Home
        Trane VUVE Vertical Classroom Catalogue
         Contents
1.       3 4 in  2 way  3 5 Cv Hydronic   Normally Open   Close off 20 psi       1 0 in  2 way  8 0 Cv Steam Normally Open   close off 15 psi  1 0 NPTI    3 wire modulating             2 way 3 way   1 2 in  2 way  1 9 Cv Hydronic   Low Cv   heat 1 2 in  3 way  1 5 Cv Hydronic   Low Cv   cooling  1 2 in  2 way  3 3 Cv Hydronic   Low Cv   cooling 1 2 in  3 way  3 8 Cv Hydronic   Med Cv   cool heat  3 4 in  2 way  4 7 Cv Hydronic   Med Cv   cool heat 3 4 in  3 way  6 6 Cv Hydronic   High Cv   cool heat       1 0 in  2 way  6 6      Hydronic   High Cv   cool heat  1 2 in  2 way  1 8 Cv Steam Only 1 2           1 2 in  2 way  4 6 Cv Steam Only 1 2           3 4 in  2 way  7 3 Cv Steam Only 3 4 NPTI   2 10 Vdc modulating                      2 way 3 way   1 2 in  2 way  1 9 Cv Hydronic   Low Cv   heat 1 2 in  3 way  1 5 Cv Hydronic   Low Cv   cooling  1 2 in  2 way  3 3 Cv Hydronic   Low Cv   cooling 1 2 in  3 way  3 8 Cv Hydronic   Med Cv   cool heat  3 4 in  2 way  4 7 Cv Hydronic   Med Cv   cool heat 3 4 in  3 way  6 6 Cv Hydronic   High Cv   cool heat       1 0 in  2 way  6 6 Cv Hydronic   High Cv   cool heat    UV PRCOOS3 EN 77    S TRANE     Controls  Piping Valve Options    Table 56  3 Wire modulating water valve specifications       Power supply 24 Vac   50 60 Hz   Power consumption 4 W   Maximum duty cycle ADM  Nominal timing    120sec              Operating ambient temperature O  C to 65  C  32 F to 150 F  Min Max fluid temperature 1  C to 95      34  F to 203  F  Operating 
2.      e Crossover connections terminate in the same end pocket as the heating coil on all 2  and 4 pipe  coils     86 UV PRC003 EN         TRANE    Mechanical Specifications    General    UV PRC003 EN    Deliver and install a complete unit ventilator certified for ventilation at AHRI 840  or tested by an  independent testing and balancing lab witnessed by owner s representative     Safety    All standard units are ULlisted in the United States and Canada and comply with NFPA 90    requirements     The unit ventilator is certified or rated in accordance to the following listings for performance proof  and safety  ETL  AHRI 840  AHRI 350  LonMark    BACnet      Equipment Construction    Exterior cabinetry is constructed of heavy gauge metal for strength and durability  All exposed  edges shall be rounded to safeguard against injury  All interior sheet metal shall be of galvanized  steel to restrain against deterioration     The front plane of the unit consists of a three panel design  The control compartment is accessible  without removing the entire front panel  The discharge air grille contains rounded edged steel bars   and are placed at a 15   slope to provide proper airflow deflection     Access for inspection and cleaning of the unit drain pan  coils  and fan section is provided  The unit  shall be installed for proper access  Procedures for proper maintenance of the unit shall is included  in the installing  operation manual     Cabinet insulation is closed cell to maximi
3.    NON    e m 6           Digit 33   2            A    for 2 pipe applications  5 8           N CN    END COVER  WITH 16 7 8  CUTOUTS   for 4 pipe  dynamic air  and wall fin applications    5 8   27      STEP DOWN FALSEBACK  END COVER  WITHOUT CUTOUTS           END COVERS  WITHOUT CUTOUTS     END COVERS  WITH 7 1 4  CUTOUTS                        Dimensional Data              End Covers  4       21     Digit 33   4  x  re  212       114   F     1 4   Digit 33   5  30   tio  21 2   2 1 4   MS 1 4      21 2   2 14   nese  25  30          to  Digit 32   D E F G H  Digit 33   4 29  ie  21 2      214   85       TRANE     Dimensional Data    Crossover Piping    16 5 8  DEPTH UNIT    7 8  1 0  FIELD  CONN W  SHUT 11 2       FLUSH OFF VALVE                             TOP VIEW   eee  H      5 3 8  SIDE VIEW  21 1 4  DEPTH UNIT  7 8  I D  FIELD y  FLUSH CONN  W  SHUT WE eu                         TOP VIEW    SIDE VIEW    Note  1 3 8 in  OD and 2 1 8 in  OD crossover piping    e Crossover piping is available for all 2  or 4 pipe coils selections  Trane provides the crossover  for the hot water only  The crossover pipe is factory insulated with 3 8 in  thick insulation     e Expansion compensation between the factory piping package and the crossover piping is  achieved using a flex hose rated at 250 psi working pressure  Flex hose is only available with  factory mounted piping packages     e Expansion compensation for the crossover piping must be handled external to the unit  ventilator
4.    The entering water temperature is  read from the auto changeover sensor and determines if the unit is capable of cooling or heating   The zone sensor module is capable of transmitting the following information to the controller     e Timed override on cancel request   e Zone setpoint   e Current zone temperature   e Fan mode selection  off auto high med low    For optimal system performance  unit ventilators can operate as part of an Integrated Comfort  System  ICS  building automation system controlled by Tracer Summit  The controller is linked  directly to the Summit control panel via a twisted pair communication wire  requiring no additional  interface device  1         command unit   The Trane ICS system can monitor or override Tracer UC400  control points  This includes such points as temperature and output positions    Tracer UC400 Zone Controller Features Include   e Single Zone VAV   e Automatic ventilation reset   e Active dehumidification   e Filter maintenance   e Water valve override   e Freeze avoidance   e Interoperability      Unused I O can be as generic I O    The Tracer UC400 is a factory installed   tested  and  commissioned BACnet   MS TP control  designed to provide control of the classroom unit ventilator  see Figure 28   The Tracer UC400  controller is designed to be used in the following applications  as stand alone operation  part of the  Trane Tracer SC building automation system  or part of another BACnet MS TP Building  Automation System  The Tr
5.   4 4 7 1 3 0  8 5 6  42 22 9 5 3  45 21 5 4 8  48 20 1 4 3  75 40 0 9 6 1  42 29 6 5 7  45 27 8 5 2  48 26 0 4 7  80 40 7 4 6 7  42 35 9 6 3  45 33 7 5 8  48 31 5 5 2  85 40 43 5 7 5  42 41 7 7 1  45 39 2 6 4  48 36 7 5 7  90 40 49       42 47 3 7 8  45 44 4 7 1  48 41 6 6 4  57 75 40 5 6 7 6  42 24 6 7 1  45 23 1 6 5  48 21 6 5 8  80 40 7 9  42 31 8 7 5  45 29 9 6 8  48 28 0 6 1  85 40 40 5 8 4  42 38 9 7 9  45 36 5 7 2  48 34 2 6 5  90 40 47 6 9 0  42 45 7 8 5  45 42 9 7 7  48 40 2 6 9  70 75 40 4 8 6  42 21 5 8 1  45 20 2 7 3  48 18 9 6 6  80 40 0 1 8 8  42 28 9 8 3  45 27 1 7 5  48 25 4 6 7  85 40 7 8      42 36 2 8 7  45 34 0 7 9  48 31 8 7 0  90 40 45  9 7  42 43 4 9 1  45 40 7 8 3  48 38 1 7 4       46 UV PRC003 EN                      Performance Data  Cooling   125   CoilE    Table 27  VUV 125  cooling coil E  3 row   16 fpi       Flow Rate  gpm  Entering Entering Entering 6        14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 8 5 19 6 9 9 e 1 8 4 5 5 4 7  0 0 9 5 7  23 0 5 4       42  45 21 5 4 9  48 20 1 4 4  42 29 8 5 9  45 27 9 5 4  48 26 1 4 8  80 40 7 5 0 9  42 36 0 6 5  45 33 8 5 9  48 31 6 5 3  95 40 43   7 1  42 41 9 7 3  45 39 3 6 6  48 36 7 5 9  90 40 49 5 3 5  42 47 5 8 1  45 44 5 7 3  48 41 6 6 6  57 75 40 5 8 7 8
6.   42 24 7 7 3  45 23 2 6 7  48 21 7 6 0  210 40 i BL  42 32 0 7 7  45 30 0 7 0  48 28 0 6 3  35 40 40 7        42 39 1 8 2  45 36 6 7 4  48 34 2 6 7  90 40 47 8 9   42 45 9 8 8  45 43 1 8 0  48 40 2 7 1  70 75 40      8 8  42 21 6 8 3  45 20 3 7 6  48 19 0 6 8  B0 40 0  9 1  42 29 1 8 5  45 27 3 7 8  48 25 5 7 0  35 40 7 9 9 4  42 36 4 8 9  45 34 1 8 1  48 31 9 7 3  90 40 45 4 9 9  42 43 6 9 4  45 40 9 8 5  48 38 2 7 6       UV PRC003 EN 47    S TRANE     Performance Data  Cooling   125   Coil F    Table 28  VUV 125  cooling coil F  4 row   12 fpi       Flow Rate  gpm       Entering Entering Entering CS   8       0   14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 6 4 19 5 9  1  1 4       4 9       7  9 7 5 1 5 8  42 24 1 5 5  45 22 5 5 0  48 20 9 4 5  15 40       6 4  42 31 2 6 0  45 29 1 5 4  48 27 1 4 8  B0 40 9 4 7 0  42 37 8 6 6  45 35 3 6 0  48 32 8 5 4  85 40 45 9 7 8  42 43 9 7 4  45 41 0 6 7  48 38 2 6 0  90 40 52 0 8 7  42 49 8 8 2  45 46 5 7 4  48 43 2 6 6  57 75 40 7 1 7 9  42 25 9 7 4  45 24 2 6 7  48 22 5 6 0  80 40 5 0 8   42 33 5 7 8  45 31 3 7 1  48 29 1 6 3  85 40 42 8 8 8  42 40 9 8 3  45 38 2 7 5  48 35 6 6 7  90 40 50  9 4  42 48 1 8 9  45 44 9 8 0  48 41 8 7 2  70 75 40  7 9 0  42 22 7 8 4  45 21 2 7 6  48 19 7 6 8  80 4
7.   460 60 3 1 6 0 25 1 3 5 85 7 8 6 10 75 15 8 28 10 35  460 60 3 1 6 0 25 1 4 7 8 14 1 15 7 19 625 20 15 38 19 225  460 60 3 1 6 0 25 1 6 11 7 14 1 15 7 19 625 20 15 38 19 225  VUVE100 115 60 1 3 5 0 25 1 0 0 0 3 5 4 375 15 2 8 3 5  208 60 1 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  208 60 1 2 1 0 25 1 3 5 86 28 2 30 3 37 875 40 29 88 37 35  208 60 1 2 1 0 25 1 4 7 81 37 5 39 6 49 5 50 39 18 48 975  208 60 1 2 1 0 25 1 6 11 72 56 3 58 44 73 80 57 98 72 475  208 60 3 2 1 0 25 1 0 0 0 2 1 2 025 15 1 68 2 1  208 60 3 2 1 0 25 1 3 5 86 16 3 18 4 23 25 17 98 22 475  208 60 3 2 1 0 25 1 4 7 81 24 79 26 0 33 6125 40 26 47 33 0875  208 60 3 2 1 0 25 1 6 11 72 32 5 34 6 43 25 50 34 18 42 725  230 60 1 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  230 60 1 2 1 0 25 1 3 7 8 32 5 34 6 43 25 50 34 18 42 725  230 60 1 2 1 0 25 1 4 10 4 43 3 45 4 56 75 60 44 98 56 225  230 60 1 2 1 0 25 1 6 15 6 65 67 1 83 875 90 66 68 83 35  230 60 3 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  230 60 3 2 1 0 25 1 3 7 8 18 8 20 9 26 125 30 20 48 25 6  230 60 3 2 1 0 25 1 4 10 4 28 66 30 8 38 45 40 30 34 37 925  230 60 3 2 1 0 25 1 6 15 6 37 5 39 6 49 5 50 39 18 48 975  277 60 1 1 6 0 25 1 0 0 0 1 6 2 15 1 28 1 6  277 60 1 1 6 0 25 1 3 7 8 28 2 29 8 37 25 40 29 48 36 85  277 60 1 1 6 0 25 1 4 10 4 37 5 39 1 48 875 50 38 78 48 475  277 60 1 1 6 0 25 1 6 15 6 56 3 57 9 72 375 80 57 58 71 975  460 60 3 1 6 0 25 1 0 0 0 1 6 2 15 1 28 1 6  460 60 3 1 6 0 25 1 3 7 8 9 4 11 0 13 75 15 10 68 13 35  460 60 3 1 6 0 25 1 4 10 4 18
8.   6 7  42 22 4 6 3  45 21 1 5 8  48 19 9 5 2  80 40 8 1 7 4  42 27 1 7 0  45 25 5 6 4  48 24 0 5 7  35 40            42 31 5 7 7  45 29 7 7 1  48 28 0 6 4  90 40 7 1 9 1  42 35 7 8 6  45 33 7 7 9  48 31 7 7 1  57 75 40 19  B   42 18 6 7 8  45 17 5 7 1  48 16 5 6 5  80 40 5 0 8 7  42 24 1 8 2  45 22 7 7 5  48 21 3 6 8  35 40 0 5 9   42 29 4 8 7  45 27 7 8 0  48 26 1 7 2  90 40 5 8 9 9  42 34 5 9 3  45 32 5 8 5  48 30 6 7 7  70 75 40 16 9 9 4  42 16 3 8 9  45 15 3 8 1  48 14 4 7 3       40    7 9 6  42 21 8 9 1  45 20 6 8 3  48 19 4 7 5  85 40 8 4 10 1  42 27 4 9 5  45 25 8 8 7  48 24 3 7 8  OQ 40 4 0 10 6  42 32 6 10 0  45 30 9 9 1  48 29 1 8 2       40 UV PRC003 EN                      Performance Data  Cooling   100   CoilG    Table 19  VUV 100  cooling coil G  4 row   16 fpi       Flow Rate  gpm       Entering Entering Entering 7          6667 10  Wet Bulb Dry Bulb Water             Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F   51 70 40 15 0 13 1 15 9  9 17 1 11 9 8 8 19 4 9 9 5 9 7 4  42 12 7 15 1 16 5 11 3 18 7 9 4 33 7 21 3 6 9  45                   30 3 19 9 6 2  48       26 8 18 5 5 5  15 40            4       9 1 3 9        42         36 7 27 6 7 5  45                   33 0 25 8 6 8  48 24 0 6 0       40 4 9 9 9  42 33 4 8 3  45 31 2 7 5  48 29 0 6 7  35 40 40 7 9 9  42 38
9.   F              F   MBh     F   MBh     F    A 50 120        15 7   140 22 2   160 28 6   180 35 1   55 120 14 8  140 20 9   160 27 1   180 33 2   60 120 14 0  140 19 7   160 25 5   180 31 3   65 120 13 1  140 18 5   160 24 0   180 29 4   70 120 12   140 17 3   160 22 4   180 27 5   B 50 120 0 6  140 29 2   160 37 7   180 46 3   55 120 19 5  140 27 6   160 35 7   180 43 8   o0 120 O   140 26 0   160 33 6   180 41 3   55 120 17   140 24 4   160 31 6   180 38 8   140 22 8   160 29 5   180 36 3   50 120 1   140 30 1   160 39 0   180 47 8   55 120 0 1  140 28 5   160 36 8   180 45 2   60 120 3 9  140 26 8   160 34 7   180 42 6   65 120 17 8  140 25 2   160 32 6   180 40 0   70 120 16 6  140 23 5   160 30 5   180 37 4       60 UV PRC003 EN                      Performance Data  Heating   150   Coil K  L    Table 45  VUV 150  steam heating coils K  low capacity   L  high capacity        Steam Pressure  psig    Entering      10 15  Air Temp         Airside Tota Airside Tota Airside  Dry Bulb   Capacity Temp Rise  Capacity Temp Rise                   Temp Rise   Size Coil    F   MBh     F  MBh     F   MBh     F    1500    0 154 7 95 5          10 148 4 91 6  20 142 2 87 8  30 136 0 83 9  40 80 1  50 76 3  60 72 5  70 68 6  L 0 140 9  10 135 2  20 129 6  30 123 9  40 118 3  50 112 6  60 107 0  70 101 3    psig   steam pressure  lIb in   gage     UV PRC003 EN 61    S TRANE     Performance Data       Electrical    Table 46  VUV 075 150  electrical performance       Blower Motor       E
10.   Horsepower  ea      Coil volume  gal  by coil type                                    gt        9     a s    16 5 8 16 5 8 16 5 8  21 1 4 21 1 4 21 1 4    320    14x20x1 2  14x24x1  1  14 x 20 x 1  2   14 x 30 x 1  1  14 x 24 x1  1   7X 42 x1  1  7   54x 1  1  7 X 66 x 1  1     7 8 10 Hose 7 8 ID Hose 7 8 10 Hose  FC 2 FC 2 FC 4    1 4       Table 2  Control methodology    Fan Speed    FSS       or infinite      CSTI       or infinite 3   Tracer ZN520    3    Tracer UC400    Infinite     a  With a field supplied 2 10 Vdc controller     Table 3  Control sequences    Fan Speeds  DX operation    1  Electric heat operation     1  Sidewall Exhaust     2  ERSA 5  2     a  Fan speed during sequence operation      b  Unit Ventilator when operating with option     UV PRC003 EN    405    1 4    Unit size    450    1 4       1500  105  16 5 8  21 1 4  30  470  14 x 24 x 1  2   14 x 30 x 1  1   7x 78x 1  1     7 8 10 Hose  FC   4    1 4    0 327  0 610  0 610  0 931  0 931  1 213  1 213  0 837    25       TRANE     General Data    Discharge and Inlet Arrangements    Figure 18  Discharge and inlet arrangements       Inlet Arrangement       Available in     16 5 8  Depth  21 1 4  Depth       Digit 13   1  RA Front with FA Back       Available          21 1 4  Depth  ONLY             Digit 13   4  Dynamic Air Barrier    26       Discharge Arrangement      Available in     16 5 8  Depth  21 1 4  Depth       Digit 23   0     B  C   0   Opening Only   A   Grille Discharge   B   Double Deflec
11.  0  45 26 2 6 3  48 24 5 5 7  75 40 7 8 8 0  42 36 2 7 6  45 34 0 6 9  48 31 6 6 2  80 40 45 7 8 9  42 43 9 8 4  45 41 2 7 6  48 38 5 6 8  85 40 53  9 9  42 51 1 9 3  45 47 9 8 5  48 44 8 7 6  90 40 00  11 0  42 57 8 10 4  45 54 2 9 4  48 50 7 8 4  57 75 40 1 4 10 0  42 30 1 9 4  45 28 2 8 6  48 26 4 7 7  80 40 40 6 10 5  42 39 0 9 9  45 36 5 9 0  48 34 2 8 0  85 40 49 6 11   42 47 6 10 5  45 44 6 9 5  48 41 7 8 5  90 40     12 0  42 55 9 11 3  45 52 4 10 2  48 49 0 9 1  70 75 40   5 11 4  42 26 4 10 7  45 24 7 9 7  48 23 1 8 7  90 40 0 9 11 7  42 35 4 11 0  45 33 2 10 0  48 31 0 8 9  42 44 3 11 5  45 41 6 10 4  48 38 9 9 3  90 40 55  12 8  42 53 1 12 1  45 49 8 11 0  48 46 6 9 8       58 UV PRC003 EN    Table 41  VUV 150  cooling coil J  DX   Suct EDB   70  F EDB   75  F  Size        Temp      SC LDB LWB      SC LDB LWB       1500 61 40 41 7 27 5 530 51 1 456 363 525 50 0  50 5  45 34 9 25 0 54 5 52 8 38 2 33 0 546 51 9  42 4  50 28 2 22 5 56 1 54 5  300 29 7 56 6 53 8 342  64 40 49 5 23 7 55 3 52 8  522 33 4 543 52 1  55 5  45 41 5 21 6 56 6 54 8 43 7 30 4 56 2 54 2 446 5  50 33 5 19 4 58 0 56 7 353 27 3 58 1 56 2 337 6  67 40 58 6 19 0 58 2 545 4605 292 56 9 53 9  62 7  45 49 1 173 59 3 56 8  507 26 6 58 5 56 3 52 6  50 39 7 15 5 60 4 58 9  40 9 23 9 60 2 58 6  42 4  70 40 701 241 601 55 7 1717  45 58 8 21 9 61 4 58 3  60 1  50 47 4 19 7 62 8 60 8  48 5  73 40 82 0  45 68 7  50 55 4    EDB   Entering Air Temperature  Dry Bulb    EWB   Entering Air Temperature  Wet Bulb    
12.  1       120 13 9  140 19 6  160 25 4  180 31 2  65 120 13 0  140 18 4  160 23 9  180 29 3  70 120 12   140 17 2  160 22 3  180 27 4  140 23 2  160 30 0  180 36 9  55 120 15 5  140 22 0  160 28 4  180 34 9  o0 120 14 6  140 20 7  160 26 8  180 32 9  65 120 13 7  140 19 4  160 25 2  180 30 9  70 120 12 8  140 19 2  160 23 5  180 28 9       44 UV PRC003 EN                      Performance Data  Heating   100   Coil K  L    Table 25  VUV 100  steam heating coils K  low capacity   L  high capacity        Steam Pressure  psig    Entering 5 10 15  Air Temp         Airside Tota Airside Tota Airside  Dry Bulb   Capacity Temp Rise  Capacity Temp Rise                   Temp Rise   Size Coil    F   MBh     F  MBh     F   MBh     F    1000    0 86 0 101 8 94 3           10 82 2   97 7 90 5  20   78 4     93 6 86 7  30 89 5 82 9  40 85 4 79 1  50 75 3  60 71 5  70 67 8  L 0 132 9  10 127 6  20 122 3  30 116 9  40 111 6  50 106 2  60 100 9  70 95 6    psig   steam pressure  lIb in   gage     UV PRC003 EN 45    S TRANE     Performance Data  Cooling   125   Coil D    Table 26  VUV 125  cooling coil D  3 row   12 fpi       Flow Rate  gpm       Entering Entering Entering Cs         0   14  Wet Bulb Dry Bulb Water  Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40   5 19 8 9 5 1 6 1  B
13.  19 8 7 7  48 18 4 6 8  80 40 8 7 9 6  42 27 5 9 0  45 25 6 8 1  48 23 8 7 1  35 40 5 0 10   42 33 5 9 5  45 31 3 8 6  48 29 1 7 6  90 40 41  10 9  42 39 4 10 2  45 36 7 9 2  48 34 2 8 1  70 75 40 19 4 10 4  42 18 6 9 7  45 17 3 8 7  48 16 1 7 7  OQ 40 0 1 10 6  42 24 9 10 0  45 23 3 9 0  48 21 6 7 9  85 40  7 11 1  42 31 2 10 4  45 29 1 9 3  48 27 1 8 2  90 40 9 1 11 7  42 37 4 11 0  45 34 9 9 8  48 32 4 8 7       42 UV PRC003 EN                      Performance Data  Cooling   100   Coil  DX     Table 21  VUV 100  cooling coil J  DX   Suct EDB   70  F EDB   75  F EDB   80  F EDB   85  F  Size EWB Temp      SC LDB LWB      SC        LWB      SC        LWB      SC LDB LWB  1000 61 40 29 1 191 521 505 318 253 51 3 493 352 310 510 479  394 363 51 0 46 0  45 24 4 17 4 53 7 52 3 26 7 230 53 5 51 4 29 5 28 1 53 7 50 2 33 0 33 0 54 1 48 7  50 19 7 15 6 55 4 54 1  215 20 7 55 6 53 4  23 8 23 8 57 7 52 5 26 6 26 6 60 1 51 3  64 40 346 16 5 546 521  864 232 533 514 387 295 524 504 416 355 518 491  45 29 0 15 0 56 0 54 2 30 5 21 1 55 2 53 6  32 5 26 8 54 9 52 8  34 9 32 2 54 9 51 8  50 23 4 13 5 57 4 56 3  246 19 0 57 2 55 8 26 2 24 11 57 4 55 2  28 2 28 2 58 6 54 4  67 40 40 9 13 2 576 537 422 203 560 531 437 271 546 525 457 335 536 51 6  45 34 3 12 0 58 8 56 1  35 4 18 5 57 7 55 6 36 7 24 6 57 0 55 1  38 3 30 5 56 4 54 4  50 277 10 8 59 9 58 4 28 5 16 6 59 5 58 1  296 22 2 59 2 57 6  30 9 27 4 59 3 57 1  70 40 48 9 16 8 59 3 548   500 23 8 57 7 543  513 30 6 56 4 53 7  45 41 0 15 2 6
14.  2  D 3  E 3  F 4  G 4  H 3  1500    1     2     2  D 3  E 3  F 4  G 4  H 3    EAT   entering air temperature    F   EWT   entering water temperature    F   CFM   tate of airflow  ft3 min    GPM   water flow  gal min    QT   total capacity  MBh    QS   sensible cooling capacity  MBh   DP   waterside pressure drop  ft H20     30 UV PRC003 EN                      Performance Data  Cooling   075   Coil D    Table 7 VUV 075  cooling coil cell     3 row   12 fpi       Flow Rate  gpm          Entering Entering Entering      2 J  lt  4    6   10  Wet Bulb Dry Bulb Water  Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F   MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 11 6 9 5 12  17  12 0 9 0 1  1   5 7  5  I5  5   42 14 5 4 9  45 13 6 4 4  48 12 7 3 9  75 40 19 7 5 7  42 18 8 5 4  45 17 6 4 8  48 16 4 4 3  90 40       0 4  42 22 8 5 9  45 21 3 5 3  48 19 8 4 7  85 40 7 7 7 1  42 26 5 6 6  45 24 8 5 9  48 23 1 5 2  90 40 1 4 7 9  42 30 1 7 4  45 28 1 6 6  48 26 2 5 8  57 75 40 16  7 1  42 15 6 6 7  45 14 6 6 0  48 13 6 5 3  80 40 1  7 5  42 20 3 7 0  45 18 9 6 3  48 17 6 5 5  35 40 5 8 9 0  42 24 7 7 5  45 23 1 6 7  48 21 5 5 9  90 40 0 4 8 5  42 29 1 8 0  45 27 1 7 2  48 25 3 6 3  70 75 40 14 3 8 1  42 13 7 7 6  45 12 8 6 8  48 11 9 6 0  80 40 19 2 8 3  42 18 4 7 8  45 17 2 7 0  48 16 0 6 2  85 40 24 1 8 7  42 23 0 8 1  45 21 5
15.  2 4 15 2 56 3 2  277 60 1 3 2 0 25 2 3 9 75 35 2 38 4 48 50 37 76 47 2  277 60 1 3 2 0 25 2 4 13 46 9 50 1 62 625 70 49 46 61 825  277 60 1 3 2 0 25 2 6 19 5 70 4 736 92 100 72 96 91 2  460 60 3 3 2 0 25 2 0 0 0 3 2 4 15 2 56 3 2  460 60 3 3 2 0 25 2 3 9 75 11 7 14 9 18 625 20 14 26 17 825  460 60 3 3 2 0 25 2 4 13 23 5 26 7 33 375 40 26 06 32 575  460 60 3 3 2 0 25 2 6 19 5 23 5 26 7 33 375 40 26 06 32 575  VUVE150 115 60 1 7 0 0 25 2 0 0 0 7 0 8 75 15 3 5 4 375  208 60 1 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  208 60 1 4 2 0 25 2 3 8 56 41 2 45 4 56 75 60 44 56 55 7  208 60 1 4 2 0 25 2 4 1142 54 9 59 1 73 875 80 58 26 72 825  208 60 1 4 2 0 25 2 6 17 13 82 4 86 6 108 25 125 85 76 107 2  208 60 3 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  208 60 3 4 2 0 25 2 3 8 56 23 8 28 0 35 40 27 16 33 95  208 60 3 4 2 0 25 2 4 11 42 36 36 40 6 50 7 50 39 72 49 65  208 60 3 4 2 0 25 2 6 17 13 47 5 51 7 64 625 70 50 86 63 575  230 60 1 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  230 60 1 4 2 0 25 2 3 11 4 47 5 51 7 64 625 70 50 86 63 575  230 60 1 4 2 0 25 2 4 15 2 63 3 67 5 84 375 90 66 66 83 325  230 60 1 4 2 0 25 2 6 22 8 95 99 2 124 125 98 36 122 95  230 60 3 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  230 60 3 4 2 0 25 2 3 11 4 27 4 31 6 39 5 40 30 76 38 45  230 60 3 4 2 0 25 2 4 15 2 41 87 46 1 57 5875 60 45 23 56 5375  230 60 3 4 2 0 25 2 6 22 8 54 8 59 0 73 75 80 58 16 72 7  277 60 1 3 2 0 25 2 0 0 0 3 2 4 15 2 56 3 2  277 60 1 3 2 0 25 2 3 11 4 41 2 44 4 55 5 60 43 76 54 7  277 60 1 3 2 0 25 
16.  32 3 46 4 63 1  22 0 34 2 49 2 66 8    Table 52  4 7 Cv rated valves in 1 2 in  piping packages    Gallons per minute  Piping package 5 6 7   9 10 11 12 13 14  1 Basic package 4 7 45 6 3 8 5 11 0 13 7 16 8 20 2 23 9 27 9 32 1  2 with CBV 4 7172 24 1 33 5 43 6 55 1 67 9          3 with strainer and CBV 4   19 1 21 4 37 2 48 5 61 3 75 5          Table 53  6 6 Cv rated valves in 3 4 in  piping packages  Gallons per minute  Piping package 9 10 11 12 13 14  15 16 17 18 19 20  1 Basic package 4 8 5 9 7 1 8 4 9 8 11 4 13 0 14 8 16 7 18 7 20 8 23 0  2 with CBV 16 8 20 7 25 1 29 8 34 9 40 5 46 5            3 with strainer and CBV 66 7212 26 2 31 7 37 7 44 2 51 2 58 8              76    UV PRC003 EN                      Controls  Piping Valve Options    Table 54  Control valve pressure drop  feet     2  or 3 way Gallons per minute  water valves  2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20  1 2         1 9 Cv  2 85 6 42 11 41 17 82 25 67 34 94                            1 2 in    4 7 Cv        2 73 3 93 5 35 6 99 8 84 10 92 13 21 15 72 18 45 21 4 24 56 27 95            3 4 in    6 6 Cv                3 51 4 33 5 25 60 24 7 33 8 50 9 75 11 10 12 53 14 04 15 65 17 34    Table 55  Vertical unit ventilator valve offering       2 position   2 way 3 way   1 2 in  2 way  1 9 Cv Hydronic   Normally Open   Close off 30 psi 1 2 in  3 way  1 9 Cv Hydronic   Close off 28 psi  3 4 in  2 way  3 5 Cv Hydronic   Normally Closed   Close off 20 psi 3 4 in  3 way  7 0 Cv Hydronic   Close off 10 psi 
17.  7 3  48 20 0 6 4  90 40 28 8 9 2  42 27 6 8 6  45 25 8 7 7  48 24 0 6 8       UV PRCOOS3 EN 31    S TRANE     Performance Data  Cooling   075   CoilE    Table 8  VUV 075  cooling coil E  3 row   16 fpi       Flow Rate  gpm       Entering Entering Entering 2 TB 10  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F   MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 12 0 9 5 12 6  17 9 12 1        0 13 6 7 6 15  5 4  42 14 7 5 1  45 13 7 4 6  48 12 7 4 0  75 40 19 9 5 9  42 19 0 5 5  45 17 7 5 0  48 16 5 4 4  90 40 4 1 0 5  42 23 0 6 1  45 21 5 5 5  48 19 9 4 9  85 40 8 0 7   42 26 8 6 8  45 25 0 6 1  48 23 2 5 4  90 40 1 7 8 1  42 30 3 7 6  45 28 3 6 8  48 26 3 6 0  57 75 40 16 5 7 4  42 15 8 6 9  45 14 7 6 2  48 13 7 5 5  80 40 1 4 7 7  42 20 4 7 2  45 19 1 6 5  48 17 7 5 7  95 40 0 1 9   42 24 9 7 7  45 23 3 6 9  48 21 6 6 1  90 40 0 6 8 8  42 29 3 8 2  45 27 3 7 4  48 25 4 6 5  70 75 40 14 4 8 4  42 13 8 7 8  45 12 9 7 0  48 12 0 6 2  80 40 19 4 8 6  42 18 6 8 0  45 17 3 7 2  48 16 1 6 4  85 40 24 3 8 9  42 23 2 8 4  45 21 7 7 5  48 20 1 6 6  90 40 29 1 9 4  42 27 8 8 8  45 26 0 7 9  48 24 1 7 0       32 UV PRC003 EN                      Performance Data  Cooling   075   Coil F    Table 9  VUV 075  cooling coil F  4 row   12 fpi       Flow Rate  gpm          Entering Entering Entering      2 J 
18.  8  26 5 15 3 61 1 59 5  27 2  13 40 44 8 15 6 60 7 55 3 345 6  45 37 6 14 2 62 4 58 6 4382  50 30 3 12 8 64 2 61 8 430 8          EWB   Entering Air Temperature  Wet Bulb    F  TC   Total Capacity  MBh    SC   Sensible Capacity  MBh    LDB   Leaving Air Temperature  Dry Bulb    F   LWB   Leaving Air Temperature  Wet Bulb    F     Table 13  Airflow correction    of design airflow        120  110  100  90  80    1 025  1 012  1 000  0 987               0 974    Total Capacity   MBh                   Sensible Capacity   MBh    1 105   1 051   0 998   0 945   0 892    Table 14  Airflow through coil J    Unit Model  Rated cfm    36    0750  748    EDB   85  F   SC LDB LWB  28 5 49 7 45 4  25 9 52 9 48 2  20 9 59 1 50 9  27 9 50 5 48 5  25 3 52 27 51 3  22 1 57 6 54 0  26 3 52 4 50 9  23 9 55 4 53 9  21 5 58 4 56 7  24 0 55 3 53 0  21 9 57 9 56 2  19 7 60 6 59 2  21 1 58 9 54 8  19 2 61 2 58 3  17 3 63 6 61 5    UV PRC003 EN                      Performance Data  Heating   075   Coil A  B  C    Table 15  VUV 075  hydronic heating coils A  1 row   12 fpi   B  2 row   12 fpi   C  2 row   16 fpi   Flow Rate  gpm       Entering C e               Air Temp  Entering   Tota Waterside           Waterside Tota Waterside  Dry Bulb Water Capacity Temp Drop Capacity Temp Drop  Capacity Temp Drop   Coil    F  Temp    F    MBh     F   MBh     F   MBh     F    A 50 120       7 9   140 11 1   160 14 4   180 17 7   55 120 7 4  140 10 5   160 13 6   180 16 7   00 120 reat  140 9 9   160 12 8   180 
19.  8 20 4 25 5 30 20 08 25 1  460 60 3 1 6 0 25 1 6 15 6 18 8 20 4 25 5 30 20 08 25 1  62 UV PRC003 EN                      Performance Data       Table 46  VUV 075 150  electrical performance  continued     Blower Motor       Electric Heat       Low FLA Option    Electrical                                                    Minimum Overcurrent Minimum  Unit FLA   Fan   Heating Total Circuit Protection Total Circuit  Model   Voltage  ea   HP Motors Elements kW Amp FLA Ampacity Device FLA Ampacity  VUVE125 115 60 1 7 0 0 25 2 0 0 0 7 0 8 75 15 35 4 375  208 60 1 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  208 60 1 4 2 0 25 2 3 7 32 35 2 39 4 49 25 50 38 56 48 2  208 60 1 4 2 0 25 2 4 9 76 46 9 51 1 63 875 70 50 26 62 825  208 60 1 4 2 0 25 2 6 14 65 70 4 74 6 93 25 100 73 76 92 2  208 60 3 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  208 60 3 4 2 0 25 2 3 7 32 20 3 24 5 30 625 30 23 66 29 575  208 60 3 4 2 0 25 2 4 9 76 31 03 35 2 44 0375 50 34 39 42 9875  208 60 3 4 2 0 25 2 6 14 65 40 7 44 9 56 125 60 44 06 55 075  230 60 1 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  230 60 1 4 2 0 25 2 3 9 75 40 6 44 8 56 60 43 96 54 95  230 60 1 4 2 0 25 2 4 13 54 2 58 4 73 80 57 56 71 95  230 60 1 4 2 0 25 2 6 19 5 81 3 85 5 106 875 125 84 66 105 825  230 60 3 4 2 0 25 2 0 0 0 4 2 5 25 15 3 36 4 2  230 60 3 4 2 0 25 2 3 9 75 23 5 27 7   34 625 40 26 86 33 575  230 60 3 4 2 0 25 2 4 13 35 82 40 0 50 025 50 39 18 48 975  230 60 3 4 2 0 25 2 6 19 5 46 9 51 1 63 875 70 50 26 62 825  277 60 1 3 2 0 25 2 0 0 0 3
20.  9 9 3  45 36 3 8 4  48 33 8 7 4  90 40 46 1 11 0  42 44 1 10 3  45 41 1 9 3  48 38 2 8 2  57 75 40 4 0 10 0  42 22 9 9 4  45 21 4 8 4  48 19 9 7 5  80 40 1 0 10 5  42 29 7 9 8  45 27 7 8 8  48 25 8 7 9  85 40 7 9 11 1  42 36 2 10 4  45 33 8 9 4  48 31 5 8 4  90 40 44 5 11 9  42 42 6 11 2  45 39 8 10 1  48 37 0 8 9  70 75 40 1 0 11   42 20 1 10 6  45 18 7 9 6  48 17 4 8 5  210 40     11 6  42 27 0 10 9  45 25 2 9 8  48 23 4 8 7  85 40 B  12 1  42 33 8 11 4  45 31 5 10 3  48 29 3 9 1  90 40 42  12 8  42 40 5 12 0  45 37 8 10 8  48 35 1 9 6       UV PRCOOS3 EN 41    S TRANE     Performance Data  Cooling   100   CoilH    Table 20  VUV 100  cooling coil H  3 row   16 fpi       Flow Rate  gpm          Entering Entering Entering 7      10  Wet Bulb Dry Bulb Water  Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F   51 70 40 14 0 12  14 9 1 16 1 11  7 0 18         8 0 6 6 7  42 11 9 14 1 10 7 17 5 8 8 30 7 19 7 6 3  45 27 5 18 4 5 7  48      lt            24 2 17 1 5 0  42           33 5 25 5 6 9  45          30 0 23 8 6 2  48                 26 4 22 1 5 5  B0 40               9    3 1  42 A   37 1 30 9 7 6  45             33 3 28 8 6 8  48 26 8 6 0  35 40 7 0 9 0  42 36 0 8 5  45 33 6 7 6  48 31 2 6 7  90 40 42 6 10 1  42 40 8 9 4  45 38 0 8 5  48 35 3 7 5  57 75 40   0 1  42 21 2 8 6  45
21.  FOR COOLING                 TN    BOILER  FOR HEAT ADD             AND OR                         CHILLER FOR  COOLING       The Importance of Air Quality    Indoor air quality  IAO  should be considered a top priority in the school environment  School  institutes contain a diverse day of activities that have a potential for air impurity sources including  cafeterias  art and science classrooms  vocational education areas  pools and locker rooms  Proper  ventilation and filtration of these spaces can pose some challenges     Occupant density in classrooms is much higher than that found in office or retail spaces  The  amount of outdoor air required to ventilate a classroom is based predominantly on the number of  students expected to occupy the space  Students also move in large groups  frequently throughout  the building  resulting in widely varied thermal loads within the zones  To compound the situation   a classroom mechanical system is typically run for 9 months of the year  and vacated for 3 months   either by turning up or off the HVAC system   To increase the IAQ challenge even more  building  construction techniques that help reduce energy costs  also tightly seal the school  This can lead  to uncirculated unfiltered air     Ventilation    Ventilation is an important factor in the maintenance of healthy air  In a poor ventilated school  building  fumes and vapors are not properly exhausted allowing particles to develop  A healthier  building is a building where the 
22.  Trane in the United States and other countries  All  trademarks referenced in this document are the trademarks of their respective owners     BACnet is a registered trademark of American Society of Heating  Refrigerating and Air   Conditioning Engineers  ASHRAE   Echelon  LoNMank  LonTalk  and LoNWoRks are registered  trademarks of Echelon Corporation          CERTIFIED     www ahridirectory org    Unit Ventilators    AHRI Standard 840      5           5    9      TRANE    Table of Contents    Features and Benefits                                                     5                 ne creat    dove wit ons                      mee Geo wie                     E 5  Install ability  Service ability and Maintain ability                        5  IAO Feats ages ea Gand ea eee oe dab ead a ada              A ed 7                                      eee ee ob eee eee ae eho eae ons 8   Application Considerations                                               10  A Choice in System        190                                              10   Selection Procedure       Hea awoke Tatius 21   Model Number Descriptions                                              23   Genera  Dale ues vapeur dg ed dd Rd               OR IE aoa HEC        d NR      XL 2b                          Data  was usns                 det pond  ur Vut e ado        hears 28   CONOIS dq                     64  Fall          SWIC      Prae      be Rem      e vd dos                 66  Customer Supplied Terminal Int
23.  also coordinates the operation of the fan in response to electric heat behavior and    electric behavior in response to hydronic heat behavior        The engine incorporates a user interface that allows adjustment of certain unit parameters           provides constant feedback on motor operation     e  he engine integrates service and troubleshooting tools     e The engine integrates a versatile configurable auxiliary temperature sensor     e The engine incorporates various safety and lockout features  such as maintaining proper fan    speeds if electric heat is called for     Status Display    Figure 21  Status display                                               1       The ECM engine board contains a four digit  seven segment display that is used to present  information in a format close to real world language  while having a small form factor  Most  characters are immediately recognizable  however  please consult Table 49 and Table 50 for the    graphical representation of each alphanumeric character     Table 49  Screen representation of alphabetical characters    A    C D  A b L d    G H I K L M    E F J  E F9 HI d HL n    Table 50  Screen representation of numeric characters    1 2       UV PRC003 EN    3 4 5    j d 5    U V    X Y 7   U u     H M e  9 0  9 0    65    S TRANE     Controls    End Device Controls    Fan Speed Switch    Figure 22     Fan speed switch          66    Note  Customer Low Voltage Interface for  Fan Speeds  Variable Fan Speed  and  24 Vac Sup
24.  automatically reduce fan speed when the sensible load is decreased  Figure 12  p  18   At full load  the fan operates at high speed and the control valve s flow is wide open  As the cooling  load decreases  the controller modulates the valve to throttle the rate of chilled water flow through  the coil  At some point  based on valve position  the unit controller switches the fan to low speed   Less airflow means that colder supply air is needed to maintain the target space temperature  The  control valve opens allowing the coil to remove more moisture from the passing air stream     The controller will also adjust the outside air damper to help properly ventilate the classroom at  the lower fan speed condition     Face and Bypass Dampers  Face and bypass control is a common and accepted method of capacity control     The face and bypass damper  consists of a single blade installed immediately upstream of the  cooling coil  The bypass is sized to have the same pressure drop as the cooling coil so that a  constant air quantity can be maintained at all times during system operation     Bypass control maintains the dry bulb temperature in the space by modulating the amount of air  flowing through the cooling coil  thus varying the supply air temperature to the space  As the face  and bypass damper begins to close some of the outside return air mix is diverted around the coil  and mixed with air coming off the coil to obtain a supply air temperature that is proportional to the  re
25.  bypass damper control is utilized for economizing and dehumidification of the  equipment during seasonal or morning warm up  The damper is constructed of aluminum grade  metal  The damper is tightly sealed and designed to minimize heat pickup in the bypass position     Controls options are  unit mounted fan speed switch  customer supplied terminal interface  CSTI    Tracer ZN520  and Tracer UC400  A variety of inputs and outputs are available for the CSTI and  Tracer controller options  A disconnect switch  for non electric heat units   fused transformer   contactor s   and terminal strip are provided with the CSTI and Tracer controller options     Customer Supplied Terminal Interface  CSTI     The control interface is intended to be used with a field supplied  low voltage thermostat or  controller  The control box contains a relay board which includes a line voltage to 24 volt  transformer  and an optional disconnect switch  All end devices are wired to a low voltage terminal  block and are run tested  so the only a power connection and thermostat controller connection is  needed to commission the unit  Changeover sensors and controls are provided whenever a  change over coil is selected  When N O  valves are selected  inverting relays are provided for use  with standard thermostats     Unit mounted Fan Speed Switch  FSS     The fan speed switch is available with or without the control interface option  The unit mounted  FSS will employ a low voltage fan switch  The low vol
26.  is closed  the fan is turned off and  the valves are fully opened     3  When in the unoccupied mode the Tracer ZN520 has an adjustable freeze avoidance setpoint   If the outside air temperature is below the setpoint the unit will open the valves to allow water  to flow through the coils     Interoperability  Interoperability allows the owner freedom to select multiple vendors  and  multiple products  With this advantage  the owner can choose the best products  the best  application  and the best service from a variety of suppliers to meet their evolving building control  needs in a cost effective manner     Generic Binary Input Output  The three generic binary inputs outputs are not part of the  normal control  but are actually controlled through the Tracer Summit system  when present  to  issue commands to the Tracer ZN520 control to turn the generic inputs outputs of add on  equipment  such as baseboard heating  exhaust fans  occupancy sensor  lighting  etc   on and off   This binary port is not affected when other binary diagnostics interrupt unit operation     UV PRC003 EN 71       TRANE     Controls  Tracer UC400    Tracer UC400    72    Figure 28        The Tracer UC400 controller delivers single zone VAV control and can be used in a stand alone  application or as part of a Trane Integrated Comfort System  ICS      Inthe stand alone configuration  Tracer UC400 receives operation commands from the zone sensor  and or the auto changeover sensor  on auto changeover units
27.  levels to a   minimum  Another solution for acoustically sensitive application is the option for    Low Acoustics      which uses the ECM technology to manage the fan speeds  However  if the room temperature rises  above the setpoint  the controller will switch to high speed for sustaining the space needs  As part  of this strategy  ventilation must also be considered  The Tracer UC400 controller will reposition  the outside air damper to confirm the minimum outside air cfm is met at both operating conditions   This setup allows the unit ventilator to meet the space comfort condition  while providing a lower  sound level and proper ventilation     Figure 9  Equipment placement       Ventilation for Acceptable IAQ    14    Supplying proper ventilation to a classroom is challenging  The various rooms that make up a  school are forever changing in their proper ventilation needs  Building occupants and their  activities generate pollutants that heighten the ventilation requirements  And because of this  intermittent occupancy  the ventilation frequency of a classroom is constantly on the move     Ventilation systems dilute and remove indoor contaminants  while mechanical heating and cooling  systems control the indoor temperature and humidity  Supplying an adequate amount of fresh air  to an occupied classroom is necessary for good indoor air quality         should be considered a top  priority in the school environment because children are still developing physically and are mo
28.  lt  4 J        6   10  Wet Bulb Dry Bulb Water Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F   MBh   MBh     F   MBh   MBh     F     MBh   MBh     F   51 70 40 11 6 9 1 12 6  17  11 4 3 9 0 9 12 7 7  5  14  5   42 13 7 4 8  45 12 8 4 4  48 11 8 3 9  42 17 8 5 3  45 16 5 4 7  48 15 3 4 2  90 40  5      42 21 5 5 8  45 20 0 5 2  48 18 6 4 6  85 40     0 9  42 25 0 6 5  45 23 3 5 8  48 21 6 5 2  90 40 9 7 7 7  42 28 3 7 2  45 26 4 6 5  48 24 5 5 7  57 75 40 15 4 750  42 14 8 6 6  45 13 7 5 9  48 12 7 5 2  80 40 0 0 7   42 19 1 6 9  45 17 8 6 2  48 16 5 5 5  85 40 24 4 7 8  42 23 3 7 3  45 21 7 6 6  48 20 1 5 8  90 40 28 7 8 3  42 27 4 7 8  45 25 5 7 0  48 23 7 6 2  70 75 40 13 5 7 9  42 12 9 7 4  45 12 0 6 7  48 11 2 5 9  80 40 18 2 8 1  42 17 3 7 6  45 16 2 6 9  48 15 0 6 1  85 40 22 7 8 5  42 21 7 8 0  45 20 2 7 2  48 18 8 6 3  90 40 27 2 8 9  42 26 0 8 4  45 24 2 7 5  48 22 5 6 7       UV PRC003 EN 33    S TRANE     Performance Data  Cooling   075   CoilG    Table 10  VUV 075  coil G  4 row   16 fpi       Flow Rate  gpm       Entering Entering Entering     2          6   10  Wet Bulb Dry Bulb Water Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F   MBh   MBh     F   MBh   MBh     F     MBh   MB
29.  only the mechanical devices that are required  to support the building load at a given time of day or night  true energy consumption savings may  be achieved     Maintenance and service information through the unit sensing devices are easily defined and  cured with an automated system     With factory shipped direct digital controls  installation and start up ofthe system are more simple     Condensate    Proper condensate trapping is required for the classroom unit ventilator s with hydronic and direct  expansion coils  steam coils do not require a trapped condensate setup   In a properly trapped  system  when condensate forms during normal operation  the water level in the trap rises until  there is a constant flow of water through the pipe  It is imperative to maintain water in the trap  and  not allow the trap to dry out during heating season     Equipment should be installed level to avoid condensate build up around the coil   Performance    Application of this product should be within the catalogs airflow and unit performance  The Trane  Official Product Selection System  TOPSS      will aid in the selection process for a set of given    UV PRC003 EN                      Application Considerations  Indoor Air Quality    conditions  If this program has not been made available  ask a local Trane account manager to    supply the desired selections or provide a copy of the program     Figure 7  System choice for the classroom unit ventilator    AND OR       CONDENSER      
30.  plate finned     Hydrostatically tested at 350 psig     All piping packages for the auxiliary preheat coil assemblies are always supplied as    a 1 2 in  package     Steam Heating Coils       1 row  tube in tube distributing coil    Piping packages for steam coils are field provided    Equipment specified with Trane controls will benefit from an optional 2 position  isolation valve  Main Coil  to be used for close off of the steam coil when the damper  is in full bypass position    The modulating piping valve  option  is shipped loose and field installed     Electric Heat Coils    Direct Expansion  DX  Coils   Refrigerant Cooling Coil     Electric preheat coils consist of special finned element for maximum life  heat transfer  and safety    Units include a high temperature cut out with a continuous sensing element  This  device interrupts electrical power whenever excessive temperatures are sensed along  the leaving air side of the coil    Power connection is made in the right hand end pocket    A circuit breaker option is available through the equipment model number     The DX refrigerant coil includes a factory mounted thermal expansion valve  TXV  and  equalizing tube  24 Vac transformer  time delay relay  frost detection  outside air  sensor    TXV is sized for R 410A refrigerant  The type of coil is order specific through the unit  model number selection     Figure 43  Coil header location       FRONT OF UNIT    UV PRC003 EN    7 8  O D   xt DRAIN            TRANE    He
31.  recovery  and post conditioning  reheat  may be applied in  the same system     For more information on outdoor air preconditioning and energy recovery  refer to the Trane  application engineering manual  Air to Air Energy Recovery in HVAC Systems  SYS APM003 EN      Figure 17  Cold coil with outdoor air preconditioning            Cooling Load       Wheel  Without    Wheel      With  Wheel    Exhaust  Air    Return Air    Outdoor  Air       Space  Ah   Reduction in cooling load due to  preconditioning    UV PRC003 EN         TRANE    Selection Procedure    UV PRC003 EN    Trane vertical classroom unit ventilators provide air delivery and capacities necessary to meet the  requirements of modern school classrooms  They are available with the industry s widest selection  of coils to precisely satisfy heating  ventilating and air conditioning loads with the best individual  type of system  Unit ventilator selection involves three basic steps    e Determine the classroom space unit cooling and or heating loads   e Determine the unit size   e Select the coil    Capacity Required    The first step in unit ventilator selection is to determine room heating and air conditioning loads   The calculation of this load is essential if the equipment is to be economical in first cost and  operating cost     Adequate ventilation is mandatory in classroom air conditioning design  The amount is often  specified by local or state codes and  in air conditioned schools  may be either the same or l
32.  unit is capable of functioning independently of one another  during occupied and unoccupied hours of the day  This allows the temperature setpoint and  ventilation setting to be changed automatically based on classroom usage  see Figure 27  p  70      UV PRC003 EN 69    S TRANE     Controls    Tracer ZN520  LonTalk     70    Figure 27  Tracer ZN520 system      47 Rover    optional     Tracer    Unit                 Vent    Coil    Fire Safety    System 4     Unit           Lighting Vent 8  System          Security Coil  System  gt             other    To other Trane Products    Building Products    Two Systems in One    In an ICS environment  the Tracer ZN520 is pre designed to install quickly and easily into the  system  Since the controller and the unit are factory tested and commissioned  the start up time  for the entire system is minimized  Trane becomes the single source of responsibility for the  equipment  unit controls  and building automation system     As a standalone controller  the Tracer ZN520 is ideally suited for fix on fail replacement of units  with old pneumatic controllers  or in situations where a BAS will be added at a later date  Once  power is applied to the controller  it will automatically start up and run based upon the setpoint on  the local zone sensor  An individual time clock can be added to the unit for local scheduling     The Tracer ZN520 is certified to the interoperable LoNMARK   Space Comfort Controller profile  This  allows the controlle
33. 0 1 8      42 30 5 8 7  45 28 4 7 9  48 26 5 7 0  35 40 9 9 9 0  42 38 1 9 0  45 35 6 8 2  48 33 1 7 3  90 40 47 7 10 1  42 45 7 9 5  45 42 7 8 6  48 39 7 7 7       48 UV PRC003 EN                      Performance Data  Cooling   125   CoilG    Table 29  VUV 125  cooling coil G  4 row   16 fpi       Flow Rate  gpm       Entering Entering Entering 6        14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F   MBh   MBh     F            MBh     F   MBh   MBh     F   51 70 40    19 8 9 4 1 8 8 4 6 1 4 7 4 5 7 6 0  42 24 6 5 7  45 22 9 5 2  48 21 3 4 6  15 40   0 0  42 31 9 6 2  45 29 7 5 6  48 27 6 5 0  80 40 40  7   42 38 6 6 8  45 36 0 6 2  48 33 4 5 5  42 44 9 7 6  45 41 8 6 9  48 38 9 6 2  90 40 53  9 0  42 50 8 8 5  45 47 4 7 7  48 44 0 6 9  57 75 40 7 7 B   42 26 5 7 7  45 24 7 7 0  48 22 9 6 2  80 40 5 8 9 6  42 34 2 8 1  45 31 9 7 3  48 29 7 6 5  85 40 43 7 9 1  42 41 8 8 6  45 39 0 7 8  48 36 2 6 9  90 40 51 4 9 8  42 49 1 9 2  45 45 8 8 3  48 42 6 7 4  70 75 40 4       42 23 2 8 7  45 21 6 7 9  48 20 1 7 1  30 40  gt  9 5  42 31 1 9 0  45 29 0 8 1  48 26 9 7 3  35 40 40 7 9 9  42 39 0 9 4  45 36 3 8 5  48 33 7 7 6  90 40 9 8 10 5  42 46 7 9 9  45 43 5 8 9  48 40 4 8 0       UV PRCOO3 EN 49    S TRANE     Performance Data  Cooling   125   CoilH    Table 30  VUV 125  cooling coil H  3 row   16 fpi       Flo
34. 0 28 2 165 57 8 56 7 29 7 23 2 57 9 56 2 331 6  6  40 49 3 16 2 58 0 544  509 249 56 6 53 9  52 8  45 41 3 14 7 59 1 56 7  42 7 22 6 58 3 56 2 4442  50 33 3 13 2 60 2 58 9  344 20 3 00 0 58 5  35 7  70 40 59 0 20 5 59 9 55 6  60 3  45 49 4 18 6 61 3 58 3  50 5  50 39 9 16 8 62 6 60 8  40 8  73 40 68 9  45 57 8  50 46 6    EDB   Entering Air Temperature  Dry Bulb    EWB   Entering Air Temperature  Wet Bulb    TC   Total Capacity  MBh    SC   Sensible Capacity  MBh    LDB   Leaving Air Temperature  Dry Bulb        LWB   Leaving Air Temperature  Wet Bulb        F   F     Table 32  Airflow correction    of design airflow        120  110  100  90  80    1 025  1 012  1 000  0 987               0 974    Total Capacity   MBh                   Sensible Capacity   MBh    1 105   1 051   0 998   0 945   0 892    Table 33  Airflow through coil J    Unit Model  Rated CFM    UV PRC003 EN    1250  1253                      Performance Data  Cooling   125   Coil  DX     EDB   80  F EDB   85  F   SC LDB LWB      SC LDB LWB  37 8 52 1 48 5 47 5 443 52 3 40 8  34 4 54 6 50 8  39 8 39 8 55 6 49 4  28 7 58 8 52 9 321 32 1 61 3 51 8  361 533 511  50 2 43 4 52 9 49 9  32 8 55 8 53 4 421 39 4 55 9 52 5  29 5 58 2 55 6 340 34 0 59 9 54 9  33 1 55 5 533 551 41 0 54 7 52 5  30 1 57 8 55 8 462 37 2 57 5 551  27 1 60 0 58 1  37 3 33 5 60 2 57 6  291 58 5 55 2 619 37 4 57 4 54 6  26 4 600 5 57 9  519 340 59 9 57 5  23 8 62 4 60 5  419 30 6 62 4 60 1  24 3 62 0 57 0   0 1 32 8 60 8 56 6  22 1 63 7 60 0  5
35. 0 8 57 6  41 9 21 6 59 8 57 2  43 0 27 8 59 0 56 7  50 33 1 13 7 62 2 60 2  338 19 5 01 7 60 0  347 25 0 61 6 59 6  73 40 5  2 19 9 614 56 0  561 26 9 59 8 55 6  45 47 9 18 1 63 1 59 2 48 7 24 44 62 2 58 9  50 38 7 16 2 64 8 62 2 39 3 22 0 64 4 61 9    EDB   Entering Air Temperature  Dry Bulb    EWB   Entering Air Temperature  Wet Bulb    TC   Total Capacity  MBh    SC   Sensible Capacity  MBh    LDB   Leaving Air Temperature  Dry Bulb    F   LWB   Leaving Air Temperature  Wet Bulb    F     UV PRC003 EN    Table 22  Airflow correction    of design airflow   Total Capacity  Sensible Capacity      MBh   MBh    120 1 025 1 105   110 1 012 1 051   100 1 000 0 998   90 0 987 0 945   80 0 974 0 892   Table 23  Airflow through coil J   Unit Model 1000   Rated cfm 989    43       TRANE     Performance Data  Heating   100   Coil A  B  C    Table 24  VUV 100  hydronic heating coils A  1 row   12 fpi   B  2 row   12 fpi   C  2 row   16 fpi   Flow Rate  gpm             28 22  24 21 6  Entering Air Entering Tota Waterside  Tota Waterside  Tota Waterside  Temp  Dry Water Capacity Temp Drop  Capacity Temp Drop  Capacity Temp Drop   Coil Bulb    F  Temp    F    MBh     F   MBh     F   MBh     F    A 50 120 9 8   140 13 9  160 17 9  180 22 0  55 120 9 3  140 13 1  160 16 9  180 20 8  5 U 120 8 7  140 12 3  160 16 0  180 19 6  05 120      140 11 6  160 15 0  180 18 4  70 120 7 6  140 10 8  160 14 0  180 17 2     50 120 15 6  140 22 0  160 28 5  180 35 0  55 120 14 7  140 20 8  160 26 9  180 33
36. 0 the unit ventilator delivers the airflow the space needs   When the air flow adjusts the outside air damper will also adjust to satisfy the space needs  This  helps maintain the proper amount of ventilation air to the occupants independent of the fan speed   As part of the ventilation strategy  the controller will reposition the outside air damper to confirm  the minimum outside airflow is met at both operating conditions     Filter Maintenance  Filter status for the controller is based on the cumulative run hours of the  unit fan  The controller compares the amount of fan run time against an adjustable fan run hour   stored in the controller  to determine when maintenance is recommended for the unit  The run   hours value may be user edited as required  The valid range for the fan run hours limit is 0 to  5000 hours with a default of 600 hours  Once the run hours limit has been exceeded  the controller  generates a maintenance required diagnostic  unit will not shut down   The user will be notified  of this diagnostic through the building automation system or when a Trane   service tool is  communicating with the controller     Active Dehumidification  On unit ventilators with reheat coils  the controller can provide active  dehumidification to the classroom  This means that the classroom relative humidity can be kept  below an adjustable setpoint independent outdoor weather conditions  Indoor humidity levels are  recommended by ASHRAE to be kept below 60 percent in order 
37. 0cfm   100  1000 cfm   125  1250 cfm   150  1500 cfm   Digit 8     Voltage  Volts Hz   Phase    0   115 60 1   1   208 60 1   2   230 60 1         208 60 3   4   460 60 3   7   277 60 1   8   230 60 3    Digit 9     Open Digit    Digits 10  11     Current Design  Sequence    Digit 12     Face  amp  Bypass   Y Yes  Include Damper   N No Damper   Digit 13     Unit Arrangement    Return Air Front   Fresh Air Back  100  Return Air Front   10096 Fresh Air Back   Dynamic Air Barrier  ERS Compatible w RH  Connection   6   ERS Compatible w LH Connection    Digit 14      Preheat   Reheat    Changeover                n n Hn ue i    A   4          Preheat  RH Clg LH Htg   B   4 Pipe Preheat  LH Clg RH        C   4        Reheat  RH Clg LH Htg   D   4 Pipe Reheat  LH Clg RH Htg    E   2         RH Connections         2         LH Connections    Digit 15   Cooling   2        Coil  0   None        2 Row  12                2 Row  16           D    3 Row  12           E   3 Row  16           F   4 Row  12 FPI    G   4Row  14 EPI          3 Row  16         EarthWise    Coil  J   3 Row  DX  R 410A  Cooling Coil    UV PRC003 EN    Digit 16     Heating Coil  None   1 Row  12          2 Row  12 EPI   2 Row  16 EPI   3 Row  12          3 Row  16          4 Row  12          4 Row  14          3 Row  16         EarthWise Coil  Steam Low   Steam High   Electric Heat   Low  Electric Heat   Med  Electric Heat   High    it 17     Motor    Electronically Commutated Motor   ECM    ECM  amp  Low Acoustic O
38. 1 085 x cfmt x  T4   T2    cfm    Total air capacity of unit with outside air damper open 100 percent           Room temperature    T2   Outside air temperature    In classrooms with exceptionally heavy air conditioning loads  unit size may be determined by the  total cooling requirement  Good practice dictates 375 to 425 cfm per ton of hydronic cooling  capacity  Normally  however  Trane classroom air conditioner coils have sufficient capacities   Example    Given  Air circulation specified   8 air changes per hour    Classroom size   35 ft long x 25 ft wide x 10 ft high   Inside design air temperature   75 degrees F    Ventilation cooling required at 58 degrees F   29 000 BTU           required   8 changes hr x  35 x 25 x 10 ft    1170 cfm  60 Minutes hr   Checking ventilation cooling capacity    29 800 BTU   1 085 x CFM x  80 58    CFM   1250    This indicates that a 1250 cfm unit would have satisfactory ventilation cooling capacity at the  design changeover point of 58  F  Coil capacity will become confirmed when the coil is selected        Coil Selection    Selecting the correct coil is done through Trane   s Official Product Selection System  TOPSS  For  your convenience  TOPSS has a mixed air calculator built into the program     UV PRC003 EN    Model Number Descriptions    Vertical Unit Ventilator  Model Number    Digits 1  2  3     Unit  Configuration    VUV  Vertical Unit Ventilator  Digit 4     Development  Sequence   E   Digits 5  6  7     Nominal Airflow  075  75
39. 15 7   05 1    O 0  140 9 3   160 12 0   180 14 8   70 120 0 1  140 8 7   160 11 2   180 13 8      50 120 12   140 17 4   160 22 5   180 27 7   55 120 11 6  140 16 4   160 21 3   180 26 2   60 120 10 9  140 15 5   160 20 1   180 24 7   65 120 10   140 14 6   160 18 9   180 23 2   70 120 9 6  140 13 6   160 17 6   180 21 7   50 120 12 9  140 18 3   160 23 6   180 29 0   55 120 12   140 17 3   160 22 4   180 27 5   60 120 11 5  140 16 3   160 21 1   180 25 9   65 120 10 8  140 15 3   160 19 8   180 24 3   70 120 10 1  140 14 3   160 18 5   180 22 7       UV PRC003 EN 37    S TRANE     Performance Data    Heating   075   Coil K  L    38    Table 16  VUV 075  steam heating coil K  low capacity   L  high capacity        Entering  Air Temp   Dry Bulb  Size Coil    F   750 K 0    Steam Pressure  psig  10           Tota Airside Tota Airside Tota  Capacity Temp Rise                Temp Rise  Capacity   MBh    F  MBh     F   MBh     84 8 75 3  72 3  69 3  66 3  63 2           psig   Steam Pressure  lb in   gage     15  Airside  Temp Rise     F   93 0  89 2  85 5  81 8  78 1  74 3  70 6  66 9  109 9  105 4  101 0  96 6  92 2  87 8  83 4  79 0    UV PRC003 EN                      Performance Data  Heating   100   Coil E    Table 17  VUV 100  cooling coil E  3 row   16 fpi       Flow Rate  gpm       Entering Entering Entering 2 J  lt      4 J 6   10  Wet Bulb Dry Bulb Water  Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT C
40. 2 4 15 2 54 9 58 1 72 625 80 57 46 71 825  277 60 1 3 2 0 25 2 6 22 8 82 3 85 5 106 875 125 84 86 106 075  460 60 3 3 2 0 25 2 0 0 0 3 2 4 15 2 56 3 2  460 60 3 3 2 0 25 2 3 11 4 13 7 16 9 21 125 20 16 26 20 325  460 60 3 3 2 0 25 2 4 15 2 27 4 30 6 38 25 40 29 96 37 45  460 60 3 3 2 0 25 2 6 22 8 27 4 30 6 38 25 40 29 96 37 45  UV PRC003 EN 63       TRANE    Controls    Why Trane Controls     64    Whether involved in a retrofit or in new construction applications  Trane has the control design to  fit the systems requirements  The broad range of control packages offer a range from a field  convertible end device package  to a complete building automation system solution with LonTalk    controls     The good news is Trane   controls are factory mounted   wired   tested and configured or  programmed with Trane   application expertise to provide comfort  efficiency  and reliability  as  well as  single source warranty and service  With Trane   s integrated controls  the installed costs are  lower because the equipment has turn key factory controls and every component of the system is  optimized to fit with the controller  Trane installs not only the controller  but also the hardware that  works intimately with the controller to allow the system to function properly  i e   piping package   valves  dampers  actuators            When a classroom unit ventilator with Trane   controls arrives to  the jobsite  it is completely ready for quick installation     Table 47  Controller inp
41. 3 3 11 2  45 49 9 10 1  48 46 5 8 9       54 UV PRC003 EN                      Performance Data  Cooling   150   Coil E    Table 37 VUV 150  cooling coil     3 row   16 fpi       Flow Rate  gpm       Entering Entering Entering 6 J   8  lt  1      10   14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 1 8    1 11 0 7 1 5 4 9 7 42  7  8 7 48  9 5 7 1  42 10 4 28 3 6 6  45 26 4 6 0  48 24 6 5 3  75 40     7 7  42 36 7 7 2  45 34 3 6 5  48 31 9 5 8  210 40 46 4 8 5  42 44 4 8 0  45 41 5 7 2  48 38 6 6 4  85 40 53 9 9 5  42 51 6 8 9  45 48 3 8 0  48 44 9 7 1  90 40 01 1 10 5  42 58 5 9 9  45 54 7 8 9  48 50 9 7 9  57 75 40 1 8 9 6  42 30 5 9 0  45 28 5 8 1  48 26 5 7 2  80 40    0 41  10 0  42 7 39 4 9 4  45    2 36 8 8 5  48    5 34 3 7 5  35 40    D 50  10 7  42  9 48 1 10 0  45  9 45 0 9 0  48    8 41 9 8 0  90 40  8 59 0 11 4  42 73 9 56 6 10 7  45 66 5 52 8 9 7  48 58 8 49 2 8 6  70 75 40 74 9 7 8 10 9  42 70 2 26 7 10 2  45 63 1 24 9 9 2  48 55 9 23 2 8 2  80 40 76 9 7 4 11   42 72 1 35 8 10 5  45 64 8 33 5 9 4  48 57 4 31 2 8 4  85 40 46 8 11 6  42 44 8 10 9  45 41 9 9 8  48 39 0 8 7  90 40 56 1 12   42 53 7 11 5  45 50 2 10 4  48 46 7 9 2       UV PRCOOS3 EN 55    S TRANE     Performance Data  Cooling   150   Coil F    Table 38  VUV 150  coo
42. 3 8  N    SIDE VIEW  Depicting Step down  Falseback    UNIT SIZE   NO  FANS                                A                               2    RETURN AIR     OPTIONAL                                     STEP DOWN  FALSEBACK                    1  THE UNIT LENGTH DOES NOT INCLUDE 5 8  END PANELS   APPLICATIONS   WHERE WINDOW     2  THE POWER CONNECTION IS MADE IN THE LEFT HAND  SEAL MAY INTERFERE y        POCKET FOR ALL OPTIONS BUT ELECTRIC HEAT    OPTIONAL    3  THE POWER CONNECTION FOR ELECTRIC HEAT OPTION    IS MADE IN THE RIGHT HAND END POCKET     4  THE UNIT SHOWN INCLUDES THE INSULATED HORIZONTAL  BAFFLE OPTION     STEP DOWN  FALSEBACK    UV PRCOOS3 EN 83       TRANE     Dimensional Data       Dynamic Air Barrier Unit     4 K O  FOR PIPING  OR ELECTRICAL    21 1 4             16 5 8     lt    2 3 8     7 8  O D     DRAIN T  12 1 2    9 1 4      i     FRESH AIR OPENING    REEL   5 1 4      EEE D        22 5 8        2 4 4   lt 9   gt  Be 8 1 8     13 1 2   gt  12 1 4     BACK VIEW SIDE VIEW     2 9  x 9  229mm x 229mm   KNOCKOUTS IN BOTTOM    2 1 4        TOP VIEW  FALSEBACK       UNIT SIZE   NO  FANS  ESEN     epe              2  2  4  4         pee       NOTE   1  THE UNIT LENGTH DOES NOT INCLUDE 5 8  END PANELS     2  THE POWER CONNECTION IS MADE IN THE LEFT HAND  END POCKET FOR ALL OPTIONS BUT ELECTRIC HEAT     3  THE POWER CONNECTION FOR ELECTRIC HEAT OPTION  IS MADE IN THE RIGHT HAND END POCKET     84 UV PRC003 EN    UV PRC003 EN           6 M    Digit 33   1       
43. 4   21 1 4     Depth without Cutouts   5   21 1 4 in  Depth with    x 7 1 4 in   Cutout   6   21 1 4      Depth with 3 1 4 in  x    16 7 8 in  Cutout    Digit 34     Front Panel  1 Standard Front Panel    2 Heavy Gauge Front Panel   Digit 35     Subbase   0   No Subbase   2   2in Subbase   4   4in  Subbase   6   6in Subbase   Digit 36     Piping Package        None   1   Ball Valves  amp  P T Ports   2   Ball Valve 8 Circuit Setter with  P T Ports   3   Ball Valve  Circuit Setter with    P T Ports  amp  Strainer  Digit 37     Flow Control    Cooling Changeover Coil  0   None  Digit 38     Flow Controls    Heating Coil  0   None    24    Digit 39     Auxiliary Drain Pan    Piping   Y   Yes  Auxiliary Drain Pan   N   No Auxiliary Drain Pan    Digit 40     Crossover Piping    0   None   1   Internal   2   External 1 3 8 in  Crossover  Piping   3   External 2 1 8 in  Crossover  Piping    Digit 41     Filter   1 Standard Throwaway Filter  2 MERV 8 Filter   3 MERV 13 Filter    Digit 42     Color    Deluxe Beige  Cameo White  Soft Dove  Stone Gray  Driftwood Gray                HH H HW I    UV PRC003 EN    General Data    Table 1  General data    Description   Unit length without end covers  in    Unit depth   standard  in     Unit depth   with false back  in    Unit height   standard  in    Shipping weight  Ib    Nominal filter size  in   and  quantity   Dynamic air filter nominal   size  in   and quantity   Drain connection size  in     Fan type   quantity   Motor data   Quantity 
44. 40 certified  These units may ship with a fan   speed setting that delivers a lower than specified airflow  perhaps to reduce sound levels  Without  an overall building design goal  these units will be installed without delivering the specified airflow  needed to support the fresh air circulation  and possibly compromise IAQ     Note  Unless the equipment is tested at the specified airflow  it is extremely difficult to determine  whether the unit meets the specified sound level     Trane sunit ventilator will not compromise air quality to support a minor reduction in airflow noise   We encourage our engineers to specify their airflow needs at full building load requirements  Fine   tuning of the speed setting may be interchanged through the unit s 3 speed fan sensor quickly and  easily  This mechanical feature ensures that the equipment supplies proper cfm to support IAQ in  the classroom  while giving complete control of equipment noise to the administrative staff     Technology that Supports Acoustic Enhancements    UV PRCOOS3 EN    Another solution to airflow noise is through Trane direct digital controls  Tracer UC400   With the  Tracer UC400 controller  an infinitely variable speed fan control for the unit ventilator delivers the  airflow output customized to support the cfm space needs  When less cfm is necessary to meet the    13       TRANE     Application Considerations    Ventilation    load of the classroom  the equipment operates at an optimum speed  keeping sound
45. 8 7 29 8 63 0 59 7  19 9 65 3 62 8 47 4 26 9 65 1 62 5    51    S TRANE     Performance Data  Heating   125   Coil A  B  C    Table 34  VUV 125  hydronic heating coils A  1 row   12 fpi   B  2 row   12 fpi   C  2 row  16 fpi   Flow Rate  gpm       Entering  gt     4   6  Air Temp  Entering Tota Waterside  Tota Waterside  Tota Waterside  Dry Bulb Water Capacity Temp Drop  Capacity Temp Drop  Capacity Temp Drop   Coil   F  Temp    F    MBh     F   MBh     F   MBh     F    A 50 120       i   12 8   140 18 0  160 23 3  180 28 5  55 120 12 0  140 17 0  160 22 0  180 27 0  60 120 11   140 16 0  160 20 7  180 25 4  65 1    10 6  140 15 0  160 19 4  180 23 9  70 120 0 9  140 14 0  160 19 2  180 22 3  140 23 6  160 30 5  180 37 4  55 120 15 8  140 22 3  160 28 8  180 35 4  60 120 14 8  140 21 0  160 27 1  180 33 3  65 120 13 9  140 19 7  160 25 5  180 31 3  70 120 13 0  140 18 4  160 23 8  180 29 3  50 120 18 4  140 26 0  160 33 6  180 41 3  55 120 17 4  140 24 6  160 31 8  180 39 0  OU 120 16 4  140 23 2  160 30 0  180 36 8  65 120 15 4  140 21 7  160 28 2  180 34 6  70 120 14 4  140 20 3  160 26 3  180 32 3       52 UV PRC003 EN                      Performance Data  Heating   125   Coil K  L    Table 35  VUV 125  steam heating coils     low capacity   L  high capacity        Steam Pressure  psig    Entering  5 10 15  Air Temp         Airside Tota Airside Tota Airside  Dry Bulb   Capacity Temp Rise                   Temp Rise                   Temp Rise  Size Coil    F   MBh     F  
46. 90 40 0    9 0  42 29 4 7 5  45 27 5 6 8  48 25 7 6 1  42 15 3 6 8  45 14 3 6 2  48 13 4 5 5  80 40 0    1 6  42 19 8 7 2  45 18 5 6 5  48 17 3 5 8  85 40 25 3 8 1  42 24 2 7 6  45 22 6 6 9  48 21 1 6 1  90 40 29 7 8 7  42 28 4 8 2  45 26 6 7 4  48 24 8 6 6  70 75 40 14 0 8 3  42 13 4 7 8  45 12 5 7 0  48 11 7 6 3  80 40 18 8 8 5  42 18 0 8 0  45 16 8 7 2  48 15 7 6 4  85 40 23 5 8 8  42 22 5 8 3  45 21 1 7 5  48 19 7 6 7  90 40 28 2 9 3  42 27 0 8 8  45 25 2 7 9  48 23 6 7 0       UV PRCOOS3 EN 3b    S TRANE     Performance Data  Cooling   075   Coil  DX     Table 12  VUV 075  cooling coil J  DX     EDB   Entering Air Temperature  Dry Bulb    F    Suct EDB   70  F EDB   75  F EDB   80  F  Size EWB Temp  TC SC LDB LWB      SC LDB LWB      SC LDB LWB         750 61 40 22 8 15 0 51 4 500 25 0 199 504 48 8  27 7 24 3 49 9 47 2 30 9  45 191 13 7 530 52 0 20 9 18 1 52 6 510  23 22 22 1 52 6 49 7  25 9  50 154 12 3 54 8 538 16 9 162 54 9 53 1 18 7 18 7 56 9 52 1 220 9  64 40 27 1 130 539 516  286 18 3 52 3 50 8 30 44 232 513 49 8 32  7  45 22 7 118 55 4 53 9 23 9 166 54 5 532 25 5 211 53 9 52 3 127 4  50 18 3 10 6 56 9 56 0 19 3 14 9 56 6 55 5 20 60 19 0 56 5 54 8 22 1  6  40 32 1 104 57 1 531 331 160 55 2 525 343 213 536 518 35 9  45 26 9 58 4 55 7 27 8 14 5 57 1 55 11  288 193 56 1 54 6  30 1  50 21 7 8 5 59 5 58 1 22 4 13 1 58 8 57 7 23 2 17 4 58 5 57 2 424 3  70 40 38 4 132 58 7 54 1  3922 18 7 569 53 6  40 3  45 32 2 12 0 60 1 57 0 329 17 0 590 56 6  33 7  50 26 0 10 8 61 6 59
47. ENING     This option allows the wallbox to be located up to   1  below the unit ventilator  This helps eliminate snow  or debris from entering the wallbox and protects   the crossover piping     UV PRCOOS3 EN    and 21 1 4  depth units  The subbase increases  the overall height of the unit ventilator from 30   to  32   34  or 36   The additional height raises   the outdoor air opening to help eliminate   snow or debris from entering the wallbox     27       TRANE    Performance Data    Table 4  Coil combination selection chart  cooling  2 pipe changeover or heating only coils     Preheat or reheat coils    Coil type  Coil description                  K          MT N    P                           prow12ti                andCcoomgdas  X     x        x     x     Xx   x  X  X  C      row tei            pvalableinTOPSS               X   X   X  Drow           X X X                            Brow 163i       XX         161P                 A   n  HTrow lo tpi  EarthWise    _   _   _ EE                      1       NE               1   Heating only    Steam  high capacity    22 4  Electric heat   3 element  Electric heat   4 element Heating only  Electric heat   6 element    Notes     1  All coil types on the left side of the grid are available in single coil  heating only  or 2 pipe changeover with exception of coil type A   2  For 2 coil or 4 pipe systems  select the cooling coil on the left side of the grid  An X corresponds to a valid heating coil combination   3  Shaded areas 
48. MBh     F   MBh     F   1250    0 86 6 128 1 94 9           10 82 7   122 9 91 1  20   79 0     117 8 87 3  30 112 8 83 6  40 107 7 79 8  50 76 0  60 72 1  70 68 3  L 0 112 1  10 107 6  20 103 1  30 98 6  40 94 1  50 89 7  60 85 2  70 80 7    psig   steam pressure  lIb in   gage     UV PRC003 EN 53    S TRANE     Performance Data  Cooling   150   Coil D    Table 36  VUV 150  cooling coil D  3 row   12 fpi       Flow Rate  gpm          Entering Entering Entering 6     1          10   14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 0 9    0 10 7 0 5 5  9 4 41 0 7 0 8 4 46 9     6 9  42 28 1 6 4  45 26 3 5 8  48 24 5 5 2  75 40 8 0 7 5  42 36 4 7 0  45 34 0 6 3  48 31 8 5 6  90 40 46 0      42 44 0 7 8  45 41 2 7 0  48 38 5 6 2  85 40 53 5      42 51 2 8 6  45 48 0 7 8  48 44 8 6 9  90 40 00 6 10   42 58 0 9 6  45 54 3 8 6  48 50 7 7 7  57 75 40 1 5      42 30 2 8 7  45 28 3 7 9  48 26 4 7 0  80 40 40 8 9 8  42 39 1 9 2  45 36 6 8 2  48 34 2 7 3  85 40 49 8 10 4  42 47 7 9 7  45 44 7 8 8  48 41 7 7 8  90 40 58 5 11 1  42 56 1 10 4  45 52 5 9 4  48 49 0 8 3  70 75 40 7 6 10 6  42 26 4 9 9  45 24 8 8 9  48 23 1 7 9  80 40 7 1 10 9  42 35 5 10 2  45 33 2 9 2  48 31 0 8 1  85 40 46 4 11   42 44 5 10 6  45 41 6 9 5  48 38 9 8 5  90 40 55 6 11 9  42 5
49. Motors       Achoice in heating cooling applied systems    e And  because the equipment is mounted directly in the living space  expense associated to  installed mechanical ductwork may be avoided     Wide Variety of Heating Cooling Coils    Trane   s unit ventilator offers a wide variety of coil configurations to be used in many design  considerations     In environments where cooling needs are of main interest  a two pipe coil coupled with a chiller   or a direct expansion coil joined with a condensing unit may be used     For heat specific applications  Trane offers a two pipe hot water only unit to be combined with a  boiler  Electric heat and steam options are also available for heating selections     When there is seasonal heating and cooling  a two pipe chilled water hot water changeover system  may be applicable to the mechanical design  This system requires a chiller and a boiler to support  the changeover necessity  However  where space constraints may present a concern  the Traneunit  ventilator may be equipped with a direct expansion coil for cooling  with an auxiliary electric heat  coil  hot water coil  or steam coil for heating     Four pipe chilled water hot water systems are also available  This system is typically applied when  both heating and cooling may be simultaneously called for in the school   Building Automation    As part of the building automation system  the mechanical HVAC system equipment may be  optimized to lower energy consumption  By running
50. OA RA  damper  The spring return system of the actuator closes the outside damper if power is lost to the  building  When ordered with factory controls  the actuator is a 3 pointfloating design  A2to 10 Vdc  actuator is available when other than Trane controls are specified     Figure 6  OA RA Actuator and      insulated damper         i OA insulated damper       S TRANE     Features and Benefits    Acoustics    Unit Filter    Each classroom unit ventilator comes equipped with a standard size throwaway filter to support  job site installation and start up  However  the Trane unit ventilator is designed to accommodate  the use of a MERV 8 or MERV 13 high capacity filter to provide greater filtration of airborne  contaminants     Dehumidification    Trane unit ventilators provide a broad range of dehumidification solutions  Active humidity control  involves monitoring and managing both the dry bulb temperature and the humidity in the  classroom  With this strategy  a reheat coil is placed downstream of the cooling coil to temper   reheat  the cold  dehumidified air leaving the cooling coil to avoid over cooling the space  Reheat  configurations are available in a variety of coil combinations     Alternately  the Tracer    UC400 or Tracer ZN520 controller can be configured to automatically  reduce the fan speed at part load conditions  This helps improve the coincidental dehumidification  performance of the unit at part load  and also lowers sound levels  To help ensure proper  
51. TC   Total Capacity  MBh    SC   Sensible Capacity  MBh    LDB   Leaving Air Temperature  Dry Bulb    F   LWB   Leaving Air Temperature  Wet Bulb    F     Table 42  Airflow correction    of design airflow        120  110  100  90  80    Total Capacity  Sensible Capacity   MBh   MBh          Table 43  Airflow through coil J    Unit Model  Rated cfm    UV PRC003 EN    1 025 1 105  1 012 1 051  1 000 0 998  0 987      0545              089  1500   1495                       Performance Data  Cooling   150   Coil  DX     EDB   80  F EDB   85  F   SC LDB LWB      SC LDB LWB  44 5 52 4 48 6  560 5 52 2 52 7 46 9  40 5 54 9 50 8 473 47 3 55 7 49 4  34 2 58 8 52 9  38 2 38 2 61 3 51 9  42 4 53 7 51 2  59 7 51 0 53 4 50 0  38 0 56 1 53 5 50 1 46 4 56 3 52 5  34 7 58 5 55 6  40 4 40 4 60 0 54 9  38 9 55 9 53 3 65 6 48 2 55 1 52 5  35 4 58 1 55 8  550 43 8 57 9 55 2  318 60 3 58 2  44 4 39 4 60 6 57 7  34 2 58 8 55 2  736 44 0 57 7 54 7  31 1 60 7 58 0 617 40 0 60 2 57 5  28 0 62 7 60 5 49 8 36 0 62 7 60 2  28 6 62 3 57 1  833 38 6 611 56 7  26 0 63 9 60 0  69 8 35 1 63 3 59 7  23 4 65 5 62 8  564 31 6 65 4 62 6    59    S TRANE     Performance Data  Heating   150   Coil A  B  C    Table 44  VUV 150  hydronic heating coils A  1 row   12 fpi   B  2 row   12 fpi   C  2 row   16 fpi   Flow Rate  gpm       Entering         4         Air Temp  Entering Tota Waterside  Tota Waterside        Waterside  Dry Bulb Water Capacity Temp Drop  Capacity Temp Drop  Capacity Temp Drop   Coil   F  Temp  
52. Vertical Classroom Unit Ventilator  750 cfm to 1500 cfm       June 2013 UV PRC003 EN       TRANE    Introduction    The Trane Classroom Unit Ventilator    Academic performance of U S  students depends  in part  on the ability to create a comfortable    learn friendly surrounding  Being too hot or too cold could hinder a students ability to achieve  academic excellence     Seasonal changes  mechanical building disrepair  and even class attendance provide real  challenges to HVAC mechanical systems  The only thing consistent about today   s classroom is its  ability to constantly change  With this in mind  Trane introduces a NEW classroom unit ventilator  design to support today s changing environment     Figure 1  Back view of unit ventilator       Figure 2  Vertical classroom unit ventilator    Maintenance free    Roomy end pockets for EC motor with        Blow through design provides  install ability and direct drive fans    freeze protection  sound  system customization attenuation  and safety    Sealed coil  but quickly  accessed for cleaning       Hassle free  and visual inspection     piping    Larger fans for Auxiliary drain  Linkage free Off the shelf lower sound levels        option    outside air damper filter sizing       2013 Trane All rights reserved UV PRC003 EN    UV PRC003 EN                      Introduction    Trademarks    EarthWise  Integrated Comfort  Rover  Trane  the Trane logo  TOPSS  Tracer  and Tracer Summit are  trademarks or registered trademarks of
53. Works    technology  the controller can send or receive data  setpoint  heat cool mode  fan request  space  temperature  etc   to and from other controllers on the communication link with or without the  existence of a building automation system  This applies to applications where multiple units might  share one zone sensor for both stand alone  with communication wiring between units  and a  building automation system     Water Valve Override  The Tracer ZN520 can be commanded via the Rover service tool to open  all hydronic valves 100 percent  This allows for the faster water balancing of each unit and the entire  system when the command is sent globally to all controllers  A properly balanced system is  essential for proper and efficient operation     Hydronic Coil Freeze Protection  Freeze Avoidance   Unit ventilator systems in cold  climates need to take precautions to avoid hydronic coil freeze up  The Tracer ZN520 does this from  three different aspects  Any of these methods of protections will result in the unit fan being  disabled  the outside air damper being shut  and the hydronic valves being opened 100 percent     The three methods of freeze avoidance include     1  Abinaryfreeze protection thermostat is mounted on the coil and will cause a latching diagnostic  if the coil temperature falls below 35  F     2       analog discharge air sensor monitors the temperature of the air coming off of the coil and  if the temperature falls below 40  F the outside air damper
54. ZN520 with w Fan Status  Tracer UC400   Tracer UC400 w Time Clock    Digit 27     Unit  or Wall Mounted  Controls    0 None   Unit Mounted  Wall Mounted  Unit Mounted Fan Speed  Switch  amp  Wall Mounted  Temperature Sensor  Wireless Zone Sensor    No                   B C9    1  2  3    4      Note  The wall mounted room sensor is  ordered as separate line item     Digit 28     Internal or External  Set Point         None   2   External   3   Digital Display   Digit 29     Timed Override  0   No   1   Yes    Digit 30     Exhaust Control         NoExhaust Control with 3 Speed  Supply Fan        Exhaust Control with 2 Speed  Supply Fan    Digit 31     Control Programming   Sensor Included     0   None  1   Humidity Sensor Programming  2   COoSensor Programming    23       TRANE     Model Number Descriptions    Digit 32     Unit Depth   Standard  16 5 8 in     21 1 4 in  Depth with Baffle   21 1 4 in  Depth with Full Sheet   Metal Back and Baffle   21 1 4 in  Depth with 25 in  High   Falseback   E   21 1 4 in  Depth with 26 in  High  Falseback   F   21 1 4       Depth with 27 in  High  Falseback   G   21 1 4in  Depth with 28 in  High  Falseback        21 1 4in  Depth with 29 in  High  Falseback   J   21 1 4 in  Depth without Baffle    Note  Selection    J    should be applied if  OA opening is raised above  standard baffle location     Digit 33     End Covers       OU            0   None   1   16 5 8 in  Depth without Cutouts   2   16 5 8 in  Depth with 3 x 7 1 4 in   Cutout   
55. acer UC400 can function as a completely standalone controller in  situations where a building automation system  BAS  is not present     The Tracer UC400 is designed to install quickly and easily into the system  Since the controller and  the unit are factory tested and  commissioned  the start up time for the entire system is minimized   Trane becomes the single source of responsibility for the equipment  unit controls  and building  automation system  As a standalone controller  the Tracer UC400 is ideally suited for fix on fail    UV PRC003 EN                      Controls  Tracer UC400    replacement of units with old pneumatic controllers  or in situations where a BAS will be added at  a later date  Once power is applied to the controller  it will automatically start up and run based  upon the setpoint on the local zone sensor  An individual time clock can be added to the unit for  local scheduling  The Tracer UC400 is BTL listed as B ASC profile  This ensures the controller to be  used with other BACnet   building automation systems     Tracer UC400 Features Include    Single Zone VAV with Fully Modulating Fan Speed  The Tracer UC400 will minimize fan  speed  and in turn energy usage  by only delivering the air flow needed     Figure 29  Cool mode nominal hydronic cooling control    Discharge temp setpoint    F                         peeds uey       No cooling load Design cooling    Space sensible load                             Ventilation Reset  With the Tracer UC40
56. ader Sizes    3 4 in  Nominal  7 8 in  ID    1 2 in  Nominal  5 8 in  1 0     1 in  FNPT    3 8 in  OD liquid line  7 8 in  OD suction line       81       TRANE    Dimensional Data    Standard Depth Unit     4        FOR PIPING    OR ELECTRICAL   ZL N          fe                    NER    LN 78  0 0  Mec uu            5   gt   7 3  o p  30              AUX   22 5 8   DRAIN CONN    optional   12 1 2       FRESH AIR OPENING  OPTIONAL  3 3 4      2 1 4     on Bu Den 3 4  13 1 2     gt  12 1 4  1 2 1 4   BACK VIEW SIDE VIEW     2 9  x 9  229mm x 229mm   KNOCKOUTS IN BOTTOM       3 3 4     16 5 8       10 7 8        UNIT MOUNTED  FAN SWITCH   OPTIONAL     UNIT SIZE    FRONT OF UNIT    2  2  4  4       RETURN AIR   OPTIONAL         NOTE   1  THE UNIT LENGTH DOES NOT INCLUDE 5 8  END PANELS     2  THE POWER CONNECTION IS MADE IN THE LEFT HAND  END POCKET FOR ALL OPTIONS BUT ELECTRIC HEAT     3  THE POWER CONNECTION FOR ELECTRIC HEAT OPTION  IS MADE IN THE RIGHT HAND END POCKET     82 UV PRC003 EN                       Dimensional Data  Falseback Unit       21 1 4         gt              16 5 8               4        FOR PIPING  OR ELECTRICAL         7 8  O D   DRAIN CONN     7 8  O D  30   AUX     DRAIN CONN    optional     22 5 8      gt  121 4        BACK VIEW SIDE VIEW  STEP DOWN    IS IN 1  21 1 4             INCREMENTS  16 5 8      gt       lt    2 3 8    2 9  x 9  229mm x 229mm   KNOCKOUTS IN BOTTOM                                                                TOP VIEW pi 14 
57. aintaining the AHRI 840 certification  for economizing requirements       An upgrade able MERV rated filters help reduce contaminants and increase filtration       Side wall power exhaust support system to help remove the stale air from the classroom         better support the air exchange    e Energy recovery unit ventilator to further pretreat and dehumidify the fresh air before it enters  the classroom unit ventilator    e Options for improved dehumidification at part load  including automatic fan speed control   face and bypass dampers  and active humidity control through reheat     A Choice in Energy Optimization    The energy consumption of a unit ventilator system can be significantly reduced through the use  of an economizer cycle  To better understand the basic function of how an outside air economizer  works  it is important to fully understand how it operates     The economizer functions by opening an outside air damper  and bringing cooler outside air into  the space  The economizer cycle is controlled with a modulating damper motor  which opens at  specified increments dependent upon readings from outside air sensors     Economizers also utilize a return air damper that closes as the outside air damper opens   Depending on the room requirements  the modulating damper motor may mix the return air with  the outside air to provide the maximum energy cost efficiencies without sacrificing comfort     When the room thermostat calls for cooling  the economizer control p
58. air is exchanged more frequently and properly filtered  Through  ventilation  stale indoor air is exhausted and fresh treated outdoor air is drawn into the building   The amount of ventilation air required is established by building codes and industry standards   Most building codes reference ASHRAE Standard 62   Ventilation for Acceptable Indoor Air  Quality   as the minimum requirement for ventilation system design  Architects  engineers and  contractors utilize this standard when determining and calculating the type of load the building  environment will place on the mechanical system     Trane Unit Ventilators Support Indoor Air Quality    The Trane unit ventilator is tested and designed to exceed ASHRAE Standard 62  This includes the  use of a higher efficiency filtration to help introduce proper levels of  fresh  diluted air for  contaminant removal     UV PRCOOS3 EN 11       TRANE     Application Considerations  Energy Efficiency    Beyond the ventilation and filtration performance of the classroom unit ventilator  maintenance of   the HVAC system is a must  Several enhancements placed on the Trane unit ventilator to support   superior IAQ performance include    e Coil presentation allows for ease of maintenance and cleaning          dual sloped non corrosive drain pan  removable  helps keep moisture in the system to     minimum    e Ultra low leak damper that results in a fixed air seal of the damper assembly    e Air exchange performance that goes beyond code while m
59. apacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F   51 70 40 12 6 11  13 5  18 6 14  9 7 16 1 8 0 0  18 1 6 0  42 17 5 5 7  45 16 6 5 2  48 15 6 4 7  15 40  5        42 22 7 6 2  45 21 5 5 7  48 20 3 5 1  50 40 3 5     42 27 5 6 9  45 26 0 6 3  48 24 5 5 6  85 40    1 8 1  42 31 9 7 6  45 30 2 7 0  48 28 5 6 3  90 40 7 5 9 0  42 36 2 8 5  45 34 3 7 7  48 32 3 7 0  57 75 40 19 5 8   42 18 8 7 7  45 17 8 7 0  48 16 8 6 3  OQ 40 5  9 0  42 24 4 8 1  45 23 1 7 4  48 21 8 6 6  85 40 0 8 9 1  42 29 8 8 6  45 28 2 7 8  48 26 6 7 1  90 40     9    42 35 0 9 2  45 33 1 8 4  48 31 2 7 6  70 75 40 17 1      42 16 5 8 8  45 15 6 8 0  48 14 7 7 2  210 40    0 9 5  42 22 1 9 0  45 21 0 8 2  48 19 8 7 4  85 40 8 7 9 9  42 27 7 9 4  45 26 3 8 5  48 24 8 7 7  90 40 4 4 10 4  42 33 2 9 9  45 31 4 9 0  48 29 7 8 1       UV PRCOOS3 EN 39    S TRANE     Performance Data  Cooling   100   Coil F    Table 18  VUV 100  cooling coil F  4 row   12 fpi       Flow Rate  gpm       Entering Entering Entering 7      10  Wet Bulb Dry Bulb Water  Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 12 4 11  13  19  14 1 10 1 4 1 15 8 B  9 7 17 9 6 1  42 15 4 17 3 5 8  45               14 7     16 3 5 3  48 15 3 4 8  75 40 
60. ating capacity is required  As room temperature approaches the comfort setpoint  the outside  air damper opens fully  and the unit handles 100 percent outside air  Unit capacity is then controlled  by modulating the heating element capacity     ASHRAE Cycle l is typically used in areas where a large quantity of outdoor air is required to offset  the air being exhausted to relieve the room of unpleasant odors and particles     ASHRAE Cycle Il    ASHRAE Cycle Il is the most widely used ventilation control  Similar to Cycle    the outside air  damper is closed during warm up  But with Cycle Il  the unit handles recirculated air through the  return air system  As temperature approaches the comfort setting  the outside air damper opens  to admit a predetermined minimum amount of outside air  This minimum has been established by  local code requirements and good engineering practices  Unit capacity is controlled by varying the  heating output  If room temperature rises above the comfort setting  the heating is turned off and  an increasing amount of outside air is admitted until only outside air is being delivered     ASHRAE Cycle ll is a very economical control sequence often referred to as integrated  economizing  This design supports optimum ventilation and provides the greatest energy savings   This is further proof of why AHRI 840 certification is important in minimizing energy consumption  through economizer performance     Freeze Protection    The most important advantage th
61. cation Considerations    Draft Barrier and OA Preconditioning    20    adjacent outdoor and exhaust air streams pass through the wheel in a counterflow arrangement  that transfers energy from one air stream to the other     During the cooling season  the drier  sensible heat and moisture transfer from the outdoor air to  the cooler  drier exhaust air  Conversely  during the heating season  sensible heat and moisture   transfers from the exhaust air to preheat and humidify the entering outdoor air stream  Figure 16  psychrometric ally depicts the impact of a preconditioning total energy wheel on a unit ventilator     This approach can t directly control humidity in the space  but it can significantly reduce the  capacity  and operating cost  of the cooling and heating equipment required to condition the  outdoor air  Capable of recovering 65 to 75 percent of the energy in the exhaust air stream  total   energy wheels used in conjunction with unit ventilators can be an attractive alternative when  upgrading existing classroom to meet ASHRAE s ventilation requirements  they reduce  perhaps  even eliminate  the extra capacity needed at the chiller plant or boiler     Figure 16  Energy recover wheel    Outdoor Air  Entering Building         Exhaust Air Supply Air  Leaving to Occupied  Building Space   Exhaust Air  from Space    The Trane ERS energy recovery unit ventilator is one example of a  cold coil  unit with outdoor  air preconditioning     Note  Both preconditioning  energy
62. coils are shipped with a dry nitrogen holding charge     Electric Coil  option     Units equipped for electric heat contain a special resistance  heating element design inserted in an  extended surface fin tube bundle for maximum element life and safety  Units specifying electric  heat include  as standard  a high temperature cut out with a continuous sensing element  This  device interrupts electrical power whenever excessive temperatures are sensed anywhere along  the leaving side of the coil  A contactor  also provided  ensure positive disconnect of electrical  power whenever the fan motor power is interrupted  All electric heat units have a power wiring  console in the right hand end pocket to better facilitate field wiring of the unit     Steam Coil  option     Units including a steam coil are of a 5 8 inch  sigma flow  tube in tube  distributing coil design   Steam coil tubing is mechanically expanded into evenly spaced aluminum fins  The supply and  return connections are on the same side  and include a 1 inch female pipe thread  FPT  termination   The coil is pitched by the manufacturer to provide condensate drainage for freeze protection     Outside Air Return Air Damper    Each unit ventilator is equipped with a linkage free  air tight damper design  This linkage free  design results in a fixed air seal of the damper assembly     UV PRC003 EN    Controls    UV PRC003 EN                      Mechanical Specifications    Face and Bypass Damper  option     The face and
63. duction in space load  Because the chilled water valve remains wide open  the portion of the air  passing through the coil is dehumidified further  improving part load dehumidification     However  face and pass control does not actively control space humidity  It still allows the space  humidity level to rise at part load  often higher than desired     For more information on various methods for improving dehumidification performance of unit  ventilator systems  refer to Trane  Dehumidification in HVAC Systems  application manual  SYS APMOO4 EN     17       TRANE     Application Considerations    Dehumidification    18    Figure 12  Face and bypass damper       FACE  amp  BYPASS  DAMPER    Figure 13  Basic components of active dehumidification control                                             ee ee       p      Outside  Air         Dry Bulb    Economizer    v       lt   S A N           Outside Air TA B Return  Damper NC Ai     ir  Actuator  gt     Fan             Oto                  Discharge Air  nsor         Temperature Sensor 2   X          Relative Humidity Sensor    CLASSROOM SPACE    UV PRC003 EN                      Application Considerations    Draft Barrier and OA Preconditioning    Figure 14  Reheat system and auto fan speed adjustment       Reheat System Temperature  Sensor  full  open A     t   5     8 S        KS         Tracer        5  2  520 fully  Board closed     Unit Ventilator     Humidity Sensor      Auto Fan Speed Adjustment with Tracer ZN520    Dyna
64. e 30  Unit mtd temp sensor   SP OCC UNOCC  OALMH    Electric heat with auto and off speeds     Figure 31  Unit mtd display sensor   SP OCC UNOCC  COMM     X13790844 01  unit     E X13790886 04  unit  3 speed     r  i                           mw    Figure 32  Unit mtd display sensor Figure 33  Wall mtd temp sensor        SP  OCC UNOCC  COMM   SP  OCC UNOCC  OALMH  COMM         13790886 03  unit  2 speed  22  212          Figure 34  Wall mtd display sensor   SP OCC UNOCC  COMM        X13790886 04  wall  3 speed              74    Figure 35  Wall mtd display sensor   SP OCC UNOCC  COMM        X13790886 03  wall  2 speed     Om    UV PRC003 EN    Figure 36  Unit mtd FSS  OALMH    wall mtd temp sensor   SP OCC UNOCC  COMM     X13511527 01  wall   X13790849 01  unit      X13651467 01  comm        Figure 38  Unit mtd FSS  OLH    wall mtd display temp sensor   SP OCC UNOCC  COMM     a4 T8        X13790886 03  wall   X13790475 01  unit     Figure 40  Wireless temp sensor with display     SB OCC UNOCC  COMM              X13790822 04  wall   X13790855 01  unit  3 speed     UV PRC003 EN        TRANE    Controls    Zone Sensors    Figure 37  Unit mtd FSS  OALMH    wall mtd display temp sensor   SP OCC UNOCC  COMM     ATA UE a    X13790886 04  wall   X13790841 02  unit     Figure 39  Wireless temp sensor   SP OCC UNOCC  OALMH  COMM        X13790492 01  wall   7 X13790855 01  unit              Figure 41  Wireless temp sensor with display     SP OCC UNOCC  COMM     O mus    X13790822 01  wa
65. e Trane blow through design provides is additional protection  against coil freeze up  In contrast  draw through configurations allow little mixing of the return and  outside air stream while locating the coil very close to the outside air inlet  This process creates   cold spots  on the coil which could lead to coil freeze up     With a blow through design  face and bypass with isolation valve control is not necessary to  provide proper freeze protection to the unit vent  The placement of the coil above the fan allows  enough space for the coil to avoid  cold spots  that could cause freezing     UV PRCOOS3 EN 15       TRANE     Application Considerations    Dehumidification    Constant Volume System    16    A typical unit ventilator is a constant volume  variable temperature device  It uses a constant fan  speed and modulates water flow through a chilled water coil to maintain the dry bulb temperature  in the space based off of a setpoint  Outdoor air is introduced at the back of the unit ventilator  and  distributed with the supply air  At design cooling load conditions  a system controlled in this  manner typically has a leaving air temperature that is cold enough  and  therefore dry enough  to  sufficiently dehumidify the space  but its ability to dehumidify can decrease significantly at part   load conditions     When the sensible load in the space decreases  part load   the constant volume system responds  by raising the dry bulb temperature of the supply air  In a chi
66. e position of the internal components is optimized to  enhance The performance and casing construction of Trane vertical unit ventilators further adds  to this acoustically superior design     Certification Standards    Comfort  energy and IAQ are all major issues that need      be woven into today s school designs   Therefore  it is important that designers of these systems have accurate information to make  system decisions  Thatis why the industry has developed performance standards and certification  programs which ensure that the equipment information provided to the design community is  correct and comparable across different manufacturers  The following list of certifications  identifies the commitment by Trane to providing the highest quality equipment and information to  our customers         AHRI 840   e ETL      Tested in accordance to AHRI 350  acoustics      LonMark         TRANE    Application Considerations    A Choice in System Design    10    The beauty of the classroom unit ventilator goes beyond its ability to heat and cool  The unit   ventilator design provides an opportunity to create a comfortable atmosphere for living  learning   and playing  while supporting energy efficiency savings  Some of the featured benefits of a unit   ventilator are    e Individual room control    e Fresh air ventilation and filtration       Individual dehumidification sequences per zone    e Energy savings solutions through economizing functions and Electronically Commutated  
67. erface                                    68  Tracer ZN520 Zone Controller                                        69  liu          RP  72                           CT t TC TITIO T           74  Valves Piping Package                                               76   Jobsite ConnectionS 2440444554440 34 64044685   4 9 393 4e      AE ed Eod deeds 81   Dimensional DA dis ss us pan          CHE Ro ue ita or                 UE RERO T REOR      82   Mechanical Specifications                                                87   UV PRC003 EN      TRANE    Features and Benefits    Fit and Finish    Equipment Size    The vertical unit ventilator delivers from 750 cfm to 1500 cfm  It is physically sized to fit the  replacement or new construction application     Cabinet Finish    The unit cabinetry is made of a durable industrial grade metal to withstand even the most rigorous  classrooms  A smooth glossy  appliance grade paint treatment increases the aesthetics of the  equipment while making it durable and easy to maintain     Access    A three panel front access of the unit ventilator is ergonomically safe for lifting removal  and allows  speedy set up during field commissioning  This design allows for the end pocket of the unit  ventilator to be open while the fan  airside  section stays closed  The panel design supports a clean  fit and finish while providing effortless access for filter change out     Top access to the unit mounted fan speed sensor option was developed with the teac
68. es to be one of the few manufacturers that meet this  certification  By meeting this certification  the designer can be assured thatthe Trane unit ventilator  will perform with energy conservation in mind     12 UV PRC003 EN    Acoustics                       Application Considerations    Acoustics    Figure 8  Unit ventilator economizer    DA                      OUTSIDE    Cal an LM 1 RETURN         AIR        A growing population  and an increase in economic pressure to maximize building footprints have   resulted in higher building occupancies and less space to place the HVAC equipment  Often times   the close proximity of the equipment    such as a floor mounted unit ventilator    may cause noise   related complaints  Reducing the likelihood of these complaints requires careful planning    e Inthe equipment sizing  under sizing and over sizing could increase noise level     e And equipment placement  absorption and number of sound sources in the room greatly affect  noise      Room NC is the sum of all sounds entering the room  Its value is based on assumptions about the  room s characteristics  Given the complexity of various building systems  it is extremely important  to assure that the design goals  commissioning  for classroom acoustics          and moisture control  are met through all aspects of the space     For example  it is not uncommon for a school to install unit ventilators that are manufacturer rated  for a specified airflow  cfm   but which are not AHRI 8
69. ess than  that specified for heating systems  The usual requirement is between 15 and 25 cfm of outside air  per occupant  based on the intended use of the room  For instance  achemistry laboratory normally  requires more ventilation for odor control than a low occupancy speech clinic     Ventilation is an important concern and should be accurately determined to assure good indoor air  quality  Purposely oversizing units should be avoided  since it can cause comfort and control  issues     Unit Size    Unit ventilator size is determined by three factors    e Total air circulation   e Ventilation cooling economizer capacity required  e Total cooling or heating capacity required    Total air circulation  if not specified by code  should be sufficient to ensure comfort conditions  throughout the room  This is usually from six to nine air changes per hour  but can vary with room  design and exposure  Often rooms with large sun exposure require additional circulation to avoid  hot spots     Ventilation cooling capacity is determined by the amount of outside air delivered with the outside  air damper fully open  and the temperature difference between the outside air and the classroom   In air conditioning applications  ventilation cooling capacities should maintain the comfort setting  in the classroom whenever the outside air temperature is below the unit or system changeover  temperature     21    S TRANE     Selection Procedure    22    Example    Ventilation cooling capacity   
70. h     F   61 70 40 12 0 9 0 12 7  17  11  0 0 1 0 12 6 7  5  14 1 5   42 13 5 4 8  45 12 6 4 4  48 11 6 3 9  75 40 18  5 6  42 17 5 5 3  45 16 3 4 7  48 15 0 4 2  90 40        42 21 2 5 8  45 19 7 5 2  48 18 2 4 6  85 40 5 8 0 9  42 24 6 6 5  45 22 9 5 8  48 21 2 5 2  90 40 9  7 7  42 27 9 7 2  45 26 0 6 5  48 24 0 5 7  57 75 40 15  750  42 14 5 6 6  45 13 5 5 9  48 12 5 5 2  80 40 19 7 7   42 18 8 6 9  45 17 5 6 2  48 16 2 5 5  85 40 24 1 7 8  42 23 0 7 3  45 21 3 6 6  48 19 7 5 8  90 40 28 3 8 3  42 27 0 7 8  45 25 1 7 0  48 23 2 6 2  70 75 40 13 3 7 9  42 12 7 7 4  45 11 8 6 7  48 10 9 5 9  80 40 17 9 8 1  42 17 1 7 6  45 15 9 6 9  48 14 7 6 1  85 40 22 4 8 5  42 21 4 8 0  45 19 9 7 2  48 18 4 6 3  90 40 26 8 8 9  42 25 6 8 4  45 23 8 7 5  48 22 0 6 7       34 UV PRC003 EN                      Performance Data  Cooling   075   CoilH    Table 11  VUV 075  cooling coil H  3 row   16 fpi       Flow Rate  gpm       Entering Entering Entering        2 TS 10  Wet Bulb Dry Bulb Water Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F   MBh   MBh     F    MBh   MBh     F   MBh   MBh     F   51 70 46 13 8 10 5 14 5 0 1 12 7 10 4 13 8 5 0 14 9 5 4  42 14 2 5 0  45 13 3 4 6  48 12 4 4 1  75 40 19  5 8  42 18 4 5 5  45 17 2 5 0  48 16 1 4 4  210 40 i 6 5  42 22 3 6 1  45 20 9 5 5  48 19 5 4 9  85 40 7 1 7   42 25 9 6 8  45 24 3 6 1  48 22 7 5 5  
71. her or  administrative staff in mind  Access to the sensor may be made through a lock key  or through an  easy open door     Figure 3  Fit and finish       Install ability  Service ability and Maintain ability    Spacious End Pockets    Easy access to piping and controls is made through the roomy equipment end pocket design  The  coil headers and drain connections are made within the unit chassis  freeing up valuable space in  the end pockets for piping or field add ins  This also grants a tighter seal to prevent air leakage     The roomy end pocket design Figure 4  p  6 allows for application requirements such as an optional  auxiliary drain pan  The auxiliary pan may be placed under the factory or field piping package     UV PRCOOS3 EN 5    S TRANE     Features and Benefits    Sliding Fan Deck    Convenient access to the fan motor and fan wheels for maintenance and serviceability is made in  part of the easy slide design of the unit ventilator fan board  Figure 5  The fan board assembly  offers hassle free access to the contractor or maintenance technician  As an added benefit  Trane   s  unit ventilator includes Electronically Commutated Motors  ECM  as standard     Figure 4  Spacious end pockets Figure 5  Sliding fan board          Energy Efficiency    Trane has a commitment to providing premium quality products that has led to the exclusive use  of Electronically Commutated Motors  ECM  in all unit ventilator models  These brushless DC  motors incorporate the latest tech
72. iciency is no less than 90 percent efficiency on 1 3 micron particles and  greater than 90 percent efficiency on 3 10 micron particles when tested in accordance with  ASHRAE Test Standard 52 2     UV PRC003 EN      TRANE    Trane optimizes the performance of homes and buildings around the world  A business of Ingersoll Rand  the  leader in creating and sustaining safe  comfortable and energy efficient environments  Trane offers a broad  portfolio of advanced controls and HVAC systems  comprehensive building services  and parts    For more information  visit www  Trane com     Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice            Ingersoll Rand       2013 Trane All rights reserved  UV PRC003 EN 04 Jun 2013 We are committed to using environmentally  Supersedes UV PRC003 EN  20 Dec 2012  conscious print practices that reduce waste        
73. in assembled units  The motor controller is mounted in a touch safe  control box with a built in integrated user interface and LED tachometer  If adjustments are needed   motor parameters can be adjusted through momentary contact switches accessible without  factory service personnel on the motor control board  Motors will soft ramp between speeds to  lessen the acoustics due to sudden speed changes  Motors can be operated at three speeds or with  a field supplied variable speed controller  The motor will choose the highest speed if there are  simultaneous conflicting speed requests  All motors have integral thermal overload protection    87       TRANE     Mechanical Specifications    88    with a maximum ambient operating temperature of 104  F and are permanently lubricated  Motors  are capable of starting at 50 percent of rated voltage and operating at 90 percent of rated voltage  on all speed settings  Motors can operate up to 10 percent over voltage     Drain Pan s     The unit drain pan consists of a corrosion resistant  environmentally friendly  dual sloped design  to facilitate condensate removal quickly  The pan is removable for cleaning  Hook up to the drain  pan for condensate removal is made on the cooling coil union side  The drain side connection shall  be easily field inverted by removing and rotating the pan 180       An auxiliary drain pan  optional accessory  is factory provided  and field installed under the main   cooling piping package  It is constructed 
74. in the occupied space     When the space humidity falls below the upper limit  the system returns to the standard cooling  mode and again operates as a traditional constant volume system     Basic components of Trane   s reheat system  include a  1  classroom unit ventilator with a main  coil and an auxiliary coil downstream   2  the Tracer ZN520 digital controller  and  3  two  sensors  one for the temperature and one for relative humidity  Sensors may be located in the  zone  or in the return air stream     If after hours operation is required  the addition of a building automation system  BAS  such as  Tracer Summit    is recommended to coordinate the chillers  pumps  boiler and unit ventilators  It  also assures proper operation of the exhaust fans     Reheat may come from new energy  electric resistance heat or boilers fueled by gas or oil  or  recovered energy     Recovered energy reheat refers to the process of salvaging or transferring energy from another  process within the facility  In this case  the recovered energy is the by product of a cooling process  which would normally be rejected or wasted  A common example may include a plate and frame  heat exchanger in the condenser water loop of a water cooled chiller system     Automatic Fan Speed Adjustment    Reducing the fan speed  supply airflow  at part load conditions is a way to improve the coincidental  dehumidification performance of a unit ventilator  The Tracer ZN520 digital controller can be   configured to
75. lectric Heat       Low FLA Option                                                       Minimum Overcurrent Minimum  Unit FLA   Fan   Heating Total Circuit Protection Total Circuit  Model   Voltage  ea        Motors Elements kW Amp FLA Ampacity Device FLA Ampacity  VUVEOZ75 115 60 1 3 5 0 25 1 0 0 0 3 5 4 375 15 2 8 3 5  208 60 1 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  208 60 1 2 1 0 25 1 3 4 39 21 1 23 2 29 30 22 78 28 475  208 60 1 2 1 0 25 1 4 5 86 28 2 30 3 37 875 40 29 88 37 35  208 60 1 2 1 0 25 1 6 8 79 42 3 44 4 55 5 60 43 98 54 975  208 60 3 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  208 60 3 2 1 0 25 1 3 4 39 12 2 14 3 17 875 20 13 88 17 35  208 60 3 2 1 0 25 1 4 5 86 18 69 20 8 25 9875 30 20 37 25 4625  208 60 3 2 1 0 25 1 6 8 79 24 4 26 5 33 125 40 26 08 32 6  230 60 1 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  230 60 1 2 1 0 25 1 3 5 85 24 4 26 5 33 125 40 26 08 32 6  230 60 1 2 1 0 25 1 4 7 8 32 5 34 6 43 25 50 34 18 42 725  230 60 1 2 1 0 25 1 6 11 7 48 8 50 9 63 625 70 50 48 63 1  230 60 3 2 1 0 25 1 0 0 0 2 1 2 625 15 1 68 2 1  230 60 3 2 1 0 25 1 3 5 85 14 1 16 2 20 25 20 15 78 19 725  230 60 3 2 1 0 25 1 4 7 8 21 49 23 6 29 4875 30 23 17 28 9625  230 60 3 2 1 0 25 1 6 11 7 28 1 30 2 37 75 40 29 78 37 225  277 60 1 1 6 0 25 1 0 0 0 1 6 2 15 1 28 1 6  277 60 1 1 6 0 25 1 3 5 82 21 22 6 28 25 30 22 28 27 85  277 60 1 1 6 0 25 1 4 7 8 28 2 29 8 37 25 40 29 48 36 85  277 60 1 1 6 0 25 1 6 11 7 42 2 43 8 54 75 60 43 48 54 35  460 60 3 1 6 0 25 1 0 0 0 1 6 2 15 1 28 1 6
76. ling coil F  4 row   12 fpi       Flow Rate  gpm          Entering Entering Entering 6 J    0      14  Wet Bulb Dry Bulb Water  Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT     F     F     F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40  8    5 I1  9 0 5 9 10 0  44 0 7 1 9 0 0 4 7 5  42 10 7 29 2 7 0  45 27 3 6 4  48 25 4 5 7  75 40 9 4 B   42 37 8 7 7  45 35 4 6 9  48 33 0 6 2  80 40 47 7 9 0  42 45 7 8 5  45 42 8 7 7  48 39 9 6 8  85 40 55 5 10 1  42 53 2 9 5  45 49 8 8 5  48 46 4 7 6  90 40 02 9 11   42 60 3 10 5  45 56 4 9 5  48 52 6 8 5  57 75 40  7 10   42 31 4 9 6  45 29 4 8 6  48 27 4 7 7  OQ 40 42 4 10 6  42 40 6 10 0  45 38 0 9 0  48 35 4 8 1  85 40 51 7 11   42 49 6 10 7  45 46 4 9 6  48 43 3 8 6  90 40 60 9 12 1  42 58 3 11 4  45 54 5 10 3  48 50 8 9 2  70 75 40 8 6 11 5  42 27 5 10 9  45 25 7 9 8  48 24 0 8 7  30 40 3 5 11 8  42 36 9 11 1  45 34 5 10 1  48 32 2 9 0  85 40 48  12 4  42 46 2 11 6  45 43 2 10 5  48 40 3 9 3  90 40 57 7 13 0  42 55 3 12 2  45 51 8 11 1  48 48 3 9 8       56 UV PRC003 EN                      Performance Data  Cooling   150   CoilG    Table 39  VUV 150  cooling coil G  4 row   16 fpi       Flow Rate  gpm          Entering Entering Entering 6 J   8       0   14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capaci
77. ll   X13790855 01  unit  2 speed     75    S TRANE     Controls    Piping Valve Options    Valves Piping Package    Control valves are mounted in a factory piping    package to include unions at the coil  p t ports on    the supply and return lines  and shut off ball valve on the supply and return     Cooling and heating coil valves are only available as 3 point modulating  non spring return type  valves  The ambient temperature range is  32  F to 150  F    Package 1     Two coil union connections    Two shut off ball valves    Two pressure temperature ports   Bypass balancing valve  3 way  packages ONLY     RETURN UNION  TT     SUPPLY UNION       P T PORT    Package 2     Two coil union connections   Shut off ball valves  supply    Two pressure temperature ports   Circuit balancing valve  return    Bypass balancing valve  3 way    packages ONLY  P T PORT      Package 3     Two coil union connections   Shut off ball valves  supply    Strainer  one at supply for debris  straining    Two pressure temperature ports   Circuit balancing valve  return    Bypass balancing valve  3 way  packages ONLY     RETURN UNION       BALL VA       BALL VA          P T PORT    BALL         STRAIMER    Water Pressure Drops in feet for Unit Vent 2  and 3 way Piping Packages    Table 51  1 9 Cv rated valves in 1 2 in  piping packages    Ga  Piping package 2 3  1 Basic package 1 9 3 2 7 1  2 with CBV 18  52 117  3 with strainer and CBV 9 55 12 4    ons per minute   4 5 6 7  12 6 19 5 28 0 38 1  20 7
78. lled water unit ventilator  this is  accomplished by modulating a valve to reduce the rate at which water flows through the          Figure 11 shows how this affects the supply air leaving the coil     the warmer coil surface that results  from less water flow provides less sensible cooling  raising the supply air temperature  and  removes less moisture from the passing air stream     Figure 11  Part load dehumidification with modulated chilled water                                     cep  dL  2              entering air        e coil curves         eo          i  Er  aa f oo                         222       H   __22  amp  eaving air    chilled water flow 9 4 5 0 3 019 1 0           The sensible cooling capacity of aconstant volume system decreases to match the smaller sensible  cooling load  Any latent cooling  dehumidification  capacity is purely coincidental  whether the  cooling coil medium is chilled water or refrigerant  As the load diminishes  the system delivers  even warmer supply air  Some dehumidification can occur in this situation  but only if the sensible  load is high enough     Some designers attack this problem by oversizing the unit ventilators  This does not solve the  problem  in fact  it can make the situation worse  Increasing the capacity of the unit ventilator may  also require increasing the supply airflow  A higher than necessary supply airflow results in  warmer supply air and  in non arid climates  less dehumidification  It   s important to under
79. mic Air Barrier    UV PRCOOS3 EN    In areas that contend with colder climates for a significant period of time  a school may wish to  employ a dynamic air barrier package  With this dynamic  draft  barrier system  the cold air is  captured off of the window  and drawn into the classroom unit ventilator s normal airflow cycle   The unit ventilator treats warms the air as if it were part of a return air makeup system  This  captured air is then discharged into the space providing comfort to the classroom s occupants     This draft barrier shield should be utilized when    e Almost 50 percent of the wall includes windows    e Outside air temperatures fall below 35  F for a significant period of time   e Or  in retrofit applications where the windows are of a single pane thickness     Figure 15  Dynamic air barrier          Outdoor Air Preconditioning    Conditioning the large amounts of outdoor air required for proper classroom ventilation can  significantly increase building cooling and heating loads  It also raises the system s first cost and  operating cost  One way to reduce the impact of the outdoor air load on the unit ventilator is to use  energy recovered from the exhaust air stream to precondition the outdoor air as it s brought into  the building    A total energy recovery  enthalpy  wheel consists of a revolving cylinder filled with a desiccant   coated medium suitable for sensible and latent  moisture  heat transfer  Figure 16  p  20  The    19       TRANE     Appli
80. mmodate wireless sensors or that require a  service tool connection  Wireless temperature sensors  which provide easy and flexible  installation  are a cost effective alternative to wired sensors     Some additional options available with the sensors include   e Easy to use display interface for clear and simple monitoring and control        Temperature setpoint control to allow the tenant to choose a temperature setpoint that satisfies  their personal preference     e Fan speed switch to allow the tenant to locally control the fan speed to better satisfy their  preference     89       TRANE     Mechanical Specifications    Filter    90       Occupancy override to allow the tenant to request temporary timed override system operation  that keeps the building conditions in occupied comfort conditions     e COMM module that is compatible with all Trane   wired temperature sensors  This accessory  provides a local RJ22 connection to Trane   service tools for easy  low cost maintenance     Units equipped with a standard throwaway filter have an average resistance of 76 percent and dust  holding capacity of 26 grams per square foot     Units equipped with 1 in  MERV 8 filters have a rating based on ASHRAE Standard 52 2  The  average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with  ASHRAE Standard 52 1 atmospheric dust spot method     Units equipped with 1 in  MERV 13 filters have a rating based on ASHRAE Standard 52 2  The  average dust spot eff
81. nfiguration Switches  Factory Set     Figure 25  CSTI adapter board field connections    3 2 1 13121110 9 8 76543241 1  VSP 10V  2  VSP 0 10V    3  VSP DC COM    24 Vac Y  hot   24 Vac Y  gnd   High    Medium        gt  Mhbbbp       oe           C       Low   V1Op Cooling   V1C1  not std    Not used   Not used    V2Op EH1St Heating    V2C1 EH2St  not std     Damper Open  13  Dmp CI  not std           N O 0 dw    N xc            N  gt  O    The control interface is intended to be used with a field supplied  low voltage thermostat or  controller  The control box contains a relay board which includes a line voltage to 24 volt  transformer  quiet contactors  for electric heat units   and an optional disconnect switch  All end  devices are wired to a low voltage terminal block and are run tested  so the only a power  connection and thermostat connection is needed to commission the unit  Changeover sensors and  controls are provided whenever a change over coil is selected  When N O  valves are selected   inverting relays are provided for use with standard thermostats     The CSTI adapter board provides all the hookups of the standard adapter board  but in addition   provides hookups for valve control  main and auxiliary coils   electric heat control  and damper  control  Screw terminal blocks provide convenient access to fan controls and to end device control   In addition  acourtesy 10 Vdc supply is provided for use with an external potentiometer or rheostat   The 10 Vdc supply su
82. nology for optimized energy efficiency  acoustical abatement   maintenance free and extended motor life  Each motor has a built in microprocessor that allows  for programmability  soft ramp up  better airflow control  and serial communication     e Trane units equipped with ECMs are significantly more efficient than a Permanent Split  Capacitor  PSC  motor     e Lower operating costs on average of 50 percent  versus a PSC motor     e The Reduced FLA option allows units to ship with a nameplate FLA rating much lower than a  typical ECM unit    Filters    Trane unit ventilators utilize an off the shelf filter design to reduce or eliminate local stocking of  filters in the school  See    General Data     p  25 for standard filter sizes     Note  High efficiency options  MERV 8 and MERV 13  are available  These filters provide greater  resistance and dust holding capabilities     Hinged Control Box    The hinged control box design maintains easy access to the electrical for connection while  supporting less potential for damage on the job site from the different construction trades     UV PRC003 EN    IAQ Features    UV PRC003 EN        TRANE    Features and Benefits    Piping   Hydronic piping for the unit ventilator may be factory installed or field provided  It fits freely inside  the unit end pockets  supplying quick hook up during the installing phase  The motorized valves  include a trouble free  pop top allowing the maintenance or service technician access to the motor  wi
83. ns    e Reset latching diagnostics   e Verify output wiring and operation    UV PRC003 EN                      Controls  Tracer ZN520  LonTalk        Force the water valve s  open to balance the hydronic system during installation set up or  service     Filter Maintenance  Filter status for the controller is based on the cumulative run hours of the  unit fan  The controller compares the amount of fan run time against an adjustable fan run hour   stored in the controller  to determine when maintenance is recommended for the unit  The run   hours value may be user edited as required  through Rover   The valid range for the fan run hours  limit is 0 to 5000 hours with a default of 600 hours  Once the run hours limit has been exceeded   the controller generates a maintenance required diagnostic  unit will not shut down   The user will  be notified ofthis diagnostic through the building automation system or when a Trane Service Tool  15 communicating with the controller     Active Dehumidification  On unit ventilators with reheat coils  the Tracer ZN520 can provide  active dehumidification to the classroom  This means that the classroom relative humidity can be  kept below an adjustable setpoint independent outdoor weather conditions  Indoor humidity levels  are recommended by ASHRAE to be kept below 60 percent in order to minimize microbial growth  and the life span of airborne illness causing germs     Master Slave  Data Sharing   Because the Tracer ZN520 controller utilizes Lon
84. nual override External push button      Noise leve Less than 35 dB  Control signal   O 3 pointfloating       020    Outside Return Air Damper Actuator    Optional outside air return air actuator is spring return and takes a 3 point floating signal      2 10 Vdc option is also available  It provides 25 in Ib of torque  The power consumption is 7       with temperature limits of  25  F to 125  F     Table 59  Outside air actuator specifications       Power supply 24 Vac  20    50 60 Hz   24 Vac  10   Power consumption Running  2 5 W   Holding  1 W  Transformer sizing 7 5 VA  class 2 power source        Overload protection     Electronic throughout 0 to 95   rotation      Control signal 2 to 10 Vdc   3  point floating with Trane   controls  Angle of rotation           Maximum 95    adjustable with mechanical stop    Torque       35inlb    7  Direction of rotation Spring return reversible with CW CCW mounting    Position indication     A  Visualindicator Oto 95             Runtime  nominal  1 90 secondconstant  independent of load     Noise level 7  Running 30dB                 80 UV PRC003 EN    Jobsite Connections    Coil Type Specification    Hydronic Main Auxiliary Reheat Coils        Cooling Coil or Heating Cooling Changeover Coil   Wavy plate finned     Hydrostatically tested at 350 psig     All piping packages for the main coil and auxiliary reheat coil assemblies are always    supplied as a 3 4 in  package     Hydronic Auxiliary Preheat Coils      Heating Coil        Wavy
85. of the same corrosion resistance material found in the  main unit drain pan  The auxiliary pan will effortlessly fit into the end pocket for condensate  disposal of the piping package     Hydronic Coils  option     All hydronic coils are a plate fin type  mechanically bonded to tubes  The coils are hydrostatically  tested to 350 psig and burst tested to 450 psig  The coils are rated in accordance with AHRI 840   A threaded drain plug is provided at the header s lowest point  and a manual air vent provided at  its highest point     The standard 4 pipe heating coil is placed in the preheat location  Optional 4 pipe heating coils are  available in the reheat position for dehumidification control     Refrigerant Coils  option     Direct expansion coils contain copper tubes mechanically expanded into evenly spaced aluminum  fins  All coils are proof and leak tested before leaving the manufacturer  The proof test is performed  at 1 5 times the maximum operating pressure  and leak tested at the maximum operating pressure   In addition  the tubes are completely evacuated of air to check for leaks in the vacuum     The refrigerant coil distributor assemblies is Venturi or orifice style with round copper distributor  tubes     Distributors are sized consistently with capacity of coil  Suction headers are fabricated from round  copper pipe    A thermostatic expansion valve  TXV  is factory selected and installed for a wide range of control  to maintain optimum control of superheat  All 
86. ply    UV PRC003 EN    UV PRC003 EN                      Controls    End Device Controls    The adapter allows direct customer interfacing through the use of terminal strips  Standard  interfacing includes     e Fan Speeds  H  M  L   for wall mounted fan speed switches   e Variable speed  0 10V  inputs    The standard adapter board eliminates many separate wiring harnesses in the panel and allows  simple  mistake proofed single plug interfacing of     e The ECM engine controller   e Transformers   e Motors   e Valves   e Dampers   e Electric heat control   e Fan speed switches   e Main power  except electric heat     The manual fan mode switch is available for fan coil units that do not have Trane factory mounted  control packages  This four position switch  off  high  medium  low  allows manual fan mode  selection and is available unit or wall mounted  The unit mounted option operates on line voltage   The wall mounted option is low voltage and has three 24 volt relays using a factory wired  transformer and relays to control the fan motor     67       TRANE     Controls  CSTI    Customer Supplied Terminal Interface  CSTI     68    Figure 24  CSTI adapter board               TE         Customer Low Voltage Interface for      Valves  Electric Heat  Dampers  Fan  Speeds  Variable Fan Speed  and  24 Vac Supply    Gy  p  u    g0   prey n    b 1 B400  28 i            1    3             2  mu     2 P        a           m          J        Valve s   Electric Heat  and Changeover  Co
87. pports up to 10 mA draw     UV PRC003 EN                       Controls  Tracer ZN520  LonTalk     Tracer ZN520 Zone Controller    Features Include    e Automatic fan speed reset  e Automatic ventilation reset  e Active dehumidification   e Manual output test   e Filter maintenance      Master slave   e Water valve override   e Freeze avoidance   e Interoperability      Three generic I O ports    The Tracer ZN520 is a factory installed   tested and  commissioned LonTalk   control board  designed to provide control of the classroom unit ventilator and the fan coil products  see  Figure 26      Figure 26  Tracer ZN520 control board                                  AUTO     5                          STATUS LED       i     vr  E           1 5        COMMUNICATION    SERVICE BUTTON     ANDLED      COMMUNICATIONS ZONE SEMSOR  CONNECTION CONNECTIONS    The Tracer ZN520 controller is designed to be used in the following applications       Aspart ofthe Trane Tracer Summit building automation system  the Tracer ZN520 becomes       important part of the Trane Integrated Comfort system  ICS     e The Tracer ZN520 can function as a completely standalone controller in situations where a  building automation system  BAS  is not present       For situations when    non Trane BAS is present  the Tracer ZN520        be where ever a LonTalk  front end system is present     Through building management of the HVAC system  optimizing energy consumption becomes  possible at a classroom level  Each
88. pressure differential Maximum   4 bar  60 psi     Pressure rating Static   20 bar  300 psi   Burst   100 bar  1500 psi   Flow characteristic Linear    Table 57  Isolation valve specifications       Power supply 24 Vac   50 60 Hz  Power consumption 5 W  Maximum fluid temperature 94  C  200  F  Minimum fluid temperature 1      34  F  Maximum operating pressure 300 psi  Maximum close off pressure 1 2 In    30 psi  3 4 in   20 psi     in   15 psi    78 UV PRC003 EN                       Controls  Piping Valve Options    Figure 42  Dimensional data for right hand piping with 3 way valve  typical     RETURN        a    1         UV PRC003 EN 79    S TRANE     Controls    Actuators    Face and Bypass Damper Actuator    An optional face and bypass actuator is 24 volt  3 point modulating  non spring return  In coming  power is 24 Vac with a consumption of 2 watts  Maximum torque of 35 in Ib     Note  Face and bypass is available with all units ventilator coils  with exception of DX and electric  heat     Table 58  Face and bypass actuator specification                3           deett    Power supply 24 Vac  20    50 60 Hz   24 Vac  10    Power consumption   2W          J    4              Transformer sizing         3 VA  class 2 power source            Angle of rotation 7     Maximum 95    adjustable with mechanical stop    Torque   Bnb  Direction of rotation  gt  Reversible with switch L R 0  Position indication Clip on indicator               Run time  nomina 90 second constant  Ma
89. ption   ECM  amp  Low FLA Option   ECM  amp  Low Acoustic  amp  Low FLA  Option   Digit 18     Other Motor Items   A None    B Toggle     Circuit Breaker    Digit 19     2  or 3 Way Valve    Cooling Changeover Coil    None   2 Way  3 Point Floating  3 Way  3 Point Floating  2 Way  2 10 Volt  3 Way  2 10 Volt  Isolation Valve  2 Way  Isolation Valve  3 Way    Digit 20     CV   Cooling or  Changeover Coil   None   Low Cv   Medium Cv   High Cv   Digit 21     2  or 3 Way Valve    Preheat or Reheat Heating Coil  None   2 Way  3 Point Floating  3 Way  3 Point Floating  2 Way  2 10 Volt   3 Way  2 10 Volt   Isolation Valve  2 Way  Isolation Valve  3 Way   Digit 22     CV   Preheat or  Reheat Heating Coil    UzZzrAIOTmmogou  o                   W           Ig                 NO  Hou ou H H H al Hou stl    IZT                           Hoi H H H ue Il         None   L   LowCv   M   Medium Cv  H   High Cv          TRANE    Digit 23     Discharge  Arrangement    0   Opening Only  No Grille   A   Discharge Grille        Double Deflection Discharge  Grille   C   Grille Discharge with Wire Mesh    Digit 24     Outside Air Damper  Control         None  A   3 Wire Actuator  B   2 10 Volt Actuator    Digit 25     Face and Bypass  Damper Control         None  A   3 Wire Actuator  B   2 10 Volt Actuator    Digit 26     Controls    0   None  Unit Mounted Speed  Switch   Customer Supplied Terminal  Interface  CSTI             w Low Temp Detection  Tracer ZN520   Tracer ZN520 w Time Clock  Tracer 
90. r to be used with another vendor s BAS and thereby still provide the high quality  of factory installation and testing  In addition  the Tracer ZN520 provides one of the most extensive  interoperable data lists of any controller of its type in the industry     Tracer ZN520 Features Include    Automatic Fan and Ventilation Reset  With the Tracer ZN520 controller  a multi speed fan  control for the unit ventilator delivers the airflow output customized to support the cfm space  needs  When less cfm is necessary to meet the load of the classroom  typically 75 to 80 percent of  the time   the equipment operates on low speed  However  if the room temperature rises  the  controller will switch to high speed  and the outside air damper will adjust to satisfy the space  needs  This helps maintain the proper amount of ventilation air to the occupants independent of  the fan speed  As part of the ventilation strategy  the controller will reposition the outside air  damper to confirm the minimum outside air cfm is met at both operating conditions     Manual Output Test   The Tracer ZN520 controller includes a manual output test function  This  function may be initiated from the blue test push button on the controller or through the Rover     service tool  This feature is used to manually exercise the outputs in a defined sequence     The purpose of this test sequence is to verify output and end device operation  The manual output  test function may also be used in the following situatio
91. re  likely to suffer the consequences of indoor pollutants  For this reason  air quality in schools is of  particular concern  Proper conditioning of the indoor air is more than a quality issue  it  encompasses the safety and stewardship of our investment in the students  staff and facility  The  beauty of a classroom unit ventilator is its ability to provide heating  cooling  ventilation and  dehumidification as a single zone system     ASHRAE Control Cycles    There is a variety of control systems available today in unit ventilators  The exact method of  controlling the amount of outside air and heating capacity can vary  However  all systems provide  a sequence of operation designed to provide rapid classroom warm up and increasing amount of  ventilation air to offset classroom load     To help supply proper ventilation to these fluctuating heat gains  the Trane unit ventilator is  designed to provide rapid classroom warm up and increasing amounts of ventilation air to offset  classroom overheating     UV PRC003 EN                      Application Considerations    Ventilation    Figure 10  ASHRAE Cycle graph    ASHRAE CYCLE    OPEN 100       pes  5     CLOSED 0  SET  2    POINT    70 xm  ON                    528  Tus  OFF   0   ASHRAE CYCLE Il    OPEN 100     OUTDOOR  AIR  DAMPER    CLOSED 0        OM   10095    HEATING  ELEMENT  CAPACITY    a     m  e    ASHRAE Cycle I    All standard unit ventilator cycles automatically close the outside air damper whenever maximum  he
92. rovides the right mix of  outside and return air to cool the classroom  The equipment s airflow is generated from both fan  energy and the economizing dampers  This design supports optimum ventilation and provides the  greatest energy savings  As the outside air temperature rises  typically above 55  F   the outside  damper closes to the minimum position  activating the second cooling stage on the room  thermostat   the cooling generating device  compressor  water pump  chiller  cooling tower   The  return air and outside air dampers modulate to support the discharged air temperature     Dampers working together with the cooling coil is called integrated economizing  which allows a  unit ventilator to mix outside air with return air  delivering an energy efficient  cost savings  solution to a school     Industry Standards    The Air Conditioning  Heating  and Refrigeration Institute  AHRI  created the AHRI 840 standard for  classroom unit ventilators to provide a consistent method of rating the unit ventilators design  performance  To achieve AHRI 840 certification  the unit ventilator must be capable of providing a  minimum of 80 percent of its ventilation  airflow  through the outside air economizer function  see  Figure 8   This measurement ensures that the expected energy savings by the economizer is  realized in actual operation     Only AHRI 840 certified equipment has been independently tested for compliance to the minimum  requirement  Trane was the first  and continu
93. signify valid selections with face and bypass dampers     Example 1     4 pipe  chilled water   hot water  Type E  3 row  16 fpi  cooling coil  may be selected with  Type B  2 Row  12 fpi  preheat or reheat coil    Example 2     4 pipe  DX cooling   steam heating  Type J  3 row DX cooling coil  may be selected with  Type L  high capacity steam heating coil    Notes      Supply and return coil connections are on the same side     e In 4 pipe systems  the cooling coil connections        on the opposite end from the heating coil  connections     e DX coils are always left hand connections   e Electric heat coils are always right hand connections     e Heating coils  hot water or steam  are right hand when in the reheat position with DX cooling  coils     28 UV PRC003 EN    UV PRC003 EN    Table 5  Airflow through coil combination    Unit size  Coil combination  0750 1000    J 1250   1500    A    833  788  759  748  717  684    10 2  1032  1011  989  934  1005    1406  1293  1315  1253  1243  1233  1215  1243  1253  1377    1669  1578  1515  1495  1437  1437  1524  1437  1495  1623                          Performance Data    Airflow by Coil Combination    29       TRANE     Performance Data    Hydronic Coil Performance    Table 6  Hydronic coil performance summary       Cooling Performance Heating Performance  Size GPM QT  05       GPM gr p  0750 A 1 833 Not available 4 0 36 9  B 2     2  D 3  E 3  F 4  G 4  H 3  1000    1     2     2  D 3  E 3  F 4  G 4  H 3  1250 A 1     2    
94. stand   this is not just a unit  coil  or fan sizing challenge  Rather  it   s an issue of properly controlling the  system in a manner provides sufficient dehumidification at all operating conditions  Proper  dehumidification with terminal units is a matter of proper control     Active Humidity Control    A common method used to address this part load humidity control challenge in a constant volume  system is active humidity control through supply air tempering  reheat   Active humidity control  involves monitoring and controlling both the dry bulb temperature and humidity in the occupied  space  Whenever the space humidity is below the preset upper limit  typically 60 percent relative  humidity   the system operates just like a normal constant volume system  However  if the space  humidity reaches or exceeds the upper limit  the cooling coil control valve is driven open regardless  of the need for sensible cooling in the space  The coil over cools the air  increasing the  dehumidification capacity of the system     With this control sequence  a reheat coil is placed downstream ofthe cooling coil to temper  reheat   the cold  dry air leaving the cooling coil in order to avoid over cooling the space  The key to cost     UV PRC003 EN    UV PRC003 EN                      Application Considerations    Dehumidification    effectively applying an active humidity control system is to use reheat only when it is needed  This  requires the sensing of both the humidity and temperature 
95. tage fan speed option will provide an  interface to factory wiring  including variable speed high medium low  HML  control  The control  box contains a line voltage to 24 volt transformer  EC motor controller  and an optional disconnect  switch     Tracer ZN520    The Tracer ZN520 discrete speed controller can be used in a stand alone application or used as part  of a Trane Integrated Comfort System  ICS  with LonTalk   communication  The Tracer ZN520 offers  the combined advantages of simple and dependable operation  Standard control features include  options normally available on more elaborate control systems  All control options are available  factory mounted   wired  and  configured and can also be field configured using a service tool     Tracer UC400    The Tracer UC400 controller delivers single zone VAV control in a stand alone application or as part  of a Trane Integrated Comfort system with BACnet   communication  The Trace UC400 offers the  combined advantages of a factory mounted   wired  and  programmed controller for dependable  out of the box operation  Standard control features include options normally available on more  elaborate control systems  All control options are available factory programmed with additional  configuration and programming in the field using a service tool     Zone Sensors  option     Trane offers a full line of wired and wireless temperature sensors  Wired temperature sensors are  the suitable alternative for locations that cannot acco
96. thout removing the valve body from the piping package     Indoor air quality  IAQ  has become a top priority in classroom design  Giving students a healthy  place to learn and develop is crucial in every school district  It is also crucial to maintaining the  building s overall construction and furnishings  Several features of Trane s unit ventilator attribute  to improved 1         Removable Drain Pan    The unit ventilator drain pan is dual sloped for effective condensate removal  This non corrosive  pan eliminates the problems associated with leaking or standing water and is removable for  cleaning     Ease of Maintenance    Internal components such as the fan and coils are accessible for visual inspection and cleaning   Maintaining a clean system increases the efficiency of the unit and is important to good   sustainable indoor air quality     This design also places the coils farther away from the outside air opening  virtually eliminating the  potential for coil freezing and the added hassles of nuisance freeze trips     OA RA Damper Design    The outside return air damper is a one piece design which is linkage free resulting in a superior air  seal  see Figure 4  p  6   This results in lower infiltration of outside air during off cycles thus  lowering the risk of freezing equipment in the winter or the intrusion of humid air into the building  during the summer     OA RA Actuator    The OA RA actuator provides true spring return operation for positive close off of the 
97. tion Discharge Grille  C   Discharge Grille with Wire Mesh    Available in        16 5 8  Depth  21 1 4  Depth    Available in   16 5 8  Depth  21 1 4  Depth       Digit 132 3  10096 Fresh Air Back    Digit 13 22  10096 Return Air Front       Available          21 1 4  Depth  ONLY       Digit 13   5  6   5  RH Energy Recovery System  ERS Compatible     6  LH Energy Recovery System  ERS Compatible    UV PRC003 EN        TRANE    General Data       Coil Combinations    Figure 19  Falseback and subbase    EXISTING  WINDOW LEDGE          HORIZONTAL   E  BAFFLE  standard             rdi         THE WALLBOX  MAY BE LOCATED  ANYWHERE  BELOW THE     BAFFLE     GROUND  LEVEL    z  zi  z  LLI            cc   lt     AIR PLENUM    GROUND  LEVEL          FALSEBACK UNIT    Falseback may be utilized as  an air plenum to locate the  wallbox anywhere along the    FALSEBACK UNIT     Step Down Falseback  The step down falseback  allows the unit ventilator to be    height of the baffle  lowered from a 30  height to 29    2B   27     26  or 25  height  The lowered  height permits the upgraded equipment  to be retrofitted below an existing  window ledge                   WALL BOX    MAY BE     LOCATED n   UP TO 1   a OUTSIDE  rs AIR IMTAKE  BELOW  MAY BE  THE UNIT Hoe  VENTILATOR    2 4  OR 6   SUBBASE  GROUND  LEVEL  GROUND  LEVEL       21 1 4  DEPTH WITHOUT BAFFLE OPTION     INSULATIED FALSEBACK FOR RAISED SUBBASE  16 5 8  DEPTH   21 1 4     Subbases are available in both the 16 5 8        OA OP
98. to minimize microbial growth and  the life span of airborne illness causing germs     Hydronic Coil Freeze Protection  Freeze Avoidance   Unit ventilator systems in cold  climates need to take precautions to avoid hydronic coil freeze up  The controller does this from  three different aspects  Any of these methods of protections will result in the unit fan being  disabled  the outside air damper being shut  and the hydronic valves being opened 100 percent     The three methods of freeze avoidance include     1  A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic  if the coil temperature falls below 35  F     UV PRC003 EN 73    S TRANE     Controls    Zone Sensors    2       analog discharge air sensor monitors the temperature of the air coming off of the coil and  if the temperature falls below 40  F the outside air damper is closed  the fan is turned off and  the valves are fully opened     3  Wheninthe unoccupied mode  the controller has an adjustable freeze avoidance setpoint  If the  outside air temperature is below the setpoint  the unit will open the valves to allow waterto flow  through the coils     Zone Sensors    Zone sensors are available as either unit  wall  or split mounted options for design flexibility  Unit  ventilators with the unit mounted zone sensor option include a thermistor in the unit s return air  path  Wall mounted zone sensor options have an internal thermistor  Zone sensors operate on  24 Vac     Figur
99. ty Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40  6 4 0 116 140 1 6 5 10  45 5 9 5     1 4 7 8  42 23 2 29 9 7 3  45 28 0 6 6  48 26 2 5 9  75 40 40 6 8 4  42 38 8 7 9  45 36 3 7 1  48 33 9 6 4  80 40       9 4  42 47 0 8 8  45 44 0 7 9  48 41 0 7 1  35 40 5   10 4  42 54 6 9 7  45 51 1 8 8  48 47 8 7 9  90 40 04 8 11 6  42 61 9 10 8  45 57 9 9 8  48 54 1 8 7  57 75 40      10 5  42 32 2 9 8  45 30 2 8 9  48 28 2 7 9  80 40 43 7 11 0  42 41 7 10 3  45 39 0 9 3  48 36 5 8 3  85 40 53  11 7  42 50 9 11 0  45 47 7 9 9  48 44 5 8 9  90 40 62    12 6  42 59 8 11 8  45 56 0 10 6  48 52 3 9 5  70 75 40 9 5 12 0  42 28 2 11 2  45 26 4 10 1  48 24 6 9 0  80 40 9 7 12   42 37 9 11 5  45 35 5 10 4  48 33 1 9 3  85 40 49 7 12 8  42 47 4 12 0  45 44 4 10 8  48 41 5 9 7  90 40 29 5 13 5  42 56 8 12 6  45 53 2 11 4  48 49 7 10 2       UV PRC003 EN 57    S TRANE     Performance Data  Cooling   150   Coil       Table 40  VUV 150  cooling coil H  3 row   16 fpi  EarthWise       Flow Rate  gpm       Entering Entering Entering 6 J 8   10   14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 5 4      12  41  5 7 10 6  45 5 7      50 5     7 4  42 28 0 7
100. ut output summary  ZN520 UC400       Binary Outputs   3 Speed Fan   2 Position Hydronic Valve  2 Position Fresh Air Damper  1 Stage Electric Heat   3 Wire Economizer Damper  3 Wire Hydronic Valve   2 Stage Electric Heat   Reheat  hydronic or electric   Generic   Binary Inputs   Condensate Overflow Detection  Low Temperature Detection  Occupancy   Generic Input   Analog Inputs                      Zone Temperature   Setpoint   Fan Mode  Auto  High  Medium  Low  Entering Water   Discharge Air   Outside Air   Generic   Analog Outputs                      Variable speed fan X   Field supplied analog valves X                 XX                                X    X X                 xxx          X X X KK XK          a  The generic input and output are for use with a Tracer Summit system only     Table 48  Controller function summary       ZN520 UC400  Control Functions  Entering Water Temp  Sampling  Purge  X X  Auto Changeover X X  Fan Cycling  Warm Up X  Pre Cool X  Data Sharing  Master Slave  X  Random Start X X  Dehumidification X X  Single Zone VAV X  Staged Capacity  2 Stage Electric Supplementary  X X  Other Functions                 Manual Test X in TU  Maintenance Timer X X  Setpoint Limits X X    UV PRC003 EN    ECM Engine Controller        TRANE    Controls  ECM Engine Controller    The Electronically Commutated Motor  ECM  engine controls and reports the performance of up    to two Trane Brushless DC  BLDC  motors     Figure 20  ECM engine controller       e The engine
101. ventilation in the classroom at lower fan speeds  the controller adjusts the outside air being  supplied to the classroom     Economizer    One big advantage of a Unit Ventilator system is the ability to provide energy savings through an  economizer cycle  During mild seasons outside air is used to provide    free    cooling  thereby   minimize or eliminate the need to run mechanical cooling equipment  To truly have an effective  economizer a Unit Ventilator must be able to bring in up to 100 percent of the design airflow  through the outside air damper opening  Trane Unit Ventilators are tested and certified to exceed  the industry standard  as defined by AHRI 840  for economizer effectiveness  This ensures the  school will realize the energy savings available through the economizer strategy     Face and Bypass Actuator    The face and bypass damper actuator incorporates a direct couple design  It provides electronic  protection against overload  A limit switch is not included  nor required as part of the design  When  reaching the damper end position  the actuator automatically stops  The gears can be manually  disengaged with a button on the housing     Quiet systems are extremely important in today   s classrooms  Trane offers many different system  solutions to balance the requirements of sound  cost         and efficiency  The Trane vertical unit  ventilator takes a comprehensive approach to delivering one of the quietest units available     Fan and Blower Motor Assembl
102. w Rate  gpm       Entering Entering Entering 6 J                  0   14  Wet Bulb Dry Bulb Water   Tota Sensible Tota Sensible Tota Sensible Tota Sensible  Temp Temp Temp Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT Capacity Capacity AT    F    F    F   MBh   MBh     F              MBh     F   MBh   MBh     F    MBh   MBh     F   51 70 40 0 5 1 0 10 5 4 7    8 9 0 7 6 4 0 7 7 41  5 6 6 0  42 24 4 5 7  45 22 7 5 1  48 20 9 4 5  15 40   0 0  42 31 6 6 2  45 29 4 5 5  48 27 1 4 9  80 40 40  7   42 38 3 6 8  45 35 5 6 1  48 32 8 5 4  85 40 46 7 8 1  42 44 5 7 6  45 41 3 6 8  48 38 2 6 0  90 40 52 9 9 0  42 50 5 8 5  45 46 8 7 6  48 43 3 6 7  42 26 3 7 7  45 24 4 6 9  48 22 5 6 1  80 40 5 7 8 6  42 34 0 8 0  45 31 6 7 2  48 29 2 6 4  85 40 43 5 0 1  42 41 5 8 6  45 38 5 7 7  48 35 6 6 8  90 40 51  9 8  42 48 8 9 2  45 45 3 8 2  48 41 8 7 3  70 75 40 4 1      42 23 0 8 7  45 21 3 7 8  48 19 7 6 9       40    4 9 6  42 30 9 8 9  45 28 7 8 0  48 26 5 7 1  35 40 40 6 10 0  42 38 7 9 3  45 35 9 8 4  48 33 2 7 4  OQ 40 48 6 10 5  42 46 3 9 8  45 43 0 8 8  48 39 7 7 8       50 UV PRC003 EN    Table 31  VUV 125  cooling coil J  DX     Suct EDB   70  F EDB   75  F  Size        Temp TC SC LDB LWB      SC LDB LWB       1250 61 40 35 1 23 4 52 7 51 0  39 4 309 52 2 499  42 5  45 29 4 21 2 54 3 52 8 32 2 28 1 54 2 51 9 335 6  50 23 7 191 55 9 54 5 25 9 25 3 56 3 53 8 2287  64 40 41 7 20 2 551 52 8  43 9 284 540 52 0 446 7  45 34 9 18 3 56 5 54 8  36 8 25 8 55 9 54 2 339 1  5
103. y    Several innovative ideas have gone into the quiet design of the Trane vertical unit ventilator  The  fans diameters have been maximized to reduce the motor rpm and thus lower the noise  while still  maintaining the cfm requirements to support ventilation and capacity requirements  The unique  direct drive fan and blower design diminishes vibration from occurring further ensuring quiet  operation     Fan Speed Control    Trane provides the capability to vary airflow for suitable applications either with three speeds or  with a 0 10 Vdc input  This lowers the sound in the space and improves the dehumidification in the  cooling season at part load  With field installed controls  this is accomplished with a unit mounted  manual fan speed switch  allowing either 2  or 3 speed control  or variable speed control with a  0 10 Vdc input  ECM controls provide a soft ramp between speed changes   a significant  contributor to overall quiet operation     UV PRC003 EN    UV PRC003 EN                      Features and Benefits    With the inclusion of the Tracer UC400 unit controller  the speed of the fan is infinitely varied  automatically in response to the load condition in the space  The controller also will adjust the  outside air being provided to properly ventilate the classroom at the lower airflow conditions     Quiet Blow Through Design    The Trane blow through unit design enables additional sound attenuation by eliminating the fan  noise from entering the space directly  Th
104. ze thermal performance  It is suitable for use in air  streams up to 4500 feet per minute  fpm   Insulation will meet the Underwriters Laboratories Fire  Hazard Classification and long term thermal resistance  LTTR  classification per CAN ULC S770  standard     Piping and control end pockets are a minimum of 12 inches wide to facilitate piping  auxiliary drain  pan  and service access     Final finish of the cabinet is cleaned  phosphatized and painted with an electrostatic powder spray  system  with a minimum thickness of 1 5 mil to avoid visible runs and resist abrasion     Unit Fans    The unit fan board assembly shall ship from the factory wired to the commission schedule for  engineered cfm expectancy  A motor speed switch is on the unit or wall for motor speed  adjustment     The fan board is a single  rigid construction  made from corrosion resistive material  It is a trouble   free slide design to provide cleaning and serviceability ease to maintenance personnel     The fans contain a double width double inlet  forward curved centrifugal design to sustain  appropriate air throw into the space  The wheels are galvanized metal to resist corrosion  The  dynamically balanced fan and motor are of direct drive style     The fan and coil arrangement are of a blow thru configuration to supply unvarying coil face velocity  avoiding cold spots on the coil     Motors    All motors are brushless DC  BLDC  electronically commutated motors  ECM  factory   programmed and run tested 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
MANUAL TÉCNICO DE INSTALAÇÃO  1 1.テストの目的 財団法人交通事故総合分析  PA-110-t プレスリリース    English - Magura  Liebert® eXM™ External Battery Cabinet    Dremel Lawn Mower 675 User's Manual  Mi106 - Milwaukee Instruments  Catalogo carpenteria Legno    Copyright © All rights reserved. 
   Failed to retrieve file