Home

SPX Cooling Technologies 05-116E User's Manual

image

Contents

1. Marley MH Fluid Cooler User Manual 05 116E SPX COOLING TECHNOLOGIES Note Z Warning A Caution Note Contents This manual contains vital information for the proper installation and operation of your fluid cooler Carefully read the manual before installation or operation of the fluid cooler and follow all instructions Save this manual for future reference Fluid Cooler location ctore etc tnter ees 5 Fluid Cooler ss 6 Receiving Fluid Cooler ia itu tremenssedtemuitianha 6 Hoisting Fluid Cooler iicet netten cie ce 6 Fluid Cooler Installation eiui nro i rion note 7 Motor Wings sen atu utri 8 Mechanical Equipment irren 11 Fluid Cooler Start Up sisi sabe enna rena 13 Fluid Gool r Op rAtION depen RE 15 Wintertime Operation issu 16 Water Treatments 22 e ree va epe e Ee navire 20 Fluid Cooler erneuern 21 BIOWO OWI OE 21 Belt Adjustment se 22 Sheave Alignment eter evo entendu 24 Fluid Cooler Maintenance 25 Seasonal Shutdown Instructions 28 Prolonged Shutdown 29 Troubleshooting itio x Ea Ens 32 Additional Information 34 The following defined term
2. match marks properly matched Repair or replace worn couplings Rebalance drive shaft by adding or removing weights from balancing cap screws See Driveshaft User Manual Fan Make certain all blades are as far from center of fan as safety devices permit All blades must be pitched the same See Fan User Manual Clean off deposit build up on blades Worn Geareducer bearings If equipped Worn fan shaft bearings Belt drive Check fan and pinion shaft endplay Replace bearings as necessary Check fan shaft endplay Replace bearings as necessary Unbalanced motor Disconnect load and operate motor If motor still vibrates rebalance rotor Bent Geareducer shaft If equipped Check fan and pinion shaft with dial indicator Replace if necessary Fan noise Blade rubbing inside of fan cylinder Adjust cylinder to provide blade tip clearance Loose bolts in blade clamps Fan shaft bearing Belt drive Check and tighten if necessary Grease bearings Scale or foreign substance in circulating water system Insufficient blowdown See Water Treatment section of this manual Water treatment deficiency Consult competent water treating specialist See Water Treatment section of this manual Cold water temperature too warm See Tower Operation Excessive drift exiting fluid cooler Entering wet bulb temperature is above design Design wet bulb temperature was too low
3. alternative biocidal treatment programs described in the following e Resume treatment with the biocide which had been used prior to shutdown Utilize the services of the water treatment supplier Maintain the maximum recommended biocide residual for the specific biocide for a sufficient period of time residual and time will vary with the biocide to bring the system under good biological control or e Treat the system with sodium hypochlorite to a level of 4 to 5 mg L ppm free chlorine residual at a pH of 7 0 to 7 6 The chlorine re sidual must be held at 4 to 5 mg L ppm for six hours measurable with standard commercial water test kits If the fluid cooler has been in operation and then shut down for a duration of time and not drained perform one of the two previous biocidal treatment programs directly to the fluid cooler storage vessel collection basin drain down tank etc without circulating stagnant water over the cooling tower fill or operating the cooling tower fan After biocidal pretreatment has been successfully completed cooling water may be circulated over the tower fill with the fan off When biocidal treatment has been maintained at a satisfactory level for at least six hours the fan may be turned on and the system returned to service Resume the standard water treatment program including biocidal treatment Operation Fluid Cooler Operation General The cold process fluid temperature obtained from an
4. destruc tive hard ice on the fluid cooler fill Certain guidelines should be followed 1 Do not allow the fluid cooler s leaving process fluid temperature to drop below 45 F If such low temperature operation is necessary or beneficial to your process establish the minimum allowable level as follows During the coldest days of the first winter of operation observe whether any ice is forming on the louver face particularly near the bottom part of the louver face If hard ice is present on the louvers you must increase the allowable cold water temperature If the minimum allowable cold process fluid temperature is estab lished at or near minimum heat load it should be safe for all operat ing conditions Having established the minimum allowable cold water temperature maintaining that temperature can be accomplished by fan manipulation as outlined in Item 4 under Fluid Cooler Operation 2 As cold air enters the louvers it causes the water flowing over the fill to be drawn inward toward the center of the tower Thus under fan operation the louvers and lower periphery of the tower structure remain partly dry seeing only random splashing from within the tower plus normal atmospheric moisture from the entering air Such lightly wetted areas are most subject to freezing Therefore if excessive ice forms on the louvers stop the fan for a few minutes With the fan off the water flow will increase in the vicinity of the louve
5. located on the access door Safety First The location and orientation of the fluid cooler can affect the safety of those responsible for installing operating or maintaining the fluid cooler However since SPX Cooling Technologies does not determine the location or orienta tion of the fluid cooler we cannot be responsible for addressing those safety issues that are affected by the fluid cooler s location or orientation The following safety issues should be considered by those responsible for designing the tower installation e access to and from the fan deck e access to and from maintenance access doors e the possible need for ladders either portable or permanent to gain access to the fan deck or maintenance access doors the possible need for handrails around the fan deck the possible need for external access platforms e potential access problems due to obstructions surrounding the tower lockout of mechanical equipment the possible need for safety cages around ladders the need to avoid exposing maintenance personnel to the potentially unsafe environment inside the fluid cooler Note Preparation Itis notintended norassumed thataccess to the fan deck on single flow models Models MHF702 thru MHF705 is needed or necessary Those are only some of the safety issues that may arise in the design process SPXstrongly recommends that you consulta safety engineer to be sure that all safety considerations have been add
6. operating fluid cooler will vary with the following influences 1 Heat load With the fan in full operation if the heat load increases the cold process fluid temperature will rise If the heat load reduces the cold process fluid temperature will reduce Heat Load Btu hr Range F GPM x 500 Note that the number of degrees range through which the fluid cooler cools the process fluid is established by the system heat load and the amount of fluid being circulated in accordance with the follow ing formula formula is only valid for 100 water as process fluid The fluid cooler establishes only the cold process fluid temperature attainable under any operating circumstance 2 Air wet bulb temperature Cold process fluid temperature will also vary with the wet bulb temperature of the air entering the louvered faces of the fluid cooler Reduced wet bulb temperatures will result in colder process fluid temperatures However the cold process fluid temperature will not vary to the same extent as the wet bulb For example a 20 F reduction in wet bulb may result in only a 15 F reduction in cold process fluid temperature 3 Fluid flow rate Increasing the process fluid flow rate GPM will cause a slight elevation in cold process fluid temperature while reducing the fluid flow rate will cause the cold process fluid temperature to decrease slightly However at a given heat load see formula above process fluid flow reduc
7. the system is to be shut down for an extended period of time it is recommended that the recirculation water system be drained Leave the basin drains open Draining the coil is not recommended draining promotes corro sion inside the coil tubes See protecting coil in Freezing weather on page 18 During shutdown clean the fluid cooler see Warning page 21 and make any necessary repairs Eliminators and louvers are easily removed to gain access to the coil Pay particular attention to mechanical equipment sup ports and sheaves or coupling or drive shafts Following each year s shutdown and cleaning inspect the fluid cooler s metal surfaces for evidence of the need to apply a protective coating Do not misinterpret grime as a need to have the tower painted If relatively bright metal can be exposed by cleaning consider that the galvanizing Note A Caution Maintenance has remained effective Unless there is evidence of a generalized failure of the galvanizing localized touch up should be all that is required To the extent that the galvanizing zinc coating still exists paint will not adhere to it readily Contact the manufacturer of the coating you intend to use for instructions Fluid cooler framework Check structural bolted connections and tighten as required Fans Check fan assembly bolting and tighten as required Use torque values prescribed in the Fan User Manual Fans shaft bearings If equipped lubricat
8. to compensate for the load increases that normally occur with the replacement or addition of production equipment and still retain continuity with respect to your fluid cooler system Fluid cooler rebuilding SPX routinely rebuilds and upgrades fluid coolers and cooling towers of all materials and manufacture If your product ever reaches the limit of its service life we recommend that you investigate the cost of rebuilding before you routinely order a new replacement tower Each MH Fluid Cooler includes a document package containing general orientation drawings and tower component manuals These documents contain important information relating to safe installation and operation of the fluid cooler Field installation is required for fan guards double flow models piping inlets and piping outlets Some optional accessories such as handrails ladders and safety cages may also require field installation A separate installation drawing or manual for each purchased option is included in the document package along with bills of material If you have purchased an option and can t find the appropriate installation drawing contact your local Marley sales representative before proceeding In addition to these specific documents numerous technical reports are published by SPX including more detailed information on a variety of cool ing tower and fluid cooler operation and service topics Your Marley sales representative will be happy to give you
9. water basin This is the recommended operating water level Adjust the float valve so that it is 75 open at that level Continue filling the system until the water reaches a level approximately 1 8 3 mm below the lip of the overflow Start your pump s and check for proper rotation as indicated by the arrow on the pump cover observe system operation A certain amount of pump down of the basin water level will occur before water completes the circuit and begins to fall from the fill in the up per module The amount of initial pump down may be insufficient to cause the float valve to open However you can check its operation by pressing down on the operating lever to which the stem of the float valve is attached Some trial and error adjustment of the float valve may be required to balance the makeup water with tower operation Ideally the float valve setting will be such that no water is wasted through the overflow at pump shutdown However the water level after pump start up must be deep enough to assure positive pump suction Open the valve on the tower bleed line and adjust bleed to the recom mended rate See Water Treatment section on page 20 Continue pump operation for about 15 minutes after which it is rec ommended that the water system be drained flushed and refilled 13 Operation 7 While operating the recirculating water pump s and prior to operat ing the cooling tower fan execute one of the two
10. 165 MHF706 102 750 MHF703 122 200 MHF706 122 885 MHF704 9061 160 MHF707 061 450 MHF704 081 210 MHF707 081 580 MHF704 101 260 MHF707_ 101 710 MHF704 121 310 MHF707_ 121 840 MHF704 062 190 MHF707 062 570 MHF704 082 250 MHF707 082 740 MHF704 102 315 MHF707 102 905 MHF704 122 375 MHF707_ 122 1071 When the use of industrial antifreeze solutions is not possible the system must be operated to meet both of the following conditions 1 Maintain sufficient flow rate through the coil 2 Maintain sufficient heat load on the process fluid Fluid exiting the coil must be maintained at or above 45 F Cycling of the recirculation pump should not be used to control process temperatures Draining the coil is not acceptable as a normal method of freeze protection draining promotes corrosion inside the coil tubes Drain ing is acceptable in an emergency if the coil is not protected by an antifreeze solution It is recommended that you discuss your freeze prevention options with your local Marley sales representative 19 Note 20 Operation Water Treatment and Blowdown Maintaining Water Quality The steel used in MH Fluid Cooler s has been galvanized with a heavy zinc coating averaging 2 0 mils in thickness Other materials used PVC fill drift eliminators and louvers aluminum fans cast iron Geareducer etc are selected to offer maximum service life in a normal fluid cooler environment defined as follows Recirculati
11. 25 18 11 08 10 F 5 56 1 58 78 51 38 25 18 15 F 8 33 C 2 38 1 18 78 58 38 28 20 F 11 11 C 3 18 1 58 1 05 78 51 38 25 F 13 89 C 3 98 1 98 1 32 98 64 48 Cooling Range Multipliers are based on drift of 0 02 of the circulating water rate Range Difference between hot water temperature and cold water temperature EXAMPLE 700 GPM circulating rate 18 F cooling range To maintain 4 concentrations the required blowdown is 0 458 or 00458 times 700 GPM which is 3 2 GPM If fluid cooler is operated at 4 concentrations circulating water will contain four times as much dissolved solid as the makeup water assuming none of the solids form scale or are otherwise removed from the system When water treatment chemicals are added they should not be in troduced into the circulating water system via the water collection basin of the cooling tower Water velocities are lowest at that point which results in inadequate mixing An ideal location would be the redistribution basin above the coil Belt Tensioning See Figure 1 and Figure 2 for MH Fluid Cooler models MHF702 thru MHF705 Loosen specified hardware located at the top and bottom of the motor support assembly before adjusting the jacking screws Do not remove the hardware it is required to support the motor Tighten the hardware after adjustment Ideal tension is the lowest tension at which the belt w
12. Check to see if local heat sources are affecting fluid cooler See if surrounding structures are causing recirculation of tower discharge air Discuss remedy with Marley representative May have to increase fluid cooler size Discuss remedy with Marley representative Actual process load greater than design May have to increase fluid cooler size Discuss remedy with Marley representative Overpumping Reduce water flow rate over fluid cooler to design conditions Fluid cooler starved for air Distribution basins overflowing Check motor current and voltage to be sure of correct contract horsepower Repitch fan blades if necessary Clean louvers fill and eliminators Check to see if nearby structures or enclosing walls are obstructing normal airflow to fluid cooler Discuss remedy with Marley representative Reduce water flow rate over fluid cooler to design conditions Be sure distribution water basin nozzles are in place and not plugged Faulty drift elimination Check to see that integral fill Louvers and eliminators are clean free of debris and installed correctly If drift eliminators are separate from fill make sure they are correctly installed and in place Clean if necessary Replace damaged or worn out components 33 34 Additional Information Increased load requirements MH Fluid Coolers are designed so that cells of either equal or unequal capacity can be added in the future This allows you
13. The fan deck ladder should not be used to enter or exit the access doors located on the cased face of the tower unless the optional access door platform is provided The purchaser or owner is responsible for providing a safe method for entering or exiting the access door Use of the fan deck ladder to enter or exit the access doors may result in a fall Included with this instruction packet are separate User Manuals on each major operating component of the tower and it is recommended that you read them thoroughly Where discrepancies may exist the separate User Manuals will take precedence The following is recommended as a minimum routine of scheduled main tenance Always shut off electrical power to the tower fan motor prior to performing any inspections that may involve physical contact with the mechanical or electrical equipment in or on the tower Lock out and tag out any electrical switches to prevent others from turning the power back on Service personnel must wear proper personal protective clothing and equipment 25 26 Maintenance Weekly Inspect for bacterial growth and general operation conditions Bacterial growth should be reported to your water treatment expert for immediate attention Monthly Weekly at start up Observe touch and listen to the fluid cooler Become accustomed to its normal appearance sound and level of vibration Abnormal aspects relating to the rotating equipment should be conside
14. These symbols represent how the motor is constructed on the inside and in no way have anything to do with a Delta or Wye electrical distribution system serving the motor When using a starter e Set motor overload protection to 110 of motor nameplate amps This setting allows the fan motor to operate during cooler weather During cooler weather it is common for the motor to draw 6 to 10 higher than nameplate amps High amps are common during tower commissioning when the tower is dry and the ambient air temperature is cool Note Installation Do not start the motor more than six times per hour Short cycling the tower will cause fuses breakers or O L s to operate and will decrease motor life When using a two speed starter e Motor rotation must be the same at slow speed and high speed Single winding motor requires a starter with a shorting contactor e Two winding motor requires a starter with out a shorting contactor e All two speed starters must have a 20 second time delay relay when switching from high speed to low speed e Do not start the motor more than six times per hour each low speed start and each high speed start count as one start When using a VFD Before beginning ensure that the motor is rated for Inverter Duty per NEMA MG 1 part 31 e Set the VFD solid state overload protection to 119 of motor nameplate amps and set maximum current parameter in the VFD to motor nameplate amps Ma
15. aim Find and remove the installation instruction drawings and bills of mate rial located in a plastic bag in the water collection basin This information should be kept for future reference and maintenance purposes Hoisting Fluid Cooler All MH Fluid Cooler models must use hoist clips and overhead lifting for handling assembled fluid cooler Forklifting from base of fluid cooler is not permitted The clips for the top modules are located at the fan deck level The clips for the lower modules are located at the bottom of the modules at the water collection basin A Hoisting Installation label which has hoisting dimensional information is located on the side casing near the tower centerline Remove tower from the carrier and hoist into place according to the instructions on the label MH Fluid Cooler upper and lower modules must be hoisted and set separately Do not preassemble modules prior to hoisting Z Warning Note Installation Hoisting clips are provided for ease of unloading and positioning the fluid cooler For overhead lifts or where additional safety is required safety slings should also be placed under the fluid cooler modules Under no circumstances should you combine the top and bottom modules of modular models and attempt to hoist them at the same time by utilizing the hoisting clips alone Fluid Cooler Installation These installation instructions are intended to help you prepare be fore your fluid cooler arrive
16. ain consistently optimum thermal performance capability They are available by contacting your Marley sales representative Replacement parts A complete stock of parts and components is main tained at one or more of the various Marley plants In cases of emergency they can normally be shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in ad vance thus avoiding the cost of special handling Be sure to mention your fluid cooler serial number from the fluid cooler nameplate when ordering parts Periodic maintenance You may wish to contract with SPX Cooling for regularly scheduled visits for the purpose of inspecting and reporting your fluid cooler s condition to make recommendations intended to prevent emergencies and to perform maintenance considered outside the norm This service is not intended to replace the important function performed by your maintenance staff Their attention assures the fluid coolers s routine operating performance and is invaluable However we recognize that the unusual manner in which a fluid cooler performs its function as well as the unique forces which act upon it may be considerations which oc casionally require the services of an expert technician Maintenance Schedule Maintenance Service Monthly Semi annually Seasonal Startup or Annually Insp
17. appropriately sized float valve connection located in collection water basin side wall Install the drain and overflow according to drawings shipped with your fluid cooler If you wish to pipe overflow and drain water to a remote discharge point make those connections at this time also La Note Caution A Warning Installation Fasteners and components provided by others that are to be attached to the tower must be compatible with the cooling tower materials i e fasteners in a stainless steel cold water basin must be stainless steel 6 Attach process fluid supply and return piping to the coil Field piping connection is an NPT male connection at the coil A welded connec tion requires removing the threaded portion of the coil For welded connections protect adjacent areas from excessive heat and sparks or damage may occur 7 Wire motor s and recirculation pump s in accordance with wiring diagram For maintenance safety purposes SPX Cooling Technologies recom mends alockout type disconnect switch for all mechanical equipment In addition to a disconnect switch the motor should be wired to main power supply through short circuit protection and a magnetic starter with overload protection Motor Wiring Wire motor leads as shown on the motor nameplate matching the supply voltage Do not deviate from the motor nameplate wiring Either of following symbols may be shown on the motor nameplate A AA Y or YY
18. arley supplies VFD and VFD controls specifically designed for our cooling products If you have purchased a Marley VFD and or controls package please follow the instructions in the User Manual for that system Most VFD problems can be avoided by purchasing the Marley drive system If you are installing a VFD other than the Marley drive please refer to that drives installation manual Improper use of a VFD may cause damage to equipment or personal injury Failure to correctly install the VFD drive will automatically void all warranties associated with the motor and any equipment that is either electrically or mechanically directly attached to the VFD drive system The length of this warranty avoidance will be contingent on properly installing the VFD system and repairing any damage that may have occurred during its operation SPX Cooling Technologies does not assume responsibility for any technical support or damages for problems associate with non Marley brand VFD systems Changing the operational fan speed from the factory settings could cause the fan to operate in an unstable region which may result in damage to the equipment and possible injury Z Warning Z Warning Z Warning Installation Mechanical Equipment The fluid cooler is designed to operate at full speed and half speed Warranty is void if the tower is operated at speeds which cause damaging vibrations to the tower and associated equipment When utilizing a variab
19. ause slipping Never apply belt dress ing as this will damage the belt and cause early failure A Dodge V Belt Tension Tester is an alternate method for tensioning V belts Check with you local belt supplier STRAIGHT EDGE Sheave Alignment e The motor sheave is to be positioned as close as possible to the motor in order to minimize stress on the motor bushings e The motor and fan sheaves may have grooves that are not used The bottom surface of the motor and fan sheaves must be aligned within Ya of each other and level within 12 6 12 in order to not adversely affect belt and sheave life Alignment can be achieved by placing a straight edge across the sheaves making sure that it is level and measuring down to the bot tom surface of both sheaves at four points The belt is to be located in the grooves closest to the motor center line Bushing Fastener Torque Values A Warning Z Warning Maintenance Bushing Fastener Torque ft lb SH Va 20 6 SDS Va 20 6 SD Va 20 6 SK e 18 13 SF 16 22 E 7 13 35 V6 12 65 Fluid Cooler Maintenance Some maintenance procedures may require maintenance personnel to enter the fluid cooler Each cased face of the fluid cooler has a door for access to the interior of the tower The optional fan deck ladder models MHF706 and MHF707 is de signed and intended solely for personnel to gain access to the fan deck
20. copies of these reports at no charge or you can download copies from our website at spxcooling com For complete parts and service assistance contact the Marley sales representative in your area If you need help locating your representative please phone 800 462 7539 or check the internet at spxcooling com SP COOLING TECHNOLOGIES 7401 WEST 129 STREET OVERLAND PARK KANSAS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Technologies Inc Printed in USA Manual 05 116E
21. d Check for proper operation of temp low water level sensor x Inspect clean buildup of contaminant from sensor x x Structure Inspect tighten all fasteners x x Inspect and touch up all metal surfaces x R Refer to Component User Manual Note It is recommended at least weekly that the general operation and condition be observed to any changes in sound or vibration that may signify a need for closer inspection Pay attention 31 Troubleshooting Trouble Cause Remedy Motor will not start Power not available at motor terminals Check power at starter Correct any bad connections between the control apparatus and the motor Check starter contacts and control circuit Reset overloads close contacts reset tripped switches or replace failed control switches If power is not on all leads at starter make sure overload and short circuit devices are in proper condition Wrong connections Check motor and control connections against wiring diagrams Low voltage Check nameplate voltage against power supply Check voltage at motor terminals Open circuit in motor winding Check stator windings for open circuits Motor or fan drive stuck Disconnect motor from load and check motor and fan drive for cause of problem Rotor defective Look for broken bars or rings Unusual motor noise Motor running single phase Check motor and attempt to star
22. e fan shaft bearings at close of each operating season see page 26 Electric motors Clean and lubricate motor at close of each operating season refer to motor manufacturer s recommendations Check motor anchor bolts and tighten as required See Page 28 for fluid coolers with motor located outside the plenum option Do not start motor before determining that there will be no interfer ence with free rotation of the fan drive The motor s should be operated for three hours at least once a month This serves to dry out windings and re lubricate bearing surfaces refer to the Marley Electric Motor User Manual Manual 92 1475 available at spxcooling com At start of new operating season make sure bearings are adequately lubricated before returning motor to service Prolonged Shutdown If shutdown period is longer than seasonal contact your Marley sales representative for additional information 29 30 Maintenance SPX Cooling Technologies Services Our interest in your MH Fluid Cooler does not end with the sale Having conceived designed and manufactured the most reliable and longest lasting fluid cooler of its class we want to make sure that you gain the maximum possible benefit from its purchase Therefore the following services are available which are intended to as sure the maximum possible service life under your operating conditions tailor the operating characteristics to your specific needs and maint
23. e is recommended Semi Annually If equipped check the belt tension and condition If equipped with dampers lubricate jack shaft bearings and tiebar linkage with silicone lubricant If dampers are equipped with pneumatic or electric actuators the manufacturer s recommended maintenance procedures should be observed If dampers are exposed to heavy dust laden air oc casional flushing of the bearings with water is recommended Clean and disinfect cooling tower with biocides Systems with biofouling high general bacterial counts or positive cultures of legionella may require Note Maintenance additional cleaning Refer to Fluid Cooler Cleaning section page 21 Consult your water treatment expert as to prudent biological evaluation testing Geareducer models used on MH Fluid Coolers are designed for 5 year oil change intervals To maintain five year change intervals use only oil designed specifically for these Geareducers If after five years turbine type mineral oil is used the oil must be changed semiannu ally Refer to the Geareducer User Manual for oil recommendations and further instructions Annually Relubricate motor s according to the manufacturer s instruc tions See instructions on the next page for towers with the motor located outside the plenum option Check to see that all bolts are tight in the fan and mechanical equipment region including the fan cylinder and fan guard Refer to Component User Ma
24. ect General Condition and Operation x x Observe Operation of Mechanical motor fan and drive mechanism x x Makeup valve if equipped x x Inspect for unusual noise or vibration x x Inspect and Clean Air inlet x x PVC drift eliminators x x Distribution basin nozzles and collection basin x x Fan and pump motor exterior x x Coil surface x Check Collection water basin level x x Blowdown adjust as required x x Geareducer Drive if equipped Check for loose fasteners including oil drain plug x Check oil level check for repair oil leaks x x Change oil R Make sure vent is open x x Check driveshaft or coupling alignment x Check for loose driveshaft or coupling fasteners x Check driveshaft or coupling bushings or flex element for unusual wear x x Lube lines if equipped Check for oil leaks in hoses or fittings x R x Belt drive if equipped Fan shaft bearing lubrication every 3 mo every 3 months every 3 months Check and tighten support fasteners x Check shaft sheave and belt alignment x Check belt tension and condition x x Check sheave bushing fastener torque x Fan Check and tighten blade and hub fasteners x Check fan blade pitch and tip clearance x Check fan cylinder for loose fasteners x Motor Lubricate grease as required R Check mounting bolts for tightness x Operate at least 3 hours a month 3 hours a month 3 hours a month Basin Heater if equippe
25. ft couplings to be sure that the motor and Geareducer are properly aligned If necessary cor rect the alignment in accordance with the included manual For belt drive equipped models observe the action of the sheaves and belts to be sure that the motor is properly aligned with the fan sheave See Belt Tensioning and Sheave Alignment on pages 22 thru 24 11 Note A Caution Note 12 Installation It is essential that the fan cylinder and fan guard be installed in ac cordance with the drawings shipped with the tower Do not force the fan cylinder out of round 4 Momentarily bump energize the motor s and observe rotation of the fan s If rotation is backwards shut off the fan and reverse two of the three primary leads supplying power to the motor If tower is equipped with a two speed motor check for proper rota tion at both speeds Check also to see that starter is equipped with a 20 second time delay which prevents direct switching from high speed to low speed If the fan is intended to be reversed for deicing purposes make sure that the starter is equipped with a 2 minute time delay between changes of direction These delays will prevent abnormal stress from being applied to the mechanical equipment and the electrical circuit components 5 Run the motor and observe the operation of the mechanical equip ment Operation should be stable and if equipped there should be no evidence of oil leakage from the Gea
26. galvanized steel therefore your water treatment program must be compatible with zinc In working with your water treatment supplier it is important that you recognize the potential effects on zinc of the specific treatment program you choose A Warning Maintenance Fluid Cooler Cleaning Any evaporative type fluid cooler must be thoroughly cleaned on a regular basis to minimize the growth of bacteria including Legionella Pneumophila to avoid the risk of sickness or death Service personnel must wear proper personal protective equipment during decontami nation Do NOT attempt any service unless the fan motor is locked out Operators of evaporative cooling equipment such as closed circuit cool ing towers should follow maintenance programs which will reduce to an absolute minimum the opportunity for bacteriological contamination Public Health Service officials have recommended that good housekeeping procedures be followed such as regular inspections for concentrations of dirt scale and algae periodic flushing and cleaning and the following of a complete water treatment program including biocidal treatment The visual inspection should take place at least once a week during the operating season The periodic flushing and cleaning should be done before and after each cooling season but in any event at least twice a year The louvers drift eliminators easily accessible fill surfaces and the coil should be flushed by use
27. ill not slip under peak load conditions Check tension frequently during the first 24 48 hours of run in operation Overtensioning shortens belt and bearing life Keep belts free from foreign material which may cause slipping Never apply belt dressing as this will damage the belt and cause early failure A Dodge V Belt Tension Tester is an alternate method for tensioning V belts Check with you local belt supplier Figure 1 Figure 2 Maintenance LOOSEN HARDWARE JACKING SCREWS SINGLE MOTOR TWO FANS See Figure 3 for MH Fluid Cooler models MHF706 and MHF707 The belts are adjusted by turning the threaded rod Before tightening or loosening the belt the double nuts holding the motor support in place must be loosened There are two jam nuts at the end of the rod next to the casing Turn the nut closest to the end of the rod to tighten the belt Turn the other nut to loosen the belt After achieving proper tension tighten the double nuts located on the fan side of the motor support against the motor support to maintain belt tension then retighten the motor support nuts Ideal ten 4 JACKING SCREWS SINGLE MOTOR SINGLE FAN 23 Figure 3 24 Maintenance sion is the lowest tension at which the belt will not slip under peak load conditions Check tension frequently during the first 24 48 hours of run in operation Overtensioning shortens belt and bearing life Keep belts free from foreign material which may c
28. le frequency drive the tower must be tested across the full range of speeds and checked against CTI guidelines for ex cessive vibration Speed ranges not meeting these guidelines must be locked out in the VFD Always shut off electrical power to the tower fan motor prior to performing any maintenance on the tower Any electrical switches should be locked out and tagged out to prevent others from turning the power back on 1 If equipped check oil level in accordance with the Geareducer User Manual for the Geareducer Although the Geareducer was filled to the proper level at the factory tipping during shipment and hoisting may have caused some loss of oil If oil is required fill Geareducer to the proper level with approved lubricant See Geareducer User Manual Check oil level at the Geareducer or dipstick standpipe located on fan deck if so equipped to confirm that the proper level is indicated 2 On double flow models MHF706 and MHF707 install fan cylinder and two piece fan guard according to the installation drawing shipped with the fluid cooler Improper installation of the fan cylinder and fan guard will destroy the structuralintegrity ofthe fan guard Failure of the fan guard couldallow operating or maintenance personnel to fall into the rotating fan 3 Spin the fan s manually to assure that all fan blades properly clear the inside of the fan cylinder If equipped observe the ac tion of the coupling or drive sha
29. ng water with a pH between 6 5 and 8 a chloride content as NaCl below 500 ppm a sulfate content SO4 below 250 ppm total al kalinity as CaCO below 500 ppm calcium hardness as CaCO above 50 ppm no significant contamination with unusual chemicals or foreign substances and adequate water treatment to minimize scaling e Startup Conditions The water conditions during initial fluid cooler op eration are crucial in preventing premature corrosion of galvanized steel white rust For at least the first eight weeks of operation pH should be controlled between 6 5 and 8 0 with hardness and alkalinity levels between 100 and 300 ppm expressed as CaCO Chlorine if used shall be added intermittently with a free residual not to exceed 1 ppm maintained for short periods Excessive chlorine levels may deteriorate sealants and other materials of construction An atmosphere surrounding the tower no worse than moderate indus trial where rainfall and fog are no more than slightly acid and they do not contain significant chlorides or hydrogen sulfide H2S Many proprietary chemicals exist for control of scale corrosion and biological growth and should be used prudently Also combinations of chemicals may cause reactions which reduce treatment effective ness and certain chemicals such as surfactants biodispersants and antifoams may increase drift rate The structure and coil of your fluid cooler consists primarily of
30. nt the water in the cold water basin and all exposed pipework from freezing Several methods are used to combat this including automatic basin heater systems and pump freeze protection systems available from Marley Basin heaters systems will not prevent the coil from freezing Unless some means of freeze prevention is incorporated into your system the tower basin and exposed pipework should be drained at the beginning of each wintertime shutdown period If tower basin is drained verify that all basin heaters have been shut off either by automatic cutoff or disconnect switch Protection Against Coil Freezing Ethylene and propylene glycol solutions are the best means to protect the coil from freezing The following table provides the coil volume for each MH Fluid Cooler model MHF706 and MHF707 coil volumes are for both coils added together Caution Operation Model Coil Volume Model Coil Volume US Gallons US Gallons MHF702_ 061 65 MHF705__061 235 MHF702_ 081 85 MHF705__081 315 MHF702 101 105 MHF705 101 390 MHF702 121 125 MHF705 121 465 MHF702 062 75 MHF705 062 285 MHF702 082 100 MHF705 082 380 MHF702 102 120 MHF705 102 470 MHF702 122 150 MHF705 122 565 MHF703 061 85 MHF706 061 390 MHF703 081 115 MHF706 081 500 MHF703 101 140 MHF706 101 610 MHF703 121 170 MHF706 121 725 MHF703 062 100 MHF706 062 475 MHF703 082 130 MHF706 082 610 MHF703 102
31. nuals for torque values Inspect the fluid cooler thoroughly making maximum use of instructions given in the separate user manuals Check structural bolted connections and tighten as required Make preventive maintenance repairs as neces sary Check to see that all bolts are tight in the fan and mechanical equipment region including the fan cylinder and fan guard Refer to Component User Manuals for torque values Every 5 Years If equipped change Geareducer oil Refer to the Geareducer User Manual for instructions Motor Relubrication Instructions Motor located outside plenum option Double flow models MHF706 and MHF707 only Open and lock out disconnect switch to make certain motor cannot be started 1 Remove guard as shown in Figure 4 Opposite end motor bearing is accessible from outside the tower 2 Remove grease fill and relief plugs at both shaft extension end and op posite end bearings and remove hardened grease using clean wire 27 Figure 4 Caution 28 Maintenance Steel Side Casing Guard Grease Relief Plug 3 Insert grease fittings in grease fill openings and add grease until grease is forced out through relief openings 4 Replace fill plugs and operate mechanical equipment 30 minutes to one hour to purge excess grease at grease relief opening Reinstall grease relief plugs and reinstall guard Resume normal fluid cooler operation Seasonal Shutdown Instructions When
32. of a moderate pressure water nozzle being careful not to cause physical damage A reliable water treatment program should be installed and maintained Filtration devices may be employed to reduce the suspended solids concentrations thus increasing the ef fectiveness of the water treatment program See Fluid Cooler Startup instructions on page 13 Blowdown A fluid cooler cools water by continuously causing a portion of it to evaporate Although the water lost by evaporation is replenished by the makeup system it exits the tower as pure water leaving behind its burden of dissolved solids to concentrate in the remaining water Given no means of control this increasing concentration of contaminants can reach a very high level In order to achieve water quality which is acceptable to the fluid cooler the selected water treatment company must work from a relatively constant level of concentrations This stabilization of contaminant concentrations is usually accomplished by blowdown which is the constant discharge of a portion of the circulating water to waste As a rule acceptable levels on which to base a treatment schedule will be in the range of 2 4 con centrations The following table shows the minimum amount of blowdown ML 2 21 Note 22 Maintenance percent of flow required to maintain different concentrations with various cooling ranges Number of Concentrations 1 5X 2 5X 3 0X 4 0X 5 F 2 78 C 78 38
33. re control When the process fluid temperature becomes too cold switching the fan to half speed will cause the cold process fluid temperature to rise stabilizing at a temperature a few degrees higher than before With a further reduction in fluid temperature the fan may be cycled alternately from half speed to off subject to the same constraint of 30 seconds of allowable acceleration time per hour as outlined above For greater insight on process fluid temperature control please read Cooling Tower Energy and its Management Technical Report H 001 A available at spxcooling com Wintertime Operation The Marley film fill system used in the MH Fluid Cooler has air entrance louvers that are molded as an integral part of the fill This feature makes these fluid coolers very forgiving of cold weather operation even atthe low temperature and reduced load conditions encountered in low temperature applications Nevertheless during operation in subfreezing weatherthe op portunity exists for ice to form in the colder regions of the fluid cooler Note A Caution Operation Slushy transitory ice forms routinely in the colder regions of the fill of low temperature towers and is visible through the tower louvers Such ice normally has no adverse effect on fluid cooler operation but its appearance should be a signal to the operator to undertake ice control procedures It is the operator s responsibility to prevent the formation of
34. red reason to shut down the fluid cooler until the problem can be located and corrected Observe operation of the motor coupling or drive shaft Geareducer if equipped and fan Become familiar with the normal operating temperature of the motor s as well as the sight and sound of all components as a whole If equipped check Geareducer oil level Shut down the unit and allow 5 minutes for the oil level to stabilize Add oil if required Check for Geareducer oil leaks Check the Geareducer as well as any optional oil lines to external oil dipstick sight glass Inspect louvers drift eliminators and basin trash screens and remove any debris or scale which may have accumulated Replace any damaged or worn out components Use of high pressure water may damage the eliminator and louver material Observe operation of the float valve Depress the operating lever to make sure that the valve is operating freely Inspect the suction screen for plug ging Remove any debris that may have accumulated Check for any buildup of silt on the floor of the collection basin Mentally make note of the amount if any so future inspections will enable you to determine the rate at which it is forming Every 3 months If equipped lubricate fan shaft bearings While rotating equipment by hand grease the bearings until a bead forms around the seals a maximum charge of 0 30 ounces MHF702 MHF704 and 1 4 ounces MHF706 MHF707 is recommended Mobil SHC 460 greas
35. reducer 6 If equipped with belt drive check the torque on the fan and motor sheave after 10 60 hrs of operation See Bushing Fastener Torque Values on page 25 If the water supply system is not being operated or if there is no heat load on the system motor amps read at this time may indicate an apparent overload of as much as 10 20 This is because of the increased density of unheated air flowing through the fan Determi nation of an accurate motor load should await the application of the design heat load Z Warning Operation Fluid Cooler Start Up Among othersources outbreaks of Legionnaires Disease have report edly been traced to cooling towers and fluid coolers Maintenance and water treatment procedures that prevent amplification and dissemina tion of Legionella and other airborne bacteria should be formulated and implemented BEFORE systems are operated and continued regularly thereafter to avoid the risk of sickness or death Water System 1 New installations should be cleaned and treated with biocides by a water treatment expert before startup Remove any and all accumulated debris from fluid cooler Pay par ticular attention to inside areas of collection water basin distribution water basins louvers and drift eliminators Make sure that cold water suction screens are clear and properly installed Fill the water system to an approximate depth of 8 203 mm in the depressed area of the collection
36. ressed Several options are available that may assist you in addressing some of these personnel safety concerns including e Louver face distribution basin access platform with ladder and handrail e Louver face redistribution basin level access platform with ladder and handrail e A handrail system around the perimeter of the fan deck with either one or two ladders for access to the deck Double flow models MHF706 and MHF707 only e Extended fan deck that provides additonal access around one end of the fan cylinder opposite the fan deck access ladder Double flow models MHF706 and MHF707 only e Ladder extensions used where the base of the tower is elevated e Safety cages for ladders e External lube lines e Access door platform e Motor located outside the tower Double flow models MHF706 and MHF707 with Geareducer drive only e External motor access platform Double flow models MHF706 and MHF707 with Geareducer drive only e Plenum walkway Double flow models MHF706 and MHF707 only Standard on all other models Mechanical equipment access platform Fluid Cooler Location Space available around the fluid cooler should be as generous as possible to promote ease of maintenance and to permit freedom of airflow into and through the fluid cooler If you have questions about the adequacy of the available space and the intended configuration of the fluid cooler please contact your Marley sales representative for g
37. rs and reduce the ice buildup 3 Under extended extreme cold conditions it may be necessary to op erate the fan in reverse This forces warm air out through the louvers melting any accumulated ice adequate heat load must be available 17 A Warning A Warning Caution Z Warning 18 Operation Reversal may be at either full or half soeed however reversal at half speed is recommended Reverse operation of the fan should be used sparingly and should only be used to control ice not to prevent it Reverse fan operation should not need to exceed 1 or 2 minutes Monitor ing is required to determine the time required to melt accumulated ice Reverse operation of fans for prolonged periods during subfreezing weather can cause severe damage to fans and fan cylinders Ice can accumulate inside fan cylinders at fan blade plane of rotation and fan blade tips will eventually strike this ring of ice damaging the fan blades or cylinder Ice can also accumulate on fan blades and be thrown off damaging fan cylinder or blades Allow a minimum of 10 minute delay between reverse operation and forward operation during subfreezing weather to permit ice to dissipate from fan blades and fan cylinders See Fan Drive Caution note on page 12 for fan speed change and reversing precautions Intermittent Wintertime Operation If periods of shutdown nights weekends etc occur during freezing weather measures must be taken to preve
38. s If discrepancies exist between these instructions and those shipped with the fluid cooler the instructions shipped with the fluid cooler will govern 1 Prior to placement of the fluid cooler confirm that the supporting platform is level and that the anchor bolt holes are correctly located in accordance with Marley drawings 2 Place bottom module on your prepared supports aligning anchor bolt holes with those in your supporting steel Make surethatthe orientation agrees with your intended piping arrangement Attach fluid cooler to supporting steel with 3 4 diameter bolts and flat washers by others See support drawing for location and quantity Position flat washers between the bolt head and the fluid cooler basin flange 3 Before setting top module in place on bottom module clean any debris from the underside of the top module fill skid and beams and from the top of the bottom module and remove shipping cover from bottom of top module replace fasteners at side of module to pre vent leaks Place top module on the top peripheral bearing surface factory installed gasket of bottom module aligning mating holes as itis set in place Attach top module to bottom module with fasteners provided according to drawings shipped with your fluid cooler 4 Connect the recirculation piping with rubber boot shipped with the bottom module piping according to drawings shipped with you fluid cooler 5 Attach makeup water supply piping to
39. s are used throughout this manual to bring at tention to the presence of hazards of various risk levels or to important information concerning the life of the product Indicates presence of a hazard which can cause severe personal injury death or substantial property damage if ignored Indicates presence of a hazard which will or can cause personal injury or property damage if ignored Indicates special instructions on installation operation or maintenance which are important but not related to personal injury hazards A Warning Preparation The Marley MH Fluid Cooler with CoolBoost purchased for this instal lation represents the current state of the art in crossflow induced draft fluid cooler design Thermally and operationally it is the most efficient fluid cooler of its class These instructions as well as those offered separately on motors fans Geareducer couplings drive shafts float valves pumps etc are in tended to assure that the fluid cooler serves you properly for the maximum possible time Since product warrantability may well depend upon your actions please read these instructions thoroughly prior to operation If you have questions about the operation and or maintenance of this product and you don t find the answers in this manual please contact your Marley sales representative When writing for information or when ordering parts please mention product serial number shown on the name plate
40. t it Motor will not start if single phased Check wiring controls and motor Motor leads connected incorrectly Bad bearings Check motor connections against wiring diagram on motor Check lubrication Replace bad bearings Electrical unbalance Check voltages and currents of all three lines Correct if required Air gap not uniform Check and correct bracket fits or bearing Rotor unbalance Rebalance Cooling fan hitting end belt guard Reinstall or replace fan Motor runs hot Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan User Manual Check for drag in fan drivetrain as from damaged bearings Wrong motor RPM Check nameplate against power supply Check RPM of motor and drive ratio Bearing overgreased Remove bearing reliefs Run motor up to speed to purge excessive grease Wrong lubricant in bearings Change to proper lubricant See motor manufacturer s instructions One phase open Stop motor and attempt to start it Motor will not stat if single phased Check wiring controls and motor Poor ventilation Clean motor and check ventilation openings Allow ample ventilation around motor Winding fault Check with ohmmeter Bent motor shaft Insufficient grease Straighten or replace shaft Remove plugs and regrease bearings Too frequen
41. t starting or speed changes Limit cumulative accelerations time to a total of 30 seconds hour Set on off or speed change set points farther apart Consider installing a Marley VFD arive for fine temperature control Deterioration of grease or foreign material in grease Flush bearings and relubricate Bearings damaged Replace bearings Motor does not come up to speed Voltage too low at motor terminals because of line drop Check transformer and setting of taps Use higher voltage on transformer terminals or reduce loads Increase wire size or reduce inertia Broken rotor bars Look for cracks near the rings A new rotor may be required Have motor service person check motor Wrong motor rotation Wrong sequence of phases Switch any two of the three motor leads 32 Troubleshooting Trouble Cause Remedy Geareducer noise If equipped Unusual fan drive vibration Geareducer bearings If new see if noise disappears after one week of operation Drain flush and refill Geareducer oil See Geareducer User Manual If still noisy replace Gears Loose bolts and cap screws Correct tooth engagement Replace badly worn gears Replace gears with broken or damaged teeth Tighten all bolts and cap screws on all mechanical equipment and supports Unbalanced drive shaft or worn couplings If equipped Make sure motor and Geareducer shafts are in proper alignment and
42. tions also cause an increase in the incoming hot process fluid temperature and thermal range Under no circumstances should the recirculation water pump s be Note cycled to control process fluid temperature It is recommenced that while process fluid is being circulated through the coil the fluid cooler recirculation water system always be in operation 4 15 Caution 16 Operation 4 Airflow rate Reducing air flow through the fluid cooler causes the cold process fluid temperature to rise This is the recommended method by which to control leaving process fluid temperature If your fluid cooler is equipped with a single speed motor the motor may be shut off when the process fluid temperature becomes too cold This will cause the process fluid temperature to rise When the fluid temperature then becomes too warm for your process the motor can be restarted When operating in this mode care must be taken not to exceed a total fan acceleration time of 30 seconds per hour Fan cycling limits From a dead stop determine the number of sec onds it takes the fan to arrive at full speed Divide this number into 30 to determine the allowable number of starts per hour Considering the normal fan and motor sizes utilized on MH Fluid Coolers anticipate that approximately 4 to 5 starts per hour are allowable If your fluid cooler is equipped with a two speed motor s you will enjoy greater opportunity for process temperatu
43. uidance Prepare a stable level support foundation for the fluid cooler utilizing weight wind load and dimensional information appearing on appropri ate Marley submittal drawings Supports must be level to insure proper operation of the fluid cooler 4 A Warning A Caution Installation The fluid cooler must be located at such distance and direction to avoid the possibility of contaminated fluid cooler discharge air be ing drawn into building fresh air intake ducts The purchaser should obtain the services of a Licensed Professional Engineer or Registered Architect to certify that the location of the fluid cooler is in compli ance with applicable air pollution fire and clean air codes Fluid Cooler Shipment Unless otherwise specified the MH Fluid Cooler ships by truck on flat bed trailers which lets you receive hoist and install the tower in one continuous operation Single cell single flow fluid coolers ship on one truck Double flow and multicell fluid coolers depending on their size may require more than one truck Responsibility for the condition of the fluid cooler upon its arrival belongs to the trucker as does the coordination of multiple shipments if required Receiving Fluid Cooler Prior to unloading the fluid cooler from the delivering carrier inspect the shipment for evidence of damage in transit If damage is apparent note the freight bill accordingly This will support your future recovery cl
44. ximum current parameter will reduce fan speed and limit amp draw to nameplate amps during cold weather operation If furnished with a mechanical O L set this at 11096 over motor nameplate amps e Motor rotation must be the same in both VFD mode and By pass mode e f cable distance between the VFD and motor is greater than 100 feet a DV DT output filter is recommended to avoid damage to the motor 100 feet distance is based on our field experience the VFD manufacture may state different distances and distance does vary depending on the VFD manufacture e Program the VFD for variable torque output Flux vector and con stant torque modes may damage the gearbox Donotstart and stop the motor using the safety switch at the motor If the drive is being commanded to run and the load side is cycled ON and OFF with the safety switch this may damage the VFD Using a VFD in cooling applications has advantages over traditional single or two speed motor control A VFD can reduce the cost of electrical en ergy being used and provide better temperature control In addition it reduces the mechanical and electrical stress on the motor and mechanical LL 2 Z Warning Z Warning 10 Installation equipment Electrical savings can be large during periods of low ambient temperature when the cooling requirement can be satisfied at reduced speeds To benefit from these advantages it is important that the drive be installed correctly M

Download Pdf Manuals

image

Related Search

Related Contents

Fender Power Stage 100 Computer Monitor User Manual  (nvr) pc-based 16-32 canaux art. ipnvr016a – ipnvr032a  Technical Publication Direction 2300000 Revision 0 GE Medical  iP3600 series Manuel en ligne  Installation Manual Installation Manual  Flash CS3  Quelques titres qui ont marqué le Xxème  Product User Manual  USER Manual  Elite EHB-1000R Use and Care Manual  

Copyright © All rights reserved.
Failed to retrieve file