Utica Boilers SSC Operation and Installation Manual
Contents
1. 5 Remove orifice as shown in figures 1 amp 2 Figure 3 Brass LP Orifice 6 050 Mbh thru 200 O ring gasket shown in figure 1 must remain in place 7 Connect gas valve using previously removed screws 8 Place LP to Natural and Converted by labels onto boiler as shown in figures 4 amp 5 9 Replace upper jacket 10 Follow instructions in Start up Procedure section of boiler s Installation Operation amp Maintenance Manual for proper startup and verification procedures Table 1 LP Orifice Propane Orifice Chart 240008864 1350018 240008865 240008866 240009904 Model __ Figure 4 Conversion Label Placement 050 075 100 150 200 Place Conversion Labels Here a Rating Plate Lighting Instructions Figure 5 Conversion Label Placement 299 Rating Plate Hg ices IRRA tT a Pre Tae Lighting Instructions Place Conversion Labels Here Table 2 Parts Lists 050 Gas Conversion Kit 550002303 DESCRIPTION PART QTY Orifice LP 3 8mm 240008864 Label Converted By 8 Label Nat to LP conversion plate 24000896 Label LP to Nat conversion plate 240008962 Instructions 240008957 1 075 Gas Conversion Kit 550002304 100 Gas Conversion Kit 550002305 Label Converted By 240008688 240008961 m N amp CO OY CO m Label Nat to LP conversion plate Label LP to Nat conversion plate 240008962
2. Instructions 240008960 150 Gas Conversion Kit 550002306 DESCRIPTION PART Q Orifice LP 5 4mm 240008865 Label Converted By 240008688 240008961 _ 1 1 2 m Label Nat to LP conversion plate Label LP to Nat conversion plate 240008962 Instructions 240008957 200 Gas Conversion Kit 550002307 DESCRIPTION PART QTY Orifice LP 5 9mm 240008866 1 Label Converted By 240008688 2 Label Nat to LP conversion plate 240008961 Label LP to Nat conversion plate 240008962 Instructions 240008957 299 Gas Conversion Kit 550002799 DESCRIPTION PART QTY Orifice LP 9 6mm 240009904 1 Label Converted By 240008688 240008961 240008962 240008957 1 1 _ Label Nat to LP conversion plate 1 1 Label LP to Nat conversion plate Instructions Technical Support 800 325 5479 web site www ecrinternational com
3. gas valve using previously removed screws 8 Place Natural to LP and Converted by labels onto boiler as shown in figures 4 amp 5 9 Replace upper jacket 10 Follow instructions in Start up Procedure section of boiler s Installation Operation amp Maintenance Manual for proper startup and verification procedures P N 240008957 Rev B 04 2013 Kit installation shall be completed by qualified agency Figure 2 Disconnect Venturi Body from Gas Valve 299 Fire explosion asphyxiation and electrical shock hazard Improper installation could result in death or serious injury Read this instruction and understand all requirements including requirements of authority having jurisdiction before beginning installation Installation not complete until appliance operation verified per Installation Operation amp Maintenance Manual provided with boiler Brass LP Orifice Converting Boiler From LP To Natural Gas 1 Follow instructions To TURN OFF GAS TO APPLIANCE found on Operating Instructions label on boiler or in Installation Operation amp Maintenance Manual Verify all electrical power to boiler is turned off Gas Valve Electrical shock hazard Turn OFF electrical power Supply at service panel 2 Remove upper jacket from boiler 3 Follow instruction TO TURN OFF GAS TO APPLIANCE Verify electrical power is OFF 4 Remove screws as shown in figures 1 amp 2 Carefully separate gas valve
4. CONVERSION KIT INSTRUCTIONS NATURAL GAS TO LP amp LP TO NATURAL GAS 050 Kit 550002303 075 Kit 550002304 100 Kit 550002305 150 Kit 550002306 200 Kit 550002307 299 Kit 550002799 Kit installation shall be completed by qualified agency Figure 1 Disconnect Venturi B from Valv 75 1 1 2 Fire explosion asphyxiation and electrical shock TORX OR hazard Improper installation could result in death or serious Injury Read this instruction and understand ALLEN SCREW HEAD 3 REQ D all requirements including requirements of authority having jurisdiction before beginning installation Installation not complete until appliance operation verified per Installation Operation amp Maintenance Manual provided with boiler VENTURI Converting Boiler From Natural Gas To LP 1 Follow instructions To TURN OFF GAS TO APPLIANCE found on Operating Instructions label on boiler or in Installation Operation amp Maintenance Manual Verify all electrical power to boiler is turned off Electrical shock hazard Turn OFF electrical power Supply at service panel 2 Remove upper jacket from boiler 3 Follow instruction TO TURN OFF GAS TO APPLIANCE Verify electrical power is OFF 4 Remove screws as shown in figures 1 amp 2 Carefully separate gas valve 5 Insert LP orifice as shown in figures 1 amp 2 See Table 1 for orifice size 6 050 Mbh thru 200 O ring gasket shown in figure 1 must remain in place 7 Connect
Download Pdf Manuals
Related Search
Related Contents
Canada - Buyandsell.gc.ca Hard Disk Recording Unit Husqvarna iZ4217SKAA User's Manual Let`snote PRO R1の主な仕様 Table of Content Introduction Software Install and 取扱説明書 第 3 版 - 株式会社ビー・ユー・ジーSST Table de plongée MT92 ASP-107 - 東芝ライテック Copyright © All rights reserved.
Failed to retrieve file