 22 49 6 5 49 49 49 43 35 28 23 60 6 8 47 41 35 29 2250 54 6 6 47 47 45 39 32 26 49 6 5 49 49 47 42 36 30 24 49 6 4 49 49 43 37 31 25 59 6 8 44 38 33 27 2000 53 6 5 45 45 42 36 31 26 48 6 4 48 48 46 42 36 31 25 47 6 4 47 47 43 36 32 25 56 6 7 40 35 30 25 1750 51 6 5 43 43 38 33 29 24 46 6 4 46 46 43 38 33 28 24 45 6 3 45 45 43 38 33 28 25 53 6 6 36 31 27 23 1500 48 6 4 41 39 35 30 26 22 44 6 3 44 44 39 35 30 26 22 43 6 2 43 43 40 36 30 26 23 These capacities are gross ratings For net capacity determine the KW of the supply air blower motor from the Blower Performance Table multiply this value by 3 415 MBH KW to determine the motor heat and deduct this heat from the gross capacity of the unit These ratings include the compressor and the outdoor fan motors but not the supply air blower motor The total outdoor fan motor power input is 0 35 KW Refer to the Blower Performance Table for the KW of the supply air blower motor 1 NOMINAL RATING ALL SENSIBLE CAPACITY 6 Unitary Products Group 036 21564 003 1005
5. 4 Unit Controls A Unit shall be complete with self contained low voltage control circuit protected by a resetable circuit breaker fuse on the 24 volt transformer side B Unit shall incorporate a lock out circuit which provides reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor Unitary Products Group 036 21564 003 1005 1 Loss of charge Low pressure switch 2 High pressure switch If any of the above safety devices trip an LED light emitting diode indicator shall illuminate C Unit shall incorporate AUTO RESET compressor over temperature over current protection D Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook up E Unit shall have freeze protection thermostat on evapo rator coil F Unit shall incorporate an ambient compensated time and temperature defrost control 1 Defrost shall be initiated on the basis of time and liq uid line temperature 2 A50 80 110 minute timer shall activate defrost cycle only if liquid line temperature is low enough to indicate a heavy frost condition 3 Defrost cycle shall terminate when liquid line sensor is satisfied and shall have a positive termination time of 10 minutes ELECTRIC HEATING SECTION JE An electric heating section with nickel chromium ele ments shall be provi
6. Barometric Relief Fixed 10 048 668 189 185 146 148 Outdoor Air Intake Damper 060 693 196 192 151 154 Roof Mounting Curb 92 Belt Drive Blower 5 CORNER BACK 44 82 CORNER A CORNER OUTDOOR COIL END OF UNIT APPROXIMATE CENTER OF GRAVITY FRONT 19 CENTER OF GRAVITY 17 Unitary Products Group FACTORY INSTALLED OPTIONS ECONOMIZERS Units equipped with the factory installed economizer option have dampers that are positioned by a spring return fully modulating damper actuator capable of introducing up to 100 outdoor air As the outdoor air intake dampers open the return air dampers close The changeover from mechanical refrigeration to economizer operation is determined by a single input electronic enthalpy control or by a dual input electronic enthalpy control Simultaneous compressor and economizer operation is also possible The single enthalpy system contains a sensor that monitors the outdoor air which automatically operates the damper actuator allowing the dampers to open or close 036 21564 003 A 1005 The dual enthalpy system contains a second sensor that monitors the return air in addition to monitoring the outdoor air described above for a single enthalpy system The logic module compares these two values and modulates the dampers providing the maximum efficiency of the economizer system The economizer is completely installed and wired at the factory Only the outdoor air hood includ
7. 1 72 9 100 100 2 04510706 56 1 27 1 82 9 100 100 208 160 2CE04511006 80 1 38 3 96 9 110 110 2 04511506 11 9 2 574 1208 125 125 2 04512006 159 2 76 6 1447 150 150 2 04513006 222 2 106 9 1826 200 200 2 04510506 53 1 22 1 76 6 100 100 2 04510706 75 1 31 2 88 1 110 110 230 160 2CE04511006 2s 10 6 1 442 104 2 125 125 2 04511506 159 2 66 2 131 8 150 150 2 04512006 21 2 2 88 3 159 4 175 175 2 04513006 29 6 2 123 3 203 2 225 225 2CE04510525 4 0 1 11 0 46 8 60 60 2CE04510725 56 1 156 526 60 60 2 04511025 80 1 22 1 60 6 70 70 208 3 60 20E04511525 6 6 11 9 2 33 1 745 80 80 b 2CE04512025 159 2 442 88 3 90 90 2 04513025 222 2 61 7 110 2 125 125 2CE04510525 5 3 1 12 7 49 0 60 60 2CE04510725 75 1 180 55 6 70 70 2 04511025 106 1 25 5 649 70 70 230 3 60 56604511525 6 6 15 9 2 38 2 80 0 90 90 2 04512025 212 2 510 96 8 100 100 2 04513025 29 6 2 712 122 0 125 125 2CE04510746 6 8 1 8 2 274 35 35 2CE04511046 10 1 1 12 1 32 3 35 35 460 3 60 2 04511546 3 3 13 6 1 16 4 37 6 40 40 2CE04512046 19 5 2 23 5 46 5 50 50 2CE04513046 28 8 2 34 6 60 5 70 70 2CE04511058 10 6 1 10 2 27 3 30 30 2 04511558 159 1 15 3 33 6 35 35 575 3 60 2CE04512058 3 3 21 2 2 20 4 40 1 45 45 2 04513058 304 2 29 3 51 1 60 60 See Notes on Page 11 12 Unitary Products Group 036 21564 003 1005 ELECTRICAL DATA Basic Unit Belt Drive
8. 4 1 34 34 33 31 27 23 19 33 4 1 998 31 27 23 19 41 4 2 29 25 21 18 15 1500 35 4 1 30 28 25 22 18 15 11 33 4 1 33 33 32 29 25 22 19 32 4 1 S22ES2ENS2N 29 26 22 19 39 4 2 26 23 19 16 13 1400 34 4 1 30 27 24 21 17 15 11 32 4 1 32 31 30 27 24 20 17 32 4 0 32 32 31 28 24 21 18 37 4 2 24 21 18 15 12 1200 32 4 1 28 24 22 19 17 14 10 30 4 1 30 29 28 25 22 19 16 29 4 0 29 29 29 25 23 20 17 35 4 1 21 19 17 14 12 1050 31 4 0 25 22 20 18 15 12 10 29 4 0 29 28 26 24 21 19 16 28 4 0 28 28 26 24 21 19 17 34 4 1 19 18 15 12 11 900 29 4 0 23 20 18 16 14 12 10 27 4 0 27 25 24 21 18 17 15 26 4 0 26 26 23 22 19 17 15 These capacities are gross ratings For net capacity determine the KW of the supply air blower motor from the Blower Performance Table multiply this value by 3 415 MBH KW to determine the motor heat and deduct this heat from the gross capacity of the unit These ratings include the compressor and the outdoor fan motors but not the supply air blower motor The total outdoor fan motor power input is 0 35 KW Refer to the Blower Performance Table for the KW of the supply air blower motor _ NOMINAL RATING ALL SENSIBLE CAPACITY 4 Unitary Products Group 036 21564 003 1005
9. 575 VOLTS Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 818 665 858 740 898 820 940 890 980 950 1500 842 695 882 755 922 835 962 895 1400 833 650 867 705 904 765 942 820 1300 858 665 893 725 932 785 1200 847 640 880 680 916 730 Available External Static Pressure IWG AR 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003 945 1044 995 1086 1035 1400 982 880 1024 920 1067 965 1107 1000 1300 970 835 1010 870 1053 920 1099 960 1200 953 780 992 815 1034 855 1080 905 NOTE
10. 6 146 7 150 150 2 04513006 222 2 106 9 1846 200 200 2 04510506 53 1 22 1 78 6 100 100 2 04510706 75 1 31 3 90 1 110 110 230 160 2CE04511006 a 10 6 1 44 2 106 2 125 125 2 04511506 159 2 66 3 133 8 150 150 2 04512006 21 2 2 88 3 161 4 175 175 2 04513006 296 2 123 3 205 2 225 225 2CE04510525 4 0 1 11 0 46 2 60 60 2CE04510725 56 1 156 520 60 60 2 04511025 80 1 22 1 60 0 70 70 208 3 60 5604511525 6 0 11 9 2 33 1 73 9 80 80 2 04512025 15 9 2 442 877 90 90 2 04513025 222 2 61 7 109 6 110 110 2CE04510525 5 3 1 12 7 48 4 60 60 2CE04510725 75 1 180 55 0 60 60 2 04511025 106 1 25 5 643 70 70 230 3 60 5604511525 6 0 15 9 2 38 2 80 2 90 90 2 04512025 212 2 510 96 2 100 100 2 04513025 296 2 712 1214 125 125 2CE04510746 6 8 1 8 2 27 1 35 35 2CE04511046 10 1 1 12 1 32 1 35 35 460 3 60 2 04511546 3 0 13 6 1 16 4 373 40 40 2CE04512046 19 5 2 23 5 46 2 50 50 2CE04513046 28 8 2 34 6 60 2 70 70 2CE04511058 10 6 1 10 2 26 4 30 30 2 04511558 159 1 15 3 32 8 35 35 575 38 60 2CE04512058 212 2 204 39 2 40 40 2 04513058 304 2 29 3 50 2 60 60 See Notes on Page 13 14 Unitary Products Group 036 21564 003 1005 UNIT DIMENSIONS BCH 3 4 amp 5 CONTROL BLOWER FIELD SUPPLIED BOX DISCONNECT SWITCH ACCESS LOCATION Direct Drive Units FILTER ACCESS 3 4 PVC FEMALE COND DRAIN See Detail A BOTTOM SUPPLY amp RET
11. E GIER CZE 44 718 1 REAR VIEW L H END VIEW 4 3 8 DIMENSION FIXED OUTDOOR 12 AIR DAMPER MOTORIZED DAMPER 16 1 2 DETAIL UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD 16 Unitary Products Group 036 21564 003 1005 ROOF CURB DIMENSIONS BCH 3 4 amp 5 TON 55 TYP AND OUTDOOR COIL END OF UNIT DUCT SUPPORT LAA BACK OF UNIT RETURN AIR 19 1 2 OF UNIT 37 134 lt Supply and Return Air including duct support rails DUCT SIZES N p supp F z W shown are typical for bottom duct applications Supply Air 19 x 19 DN Return Air 19 x 19 For location of horizontal duct applications on back of unit refer to Unit Dimension details 3 4 X 1 1 4 WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES 2 UNIT BASE WOOD L UNIT BASE RAILS 8 MIN ABOVE FINISHED ROOF COUNTERFLASHING CURB FRAME F pr A CANT STRIP 3 INSULATION AND ROOFING MATERIAL N ROOF DECK AND SUPPORT STRUCTURE COMPONENT WEIGHTS AND CENTER OF GRAVITY OPTIONS ACCESSORIES BASIC UNIT 5 7KWI 18 CORNER WEIGHTS 11 10 15 23 UNIT 07 location Ibs 20 30 KW 28 p D Economizer 50 GB 628 178 174 137 439 Motorized Outdoor Air Damper 26
12. F Input Entering Dry Bulb F oF MBH KW 86 83 80 77 74 71 68 MBH KW g6 83 80 77 74 71 68 49 5 2 39 34 29 23 2000 41 5 0 40 40 37 32 26 21 40 49 40 40 39 34 29 23 18 40 4 8 40 40 40 34 30 24 19 47 5 1 37 32 27 22 1800 40 4 9 37 36 35 30 25 20 39 4 8 39 39 37 34 29 24 19 38 47 38 38 38 33 30 25 20 46 51 34 29 25 20 1600 39 4 9 36 36 32 28 23 19 37 4 7 37 37 36 33 28 24 19 37 4 7 37 37 37 34 28 25 20 44 5 0 31 27 23 19 1400 37 4 8 36 34 30 26 21 17 36 4 7 36 35 34 30 26 22 18 36 4 6 36 36 34 31 26 23 19 42 4 9 28 24 21 17 1200 36 4 7 34 31 27 24 20 17 35 4 6 35 34 30 28 24 20 17 35 4 6 35 35 31 29 24 21 18 These capacities are gross ratings For net capacity determine the KW of the supply air blower motor from the Blower Performance Table multiply this value by 3 415 MBH KW to determine the motor heat and deduct this heat from the gross capacity of the unit These ratings include the compressor and the outdoor fan motors but not the supply air blower motor The total outdoor fan motor power input is 0 35 KW Refer to the Blower Performance Table for the KW of the supply air blower motor NOMINAL RATING ALL SENSIBLE CAPACITY Unitary Products Group 036 2
13. FOR 208 VOLTS MULTIPLY VALUES BY 0 95 INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS 48 SIDE DUCT APPLICATIONS 230 460 575 VOLTS Available External Static Pressure IWG MODEL BCH 048 MODEL BCH 048 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 95 SA 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 818 665 858 740 898 820 940 890 980 950 1500 842 695 882 755 922 835 962 895 1400 833 650 867 705 904 765 942 820 1300 858 665 893 725 932 785 1200 847 640 880 680 916 730 Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2000 1103 1270 1900 1085 1210 1800
14. STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRF SUPPLY AIR BLOWER PERFORMANCE BCH036 048 8 060 with Direct Drive 230 460 575 VOLTS SIDE DUCT APPLICATIONS LOWS Available External Static Pressure IWG eren 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM Watts Watts Watts Watts Watts CFM Watts Watts 1720 825 1665 795 1600 765 1540 735 1490 700 1380 670 036 1660 850 1630 820 1590 780 1550 750 1500 720 1450 690 1400 665 1360 650 1270 610 LOW 1470 750 1440 725 1410 700 1370 675 1330 650 1290 625 1250 610 1220 600 1130 560 HI 2000 1010 1950 975 1905 945 1840 910 1770 825 1660 825 1530 775 048 MED 1810 910 1780 880 1740 850 1700 825 1665 800 1620 775 1560 740 1480 700 1390 660 LOW 1635 810 1610 1780 1580 760 1555 740 1540 730 1510 715 1460 690 1400 660 1300 615 HI 2500 1400 2420 1350 2340 1300 2260 1250 2160 1190 2060 1135 1925 1065 060 MED 2390 1350 2350 1300 2300 1255 2245 1210 2190 1165 2130 1120 2065 1075 1990 1030 1900 970 LOW 2270 1320 2230 1270 2190 1220 2145 1170 2090 1110 2030 1070 1960 1020 1890 970 1810 920 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 9
15. factory tested prior to shipment All unit wiring shall be both numbered and color coded Enclosed in each unit shall be a factory test log sheet consisting of the unit tested pressures temperatures and amps as tested prior to shipment All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling amp heating performance shall be rated in accordance with DOE and ARI test procedures Units shall be listed under UL 1995 CAN CSA No 236 M90 conditions UNIT CABINET 1 Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non chalking powered paint finish certified at 750 hours salt spray test per ASTM B117 standards 2 Indoor blower section shall be insulated with up to 1 thick insulation coated on the air side Aluminum foil faced insulation shall be used in the furnace compart ment and be fastened with ridged fasteners to prevent in sulation from entering the air stream 3 Cabinet panels shall be large size easily removable for servicing and maintenance 4 Full perimeter base rails shall be provided to assure reli able transit of equipment overhead rigging fork truck ac cess and proper sealing on roof curb applications 5 Disposable 1 filters shall be furnished and be accessible through a removable access door sealed air tight Units filter track shall be designed to accommodate either 1 or 2 filters 6 Fan performance measur
16. filters The unit filter racks can accommodate 1 or 2 filters without any modifications al YORK SUNLINE 2000 Heat Pump LOW VOLTAGE DIRECT DRIVE CONNECTIONS BLOWER MOTOR Belt Drive Option ELECTRICAL also available on some DISCONNECT models MOUNTING LOCATION Direct Drive Models ECONOMIZER HOOD OUTDOOR AIR OPENING FOR SLIDE IN PLUG IN INTERNAL ECONOMIZER OPTION ACCESSORY SIDE RETURN AIR DUCT OPENING Return Air amp Supply Alr Side by Side BOTTOM RETURN AIR DUCT OPENING Return Air amp Supply Air ELECTRIC HEATER LOCATION ACCESSORY COPPER TUBE ALUMINUM FIN OUTDOOR COIL HIGH EFFICIENCY COMPRESSOR WITH CRANKCASE HEATER BASE RAILS WITH FORKLIFT SLOTS AND LIFTING HOLES Side by Side 3 4 PVC FEMALE CONDENSATE DRAIN KNOCKOUT FOR BOTTOM POWER ENTRY KNOCKOUTS FOR SIDE POWER AND CONTROL TERMINAL BLOCK ENTRY For Single Point Power Supply with Electric Heat TABLE OF CONTENTS Description i ides re o eh ia dies 1 Heater 10 Features Field 10 Ratings Electrical Data Basic Units Direct Drive 11 Physical Elec Data Ht Pump Elec Ht 3 Ton Direct Drive 11 Cooling Capacities 3 Elec Data Ht Pump Elec Ht 4 8 5 Ton Direct Drive 12 Cooling Capacities 4 Ton 5 A Elect
17. operation BURGLAR BARS Designed to work with above roofcurbs Fits duct openings of curb supply and return air openings 21 6 THERMOSTATS Multiple models available from 22 M C O Electronic or Electrical Mechanical ver sions ANTI RECYCLE TIMER Assures 5 minute off time between compressor cycles ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW 036 21564 003 A 1005 OTHER FACTORY INSTALLED OPTIONS HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHENOLIC COATED COND COIL 3 ELECTRONIC ENTHALPY ECONOMIZER 4 DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER Unitary Products Group 036 21564 003 1005 Unitary Products Group 23 ISO 9001 8 Certified Quality Management System A CERTIFIED REC 5 95 a YORK Heating and Air Conditioning Unitary Products Group 5005 York Drive Norman OK 73069 Subject to change without notice Printed in U S A 036 21564 003 A 1005 Copyright 2005 by York International Corporation All Rights Reserved Supersedes 036 21564 002 A 0404
18. 03 1005 ELECTRICAL DATA Basic Unit Direct Drive VOLTAGE OUTDOOR SUPPLY MAX MAX MODEL SUP LIMITATIONS COMPRESSOR FAN AIR MINIMUM FUSE HACR BCH PLY SEE NOTE 1 MOTOR BLOWER CIRCUIT SIZE BREAKER MIN MAX RLA LRA FLA MOTOR AMPACITY SEENOTE2 SIZE 2 FLA AMPS AMPS 208 230 1 60 187 253 19 0 105 1 7 4 4 29 9 45 45 036 208 230 3 60 187 253 11 9 85 1 7 4 4 21 0 30 30 460 3 60 414 504 5 9 42 1 0 2 2 10 6 15 15 575 3 60 518 630 4 8 34 1 0 2 2 10 2 15 15 208 230 1 60 187 253 25 0 105 2 3 5 0 38 6 50 60 048 208 230 3 60 187 253 14 7 130 2 3 5 0 25 7 40 40 460 3 60 414 504 7 7 64 1 4 2 2 13 2 20 20 575 3 60 518 630 6 4 52 1 4 2 2 11 6 15 15 208 230 1 60 187 253 32 1 169 2 3 6 6 49 0 80 80 060 208 230 3 60 187 253 19 3 123 2 3 6 6 33 0 50 50 460 3 60 414 504 10 0 62 1 4 3 3 17 2 25 25 575 3 60 518 630 7 9 50 1 4 3 3 14 6 20 20 NOTES 1 Rated in accordance with ARI Standard 110 utilization range 2 Dual element time delay type ELECTRICAL DATA Heat Pump with Supplemental Electric Heat Direct Drive HEATER etal ELECTRIC HEATERS KX MODEL POWER ACCESSORY FUSE 2 BLOWER TOTAL CIRCUIT 1 HACR BCH SUPPLY MODEL KW STAGES SIZE MOTOR AMPACITY BREAKER NUMBER AMPS AMPS FLA AMPS 2CE04510506 4 0 1 19 1 53 8 60 60 2CE04510706 5 6 1 27 1 63 7 70 70 208 1 60 2CE04511006 4 4 8 0 1 38 3 77 7 80
19. 10 240 2 Rated in accordance with ARI Standard 270 3 Heaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by the total elec in watt hours during the same period power input EER Energy Efficiency Ratio the cooling capacity in BTU s per hour BTUH divided by the power input in watts at any given set of rating conditions expressed in BTUH per watt BTUH watt COP Coefficient of Performance the total heating capacity provided by the refrigeration system including circulating fan heat but excluding supplementary resistance BTU s per hour divided by the total electric input watts x 3 412 SOUND POWER RATINGS Sound Power dB 1072 Watts Unit ESP Blower Size CFM Octave Band Centerline Frequency Hz SWL dB A IWG Speed KW 63 125 250 500 1000 2000 4000 8000 dB A 10 ft 038 1200 0 60 LOW 0 60 84 84 74 67 69 62 57 52 74 41 048 1600 0 55 HIGH 0 80 85 85 75 68 70 63 58 53 75 42 060 2000 0 45 HIGH 1 00 86 86 76 69 71 64 59 54 76 43 At a distance of 10 ft from the blower NOTE These values have been accessed using a model of sound ion from a point source into the hemispheric free field The dBA values provided are to be used for reference only Calculat
20. 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003 945 1044 995 1086 1035 1400 982 880 1024 920 1067 965 1107 1000 1300 970 835 1010 870 1053 920 1099 960 1200 953 780 992 815 1034 855 1080 905 INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1 FILTERS REFER THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS Unitary Products Group 036 21564 003 1005 SUPPLY AIR BLOWER PERFORMANCE BCHO060 with Belt Drive BCHO60 SIDE DUCT APPLICATIONS 230 460 575 VOLTS Available External Static Pressure IWG el 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440 2100 930 1060 957 10
21. 1564 003 1005 COOLING CAPACITIES 5 TON 60 Air On Temperature of Air on Outdoor Coil Indoor 85 F Coil Total Power Sensible Capacity MBH Total Power Sensible Capacity MBH WB Cap Input Entering Dry Bulb F Cap Input Entering Dry Bulb F eF MBH KW 46 83 80 77 74 71 68 MBH KW 86 83 80 77 74 71 68 67 6 0 51 45 38 31 2500 64 5 9 56 56 50 43 37 30 59 5 9 59 59 57 50 44 38 31 58 5 8 58 58 51144 39 32 66 5 9 48 42 36 30 2250 63 5 9 55 54 48 42 35 29 57 5 8 572 50 44 38 32 57 5 8 57 ESI 50 45 39 33 65 5 9 45 40 34 29 2000 61 59 55 51 45 40 34 29 56 5 8 56 56 49 44 38 33 56 5 7 56 56 50 44 39 34 62 5 9 43 38 33 28 1750 59 5 8 53 48 44 39 34 29 54 5 7 54 54 48 43 38 33 54 5 7 54 54 49 43 39 34 60 5 8 41 36 32 28 1500 57 5 8 51 46 42 38 34 29 52 5 7 524852 46 42 38 34 52 5 6 520152 47 42 39 35 Air On Temperature of Air on Outdoor Coil Indoor 105 F 115 F Coil Total Power Sensible Capacity MBH Total Power Sensible Capacity MBH WB Cap Input Entering Dry Bulb F Cap Input Entering Dry
22. 3 7 38 38 34 29 24 20 15 38 3 6 38 38 37 35 30 26 21 37 3 6 37 37 37 35 30 26 22 46 37 32 28 24 20 16 42 3 7 36 34 30 27 22 18 14 37 3 6 37 37 36 33 28 25 21 36 3 6 36 36 36 33 29 25 21 45 37 30 27 22 18 15 41 36 33 29 26 21 18 13 1750 1500 1400 36 3 6 36 35 34 30 27 23 19 36 3 5 36 36 35 31 27 24 20 44 3 7 29 25 22 18 14 1200 39 3 6 34 30 27 23 20 17 13 35 3 6 35 34 33 29 26 23 19 35 3 5 35 35 34 31 28 24 20 42 3 6 26 23 20 17 14 1050 38 3 6 31 27 25 22 18 15 12 34 3 5 34 33 31 28 25 22 19 33 3 5 33 33 31 28 25 22 20 40 3 6 23 21 17 15 13 900 35 3 6 27 25 22 19 17 15 12 32 3 5 32 30 28 25 22 20 17 31 3 5 31 31 28 26 23 21 18 Air On Temperature of Air on Outdoor Coil Indoor 105 F 115 Total Power Sensible Capacity MBH Total Power Sensible Capacity MBH crm WB Cap Input Entering Dry Bulb F Cap Input Entering Dry Bulb F F MBH KW 86 83 80 77 74 71 68 MBH KW 86 83 80 77 74 71 68 42 4 2 30 26 23 19 15 1750 36 4 1 31 31 28 24 20 16 12 34
23. 4 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 0 4600 70 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8 4 0 4 6 5 2 80 MBH 10 7 15 0 19 5 24 5 30 5 37 4 45 3 51 8 KW 3 5 3 6 3 8 3 9 4 0 4 2 4 8 5 4 55 MBH 10 9 15 3 19 9 24 9 31 7 38 9 47 0 53 8 KW 3 1 3 2 3 3 3 4 3 5 3 7 4 2 4 8 4200 70 MBH 10 5 14 7 19 1 24 0 30 5 37 4 45 2 51 7 KW 3 2 3 3 3 4 3 5 3 6 3 8 4 4 5 0 80 MBH 9 6 13 5 17 6 22 0 28 1 34 4 41 6 47 6 KW 3 3 3 4 3 5 3 6 3 8 4 0 4 6 5 2 55 MBH 18 2 24 7 31 1 38 4 45 6 55 4 64 7 75 6 KW 5 0 5 1 5 2 5 3 5 3 5 6 5 9 6 5 2500 70 MBH 17 5 23 7 29 9 37 0 43 9 53 3 62 2 72 7 5 2 5 3 5 4 5 5 5 6 5 9 6 2 6 8 80 MBH 16 1 21 8 27 5 34 0 40 4 49 0 57 2 66 9 KW 5 4 5 6 5 7 5 8 5 9 6 0 6 5 7 2 55 MBH 18 0 24 4 30 8 38 1 45 0 54 7 63 9 74 7 4 8 4 9 5 0 5 3 5 5 5 8 6 4 2000 70 MBH 17 3 23 5 29 6 36 6 43 3 52 6 61 4 71 8 KW 4 9 5 0 5 1 5 2 5 5 5 8 6 1 6 7 80 MBH 15 9 21 6 27 2 33 7 39 8 48 4 56 5 66 1 KW 5 1 5 3 5 4 5 5 5 8 6 1 6 4 7 0 55 MBH 16 2 22 0 27 8 34 3 41 4 50 2 58 7 68 6 KW 4 5 4 6 4 7 4 8 5 0 5 3 5 5 6 1 4500 70 MBH 15 6 21 2 26 7 33 0 39 8 48 3 56 4 66 0 KW 4 7 4 8 4 9 5 0 5 2 5 5 5 8 6 4 80 MBH 14 4 19 5 24 6 30 4 36 6 44 5 51 9 60 7 KW 4 9 5 0 5 1 5 2 5 5 5 8 6 1 6 7 Unitary Products Group MODEL BCH 036 MODEL BCH 036 036 21564 003 A 1005 SUPPLY AIR BLOWER PERFORMANCE 036 amp 048 with Belt Drive BCHO036 SIDE DUCT APPLICATIONS 230 460
24. 5 INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1 FILTERS THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER ADJUSTABLE FIXED BLOWER MOTOR MOTOR PULLEY BLOWER PULLEY BELT MODEL TRPM Hp ppm FRAME SERVICE Pa BORE 1 EN DESIG SIZE FACTOR DIA in in A NATION BCH 036 790 1120 1 12 1725 56 115 24 34 TB 57 1 37 3 A36 BCH 048 790 1120 1 1 2 1725 56 115 24 34 7 8 5 7 1 37 3 A36 BCH 060 850 1220 1 1 2 1725 56 115 24 34 7 8 5 2 1 37 3 A36 AII motors have solid bases and are inherently protected These motors can be selected to operate into their service factor because they are located in the moving air upstream of any heating device Unitary Products Group STATIC RESISTANCES 036 21564 003 A 1005 EXTERNAL STATIC PRESSURE DROP RESISTANCE IWG DESCRIPTION CFM 1000 1200 1400 1600 1800 2000 2200 2400 2600 Economizer 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 Electric Heaters 5 15 KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 20 30 KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 Bottom Duct Connections 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 Deduct these resistance values from the available external static pressure shown in the respective Blower Performan
25. 70 983 1080 1010 1100 1039 1160 1064 1260 1092 1340 060 2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225 1900 894 885 940 940 980 980 1014 1020 1047 1095 1800 855 815 903 860 950 905 988 940 1022 970 1700 884 815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 060 2000 1100 1285 1133 1340 1169 1385 1205 1445 1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 95 INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1 FILTERS REFER TO THE
26. 80 2CE04511506 11 9 2 57 4 101 6 110 110 2CE04512006 15 9 2 76 6 125 5 150 150 2CE04510506 5 3 1 22 1 57 5 70 70 2CE04510706 7 5 1 31 2 68 9 80 80 230 1 60 2 04511006 4 4 10 6 1 44 2 85 1 90 90 2 04511506 15 9 2 66 2 112 7 125 125 2 04512006 212 2 88 3 140 3 150 150 2CE04510525 4 0 1 11 0 34 8 40 40 2CE04510725 5 6 1 15 6 40 5 45 45 208 3 60 2 04511025 4 4 8 0 1 22 1 48 6 50 50 036 2 04511525 11 9 2 33 1 62 4 70 70 2CE04512025 15 9 2 44 2 76 2 80 80 2CE04510525 5 3 1 12 7 36 9 45 45 2CE04510725 7 5 1 18 0 43 5 50 50 230 3 60 2 04511025 4 4 10 6 1 25 5 52 8 60 60 2 04511525 15 9 2 38 2 68 8 70 70 2 04512025 21 2 2 51 0 84 7 90 90 2CE04510746 6 8 1 8 2 21 2 25 25 2CE04511046 10 1 1 12 1 26 4 30 30 460 3 60 2CE04511546 22 13 6 1 16 4 31 9 35 35 2CE04512046 19 5 2 23 5 41 2 45 45 2CE04511058 10 6 1 10 2 15 5 20 20 575 3 60 2CE04511558 2 2 15 9 1 15 3 21 9 25 25 2CE04512058 21 2 1 20 4 28 2 30 30 1 Dual element time delay type 2 Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused Nominal Voltage Voltage sin x Electric Heat 208 208 1 00 These electric heaters DO NOT include a fuse box If a fuse box is Correction required to meet a local code eg Chicago the following fuse Factors 240 230 0 92 block accessories are available for field installation 480 460 0 92 600 575 0 92 2FB04700425 208 240 Volts Fuse Block 2FB04700546 460 Vol
27. CE04510706 7 5 1 31 2 73 1 80 80 230 1 60 2 04511006 8 6 10 6 1 44 2 89 3 90 90 2 04511506 15 9 2 66 2 116 9 125 125 2 04512006 212 2 88 3 144 5 150 150 2CE04510525 4 0 1 11 0 35 7 40 40 2CE04510725 5 6 1 15 6 41 4 45 45 208 3 60 2 04511025 5 3 8 0 1 22 1 49 5 50 50 036 2CE04511525 11 9 2 33 1 63 3 70 70 2CE04512025 15 9 2 44 2 77 1 80 80 2CE04510525 5 3 1 12 7 37 8 45 45 2CE04510725 7 5 1 18 0 444 50 50 230 3 60 2 04511025 5 3 10 6 1 25 5 53 7 60 60 2CE04511525 15 9 2 38 2 69 7 70 70 2 04512025 21 2 2 51 0 85 6 90 90 2CE04510746 6 8 1 8 2 21 7 25 25 2CE04511046 10 1 1 12 1 26 7 30 30 460 3 60 2CE04511546 31 13 6 1 16 4 31 9 35 35 2CE04512046 19 5 2 23 5 40 8 45 45 2CE04511058 10 6 1 10 2 16 6 20 20 575 3 60 2CE04511558 3 1 15 9 1 15 3 23 0 25 25 2CE04512058 21 2 1 20 4 29 4 30 30 1 8 Dual element time delay type KW 2 Standard circuit breakers may be used in Canada and on applications Nominal Voltage Voltage Multipier over 60 amps where the heaters are separately fused Kada Heat 208 208 1 00 DM 240 230 0 92 These electric heaters DO NOT elisa fuse box If a fuse box is 480 460 0 92 required to meet a local code eg Chicago the following fuse block accessories are available for field installation 600 575 0 92 2FB04700425 208 240 Volts Fuse Block 2FB04700546 460 Volts Unitary Products Group 13 036 21564 003 1005 ELECTRICAL DATA Heat Pump with Supplemental Electric Heat Belt Driv
28. T E WE elit TRANSFORMER ee cena 29 C EN B nemen 24 VOLT NOT USED 1 24 volt thermostat with subbase 2TH11700224 for manual changeover 2TH11704124 for automatic changeover 2 Only required on units with supplemental electric heat TRANSFORMER TO REMOTE SENSOR 2TH04702224 IF USED 1 Electronic programmable Thermostat 2ET04700324 with subbase for both manual and automatic changeover 2 Only required on units with economizer Remove jumper J2 from terminals 4 and 9 on jumper plug P7 The outdoor air intake dampers will return to their fully closed position when the thermostat switches to the unoccupied mode 3 Second stage cooling is only required on units with economizer Remove jumper J1 from terminals 8 and 10 on jumper plug connector 7 Only required on units with supplemental electric heat POWER WIRING CONTACTOR Sap FIELD SUPPLIED S DISCONNECT Ug roo gt SINGLE pms acest 4 O p r gt PHASE Doc NER 5 E GROUND REFER TO ELECTRICAL DATA O7 oe SURF TABLES TO SIZE THE 2 LUG DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 10 CONTACTOR 829 FIELD SUPPLIED Fe DISCONNECT PHASE ROUND aa a 220 012 POWER LUG REFER TO ELECTRICAL DATA L SUPPLY TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION Unitary Products Group 036 21564 0
29. TECHNICAL GUIDE DESCRIPTION YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3 4 and 5 ton sizes The units were designed for residential and light commercial applications They can easily be installed on a roof curb slab roof jack or frame All units are self contained and assembled on rigid full perimeter base rails allowing for 3 way fork lift access and overhead rigging Every unit is completely charged wired piped and tested at the factory to provide for a quick and easy field installation The units are available with supplemental electric heaters as field installed accessories Both down and side discharge airflows are available without having to swap panels The installer simply removes the duct covers for the desired configuration Economizers may be used on either side or down discharge applications with no modifications required All models include a 1 year limited warranty on the complete unit Compressors and electric heater elements each carry an additional 4 year warranty FEATURES CONTROLS These heat pumps utilize a unique time temperature defrost circuit which adjusts the time between defrost cycles based on the outdoor temperature to provide optimal comfort control and ensure reliable operation The ambient modified time temperature defrost control extends the time below 35 F and shortens the time above 35 F The nom
30. URN AIR FILTER ACCESS BLOWER MOTOR ACCESS FIELD SUPPLIED DISCONNECT SWITCH LOCATION Shipped attached to the blower housing inside the blower compartment WIRING ENTRY See Detail B CONTROL BOX ACCESS Unitary Products Group Sei zac OUTDOOR COIL COMPRESSOR n gt ZE ELECTRIC HEAT ACCESS AIR ZZ suman 2 1 2 uM s OUTDOOR AIR Economizer 1 1 1 All dimensions inches They sub ject to change without notice Certified di mensions will be provided upon request WITH RAI Shown separately to illustrato bottom duct openings and power connection locations NOTE For curb mounted units refer to the duct hanger dimensions of the curb for the proper size of the supply and return air duct connections UTILITIES ENTRY DATA KNOCKOUT HOLE SIZE USED FOR DIA de Control Wiring 718 Side or Bottom B 2 Power Wiring Side or Bottom Knockouts in the bottom of the unit can be located by the slice in the insulation Do not remove the 2 knockout ring CLEARANCES Front 24 12 Less Economizer Back 36 With Economizer or Fixed Air Motorized Air Damper Left Side Filter Access 26 With Economizer Right Side OD Coil 24 Below Unit 0 Above Unit 72 For Outdoor Air Discharge NOTE Units and ductwork are
31. and wired The outdoor air hood needs only to be field assembled and installed Adjustable belt drive blowers are available on most models from the factory for complete air flow flexibility FIELD INSTALLED ACCESSORIES Accessories were designed for quick and easy installation The motorized damper and economizers simply slide in and electrical connections are made by modular plugs Electric heaters mount easily and knockouts are provided in the internal partitions to connect the elements to the control box single point kit The motorized air damper includes a slid in plug in damper assembly with a rainhood and filters The outdoor air dampers open when the indoor fan motor is energized The damper is capable of providing 0 through 100 of outdoor return air opening The manual outdoor damper provides 0 through 35 or 0 through 100 of return air opening field adjustable Designed for duct mounted side or bottom supply return applications Includes rain hood assembly and filter The 14 high roof curb is shipped knocked down A roof curb deck is not required because the bottom of the unit is insulated WIDE RANGE OF INDOOR AIRFLOWS All models operate over a wide range of design conditions with a 3 speed direct drive fan motor Belt drive blowers are also available on all models FULL PERIMETER BASE RAILS The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during
32. approved for zero clearance to combustible materials when equipped with electric heaters Units may be installed on combustible floors made from wood or class A B or C roof covering material 2Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet 15 036 21564 003 1005 UNIT DIMENSIONS CONT D BCH 3 4 amp 5 TON DUCT COVERS Units are shipped with all air duct openings covered For side duct applications 1 Remove and discard the supply and return air duct covers 2 Connect ductwork to duct flanges on the rear of the unit For bottom duct applications 1 Remove the side supply air duct cover to gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove and discard the bottom return air knockout panel REAR VIEW 3 SIDE SUPPLY AND RETURN AIR DUCT OPENINGS 4 27 1 22 1 5 8 i CONDENSATE DRAIN must be trapped 27 1 2 19 3 4 N B OO 2 C gt REAR VIEW 4 19 1 2 44 7 8 lt DETAIL L H END VIEW UNIT WITH ECONOMIZER RAINHOOD 2712 gt 10 1 4 7 ne 19 1 8 30 3 12 8 1 4
33. ce Table The pressure thru the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer operation HEATER CFM LIMITATIONS HEATER UNIT MODEL SIZE NOMINAL TONS HEATER UNIT MODEL SIZE NOMINAL TONS SIZE VOLTAGE 3 4 5 SIZE VOLTAGE 3 4 5 NOM KW MINIMUM SUPPLY AIR CFM NOM KW MINIMUM SUPPLY AIR CFM 5 1 100 1 300 1 600 7 1 100 1 300 1 600 7 1 100 1 300 1 600 10 1 200 1 300 1 600 10 208 1 200 1 300 1 600 15 460 3 60 1 200 1 300 1 600 15 230 1 60 1 200 1 300 1 600 20 1 300 1 300 1 600 20 1 3002 1 300 1 600 30 1 600 30 1 600 10 1 200 1 300 1 600 5 1 100 1 300 1 600 15 575 3 60 1 200 1 300 1 600 7 1 100 1 300 1 600 20 1 300 1 400 1 600 10 208 1 200 1 300 1 600 30 1 800 15 230 3 60 1 200 1 300 1 600 1208 230 and 460 volt heaters are UL approved 20 1 300 1 300 1 600 2208 230 and 575 volt heaters CGA approved 30 1 600 2CGA minimum is 1 400 CFM FIELD WIRING CONTROL WIRING 24 VOLT THERMOSTAT M ELECTRONIC THERMOSTAT UNIT TERMINAL TERMINALS UNIT TERMINAL STRIP 1 c 2 a qe THERMOSTAT 144 gt TERMINALS 41 JUMPER p 5 0 2222222 o 4 0 Wr Fi ie mie ee ee 24 VOL
34. ded in a range of 5 thru 30 KW of fering two stages of capacity 16 KW and above on 208 230 volt heaters and 20 KW and above on 460 and 575 volt heaters The heating section shall have a primary limit control s and automatic reset to prevent the heating element sys tem from operating at an excessive temperature The Heating Section assembly shall slide out of the unit for easy maintenance and service Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing where required UNIT OPERATING CHARACTERISTICS 1s Unit shall be capable of starting and cooling at 125 F outdoor temperature exceeding maximum load criteria of ARI Standard 210 240 The compressor with standard controls shall be capable of cooling down to 45 F outdoor temperature ELECTRICAL REQUIREMENTS All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications Separate side and bottom openings shall be provided for the control wiring STANDARD LIMITED WARRANTIES Compressor 5 Years Elect Heat Elem 5 Years Parts 1 Year Unitary Products Group OPTIONAL OUTDOOR AIR Shall be made available by either or 1 ELECTRONIC ENTHALPY AUTOMATIC ECONO MIZER Outdoor and return air dampers that are inter locked and positioned by a fully modulating spring r
35. e SUPPLY ELECTRIC HEATERS WIE MODEL POWER ACCESSORY FUSE 2 BCH SUPPLY MODEL BLOWER TOTAL CIRCUIT size HATT MOTOR STAGES amps AMPACITY BREAKER NUMBER AMPS FLA AMPS 2CE04510506 4 0 1 19 1 65 2 80 80 2CE04510706 5 6 1 27 1 748 90 90 208 1 60 2CE04511006 8 6 8 0 1 38 3 89 2 100 100 2 04511506 11 9 2 574 112 7 125 125 2 04512006 159 2 76 6 136 7 150 150 2 04510506 53 1 22 1 68 8 80 80 2 04510706 75 1 313 802 90 90 230 1 60 2 04511006 86 10 6 1 442 96 4 110 110 2 04511506 159 2 66 3 124 0 125 125 2 04512006 21 2 2 88 3 151 6 175 175 2CE04510525 40 1 11 0 39 7 50 50 2CE04510725 5 6 1 15 6 45 5 50 50 208 3 60 2CE04511025 52 80 1 22 1 53 6 60 60 Gas 2 04511525 11 9 2 33 1 674 70 70 2 04512025 159 2 442 812 90 90 2CE04510525 5 3 1 12 7 41 9 50 50 2CE04510725 75 1 18 0 48 5 50 50 230 3 60 2CE04511025 52 106 1 25 5 57 8 60 60 2 04511525 159 2 382 73 7 80 80 2 04512025 212 2 510 897 90 90 2CE04510746 6 8 1 82 23 8 25 25 2CE04511046 10 1 1 12 1 28 8 30 30 460 3 60 20E04511546 26 13 6 1 164 34 1 35 35 2 04512046 19 5 2 23 5 429 45 45 2CE04511058 10 6 1 10 2 24 2 25 25 575 3 60 2CE04511558 26 15 9 1 15 3 30 5 35 35 2 04512058 212 2 204 36 9 40 40 2 04510506 40 1 19 1 74 9 100 100 2 04510706 56 1 27 1 84 9 110 110 208 160 2CE04511006 T 80 1 38 3 98 9 110 110 2 04511506 11 9 2 574 122 8 125 125 2 04512006 159 2 76
36. embly to take in the design CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation During economizer operation a mixed air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 F Changeover from compressor to economizer operation shall be provided by two integral electronic enthalpy controls one that senses outdoor air and one that senses indoor air Both enthalpy sensors supply input to the logic module which modulates both sets of dampers for maximum economizer savings The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit Water eliminator filters shall be provided Simultaneous economizer compressor operation is also possible Dampers shall fully close on power loss OTHER PRE ENGINEERED ACCESSORIES AVAILABLE 1 ROOF CURB 14 AND 8 high full perimeter knock down curb with hinged design for quick assembly MANUAL OUTDOOR DAMPER Provides 096 through 35 or 096 through 100 outdoor air capability field ad justable Designed for duct mounted side supply return applications Includes a hood and a screen assembly OUTDOOR COIL GUARD Prevents coil damage BAROMETRIC RELIEF DAMPER Contains a rain hood air inlet screen exhaust damper and mounting hardware Used to relieve internal air pressure through the unit during economizer
37. eturn damper actuator The maximum leakage rate for the outdoor air intake dampers shall not exceed 296 when dampers are fully closed and operating against a pressure differential of 0 5 IWG A unit mounted potenti ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 F Changeover from compressor to economizer eration shall be provided by an integral electronic en thalpy control that feeds input into the basic module The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit Water eliminator fil ters shall be provided Simultaneous economizer com pressor operation is also possible Dampers shall fully close on power loss DUAL INPUT DIFFERENTIAL ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER Outdoor and return air dampers that are interlocked and positioned by a fully modulating spring return damper actuator The maximum leakage rate for the outdoor air intake dampers shall not exceed 2 when dampers are fully closed and operating against a pressure differential of 0 5 IWG A unit mounted potentiometer shall be provided to adjust the outdoor and return air damper ass
38. inal defrost times are field adjustable to 50 80 and 110 minutes The defrost time is initiated and terminated by a liquid line control with a 10 minute override limit built into the defrost control COMMON FOOTPRINT COMMON CABINET The 3 4 and 5 ton units all share the exact same cabinet and therefore the same roof curb You now have the flexibility of setting one curb and after the internal load has been determined placing the proper tonnage unit on that curb HIGH EFFICIENCY All units have a minimum SEER of 10 a COP of 3 0 high and 2 0 low and an HSPF as high as 7 3 These efficiencies exceed all legislated minimum levels and provide low operating costs 036 21564 003 A 1005 ad YORK SINGLE PACKAGE AIR TO AIR HEAT PUMPS B3CH 036 048 amp 060 208 230 460V 5 036 amp 060 575V B6CH 048 3 4 AND 5 NOMINAL TONS 10 SEER SUNLINE 2000 CONVERTIBLE AIRFLOW DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit and discard them If a bottom supply return is desired you simply remove the two bottom duct covers and discard them No panel cutting or swapping is required Convertible airflow design allows maximum field flexibility and minimum inventory FACTORY INSTALLED OPTIONS Economizers can be installed at the factory They are shipped installed
39. ing its filters need be assembled and installed in the field BELT DRIVE BLOWERS Adjustable belt drive blowers providing maximum flexibility to handle many airflow requirements are available on all models FIELD INSTALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER Includes slide in plug in damper assembly with fully modulating spring return motor actuator capable of introducing up to 100 outdoor air one outdoor air electronic enthalpy sensor and a rainhood with filters The rainhood is painted to match the basic unit and must be field assembled before installation Economizer dampers are 2 low leakage type DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER Includes the same damper system and rainhood with filters as described for a single enthalpy economizer above except this accessory contains two enthalpy sensors It uses a differential enthalpy control that compares the outdoor air versus the return air The logic module then optimizes the economizer operation for additional savings over the single input economizer MOTORIZED AIR DAMPER Includes a slid in plug in damper assembly with a rainhood and filters The outdoor air dampers open when the indoor fan motor is energized The damper is capable of providing 0 through 100 of outdoor return air opening MANUAL OUTDOOR DAMPER Provides 0 through 35 or 0 through 100 of return air opening field adjustable Designed for duct mounted side or bot
40. ing ports shall be provided on the outside of the cabinet to allow accurate air measure ments of evaporator fan performance without removing panels or creating air by pass of the coils 7 Units vertical discharge and return duct configuration shall be designed to fit between standard 24 O C beams without modification to building structure duct work and base unit 8 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards Condensate connection shall be a minimum of 3 4 I D female be a ridged mount connection INDOOR SUPPLY FAN ASSEMBLY 1 Fan shall be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power rating plus the service factor Units shall be designed not to operate above service factor 20 2 Fan wheel shall be double inlet type with forward curved blades dynamically balanced to operate smoothly throughout the entire range of operation Airflow design shall be constant air volume 3 Bearings shall be sealed and permanently lubricated for longer life and no maintenance OUTDOOR FAN ASSEMBLY 1 The outdoor fan shall be of the direct driven propeller type discharge air vertically have aluminum blades riveted to corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation 2 The
41. ion of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each system This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings PHYSICAL DATA BASIC U NITS BCH MODES 036 048 060 CENTRIFUGAL BLOWER Dia x Wd in SUPPLY AIR FAN MOTOR HP DIRECT DRIVE X 1 MOTOR HP BELT DRIVE 1 5 1 5 ROWS DEEP 3 3 gt FINS PER INCH 15 15 FACE AREA Sq Ft 5 1 5 1 PROPELLER DIA in 22 24 i ae FAN MOTOR HP p A NOM CFM TOTAL 4200 4500 ROWS DEEP 1 1 FINS PER INCH 20 20 FACE AREA Sq Ft 17 1 17 1 AIR QUANTITY PER UNIT 15 x 20 x 1 2 2 FILTERS QUANTITY PER UNIT 14 X 25 X 1 1 1 SEE NOTE TOTAL FACE AREA sq ft 6 6 6 6 CHARGE REFRIGERANT 22 lbs oz 9 2 8 4 COMPRESSOR HERMETIC RECIPROCATING Qty 1 1 NOTE Filter racks can accommodate 1 or 2 thick filters Unitary Products Group 036 21564 003 1005 COOLING CAPACITIES 3 BCH036 Air On Temperature of Air on Outdoor Coil Indoor 85 F 95 F Coil Total Power Sensible Capacity MBH Total Power Sensible Capacity MBH crm WB Cap Input Entering Dry Bulb F Cap Input Entering Dry Bulb F oF MBH KW 86 83 80 77 74 71 68 MBH KW 86 83 80 77 74 71 68 47 3 7 34 29 25 22 17 44
42. ithout the economizer To obtain maximum economizer operating savings a two stage cooling thermostat should be used To obtain two stage cooling operation a jumper wire must be removed on the low voltage relay board See unit wiring diagram OUTDOOR THERMOSTAT A 24 volt thermostat providing two stages of control for units equipped with supplemental electric heaters Unitary Products Group 036 21564 003 1005 TYPICAL APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION TYPICAL ROOF TOP INSTALLATION iae FIELD SUPPLIED DISCONNECT SWITCH as PRO US ee P aS 5 p ERIC PA AN t ARE 1 uu LED av E ES 2 ROOF CURB 7 CONDENSATE TRAP 1 SUPPLY AIR DUCT CONTROL WIRING RETURN AIR POWER INDOOR DUCT SUPPLY THERMOSTAT Unitary Products Group 19 036 21564 003 1005 MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION Units shall be factory assembled single packaged Heat Pumps designed for outdoor mounted installation Units shall have minimum SEER ratings of 10 0 They shall have built in field convertible duct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired piped charged with R 22 refrigerant and
43. outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions REFRIGERANT COMPONENTS 1 Compressors A Shall be fully hermetic type direct drive internally pro tected with internal high pressure relief and over tem perature protection The hermetic motor shall be suction gas cooled and have a voltage range of or 10 of the unit nameplate voltage B Shall have internal isolation and sound muffling to mini mize vibration and noise and be externally isolated on a dedicated independent mounting 2 Coils A Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed Special Phenolic coating shall be available as a factory option B Evaporator and Condenser coils shall be of the direct expansion draw thru design 3 Refrigerant Circuit and Refrigerant Safety Components shall include A Independent fixed orifice expansion devices B Filter drier strainer to eliminate any moisture or foreign matter C Accessible service gage connections on both suction and discharge lines to charge evacuate and measure refrigerant pressure during any necessary servicing or troubleshooting without losing charge D The refrigeration system shall provide at least 15 F of liquid sub cooling at design conditions E Unit shall have a suction line accumulator
44. rical Data Basic Units Belt Drive 13 Cooling Capacities 5 Ton Heating Capacities assesses ita Elec Data Ht Pump Flec Ht 3 Ton Dive TT 13 Supply Air Blower Perf 3 amp 4 Ton w Belt Drive a Elec Data Ht Pump Elec Ht 4 amp 5 Belt Drive 14 Supply Air Blower Perf 5 Ton w Belt Drive 9 Unit DIMENSIONS ua maman maha 15 Supply Air Blower Perf 3 4 amp 5 Ton w Direct Drive 9 Roof Curb DIMENSIONS esasan sa tene dieedi tar 17 Motor Drive Data Factory Installed Options Field Installed Accessories 18 Static Resistances cuiies eie pese estis Typical Applications 19 Unitary Products Group 036 21564 003 1005 RATINGS CAPACITY RATINGS ARI RATINGS SEE NOTE 1 NOMINAL MODEL COOLING ee HEATING CAPACITY GB AL E BCH PERFORMANCE SEE NOTE 2 HSPF 47 F 17 F KW MBH SEER EER bels MBH COP MBH COP 240V 480V 600V 036 39 10 00 9 20 8 6 7 3 39 0 3 0 23 0 2 1 5 7 10 15 amp 20 7 10 15 amp 20 10 15 amp 20 048 48 10 20 9 25 8 6 6 7 48 0 3 0 26 4 2 0 5 7 10 15 amp 20 7 10 15 amp 20 10 15 amp 20 060 59 10 00 9 20 8 4 7 0 590 3 0 36 0 2 1 5 7 10 15 20 8 30 7 10 15 20 8 30 10 15 20 8 30 NOTE 1 Certified in accordance with the Unitary Small Equipment certification program which is based on ARI Standard 2
45. shipment The rails provide fork lift access from 3 sides and rigging holes are also provided so that an overhead crane can be used to place the units on a roof FEATURES CONT D SYSTEM PROTECTION Crankcase heaters and internal compressor protection are standard on all compressors Every unit has a liquid line filter drier low pressure switch high pressure switch and high temperature switch to protect all system components A suction line freezestat is supplied on all three phase units to protect against loss of charge and coil frosting due to low economizer outdoor air temperature while the compressor is running All units will provide cooling at ambient temperatures down to 45 F UTILITY CONNECTIONS MADE EASY Electric utility knockouts are provided in the unit underside as well as the side of the unit A clearly identified location is provided to mount a 036 21564 003 A 1005 field supplied electrical disconnect switch Utility connections can be made quickly and with a minimum amount of field labor SIMPLE CONTROL CIRCUIT Mate n lock plug connectors are used where line and low voltage wires pass thru internal bulkheads This allows for easier troubleshooting and component replacement The electrical control box is not located in the compressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway
46. tom supply return applications Includes rain hood assembly and filter ELECTRIC HEATERS Include nickel chromium elements a terminal block fuses where required by UL all the necessary connectors and hardware All heaters utilize single point power supply hookup Capacities from 5 KW thru 30 KW heating are available 18 FUSE BLOCK KITS These kits have a fuse box with a fuse block and fuses They re available for all 460 3 60 volt heaters and 208 230 3 60 volt heaters 7 KW and smaller ROOF CURB This 14 high full perimeter roof curb is knocked down for field assembly and contains duct supports that can easily be shifted for the desired unit duct arrangement No deck is required because the unit underside is insulated START ASSIST KIT Standard on 4 ton units Provides increased starting torque for 3 and 5 ton single phase units in areas with low voltage conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 minutes off time between compressor cycles OUTDOOR COIL GUARD Consists of grille type sections for assembling over the outdoor coil to protect it from damage WALL THERMOSTAT The units are designed to operate with 24 volt electronic and electro mechanical thermostats All units can operate with single stage heat single stage cool thermostats with or w
47. ts Unitary Products Group 11 036 21564 003 1005 ELECTRICAL DATA Heat Pump with Supplemental Electric Heat Direct Drive SUPPLY ELECTRIC HEATERS MAX MODEL POWER ACCESSORY FUSE 2 BCH SUPPLY MODEL BLOWER TOTAL CIRCUIT Size HATT MOTOR STAGES amps AMPACITY BREAKER NUMBER AMPS FLA AMPS 2CE04510506 40 1 19 1 62 6 80 80 2 04510706 56 1 27 1 722 90 90 208 1 60 2CE04511006 5 0 8 0 1 38 3 86 6 100 100 2 04511506 11 9 2 574 110 1 125 125 2 04512006 15 9 2 76 6 134 1 150 150 2 04510506 5 3 1 22 1 66 2 80 80 2 04510706 75 1 312 776 90 90 230 1 60 2CE04511006 5 0 10 6 1 44 2 93 8 100 100 2 04511506 159 2 66 2 121 4 125 125 2 04512006 21 2 2 88 3 149 0 150 150 2CE04510525 4 0 1 11 0 39 5 50 50 2CE04510725 5 6 1 15 6 45 3 50 50 208 3 60 2CE04511025 5 0 8 0 1 22 1 534 60 60 2 04511525 11 9 2 33 1 67 2 70 70 2 04512025 159 2 442 81 0 90 90 2CE04510525 53 1 12 7 417 50 50 2 04510725 75 1 180 483 50 50 230 3 60 2CE04511025 5 0 10 6 1 25 5 57 6 60 60 2 04511525 159 2 382 73 5 80 80 2 04512025 212 2 51 0 89 5 90 90 2CE04510746 6 8 1 8 2 23 4 25 25 2 04511046 10 1 1 12 1 284 30 30 460 3 60 20E04511546 22 13 6 1 16 4 33 7 35 35 2 04512046 195 2 23 5 425 45 45 2CE04511058 10 6 1 10 2 24 9 25 25 575 3 60 2CE04511558 22 159 1 15 3 30 7 30 30 2 04512058 212 2 204 37 1 40 40 2 04510506 40 1 19