Home
Quadra-Fire GARNET-T GARNET-D-CSB User's Manual
Contents
1. senex SFexblePpelengn senes HoFewwPpelewm sereo Gas e ein 2 sees o Page 46 Quadra Fire Garnet T 7016 127F SV4LA24 SV4LBA24 4DT EL45B 4D45LB SV4EBR45 gt O n P N CO Description HHT SL P Simpson Selkirk Amerivent Security M Multi Pack 6 Dura Vent Direct Temp Direct Secure Vent DirectVent Pro 6 Bow Swivel Back ass SMS 00 Ebon Gaveres straw Sese res Xs 00 Eto Swer Gatas we sw D Eo Swivel Back wes e tic at Si Co omas O l ww tion Sho tz emm TS Attic Insulation Shield Adjustable 120 4eDVMS fe Coig Sap ane scs we Sus Coil to ones plane Comer wen Demane coing Feso Back secs Decorative Radus Cover wcmows Sid Fox ap CapwihFresop sera o Flex Tap Cap wih resp nd 0 Hex Pe senmemem _ WaewyOWmeycmeso nt one resp 4e or 45 ore Wal Tinbe Back amm O Fm Pete ek 4 m va Wal Thimble S
2. b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve a ON OFF switch or Check the ON OFF switch and wires for proper connections Place the wires defective jumper wires across the terminals at the switch If the burner comes on replace the defective switch If the switch is OK place the jumper wires across the switch wires at the gas valve IF the burner comes on the wires are faulty or connections are bad 3 The pilot is burning there is no gas to the burner the valve knob is in the ON position and the ON OFF switch is in the ON position b Thermopile may If the pilot flame is not close enough physically to the thermopile adjust not be generating the pilot flame sufficient millivoltage Be sure the wire connections from the thermopile at the gas valve ter minals are tight and that the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading at TH TP amp TP terminals of the gas valve The meter should read 325 millivolts minimum while holding the valve knob depressed in the pilot position with the pilot lit and the ON OFF switch in the OFF position Replace the faulty thermopile if the reading is below the specified minimum With the pilot in the ON position disconnect the thermopile leads from the valve Take a reading at the thermopile leads The reading should be 325 millivolts minimum Replace the therm
3. suPPoRT BOX PIPE LENGTH QA OA I i L1 E s a A Figure 5 10 Step 1 Check the installation instructions for required 1 in 25mm clearances air space to combustibles when passing through ceilings walls roofs enclosures attic rafters or other nearby combustible surfaces See page 17 Figure 5 16 Check the instructions below for maximum vertical rise of the venting system and any maximum horizontal offset limitations All offsets must fall within the set parameters of the vent graph Figure 5 2 located on page 11 NOTE Maximum vertical rise allowable is 25 ft 8m Figure 5 11 NOTE Maximum number of 45 elbows permitted for a vertical installation is eight provided their installation does not decrease maximum allowable horizontal run as specified by vent graph on page 11 August 1 2008 Quadra Fire Garnet T 7016 127F Fire Risk Explosion Risk Maintain vent clearance to combustibles as speci fied Do not pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause fire 25 ft 8m MAXIMUM Figure 5 11 Step 2 Set the gas appliance in its desired location Drop a plumb bob down from the ceiling to the position of the appliance flue exit and mark the location where the vent will penetrate the ceiling Drill a small hole at this point Next drop a plumb bob from the roof to the hole previously drilled i
4. 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you smell gas STOP Follow B of the safety information above If you don t smell gas go to the next step 7 Push gas control knob in and turn counterclockwise to the pilot position NOTE Knob cannot be turned unless knob is pushed in slightly Do not force 8 PIEZO IGNITER Press down on the gas control knob in pilot position and simultaneously press the piezo igniter This may take many repetitions for lighting ELECTRONIC IGNITER If the unit is equipped with an electronic igniter it should begin sparking right away 9 The pilot should be visible through the door opening 10 Reinstall door and face Wait five minutes to allow pilot flame to stablize and establish proper draft MILLIVOLT 11 After the pilot is lit continue holding control knob down for approximately GENERATOR 4 30 seconds Release the knob and it will pop back up Pilot should remain lit If it goes out repeat steps 7 through 9 If the knob does not pop up when released stop and immediately call your service technician or gas supplier If the pilot will not stay lit after several tries turn the gas control knob clockwise 44 to OFF and call your service technician or gas supplier 12 Push down and turn gas control knob counterclockwise se to ON 13 Push burner rocker swit
5. Top of Stove to Alcove Ceiling 19 3 8 in 49cm Distance entre le haut du po le et le plafond ronmounpowx HEARTH A non combustible hearth pad is not required However the floor beneath the stove must be stable level and strong enough to support the stove without a tipping hazard CHEMIN E Un coussinet non combustible de chemin e n est pas exig Cependant le plancher en dessous du po le doit tre droit niveau et assez fort pour supporter le po le sans le hasard de basculer a 5 a D Man LO 2008 2006 a Jan Mar te vey t ml nul n Li Li Manufactured Date LU J UV EI A U U 8 Page 2 Quadra Fire Garnet T 7016 127F August 1 2008 TABLE OF CONTENTS Section 1 Listing and Code Approvals Section 7 Electrical Information A Appliance Certifications 4 A Recommendation for Wire 29 B Glass Specifications 4 B Connecting to the Appliance 29 C BTU Specifications 4 C Standing Pilot Ignition System Wiring 29 D High Altitude Installations 4 E Non Combustible Materials 4 F Combustible Materials 4 Section 8 Appliance Setup G Requirements for the A Remove Shipping Materials 31 Commonwealth of Massachusetts 5 B Leg Leveling System 31 C Flue Restrictor Installation
6. 951mm Clearance from stove corner to combustible wall MINIMUM OF 6 in 152Mm OF PIPE THROUGH THE WALL WALL THIMBLE TERMINATION CAP TRIM RING HEAT SHIELD OVER TOP HALF OF PIPE Quadra Fire Garnet T 7016 127F August 1 2008 Gas Information A Fuel Conversions Before making gas connections ensure that the appliance being installed is compatible with the available gas type Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a quali fied technician using Hearth amp Home Technologies specified and approved parts 1 Converting to LP Gas NOTE Gas conversions should only be performed by a qualified service person and or where required by state and local codes licensed installer service technician In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter KIT CONTENTS Replacement orifice replacement pilot injector valve regulator conversion label TOOLS REQUIRED Power drill a 90 drill is helpful Slotted screwdriver or Torx TH20 2 Phillips bit 5 32 Allen wrench 3 8 open end wrench Remove 2 screws Figure 6 1 Lift off the appliance top and place it on a flat sur face with the porcelain side up to prevent damage Remove the appliance front by sliding it upwards in the grooves being careful not to chip the porcelain Lay the appliance front face up on a flat surf
7. the bottom of the graph 3 The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run EXAMPLE 1 If the vertical dimension from the center line of the flue vent to the center of the 90 elbow is 7 ft 2m the horizontal run to the outer wall flange must not exceed 9 ft 8 in 3m EXAMPLE 2 If the vertical dimension from the center line of the flue vent is 21 ft 6m the horizontal run to the outer wall flange must not exceed 4 ft 3 in 1m 4 Each 90 elbow is equivalent to 3 ft 914mm of vent pipe and each 45 elbow is equivalent to 1 ft 305mm of vent pipe and must be subtracted from the vent pipe run A single horizontal to vertical 90 elbow is already calculated into the allowable 15 ft 5m run Each additional 90 elbow reduces the maximum horizontal distance by 3 ft 914mm EXAMPLE The use of 3 elbows would reduce the allowable horizontal run to 9 ft 3 1 2 elbows x 3 ft 6 ft 15 ft max 6 ft 9 ft max 25 ft 8m Maximum Vertical Example 2 E Venting Guidelines NOTES The maximum horizontal vent run is 15 ft bm when the vertical vent rise is 10 ft 3m Horizontal sections require a 1 4 in 6mm rise for every 12 in 305mm of horizontal travel Exterior Vent Diameter 6 5 8 in 168mm Inner Vent Diameter 4 in 102mm Horizontal sections require noncombustible support every 3 ft 914mm e g wall straps Fo
8. Drill Driver Pliers Wrench Set Hammer Framing Square Phillips Screwdriver Framing Material Flat Blade Screwdriver Hi temp caulking material Plumb Line Voltmeter Level Gloves Manometer Safety Glasses Tape Measure Non corrosive Leak Check Solution or combustible gas detector Page 6 Quadra Fire Garnet T 7016 127F August 1 2008 Appliance Location and Clearances NOTE AX WARNING Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Fire Risk Provide adequate clearance Illustrations diagrams are not drawn to scale Around air openings Actual installation may vary due to individual design To combustibles preference For service access Locate appliance away from traffic areas A Selecting Appliance Location When selecting a location for your appliance it is important to E A WARNING consider the required clearances to walls see Figure 3 1 Fire Risk e Locate and install appliance to all NOTE For actual appliance dimensions refer to clearance specifications in manual Section 12 B Clearances G Alcove i Sree mse i ifs i f 7 e B n a in MU P di l m m A measurement is from stove top not side asa E EE Figure 3 1 It is permissible to place the appliance on carpet WARNING CAUTION Fire Risk Some carpet materials may be sensitive to radiant heat from the Odor ASS appliance causing discoloration or odor Tipping Risk e Install
9. E rn uo M E L A 2 Page 56 Quadra Fire Garnet T 7016 127F August 1 2008
10. Tasks inspect Maintenance Tasks TZ Verify no obstructions 10 aro J 3 Very maintenance of proper clearance to combustible household objects Gasket Seal Glass Assembly and Glass 4 Verify that latches engage properly and glass attachment components are intact and operat ing properly Replace as necessary 5 Clean glass Replace glass assembly if severely coated with silicate deposits that cannot be removed Valve Compartment 1 Vacuum and wipe out dust cobwebs debris or pet hair Use caution when cleaning these and Firebox Top areas Screw tips that have penetrated the sheet metal are sharp and should be avoided 2 Remove any foreign objects 3 Verify unobstructed air circulation 1 Inspect for broken damaged or missing logs Replace as necessary 2 Verify correct log placement and no flame impingement causing sooting Correct as neces sary 1 Inspect for paint condition warpage corrosion or perforation Sand and repaint as neces sary 2 Replace appliance if firebox has been perforated Burner Ignition and 1 Verify burner is properly secured and aligned with pilot or igniter Operation 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary USE CAUTION WHEN CLEANING HANDLING CERAMIC BURNER 3 Replace ember material with new dime size and shape pieces Do not block ports or obstruct lighting paths 4 Check for smooth lighting and ignition car
11. appliance on a stable level platform floor strong enough to support appliance NOTE Flooring beneath appliance may reach 90 degrees without tipping plus room ambient temperature Check with flooring USE wood flooring ceramic tile brick hearth manufacturer for maximum temperature allowed on flooring or high pressure laminate flooring applied surfaces directly over the sub flooring material August 1 2008 Quadra Fire Garnet T 7016 127F Page 7 Termination Locations A Vent Termination Minimum Clearances Fire Risk Explosion Risk Maintain vent clearance to combustibles as specified Do not pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause fire Measure vertical clearances from this surface Measure horizontal clearances from this surface See Figure 4 4 for specific clearances Figure 4 1 Termination Clearances GAS WOOD OR FUEL OIL TERMINATION GAS C TERMINATION Gas Wood amp Fuel Oil recon MERO coments Horizontal distance between terminations Vertical distance between terminations Figure 4 2 Multiple Vertical Termination Page 8 Quadra Fire Garnet T 7016 127F HORIZONTAL OVERHANG 20 INCHES MIN VERTICAL LOWEST DISCHARGE OPENING GAS DIRECT VENT TERMINATION CAP L ROOF PITCH IS X 12 H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Roof Pitch H Min Ft Plat
12. correct J Intake Damper Operation The intake damper can be used with or without the flue restric tor to adjust the air flow Opening the damper makes the flames shorter and more active Closing the damper makes the flames taller and less active Page 36 Quadra Fire Garnet T 7016 127F OPEN CLOSE Figure 8 17 Loosen the wingnut that secures the damper The wingnut is located on the underside of the appliance to the right of the pilot assembly To CLOSE the intake damper pull the wingnut forward toward the front of the appliance To OPEN the damper push the wingnut back Adust the damper in 1 4 in increments until the desired flame is achieved After adjustment tighten the nut K Shutter Adjustment Figure 8 18 The shutter is located on the underside of the appliance on the right side To adjust the shutter loosen the wingnut Retighten the wingnut after adjustment Moving the shutter bolt to the right closes the shutter Moving the shutter bolt to the left will open the shutter Opening the shutter causes flames to become shorter and blue Closing the shutter creates taller orange yellow flames NOTE Do not close so much as to cause a sooty flame Improper adjustment can cause sooting in the firebox and or on the outside of a house with a horizontal termination After adjustment tighten nut to lock in place August 1 2008 Operating Instructions A Before Lighting Appliance Read
13. dealer s VIP site When ordering supply serial and model numbers to ensure correct service parts Alphabetical Order Adapter DV SBin EO 10 ar Shutter ssemby fo 2 BakShed 2016 140 7 Bale 2016 125 15 BafleBack 2018 126 Blower Shroud Bag ro Blower Shroud TOP Bower Univesa Gas as EE ET BBumerStp Yd 010 182 BBumerSupot 2016 120 Bumer Assembly or Burner Neck Assembly 7016 166 Burer with Neck Assembly fot Cable Switch Assembly S I T Component Pack BK 7016 007 PMH 7016 027 Includes ON OFF Valve Mineral Wool Pilot Injector EZ LP 35 Conversion Regulator S I T LP Conversion Label Orifice Plug CCR 7016 028 I N NO O CO c Oo Insert 56 Leveling Assembly Snap Disc Bracket Warranty Card Owner s Manual Restrictor Touch up Paint and Fasteners CLG 7016 024 CME 7016 025 7016 006 3 7016 004 7016 117 7016 108MBK 7016 108POR 7016 108PWD ND Ro 2 Door Right Matte Black 7016 107MBK 22 Door Right Porcelain specify color 7016 107POR 2 Door Right Powder Coat specify color 7016 107PWD NO 842 4580 7000 197 7016 122 7016 130 0 7016 106MBK 0 7016 106POR NO TRO IN 0 7016 106PWD 19 464 0160 460 0610 844 3010 24 Gasket Pilot 1000 196 Glass Assembly 7016 023 August 1 2008 Quadra Fire Garnet T 7016 127F Page 49 QUADR FIDE 2 Setvice Parts List cows GARNET T NG LP Exploded Parts Diagram Beginning Manufacturing Date 6 16
14. e Gas build up during line purge may ignite e Purge should be performed by qualified technician e Ensure adequate ventilation e Ensure there are no ignition sources such as sparks or open flame When installing this appliance at an elevation above 2000 feet it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size Input rate should be reduced by 4 for each 1000 feet above a 2000 foot elevation in the U S A Ifthe heating value of the gas has been reduced these rules do not apply To identify the proper orifice size check with the local gas utility A small amount of air will be in the gas supply lines When first lighting appliance it will take a short time for air to purge from lines When purging is complete the appliance e If installing this appliance at an elevation above 4500 feet will light and operate normally in Canada check with local authorities Air only needs to be purged again if gas valve has been turned to the OFF position CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Check all fittings and connections Do not use open flame e After the gas line installation is complete all connections must be tightened and checked for leaks with a commercially available non corrosive leak check solution Be sure to rinse off all leak check solution following testing Fittings and connections may have loosened during shippi
15. e Security Secure Vent DO NOT USE FIELD FABRICATED VENTING COMPONENTS Refer to the venting manufacturer s instructions This product is approved to be vented either horizontally through the side wall or vertically through the roof You may vent through a Class A or masonry chimney if an approved adapter is used This appliance is a direct vent heater All combustion air must come directly from the outside of the building The vent pipe for this unit consists of an inner and an outer pipe The inner pipe carries the appliance exhaust out of the system and the outer pipe brings fresh combustion air into the appliance e A round support box wall thimble or heat shield is required when the venting passes through a combus tible wall e A support box or ceiling firestop is required when the venting passes through a ceiling e Roof flashing and a storm collar are required when vent ing passes through the roof e Follow instructions provided with the venting for instal lation of these items Fire Hazard Explosion Risk Asphyxiation Risk Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance Vent this appliance directly outside Use separate vent system for this appliance May impair safe operation of this appliance or other appliances connected to the flue Page 10 Quadra Fire Garnet T 7016 127F B Use of Elbows caution ALL ve
16. from appliance When first operated this appliance may release an odor for the first several hours This is caused by the curing of the paint and the burning off of any oils remaining from manufacturing If appliance has not been used for some time dust can build up and cause an odor Film on the glass Metallic noise This is a normal result of the curing process of the paint and logs Glass should be cleaned within 3 to 4 hours of initial burning to remove deposits left by oils from the manufacturing process A non abrasive cleaner such as gas appliance cleaner may be necessary See your dealer Noise is caused by metal expanding and contracting as it heats up and cools down similar to the sound produced by a furnace or heating duct This noise does not affect the operation or longevity of the appliance August 1 2008 Quadra Fire Garnet T 7016 127F Page 39 Troubleshooting 10 With proper installation operation and maintenance your gas appliance will provide years of trouble free service If you do experience a problem this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the corrective action to be taken This troubleshooting guide can only be used by a qualified service technician Symptom Possible Cause Corrective Action 1 After repeated trig a Defective ignitor Check the spark at the electrode and pilot If no spark and electrode gering of the pie
17. is desirable above the roofline due to its higher corrosion resistance NOTE 1 If an offset is necessary in the attic to avoid obstructions it is important to support the vent pipe every 3 ft 914mm to avoid excessive stress on the elbows and possible separation Wall straps are available for this purpose Figure 5 12 2 Whenever possible use 45 elbows instead of 90 elbows The 45 elbow offers less restriction to the flow of flue gases and intake air Step 6 Slip the flashing over the pipe section s protruding through the roof Secure the base of the flashing to the roof with roofing nails Ensure the roofing material overlaps the top edge of the flashing as shown in Figure 5 14 Verify that the chimney is the required height above the roof See roof pitch table Figure 4 3 on page 8 CAP AND STORM COLLAR NOT SHOWN FOR CLARITY Shingles overlap on top edge of flashing Figure 5 14 Step 7 Continue to assemble pipe sections until the height of the vent before adding the termination cap meets the minimum code requirements as outlined in the current CAN CGA B149 Installation Codes in Canada the National Fuel Gas Code NFPA 54 ANSI Z223 1 in USA or local codes Note that for steep roof pitches the vent height must be increased See Roof Pitch Table Figure 4 3 on page 8 In high wind conditions nearby trees adjoining rooflines steep pitched roofs and other similar factors can result in poor draf
18. notch in left front log F Mineral Wool Explosion Risk Follow ember placement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interferes with proper burner operation Figure 8 9 Place individual pieces of embers in front of and around the gas log where they can be seen Space them so that gas can contact them on all sides Avoid stacking the embers on top of each other NOTE Do not block gas ports August 1 2008 G Glass Replacement Turn the appliance OFF and let it cool down before replacing the glass Lift off the appliance top and place it on a flat surface with the porcelain side up to prevent damage Remove the appliance front by sliding it upward in the grooves being careful not to chip the porcelain Lay the front face up on a flat surface Unhook latch now exposed on top of the appliance Pull the top of the glass frame towards you and lift it out of the retainer along the bottom of the firebox Replacement is the reverse of the removal CAUTION Handle glass assembly with care Inspect the gasket to ensure it is undamaged Inspect the glass for cracks chips or scratches Do NOT strike slam or scratch glass Do NOT operate appliance with glass door removed cracked broken or scratched Replace glass assembly as a complete assembly H Blower Installation TOOLS REQUIRED Short 2 Philips head screw
19. of 6 in 152mm horizontal run of vent with a 1 4 in 6mm rise run towards the termination Each 1 ft 305mm of horizontal venting must include a 1 4 in 6mm rise Never allow the vent to run downward This could cause high temperatures and may present the possibility of a house or structure fire The location of the horizontal vent termination on an exterior wall must meet all local and national building August 1 2008 Quadra Fire Garnet T 7016 127F codes and must not be easily blocked or obstructed see Figure 4 4 on page 9 For installations requiring a vertical rise on the exterior of the building a snorkel kit is available with a 14 in 356mm and a 36 in 914mm tall snorkel termination cap Follow the same installation procedures as used for standard horizontal terminations If the snorkel termination must be installed below grade i e basement application proper drainage must be provided to prevent water from entering the snorkel termination Do not backfill around snorkel termination Step 4 Position the horizontal vent termination cap in the center of the 10 in x 10 in 254mm x 254mm square hole and run a bead of non hardening mastic around its outside edges so as to make a seal between it and the wall attach termination cap to the exterior wall with the four wood screws provided The arrow on the vent cap should be pointing up Figure 5 6 WALL THIMBLE Figure 5 6 NOTES 1 The fou
20. veranda porch deck balcony or over hang vinyl 18 inches 42 inches clearance from sides of electrical service 6 inches See Note 3 clearance above electrical service 12 inches See Note 3 6 inches 12 inches non vinyl sidewalls vinyl sidewalls Qun termination caps x 3 Rmax 2 termination caps xQacrua NOTE Local clearances codes or regulations may require different NOTE Termination caps may be hot Consider their proximity to doors or other traffic areas WARNING In the U S Vent system termination is NOT permitted in screened porches You must follow side wall overhang and ground clearances as slated in the instructions In Canada Vent system termination is NOT permitted in screened porches Vent system termination is permitted in porch areas with two or more sides open You must follow side wall overhang and ground clearances as stated in the instructions Quadra Fire assumes no responsibility for the improper perfor mance of the appliance when the venting system does not meet these requirements CAUTION IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING IT IS SUGGESTED THAT A VINYL PRO TECTOR KIT BE INSTALLED Page 9 Vent Information A Venting Components In order to comply with applicable codes and product warranties use only following venting components Hearth 8 Home Technologies HHT e Simpson Dura Vent e Selkirk Direct Temp Amerivent Direct
21. 04 Ending Manufacturing Date IMPORTANT THIS IS DATED INFORMATION The most current information is located on your dealer s VIP site When ordering supply serial and model numbers to ensure correct service parts Part Description Part Alphabetical Order __ Hinge Pins Gold set of 2 844 5750 6 Ignition Module 230 1880 Injector Pilot EZ LP 35 200 2630 Knob Extension HI LO S I T 571 533 Knob Extension ON OFF S I T 571 534 Knob Speed Control 19942 229 0640 7000 000 7016 018 7000 140 200 2550 15697A 230 1781 842 4280 7016 164 7016 165 230 1520 230 1570 7016 005 7016 121 7016 145 7016 109MBK 7016 109POR Latch Draw Leveling Assembly Log Set Magnet Round C1 Mineral Wool ON OFF Valve Pilot Assembly NG Pilot Assembly NG EZ with Injector Pilot Shield Pilot Spacer Regulator Conversion S l T LP Regulator Conversion S l T NG 18 Relief Door Assembly Relief Door Bracket Restrictor Side Matte Black Side Porcelain specify color 1 1 Side Powder Coat specify color 7016 109PWD 7009 108 230 0960 842 0370 13 7016 143 14 230 0730 200 2950 842 0250 16_ Top Matte Black O H464 0140MBK 6 Top Porcelain specify color 464 0140POR 6 464 0140PWD 7016 142 7016 133 842 0230 842 0240 7009 114 Top Powder Coat specify color Valve Bracket 4 4 Valve S I T LP Valve S I T NG Wire Harness S lt D O lt D Page 50
22. 31 D AACCESSOMES cidad 32 Section 2 Getting Started E Positioning the Logs 32 A Design amp Installation F Mineral Wool 32 Considerations sus 6 G Glass Replacement 33 B Tools and Supplies Needed 6 H Blower Installation 33 C Inspect Appliance amp Components 6 Ignition Module Access and Battery Replacement seeesse 36 J Intake Damper Operation 36 Section 3 Appliance Location amp Clearances K Shutter Adjustment 36 A Selecting Appliance Location T B Clearances to Combustibles 7 Section 9 Operating Instructions A Before Lighting Appliance 37 Section 4 Termination Locations B Lighting Appliance 38 A Vent Termination Minimum C After Appliance is Lit 39 Clearariees isa 8 D Frequently Asked Questions 39 Section 5 Vent Information Section 10 Troubleshooting 40 A Venting Components 10 B Use of Elbows 10 C Measuring Standards 10 Section 11 Maintaining amp Servicing Appliance D How to Use the Vent Graph 11 A Mai
23. 4mm gt 6 5 8 in 162mm 168mm SLP45 BK 6 5 8 in 168mm 17 24 in 432 610mm 6 1 2 in 1 11 3 4 in 298mm A i i 6 5 8 in SLP12AM SLP12M f fp 68mm SLP6M 35 3 4 in 908mm 23 3 4 in 603mm SLP24M SLP36M 4 in 102 mm inner pipe 6 5 8 in 168 mm outer pipe Figure 12 2 SL D Series Vent Components August 1 2008 Quadra Fire Garnet T 7016 127F 9 5 8 in SLP90M 244mm 47 3 4 in 1213mm SLP48M Page 45 C Vent Components List Description HHT SL P Simpson Selkirk Amerivent Security M Multi Pack 6 Dura Vent Direct Temp Direct Secure Vent DirectVent Pro a Pipe eng avers se ere eng mea LI L Pie Length Gavenied sen ws xs Sus Pip Leng Bick mme owes om as pleno re eng BO om Pipe Lang Gavenied oe we l pe Lengm ga ons m 8 Pie Lang Ganz 4s 4m HPPplewngak omes xm Adjustable Length 37 A S E Adjustable Length 17 Gavenied supra Sd Cd Adjustable Length a A A A S risene tengo r Be Adjustable Length 11 14 Galvanized N Adjustable Length 11 14 Black fe ADTAJB fe NENNEN NENNEN usb Lang 2 Gavenied Fede Preter
24. 9 C Wiring errors can cause improper and dangerous operation Verif t ft rated wire CHD PrOPET OPE ANO ees eie Wire must have high temperature insulation Page 30 Quadra Fire Garnet T 7016 127F August 1 2008 Appliance Setup A Remove Shipping Materials Remove shipping materials from inside or underneath the firebox When your installation falls within a shaded area on the vent graph page 11 a flue restrictor must be installed for proper operation C Flue Restrictor Installation B Leg Leveling System Figure 8 1 Thread Allen bolts through nuts until flush The Allen bolts and nuts are included in the component pack inside the appliance firebox Figure 84 Installation of the flue restrictor requires the removal of the baffle located inside the firebox Remove the baffle by first removing the two screws holding the baffle in place one on each side Lift the baffle out of the bracket along the back of the firebox angle the baffle slightly and remove it from the firebox Figure 8 2 Slide assembled nuts and bolts into the slots on the legs with the nuts on the bottom Figure 8 5 With the baffle removed remove the two screws Figure 8 3 Use a 5 32 in 4mm Allen wrench to adjust legs located in the back of the firebox Reuse the screws to install up and down to desired level the flue restrictor August 1 2008 Quadra Fire Garnet T 7016 127F Page 31 D Accessories Install approved acce
25. Au Gaz pour les Maisons fllbiles et les V hicules Motoris s CAN CGA 2 17 M91 Gas Fired Gas Fired Appliances fuse at High Altitudes This appliance is manufactured for opera i Appliances for use at High Altitudes Cet appardlllest manufactur pour l op ration avec le Gaz Naturel Pour une m Gas For conversion to Mbpane Manufacturer s instructions must be used This appliance Pay be i conversion au gaz propane Manufacturier instruc Se ri a l N u m be r in a bedroom or bedsitti room in Canada remote thermostat installation is required Blaer is optional chambre coucher ou salle de s jour au Canada l installation d un thermostat distance est exig e Ventilateur Order Part BK GAS Rite power cord away from unit Do not route cord under or in front optionnel Pi ce BK GAS Eloignez le fil lectrique de l appareil Ne pas faire passer le fil lectrique au dessus ou en dessous de l appareil Hg TED CIRCULATOR VENTILATEUR CIRCULATOIRE M od e N a m e Rating Evaluation du Ventilateur No blower Sans ventilateur allum 60 Hz 150 Watts a Maximum horizontal length Avec longueur horizontale maximum Le Canada tuyau minimum 67 38 NG 69 52 LP Test La b amp Re po rt N O For use with Natural Gas For use with Propane Usage au gaz naturel Usage au gaz propane 0 2000 FT 0 2000FT Input Rate on HI BTU Hr 17 000 17 000 PWN bance e HI BTU Hr Input
26. INE TERMINATION CAP 17 3 4 in WALL THIMBLE WALL THIMBLE COVER Type C 45 Elbow in Corner Installation 45 Elbow 2 in 54mm Clearance from stove corner to combustible Y 2 in 51mm Clearance from stove corner to combustible wall Figure 5 3 Page 12 Quadra Fire Garnet T 7016 127F Step 1 Determine the desired location of the appliance Check to ensure that wall studs or roof rafters are not in the way when the venting system is attached If this is the case you may want to adjust the location of the appliance Fire Hazard Exhaust Fume Risk Impaired Performance of Appliance Ensure vent components are locked together correctly Pipe may separate if not properly joined Step 1 Determine the desired location of the appliance Check to ensure that wall studs or roof rafters are not in the way when the venting system is attached If this is the case you may want to adjust the location of the appliance Step 2 Direct vent pipe is designed with a locking connection To connect the venting system to the appliance flue outlet a twist lock adapter is built into the appliance at the factory Wall thickness may vary Remember to include wall thickness in minimum clearances when figuring venting lengths for your installation needs Note Female ends of direct vent pipe elbows are designed to slide straight onto the male ends of adjacent pipes by orienting the pipe indentations so
27. Quadra Fire Garnet T 7016 127F August 1 2008 DUADRA FIRE Accessories__GARNET T NG LP Exploded Parts Diagram Beginning Manufacturing Date 6 16 04 Ending Manufacturing Date IMPORTANT THIS IS DATED INFORMATION The most current information is located on your dealer s VIP site When ordering supply serial and model numbers to ensure correct service parts Manual Thermostat 812 3760 812 3760 Programmable Thermostat Remote Control Smart Stat Remote Control Smart Batt Speed Control Rheostat Snap Disc for Blower 125 20 230 0470 Slim Line Wall Thimble HTI DV WT Glass Assembly with Frame 7016 004 Warming Shelves Porcelain Mahogany WS GAR PMH Mesh Screen SCR GAR D Warming Shelves Matte Black WS GAR MBK August 1 2008 Quadra Fire Garnet T 7016 127F Page 51 F Service And Maintenance Log Date of Service Performed By Description of Service Page 52 Quadra Fire Garnet T 7016 127F August 1 2008 G Homeowner s Notes August 1 2008 Quadra Fire Garnet T 7016 127F Page 53 G Homeowner s Notes Page 54 Quadra Fire Garnet T 7016 127F August 1 2008 H Warranty Policy QUADRA LIMITED LIFETIME WARRANTY The Hearth amp Home Technologies limited Lifetime Warranty guarantees that the following components will work as designed for the life time of the stove or Hearth amp Home Technologies will repair or replace them These items include but are not limited to steel and cast iron comp
28. Rate on LO BTU Hr 12 000 Pui di alu e LO BTU Hr Maximum Output BTU Hr 14 500 Puissa aximum BTU Hr Main Burner Orifice 49 Orifice du Br leur Principal Minimum Inlet Pressure Inches W C 4 5 i ion Minimum de la Valve pouces W C Maximum Inlet Pressure Inches W C 7 0 Ssion Maximum de la Valve pouces W C Manifold Pressure on HI Inches W C 3 5 ression du Collecteur d chappement HI pouces W C Max Venting Blower On Ventilation Maximum Ventilateur Allum Q This appliance equipped for altitudes 0 2000 0 610m in USA and in Canada for altitudes IP 13 0m In USA for Altitudes above 2000 the vent configuration orifice or combination of both may need to be changed See Owner s Manual for information on making hese cha is appliance must be installed in accordance with local codes if any and Commonwealth of Massachusetts approved if none follow ANSI Z223 1 in USA CAN 1 B149 a Ins and use only in accordance with manufacturer s installation and operating instructions NOTE Have the gas supply line installed in accordance with local building codes by a qual and or licensed as required by the locality In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter Cet appareil est quip pour 18 v 0 0 610m aux Etats Unis et au Canada pour les altitudes de 0 4500 0 1370m Pour les altitudes au dessus de 2000 aux Etats Unis
29. Termination Cap 3 in 76mm Co Axial to Flex Liner Co Linear Connector Pipe Length Optional Flex Liner 25 ft 8m of 3 in 76mm Flex Liner Exhaust Section This section of the chimney must be Co Linear Connector Pipe Length Optional The chimney must be sealed from the 4 ft 1m section termination using a smoke shelf or a damper The seal should be 6 in 152mm below the end of the 4 ft 1m Air Intake section A ERAS u WRC 4 ft 1m of 3 in 76mm Flex Liner Air Intake Section Figure 5 24 Page 20 Showing two 35 ft 11m Sections of Type C Up amp Out Installation TERMINATION CAP TOP ADAPTOR FLASHING 4 in 102mm FLEX LINER Type D Hearth Mount Chimney Liner Termination Cap icc Alcove Clearance to Combustibles must be maintained 25 ft 8m of 3 in 76mm Flex Liner Exhaust Section This section of the chimney must be sealed Chimney must be sealed from 4 ft 1m section to termination using a smoke shelf or a damper Seal AUN should be 6 in 152mm DOO YOON RNY below end of 4 ft 1m Air IRON M 4 ft 1m of Intake section 3 in 102mm Flex Liner Air Intake Section Co Axial to Co Linear Connector In the Commonwealth of Massachusetts the word damper shall be replaced with the words flue restrictor Quadra F
30. UADRA FIRE GARNET T DIRECT VENT ROOM HEATER Owner s Manual Installation and Operation Model GARNET MBK T Jor GARNET D MBK aia us GARNET D PMH OMNI Test Laboratories Inc GARN ET D CS B GARNET D CWL DO NOT DISCARD THIS MANUAL Important operating and Read understand and Leave this manual with maintenance instructions follow these instructions party responsible for use included for safe installation and and operation operation AX WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death T LN E Glass and other surfaces are I aw hot during operation AND cool down HOT SURFACES Do not store or use gasoline or other flam x mable vapors and liquids in the vicinity of this oo will cause or any other appliance Do not touch glass until it is cooled What to do if you smell gas NEVER allow children to touch glass Do not try to light any appliance Keep children away CAREFULLY SUPERVISE children in th Do not touch any electrical switch Do not E Enneren Ine Same TOOM as use any phone in your building Alert children and adults to hazards of high temperatures Immediately Call your gas supplier from a High temperatures may ignite clothing or other flammable materials neighbor S phone Follow the gas supplier S Keep clothing furniture draperies a
31. ace Remove burner First remove ONLY the two screws indi cated in DO NOT remove the screws from the burner top Lift the burner up and out of the firebox August 1 2008 Quadra Fire Garnet T 7016 127F PILOT HOOD MILLIVOT GENERATOR THERMOCOUPLE Figure 6 2 Pull off pilot hood and set aside NOTE Do not remove the wire clip 5 32 in Allen e wrench Figure 6 3 Use a 5 32 in Allen wrench to remove the pilot injector Replace pilot injector with the appropriate size injector supplied with the appliance 35 for Propane 62 for Natural Gas Replace pilot hood snapping into position Be sure to align notch on left side of pilot hood Figure 6 4 Remove main burner orifice using a 3 8 in wrench Replace orifice with the proper size as indicated below for your gas type and venting PROPANE 56 NATURAL GAS 49 Reinstall burner Page 25 2 Valve Regulator Replacement with the kit Tighten screws securely Reference torque 25 in lb Install the enclosed identification label F to the valve body where it can be seen AX WARNING Fire Risk Fill out the conversion label and attach it to the valve cover Explosion Risk e Disconnect any electrical cords and turn off gas supply to unit before proceeding if converting fuel on an appliance already fully installed v Fire Risk Explosion Risk Gas Leak Risk Rubber gasket must be seated properly on valve face Remove u
32. ace with insulation Page 17 2 Cathedral Ceiling Step 1 Follow installation Steps 1 and 2 under vertical installation section page 15 Step 2 Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3mm larger than the support box outline Step 3 Lower the support box through the hole in the roof until the bottom of the support box protrudes at least 2 in 51mm below the ceiling Figure 5 17 Align the support box both vertically and horizontally with a level Temporarily tack the support box in place through the inside walls and into the roof sheathing Level Cathedral Ceiling Support Box 2 in 51mm Min below finished ceiling Cut hole 1 8 in 3mm greater in size than pattern of support box as it is projected onto roof line Figure 5 17 Step 4 Using tin snips cut the support box from the top corners down to the roofline and fold the resulting flaps over the roof sheathing Figure 5 18 Before nailing it to the roof run a bead of non hardening mastic around the top edges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 5 Assemble the desired lengths of pipe and elbows necessary to reach from the appliance up through the round support box Ensure that all pipe and elbow connections are in their fully twist locked position Assemble as in
33. add 3 in 76mm to this measurement and cut a section of 4 in 101mm flex pipe to that length the flex should be fully extended Step 3 Connect the end of the flex pipe section to the underside of the top adapter using four sheet metal screws Figure 5 21 Flex Pipe n S sheet Metal Screws Figure 5 21 Step 4 Pass the flex pipe down through the center of the chimney system and center the top adapter on the top of the chimney pipe Drill four 1 8 in 3mm diameter holes through the top adapter and into the chimney top Ensure that you are drilling into the metal on the chimney Twist lock the high wind termination cap onto the top adapter Figures 5 22 and 5 23 Figure 5 22 High Wind Termination Cap Sheet Metal Screws Drill Four 1 8 in 3mm Diamater Holes Figure 5 23 Step 5 Pull the flex pipe down through the ceiling support box until it protrudes approximately 3 in 76mm Connect the flex pipe to the retro connector and attach with sheet metal SCrews Step 6 Push the flex pipe back up into the ceiling support box center the retro connector and attach it to the support box with sheet metal screws Step 7 The connection between the appliance and the retro connector may be completed with sections of direct vent pipe August 1 2008 Quadra Fire Garnet T 7016 127F Page 19 4 Existing Masonry Chimney Type A amp B Co Axial to Co Linear Type A Chimney Liner
34. ass Risk of injury or property damage Before servicing Turn off gas Turn off electricity to appliance Ensure appliance is completely cooled After servicing Replace front and glass if removed Reseal and reinstall any venting removed for servicing When cleaning glass door Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL Remove and clean glass assembly Replace glass assembly and operate appliance for additional 12 hours Refer to maintenance instructions AX WARNING Annual inspection by qualified technician recommended Check Condition of glass glass assembly and glass seal Obstructions of combustion and ventilation air Obstructions of termination cap Burner ignition and operation Burner air shutter adjustment Gas connections and fittings Clean Glass Air passageways grilles control compartment Burner burner ports USE CAUTION WHEN CLEANING HANDLING CERAMIC BURNER Risk of Fire Delayed ignition or explosion Exposure to combustion fumes e Odors WARNING Inspect external vent cap regularly Ensure no debris blocks cap Combustible materials blocking cap may ignite Restricted air flow affects burner operation Page 42 Quadra Fire Garnet T 7016 127F August 1 2008 A Maintenance
35. ch on the control panel to ON If thermostat is to be used leave switch in OFF position and set the thermostat to desired setting 14 Reconnect electrical power to appliance Bo PILOT HOOD HERMOCOUPLE x TO TURN OFF GAS TO APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if service is to be performed 3 Push in gas control knob slightly and turn clockwise to OFF position Page 38 Quadra Fire Garnet T 7016 127F August 1 2008 D After Appliance is Lit Initial Break in Procedure When you light your appliance you may notice that it pro duces heat which does have an associated odor or smell If you feel this odor is excessive it may require the initial three to four hour continuous burn on high followed by a second burn up to 12 hours to fully drive off any odor from paint and lubricants used in the manufacturing process Condensation on the glass is normal NOTE The appliance should be run three to four hours on the initial start up Turn it off and let it cool completely Remove and clean the glass Replace the glass and run the appliance for an additional 12 hours This will help to cure the products used in the paint and logs During this break in period it is recommended that some windows in the house be opened for air circulation This will help avoid setting off smoke detectors and help eliminate any odors associated with the a
36. cident or misuse of the product shall nullify this warranty Labor to repair or replace items covered under the limited Lifetime Warranty will be covered for the first five years per our warranty ser vice fee reimbursement schedule Parts covered under the limited Lifetime Warranty will be covered for the lifetime of the appliance up to a maximum of ten 10 years after Hearth amp Home Technologies discontinues the model and two 2 years for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The re placement of consumer replaceable items and installation of upgraded component parts do not quality for a service call fee and will not be covered This limited Lifetime Warranty does not extend to or include surface finish on the appliance door gasketing glass gasketing glass fire brick pellet logs kaowool or other ceramic insulating materials It does not cover installation or operational related problems such as overfiring use of corrosive driftwood downdrafts or spillage caused by environmental conditions nearby trees buildings hilltops moun tains inadequate venting or ventilation excessive offsets or negative air pressures caused by mechanical systems such as furnaces fans clothes dryers etc Any installation construction transportation or other related costs or expenses arising from defective part s repair replacement etc wi
37. driver 11 16 wrench and a 3 8 wrench FROM THE KIT YOU WILL NEED Blower in mounting with wiring harness speed control rheostat speed control knob pal nut snap disc screws and 1 zip tie FROM THE APPLIANCE COMPONENT BAG YOU WILL NEED Snap disc bracket 10 32 nut KIT CONTENTS 1 Blower Mounted in Housing 2 Speed Control Knob 3 Pal Nut 4 Ceramic Snap Disc 5 Speed Control Rheostat 6 Wire Harness attached to Blower 7 12 Screws 8 12 inch Glass Tape 9 1 Zip Tie 10 Bracket 1 11 Snap Disc Bracket August 1 2008 Quadra Fire Garnet T 7016 127F Figure 8 10 Open and inspect contents of the blower kit The contents of the kit are listed at left If any of the parts are missing or damaged please contact your dealer for replace ments NOTE Not all parts will be used for this installation Figure 8 11 Remove the top of the appliance and set aside Remove the back shield by removing the two screws along the top of the shield Place the blower on the floor behind the appliance and route the ends of the wiring harness through the rubber grommet on the underside Holding the blower in place attach it to the appliance with four of the screws provided Page 33 SNAP DISC SNAP DISC BRACKET x SPADE TERMINALS Figure 8 12 Install the snap disc A snap disc bracket is located in the appliance s component bag Bend the two spade temi nals on the snap disc f
38. ess wire length 7 Low voltage and 110 VAC voltage cannot be shared within the same wall box August 1 2008 Quadra Fire Garnet T 7016 127F 8 Ensure the thermostat is mounted level for accurate readings 9 The thermostat should be mounted on an inside wall and not in direct line with the appliance convection air 10 If the thermostat is located too close to the appliance you may need to set the temperature setting slightly higher to maintain the desired temperature in your home Do not connect this appliance to a thermostat serving any other appliance Bedroom installation in Canada requires this appliance to be connected to a thermostat Shock hazard This appliance is equipped with a three pronged grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug C Standing Pilot Ignition System Wiring This appliance DOES NOT require 110 VAC supply for operation A wiring diagram is shown in Figure 7 1 on the next page This appliance is equipped with a millivolt control valve Page 29 Pilot Igniter m gt Thermocouple p lt J vl JI n PILOT ASSEMBLY ON OFFAES Switch A HH TH Figure 7 1 CAUTION i m 3111 Shock hazard Label all wires prior to disconnection when servicing controls P 9 Replace damaged wire with type 105
39. h amp Home Technologies 1445 North Highway Colville WA 99114 Division of HHT INDUSTRIES Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer please visit our web site at www quadrafire com CAUTION Do NOT discard this manual Important operating and maintenance instructions included Read understand and follow these instruc tions for safe installation and operation Leave this manual with party responsible for use and operation Your Records for Model Garnet T DEALERSHIP WHERE PURCHASED SERIAL NUMBER DATE PURCHASED DATE INSTALLED DEALER TELEPHONE This product may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 6006743 6019099 6048195 6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 6769426 6774802 6796302 6840261 6848441 6863064 6866205 6869278 6875012 6880275 6908039 6919884 D320652 D445174 D462436 Canada 1297749 2195264 2225408 2313972 Australia 780250 780403 1418504 or other U S and foreign patents pending HEARTH
40. inlet to building or the combustion air inlet to any other appliance a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor or meets Note 2 NOTE 1 On private property where termination is less than 7 feet above a sidewalk driveway deck porch veranda or balcony use of a listed cap is suggested See vents components pages NOTE 2 Termination in an alcove space spaces only open on one side and without an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be at least 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap 3 All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap NOTE 3 Location of the vent termination must not interfere with access to the electrical service Figure 4 4 Quadra Fire Garnet T 7016 127F X NN CAIN AAV x XS 00 X OK AREA WHERE TERMINAL IS NOT PERMITTED 3 ft U S A 6 ft Canada clearance to a mechanical powered air supply inlet as clearance above paved See Note 1 sidewalk or a paved driveway located on public property clearance under
41. ire Garnet T 7016 127F August 1 2008 CAUTION Ensure that existing chimney is functionally sound and clean Have inspection done by qualified chimney sweep or professional installer BEFORE converting to direct vent appliance Step 1 Before cutting any holes assemble the desired sections of direct vent pipe to determine the center of the masonry penetration Step 2 Once the center point of the penetration has been determined cut a 6 in 152mm diameter hole in the masonry If the hole is too large the retro connector might not mount properly if the hole is too small the appliance might starve for intake air If there is a frame wall in front of the masonry wall cut and frame a 10 in 254mm square opening in the wall centered around the 6 in 152mm masonry opening If there is sheet rock only no studs in front of the masonry the 10 in 254mm opening is still needed but does not need to be framed If the hole is framed a wall thimble is required This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles Figure 5 25 Studwall 10 in x 10 in 254mm x 254mm framed opening in wall Retro Connector Wall Thimble Cover 4 Masonry Bolts Not Included NOTE FORHEARTH APPLICATIONS REFER TO PAGE 19 FOR THE USE OF A CO AXIAL TO CO LINEAR APPLIANCE CONNECTOR Figure 5 25 Step 3 Secure the flashing to the top of the masonry chimney usi
42. irements of this subdivision can not be met at the time of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS August 1 2008 Quadra Fire Garnet T 7016 127F Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installa tion unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a 1 through 4 Exemptions The following equipment is exempt from 248 CMR 5 08 2 a 1 through 4 The equipment listed in Chapter 10 entitled Equipment Not Required To Be Vented in the m
43. it protrudes through the exterior wall See Figure A on the next page Use that mark as a guide to trim off excess heat shield with a pair of sheet metal shears Figure 5 34 When installing the trim ring heat shield assem bly make sure the trim ring is centered in the hole and that the shield is above the pipe There must be a minimum of 3 4 in 19mm minimum clearance maintained to combus tibles from the top of the heat shield Ensure that framing on the inside of the wall is a mini mum inner framing diameter of 10 in x 10 in 254mm x 254mm The four trim ring mounting screws provided should be replaced with appropriate fasteners for stucco brick con crete or other types of sidings Page 23 FIG A 90 DEGREE ELBOW Place mark where protrudes through exterior wall to cut off excess 90 ELBOW see ZA EE PIPE LENGTH PKK KK PKK KKK 10000006 TRIM RING SOLID OR VENTILATED FIG C MINIMUM CLEARANCE INTERIOR WALL 2 in 51mm clearance from rear of stove CENTER LINE Figure 5 33 Page 24 LATONA DAN PODIO ee tes MODAN 4 _ XX AAAAAA Use HEAT SHIELD or WALL THIMBLE TERMINATION CAP FIG B 45 DEGREE ELBOW NOTE Wall Thimble removed to show Heat Shield TRIM RING HEAT SHIELD OVER PIPE from stove corner to combustible wall eZ AZ VA 2 in
44. ive surface See page 33 the following information before installing e Remove log set and component pack from firebox e Where th li is to be installed AE PI AO Report to your dealer any parts damaged in shipment The vent system configuration to be used particularly the condition of the glass e Gas supply piping Read all of the instructions before starting the instal lation Follow these instructions carefully during the e Electrical wiring i installation to ensure maximum safety and benefit e Whether optional accessories devices such as a blower thermostat or remote control are desired F Hearth amp Home Technologies disclaims any responsibility for and the warranty will be Keep appliance dry voided by the following actions Mold or rust may cause odors e Water may damage controls Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth amp Home B Tools and Supplies Needed Technologies T Improper positioning of the gas logs or the glass door Before beginning the installation be sure that the following Installation and or use of any component part not approved tools and building supplies are available Note Not all by Hearth amp Home Technologies tools will apply to every installation Any such action may cause a fire hazard Reciprocating saw Variable Speed
45. k for proper installation and freedom from debris or blockage installation 6 Glass soots a Flame impinge Adjust the log set so that the flame does not excessively impinge on it ment Check that logs are placed according to installation instructions b Improper shutter Adjust the air shutter at the base of the burner setting c Debris around Inspect the opening at the base of the burner NO MATERIAL SHOULD opening at base of BE PLACED IN THIS OPENING burner 7 Flame burns blue a Insufficient Ensure that the vent cap is installed properly and free of debris Ensure and lifts off burner oxygen being sup that the vent system joints are tight and have no leaks plied Ensure that no debris has been placed at the base of or in the area of the air holes in the center of the base pan beneath the burner Ensure that the glass is tightened properly on the appliance particu larly on top corners August 1 2008 Quadra Fire Garnet T 7016 127F Page 41 Maintaining and Servicing Your Appliance 11 Although the frequency of your appliance servicing and maintenance will depend on use and the type of installation CAUTION a qualified service technician should perform an appliance check up at the beginning of each heating season Ge Handle glass assembly with care NOTE Clean glass after initial 3 4 hours Z operation Longer operation without cleaning A WARNING 2 glass may cause a permanent white film on gl
46. la configuration dugsentilateur e ou les deux peuvent possiblement avoir tre chang Voyez le manuel du propri taire pour les informations sur ces changements Cet appareil doit tre install e gl avec cod pcaux s il y a lieu et approuv par dans la R publique de Massachusetts sinon lisez ANSI Z223 1 CAN 1 B149 Installez et utilisez en accords avec les instructions iion eWLop rWion du manufacturier REMARQUE Le conduit gaz doit tre install conform ment aux codes de construction locaux L installation doit tre effectu e par un technicien qualife ieu SAS licence de mani re respecte r glememis municipaux Dans la R publique de Massachusetts l instalaatOn doit tre ef etw e par un plombier ou un installateur Lasperet EC A measurement is from stove top not side Side of stove top to side wall 6 in 15cm Du cot du po le au cot du mur Rear of stove to back wall 2 in bcm Le contr le arri re au mur arri re Corner of stove top to side wall Left 2 in bcm Du coin arri re du po le au mur de cot gauche Corner of stove top to side wall Right 2 in bcm Du coin du dessus du po le au mur de cot droit acces a la valve Minimum Alcove Height 43 in 109cm Hauteur minimum du plancher au plafond Maximum Alcove Depth 36 in 91cm Profondeur maximum de l alcove Minimum Alcove Width 30 in 76cm Largeur minimum de l alcove Mantle Clearance from stove top 19 1 2 in 50cm Espace libre du po le au manteau
47. leted as each model undergoes a quality and performance control inspection From design to fabrication to shipping This commitment begins with our research of the market X Our guarantee of quality is more than a word it s Quadra including Voice of the Customer contacts ensuring we Fire tradition and we proudly back this tradition with a Lim make products that will satisfy your needs Our Research ited Lifetime Warranty advanced technology to achieve the optimum operation of the warmth and comfort of your hearth appliance Thank our stoves inserts and fireplaces And yet we are old fash you for choosing Quadra Fire ioned when it comes to craftsmanship Each appliance is SAMPLE OF SERIAL NUMBER SAFETY LABEL LOCATION HANGING ON A CHAIN ON BACK OF APPLIANCE ciii Ae Laboratories Inc VENTED GA O ONU YY OLID FUEL 1445 North Highway Report No Rapport Num ro FOURNAISE AU GAZ AVEC VENTILATIBINNE PAS UTILISER AVEC LE Colville WA 99114 061 S 35c 5 COMBUSTIBLE BDLIDE www quadrafire com gie ODEL MOD LE GARNET T Serial No Num ro du E 1 APPROVED FOR CANADA AND USA TO APPROUV POUR LE CANADA ET LES TATS E ANSI Z21 88b 2003 CB 2 33b 2003 Vented Gas Fireplace Heaters and applicable sed ANSI Z21 88b 2003 CSA 2 33b 2003 Fournaisegau Gaz avec Ventilation et les sections applicable de UL 307b Gas Burning Heating Afliances for Manufactured Homes and Recreational Vehicles CA AT Appareils de Chauffage
48. ll installation instructions for all Product Approved side wall horizontally vented gas fueled equipment all vent ing instructions all parts lists for venting instructions and or all venting design instructions shall remain with the appli ance or equipment at the completion of the installation See Gas Connection section for additional Common wealth of Massachusetts requirements Page 5 Getting Started A Design amp Installation Considerations C Inspect Appliance amp Components ate with all combustion air drawn from outside of the building OA AWARNNG o 4h WARNING and all exhaust gases expelled to the outside No additional air Source is required E Inspect appliance and components for damage Damaged parts may impair safe CAUTION operation Do NOT install damaged components Do NOT install incomplete components Check building codes prior to installation Do NOT install substitute components Installation MUST comply with local regional state and national codes and regulations Consult local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits Quadra Fire direct vent gas appliances are designed to oper Report damaged parts to dealer Carefully remove the appliance and components from the packaging e Remove cast door and glass door and set aside on pro When planning an installation it is necessary to determine tect
49. ll not be covered by this warranty nor will Hearth amp Home Technologies assume responsibility for them Further Hearth amp Home Technologies will not be responsible for any incidental indirect or consequential damages except as results in damage to the interior or exterior of the building in which this appliance is installed This limited Lifetime Warranty does not apply to the venting components hearth components or other accessories used in conjunction with the installation of this product not manufactured by Hearth amp Home Technologies This warranty is void if the stove has been overfired or operated in atmospheres contaminated by chlorine fluorine or other damaging chemicals the stove is subjected to prolonged periods of dampness or condensation or there is any damage to the stove or other compo nents due to water or weather damage which is the result of but not limited to improper chimney or venting installation Hearth amp Home Technologies may at its discretion fully discharge all obligations with respect to this warranty by either repairing or replacing the unit or refunding the wholesale price of the defective part s This limited Lifetime Warranty is effective on all appliances sold after May 1 2002 and supersedes any and all warranties currently in existence Policy 250 8620 Rev K August 1 2008 Quadra Fire Garnet T 7016 127F Page 55 I Contact Information QUADRA CONTACT INFORMATION IRE Heart
50. n the ceiling and mark the spot where the vent will penetrate the roof Determine if ceiling joists roof rafters or other framing will obstruct the venting system You may wish to relocate the appliance or to offset as shown in Figure 5 12 on the next page to avoid cutting loadbearing members When location is determined drill small hole Page 15 connected to Wall Strap Wall Strap Figure 5 12 Step 3 To install the round support box wall thimble cover in a flat ceiling cut a 10 in 254mm square hole in the ceiling centered on the hole drilled in Step 2 Frame the hole as shown in Figure 5 13 Ceiling 275 227 Joists I 1 1 2 in 38mm Long Wood Screws Figure 5 13 Step 4 Assemble the desired lengths of pipe and elbows necessary to reach from the appliance up through the round support box Ensure that all pipe and elbow connections are in their fully twist locked position Assemble as instructed Step 5 Cut a hole in the roof centered on the small drill hole placed in the roof in Step 2 The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles as specified Continue to assemble lengths of pipe and elbows Page 16 Quadra Fire Garnet T 7016 127F necessary to reach from the ceiling support box wall thimble up through the roof line Galvanized pipe and elbows may be utilized in the attic as well as above the roofline The galvanized finish
51. nd other combustibles instructions away f you cannot reach your gas supplier call the fire department In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas e Installation and service must be performed fitter by a qualified installer service agency or the See Table of Contents for additional Commonwealth of Mas gas supplier sachusetts requirements This appliance may be installed as an OEM installation in manufactured home USA Installation and service of this appliance should be only or mobile home and must be installed in accordance with the manufacturer s performed by qualified personnel Hearth amp Home instructions and the manufactured home construction and safety standard Title 24 Technologies suggests NFI certified or factory trained CFR Part 3280 or Standard for Installation in Mobile Homes CAN CSA Z240MH professionals or technicians supervised by an NFI certified professional This appliance is only for use with the type s of gas indicated on the rating plate www quadrafire com 7016 127F August 1 2008 Congratulations and Welcome to the Quadra Fire Family Hearth amp Home Technologies welcomes you to our tradition meticulously fabricated and gold and nickel surfaces are of excellence In choosing a Quadra Fire appliance you hand finished for lasting beauty and enjoyment Our pledge have our assurance of commitment to quality durability to quality is comp
52. ng a bead of non hardening sealant adhesive If the flashing is larger than the top of the chimney cut and fold flashing as needed to fit chimney Figure 5 26 Cut and bend flashing as needed NC fit LY LY QD Gp Sealant adhesive Figure 5 26 Step 4 To determine the length of flex needed measure from 3 in 76mm above the top of the flashing down to the level of the opening Add the distance from the center of the chimney out through the wall Cut a piece of 4 in 102mm flex to this length extended to its nominal length Be sure to leave 2 3 in 51 76mm of flex above the existing chimney to allow for connection to the termination kit Step 5 Connect the flex liner to the top adapter using three sheet metal screws Figure 5 21 page 19 Step 6 Feed the flex liner through the flashing into the chimney Carefully feed the flex liner down the chimney to the bottom and out the opening in the masonry wall forming an angle to line up the flex liner with the vent opening on the appliance Fire Risk Explosion Risk Do not let the flex liner sag below the level at which it will connect to the appliance or connector This could allow hot gas to become trapped and potentially become a fire hazard The flex liner path should always be sloped up toward the termination cap Step 7 If additional lengths of flex liner are needed to span the chimney height use a flex coupler to connect the pieces of flex line
53. ng and handling Fire hazard Do NOT change the valve settings This valve has been preset at the factory e Changing valve settings may result in fire hazard or bodily injury Page 28 Quadra Fire Garnet T 7016 127F August 1 2008 Electrical Information A Recommendation for Wire See B5 below for recommended maximum lead length two wire when using wall thermostat switch NOTE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C221 1 B Connecting to the Appliance Wire 110v to electrical junction box Do NOT wire 110v to the valve Do NOT wire 110V to wall switch Incorrect wiring will damage millivolt systems wis 1 This appliance may be used with a wall switch wall mounted thermostat and or a remote control 2 If using thermostat use one compatible with a millivolt gas valve system 3 Follow parameters for locating thermostat see individ ual thermostat instructions to ensure proper operation of appliance 4 Use low resistance thermostat wire for wiring from igni tion system to the wall switch and thermostat 5 Use the following chart for wire sizing Wire Size Max Length 16 gauge 65 feet 18 gauge 40 feet 20 gauge 25 feet 22 gauge 18 feet 6 Keep wire lengths as short as possible by removing any exc
54. nstructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot that must be lit manually When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to the lowest setting if applicable and turn off the switch at the control panel Disconnect the power from the appliance Open the door of the appliance May need to remove face front first
55. nt configuration specifications MUST be followed This product is tested and listed to these specifications Appliance performance will suffer if specifications are not followed Diagonal runs have both vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45 elbows may be used in place of one 90 elbow On 45 runs one foot of diagonal is equal to 8 1 2 in 216mm horizontal run and 8 1 2 in 216mm vertical run A length of straight pipe is allowed between two elbows See Figure 5 4 lt Horizontal Figure 5 1 C Measuring Standards Vertical and horizontal measurements were made using the following standards Pipe measurements are from center line to center line Horizontal terminations are measured to the outside of the mounting surface flange of termination cap See Figure 4 1 on page 8 e Vertical terminations are measured to the top of the last pipe before termination cap Horizontal pipe installed level with 1 4 in rise August 1 2008 D How to Use the Vent Graph 1 Measure the vertical distance from the center line of the flue pipe to the center of the 90 elbow On the graph below draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line 2 From the point of this intersection draw a vertical line to
56. nt pipe into the vent termination cap assembly It is important that the vent pipe extend into the vent termination cap a sufficient distance so as to result in a minimum pipe overlap of 1 1 4 in 32mm Secure the connection between the vent pipe and the vent termination cap by attaching the two sheet metal strips extending from the vent termination cap assembly into the outer wall of the vent pipe Use the two sheet metal screws provided to connect the strips to the pipe section Figure 5 9 Page 14 Quadra Fire Garnet T 7016 127F 1 4 in 6mm Fold Strap Here Sheet Metal Screw Wall Thimble Cover Ceiling Firestop as Required by Local Jurisdiction Note The attachment from the vent pipe to the vent termination cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding WARNING Fire Hazard Exhaust Fume Risk Impaired Performance of Appliance Ensure vent components are locked together correctly Pipe may separate if not properly joined Do NOT connect a pipe section to a termination cap without using the telescoping flue section found on the termination cap Burn Risk Local codes may require installation of a cap il shield to prevent anything or anyone from hd HET touching the hot cap August 1 2008 G Vertical Termination 1 Direct Vent Pipe VERTICAL TERMINATION CAP STORM COLLAR am FLASHING FIRESTOP D 7 J EXJ
57. ntenance Tasks 43 E Venting Guidelines 11 F Horizontal Termination 12 G Vertical Termination 15 Section 12 Reference Materials H Slim Line Wall Thimble 23 A Appliance Dimension Diagram 44 B Vent Components Diagram 45 C Vent Components List 46 Section 6 Gas Information D Service Parts List 48 A Fuel Conversions 25 E Accessories LL puse us ota e Um 51 B Gas Pressures ccccocccccccnoconnncocnocunnnnanos 27 F Service and Maintenance Log 52 C Gas Connection 27 G Homeowners Notes 53 H Warranty Policy 55 l Contact Information 56 August 1 2008 Quadra Fire Garnet T 7016 127F Page 3 Listing and Code Approvals 1 A Appliance Certification MODEL LABORATORY OMNI Test Laboratories Inc 061 S 35c 5 TYPE Direct Vent Gas Heater STANDARD ANSI Z21 88a 2003 CSA 2 33a 2003 UL307b CAN CBA 2 17 M91 The product is listed to ANSI standards for Vented Gas Appliance Heaters and applicable sections of Gas Burning Heating Appliances for Manufactured Homes and Recre ational Vehicles and Gas Fired Appliances for use at High Alti
58. onents all gas burners gas logs combustion chambers heat exchanger systems stainless steel firebox components plating doors glass damaged by thermal breakage steel baffle supports steel and ceramic baffles and manifold tubes Labor is for the first five years Lifetime Warranty THREE YEAR WARRANTY Our pellet firepots are covered under Hearth amp Home Technologies three year warranty program Labor is for 3 years TWO YEAR WARRANTY All electrical components such as but not limited to blowers wiring vacuum switches speed controls control boxes thermodisc switches pilot assembly gas valves thermostats and remotes are covered under Hearth amp Home Technologies two year warranty program Effec tive April 2005 igniters are also covered under the two year warranty Labor is for two years ONE YEAR WARRANTY Porcelain and Powder Coat finishes are warranted against manufacturer defects for one year Labor to repair or replace these parts is covered for one year reimbursed per our warranty service fee schedule CONDITIONS This warranty is non transferable and is made to the original retail purchaser only provided that the purchase was made through an authorized dealer of Hearth amp Home Technologies It must be installed and operated at all times in accordance with the Installation and Operating Instructions furnished with this product as well as any applicable local and national codes Any alteration willful abuse ac
59. opile if the reading is below the minimum Page 40 Quadra Fire Garnet T 7016 127F August 1 2008 Symptom Possible Cause Corrective Action 3 Continued c Defective valve Turn the valve knob to the ON position Place the ON OFF switch in the ON position Check the millivolt meter at the thermopile terminals The millivolt meter should read greater than 125mV If the reading is accept able and if the burner does not come on replace the gas valve d Plugged burner Check the burner orifice for stoppage Remove stoppage orifice e Wall switch or Follow the corrective action in Symptom and Possible Cause 1 a wires are defective Check the switch and wiring Replace where defective 4 Frequent pilot outage a Pilot flame may Clean and adjust the pilot flame for maximum flame impingement on problem be too high or too thermocouple Follow lighting instructions carefully low or blowing high causing safety pilot to drop out 5 The pilot and main a No LP in tank Check the LP propane tank Refill the fuel tank burner extinguish while b Inner vent pipe Check for proper vent connection at flue collar and all vent joints in operation leaking exhaust gases back into the system c Horizontal vent The horizontal vent cap should slope down only enough to prevent any improperly pitched water from entering the appliance d Bad thermopile or Replace if necessary thermocouple e Improper vent cap Chec
60. ost current edition of NFPA 54 as adopted by the Board and e Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separated from the dwelling building or structure used in whole or in part for residential purposes MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided When the manufacturer of Product Approved side wall horizontally vented gas fueled equipment provides a vent ing system design or venting system components with the equipment the instructions provided by the manufacturer for installation of the equipment and the venting system shall include Detailed instructions for the installation of the venting sys tem design or the venting system components and A complete parts list for the venting system design or venting system Gas Equipment Venting System NOT Provided When the manufacturer of a Product Approved side wall hor izontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special vent ing systems the following requirements shall be satisfied by the manufacturer The referenced special venting system instructions shall be included with the appliance or equipment installation instructions and The special venting system shall be Product Approved by the Board and the instructions for that system shall include a parts list and detailed installation instructions A copy of a
61. pper and lower back shield Loosen the set col lars on the extension rods with the 3 32 in Allen wrench Remove the rods and adapter cap Dono install a valve or regulator that has been dropped Fire Risk Explosion Risk e f the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation of this conversion kit The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied with the kit Figure6 5 Turn control knob to the OFF position ensure that gas supply to the valve has been turned off Using a Torx TH20 or slotted screwdriver remove the three pressure reg ulator mounting screws A pressure regulator tower B and diaphragm C Figure 6 6 Ensure that the rubber gasket D is properly positioned and install the new HI LO pressure regulator assembly to the valve using the new screws E supplied Page 26 Quadra Fire Garnet T 7016 127F August 1 2008 B Gas Pressures Proper input pressures required for optimum appliance per formance gas line sizing requirements need to be followed from NFPA51 AX WARNING py Fire Risk Explosion Hazard High pressure will damage valve Disconnect gas supply piping BEFORE pre
62. ppliance s initial burning Fire Risk High Temperatures JN i Keep combustible household items away from appliance Do NOT obstruct combustion and ventilation air e Do NOT place combustible items on top of or in front of appliance Keep furniture draperies away from appliance E Frequently Asked Questions CAUTION Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Smoke and odors released during initial operation Open windows for air circulation Leave room during initial operation e Smoke may set off smoke detectors Smoke and odors may be irritating to sensitive individuals Fire Hazard Keep combustible materials gasoline and other flammable vapors and liquids clear of appliance Do NOT store flammable materials in the appliance s vicinity Do NOT use gasoline lantern fuel Kerosene charcoal lighter fluid or similar liquids in this appliance Combustible materials may ignite ISSUE SOLUTIONS Condensation on the glass This is a result of gas combustion and temperature variations As the appliance warms this condensation will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the appliance is allowed to burn for 20 to 40 minutes Odor
63. r an audible click will turn the blower OFF Turning the control knob to the right clockwise until you hear a click will turn the blower ON Turning the control knob further to the right will reduce the speed of the blower August 1 2008 Thermal Disc WHITE Qo Fan Speed Control WHITE lt O T co Power Cord 110 VAC Ground Strain Relief j Bushing 3 PA Fan Assembly Figure 8 15 Blower Wiring Diagram August 1 2008 Quadra Fire Garnet T 7016 127F Page 35 I Ignition Module Access and Battery Replacement Figure 8 16 The ignition module is located under the appliance attached to the decorative cover Lift off the appliance top and place it on a flat surface with the porcelain side up to prevent damage Remove the appliance front by sliding it upwards in the grooves being careful not to chip the porcelain Lay the appliance front face up on a flat surface With the cast iron front of the appliance removed remove the decorative cover located under the appliance To remove the cover remove the two screws on the front of the appliance that hold the cover in place Pull the cover forward down and out The module will then be accessible for service or battery replacement The single AA 1 5V battery that powers the ignitor is located in the module To replace the battery open the battery compartment and remove the old battery Replace the battery making sure the polarity is
64. r any vertical termination a minimum of 6 in 152mm vertical must be used EXCEPTIONS FOR HORIZONTAL INSTALLATIONS The maximum horizontal vent run is 30 in 762mm The maximum horizontal vent run with a 45 elbow is 18 in 457mm No external minimum rise is required The minimum horizontal vent run is 6 in 152mm NOTE If your installation falls within the gray shaded area on graph see information on intake damper operation on page 36 In the Commonwealth of Massachusetts the word damper shall be replaced with the words flue restrictor VERTICAL DISTANCE FROM APPLIANCE TO 90 ELBOW Example 1 8 6 ft 2m Minimum Vertical Termination y FANNIN PEARL BT TRAX IX X P6 IX X KKK RO 6 in 152mm Minimum starter pipe Figure 5 2 August 1 2008 Quadra Fire Garnet T 7016 127F Install Flue Restrictor 12 414 15 Termination Cap 30 in 762mm Maximum Horizontal run with no vertical pipe and with 1 4 in 6mm rise per foot Must use approved Termination Cap Page 11 F Horizontal Termination Type A Up amp Out Installations for Top Vent Configurations He eS 7 PIPE LENGTH WALL THIMBLE WALL THIMBLE COVER 90 ELBOW center line A TERMINATION CAP PIPE LENGTH Hl CAXXU000U093 EJ CANSA WM NOMAS PA RIN PA AA XXXXXXXXI Type B Rear Installations for Use with Rear Vent Kit CENTER L
65. r together Connect the flex to the coupler by using four sheet metal screws for each side Figure 5 27 on the next page Quadra Fire Garnet T 7016 127F August 1 2008 Page 21 Flex Liner 6 in 152mm diameter opening in masonry wall Flex Coupler Sheet Metal Screws Retro Connector Figure 5 27 3 Masonry Bolts Not included Step 8 Figure 5 29 Secure the top adapter to the flashing Use three sheet metal screws through the side of the top adapter into the flange on the flashing Figure 5 28 Twist lock the high Step 10 wind termination cap on to the top adapter Slide wall thimble cover over retro connector and secure with masonry bolts Figure 5 30 If you have a framed wall in front of the masonry use wood screws to mount wall High Wind thimble cover to framed wall over retro connector and 10 Termination Cap in 254mm square framed opening Figure 5 25 page 21 If needed add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimble cover Top Adaptor ad Sheet Metal Screws Retro Connector Figure 5 28 Wall Thimble Cover 4 Masonry Bolts Step 9 Not included Attach the flex to the retro connector Use three sheet metal screws to attach the flex liner to the connector Figure 5 29 Mount the retro connector to the masonry wall using masonry bolts Redrill larger holes on connector as needed Step 11 Be careful to ensure that
66. r wood screws provided should be replaced with appropriate fasteners for stucco brick concrete or other types of sidings 2 A termination cap with a built in vinyl siding standoff is highly recommended on a building with vinyl siding The pilot hole will be 2 in 51mm closer to the bottom of the square than the top Using a framing square draw a 14 in x 14 in 356mm x 356mm square around the pilot hole in the siding See Figure 5 7 on the next page Page 13 Figure 5 7 NOTE Some termination caps may cause the vent pipe to be off center on the flashing Ensure that proper clearances to combustible materials are maintained If you are not using an approved termination cap with a built in vinyl siding standoff on a building with vinyl siding a vinyl siding standoff should be installed between the vent cap and the exterior wall Figure 5 8 Attach the vinyl siding standoff to the horizontal vent termination The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material Vent terminal shall not be recessed into a wall or siding Remove siding from the area where the standoff will be located VINYL SIDING Bolt horizontal top to vinyl standoff WALL THIMBLE COVER Vinyl siding standoff with siding beneath removed WALL THIMBLE Figure 5 8 Step 5 Place the wall thimble cover over the pipe assembly and slide the appliance and vent assembly towards the wall carefully inserting the ve
67. rom a horizontal to a vertical position Insert the snap disc through the hole in the snap disc bracket and attach the two white wires from the wiring harness to the snap disc Figure 8 13 With the cast iron front of the appliance removed remove the decorative cover located under the appliance To remove the cover remove the two screws on the front of the appliance that hold the cover in place Pull the cover forward down and out Attach the snap disc bracket to the stud located under the left side of the appliance using the 10 32 nut Page 34 Quadra Fire Garnet T 7016 127F p T Figure 8 14 Install the speed control rheostat The speed control mounts to the decorative cover previously removed Insert the stem of the speed control through the hole located on the right side of the cover Secure with the pal nut using an 11 16 in wrench Attach the black and white wires that were routed under the appliance Push the speed control knob onto the stem and re attach the decorative cover Secure the wires up and out of the way using the zip tie provided Plug in the blower NOTE The blower will not run until the appliance has heated up enough to activate the snap disc This can take up to 15 minutes depending on the temperature of the room Likewise the blower will not turn off until the appliance has cooled off enough to turn off the snapdisc Turning the control knob to the left counterclockwise until you hea
68. ryover to all ports Verify there is no ignition delay 5 9 Inspect thermocouple thermopile sensor rod for soot corrosion and deterioration Clean with emery cloth or replace as required 10 Verify millivolt output Replace as necessary Venting 1 Inspect venting for blockage or obstruction such as bird nests leaves etc 2 Confirm that termination cap remains clear and unobstructed by plants etc 3 Verify that termination cap clearance to subsequent construction building additions decks fences or sheds has been maintained 4 Inspect for corrosion or separation 5 Verify weather stripping sealing and flashing remains intact Remote Controls 1 Verify operation of remote 2 Replace batteries in remote transmitters and battery powered receivers August 1 2008 Quadra Fire Garnet T 7016 127F Page 43 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For clearances refer to Section 3 AR INA Y NN OX KK X XX AU A OY YY NINA NON Location inches Milimeter Location inches Millimeter P A aras ms o rae m L8 we ase e 2585 600 Figure 12 1 Appliance Dimensions Page 44 Quadra Fire Garnet T 7016 127F August 1 2008 B Vent Components Diagram 6 1 2 in AN XS A 6 3 8 in 162mm 6 1 2 in 165mm 9 5 8 in mem T 6 3 8 in 24
69. ssories per instructions included with accessories Refer to Section 12 for appropriate accesso ries ay Shock or fire risk Use ONLY optional accessories approved for this appliance Using non listed accessories voids warranty Using non listed accessories may result in a safety hazard Only Hearth amp Home Technologies approved accessories may be used safely E Positioning the Logs While still breakable the logs do not become fragile until after the appliance is burned and they have cured After curing any handling must be done with care as breakage can easily occur PLEASE NOTE Logs have been designed to work specifically with the burner of this appliance Exact placement will ensure proper operation of your gas appliance and reduce sooting The three piece log set is packed in the components box and consists of the following Qty Name Diagram 1 Rear Log Fig 1 1 Left Log Fig 2 1 Right Log Fig 3 Figure 8 6 Gently remove top of unit and set aside Remove cast face by sliding straight up and set aside Remove the glass by releasing the latch located on the top of the appli ance Lean glass frame forward and lift out Place the notch in the Rear Log over the pilot assembly Push the log all the way to the rear of the firebox Page 32 Quadra Fire Garnet T 7016 127F Figure 8 7 Align left front log with notch in burner and notch on rear log Figure 8 8 Align right front log with burner and
70. ssure testing gas line at test pressures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig M Verify inlet pressures High pressure may cause overfire condition Low pressure may cause explosion Install regulator upstream of valve if line pressure is greater than 1 2 psig Pressure requirements for appliance are shown in the table below PRESSURE NG IP Minimum Inlet Pressure 5 inches w c If the pressure is not sufficient ensure 1 the piping used is large enough 2 the supply regulator is adequately adjusted 3 that the total gas load for the residence does not exceed the amount supplied The supply regulator the regulator that attaches directly to the residence inlet or to the propane tank should supply gas at the suggested input pressure listed above Contact the local gas supplier if the regulator is at an improper pressure August 1 2008 Quadra Fire Garnet T 7016 127F C Gas Connection NOTE Have the gas supply line installed in accordance with local building codes if any If not follow ANSI Z223 1 Instal lation should be done by a qualified installer approved and or licensed as required by the locality In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter NOTE A listed and Commonwealth of Massachusetts approved 1 2 inch 13mm T handle man
71. structed Page 18 Quadra Fire Garnet T 7016 127F Figure 5 18 Step 6 Place the support clamp provided with the support box inside the support box at the bottom and secure to the pipe section The clamp allows the support box to support the weight of the pipe sections Continue to add pipe sections until you are above the roofline Step 7 Complete the cathedral ceiling installation by following the same procedures outlined in steps 7 through 9 for vertical installations pages 16 17 Step 8 Install the black trim collar around the outside of the cathedral ceiling support box Figure 5 18 The two pieces of the trim collar slide over one another to allow for easy adjustment around the support box Using the six screws provided secure the four corners and the overlapping sections of the trim collar to the ceiling You may want to predrill the holes for the overlapped sections for ease of installation Cathedral Ceiling Support Box Screws Figure 5 19 August 1 2008 3 Class A Metal Chimney ADAPTOR CONNECTOR Figure 5 20 CAUTION Ensure that existing chimney is functionally sound and clean Have inspection done by qualified chimney sweep or professional installer BEFORE converting to direct vent appliance Step 1 Remove existing chimney cap Step 2 Measure the distance from the top of the chimney to the bottom of the ceiling support box
72. t or down drafting In these cases increasing the vent height or switching to the high wind termination cap may solve this problem August 1 2008 Step 8 Slip the storm collar over the pipe and push it down to the top of the flashing Figure 5 15 Use non hardening sealant above and below the joint between the storm collar and the pipe a oo High Wind Termination Cap Secure Flashing with Non Hardening Sealant and Roofing Nails Figure 5 15 Step 9 Twist lock the vent cap and seal Note For multi story vertical installations a ceiling firestop is required at the second floor and any subsequent floors Figure 5 16 The opening should be framed to 10 in x 10 in 254mm x 254mm inside dimensions in the same manner as shown in Figure 5 13 Ceiling Firestop Minimum 1 in 24mm Clearance Minimum 1 in 24mm Clearance Minimum 1 in 24mm Clearance Minimum 1 in 24mm Clearance Figure 5 16 August 1 2008 Quadra Fire Garnet T 7016 127F Fire Risk Explosion Risk e Any occupied areas above the first floor including closets and storage spaces which the vertical vent passed through must be enclosed The enclosure may be framed and sheetrocked with standard construction materials however refer to these installation instructions for the minimum allowable clearance between the outside of the vent pipe and the combustible surfaces of the enclosure Do not fill any of the required air sp
73. the connector is centered in the The connection between the appliance and the retro d and the mounting holes line up with the masonry connector may be completed with sections of direct vent wall pipe Figure 5 30 Page 22 Quadra Fire Garnet T 7016 127F August 1 2008 H Slim Line Wall Thimble CAUTION Sharp Edges Wear protective gloves and safety glasses during installation BEFORE YOU BEGIN Review the venting configurations in Figures A B and C on the next page 1 Assembling Slim Line Trim Ring and Heat Shield Figure 5 31 Lay the trim ring on flat surface and bend up the six welded brackets into a 90 degree position The brackets along the outer edge of the ring are for locating the ring in the center of the hole Figure 5 32 The heat shield is shipped flat and must be hand bent into a half circle before attaching it to the trim ring Bend the heat shield as shown NOTE Wear leather gloves when bending the heat shield to prevent injury August 1 2008 Quadra Fire Garnet T 7016 127F Figure 5 33 Attach the heat shield to the trim ring with the four screws provided Screws go through the heat shield and into the brackets on the trim ring 2 Installing Slim Line Trim Ring and Heat Shield Measure from the floor to the center of the vent pipe Cut out a 9 1 2 in 241mm hole in the wall Hold the trim ring heat shield assembly in place and put a mark on the shield with a black marker where
74. they match and slide into the entry slots on the male ends see Figure 5 4 Push the pipe sections completely together then twist lock one section clockwise approximately one quarter turn until the two sections are fully locked The female locking lugs may not be visible from the outside They may be located by examining the inside of the female ends Female Locking Lugs Male Locking Lugs Figure 5 4 August 1 2008 Fire Risk Explosion Risk Combustion Fume Risk Use vent run supports per installation instructions Connect vent sections per installation instructions Maintain all clearances to combustibles Do NOT allow vent to sag below connection point to appliance Maintain specified slope if required Improper support may allow vent to sag or separate Step 3 For installations using a round support box wall thimble check pipe manufacturer s instructions mark the wall for a 10 in x 10 in 254mm x 254mm square hole The center of the square hole should line up with the center line of the horizontal pipe as shown in Figure 5 5 Cut and frame the hole in the exterior wall where the vent will be terminated If the wall being penetrated is constructed of noncombustible material i e masonry block or concrete a 7 in 178mm diameter hole is acceptable CENTER OF CENTER LINE CENTER THIMBLE LINE Figure 5 5 NOTE 1 Installation requires a minimum
75. this entire manual prior to using the appliance Failure to follow the instructions may result in property damage bodily injury or even death e Remove all shipping materials from inside and or underneath the firebox e Review proper placement of logs mineral wool e Check the wiring e Check the baffle adjustment e Ensure that there are no gas leaks e Ensure that the glass is sealed and in the proper posi tion e Ensure that the flow of combustion and ventilation air is not obstructed front grilles and vent caps Glass door must be in place when appliance is operating Risk of e Combustion Fumes Fire Do NOT operate appliance with glass door removed Open viewing glass for servicing only Glass door MUST be in place and sealed before operating appliance Only use glass door certified for use with appliance Glass replacement should be done by qualified technician HOT DO NOT TOUCH SEVERE BURNS MAY RESULT CLOTHING IGNITION MAY RESULT Glass and other surfaces are hot during operation and cool down Keep children away CAREFULLY SUPERVISE children in same room as appliance Alert children and adults to hazards of high temperatures Do NOT operate with protective barriers open or removed Keep clothing furniture draperies and other combustibles away August 1 2008 Quadra Fire Garnet T 7016 127F Improper installation adjustment alteration service or maintenance can cause inj
76. to O12 srira ana rada dcdit kd ed 1 0 Over 6 12 t0 MZ corista inc dea o 1 25 Over 7 12 to 8 12 asian 1 5 Over 8 12 10 9 12 ss erica id vnnd c 207 Over 9 12 to 10 12 2 0 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 citan dict 6 0 Over 16 12 to 18 12 caesen 7 0 Over 18 12 10 20 12 conri 7 5 Over 20 12 to 21 12 sonia da vista d adici d ri cin 8 0 9 foot minimum in snow regions Figure 4 3 Minimum Height from Roof to Lowest Discharge Opening Figure 4 3 specifies minimum vent heights for various pitched roofs August 1 2008 August 1 2008 VENT TERMINAL X AIR SUPPLY INLET 12 inches See Note 1 clearances above grade veran da porch deck or balcony clearances to window or door that may be opened or to per manently closed window Glass vertical clearance to unventilat ed soffit or to ventilated soffit lo cated above the terminal for vinyl clad soffits and below electrical service 12 inches 18 inches 30 inches 9 inches clearance to outside corner 6 inches clearance to inside corner 3 ft Canada not to be installed above a gas meter regulatorassembly within 3 feet 90cm horizontally from the center line of the regulator 3 RR NR clearance to gas Service regula tor vent outlet 9inches U S A 12 inches Canada clearance to non mechanical air supply
77. tudes Manufactured Home or Mobile Home installation may occur only after the home is site located and must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not applicable the Standard for Manufactured Home Installations ANSI NCSBCS A225 1 or Standard for Gas Equipped Recreational Vehicles and Mobile Housing CSA Z240 4 When installed the appliance must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 B Glass Specifications This appliance is equipped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass NOTE This installation must conform with local codes In the absence of local codes you must comply with the National Fuel Gas Code ANSI Z223 1 latest edition in the U S A and the CAN CGA B149 Installation Codes in Canada Do NOT use this appliance if any part has been under water Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water Page 4 Quadra Fire Garnet T 7016 127F C BTU Specifications Model Maximum Minimum US or Canada Input Input BTU BTU Orifice Size State 96 DMS Thermal efficiency maximum pipe with blo
78. ual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet e Ifsubstituting for these components please consult local codes for compliance AX WARNING Gas Leak Risk e Support control when attaching pipe to prevent bending gas line NOTE The gap between the supply piping and gas access hole may be plugged with non combustible insulation to prevent cold air infiltration Leak test all gas line joints and the gas control valve prior to and after starting the fireplace Before making the gas connection ensure that the appliance you are installing is designed for the type of gas being supplied This information can be found on the Ratings Label under the appliance If the appliance has been converted to propane LP the valve cover should have a label stating that the unit has been converted to propane Connect the gas line at the 3 8 in 9 5mm pipe connector on the valve at the back of appliance We recommend connecting the appliance with an approved flex gas line If flex gas lines are not approved in your area you must connect a hard pipe to the gas hookup You must supply a manual shut off valve in a visible location within 3 feet 914mm of the appliance Page 27 Omni Test Laboratories listed gas appliances are tested and approved without requiring changes for elevations from 0 to 2000 feet in the U S A and O to 4500 feet in Canada i Fire or Explosion Hazard
79. upport Boroaia sor O ww TERMINATION CAPS BIS ss TERMINATION CAPS amp KITS Basic Horizontal Teminaion Kiva JJ A come sem chimney trer Tema orzo emirato JO ro ao aoa sex mwKSee Stove Adaptor Kit Vertical Cap Kit LINK STOVE Trapezoid Termination Kit 3 1 8 4 3 4 SLP TRAPY gt Je Trapezoid Termination Kit 5 1 4 X9 1 4 SLP TRAP2 Vertical Termination Cap SLP TVHW 46DVA VCH 4DT VKC 4DVT SV4CGV Stove Adaptor Kit Vertical Cap Kit Includes 30 4 flex adapters wall thimble masonry ZC flashing 991DA vertical cap NOTES Before cutting any holes check pipe manufacturers current instructions Each pipe manufacturer has their own list of parts for kits SL is not interchangeable with SLP August 1 2008 Quadra Fire Garnet T 7016 127F Page 47 DUADRA FIRE 2 Service Parts List__GARNET T NG LP Exploded Parts Diagram Beginning Manufacturing Date 6 16 04 Ending Manufacturing Date Baffle AA le KE ES Door Assembly Gasket Pilot Log Set 3 Switch Bracket Door Left 5 Ignition Module Switch Rocker ON OFF T Burner Assembly Page 48 Quadra Fire Garnet T 7016 127F August 1 2008 Baffle Back DUADR FIDE Service Parts List cows GARNET T NG LP Exploded Parts Diagram Beginning Manufacturing Date 6 16 04 Ending Manufacturing Date IMPORTANT THIS IS DATED INFORMATION The most current information is located on your
80. ury or property damage Refer to the owner s information manual provided with this appliance For assistance or additional information consult a qualified installer service agency or the gas supplier Do NOT use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water B Controls FAN SPEED This knob controls the speed of the blower that pushes the heated air into the room MAIN BURNER This control is used to turn the appliance on and off PILOT IGNITOR The pilot ignitor is used only to start the pilot When the valve control knob is turned to the pilot position and fully depressed press the piezo ignitor repeatedly creating a blue spark directly next to the pilot igniting the pilot flame VALVE CONTROL This knob is used to control gas to the appliance and for starting the pilot There are three positions ON OFF amp PILOT The indicator on the valve indicates the position of the knob COMFORT CONTROL This knob controls the flame height from low LO to high HI NOTE If using a remote control wall switch or thermostat the On Off Switch must be left OFF Turning the On Off Switch to ON will keep the appliance on continually Page 37 C Lighting Appliance FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these i
81. wer on Canada minimum pipe D High Altitude Installations Omni Test Laboratories listed gas appliances are tested and approved without requiring changes for elevations from O to 2000 feet in the U S A and 0 to 4500 feet in Canada When installing this appliance at an elevation above 2000 feet it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size Input rate should be reduced by 4 for each 1000 feet above a 2000 foot elevation in the U S A If the heating value of the gas has been reduced these rules do not apply To identify the proper orifice size check with the local gas utility If installing this appliance at an elevation above 4500 feet in Canada check with local authorities E Non Combustible Materials Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C shall be considered non combustible materials F Combustible Materials Materials made of or surfaced with wood compressed paper plant fibers plastics or other materials that can ignite and burn whether flame proofed or not or whether plastered or unplastered shall be considered combustible materials August 1 2008 NOTE The following requirements reference various Massachusetts and national codes not contained in this document G Requirements for the Commonwealth of Massachusetts For all side wall hori
82. zo wire is properly connected replace the ignitor b Defective pilot or Using a match light the pilot If the pilot lights turn off the pilot and misaligned electrode trigger the piezo button again If the pilot lights an improper gas air spark at electrode mixture caused the bad lighting and a longer purge period is recom mended If the pilot will not light ensure the gap at the electrode and pilot is one eighth 1 8 inch to have a strong spark If the gas is OK button the spark ignitor will not light the pilot replace the pilot c No gas or low gas Check the remote shut off valve from the appliance Usually there is pressure a valve near the gas main There can be more that one 1 valve from the appliance and the main d No LP in tank Check the LP propane tank You may be out of fuel a Defective thermo Check that the pilot flame impinges on the thermocouple Clean and or couple adjust the pilot for maximum flame impingement 2 The pilot will not stay lit after carefully follow ing the lighting instruc tions Ensure that the thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter wire on the thermocouple copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple
83. zontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied Installation of Carbon Monoxide Detectors At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling building or structure served by the side wall horizontal vented gas fueled equip ment lt shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adjacent floor level In the event that the requ
Download Pdf Manuals
Related Search
Related Contents
Intra-oral Camera User's Manual 20 SAT.pmd - gahesa.com Cosechadoras MF 34 y 38 レクリエーション スポーツを 楽しもう! Centaur 3.1 : Installation Manual Bosch GKS 55 GCE XFX NVIDIA GeForce 8800 GTS 320MB DDR3 Extreme GeForce 8800 GTS Copyright © All rights reserved.
Failed to retrieve file