Home
        Soleus Air KFR/KFS Series User's Manual
         Contents
1.                                 E 28  Troubleshootihg ep  E 29 30    Warran  Vy uu u ems 31    Safety precautions    Use 230V 60Hz or 115V 60Hz  power supply only         Do not turn off the power supply cir    Keep the power supply circuit breaker   Depending on the electrical specifi   cuit breaker or pull out the unit power   and power plug free from any type of   cations of your unit  use only 230V   cord during unit operation  This may   debris  If using a power supply cord  be   60Hz or 115V 60Hz power supply   cause electrical hazards and  or a fire    sure to connect to plug firmly  This will   Failure to do so may result in electri   minimize the risk for electrical shock or   cal problems or hazards   any other type of electrical hazard           Power supply wires must be located   Never insert any type of object into  Be sure that the indoor and outdoor   in areas where they will not be dam    the outdoor unit fan  Because the fan   units are not in operation when discon    aged or cut  rotates at a high speed  this may   necting the power supply to the unit   cause injury        Any type of repairs or maintenance   Be sure that your hands are not wet   Be sure that the outdoor unit is free  done to the units must be done by a   when touching any of the operation   and clear of any debris around the out   professionally licensed contractor    buttons on the indoor unit  side of the unit  Do not place or lean  Any unqualified person should not at  any items on the 
2.              2      N i NOTE            is      low pressure           B is the high pressure valve  B A ini i       and D        the joints of connecting pipes    Vu le of indoor unit   Checking ponts VHS  hr   of outdoor uat                       dM  s JL  Cornscinc pipe nut                      pa   s h E            ci  The outdoor unit is supplied with a R 22 charge sufficient for 15 feet of refrigeration tubing  zur     2542    The outdoor unit s liquid and suction valves are closed to contain the charge within the Valve body t  0  unit  The recommended procedures for charge adjustments are as follows  EE  m  Additional Charge Needed for Refrigeration lines over 15 feet  Liquid Line O D   Inches  Additional R 22  oz   ft     Hi rod    6 nie   1  After connecting the refrigeration tubing to the indoor and outdoor units  connect a    RATT  vacuum pump to the refrigeration valve service ports  Lcw prassura valve       2  Evacuate through the liquid and suction valve service ports to 500 microns or less for a minimum of 30 minutes  Close  the valves to the pump and monitor the vacuum for 15 minutes  The vacuum should not rise above 800 microns     3  Ifa vacuum of 500 microns cannot be obtained  or if it rises ablve 800 microns over the 15 minute period  discontinue  evacuation  pressurize the system with nitrogen and look for leaks  Repair any leaks that are found and repeat step 2    4  Close the valves to the vacuum pump  turn the pump off  and disconnect it from the refr
3.        YEL                    26         Electrical schematic diagram    Were S WE NIA   THR CONDENSTN  BH      SUPPLY  ELECTRICAL SCHEMATIC DIAGRAM OF THE CONDENSING UNIT             UUTDOUR        MUTOR    TN    1                      CAPACITOR    REVERSING VALVE  CAPACITOR                    SUPPLY  208 200 602                 moram          WARNING      USE COPPER WIRES ONLY FOR POWER SUPPLY       WARNING RISK OF ELECTRIC SHOCK CAN CAUSE INJURY OR DEATH   DISCONNECT ALL ELECTRIC POWER SUPPLIES BEFORE SERVICING       DURING CONNECTION OF THE REFRIGERATION TUBES  IF EXCESSIVE  TORQUE IS IMPOSED ON FLARE NUTS  SERVICE VALVE ON DISCHARGE  LINE MAY BE DAMAGED  WHEN TIGHTENING FLARE NUTS OR NARROW  PIPE  TORQUE SHOULD BE ADJUSTED BETWEEN 13 7 18 6N M   140 190GF CM        DONOT PUTINDOOR UNIT IN LOCATIONS WHERE IT MAY GET WET       ELECTRICAL INSTALLATION MUST BE IN ACCORDANCE WITH LOCAL AND  NATIONAL ELECTRICAL CODES       THE INSTALLATION OF THESE UNITS REQUIRES QUALIFIED PERSONNEL     CERTIFIED APPROVED  POWER SUPPLY CONDUCTORS MUST BE USED    B AN INDEPENDENT BRANCH CIRCUIT BREAKER MUST BE USED       MAXIMUM INTER CONNECTING WIRE LENGTH SHOULD NOT EXCEED  11 3M  37FT        REFRIGERATING PIPE LENGTH MUST BE LIMITED BETWEEN 4 10M   13FT 33FT   IF THE LENGTH EXCEEDS 7 62M 25FT    THE COOLING   OR HEATING  CAPACITY MAY BECOME IMPAIRED       DIFFERENCE IN HEIGHT BETWEEN INDOOR AND OUTDOOR UNIT SHOULD  NOT EXCEED 7M 26              28      Troubleshooting    If after checking th
4.      frorn indoor unit during  COOLING  or  DRY   operalion                  29        Troubleshooting           Open circuit or short circuit of room  1 time Abnormality of room temperature temperature sensor   sensor      e Incorrect connection of the sensor         Open circuit or short circuit of defrost  2 times Abnormality of defrost sensor  sensor   e Incorrect connection of the sensor       e Indoor fan motor is defective   3 times Abnormality of indoor fan motor   e Bad connection to motor   e Compressor is defective   4 times Abnormality of outdoor unit  e Refrigerant is low  e Capacitor is defective     Continuous No defect unit in defrost mode   blink         30      
5.   Be sure to stop unit operation before  replacing batteries        How to use remote control                      raving sigral    Signal sent symbol 2   will flash    for a short time when signal is sent     The range that Ihe signal can reach  is about 23 feet when pointing at the  front of the indoor unit     Be sure that remote control receiver  on the indoor unit is not obstructed  in any way  This will ensure that     proper signal can be received from  the remote control     The remote control should not be    exposed to any direct sunlight  This  can lead to altering of set programming    and or permanent damage to the remote  control           Operation modes    Operation instructions    Operation modes _            Selecting mode       Each time the MODE button is pressed  the operation made  is changed in the following sequence    HEATING         COOLING      gt  DRy     FAN      Y     I FEEL                     I FEEL  mode s described on page    0     Wher operating     fan only          the campressor wil        operate                  mode       Each time the  FAN  button is pressed  the fan speed is  changed in sequence                          MED     LO     J              On FAN ONLY made  only  HU  MED  and    LO           available     While un  DRY mode  sirflow is set by air conditicner automatically    FAN  button is ineffective in this case        Setting temperature        lt 2  Press once tc lower temperature by 1 F       HI  POWER     a gt  Press 
6.   e Remove plate and drill marked hole at a depth of 1 75 inches  moles te            of Your mounting          Faye diferent  from    the one above  but installation method is simllar     e Insert the screw plugs into the holes and affix the mounting plate using the tapping screws     e Once mounting plate is securely fastened to the wall  then locate an area on the wall for the access hole for the refrigeration  line condensate line wiring bundle          2  Access hole for refrigeration lines condensate drain line wiring bundle        These directions must be followed at least for the condensate drain line  There must  be rear access for the condensate drain line to drain properly from the unit        Decide on a location for the access hole according to the location of the unit       Drill an approximately 2 5 inch hole  making sure that there is a tilt downward of a 1 4  inch  This will ensure that proper drainage is maintained for the condedsate drain line      If you are not using rear access for the refrigeration lines and wiring  hole will does  not need to be as large      e  tis recommended that a wall sleeve of some sort  i e  PVC pipe  be used to keep the hole neat and tidy     all hole                          polythene               in   dil outward         17            Installation instructions      3  Indoor unit refrigeration line installation  e The refrigeration lines and wiring can be routed to the outdoor unit in a number of ways  left or right from the
7.  Affix the screw underneath the unit to the mounting plated after completed with installation     Suppport plate       Connection of condensate drain extension line     Place glue on the end of the drain line extension end   e Fully insert the end of the drain line to the extension line  Make sure it is properly inserted to no less than 3 8 of an inch so that water    does not leak from the hose  Gluc     lt  3 8 inch    4                       LI          U N                  Drain hose            Extension drain hose            20         Installation instructions                 FLARE       FLARED TUBE    7    FIGURE  CFTTUMG COPPER      ceo     9 4                            CORRECT WRONG WRONG        2            Outdoor unit installation    1  Install the outdoor unit  e Outdoor unit must be mounted on a solid  level foundation  If possible  affix unit using bolts to the foundation     e  f installing on a wall or structure  be sure that construction of the wall or structure can support the weight of the unit and  that consideration is given to the integrity of the construction  Since the unit can vibrate during operation  movement of  sound of the unit should be considered when installing the unit     e Since the unit discharges air during operation  plants or other obstruction should be free and clear of the unit to ensure  proper operation     e Owners should advised to avoid lawn mowers or other machinery discharge toward the unit  as debris can damage the  finned c
8.  back of the  unit   by using the cut out access pieces on the casing of the unit   e Bend the refrigeration lines carefully to the required positon in order to be aligned with the drilled hole   piping direction              ac  y  T    ouou  access      i    Saw the cut out access off When installing the refrigeration lines at the directions 1  2 or 4   along the side of the casing saw the corresponding cut out piece off the indoor unit casing     j 2    x                e After connecting refrigeraton lines  see directions below   install the condensate drain line  see page21 24fordetailed  instructions on connecting condensate drain line   Then connect all wiring  see pages 2 5 27 for detailed instructions on  wiring   After all connections are made  bundle the refrigeration lines  wiring  and condensate drain line together using a  thermal insulation and vinyl duct tape          wrapped with vinyl      duct type    Refrigeration lines insulation        e Itis important that both the liquid and suction  refrigeration lines areindividually insulated to ensure  that they do no sweat and also to maintain proper unit             capacities  This is necessary since the refrigeration is large pipe        Tapa   metered from the outdoor unit and will produce condensation on both refrigeration    gt            lines if not proper insulated  power cord i  Refrigeration lines Condensate drain line wiring bundle thermal insulation  srnal  e Place the condensate drain line under the 
9.  can set the timer on with the                  button when  you      out in the morning to achieve a comfortable room temperature for when you  get home  You can also set the timer      at night to enjoy a more comfortable sleep        Timer setting    Set the switch on Set the switch off timer  timer when the during operation  appliance is off                        passes  LCD displays the remained time   The previous set time is stored and the next set time begins with the previcusly sel one     On  timer and off timer cannot be set at the same time   The room may not reach your desired temperature within the prasel tima because oF  differant sizes of rooms and or climatic conditions    Example  set an operation after 9 5 hours    Set the operating mode  temperature and indoor fan speed first  then  press the  TIMER  button until  9 5h  appears  Press the TIMER button     h    flashes on the LCD  then vou can set      time     Each time the button is pressed      set       ncressas by       a  Four within 10 hours ard    increases by one hour beyond 10 hours  The range that can be            0 5 hour to 24 hours     Point the remote controller at      signal receiver of the indoor unit   press the  SET  button when the letter  h  flashes          beep    will be heard          imer indicator on the indoor unit lights up        Letter  n  stops flashibg     To cancel the set timer  press the         button        beep    will ba heard  and the timer indicator light on the 
10.  ceiling                 Distance from wall  should be 2 ir                 Distanca fram the wall     Should be 2 in    Distance from flaor    should be 79 in    air iniake distance        the wall  air intake distance        227                 the wall should     10 ir ud      Above figure is only a simple presentation    of the unit  it may not match the external  appearance of the unit you purchased      Please install the air conditioner  according to laws and local codes       16         Installation instructions      Select the installation locations    Indoor unit installation location  Installation Diagram      Cc indoor unit so that there is not obstruction near the supply air or return air indoor unk    The wall that the indoor unit hangs on must be free from internal obstructions to  facilitate a clear hole for the refrigeration lines and condensate line to go through       Proper clearances must be maintained to ceilings and walls per instructions on page 16   Easy access must be maintained for removal of the air filter     Pipe length is  49 ft Max                 E E                Indoor unit and remote control must be at least 3 feet from televisions  radios  etc           aQutiloor unit      Indoor unit and remote control must be kept out of direct sunlight and or fluorescent 5     lighting  2   e The wall that      indoor unit hangs on must strong enough to bear the weight of the          unitto ensure quieter operation     Outdoor unit installation locati
11. EATING  downward    FAN ONLY   og      Operation mode Direction of airflow    COOLING  DRY  horizontal         Vertical airflow control use the remote control     Use the following steps to set desired directions of airflow     Swinging airflow option    Press the  SWING  button once  the vertical adjustment  louvers wili swing sweep up and down automatically    Fixed airflow option    Press the    SWING    button once more as soon as the louvers  are at the desired airflow directions and the louver will stop     Horizontal airflow control  set manually      Manually tum the control rads of the  horizontal adjustment louvers to  change horizontal flow as shown       Note  Tha shape of the unit may look different from  that of the nir conditioner you have selected     bs  control rods of hortzontal  adjustmanl louvers      Do not turn the vertical adjustments louvers manual or a malfunction may occur  If a  malfunction does not          the unit first and          off the power supply  Then restore  power supply again and set unit operation       Vertical adjustment louver should not tilt downward for a long time at cooling or dry  mode to prevent condensed water from dripping from the indoor coil       When the vertical adjustment louvers are set using the  SWING  button  the angle  of           will be remembered by the unit as lang as it is in the same operation made   Once the mode is changed  the louver will return to the preprogrammed auto anale     Operation instruction
12. Soleus          Split          Room Air Conditioner   Single Zone Wall Mount Heat Pump    INSTALLATION AND OPERATION INSTRUCTIONS                        2                                                                    k                     M             PZ IIII IST IIIIIIIIAIMII   IAIII IIIAIIIII2IIII lt I        KFR KFS Series    Please read this owner s manual carefully before using your air  conditioner           Contents    Safety PRECAUTIONS  cmm 1  Identification of parts         sei cece ee ccs cece castes emetic 2  Indoor Unit   Operation and display                                                               3 4  Hemole controller  uuu u                             5 6  Operation instructions   Modes                                                                        7  Air flow direction  control  u    uU Uus too                   8  PL 4 5 5 us  ec IET 9  Timer operation mode            Uu                                        enana 10  Sleep operation mode                                                                                      11                          Mee em 12  Prol  GUi  m u                                         13  RefrigGration            dem 14  5                   amp                                 RR PME 15  Installation instructions                                                   u                        16 24  System start up Procedures Electrical Schematics                                  25 27                             
13. ance to raise temperature by 4 F    Range of available set temperatures    Heating  Cooling 64              room temporature   4                 Turning on        Press  ON OFF  button  When the appliance receives  a signal  a           will be heard  The RUN indicator will  then light up     AUX operation    Open the front panel to press the manual switch to run on off the  unit when your remote control is damaged or batteries have died            Open the front panel of The appliance oparates at  the indoor unit and press    I FEEL mode     the switch    The RUN indicator lights up   Press it once again  The RUN indicator light turns  cff and unit shuts down     Tha name and pasilloan of the manual switch may vary from different models  but their function        the same      When the compressor shuts off or if changing modes curing operation of the unit  the unt may not respond at ance  1 may be necessary lo wail up lo 3 minules due lo        compressor protector       There is a 2 5 minute delay on the indoor fan             heating mode operation  Time of delay depends on how longs it  takes for the indocr coil      came up to    desirable temperature                 Operation instructions    Airflow direction control    Vertical airflow is aulomatically adjusted to    certain angle  in accordance with the operation mode after turning on the unit       The direction of airflow can  also be manually adjusted by  pressing the    SWING    button  of the remote control     H
14. e following conditions the unit still does not operate  call a qualified service technician     Possible Condition      Fauk trio or fuse is blown     Fauk device trips to protect the appliance   Does not run    Batteries in the remote controller are dead   Plugis not properly plugged into outlet           Is the air filter dirty       Are the intakes and outlets of the indoor or  outdoor units blocked     Is the temperature set properly     No cooling or  heating    If strong interference from excessive static  electricity discharge  power supply voltage  abnormality  is present  operation may be  abnormal   f this occurs  disconnect from the  power supply and connect back 2 3 seconds later    Ineffective control    Does not operate      Changing modes during operation  must wait for    immediately  53  3 minute delay     Odors may come from another source  such as furniture  cigarettes  etc    These odors may remain on the indoor coil   or filter which may require cleaning     Sound af Caused by the flow of refrigerant in the  flowing water   air conditioner   Sound from defrost mode in heating mode      Nota Far some modal with a compresso  mdiesler  red   it lights up  unaq defrosting         The sound may be generated by tha expansion  Slignt crackling    or contraction      the front plastic panel dus to  heard change af temperature        Moisture from         Mist appears when the roam air becomes        outlet            very cold because of coo  air discharged  pes 
15. e to make indoor  fan motor run in highast speed     Identification of parts       ONIOFF      qm                     SLEEP        SWING          HEATING               is only available for heat pump model     The remote control continuas to display even when the unit has stopped operation     W There is no  HI POWER  mode for same models                       Press to turn appliance    Sleep Indicator  Heating indicator    Cooling indicator  Dry indicator  Fan only indicator          ON OFF         Used to adjust set  temperature    Press once to lower  the set temperature    by 1  F      gt  Press once to raise     the sel temperalure  by 1  F    To change operation  modes    Used to set times in timer  operation mode     Used to send information  programmed in timer  operation mode          Identification of parts    Remote control    How to insert batteries        Pul      open  the cover    8 Insert batleries properly     in the compartment  according to polarity        Push up to close  the cover     The service life of an alkaline batlery is about 1 year  When Ihe indoor uni  does not resound to a s gnel  or  the display becomes dim  replace the batteries at once    Replace with fresa zattarles        Do not use used  batteries     To prevent leakage take out the battenes when unr wel  not      used for      extended period of time       After replacing the batteries  if the remote  control does not display  take them out    for    pariod of 20 seconds and replace     
16. igerant valve service ports  Open  the liquid and suction service valves fully  releasing the R 22 into the system  Connect the service gauges to the refrigerant  valve service ports    5  Setthe indoor remote control to cool mode and ensure proper operation  Allow unit to run for a period of 10 minutes to  allow system pressures to stabilize      Make sure that proper pressures are observed      Check proper temperatures in space  to ensure temperatures match those on remote control     Check condensate drain hose for proper drainage      Checkfor any abnormal vibration noises and correct as needed      Check for any signs of refrigerant leakage    6  Setthe indoor remote control to heat mode and ensure proper operation  Allow unit to run for a period of 10 minutes to  allow system pressures to stabilize  Fllow same checkouts as cool mode       23      HOW TO INSTALL DRAIN ACCESSORIES    There will be some water dripping from the condenser when the heat pump is working during the heating mode   Two drain caps  a drain elbow with rubber collar and a plastic hose  5 8  x 6   are supplied for user s choice     INSTALLATION STEPS      1  Observe the drainage flow of the three drain holes on the base while pouring water into the condensing unit  evenly around the condenser   Figure 1      2  Connect the drain elbow and the plastic hose   Figure 2      3  Insert the drain elbow connected with the drain hose into the hole which has the largest drainage flow and  rotate it to the wa
17. indoor unit will turn off         10        Operation instructions    SLEEP operation mode    a SLEEP moce can      set      I FEEL         COOLING ar HEATING aneraton Todas     This function allows    mere comfortah    environment for times cf sleep          The far speed is automatically set at ultra low speed  which is lower than low speed     The fan does NOT shut off during sleep mode     Before going to           press the  SLEEP  buttan The sleep moce will Ihean       activated     When operating under the Cooling or Dry modes  set the temperature increases by  2 F degree over a 2 hour period  lt       then remain at that temperature until the urit  is manualy tumed off or operation mode is charged  See chart below for more detail      When operating under the Heating moed  the set temperature decreases a total of        degrees over a 3 bour period  it will then remain el hat temserature until the unit  is manualy tumed off or operation made is changed See chart below for more delail         13 recommended ta use SLEEP mode                  with OFF TIMER to achieve    mara  aconomical and enargy saving                     COOLING or DRY    Rise by 1 F   gt                     Rise by          HEATING  HEATING mode is not available for cooling only modes     5 hours timer                    by    F  SET TEMP        edd         Maintenance    Front panel maintenance  Cut off the power supply    Turn off Ihe appliarve  before cutting off the  wer supply     Grasp pasiti
18. le j     di    Indoor unit 1  terminal oleck         Con rol wiring       Cabinet  4  9  gt   Screw           87  5  Conduit fittings  Condur  Connector  Turning the Conduil                              cum loosen il Iron  conduit   Connector a          Connector Nut  lum r3 f  counterc ockwise         loen it fram connector    Cor iuit       Installation instructions       6  Installation of conduit bracket      The shape cf conduit brackat is shown as below       Vonduil brackel       e Pul the conductors through the Conduit and Connector  Tighten the Conduit Connector to the conduit      Pul the conductors through the Connector and      Conduit Bracket  Tighten the Connector Nut to Ihe Connector      Tumthe locknut counterclockwise to tighten the locknut                 Tan the locknut counterclockwise to  tighten    lo the connector     Condut Ccanector Connector Nut          Mounting the Indoor unit to the Mounting Plate   cn __4                  Hook the indoor unit onto the upper portion of the mounting plate by connecting the hooks at the  rear top of the indoor unit with the upper edge of the mounting plate        To ensure that the hooks are properly seated on the mounting plate  check if the unit can slide  by moving it to the left and right  If the unit moves  it is not properly seated        A unit support plate in the mounting plate can be used if the unit is on a slanted wall and can      also be used to ease the connection    the refrigeration lines     Hook e
19. ll side of the building in order to make the drainage flow against the wall  The other two holes  of the base should be stopped by using the two drain caps   Figure  2     NOTE     If the drain hole inserted with the drain elbow is not at the desired location  adjust the level of the condensing unit  slightly  and then reinstall the accessories according to the above steps     Drain cap    Install Drain elbow  8         Plastic hase            24      Electrical schematic diagram    FLECTRICAL SCHEMATIC DIAGRAM OF THE INDOOR UNIT                   7      Tag nean X072    anann                         t                           1    100 HAY                                          S AUTOSWBEP BOTUN  Na 4    DUTDOOR UNIT    capacttort      N    L     INROOR FAN MOTON           ex CO           THERMISTOR       ELECTRICAL SCHEMATIC DIAGRAM OF THE INDOOR UNIT by ae 4    I        I            4          TOANDE    N        LNA  rar           ETN     M    ALTUSREZP                       UNIT     H R41ST R    KFR 24G              FAN NOTOR         25         Electrical schematic diagram    ELECTRICAL SCHEMATIC DIAGRAM OF THE CONDENSING UNIT ELT    THR L2Dy                DL THOUR                CAPACLTOR       A  BLU    REVERSING VALVE       CAPACITOR       ELECTRICAL SCHEMATIC DIAGRAM OF THE CONDENSING UNIT                    2U08   230V   60Hz    DLTUQUR FAN MUTUR        ORN  CAPACITOR    BLU       Bul          RRVERSTNG VALVE  CAPACITOR    8     N  WT R S    COMPRESSOR            
20. lowing cases may cause the internal  safety device to trip        Outdoor air temperature is over 75F     HEATING Outdoor air temperature is below 32F    Room temperature is over           Outdoor air temperature is over 108 F  Room temperature is below 70     Room tamperalure      below BAF    If the air condivoner runs in  COOLING  or   DRY  mode wilh door or window opened          a long time when relative humidity is above  50   dew may dnp down from the air oullel     Features of protector       fault protector device will operate during  the following cases      Stopping the unit and resterting it at once or  changing modes curing operation you will           to wait 3 minutes for time celay      Puting the plug into the wall cutlet and turning  an Ihe sppliancs st          you will          to wait           20 seconds    e    e fel operatons have stopoed due to the fault    protector  press    on off    butten lo reset        unit      Sel timer again if it nas been cancelled       Noise pollution          Install the indoor unit on    wall thal will be  able to hold its own weight  this will ensure  that it operates more quietly     Ses page 19 for further instructions about              unit                 s Install the              unit in a location where  ar discharge and operation noise will not  be bothersome to sumounding residents    See page 18 foe further                   abou    naoor   unit anstallsion     s Do nol place any abstacles in front af the ai
21. nto       the ends of the copper tubing       e The length of the pipe protruding from the face of the flare die is determined by the particular flaring tool that will be  used     e Fix the pipe firmly on the flare die  Match the centers of both the flare die and the flaring punch  and then tighten the  flaring punch fully     e Once flaring is complete  connection of the tubing is ready  Align the center of the tubing and tighten the flare nuts  using a torque wrench           Installation instructions    Properly connect the electrical wiring between the indoor and outdoor unit as shown below     WARNING    THIS APPLIANCE MUST BE GROUNDED    IMPORTANT    The figures shown below are for information purposes only  Make sure that local and or national codes and regulations  are complied with when making connections     4 Interconnecting wires    1  Remave the indoor terminal cover   Open the front panel and remove the indoor  terminal board cover     Froni panel                         ome         i      gt  Chassis    Heat pump    Indoor unit Outdoor unit           LI  Cowduit       lo              lnr Conneeling Conductora    i                                   TT      t     RU                               12                                     e            au T HIS T    Defrost sansor wring Lebe aos eee     2  Supply wiring  control wiring and defrost cable connection        Altached Heat pump    defrast wire      _   Quick connector   1    hy 2                        cab
22. oil surfaces and reduce effciency of the unit    2  Outdoor unit refrigeration line connection   e Remove the valve caps at the outdoor unit where f refrigeration tubing will be connected       Connectthe refrigeration tubing using flaring techniques described earlier  in the indoor unit installation  Be sure to use required torque     Attention      e A baffle is needed when installation is in locations near the sea or areas JE  with strong winds   e      Be sure that unit airflow is not obstructed in any way or that reciculation of Q       discharge air does not occur       21         Installation instructions      3  Wiring connection      Remove the electrical cover of outdoor unit  1 screw        Connect wires as shown below in the illustrations           Heat Pump     gt  Power supply inter connecting          conductors  in conduit A      to the indoor unit           Control inter connecting  conductors in conduit B      to the indoor unit           The conduit should not be loosened after being fixed  otherwise  it may cause abnormal noise when the unit is  running     Number 14 wire should be used for KFR 18GW   Number 12 wire should be used for KFR 24GW   Number 14 wire should be used for KFR 09GW  KFR 12GW A   Number 16 wire should be used for KFR 12GW      22     Installation instructions      System Start Up and Charge Adjustment Procedures    Leakage check    Properly check refrigeration tubes and connections for any leaks prior to system start up procedures    
23. on     Outdoor unil  e Outdoor unit location must be well ventilated  Avoid installing where any type of flammable  gas could leak     e Proper clearances mustbe maintained per instructions on page 16  2    e The maximum length for refrigeration lines is 49 ft  For refrigeraton lines exceeding 231  an  additional  75 pounds must be added per 3 5 feet        The Maximum height between indoor and outdoor units in 25ft  If the outdoor unit is located    above the indoor unit more than 4 ft   a suction line oil trap must be installed         The outdoor unit must not be located in environments that have high contents of acidic    be less      254         distance should       substances  vulcanized gasses  or high salt contents in the air  i s       e The outdoor unit must not be located near locations where dirt  mud       debris        be caked                TE E  onto the outdoor coil or unit       line                eThe foundation that the outdoor unit sits on must be solid and sound so as to decrease noise vibration       Noobstructions should be placed around the outdoor unit  p                     RS card Mounting plate             wr  Indoor unit installation            Ee         A  1  Installing the mounting plate tat A         Hold mounting plate on the wall where unit will be located  Using a level or plumb line  AO m  ensure that the plate is level  Once the plate is level  mark holes that will be used to jf Dropping        hold plate on the wall  holes tor liring
24. on  a  and  pull outward to remove the  front panel        Wipe Panel with  a soft  dry cloth     Use lukewarm water   Uae a ery arz     m  soft cloch to   to clean if the unit is   very dirty    Never use substances such as  gasoline or polishing liquids to  clean the unit     Never use water directly onto the  indoor unit                    51  Electric  shora     Reinstall and shut the front panel     Reinstall and shut the frant panal hy  pressing position  b  downward     h  b     7                                  2195    Air filter maintenance    The filter must be cleaned as follows  when the air conditioner has run for  approximately 100 hours     Stop the appliance and remove  the air filter     nul oa   1 Open the front pancl     2 Press the handle of the filter            fram tha front     3  Slide out the filter     Clean and reinstall the air filter     lf the filter is extremely dirty wash  the filter with a solution of detergent  in lukewarm water  After clearing  allow filter to dry thoroughly out    of direct sunlight        For an air conditioner equippad  with an electrostatic and a charcoal  precipitator  optional parts        Do not clean the electrastatic filter with sater It  should be cleaned using a soft  dry cloth              charcoal filter        be washed using lukewarm  water and a neutral detergent       t is recommend       the electrostatic ard charcoal  filler be replaced after 8 monins of operation           Operating condition    The fol
25. r  discharge of the outdoor unit  This will cause  damage ic the compressor anc motor and  will cause these companents to be noisier   See page 18 for further instnictians en urit   dearances     Inspection       After using the unit for an extended period  of time  the unit should be inspected for the  following items        Overhaaring of the power supply core or plua   e Abnormal aperating sound or unit vibrations     Water leaking from the unit excessively         Indoor unit cabinet becoming electrified    if any of theses symptoms occurs  call a qualified  service technician immediately   It is recommended thet a detailed inspection be made  by 8 qualified technician          3 years cf operation   If even if the above symptoms do not occur     Features of HEATING mode    At the beginning of HEATING operation there is a 2 5 minute delay cn the indoor fan  This is to allow the indoor coil to raise in temperature for proper operation     Defrost mode    In HEATING operation the appliance will defrost the outdoor coil automatically to raise  efficiency This procedure lasts 2 10 minutes  During defrosting mode the indoor fan stops  operation  After defrosting complete  it returns ta the heating mode automatically    It may be difficult to raise the indoor temperature when outdoor temperature is very low   35 F  this is due to nature of heat pumps and their loss    efficiency as outdoor  temperatures decrease          Refrigeration cycle  Indoor unit    HEAT PUMP       defro
26. refrigeration lines  power              pipa  e Insulation material should be a polythene foam that is approximately a 1 4 Or ROEE         inch wall thickness         Condensate drain line should have a downward slope at all times to ensure 4     gt  drain hose    proper drainage  Do not allow the drain line to be twisted  horizontal or the dorast          eRe pamp     end ofthe line be immersed in water  If an extension is added to the drain line  make sure that it is also properly insulated     Connection of refrigeration lines        Do not use contaminated or damaged copper tubing for refrigeration lines  If any of the tubing  mr   a35     evaporator or condenser coils have been exposed to the air for more that 15 seconds  itis  important that they are vacuumed and purged with field supplied refrigerant  Do not remove  plastic or rubber plugs and brass nuts from the valves  fittings  tubing  or coils until they are  ready to be connected       Use proper tubing cutters to cut the refrigeration lines  advancing the blade of the tubing cutters  slowly  Extra force or improper cutting will cause tubing distortion and also extra burring       Once refrigeration tubes are cut  remove burrs from cut edges with a remover  This will avoid    unevenness on the flare faces  which could cause a gas leak  Hold the ends of the pipes  downward to prevent metal from going into the tubes        e Insert the flare nuts  mounted on the connection ends of both the indoor and outdoor units o
27. s            FEEL mode    Press the    ON OFF    button then choose the  I FEEL    mode by pressing                button  The  automatically controlled at the optimum temperature and airflow volume which unit will be is  determined by the indoor temperature     Operation mode   Temperature setting Chart    Indoor temperature Operalian made Set temperature    below 70  F  HEATING                 Roar temperature at             DRY initial operation    overa2    79F     Not available tor cooling only models     Temperature airflow volume and direction are controlled automatically   Remote controller is still functional if you wish to change setting     Your feeling buttan adiustment procedure    i Press twiceto lower the   Slightly warmer     settamp by 2       decrease by asa HI       can be set f    Press four times to lower the        set temp bv 4      Press twiceto raise the  Slightly cooler ub iure E  A rise by 4 F        can he set m  Press four times to raise the  settemp by 4F       Uncomfortable Indoor fan speed alternates between  because of Hi  Med and Low each time this button  unsuitable air is pressed    flow volume     Uncomfartable Press it once  the vertical adjustment  because of louver swings lo change verlical airflow  unsuitable flow direction  Press it again  swings stops   direction  For horizontal airflaw direction  please  refer to the previous page for details           Operation instructions    Timer operation mode    This is a function in which you
28. st heating cooling  Flows of refrigerant       Outdoor unit       accumulator  w   3  Y         gt   _                                         i  S kawa         x              capillary     E A             V Y  i M        reversing valve                    4                        condenser coil        14     Specifications    PERFORMANCE RATINGS    MODEL   KFS 12G   KFR 12G   KFR 6G     Capacity Cooling  BTU h  23100   Capacity Heating  BTU h  23266   SEER 10 4   Moisture Removal Pts h       Air Flow 890 1100 1200  Sound Rating Indoor dB  lt 45  Sound Rating Outdoor dB  lt 59  Operating Range   Cooling  F 60 to 109  Operating Range   Heating  F 28 to 75    ELECTRICAL DATA    Power Source 115 60 1 230 208 60 1 230 208 60 1 230 208 60 1                 Min  Ampacity  A   Cooling Watts   Amps 2323   10 1  Heating Watts   Amps 2379   10 3         TD                                   28   245   2                              Connections Flare Flare Flare Flare    Liquid      OD fi    w   mw  04            line Length  t    Max Height Difference  ft   DIMENSIONS  amp  WEIGHTS      OUTDOOR secrion   KFS 2GWH                                         _KFS T2GWH      Specifications are subject to change without prior notice  Visit our website   www soleusair com  Copyright 2003 Soleus International Inc     EN  a     KR    5  REFRIGERANT LINES  9    27  3 8  5 8  49             E            15     Installation instructions       Installation diagram of air conditioner    5 Distance from
29. unit    tempt to repair the units themselves           identification of parts       Note  The condensate water drains  at COOLING or DRY operation     The figures in this manual are based on the external view of a standard model   Consequently  the shape may differ from that of the air conditioner you have selected        2       Identification of parts    Operation and Display    KF R   O9GW KF R 12GW  KF RHI2GW A KF S  12GW    Used to tum ON OFF the unit  when the remote control is  unavailable     Lights up when HI POWER is set     Lights up during set time of  timer operation mode   Lights up during unit operation     Signal receiver for the  remote control           identification of parts    Operation and Display    KF R  18GW  KF R  24GW    Used to turn ON OFF the unit  when the remote control is  unavailable     Lights up when HI POWER is set     Lights up during set time of  timer operation mode     Lights up during unit operation   Signal receiver for the  remote control              Remote controller    Sends signal to the indoor  unit       FEEL   FEEL  mode  signal transmit     2   9              speed    K high fan speed    p medium fan speed     low fan speed    lt      HI POWER fan speed    Press to select the  indoor fan speed        Press to set sleep mode  and press again to cancel     Press tp camcel timer set  during timer operation mode        Press to activate deactivate  vartical airflow oscillation     Press this button during cooling  or heating mod
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Service Manual FCB Pinnacle 2 and 4 Flavor [ 005271 ]  Gefen EXT-RMT-2-CAT5 console extender  Samsung SGH-D500B מדריך למשתמש  LoggerNet Instruction Manual - Bad Request  Galaxy 3 Series User Guide - Click 24 Fire and Security Maintenance  Toshiba ZL2/55 User's Manual    Manual de usuario Dinamic Caldera de Biomasa  BA_manual Chemeleon 15_30_50 en_dt 110720      Copyright © All rights reserved. 
   Failed to retrieve file