Liebert 700-2200 VA User's Manual

image

Contents

1. 0 25 50 75 Percent Load 100 0 25 50 75 100 Percent Load 21 AUDIBLE ALARM CONDITIONS CONDITION ALARM utility failure minutes of run time remaining minutes of run time remaining Battery replacement Two second beep every minute UPS output overload One short beep every second UPS fault FUSE REPLACEMENT PROCEDURES FOR 700 VA MODELS Insert flat blade screw AC Inlet driver into slot and pull fuse holder out to remove on Fuse Holder A8 Kode w Ba A Al By e Input Fuse Ia e Spare Fuse CAUTION Before changing the supply fuse turn off the UPS and unplug the input cord from the AC input power supply and from the UPS 1 Remove the fuse holder by inserting a flat blade screwdriver into the slot and pulling out as indicated in the figure above Remove the input fuse Remove the spare fuse from its position by using the screwdriver to push it out Place spare fuse in the input fuse position and replace the fuse holder The fuse holder will lock into position 5 Reconnect the input power lead to the UPS and the input power lead to the input AC supply 6 Restart the UPS The UPS is ready for normal operation NOTE For 1000 1400 and 2200 VA units press the reset circuit protector button 22 MINI TOWER SPECIFICATIONS Model Number PS7OOMT 120 PS1000MT 120 PS1400MT 120 PS2200MT 120 Model Rating VA W 700 450 100
2. Load Battery Level Indicators Utility High Low Utility Alarm silence Test a LED ON On Off LED OFF UTILITY HIGH LOW MODE OPERATION If high or low voltage conditions occur the PowerSure Interactive UPS will automatically correct the utility voltage by either lowering or raising the input voltage condition The UPS will continue to correct these conditions indefinitely without draining battery power The figure below indicates approximately 51 75 loading while automatically correcting the utility voltage Load Battery Level Indicators Utility High Low Utility Alarm silence Test On Off BATTERY MODE OPERATION Battery mode occurs in event of extreme input conditions or complete utility failure The battery system along with the bi directional converter generates power for the connected load During battery mode an alarm sounds every 10 seconds This will change to 2 beeps every 5 seconds when battery runs low approximately 2 minutes remaining Each load battery level indicator represents a 25 capacity level As capacity decreases fewer indicators remain illuminated Utility LED will flash every second indicating the UPS is operating from battery mode Battery mode supports a full rated load for approximately 5 minutes before it shuts down To increase this time turn off non essential pieces of equipment such as idle computers and monitors WARNING Turning o
3. CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed before replacing the batteries e Turn off and disconnect the UPS from utility power prior to opening the battery replacement door Remove rings watches and other metal objects Use a Phillips cross head screwdriver with insulated grips Do not lay tools or other metal objects on top of the batteries If the battery replacement kit is damaged in any way or shows signs of leakage contact your dealer immediately e Do not dispose of batteries in a fire the batteries may explode If you feel unqualified to replace the battery do not open the battery door Call Liebert Technical Support LTS World Wide Technical Support numbers are located at the end of this section 1 Using a Phillips cross head screwdriver loosen the 4 screws around the battery door as in Figure 1 Carefully remove the battery door by pulling it forward Lay the battery door and screws aside for reassembly 2 Again using a Phillips cross head screwdriver loosen the 4 screws holding the battery retaining plate as in Figure 2 Carefully remove the battery retaining plate by pulling it forward Lay the battery retaining plate and screws aside for reassembly 3 700 1000 1400 VA models Gently pull on the white tabs located on both sides of the battery until wiring is exposed Figure 3 Disconnect red wire figure 4 and
4. Take the proper precautions when lifting or moving the UPS 2 Visually inspect the UPS for freight damage Report any damage to the carrier and your dealer 3 Locate the UPS indoors where it cannot be accidentally disconnected Locate it in an area with unrestricted airflow away from water flammable liquids gases corrosives or conductive contaminants Maintain a minimum of four 4 inches 102 mm clearance in front and rear of the UPS Maintain an ambient temperature range of 32 to 104 F 0 to 40 C NOTE UPS operation in temperatures above 77 F 25 C reduces battery life 4 Gently lay UPS on its bottom side so that the front bezel is facing you 5 The Rackmount UPS must be supported by a shelf or rails The front bezel will not support the weight of the UPS CAUTION To increase the stability of the rack enclosure place the UPS in the lowest possible rack position 6 Refer to the Installation instructions supplied with the Rack Slide or Shelf Kits to complete the installation procedures T After the UPS has been installed in the Rack enclosure plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National Electric Code ANSI NFPA 70 or local codes Use a 15 amp rated device for the 700 1000 or 1400 VA units and a 30 amp device for the 2200 VA unit The wall receptacle must be grounded 8 Ensuring load equipment is turned off plug all lo
5. connector located on the rear of the UPS This capability is used in applications requiring the UPS to provide status and power monitoring information to the computer system For example during a utility power failure the information can be used by the Computers operating system or application program to automatically save information in buffers to close files and shut down operations prior to battery capacity depletion Monitoring of the UPS via a computer system is easily made with a Liebert SiteNet 1 shutdown kit sold separately Consult your local Liebert representative to determine the correct software kit for your application The kit includes special purpose cable and shutdown software UPS INTELLIGENT COMMUNICATIONS The PowerSure Interactive UPS has the capability to communicate intelligently with stand alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UPS By purchasing the optional Liebert SiteNet 2 software package sold separately intelligent communications allows the following capabilities Quantitative monitoring of utility and UPS power Quantitative monitoring of internal UPS parameters Periodic tests of battery quality and replacement notification Timed and delayed shutdown of the UPS Logging of power disturbances and anomalies Contact your local Liebert representative dealer or reseller for more information about SiteNet 2 softwa
6. detachable w 6 ft attached w 6 ft attached w 6 ft attached w NEMA 5 15 P NEMA 5 15 P NEMA 5 15 P NEMA L5 30 P 5 CH Cc Power Cord OUTPUT AC PARAMETERS Output Receptacles e 103 VAC to 132 VAC Max Current Rating 5 8 A 18 3 A Frequency 50 Hz or 60 Hz Waveform Sinewave Utility Mode Overload 200 for gt 2 cycles 110 for gt 5 minutes Battery Mode Overload 150 for gt 1 cycle 110 for gt 30 seconds BATTERY PARAMETERS Valve regulated nonspillable lead acid Qty xX Voltage X Rating 2 x 12V x 7 0 or 7 2 AH 3 x 12V x 7 0 or 7 2 AH 4 x 12V x 7 0 or 7 2 AH 8 x 6V x 12 AH Batt Mfg Part Number CSB GP1270F2 or Panasonic LC R127R2CH1 Panasonic LC R0612CH1 Transfer Time 2 6 ms typical Back up Time See Typical Battery Discharge Curves Recharge Time 3 Hours to 95 capacity after full discharge into 100 load 4 lt O D ENVIRONMENTAL Operating Temperature 32 F to 104 F 0 C to 40 C Storage Temperature 5 F to 122 F 15 C to 50 C Relative Humidity 0 to 95 non condensing Operating Elevation Up to 10 000 ft 3000 m at 35 C without derating Storage Elevation 50 000 ft 15 000 m maximum Audible Noise lt 45 dBA at 1 meter AGENCY Safety RFI EMI Immunity UL 1778 c UL Listed FCC Part 15 Subpart B Class A IEC 801 2 Level 4 IEC 801 4 Level 4 IEEE 587 Category A 24 25 0 Liebert 1050 Dearborn Drive Columbus OH 43229 614 888 0246 P
7. is the second uppermost LED contained in load battery level indicators A flashing LED indicates the UPS has detected a problem An alarm sounds to alert that the UPS requires attention Refer to Troubleshooting Guide Alarm Silence Battery Test Button The Alarm Silence Battery Test button serves a dual purpose During normal mode operation press button for at least one half second to test capacity of the battery system The UPS will operate in battery mode for approximately 15 seconds The illuminated LED indicators in Load Battery Level determine battery mode capacity in 25 increments During battery mode operation or active alarm condition this button functions as the alarm silence feature Pressing this button for at least one half second will silence the alarm After the alarm is silenced the PowerSure Interactive will reactivate the alarm system to alert of additional problems The low battery alarm is the single alarm that cannot be silenced During a Battery Test if the top two LEDs do not illuminate allow the UPS to recharge the batteries for 24 hours After 24 hours retest the batteries If the batteries have been retested and the top two LEDs still do not illuminate contact your dealer or Liebert Technical Support LTS for a battery replacement kit Site Wiring Fault Indicator RED An illuminated LED indicates the UPS has detected a miswired utility receptacle Contact a qualified electrician for assistance POWERSU
8. reduce number of loads connected to UPS Check load equipment for faults UPS shuts down with the Fault UPS shutdown due to internal UPS requires service Contact indicator and diagnostic LEDs A failure your dealer or LTS amp B are illuminated UPS shuts down with the Fault UPS shutdown due to an internal Ensure UPS is not overloaded indicator and diagnostic LEDs A over temperature condition ventilation openings not blocked amp D are illuminated or room ambient temperature not excessive Wait 30 minutes to allow UPS to cool then restart UPS If it does not restart contact your dealer or LTS UPS shuts down with the Fault UPS shutdown due to acommand Your UPS has received a signal indicator and diagnostic LEDs B from the communications port s or command from the attached amp D are illuminated computer If this was inadvertent ensure the communication cable used is correct for your system For assistance contact your dealer or LTS 20 Run Time Mins Run Time Mins POWERSURE INTERACTIVE TYPICAL BATTERY DISCHARGE CURVES Discharge times are at 25 C ambient 1000 VA Run Time Mins 0 25 50 75 Percent Load 1400 VA 100 0 25 50 75 100 Percent Load 2200 VA Run Time Mins
9. the black wire figure 5 2200 VA model Pull apart the Battery harness connector Figure 6 amp 7 Remove batteries 4 Unpack new batteries taking care not to destroy the packing 5 Slide new batteries into the cavity noting the white pull tabs are facing outward 6 For 700 1000 1400 VA models Connect the battery wires first black to black then red to red For 2200 VA models Connect the battery harness connector Push batteries back into cavity NOTE There will be a small spark when connecting the Red to Red connectors on 700 1400 VA models and on the 2200 VA model when connecting the battery harness connector This is normal and will not harm you or the UPS 7 Replace the Battery retaining plate by inserting the 4 screws into their associated holes Tighten the 4 screws to secure the battery retaining plate In place 8 Replace the Battery door by inserting the four 4 screws into their associated holes Tighten the four 4 screws to secure the battery door in place 9 Dispose of batteries in accordance with your local laws and regulations 17 18 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the PowerSure Interactive UPS develops a problem Use this information to determine whether external factors cause the problem and how to remedy the situation 1 The fault indicator will flash every second to indicate the UPS detected a problem An a
10. to red then black to black 2200 VA models first connect top battery connector A to bottom battery connector A then connect UPS connector B to the top battery connector B NOTE There will be a small spark when connecting the black connectors on 700 1400 VA models and connector B on the 2200 VA model This is normal and will not harm you or the UPS 9 Replace battery door by inserting the two metal tabs into the slots at the base of the UPS and pushing it closed at the top Tighten the two screws to lock the battery door closed 10 Flip the bezel back into place and align bottom clips to the lower slots in the battery door Once aligned push bezel back onto the UPS until it latches into position This may require a gentle tap 11 Dispose Recycle of old batteries in accordance with your local laws and regulations 15 MINL TOWER BATTERY REPLACEMENT Pull bezel forward Rotate bezel on top Remove battery door 700 VA Model To Disconnect Gently pull wiring away To Connect Connect red wire to red terminal then black wire to black terminal by pushing towards connector 1000 1400 VA Model To Disconnect Gently pull wiring away To Connect Connect red wire to red terminal then black wire to black terminal by pushing upward 2200 VA Model To Disconnect Pull apart connections A amp B To Connect Push connections A together amp connections B together 16 RACKMOUNT BATTERY REPLACEMENT
11. 0 670 1400 950 2200 1600 DIMENSIONS in mm Unit 5 5 x 14 4x 7 0 6 8 x 17 5 x 8 9 6 8 x 17 5 x8 9 7 6 x 20 1 x 13 2 WxDxH 140 x 365 x 178 172 x 447 x 227 172 x 447 x 227 194 x 511 x 336 Shipping 10 5 x 19 2 x 11 75 12 0 x 22 25 x 14 12 0 x 22 25 x 14 13 0 x 25 0 x 18 5 WxDxH 265 x 492 x 300 307 x 581 x 358 307 x 581 x 358 330 x 635 x 470 WEIGHT Ibs kg Unit 81 7 37 1 Shipping 87 0 39 5 INPUT AC PARAMETERS Voltage Range Voltage Raise Voltage Lower Frequency 120 VAC 25 23 Maintains output to 120 VAC 14 when input is 120 VAC 25 Maintains output to 120 VAC 10 when input is 120 VAC 23 45 55 Hz or 55 65 Hz auto sensing 6 ft detachable wi 6 ft attached w 6 ft attached w 6 ft attached w NEMA 5 15 P NEMA 5 15 P NEMA 5 15 P NEMA L5 30 P 5 CH C Power Cord OUTPUT AC PARAMETERS Output Receptacles e 103 VAC to 132 VAC Max Current Rating 5 8 A 18 3 A Frequency 50 Hz or 60 Hz Waveform Sinewave Utility Mode Overload 200 for gt 2 cycles 110 for gt 5 minutes Battery Mode Overload 150 for gt 1 cycle 110 for gt 30 seconds BATTERY PARAMETERS Valve regulated nonspillable lead acid Qty xX Voltage X Rating 2 x 12V x 7 0 or 7 2 AH 3 x 12V x 7 0 or 7 2 AH 4 x 12V x 7 0 or 7 2 AH 8 x 6V x 12 AH Batt Mfg Part Number CSB GP1270F2 or Panasonic LC R127R2CH1 Panasonic LC R0612CH1 Transfer Time 2 6 ms typical Back up Time See Typical Battery Discharge C
12. PowerSure Interactive 700 2200 VA 120 V USER MANUAL English IMPORTANT SAFETY INSTRUCTIONS WARNING Do not attempt to service this product yourself except to replace the battery Opening or removing the cover may expose you to dangerous voltages even when the AC cord is disconnected from the electrical outlet Refer all servicing to qualified service personnel 1 SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS THAT SHOULD BE FOLLOWED DURING INSTALLATION AND MAINTENANCE OF THE UNINTERRUPTIBLE POWER SYSTEM UPS AND BATTERIES CONSERVER CES INSTRUCTIONS CETTE NOTICE CONTIENT DES INSTRUCTIONS IMPORTANTES CONCERNANT LA S CURIT 2 This product is not intended for use with life support and other U S FDA designated critical devices See Limited Warranty 3 CAUTION A BATTERY PRESENTS A RISK OF ELECTRICAL SHOCK OR BURN FROM HIGH SHORT CIRCUIT CURRENT OBSERVE PROPER PRECAUTIONS ATTENTION UNE BATTERIE PRESENT UN RESQUE DE CHOC LECTRIQUE OU DE BRULURE PAR TRANSFERT D NERGIE SUIVRE LES PR CAUTIONS QUI S IMPOSENT 4 WHEN REPLACING THE BATTERIES USE THE SAME NUMBER AND TYPE OF BATTERIES PROPER DISPOSAL OF BATTERIES IS REQUIRED REFER TO YOUR LOCAL CODES FOR DISPOSAL REQUIREMENTS POUR LE REMPLACEMENT UTILISER LE M ME NOMBRE ET TYPE DE BATTERIES L ELIMINATION DES BATTERIES EST R GLE MENT E CONSULTER LES CODES LOCAUX CER EFFET 5 Read all safety and operating instruction
13. RE INTERACTIVE MINI TOWER 1 2 3 4 5 6 Level Indicators Battery Test Button 700 VA Fault Indicator Load Battery Alarm Silence On Off Button Output Receptacles DB 9 Interface Port AC Inlet Intellislot Communications Port Circuit Protector or Fuse Site Wiring Fault Indicator 1000 1400 VA POWERSURE INTERACTIVE RACKMOUNT Fault Indicator Utility High Low Indicator Load Battery Utility Battery Level Indicators Status Indicator Load Batter Utility High Low Utility Alarm Silence Battery Test Button On Off Button 2200 Model 700 1400 Models 700 Model has detachable cord 1 Output Receptacles 2 DB 9 Interface Port 3 AC Inlet 4 _Intellislot Communications Port 5 Circuit Protector or Fuse 6 Site Wiring Fault Indicator 10 OPERATION NORMAL MODE OPERATION During normal operation utility power provides energy to the UPS The filters and the power conditioning circuit process this power to provide computer grade power to connected loads The UPS maintains the batteries in a fully charged state The front panel displays the percentage of load on the UPS output The figure below indicates approximately 51 75 loading 76 to 100 load Flashes to indicate overload a 51 to 75 load 26 to 50 load 0 to 25 load
14. RFI They minimize any surges or interference present in the utility line and keep the sensitive equipment protected AUTOMATIC VOLTAGE REGULATOR In normal operation the Automatic Voltage Regulator AVR passes utility AC power to the connected load When utility power voltage is outside acceptable limits the AVR activates It raises undervoltage power and lowers overvoltage power This keeps the UPS output voltage within the connected equipment s tolerances and allows wide utility voltage fluctuations without utilizing battery power BI DIRECTIONAL CONVERTER In normal operation the bi directional converter converts utility AC power into regulated DC power to float charge the battery system Upon a utility power failure the bi directional converter receives its required energy from the battery and inverts it into precise regulated sinewave AC power Charging takes place whenever the UPS is plugged into the wall outlet whether it is ON or OFF and utility power is within acceptable limits BATTERY The PowerSure Interactive utilizes valve regulated nonspillable lead acid batteries At typical room temperatures and with the UPS float charging the battery system will last many years For battery run times refer to the Typical Battery Discharge Curves INPUT OUTPUT TVSS Automatic L and Voltage gt L EMI RFI Filters Regulator Bi Directional Converter MINL TOWER INSTALLATION 1 Unpack the
15. UPS carefully noting the packing method Retain the box and packing material for possible future shipment CAUTION The UPS is heavy see specifications Take proper precautions when lifting or moving it 2 Visually inspect the UPS for freight damage Report damage to the carrier and your dealer 3 Locate the UPS indoors where it cannot be accidentally disconnected Locate it in an area with unrestricted airflow away from water flammable liquids gases corrosives or conductive contaminants Maintain a minimum of four 4 inches 102 mm clearance around the UPS Maintain an ambient temperature range of 32 to 104 F 0 to 40 C NOTE UPS operation in temperatures above 77 F 25 C reduces battery life 4 Ensuring load equipment is turned off plug all loads into the UPS output receptacles 5 Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National Electric Code ANSI NFPA 70 or local codes Use a 15 amp rated device for the 700 1000 or 1400 VA units and a 30 amp device for the 2200 VA unit The wall receptacle must be grounded 6 Turn on the UPS by pressing the On Off button then turn on the connected load equipment The UPS is ready for normal operation RACKMOUNT INSTALLATION 1 Unpack the UPS carefully noting the packing method Retain box and packing material for possible future shipment CAUTION The UPS is heavy see specifications
16. ads into the UPS output receptacles 9 Turn on the UPS by pressing the On Off button then turn on the connected load equipment The UPS is ready for normal operation CONTROLS AND INDICATORS On Off Button The On Off button controls output power to connected load s CAUTION Pressing the On Off button when AC utility is not present will cause the UPS to begin operating from battery This should not be performed unless the UPS input is connected to a properly grounded receptacle Load Battery Level Indicators ALL GREEN The Load Battery Level Indicators have dual functions During normal mode operation LED indicators display electrical load placed upon the UPS and during battery mode operation LED indicators display battery capacity remaining Each LED designates a 25 load or battery capacity increment All four LED indicators illuminate at full load battery capacity If the UPS becomes loaded beyond full rating the top LED indicator will flash continuously while an alarm sounds Utility Battery Status Indicator GREEN An illuminated LED indicates the power button is on and utility power is available A flashing LED along with an alarm signifies utility voltage is out of specification and UPS is operating in battery mode Utility High Low Indicator AMBER An illuminated LED indicates the UPS is correcting utility power due to a utility overvoltage or undervoltage condition Fault Indicator GREEN The Fault indicator
17. al fuse is blown indicating Do not attempt to open or service internal fault the UPS Contact your dealer or LTS Utility indicator flashing UPS not plugged in UPS is operating in battery mode make certain UPS is securely plugged into the wall receptacle UPS input protection has opened UPS is operating in battery mode Save data and close applications Replace UPS input fuse or reset input breaker then restart UPS Utility voltage out of UPS input UPS is operating in battery mode range Save data and close applications Ensure utility supply voltage is within acceptable limits for UPS UPS has reduced battery time Batteries not charged Keep UPS plugged in continuously at least 24 hours to recharge batteries oer a is overloaded Check load level eed and remove non eed loads lista may not be able to hold Replace batteries Contact your a full charge due to age dealer or LTS for replacement battery kit Fault indicator and diagnostic UPS fan failure or battery UPS requires service Contact LED A are illuminated overcharge your dealer or LTS Fault indicator and diagnostic UPS failed the battery test Replace batteries Contact your LED B are illuminated dealer or LTS for replacement battery kit UPS shut down Fault indicator UPS overloaded or load Check load level display and and diagnostic LED D are equipment is faulty remove non essential loads illuminated Recalculate load VA and
18. be observed before replacing the batteries e Turn off and disconnect the UPS from utility power prior to opening the battery replacement door Remove rings watches and other metal objects Use a Phillips cross head screwdriver with insulated grips Do not lay tools or other metal objects on top of the batteries If the battery replacement kit is damaged in any way or shows signs of leakage contact your dealer immediately e Do not dispose of batteries in a fire the batteries may explode e f you feel unqualified to replace the battery do not open the battery door Call Liebert Technical Support LTS World Wide Technical Support numbers are located at the end of this section 1 Grasp the front bezel near the top and pull forward 2 Rotate the bezel upward and lay it on top of the UPS 3 Loosen the two screws at top of the battery door and remove door by pulling it forward slightly and lifting it off Lay battery door and screws aside for reassembly 4 700 1000 1400 VA models gently pull battery wiring out and disconnect the two wires one red and one black 2200 VA models pull apart connectors A and B 5 Grasp white pull tabs located on sides of the front battery and pull batteries out of the UPS 6 Unpack new batteries taking care not to destroy the packing 7 Slide new batteries into the cavity noting the white pull tabs are facing outward 8 700 1000 1400 VA models connect the battery wires first red
19. demarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SL 23550 2 98 Rev 5 0
20. ff the UPS while in battery mode will result in loss of output power The figure below displays approximately 51 75 battery capacity remaining 76 to 100 load 51 to 75 load 26 to 50 load 0 to 25 load Flashes to indicate low battery Load Battery Level Indicators Utility High Low Utility Alarm silence Test On Off Flashes every second BATTERY RECHARGE MODE The UPS resumes normal operation once utility power is restored At this time the bi directional converter begins recharging the battery whether the UPS in ON or OFF 12 COMMUNICATIONS INTERFACE PORT The PowerSure Interactive UPS contains a standard DB 9F recepticle located on the rear of the UPS unit Several signals are provided on this port and are assigned as follows PIN ASSIGNMENT DESCRIPTION 1 Low Battery open collector 2 UPS TxD typical RS 232 levels 3 UPS RxD typical RS 232 levels 4 Remote Shutdown 5 12V DC 1 0 mA max battery operation 5 Common No connection Low Battery open emitter Utility Fail open emitter 9 Utility Fail open collector Pin Assignment Collector to Emitter Open Collector Open Emitter Maximum voltage and current on pins 1 7 8 9 is 80V DC 10 0 mA UPS MONITORING The PowerSure Interactive UPS has the capability of being monitored with stand alone computers network workstations network servers or UNIX hosts via the DB 9 female
21. ight emitting diode LED bar display to indicate load percentage or battery capacity depending upon the mode of operation It also provides self diagnostics a combination alarm silence battery test button and two levels of alarms when the unit is operating on battery The PowerSure Interactive has an interface port for communications between the UPS and a LAN server or other computer system This port provides detailed operating information including voltages currents and alarm status to the host system when used in conjunction with Liebert SiteNet software SiteNet software can also remotely control UPS operation CAUTION This equipment has been tested and complies with limits for a Class A digital device pursuant to Subpart B of Part 15 of FCC rules These limits provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy If it is not installed and used in accordance with the instruction manual it may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference which the user must correct at his own expense MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION TVSS AND EMI RFI FILTERS These UPS components provide surge protection and filter Electromagnetic Interference EMI and Radio Frequency Interference
22. larm will sound alerting that the UPS requires attention One or more additional load battery level LED segments will be illuminated to provide a diagnostic aid to the operator as described below D indicator Load Battery Esch Fault indicator flashes every second Level Indicators B indicator A indicator Utility High Low Utility Alarm silence Test On Off A UPS fault fan failure battery overcharge NOTE The internal fan operates intermittently as needed B UPS failed battery test D UPS shutdown due to output overload time out A amp B UPS shutdown due to main input relay failure output short circuit A amp D UPS shutdown due to over temperature condition B amp D UPS shutdown due to command from communication ports remote shutdown or SNMP The fault indicators will be illuminated indefinitely while battery charger is operational or for a maximum of 5 minutes while battery charger is not operational If a problem persists consult your dealer or contact Liebert Technical Support LTS World Wide Technical Support numbers are located at the end of this section 19 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS fails to start when On Off UPS output short circuited or Ensure UPS is off Disconnect all button is pressed overloaded loads and ensure nothing is lodged in output receptacles Ensure loads are not defective or shorted internally Intern
23. owerSure Interactive Technical Support France Germany Italy Netherlands Internet Web site Worldwide FAX Tech Support The Company Behind The Products With more than 500 000 installations around the globe Liebert is the world leader in computer protection systems Since its founding in 1965 Liebert has developed a complete range of support and protection systems for sensitive electronics Environmental systems close control air conditioning from 1 5 to 60 tons Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center 700 2200 VA 120 V 1 800 222 5877 614 841 6755 44 0 1793 553355 33 1 4 87 51 52 49 89 99 19 220 39 2 98250 1 00 31 475 503333 upstech liebert com http www liebert com 614 841 5471 While every precaution has been taken to ensure Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 1998 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered tra
24. re UPS INTELLISLOT COMMUNICATIONS The PowerSure Interactive UPS contains an Intellislot communications port for the optional internal communications such as the Ethernet SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative dealer or reseller CAUTION TO MAINTAIN SAFETY SELV BARRIERS AND FOR ELECTROMAGNETIC COMPATIBILITY SIGNAL CABLES SHOULD BE SEGREGATED AND SEPARATELY RUN FROM ALL OTHER POWER CABLES WHERE APPLICABLE MAINTENANCE The PowerSure Interactive UPS requires very little maintenance The batteries are valve regulated nonspillable lead acid and require that they be kept charged to obtain their designed life Whether ON or OFF the UPS continuously charges the batteries when connected to the utility supply When storing the UPS for any length of time it is recommended to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries The PowerSure Interactive UPS is designed to allow the user to safely replace the batteries Read the safety cautions before proceeding Contact your local Liebert representative dealer or reseller to obtain the appropriate replacement battery kit 14 MINL TOWER BATTERY REPLACEMENT CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should
25. s before operating the UPS Adhere to all warnings on the unit and in this manual Follow all operating and user instructions 6 Turn the UPS off and unplug it before cleaning Use only a soft cloth never liquid or aerosol cleaners 7 The UPS is designed for data processing equipment Do not plug appliances such as hair dryers heaters vacuum cleaners or electric drills into the UPS output receptacles 8 WARNING Do not modify input cable Consult your dealer if connector does not match the utility receptacle The UPS must be grounded at all times while in use Turn the UPS off before unplugging 2 10 11 12 13 it or the safety ground will be removed Operate UPS only from a properly grounded 120 VAC outlet 2 wire plus ground The UPS is equipped with a grounded NEMA 5 15P or L5 30P input power plug depending upon model Do not defeat the safety purpose of this plug If unable to fully insert the plug into the wall outlet contact a qualified electrician for assistance Route power supply cords so they are not walked on or pinched Never block or insert any object into the ventilation holes or other openings Maintain a clearance of four 4 inches 102 mm around the UPS for proper air flow and cooling Always turn off the UPS and unplug it before starting the battery replacement procedure Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required preca
26. urves Recharge Time 3 Hours to 95 capacity after full discharge into 100 load 4 lt O D ENVIRONMENTAL Operating Temperature 32 F to 104 F 0 C to 40 C Storage Temperature 5 F to 122 F 15 C to 50 C Relative Humidity 0 to 95 non condensing Operating Elevation Up to 10 000 ft 3000 m at 35 C without derating Storage Elevation 50 000 ft 15 000 m maximum Audible Noise lt 45 dBA at 1 meter AGENCY Safety RFI EMI Immunity UL 1778 c UL Listed FCC Part 15 Subpart B Class A IEC 801 2 Level 4 IEC 801 4 Level 4 IEEE 587 Category A 23 RACKMOUNT SPECIFICATIONS Model Number PS700RM 120 PS1000RM 120 PS1400RM 120 PS2200RM 120 Model Rating VA W 700 450 1000 670 1400 950 2200 1600 DIMENSIONS in mm Unit 19x 18 x 5 25 19 x 18 x 5 25 19 x 18 x 5 25 19x18x7 WxDxH 483 x 457 x 133 483 x 457 x 133 483 x 457 x 133 483 x 457 x 178 Shipping 27 5 x 24 x 11 27 5 x 24 x 11 27 5 x 24x 11 27 5 x 24 x 12 WxDxH 699 x 610 x 279 699 x 610 x 279 699 x 610 x 279 699 x 610 x 305 WEIGHT Ibs kg Unit 41 5 18 9 51 29 23 3 57 2 26 0 86 0 39 1 Shipping 50 82 23 1 59 85 27 2 66 1 30 0 95 3 43 3 INPUT AC PARAMETERS Voltage Range Voltage Raise Voltage Lower Frequency 120 VAC 25 23 Maintains output to 120 VAC 14 when input is 120 VAC 25 Maintains output to 120 VAC 10 when input is 120 VAC 23 45 55 Hz or 55 65 Hz auto sensing 6 ft
27. utions To replace batteries refer to the battery replacement procedure If you feel unqualified to replace the batteries do not open the battery door Refer all servicing to qualified service personnel CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to skin and eyes and may be toxic INTRODUCTION amp SYSTEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure Interactive Uninterruptible Power System UPS It provides conditioned power to microcomputers and other sensitive electronic equipment Upon generation AC power is clean and stable However during transmission it may be subject to voltage sags spikes or complete power failure which may interrupt computer operations cause data loss or even damage equipment The PowerSure Interactive protects equipment from these disturbances The PowerSure Interactive comes in nominal power ratings of 700 1000 1400 or 2200 VA Complete specifications appear near the end of this section The PowerSure Interactive is a compact line interactive UPS A line interactive UPS continuously conditions and regulates its output voltage whether the utility power is present or not It supplies connected equipment with clean sinewave power to simulate as much as possible the power generated by the utility Sensitive electronic equipment operates best from sinewave power For ease of use the PowerSure Interactive contains a l