Siemens 6DS2-510-0xx00-0xa0 User's Manual

image

Contents

1. KEKKKKKKKKKKKKKKKK Start L2AMPRO INI Pe KKEKKKKKKKKRKKKKKKKKEKK gt for Bridge CS L2 PROFIBUS lt KKEKKKKKKKEKKKKKKKKK IF964 parameters KKEKKKK KKK KKK K KKK KKK KKK KKK KEKEK boardtyp IF964 slot 5 modulbox 1 KKEKKKKKKKEKKKKKKKKEK LZ bus parameters KEKKKKKKKKE KK KK KKK KKK KKEKKKKEK T2 ts 32 12 hsa 32 12 baud rate 507 12 tsl 3000 12 tqui 0 12 tset 240 12 max_tsdr 980 12 min _tsdr 150 12 ttr 90000 12 g 30 kkxkxkxkxkxkxkxkxkxkxkxkxkxkxkkxx k End L2AMPRO INI file kkxkxkxkxkxkxkxkxkxkxkxkxkxkxkxkxkxkkkxx k Caution If the bus circuit CP5412 A1 is connected in parallel to the IF964 DP module the duplicate interrupts can lead to serious system errors Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 17 of 20 Product Information February 1999 BRIDGE CS L2 6 4 Parameter of configuration file SYS_PAR INI The configuration file SYS_PAR NI includes the parameter for inverting of the DIO In Outputs If the file SYS_PAR IN is not present the operation system uses the default settings from file SYS_PAR DEF Parameter DIO_MASKE_EIN xxx 000 Inputs not negated 255 Inputs negated Parameter DIO_MASKE_AUS xxx 000 Outputs not negated 255 Outputs negated System parameters 10 05 96 ID 99999999 Note Your Bridge serial number DIO settings all inputs and outputs inverted DIO DIO_MASKE_EIN 255 DIO_MASKE_AUS 255 SCHL S 0000 1111 2222 3333
2. Telegrams can be lost during periods of high activity when the target address cannot accept the telegrams from the bridge quickly enough The reception part of the bridge is choked during periods of high activity In this way the transmitter learns of the bridge s coupling backlog and can if necessary repeat the telegrams This means that telegrams are no longer lost in this situation Control of STOP LED when bus coupling errors occur If the bridge recognizes a bus coupling error it is reinitialized This is indicated by addressing the STOP LED even if the bridge functions correctly afterwards M Ifa bus coupling is successfully reinitialized due to an error this event is signaled m on by a flashing LED either LED USR1 for TPM478 or USR2 for CP5412 This condition is then terminated if the key switch is set to any other position Behavior when switch set to RUN P No function was allocated to this setting in the technical description Tab 4 1 It is however identical with the RUN setting Adaptation of the technical description Startup still occurs if configuration file is missing or configuration parameters are incorrect If certain configuration parameters are incorrect or the configuration file BR_SYS INI is missing the bridge is started with the bus parameters BA 3 and TA 20 without taking the existing network configuration into consideration The RUN LED flashes and the INTF LED according to Table 4 1 of th
3. End Copyright SIEMENS AG 1996 1999 All Rights Reserved 79220 A0978 A 05 7637 Page 18 of 20 Product Information February 1999 BRIDGE CS L2 7 Connector Pin Assignment IF961 DIO Following amp C Signals are available on IF961 DIO module Function Assignment of the Outputs Common amp C signal lamp max aed mA Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 19 of 20 Product Information February 1999 BRIDGE CS L2 8 Status display and error messages The lamp test all LEDs on is not activated when switching on the network but only with master reset and soft reset If the memory card is pulled during operation after one minute the bridge functionality can no longer be guaranteed This is signaled by a flashing STOP LED and the LED USR1 If the BRIDGE CS L2 recognizes an error in the bus coupling TPM478 the bus coupling is automatically reinitialized and the LED USR1 flashes rapidly If reinitialization is successful the RUN LED is continuously illuminated while a more persistent error is indicated by the STOP LED Moving the key switch in any way e g from RUN to RUN P or vice versa will cancel the flashing LED USR1 If the BRIDGE CS L2 recognizes an error in the bus coupling CP5412 A1 the bus coupling is automatically reinitialized and the LED USR2 flashes rapidly If reinitialization is successful the RUN LED is continuously illuminated while a
4. 1 but not under Windows NT Subdirectories on the Memory Card will not be copied These have to be saved to the PC Programming device bevor starting the upgrade procedure The upgrade directory is not deleted This means that if an error should occur during the upgrade process the process can be repeated Attention If more than one Bridge memory card are upgraded the directory UPGRADE 201 must either be deleted or renamed between the individual upgrade processes The upgrade directory can also be used as a backup copy of the entire system software This means that repairs can be carried out on memory cards with defective software create directory UPGRADE 200 copy backed up file to it and start the batch file Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 4 of 20 Product Information February 1999 BRIDGE CS L2 2 3 Procedure for Update V01 05 to V01 06 2 3 1 Update by Commissioning Terminal You will find the files listed below in the directory A UPDATE 106 on the UPDATE diskette delivered to you Copy these files to the directory C ASBEDIEN on your Commissioning Terminal PC or into the current working directory e g C TEMP is specified in ASBEDIEN PIF On the Commissioning Terminal PC connected to the BRIDGE CS L2 start the program ASBEDIEN exe via ASBEDIEN PIF under Windows so that the program runs in full screen mode and without a screen saver Now in command mode copy
5. ASBEDIEN Install this on your PC to be used for commissioning of the BRIDGE CS L2 according to the installation instructions in the document file ASBEDI_E DOC in the directory ASBEDIEN and connect your PC to the serial commissioning interface of your BRIDGE CS L2 via a serial interface For operation under Windows 3 1 a PIF file is delivered with the software This contains the following settings run in full screen mode exclusive foreground execution foreground priority very high For operation under Windows 95 the following setting should be specified idle time activity very low no screen saver Using your Commissioning terminal installed in this manner and the commands of the ASBEDIEN input program you can access all data on the memory card inserted in the BRIDGE CS L2 Read the parameter files which have to be processed to enable parameterization from the memory card into a file on your PC using the command COPY_PC You can modify this file on your PC according to your system configuration using the ASCII editors which can be executed under DOS and then write them back onto your memory card using the ASBEDIEN command COPY_TM Note Before starting the UPGRADE UPDATE activities please ensure that a current backup of any files that are to be modified exists This will allow the previous software version to be restored in the even of unforeseen circumstances The files on the memory card are not write protected so care
6. Appearance M Modification e F Delay of telegram transport A Very sporadically within the Bridge it can happen that telegrams were not passed through immediatelly but only when new telegrams were be added M Immediate pass through of the received telegrams e F Commissioning commands COPY_PC and COPY_TM A Both file transfer commands break off with error message M Serial transmission corrected Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 6 of 20 Product Information February 1999 BRIDGE CS L2 3 1 Removed Errors already with V02 00 F A Zz pT Zz T zm zm Time synchronization Time telegrams were not always transmitted at high priority In exceptional circumstances several time telegrams with different time data were transmitted shortly after one another The throughput time of time telegrams in the bridge was optimized Behavior when switch set to STOP In the STOP state old telegrams were kept e g several time telegrams at the same time and full receive buffers on the bridge s bus couplings caused the other bus participants to repeatedly send messages unnecessarily Telegrams are no longer kept in the STOP state Behavior when switch set to MRES Soft Reset This function caused the bridge to stop which could then only be restarted with a cold start Functions according to Table 4 1 of the technical description Loss of telegrams during periods of high activity
7. PROFIBUS TM hexadezimal Parameter REDUNDANZ x Redundancy operating mode of CS275 bus x 1 Redundancy on CS275 long distance bus Standard x 0 No redundancy on CS275 long distance bus Examples of standard system settings TA 32 BA 0 Range 32 TPM478 Slot 6 REDUNDANZ 1 ADR C600 DPR C8 RANGE 20 BATA 0020 REDUNDANZ 1 Note e The BATA must be set individually for each application BRIDGE cannot start up with the default factory setting e The range is set to its maximum size i e 20h e The parameters ADR and DPR correspond to the standard settings of BRIDGE CS L2 In case you change these parameter knowledge about the slot addresses of SIMATIC M7 is required since incorrect entries can lead to serious system errors e If the REDUNDANZ parameter is missing in the configuration file the CS275 bus will operate redundantly Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 13 of 20 Product Information February 1999 BRIDGE CS L2 6 2 Parameter of configuration file DOS _CONF DAT for CP5412 A1 The configuration file DOS_CONF DAT includes the PROFIBUS TM bus parameters A specification of slot coordinates is not necessary Bus parameters Parameter 12_ts Station No on PROFIBUS TM decimal representation Default setting 32 Must be identical to the station address in BATA from BR_SYS INI lf different addresses are entered the parameter I2_ts from DOS _CONF D
8. should be taken when accessing the memory card To back up the files from the memory card to your archive use the ASBEDIEN command COPY PG Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 3 of 20 Product Information February 1999 BRIDGE CS L2 2 2 Procedure for Upgrade to V02 01 with Programming Device PG740 Switch off the power supply of the BRIDGE CS L2 before pulling the memory card For the upgrade insert the memory card into the MEM CARD slot of the PG740 Now start the batch UPGRADE BAT if applicable information on the memory card drive default setting is E This batch file creates a directory C UPGRADE 201 for this at least 1 MByte must be free on drive C copies all files from memory card into the upgrade directory deletes the RMOS system file as this can never be copied to the MC deletes all BAK files copies the packed upgrade files from disk into the directory the system files to be upgraded are then overwritten reformats the memory card and sets up the RMOS system copies all files from the upgrade directory to the memory card Now perform the following two steps 1 Put the upgraded memory card in the allocated Bridge CS L2 and initiate a reboot of the CPU power on 2 Install the new terminal program ASBEDIEN V1 06 to your PC from the diskette included with your delivery IBS tools Notes The upgrade batch runs under Windows 95 and 3
9. AT is used Note The station addresses should be assigned without gaps if possible This may increase the performance Parameter I2_hsa Highest station address on PROFIBUS TM decimal representation Default setting 32 Note Ifthe actual highest station address is entered exactly this may increase the performance However to retain a reserve it is also advisable when configuring to set a higher station address than that actually present Parameter 12_ttr Token rotation time decimal representation Default setting 90000 The default setting applies to a maximum of 10 active stations on the PROFIBUS TM bus If more than 10 stations are present on the PROFIBUS TM bus the parameter must be calculated according to the following equation and entered I2_ttr 9000 number of active PROFIBUS TM stations Note The factor 9000 in the equation only applies to a baud rate of 1 5 MBaud All bus parameters are matched to a transmission rate of 1 5 MBaud Optimization requires detailed knowledge of the PROFIBUS standard Part 1 DIN 19245 Selection of a different transmission rate is illegal and may result in faulty functioning The bus parameters are described in the SINEC Manual TF5412 MS DOS WINDOWS C79000 G8976 C031 Attention Apart from the bus parameters the configuration file DOS CONF DAT also contains system parameters for handling BRIDGE CS L2 communication tasks Unauthorized modifications to these usually result in m
10. CPU 486 3 IF 961 DIO CPU 486 3 IF 962 COM a EXM 478 IF 964 DP System bus L2AMPRO INI D Copyright SIEMENS AG 1996 1999 All Rights Reserved 79220 A0978 A 05 7637 Page 9 of 20 Product Information February 1999 BRIDGE CS L2 4 2 Instructions on installing the CPU 486 3 e The hardware version of the CPU 486 3 must be at least 2 Earlier versions can cause serious errors in the functions that use an interface module e When using the TPM 478 with a CPU 486 3 the CPU BIOS must be at least version V2 07 This is guaranteed if hardware version 2 of the CPU 486 3 is used e When installing the new CPU 486 3 modules the red INTF LED can illuminate for several seconds during booting This indicates that the BIOS has found a configuration that does not agree with the last one saved To stop this procedure the data with the configuration found by the BIOS when booting up must be saved This can be achieved when operating the machine for the first time in the following way for further information please refer to the SIMATIC S7 module manual a Connect the terminal hyper terminal program to the COM1 port of the BRIDGE CS L2 b During booting of the BRIDGE CS L2 press the Q key until the BIOS comes up c Select the window with the system parameters d Leave the window with the system parameters without making any changes e Leave the BIOS setup with the SAVE option This creates among other things a new checksum
11. SIEMENS Program Library Karlsruhe S79220 A0978 A 05 7637 Product Information BRIDGE CS L2 Var V02 01 Issue February 1999 Descriptors TELEPERM M BRIDGE CS L2 UPGRADE UPDATE Summary The present Product Information relates to the System Software Package Name Variant Product no MLFB BRIDGE CS L2 V02 01 6DS2 510 0XX00 0XA0 BRIDGE CS L2 V02 01 6DS2 510 0XX00 0XB1 upgrade update V01 06 Description Erganzende Systemdoku ASx88 TM Technische Beschreibung BRIDGE CS L2 German C79000 G8000 C700 Supplem System Docu ASx88 TM Technical Description BRIDGE CS L2 English 79000 G8076 C700 This manuals have to be ordered seperate if required SIEMENS AG 1996 1999 Anderungen vorbehalten Subject to alteration Sous r serve de modications Con riserva di modifiche Product Information February 1999 BRIDGE CS L2 1 Scope The product information for the system software V02 00 remains valid The following information represents a supplement The delivery consists of 6DS2 510 OXX00 0XA0 6DS2 510 OXX00 0XB1 Upgrade Update BRIDGE CS L2 Memory Card Diskette 3 5 with BRIDGE CS L2 software Diskette 3 5 with tools for installation Diskette 3 5 with tools for installation Software contract and registration card Software contract Product Information Product Information Note on software protection The memory card must be considered as part of the CPU If the memory card i
12. ajor faults in the BRIDGE CS L2 Note The BUS address BA cannot be configured in DOS_CONF DAT Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 14 of 20 Product Information BRIDGE CS L2 Example of a configuration file DOS_CONF DAT FILE FOR INSTALLING TF IHI DRIVER INSTTOOL VERSION V 2 20 02 11 93 numboards 1 boardtyp 5412 SCP device CP L2 1 12 hsa I2 ts 12 physical layer 0 12 lock sap NONE num channel 4 numproc 2 5 5 0 channel name ADM FLG SCP channel type SCP LHI SCP element size 384 numhostbuffer 2 75 75 2 numboardbuffer 2 1 1 2 dpram adr 0xD0000 dpram_size 0x10000 12 station type 1 12 baud rate 7 12 medium red 0 12 retry ctr 1 12 default sap 10 12 network connection sap 37 12 tsl 3000 2 tqui 0 I2 tset 240 12 max tsdr 980 T2 2 2 in tsdr 150 EER g 30 12 in ring desired 1 int vector 12 server id CPADMI window size 8 Download FW5412 Vendor SIEMENS HW device PC To be set installation specific real station address February 1999 default I2_ts 32 highest station address at segment 90000 for 2 to 10 active stations 9000 x number of active stations for 11 t
13. e technical description is continuously illuminated to indicate that the configuration parameters are incorrect or missing Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 7 of 20 Product Information February 1999 BRIDGE CS L2 Caution When upgrading the bridge system software care must be taken that the bus coupling module TPM478 is version 5 or later otherwise all error corrections will not be effective 4 Extended Functions Installing the new M7 CPU 486 3 From V02 00 the BRIDGE system software runs not only on the CPU 488 4 but also on the new CPU 486 3 The changes to the order configuration are described in detail in the PLT 112 catalogue 1998 version The CPU 486 3 replaces the CPU 488 4 In contrast to the CPU 488 4 the CPU 486 3 has only two module ports for interface modules instead of three Caution A memory card upgraded from V01 03 to V01 05 V01 06 will not run on the CPU 486 3 For this CPU either an original delivery of V02 xx has to be used or an upgrade to V02 01 has to be done Replacing the CP5412 A1 with an IF964 DP interface module Now not only the CP5412 A1 module in the AT adapter card ATM 478 can be used as a bus circuit for the PROFIBUS TM system bus but an IF964 DP interface module in an EXM 478 extension module can also be used The extended configuration is described in Chapter 6 3 of this product information The configuration file L2AAMPRO INI f
14. ing this you should ensure compatibility with the other bus participants DOS_CONF DAT BR_SYS INI Remark resp L2AMPRO INI station address TA I2_ts xx dez BATA yyxx hex yy BA xx TA bus address BA BATA yyxx hex yy BA xx TA range RANGE xx hex Bridge filter highest station address I2_hsa xx dez of all stations at the PROFIBUS TM CS275 redundancy REDUNDANZ x x 1 redundant x 0 non redundant If the coupling module CP5412 A1 is used for the PROFIBUS TM SINEC L2 system bus the DOS_CONF DAT initialization file must be used see Chapter 6 2 If however the IF964 DP interface module is used the L2AMPRO INI initialization file must be used see Chapter 6 3 Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 12 of 20 Product Information February 1999 BRIDGE CS L2 6 1 Parameter of configuration file BR_SYS INI Parameter ADR xxxx Address of the Dual Port RAM of the TPM 478 C600 standard system setting hexadecimal Parameter DPR xx Address of the register of the TPM 478 C8 standard system setting hexadecimal Parameter RANGE xx Address range of all PROFIBUS TM stations which are coupled over the BRIDGE CS L2 Permissible range 1 20 hexadecimal Standard system setting 20 hexadecimal Parameter BATA xxxx Definition of the CS address of the BRIDGE in hexadecimal representation High byte Bus No BA hexadecimal Low byte Station No TA on CS275 bus resp
15. ing must be limited to a maximum of 10 e The Bridge buffers transactions that cannot be passed on directly to the receiver Once the connection is reestablished the backlog of telegrams is caught up Messages transmitted in the catch up period can have older time stamps e With PROFIBUS TM the transport of multi address transactions is ensured by PROFIBUS mechanisms If a receiver of a multi address transaction is not available no display task is generated Caution When working on initialization files INI tabs O9H should not be used Spaces 20H should be used instead Failure to comply could lead to interpretation errors Note BRIDGE cannot start up if the parameter ADR in the initialization file BR_SYS INI is not set correctly In this case BR_SYS must be parameterized by means of the emergency operation which is entered by switching the CPU off holding the key switch to MRES and switching the CPU back on ADR C600 means that TPM 478 is inserted in slot 6 standard setting ADR C800 means that TPM 478 is inserted in slot 8 Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 11 of 20 Product Information February 1999 BRIDGE CS L2 6 Configuration of the bus connections The parameters for the BRIDGE CS L2 are set in the configuration files BR_SYS INI DOS_CONF DAT or L2AMPRO INI and SYS_PAR INI amp Subsequent parameters for BRIDGE CS L2 should be set individually In do
16. ith the new emergency utility disk press MRES during switch on Together with the new ASBEDIEN V1 06 an error free transfer can be expected e Before the next RESET the files IBS_BEDI 386 and STARTER 386 must be successfully transferred Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 5 of 20 Product Information February 1999 BRIDGE CS L2 2 3 2 Update by Programming Device PG740 Before starting the UPDATE activities pulling the memory card please ensure that a current backup of any files that are to be modified exists This will allow the previous software version to be restored in the even of unforeseen circumstances Switch off the BRIDGE CS L2 before pulling the memory card Copy the files listed under 2 3 1 from the update diskette into a new directory having the name of your PG740 For the update insert the memory card into the MEM CARD slot of the PG740 Now copy all files from the directory name onto the memory card either using the file manager or explorer or using a DOS box COPY name E y Now perform the following two steps 1 Plug the upgraded memory card of the Bridge back into the allocated BRIDGE CS L2 and initiate a reboot of the BRIDGE CS L2 reset or off on 2 Install the new terminal program ASBEDIEN V1 06 to your PC from the second diskette included with your delivery IBS tools 3 Removed Errors from V02 00 to V02 01 F Function concerned A
17. more persistent error is indicated by the STOP LED Moving the key switch in any way e g from RUN to RUN P or vice versa cancels the flashing LED USR2 Operational modes switch key switch The switch setting RUN P is functionally identical to the setting RUN In the STOP operational mode key switch setting the coupling via the BRIDGE CS L2 is interrupted The couplings for the PROFIBUS TM and for the CS275 continue to participate in the token circulation and indicate this through the display on the front plate In this mode messages can get lost on the BRIDGE CS L2 In the case of a soft reset all messages in the buffer are deleted and the bus couplings TPM478 and CP5412 A1 or IF964 DP are reset Afterwards communication is restarted by initializing the bus couplings TPM478 and CP5412 A1 or IF964 DP In addition a LED lamp test is carried out Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 20 of 20
18. o 32 stations max I2_ttr 288 000 default I2_hsa 32 default I2_ttr 90000 Copyright SIEMENS AG 1996 1999 All Rights Reserved S 79220 A0978 A 05 7637 Page 15 of 20 Product Information February 1999 BRIDGE CS L2 The parameter assignments int_vector 12 and dpram_adr 0xD0000 with which the interrupt and DPRAM address range are set agree with the default settings of the bridges and the DIP switches on the interface module CP5412 A1 which are already factory set when delivered Caution If the L2AAMPRO INI configuration file is also saved on the memory card this configuration takes precedence i e a parameter file DOS CONF DAT existing in parallel and a bus circuit CP5412 A1 are ignored 6 3 Parameter of configuration file L2AMPRO INI for module IF964 DP 1 1 Parameters for slot addressing Parameter slot Slot No according to incrementing of SIMATIC M7 400 System setting 5 Parameter modulbox Module slot No according to incrementing of SIMATIC M7 400 System setting 1 The settings which correspond to the standard system configuration have been preselected for the coordinates of the IF964 DP and should therefore be used unchanged Any changes to these parameters require knowledge of the slot addressing for SIMATIC M7 and incorrect entries may result in major system faults 2 Bus parameters Parameter 12_ts Station No on PROFIBUS TM decimal representation Must be identical to the stati
19. of the BIOS data the checksum is then saved in the module f When the system is booted up in future the INTF LED will not illuminate unless there is a further CPU error e When booting up the Bridge CS L2 the BIOS start up of the CPU 486 3 lasts about 10 seconds A criterion for this is that only the red STOP LED of the CPU 486 3 is lit When the operating system RMOS32 and the bridge system software are then subsequently loaded the green SD LED flashes or is lit continuously If there is a significant delay before the green SD LED illuminates the BIOS settings can be changed to reduce the BIOS start up time The following settings in particular should be implemented for further information please refer to the SIMATIC S7 module manual 1 SETUP page Hard Disk Switch off Auto option SETUP page Floppy Card Set drive A to MemCard e With the BRIDGE CS L2 the module slots on the CPU 486 3 must not be fitted with an IF964 interface module An IF964 module inserted here cannot be addressed by the BRIDGE CS L2 system software Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 10 of 20 Product Information February 1999 BRIDGE CS L2 5 Limited operating performance No safety relevant faults are currently known the known faults are assigned to fault class 3 and lower e When using the load RAM function of PROGRAF AS by means of BRIDGE CS L2 to an AS x88 TM the bus load sett
20. on address in BATA from BR_SYS INI lf different addresses are entered the parameter I2_ts from L2AMPRO INI is used Note The station addresses should be assigned without gaps if possible This may increase the performance Parameter 12_hsa Highest station address on PROFIBUS TM Default setting 32 Note Ifthe actual highest station address is entered exactly this may increase the performance However to retain a reserve it is also advisable when configuring to set a higher station address than that actually present Parameter 12_ttr Token rotation time decimal representation Default setting 90000 The default setting applies to a maximum of 10 active stations on the PROFIBUS TM bus If more than 10 stations are present on the PROFIBUS TM bus the parameter must be calculated Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 16 of 20 Product Information February 1999 BRIDGE CS L2 according to the following equation and entered I2_ttr 9000 number of active PROFIBUS TM stations Note The factor 9000 in the equation only applies to a baud rate of 1 5 MBaud All bus parameters are matched to a transmission rate of 1 5 MBaud Optimization requires detailed knowledge of the PROFIBUS standard Part 1 DIN 19245 Selection of a different transmission rate is illegal and may result in faulty functioning Example of a configuration file L2AAMPRO INI
21. or the IF964 takes precedence over the parameter file DOS_CONF DAT for CP5412 A1 In order to maintain the previous bus configuration when updating the new INI file is supplied as L2AAMPRO INX on the update diskette The file should be renamed accordingly if an IF964 DP is to be used The file L2AAMPRO INI is supplied as standard on the memory card with new deliveries of version V02 xx With new deliveries of version V02 xx the PROFIBUS TM system bus is accessed with the interface module IF964 DP as standard which is operated in the EXM 478 extension module This replaces the previous configuration with the CP5412 A1 bus coupling in the ATM 478 extension module Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 8 of 20 Product Information February 1999 BRIDGE CS L2 4 1 Configuration of the BRIDGE CS L2 with CPU 486 3 and IF964 DP As the CPU 488 4 is replaced by the CPU 486 3 and the CP5412 A1 is replaced by the IF964 DP interface module there are the following alterations to the previous description of the standard configuration EXM 478 with one IF964 Memory CPU 486 3 Card Power Supply DC 24 V Service and 7 Diagnostic lle 8 Process control monitoring dol A e j System bus PROFIBUS TM y w o Cea Module Interface Configuration box Module file PS 407
22. s removed during current operation the BRIDGE CS L2 enters STOP as a result of the software protection i e telegrams are no longer processed Attention Before commissioning please read the current documentation carefully Product Information present document Technical TELEPERM M Bridge CS L2 Description Technical Description C79000 T8076 C707 included in Supplementary System Documentation ASx88 TM C79000 G8076 C700 Copyright SIEMENS AG 1996 1999 All Rights Reserved S79220 A0978 A 05 7637 Page 2 of 20 Product Information February 1999 BRIDGE CS L2 2 Commissioning The Memory Card contains the entire system software for the Bridge version V02 01 To perform an upgrade or update from diskette a BRIDGE CS L2 memory card must be available The upgrade procedure is performed offline with a PC or a programming device having a compatible MC interface e g PG740 The update procedure is performed either from the IBS terminal online or from a programming device having a compatible MC interface e g PG740 A description of the upgrade procedure is provided under heading 2 2 in this document of the update procedure under heading 2 3 Caution The file RM3_PC1 SYS on the memory card must never be deleted moved or overwritten as this would mean that the memory card would no longer be bootable 2 1 Startup by Commissioning Terminal Additional the IBS Tool diskette contains your local tool in the directory
23. the files previously backed up to the PC to the memory card in the BRIDGE CS L2 in the following sequence lt esc gt COPY TM IBS BEDI 386 resp lt esce COPY_TM C ASBEDIEN IBS BEDI 386 lt esc gt COPY TM STARTER 386 resp lt ssc gt COPY TM C TEMP STARTER 386 lt esco gt COPY TM BRI BEDI 386 lt Esc gt COPY TM BRIDGE 386 lt esco gt COPY TM ITASK EXE lt Esco gt COPY TM RMOS IN lt esco gt COPY TM L2AMPRO INX lt esco gt COPY TM VERSION TXT If necessary the following file should be modified in accordance with this product information BR_SYS IN settings for non redundant operation of the CS 275 bus After a successful transfer exit ASBEDIEN with Alt X Now perform the following two steps 1 Initiate a reboot of the BRIDGE CS L2 reset or off on 2 Install the new terminal program ASBEDIEN V1 06 to your PC from the diskette included with your delivery IBS tools Attention The data transfer was only successful if the command COPY_TM ends without error messages and without any manual intervention e g termination with ESC In the case of errors the copy procedure must be repeated If problems occur during the data transfer frequent terminations we recommend the following procedure e If the first file IBS_BEDI 386 was transferred without errors the BRIDGE CS L2 can be rebooted w

Download Pdf Manuals

image

Related Search

Related Contents

South Shore Furniture 3342213 Instructions / Assembly  DDP-405 USER'S MANUAL  AccXES Client Tools 10.0 Guida per l`utente  シグナスX [FI]用 ハイパーS−Stageキット 取扱説明書    nouvelles aiguilles emg à usage unique  termoconvettore split - manuale di istruzioni • ptc convector  phyCORE-AM3517 Hardware Manual  Fiche technique Manobrassard adulte  Descargar ficha técnica  