1. le L N IS SPDP Alberta only Plus C C P Customer Connection Point SPDP British Columbia Only Network Inteface Box NIB LEGEND GE TELEPHONE Distribution Device SPDP SERVICE PROVIDER DEMARCATION POINT C TELEVISION NETWORK INTERFACE BOX NIB DEMARCATION POINT A POINT WHERE THE Is COMPUTER OPERATIONAL CONTROL OR OWNERSHIP CHANGES TELUS Communications Inc c 2006 9 22 Page 9 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH Within the PC e residence cable Central CPE To central wiring optional office center n PEAD Network interface Network interface box Outside deck Weather resistant outlet Registered jack RJ 11 lt i ll CPE Customer provided equipment Multimedia outlet DD Distribution device OC Outlet cable Courtesy of BICSI Diagram 2 Typical Residential LOGICAL VIEW TELUS Communications Inc c 2006 9 22 Page 10 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH Outside deck Weather resistant outlet Oc Breakfast Koen Bath Family area room OC Laundry cable op First floor in CL Dining Garage Living room J room Nanig Foyer Bath Bath CL Bedroom 1 OO Master Second floor c bedroom Bedroom 2 LC Bedroom 3 CL V Multimedia outlet CL Closet DD Distribution device NIB Network interface box OC Outlet cable
2. 1 OUTLET Diagram 4 Correct placement of cables and outlets 4 5 Telephones And Communications Devices In Bathrooms The Canada Electrical Code Rule 60 400 in summary provides Communication equipment located in a bathroom shall be permanently fixed on the wall and shall be located so that no part may be reached or used from the bath or from the shower enclosure Telephone jacks are not permitted in bathrooms TELUS Communications Inc c 2006 9 22 Page 13 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 4 6 What Type Of Telephony Devices To Connect Telephony devices shall be certified and approved by CSA International CSA identified by the following mark Note Faulty customer owned telephony equipment could result in a service charge if TELUS is called to diagnose the problem Figures 2 and 3 are extracted courtesy of BICSI from BICSI Telecommunications Distribution Methods Manual TDMM 10 edition Chapter 17 Residential Cabling TELUS Communications Inc c 2006 9 22 Page 14 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 5 Wire Cable and Outlet Hardware 5 1 Wire Or Cable Selection Telecommunications wiring must comply with all laws and regulations whether federal or provincial and the Canadian Electrical Code The minimum grade of inside wiring TELUS recommends is CAT 5e Inside Wiring Cable IWC or Premises Communication
3. Cable PCC that is Canadian Standards Association CSA approved designated CMR formerly FT4 fire rated per CSA standard C22 2 No 214 M90 The cable should have a minimum of four pairs twisted 24 AWG solid copper wires The outside cover of the wire should be clearly stamped CSA IWC CMR 24 AWG and have a level 5 voice and data transmission rating CAT 5e except where the local electrical authority states that CMP formerly FT6 is required Do not use flat wire such as telephone set line cord or lamp wire for prewiring as it can cause transmission problems errors and low throughput 5 2 Identifying Conductors In Cabling And Multimedia Outlets To identify the conductors in new cat 5e cable strip off a portion of the outer sheath This will expose the individual conductors which are twisted together in pairs Each working telephone line requires one pair of conductors and each pair consists of a Tip T and a Ring R conductor Each MO required for Internet use requires all eight conductors or wires ie four pairs The manufacturer identifies each conductor by a standard colour code as shown in Table 2 All conductors must be connected TABLE 2 Identifying Conductors in Outlet Cable TIA EIA 568 A wiring configuration PAIRS LINES 4 AND 8 WIRE COLOR CODE Ai Ge 1 TIP GREEN WHITE WITH BLUE BAND 5 RING RED BLUE WITH WHITE BAND 4 2 TIP BLACK WHITE WITH ORANGE BAND 3 RING YELLOW ORANGE WITH WHITE BAND 6 3 TIP WH
4. Courtesy of BICSI Modified by TELUS Diagram 3 Typical Residential Premises Cabling System Physical View 4 3 Other Considerations For New Homes Install a standard electrical outlet box 300 mm 12 in to floor to a stud at each location that a computer television powered phone may be required to accompany each multimedia outlet TELUS Communications Inc c 2006 9 22 Page 11 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 4 4 Cable Routing Plan the route to avoid possible damage from future construction rubbing overheating dampness or contact with power wires The Canadian Electrical Code Part 1 Rule 60 300 requires a minimum of 50 mm approximately 2 separation from power cables We recommend 12 inches The cable route must follow a supported path through floor joists over ceilings through wall studs and behind baseboards If possible the route you select should conceal the cable TELUS recommends a minimum of two cable runs ie two separate four pair cables to each multimedia outlet to provision for future growth or upgrade of the multimedia outlet faceplate Separate runs will allow for ease of movement and arrangement of an occupants telephone Internet or advanced multimedia services will reduce time to locate faults and allow sufficient cable pairs for maintenance and provide for future service additions Things not to do e Do not run parallel to power cables withi
5. Requirements For Alberta use Form P630 Residential Service Entrance Requirements Forms are available from the Building Industry Consulting Service Web site at http www telus com bics or call TELUS Prewire at 1 800 665 5259 in British Columbia 1 888 530 6900 in Alberta TELUS Communications Inc c 2006 9 22 Page 33
6. outlet according to the TIA EIA 568 A standard as above e You must wire up all conductors to the multimedia outlet or 8 pin modular jack commonly known as RJ 45 Cat 5e cable consists of eight wires all should be connected as previously shown e The pairs within cat 5e cabling have twists in them It is important to insure all pairs have the correct twist ratios maintained right up to the jack or outlet terminations Do TELUS Communications Inc c 2006 9 22 Page 16 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH not leave longer pieces straight and untwisted This will ensure maximum data rates and minimize interference When running outlet cable four pair 24 GA CAT 5e minimum from multimedia outlets to your wiring distribution location DD ensure each run is a home run that means a single direct unbroken cable length No daisy chaining This may be referred to as Star Topology or Star Wiring see Diagram 2 and 3 Again we recommend a minimum of two cable runs ie two separate 4 pair cables to each MO to provision for future growth or upgrade of MO faceplate Keep cable runs direct and unbroken between MO and distribution device DD Although it may be tempting to splice two short lengths together to economize on cable costs doing so will cause interference limit flexibility and degrade network performance Place outlets prior to cladding the wall If possible protect terminations
7. sese sese eee eee eee 8 4 1 tte eler le EE 8 4 2 Outlet Locations Recommendations and Best Practices eee 8 4 3 Other Considerations For New Hommes sese eee 11 4 4 e eur EE 12 4 5 Telephones And Communications Devices In Batbrooms sss sese eee eee eee ee 13 4 6 What Type Of Telephony Devices To Connect 14 5 Wire Cable and Outlet Hardware cccccccccccccccccccccececeeeeeceeeeeceeeseneeaneneeeneneeeeecanenanenenenenananans 15 5 1 Wire Or Cable Selection e 15 5 2 Identifying Conductors In Cabling And Multimedia Outlets sss sss sss sese eee 15 5 3 Outlet Ty PS ET 16 SA Installation Best Practices 229 g toeege EES dee NENNEN Idadavantdetiasetddendialdens 16 5 4 1 Multimedia Outlet Tips 16 5 4 2 Cable Or Wiring Tips 17 5 4 3 RIEDER 18 5 5 Multimedia eli 1 niuia eege dee NEE ENEE EE 19 6 Distribution Device DD 20 6 1 IANO WAC EEN 20 6 1 1 Recommended Solution eee 20 6 2 Installation Best Practices e 21 6 3 Connecting ADSL Service sse eee eee eee eee 21 7 Connecting Telephone Gervice irratiei iertare ka ee ikatan ha parie tAn iia a ni taa 22 Tal Safety Precautions EE 22 7 2 TT Te Hee Tai e a T 22 7 3 RIZ TRe Vleiek Ge 22 8 Testing The Wiring And Multimedia Outlets sss sse eee 24 9 Appendix A Sample Test Summary Report sse ee eee ee 25 10 Appendix B Wiring Terminations sees eee eee eee eee eee 26 10 1 Wiring Terminations In NID sss sese eee ee eee eee eee eee 26 10 2 IDC Termination Instructions ee e e 26 1
8. the Provincial or Municipal Electrical Inspection Branch may require a permit prior to any prewiring adding to or rearranging the communications and data interior wiring They may also require that the work be inspected upon completion Contact your local Provincial or Municipal Electrical Inspection Branch for further information regarding these requirements If outlets are to be located in exterior walls or walls between suites obtain advice on maintaining the integrity of the vapour barrier or fire rated wall While TELUS uses reasonable efforts to include accurate and up to date information in this Document your use of this Document is at your risk Changes or updates to the contents of this Document may occur without notice to you TELUS shall not be liable to the user or any other person for damages or loss of any kind or nature including but not limited to injury or death resulting from the user s or any other person s unfamiliarity with the CEC or any other laws or regulations applicable to prewiring or the installation of wires or cables or for reliance by the user or any other person on the matters contained in this document You hereby agree that you shall not use any information contained in this Document in any claims proceedings suits or actions against TELUS its suppliers or affiliates You may not post publish reproduce transmit or otherwise distribute information or material from this document a constituting or e
9. 1 Appendix C DD Panel Configuration Ortronics sss sees sees eee ee eee eee eee eee 28 11 1 ORTRONICS MDUTSP IDC Pin Identification sss ss eee eee 29 11 2 DD Panel Termination Ortronics sese ee eee e eee 30 12 Appendix D 8 PIN Modular Jack Terminating Instructions A 31 13 Appendix E Strata Developments eee eee eee eee eee 32 14 Appendix F Industry standards AAA 33 TELUS Communications Inc c 2006 9 22 Page 3 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH Terms and Conditions of Use Any installation of premise wire shall be in accordance with the laws rules regulations technical standards and codes in effect at the time of installation whether federal or provincial The prewiring of a premise will have an immediate impact on the service to the premise as well it could affect the network system of TELUS As a result TELUS advises that any design installation and wiring is to be carried out by a trained telecommunication technician All telecommunications technicians are to be trained and certified by the manufacturer and supplier of the product or equipment to be installed This document makes references to and summaries of the rules as provided in the Canadian Electrical Code CEC The reference and summaries of these rules are provided for brevity and convenience Prior to any design installation or prewiring of a premise every trained technician is to be familiar with the CEC The CEC and
10. 12 from the end e Untwist a SINGLE twist of the CAT5e Inside Wire pair White Blue and terminate on the screw terminals of the Pots Splitter marked Phone e Strip the ends of the CAT5e Inside Wire pair White Green 1 2 from the end e Untwist a SINGLE twist of the CAT5e Inside Wire pair White Green and terminate on the screw terminals of the Pots Splitter marked ATU R 10 2 IDC Termination Instructions MiniRocker Connector Termination Procedure 1 Wire Termination x L lt Figure 1 Figure 2 Figure 2A Full wire Open contact Insert wire pair Visually inspect for full Close firmly Hear actuator by into color coded wire insertion through feel snap and lock simply pulling ports Figure the transparent body Figure 3 Repeat for back on Baseball 2 Figure 2A each connection caps with thumb Note Make sure that or finger Do not all contact actuators over open Figure are left in the down 1 or locked position TELUS Communications Inc c 2006 9 22 Page 26 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 2 Re termination Figure 4 Open contact actuator to fully open position by simply pulling back on baseball caps with thumb or finger Do not over open Figure 4 Remove wire by pulling it out fully 5 Figure If existing wire is to be re used cut off at least 14 6mm before re termination Figure 5 Repea
11. ITE WHITE WITH GREEN BAND 1 RING BLUE GREEN WITH WHITE BAND 2 4 TIP BROWN WHITE WITH BROWN BAND 7 RING ORANGE BROWN WITH WHITE BAND 8 TELUS Communications Inc c 2006 9 22 Page 15 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 5 3 5 4 5 4 1 Orange Pair 2 Green Blue Brown Pair3 Pair 1 Pair4 of aa Diagram 5 Standard 8 pin modular jack TIA EIA 568A Standard Outlet Types A multimedia outlet MO provides the means to connect to the following e Advanced Multimedia Services e Data Broadband High Speed Internet and Data Networking e Telephone and or e Optional Co ax for Cable TV Multimedia outlets may combine a multitude of sockets jacks or connectors of any of the following types 8 pin modular jack RCA S Video F connectors for Cable TV coax or fibre optics This would be called a multifunction outlet e g Belden CDT MDVO multimedia module or equivalent All 8 pin modular jacks must be wired to match the TIA EIA 568 A pinout configuration This industry standard has been adopted by Canada If MO s combine 8 pin modular amp F connectors then the 8 pin modular jack portion shall also conform to TIA EIA 568 A pinout standards Exterior outlets must be weatherproof Installation Best Practices See also Section 3 Planning Multimedia Outlet Locations and Cable Routing Multimedia Outlet Tips e Connect 8 pin modular jacks within each multimedia
12. O Multimedia Outlet means a wall mounted or flush mounted unit that may house a number of sockets or jacks for connecting up Cable TV telephone or data network devices NIB means Network Interface Box often containing Protector POTS Splitter etc OC Outlet Cable means a cable run that originates from the DD and terminates in a room at a Multimedia Outlet MO Set Run a run of standard Cat 5e cable comprising a group of eight wires or four pairs each wire corresponds to a pin on the 8 pin modular jack CCP CCB customer connection point or block PC a personal computer TELUS Communications Inc c 2006 9 22 Page 6 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 3 Quick Summary of Key Points gt A MUST READ FOR CONTRACTORS 4 3 1 3 2 3 3 3 4 Routing Cables see Section 4 4 for details v individual Cat 5e runs in 1 conduit preferred 90m maximum length v do not run cables near power light fixtures transformers fluorescent lighting v do not bend cable sharply observe minimum bend radii of cable do not crimp pinch or stretch install a single unbroken length between outlet and Distribution Device DD which is located at a centralized location ie Star Wiring Topology no daisy chaining no splicing of cable sections Outlet Installation Section 5 4 v room outlets include a single 8 Pin modular jack RJ 45 for TELUS TV or a
13. TELUS TELUS PARTNERED VARMHOME SOLUTIONS WIRING GUIDELINES FOR SINGLE FAMLY DWELLINGS FOR BC Version 2 0WH Date September 22 2006 TELUS Confidential 1 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH one connection endless possibilities For years TELUS has been providing excellence through ongoing development of existing and future products and services for our community As part of the TELUS Future Friendly Home we would like to introduce you to our Warm Home To enjoy the benefits of a Warm Home it does not have to be expensive time consuming or complicated The TELUS Warm Home Program works along with the TELUS Home Solutions Partner Program to help residential builders and developers provide premium telecommunications solutions to their homebuyers while raising the development s profile through carefully planned marketing The Warm Home enables the delivery of TELUS services to the homeowner at the time of move in allowing the homeowner to focus more on other pressing matters These services span across three primary types of media telephone high speed internet access and television With such services available at consumers fingertips almost immediately they ll have an extra incentive to confirm their purchase This document provides guidelines and recommendations for pre wiring new homes with Ethernet cables Cat 5e during the construction stage prior to the installation o
14. ce is necessary to ensure access to the cabinet A 15A 120 VAC nominal non switchable duplex electrical outlet must be provided adjacent to the space board or cabinet or within 0 3 m 1 ft of the DD The height of the electrical outlet should be suitable for the DD and associated equipment being installed and shall be in compliance with the Canadian Electrical Code Recommended Solution TELUS recommends the installation of an approved TELUS Structured Media Box as the DD 14 25 Wx20 Hx4 0 D 14 25 Wx36 Hx4 0 D 14 25 Wx10 Hx4 0 D TELUS Communications Inc c 2006 9 22 Page 20 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH The TELUS Panel Ortronics MDUTSP This distribution panel mounts inside the Ortronics Connect series enclosures and TELUS enclosures These panels distribute TELUS TV Telephone Data Ethernet and have a Security port to interface with alarm panels See Section 11 Appendix C DD Panel Configuration Ortronics 6 2 Installation Best Practices Required Space Ortronics Enclosure Distribution Panel TELUS MDUTSP1 Entry point for runs from Multimedia Outlets in rooms and cable run from NIB Multiple cat 5e runs from rooms and NIB Entry points to DD Distribution Enclosure Reserved area to mount Modem and Router Un switched 120V Duplex outlet For larger homes with more runs additional components may be required ONO OP wh Locate your DD panel
15. double modular jack RJ 11 amp RJ 45 for Tel Data minimum install two outlets per room v minimum install one outlet adjacent to each Cable TV outlet v terminate all 8 conductors in the outlet cable to the jack according to TIA EIA 568 A standard Central Distribution Location DD Section 6 v all installed runs of outlet cable must be terminated at a centralized location that will allow placement of a cross connect switch router and programmable equipment This is the Distribution Device DD 18 x 18 minimum space REQUIRED in closet storage room at reasonable working height 48 for cable run terminations and for the central distribution location ie the DD we sr bD a 1 x duplex 15A unswitched power receptacle dedicated to TELUS equipment and installed next to panel or within the reserved space Section 6 1 Ip grounding mandatory if metal cabinet installed Section 6 1 v locate your DD panel cabinet no closer than 12 30cm to a power distribution panel v complete the Label on the inside of the DD Panel cover by identifying the outlet cable runs with MO location id e g MBRO1 and type of service on each if known TELUS Media Hub Installation Notes Section 11 TELUS Communications Inc c 2006 9 22 Page 7 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 4 4 1 4 2 Planning Multimedia Outlet Locations and Cable Routing Introduction T
16. ed to the individual room outlets when a patch cord is connected from the modem or router as required Pairs 2 amp 3 are passed to IDC on rear at each location non bridged e TV JACKS o Straight 4 pair IDC on the back to a RJ45 on the front CAT 5e Designated TELUS TV inside wire set runs are terminated as required Service is provided when a patch cord is connected from a switch e AUX JACKS o Straight 4 pair IDC on the back to a RJ45 on the front CAT 5e For future expansion TELUS Communications Inc c 2006 9 22 Page 29 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 11 2 DD Panel Termination Ortronics All terminations on the Ortronics Panel are to be completed with the appropriate 110 Tools NOTES Terminate the 4 pair CAT 5e feed to the panel on the back of the Incoming Jack Terminate all Tel Data runs on Locations 1 13 Terminate all TELUS TV runs on TV1 4 locations and AUX 1 amp 2 in required Complete the Label on the inside of the panel cover For single set runs to each location the Ortronics MDUTFP11 or ATI 040 514D 68F2 WHT jacks may be used If 2 set runs are placed to each location 1 will be dedicated for Tel Data and the other will be dedicated for TELUS TV and terminated on the panel as indicated This scenario requires the Ortronics jack MDUTFP11 for the Tel Data and an RJ45 EDVO outlet added in the bottom knockout position OT eGo NOs When single Cat 5e set runs are used w
17. een improperly installed or maintained Description of prewiring Prewiring is a method of installing communications and data cabling such that it is concealed within the interior partition walls of your home Prewiring is done at the framing or hollow frame stage at the same time as the electrical wiring and before the application of insulation drywall and vapour barrier Once the walls have been surfaced existing wiring cannot be removed or replaced without disturbing the wall TELUS Communications Inc c 2006 9 22 Page 5 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 2 1 10 11 12 Definition Of Terms BIX means a block or strip into which conductors from a network cable are punched eg Belden CDT IDC Cat 5e means commonly and readily available standard network cable DD Distribution Device means one or any combination of the following cross connect router WAP switch or ADSL modem 8 pin Modular Jack means a standard socket or jack found within a multimedia outlet often called RJ 45 IDC means an Insulation Displacement Connector being a type of wire connection device in which the wire is punched down into a double metal holder and as a result the metal holders strip the insulation away from the wire thus causing the electrical connection to be made Inside wire means the wiring that is under the responsibility and control of the customer M
18. f drywall The guidelines are best used when combined with the TELUS Hub where all telecommunications cabling comes together in the home As technology continues to evolve so should the cabling systems to support homeowners changing needs TELUS recommends an integrated end to end solution for all category 5e wiring cabling by fully trained and certified electricians and wiring contractors And to make residential development projects as straightforward as possible TELUS will continue to make changes to this document to ensure alignment with Residential Cabling Standards and CSA T525 For more information about the Warm Home Program and how we can help you differentiate a residential development project in your community please call us today at 1 866 844 1544 or visit our website http Awww telus com mybuilding TELUS Communications Inc c 2006 9 22 Page 2 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH TABLE OF CONTENTS 1 Terms and Conditions of B L TTT 4 2 General Tai reen LiL A EErEE saves EEEE EEE AE ood E A EE EAE sagddvaiaadeodaddeantacdeaubes 5 2 1 DeTiNItIOM OF KEEN 6 3 Quick Summary of Key Points sese sese eee eee 7 3 1 Routing Cables see Section 4 4 for details 7 3 2 Outlet Installation SSeCION D 4S EE 7 3 3 Central Distribution Location DD 1 Section pl 7 3 4 TELUS Media Hub Installation Notes Section 11 7 4 Planning Multimedia Outlet Locations and Cable Routing sss
19. f not planning Adequate wiring will give customers flexibility in arranging their telephone second line FAX lines and multimedia services such as TELUS PureRadio or networked audio devices Please refer to Form P546 BC or P630 AB for connection to TELUS service and owner developers support and housing requirements Wiring standards should also be considered to accommodate for tomorrow s communication technologies Security wiring and cablevision wire should also be planned at this time For details on wiring standards please see Section 5 Wire Cable and Hardware TELUS must be contacted when the pathway is in place to install the service entrance wire and the demarcation block Outlet Locations Recommendations and Best Practices Suggestions for locating outlets can be found in Diagram 3 In each room locate outlets as follows 1 to allow two per room minimum at least one near the Television and one for the PC or telephone 2 on walls that make up a corner where Television or PC might be located 3 to prevent cross room or cross doorway cable runs see Diagram 3 and 4 to suit present and future needs e g TELUS multimedia services use in the kitchen TELUS Communications Inc c 2006 9 22 Page 8 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH DIAGRAM 1 lt Aerial Option Bedroom 1 G Bedroom 2 R D LS D b i 3 D DU Li Room Kitchen N LU LU LU LU
20. ith the TELUS MDUTSP1 Panel Distribution Device a dual jack consisting of single RJ 11 and RJ 45 8 Pin Modular such as an Ortronics MDUTFP1 1 88 or an ATI 040 514D 68F2 WHT can be used TELUS Communications Inc c 2006 9 22 Page 30 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 12 Appendix D 8 PIN Modular Jack Terminating Instructions The RJ 45 jacks are to be terminated according to TIA 568 A standards as shown below Standard 4 Pair Wiring Color Codes Pair 1 T White Blue R Blue White Pair 2 T White Orange R Orange White Pair 3 T White Green R Green White Pair 4 T White Brown R Brown White A Band Striped Twisted Pair Wire eS TIP Pair 2 A BASE COLOR BAND COLOR Pair 3 Pair 1 Pair 4 W GRGR WO BL WBL O WBR BR T568A TELUS Communications Inc c 2006 9 22 Page 31 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 13 Appendix E Strata Developments The following is an example of a Strata style development where the TELUS Entrance Cable is terminated and protected in a structure near the entrance to the development The MDU Pots Splitter is also located in this location PUBLIC PROPERTY TELUS Entrance Cable PUBLIC PROPERTY 1 A Transition Housing must be placed at each house for transitioning the drop cable to the 4 pair CAT 5e inside wire from the TELUS Hub 2 When individual 4 pair d
21. n the same stud or joist space otherwise transmission and interference problems may be experienced Refer to Diagram 4 for suggested correct installation e Donotrun communications and data cables through holes occupied by electrical cables e Donotrun communications and data cables in parallel with any power wiring e Multimedia outlets should not be located within the same studs as a power outlet e Never run power in same conduit as communications and data cables e f power cables are housed in metal armored sheathing then the above limitations may not apply likewise minimum separations may not apply since damaging power emissions EMI are shielded by the sheathing e Ensure avoidance of fluorescent light fixtures see Table 1 below for minimum separations e Ensure avoidance of low voltage style track light fixtures containing transformers e Do not bend communications and data cables sharply minimum bend radii four x diameter of cable for cat 5e 2 5 inch for co ax RG 6 TELUS Communications Inc c 2006 9 22 Page 12 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH TABLE 1 Minimum Separations Guide Interferer Clearance Fluorescent lighting 12 305 mm Power cables 110V 12 305 mm Unshielded power lt 2kVA 5 127 mm Unshielded Power gt 5kVA 24 610 mm Transformers motors elevators 40 1016 mm j e MULTIMEDIA
22. ncouraging conduct that would constitute a criminal offence or give rise to civil liability b which is protected by copyright or other intellectual property right or derivative works thereof without obtaining permission of the copyright holder c otherwise use this Document in a way that is contrary to law or which would adversely impact use of this Document by other users including the posting or transmitting of other information Neither TELUS its suppliers affiliates nor any other party involved in creating producing or delivering the Document is liable for any direct indirect incidental special consequential punitive or other damages whatsoever including business interruption loss of use data information profits regardless of the form of action including but not limited to contract negligence or other tortious act arising out of or in connection with your use of the Document even if TELUS has been advised of or foresees the possibility of any damages occurring Without limiting the foregoing everything in the Document is provided to you AS IS WITHOUT REPRESENTATION WARRANTY OR CONDITION OF ANY KIND EITHER EXPRESS IMPLIED OR STATUTORY INCLUDING BUT NOT LIMITED TO IMPLIED REPRESENTATIONS WARRANTIES OR CONDITIONS OF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE DURABILITY TITLE OR NON INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS You agree to defend indemnify and hold TELUS its suppliers and affiliates harmless fr
23. o enable your home for enhanced systems TELUS multimedia services or as a smart home all installed runs of outlet cable must be terminated at a centralized location that will allow placement of a cross connect switch router and programmable equipment that your system requires This centralized location is identified by the Distribution Device DD in most diagrams see Diagram 1 2 amp 3 A prewired cable run to the network interface box NIB from the centralized location or DD will also be required When selecting Multimedia Outlet MO locations select those that suit both your present and future needs TELUS suggests you consider a minimum of two 2 outlets in each of the areas shown here in Diagram 3 A separate cable run will be required for each service or device at each outlet For example if the outlet contains two sockets one for telephony and one for Internet service then two sets of four pair cable may need to be run to this outlet For rooms designated as likely candidates for the location of entertainment or multimedia equipment e g living room family room home office home theatre room or den additional wall outlets should be allocated It is not necessary to have a communications and data device connected at every prewired location however by planning ahead you reduce the cost of future outlet installations Unsightly surface wire additional installation time and inflexibility of device arrangements are consequences o
24. om any and all liabilities costs and expenses including reasonable legal fees related to any violation of these Terms and Conditions by you or in connection with your use of this Document or with the placement or transmission of any message or information from the Document by you TELUS failure to insist upon or enforce strict performance of any provision of these Terms and Conditions shall not be construed as a waiver of any provision or rights contained in these Terms and Conditions By using this document you agree that these Terms and Conditions shall be governed by the laws of the province of British Columbia and the federal laws of Canada applicable therein and you agree to be bound by the laws of these jurisdictions TELUS Communications Inc c 2006 9 22 Page 4 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 2 General Information Purpose of guide This guide is intended for use in new construction additions and remodeled single dwellings for telephone TELUS multimedia services broadband Internet or home networking This guide specifically applies to wood frame residences What you are responsible for You are responsible for a correcting any service difficulty that the installation or prewiring creates and which harms the telecommunications network b paying a service charge when TELUS makes a repair visit to your premises in order to remedy problems resulting from wiring that has b
25. or cabinet no closer than 12 30cm to a power distribution panel suggested distance is 24 or 60cm to protect network equipment from sources of interference Clearly mark all set runs with MO location id and type of service on each if known suggested e g MBR01 KTCH01 DNGRO1 LIVRO1a LIVRO1b Clearly identify and mark all services and ports Use a tone generator or Fluke MicroscannerPro kit to assist in determining which cable runs connects to which room See instructions supplied with your tool 6 3 Connecting ADSL Service For single room outlet requiring ADSL service 1 patch RJ 11 jumper from RJ 11 jack marked ADSL to the RJ 11 jack on modem 2 patch RJ 45 jumper from ADSL modem to appropriate room outlet jack For multiple outlets requiring service 1 install a switch or residential gateway 2 patch RJ 11 jumper from RJ 11 jack marked ADSL to the RJ 11 jack on modem 3 patch RJ 45 jumper from ADSL Modem Ethernet port into one switch gateway router port possibly marked WAN or UPLINK port patch all TELUS Communications Inc c 2006 9 22 Page 21 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 7 1 7 2 7 3 outlets to be ADSL Enabled into remaining ports on switch gateway router you may own Connecting Telephone Service Safety Precautions Remember when working on existing telephone service it is possible to come in contact with electrical currents Again TELUS recommends tha
26. pin or other grounds Example Test steps Insert test cable from test instrument into Modular 8 pin J ack RJ 45 socket of Multimedia Outlet Run Wiremap test to ensure correct cable socket wiring Pass Run Length test Length required less than 90m 295 ft Less than 90m Check for cable faults indicated by distance Open or Short is away from outlet under test No faults or zero distance Check far end connector at DD is not faulty No faults Note This verification check for residential wiring does not test the information carrying capacity of the link Network cables installed in typical residences are shorter than those found in commercial installations and do not suffer as much from losses Good capacity can be expected when the guidelines for cable routing and installations have been adhered to Suggested testing devices include e FLUKE MicroScannerPro or better e FLUKE DSP4300 e Agilent Wirescope 350 e ResiTester or similar TELUS Communications Inc c 2006 9 22 Page 24 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 9 Appendix A Sample Test Summary Report Home Network Certification Verification Check Sheet and Install Record Installation date SE Crew Service contact Ph Installation Installer Company Name Development Name Address Address City Lot Block Prov Post Code City Phone Pro
27. r or building inspector Leave at least 30 cm 12 of excess cable at the outlet end TELUS Communications Inc c 2006 9 22 Page 17 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH For new homes consider using conduit to allow for easy pulling of future wiring Exterior cabling must use exterior grade cable Do not kick cabling under baseboards cabling is loose and can become snagged and damaged Attaching to baseboards is ok 5 4 3 DDTips Leave a minimum of 1 5m excess on all cable runs at the DD At a minimum install two cable runs communications and data from your DD to the TELUS demarcation point and NIB when required TELUS recommends IDC style strips or blocks and jumpers patchcords required for cross connects It is critical to ensure all pairs have the correct twist ratios maintained right up to the IDC strip or block terminations Do not leave longer pieces straight and untwisted This will ensure maximum data rates and minimize interference TELUS Communications Inc c 2006 9 22 Page 18 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 5 5 Multimedia Outlets Examples of Multimedia Outlets follow TDN Faceplate with interchangeable jack module Ortronics MDUTFP11 Faceplate with fixed jack non interchangeable ATI 040 514D 68F2 WHT The 8 pin modular jacks RJ 45 must meet the TIA EIA 568 A B pin out standard in order to meet indu
28. rops are placed to each housing unit all 4 pairs of the drop and the 4 pair CAT 5e inside wire from the TELUS Hub must be terminated on an approved CAT 5e connector i e a grease filled BIX strip complete with BIX Wire Retainer clips TELUS Communications Inc c 2006 9 22 Page 32 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 14 Appendix F Industry standards Standards pertaining to the creation of this TELUS wiring guide National Building Code of Canada Canadian Electrical Code and British Columbia Alberta Electrical Code CAN CSA No T525 94 Residential Wiring for Telecommunications CAN CSA C22 2 No 182 4 M plugs Receptacles Connectors for Communication Systems CAN CSA T530 M90 Building Facilities Design Guidelines for Telecommunications CAN CSA T528 Design Guidelines for Telecommunications CN CSA T528 Design Guidelines for Administration of Telecommunications Infrastructure in Commercial Buildings CS 03 Terminal Attachment Program TIA EIA 568 A 8 pin modular jack wiring configurations TIA 570 A and TIA 570 B Residential Telecommunications Infrastructure Standard Acknowledgements Diagrams 2 and 3 in this guide are extracted courtesy of BICSI from BICSI Tele communications Distribution Methods Manual TDMM 10 edition Chapter 17 Residential Cabling Additional Information For British Columbia use Form P546 Residential Service Entrance
29. s to Pins 3 amp 6 e Pair 3 connects to Pins 1 amp 2 e Pair 4 connects to Pins 7 amp 8 RJ45 patch cord included then patch dial tone to security in Blank is included for future use if required An addition RJ45 may be inserted e SECURITY JACK o IN JACK All 4 pairs plugged into security in Pair 1 is bridged to in of RJ31X for POTS service only when a RJ45 plug is inserted into RJ31X port Pairs 2 3 amp 4 from the RJ45 are distributed to security out o RJ31X JACK When the cord to the Alarm Panel is plugged in dialtone is routed thru the alarm panel and back out to the out of the RJ31X Out pair of RJ31X bridged to pair 1 of OUT o OUT JACK Patch Cord from OUT to ADO to feed dialtone and DSL to jacks e ADO JACK o Pairs 1 amp 4 are bridged to pairs 1 amp 4 of LOC 1 thru LOC 13 and EXP When the patch cord from SECURITY OUT is connected dialtone is supplied to LOC 1 thru LOC 13 and EXP jacks When the patch cord from SECURITY OUT is connected DSL is supplied to DATA INTO MODEM Pairs 2 amp 3 are bridged to DATA INTO MODEM e DATA INTO MODEM JACK o RJ11 cord feeds DSL signal to modem PAIRS 2 amp 3 PINS 1 2 amp 3 6 e LOC 1 thru LOC13 amp EXP JACKS o Pairs 1 amp 4 are bridged between jacks o Straight 4 pair IDC on the back to a RJ45 on the front Inside wire set runs providing POTS and DSL services are terminated on LOC1 thru LOC13 as required DSL service is provid
30. stry certification and cabling standards Combination 8 pin modular amp F connector jacks e g Belden CDT MDVO multimedia module or equivalent shall also conform to TIA EIA 568 A B pin out standards TELUS Communications Inc c 2006 9 22 Page 19 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 6 6 1 Distribution Device DD Hardware Builders and homeowners will require hardware to terminate in home wiring from outlets a means to patch or distribute smart home services through to outlets and provide flexible reconfiguration of such A distribution device DD is a cross connect facility used for the termination and connection of outlet cables distribution device cords and equipment cords There is no requirement for secondary protection at the DD A DD must be installed inside each home in a location that is accessible for cabling maintenance The location should be centralized within the home to minimize the length of outlet cables Initial DD space requirements should be sized at a minimum of 450 mm 18 width and 450 mm 18 height The DD should be positioned such that sufficient unobstructed clearance will be available for some potential protrusion of equipment outside the wall surface If the location of DD necessitates security or physical protection for example if located in a closet or a high traffic area a cabinet is recommended The cabinet may protrude from the wall Clearan
31. t termination procedure above 3 Testing Routine Using The Test Clip Figure 6 Test Ports To Test Insert test clip into test ports on face of MiniRocker connector refer to Figure 6 Fully insert test clip to full stop as shown Figure 6A Figure 6A Figure 7 Side only open test clip inserted Figure 7 To test the CO Input contact actuator with Remove the test clip Close contact actuator firmly Hear feel snap and lock Figure 8 TELUS Communications Inc c 2006 9 22 Page 27 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 11 Appendix C DD Panel Configuration Ortronics ee ee R D eae TEE TE a a aa Serie v ees cee E Z meda US NL HHH H NUNN N TO SECURITY SYSTEM aa at le tee A FROM NID e Ges DSL MODEM T Paren TO LOCATION PATCHED Oo MPU pele et TO MULTIPLE O LOCATIONS OR OF COMPUTERS LOC 1 13 DSL ROUTER MODEM TorouteR TELUS Communications Inc c 2006 9 22 Page 28 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 11 1 ORTRONICS MDUTSP IDC Pin Identification e INCOMING JACK o IDC onthe back to a RJ45 on the front 4 pair feed from NIB is terminated on the IDC s Pr1 Dialtone e Pr2 Vacant e Pr3 DSL Signal e Br 4 Reserved for 2 line All Pairs are connected through to the RJ45 Incoming Jack e Pair 1 connects to Pins 4 amp 5 e Pair 2 connect
32. t installations be carried out by a trained technician Work on telephone or any wiring should never be undertaken during thunder and lightning storms To reduce possible feedback of potentially hazardous voltages either caused by lightning strikes or contact with high voltage power lines the Canadian Electrical Code requires the installation of a primary protector as per Rule 60 200 as noted below 60 200 Provision of Primary Protectors 1 A primary protector shall be provided on each electrical communication circuit except as provided in Subrule 4 2 The primary protector shall be located in on or immediately adjacent to the structure or building served and as close as practicable to the point at which the conductors enter or attach 3 The primary protector shall not be located in any hazardous location as defined in Sections 18 20 and 24 nor in the vicinity of flammable or explosive materials 4 A primary protector need not be provided if no portion of the circuit is considered exposed plant Primary protection must be provided on circuits considered exposed plant Where located outdoors the circuit shall be located below grade level and installed in a conduit These circuits shall not have any exposure to lightning or contact with power lines at all times Direct buried cable conductors are generally classed as exposed plant because they are usually susceptible to lightning strikes Service Connection In new homes the
33. telephone entrance cable aerial or underground terminates in the NIB box located on the outside walls of your single family residential buildings It is usually located close to the electrical meter To gain access to the NIB box or NIB lid and to the demarcation jacks loosen the screws and optional customer lock located on the right hand side of the NIB box or lid With the outer door swung open access to the demarcation jacks and or inside wire is now possible In accordance with regulations TELUS must be contacted to determine the proper demarcation point Demarcation Point The terminals found on demarc blocks and protectors could be marked in a number of ways Conductor Colour Identification TELUS side Customer side TIP Green T1 Tin Tout RING Red R1 Rin Rout TELUS Communications Inc c 2006 9 22 Page 22 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH WARNING Altering or adding to the telephone protector could be hazardous to your property or person and should never be undertaken except by a trained telephone technician TELUS Communications Inc c 2006 9 22 Page 23 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 8 Testing The Wiring And Multimedia Outlets Verification testing should be performed on all outlet and cable installations Test for the following faults opens shorts miswires discontinuities pin to
34. vince Postal Code Email Example is shown on first line with number of drops per cable type Note C3 category3 C5 category5 C5e category 5e Test V Verified for continuity wiremap and length C Certified to cabling performance specified per the ANSI TIA EIA 570 A Standard SE Location C6 category 6 Other Note Example MBRO1 primary TELUS outlet TELUS Communications Inc c 2006 9 22 Page 25 Wiring Guidelines for Warm Home Single Family Dwellings Version V3 0WH 10 Appendix B Wiring Terminations 10 1 Wiring Terminations In NIB Ensure no more than 2 twists are undone when terminating CAT 5e cable 1 Drop Wire and Inside Wiring to be terminated according to the following instructions T stands for Tip and will always be the Predominately White wire with a colored stripe R stands for Ring and will always be the Predominately Colored wire corresponding to the Tip colored stripe See attachment IDC Termination Instructions Terminate the Copper Drop wire on the protection unit on the door in the following manner e Untwist a SINGLE twist of the CAT5e Drop Wire pair White Blue and terminate on the IDC connector marked T in and R in Terminate the CAT5e Inside wire on the Pots Splitter unit on the door in the following manner e Strip the ends of the CAT5e Inside Wire pair White Blue
35. with plastic bags tied on at both MO and DD cable ends prior to completing drywall and painting Coloured jacks for installation into MO may be a useful option for identifying services eg black for LAN internet or white for phone 5 4 2 Cable Or Wiring Tips Do not pull communications and data cables through holes occupied by electrical cables maximum run length is 90m Cables that cross should be at 90 degrees to each other Do not exert gt 25lbs of pulling force on 4 pairs CAT 5e and 6 Do not splice wires on runs pull another if things go wrong Where required secure the cable every 600 mm 24 with a round staple designed for the wire Do not pinch the wire Use plastic non metallic staples to support wire and leave the wire loose in the staples Do not drive staples all the way in as microbends in the copper reduce transmission quality Avoid sharp edges and turns and do not kink the cable minimum bend radii is 10 x diameter of cable for CAT 5e 2 5 inch for co ax RG 6 If a staple pierces the cable the entire length of cable must be replaced to prevent transmission problems Where sheet metal framing is used install grommets to protect the cable from the sharp metal edges When drilling through floor joists ensure that the structural integrity is not being jeopardized For example prefabricated joists may have manufacturers specification location for drilling holes Check with your design engineer manufacture