Home
Honeywell TB7600 User's Manual
Contents
1. Room Temp Override BV8 Present_Value R W Y Outdoor Temperature Present_Value R W Y Y Y Y Outdoor Temp Override BV 10 Present_Value R W Room Humidity AV 11 Present_Value R Occupancy Command MV 12 Present_Value R W Y V System Mode MV 13 Present_Value R W System Mode MV 14 Present_Value R W Y Y Y Y MV 15 Present_Value R W Y Supply Temp 16 Present_Value R Y Supply RH AV 17 Present_Value R Keypad Lockout MV 18 Present_Value R W Y V Control Output GR 19 Present_Value R Y 7 PI Heating Demand AV 20 Present Value R Cooling Demand AV 21 Present_Value R Y Y Y Y Y Economizer Output AV 22 Present_Value R Controller Status GRP 23 Present_Value R Y Y AUX BI 24 Present_Value R Y Y Y Y G Fan BI 25 Present_Value R Y V Y V Y1 Cool BI 26 Present_Value R Y2 Cool BI 27 Present Value R V W1 Heat BI 28 Present_Value R V V V W2 Heat BI 29 Present_Value R Y Y Reversing Valve BI 30 Present_Value R DI 1 Status BI 31 Present Value R Y Y Y
2. F 35 C 40 F 40 C Deadband AV 52 2 F 1 C 4 2 C 2 F 1 C Password Value AV 59 0 1000 0 Power up Delay AV 60 10 sec 120 sec 10 sec Unoccupied Time AV 68 0 5 hrs 24 0 hrs 0 5 hrs Economizer Changeover Setpoint AV 77 14 F 10 C 70 F 21 C 55 F 13 C Economizer Minimum Position AV 78 0 100 0 Mixed Air Setpoint AV 80 50 F 10 C 90 F 32 C 55 F 13 C High Balance Point AV 82 34 F 1 C 90 F 32 C 90 F 32 C Low Balance Point AV 83 40 F 40 C 30 F 1 C 12 F 24 C Dehumidification RH Setpoint AV 89 15 95 70 Dehumidification Hysterisys AV 90 2 20 5 Dehumidification Low OA Lockout AV 91 40 F 40 C 122 F 50 C 32 F 0 C Humidification RH Setpoint AV 95 10 90 50 5d em AV 96 0 100 N A High Limit Spt AV 97 50 90 85 Low RH Setpoint AV 98 10 90 20 Low Temp Reset RH Setpoint AV 99 40 F 40 C 15 F 9 5 C 20 F 29 C High Temp Reset RH Setpoint AV 100 20 F 6 5 C 55 F 13 C 32 F 0 0 C Humidifier Output AV 101 0 100 N A 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS List of Property Enumeration Sets for BI and BV objects Table 9 List of Property Enumeration Sets for Bl and BV objects Object Name Inactive_Text Active_Text Default value Room Temp Override BV 8 Nor
3. Y Y 012 Status 32 Present_Value Local Motion BI 33 Present Value R Y Y Effective Occupancy MV 34 Present_Value R Controller Alarms GRP 35 Present_Value R Y Y V Frost Alarm BI 36 Present_Value R V V Clock Alarm BI 37 Present_Value R Filter Alarm BI 38 Present_Value R Y Y y Y Y Service Alarm BI 39 Present Value R Fan Lock Alarm BI 40 Present_Value R Y Y Y Y Temperature Setpoints GRP 41 Present Value R Y Y Y Occupied Heat Setpoint AV 42 Present_Value R W Occupied Cool Setpoint AV 43 Present_Value R W Y Y Y Y Y 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Table 5 Objects m m m m m m m m m m zx zx x x zx zx x zx zx x x x x x x x x x x Object Name Object Property lt lt Instance S D S D 3 B S D S D N N N N N N m m m m m m m m m m plat AV 44 Present_Value R W Setpoint Unoccupied Cool 45 Present_Value R W Setpoint General
4. Any device containing a monitored object could be subject to network traffic congestion if such a polling interval is used Honeywell strongly recommends a polling interval of 5 seconds minimum for any graphic interface This becomes even more critical in area graphics where a single representation might poll many devices If proper poll rate is not respected devices may be reported offline by certain front end by saturating the traffic handling capacity of BACnet MS TP without COV subscription 9 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Free programmed object or loops As for the application program you might want to read and write any MS TP data on an If Once basis or a Do Every loop basis instead of reading or writing to a 3rd party device s object directly in the program Otherwise any read or write request will occur at the Supervisory Controller s program scan rate which might as well be in hundredths of milliseconds This can easily bog down a network as single commands can be sent to all ASC devices down the MS TP trunks every hundredth of milliseconds Programs writing to the devices should have a structure similar to the following If Once Schedule On then Do Every 5 min MV11 Occupied If Schedule On Then End if MV11 Occupied If Once Schedule Off Then OR Else MV11 Unoccupied MV11 Unoccupied End If End If End Do Retries and Timeouts Another thing to look for in a BACnet i
5. Cause Solution Thermostat does not come online Two or more controllers have the same MAC address Modify each duplicate address to a unique number The MS TP network has too many devices Do not exceed the maximum number of devices and maximum length allowed by the EIA 485 specifications Too many devices were installed without any repeaters Repeaters need to be installed as specified in this document The MS TP cable runs are broken Locate the break and correct wiring MS TP connections at the module were reversed Respect polarity of the wires on a MS TP network The thermostat does not have power Apply power to the thermostat 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS APPENDIX A BACNET OBJECTS TB7600 SERIES PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT PICS Vendor Name Honeywell Vendor ID 140 Product Name TB7600 Thermostat Series Product Model Number TB7600A5x14B TB7614B5x 14B TB7605B5x 14B TB7607B5x14B TB7600H5x 14B TB7652A5x 0B TB7652B5x 14B TB7656B5x 14B TB7657B5x14B and TB7652H5x0B Product Description The TB76xx series BACnet communicating thermostat has been specifically designed for RTU and heatpump applications to be monitored on a BACnet MS TP network Supported BACnet Services The BACnet communicating thermostat meets all requirements for designation as an Application Specific Controller B ASC The BACn
6. a network N A Right after power is applied 2 long blinks and then no blinking Polarity has been reversed at the Reverse polarity at the module module INTEGRATION This section provides compatibility and programming information useful when setting up TB7600 Series thermostats on a WEBs AX building automation system Global Commands The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front end GLOBAL COMMANDS ALL DEVICES ALL THERMOSTATS OUTDOOR TEMPERATURE OUTDOOR TEMPERATURE AV9 OUTDOOR TEMPERATURE AND HVAC PLANT CURRENT MODE SYSTEM MODE MV13 BAS CURRENT ENERGY SAVINGS MODE FAN MODE MV15 GLOBAL COMMANDS SPECIFIC DEVICES SPECIFIC AREA THERMOSTATS SCHEDULE OCCUPANCY COMMAND MV12 SCHEDULE AND OUTDOOR TEMPERATURE OCCUPIED HEATING SETPOINT AV42 UNOCCUPIED HEATING SETPOINT AV44 OCCUPIED COOLING SETPOINT AV43 UNOCCUPIED COOLING SETPOINT AV45 RESTRICT SER ACCESS TO THERMOSTAT KEYPAD LOCKOUT MV18 ROOM TEMPERATURE FOR TESTING AND OVERRIDE ROOM TEMPERATURE AV7 MSTP NETWORK BAS FRONT END TB7600 SERIES TSTAT GLOBAL COMMAND CONTROL LEVEL DEVICE LEVEL M32570 Fig 6 Global commands from a BAS front end to a TB7600 series thermostat
7. soon as there is a change to the device s MAC For example when a TB7600B5x14B thermostat with a MAC address of 63 is connected to a network its default Device Name will be TB7600B5x14B 63 and its default Device ID will be 76063 Device Name and Device ID properties are writable in Honeywell device object Both properties can be renamed from any BACnet network management tool as long as the tool itself can write to these properties Integrating Honeywell Devices on an MS TP Network Before doing any BACnet integration make sure to have Honeywell PICS Protocol Implementation Conformance Statement This PICS document lists all the BACnet Services and Object types supported by a device and can be found at http customer honeywell com The TB7600 Series does not support the COV service COV reporting allows an object to send out notices when its Present Value property is incremented by a pre defined value Since this is not supported at Honeywell end special attention should be given to the polling time settings at the Supervisory Controller and Workstation level when using a graphic interface or an application program to read or write to a Honeywell object Graphical interfaces For example some graphic interface might poll every data linked to the graphic page on a COV basis If the 3rd party device does not support COV the graphic interface then relies on a pre configured polling interval which is usually in hundredths of milliseconds
8. 7 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Typical Graphical User Interface GUI Objects The following objects should be typically used in a GUI Room Temperature AV7 Occupied and Unoccupied Heat Setpoints AV 42 and AV44 Occupied and Unoccupied Cool Setpoints AV 43 and AV45 Outdoor Temperature AV9 Supply Temperature A116 If available Occupancy Command MV12 Effective Occupancy MV34 System Mode RTU MV14 or System Mode HPU MV13 G Fan BI25 Y1 Cool BI26 Y2 Cool BI27 W1 Heat 28 W2 Heat BI29 or Reversing Valve BI30 Economizer Output AV22 if available Aux BI24 DI 1 Status BI31 DI 2 Status BI 32 Frost Alarm BI36 if available Filter Alarm BI38 if available Service Alarm 9 if available Fan Lock Alarm B140 if available Filter Aarm 38 6 Fan 25 Y1 Cool 1 BI 26 Y2 Cool 2 BI 27 Heat 1 BI 28 Wi Heat 2 BI 29 Occupancy MV 12 Occupied System Mode RTU MV 14 AUX 24 DI 1 Status BI 31 012 Status BI 32 Frost Alarm 36 Service Alarm BI 39 Room Temperature AN 7 68 2 F Occupied Heat Setpoint AV 42 69 0 F Occupied Cool Setpoint AV 43 72 0 F Sup ply Unoccupied Heat Setpoint AV 44 Temperature A116 Unoccupied Cool Setpoint AV 45 Fig 7 Typical GUI for a TB7605B5014B with Economizer control 63 4523 01 8 BACNET INTEGRATION MANUA
9. GEND EOL END OF LINE RESISTOR R RS485 REPEATER SC SUPERVISORY CONTROLLER M32574 Fig 4 Incorrect usage the second repeater in series may result in an unreliable system 5 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS End Of Line EOL Resistors MS TP network must be properly terminated For daisy chain configurations you must install an EOL resistor at each end of the daisy chain Depending on your MS TP network configuration the resistance value of the EOL resistor may change 7600 TB7300 and or TB7200 thermostats are installed at both ends of the MS TP network 120 Ohms resistor should be installed at each end ATB7600 TB7300 or TB7200 device is installed at one end of the MS TP network and another device is installed at the other end Install an End Of Line resistor value that matches the other device s instructions regarding its EOL resistor value Other devices are installed at both ends of the MS TP network Follow the other device s instructions regarding its EOL resistor value NETWORK ADAPTER The polarity of the connection to the cable is important From one module to the other it is important that the same color wire be connected to plus or and the other color wire be connected to the minus or Fig 5 shows the proper MS TP connections and the location of the Status LED This Status LED may help to troubleshoot network problems Status Board rev
10. Honeywell BACnet Integration Manual for TB7600 Series Thermostats r 2s ggg 7600 Series Thermostat with Occupancy Sensor TB7600 Series Thermostat PRODUCT OVERVIEW The TB7600 PI thermostat family is specifically designed for single stage and multi stage control of heating cooling equipment such as rooftop and self contained units The TB7600 Series are communicating thermostats with models available in BACnet MS TP and ZigBee wireless mesh protocols and can be easily integrated into a WEBs AX building automation system based on the NiagaraAX platform The product features an intuitive menu driven back lit LCD display which walks users through the programming steps making the process extremely simple Accurate temperature control is achieved due to the product s PI time proportional control algorithm which virtually eliminates temperature offset associated with traditional differential based thermostats REFERENCE MANUAL The TB7600 thermostats are also compatible with the Honeywell PIR occupancy sensor covers Thermostats equipped with a PIR cover provide advanced active occupancy logic which will automatically switch occupancy levels from Occupied to Unoccupied as required by local activity being present or not This advanced occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort All thermostats can be ordered with or witho
11. L FOR TB7600 SERIES THERMOSTATS Recommended Configuration Objects The following objects and group objects should be typically used for configuration purposes If your BAS allows you to remove objects from your database Honeywell recommends removing all configuration objects once your setup is complete This will prevent unnecessary polling of unused objects and will help speed up the network General Options 1 Group GRP 46 and its complete list of objects General Options 2 Group GRP 58 and its complete list of objects Programmable Model Configuration Options Group GRP 69 and its complete list of objects Stages Configuration Options Group GRP 72 and its complete list of objects Economizer Model Configuration Option Group GRP 76 and its complete list of objects Heatpump Model Configuration Option Group GRP 81 and its complete list of objects Dehumidification Model Configuration Option Group GRP 87 and its complete list of objects Humidification Model Configuration Option Group GRP 94 and its complete list of objects Default Device Name and default Device ID Default Device Name is set to Model number MAC Where MAC is the current MAC address of the device Where Model number is Honeywell part number The device name will be upgraded as soon as there is a change to the device MAC address Default Device ID is set to 76000 MAC Where MAC is the current MAC address of the device The device ID will also be upgraded as
12. Options 1 GRP 46 Present_Value R Temperature Scale BV 47 Present_Value R W Y Heating Setpoint Limit 8 Present_Value R W Y Y y Y Cooling Setpoint Limit 9 Present_Value R W Y Heating Lockout AV 50 Present_Value R W Temperature Cooling Lockout AV 51 Present_Value R W xr E ae Temperature Deadband AV 52 Present_Value R W Heating MV 53 Present_Value R W Cooling MV 54 Present_Value R W Frost Protection BV 55 Present_Value R W Y V Aux Contact BV 56 Present_Value R W Menu Scroll BV 57 Present_Value R W Y General Options 2 GRP 58 Present_Value R Y Y Password Value AV 59 Present_Value R W Y Power up Delay AV 60 Present_Value R W Occupancy My 61 Present_Value R W Vivi Fan Control BV 62 Present_Value R W V Anticycle MV 63 Present_Value R W Fan Purge Delay BV 64 Present_Value R W Y DI 1 Configuration MV 65 Present Value R W Y DI 2 Configuration MV 66 Present_Va
13. Properties Writable Properties Supported Analog Input Reliability Out_of_Service Present Value Analog Value 0 Reliability Out of Service Object Reliability Binary Input Active_Text Out_of_Service Inactive_Text Reliability Present_Value Binary Value Active_Text Out_of_Service Inactive_Text Object Identifier Device 0 Max Master Object_name Max Info frames eS Max_Master Group 0 0 N A N A Reliability Present_Value Mul state value x a States_Text Out of Service Present Value Schedule 0 Weekly_schedule Weekly Schedule The following AV s are defined as read only When Out of Service properties is set to true the Present Value if written is not derived from the application level of the thermostat Room Humidity AV11 PI Heating Demand AV20 PI Cooling Demand AV21 Economizer Output AV22 EffReset Humidification RH Spt AV96 Humidifier Output AV101 Object_Name property is writable for 1 object only Room Temperature AV7 Proprietary Properties Table 7 Proprietary Properties Property name ID BACnet Data type Description The version number of the BACnet communications Major Version 1000 CharacterString module This is the hardware version number MS TP Address 1001 Unsigned Display the MAC layer address of the module MS TP Baud Rate 1002 Unsigned Display the communi
14. R W Low Balance Point AV 83 Present_Value R W Comfort Mode BV 84 Present_Value R W Reversing Valve BV 85 Present Value R W N Configuration Compressor Interlock 86 Present_Value R W Configuration Options RH Display BV 88 Present_Value R W Denumidifigsuon Present_Value R W Setpoint 90 Present Value R W Hysterisys Dehumidification Low OA cont AV 91 Present Value R W Deriumidification BV 92 Present_Value R W Lockout Functions Dehumidification Output BI 93 Present_Value R d Status Sea e erm ods laesi CUTS y Configuration Options Humiditication 95 Present Value R W y v Setpoint Eff Effective Reset Humidification RH Spt 96 Present_Value R Y Setpoint Humidification High Limit Spt Setpoint AV 97 Present_Value R W Low RH Setpoint AV 98 Present_Value R W Low Temp Reset RS Present_Value R W Setpoint High Temp Reset RH Present_Value R W Setpoint Humidifier Output AV 101 Present_Value R Local Schedule SCH 102 Present_Value R W 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Standard Object Types Supported Table 6 Standard Object Types Supported 2 Optional Supported Dynamically Dynamically 3 Object Type Objects Creatablo Deletable
15. ations and the proper daisy chain configuration Other methods of wiring an EIA 485 network may give unreliable and unpredictable results There are no troubleshooting methods for these types of networks Therefore a great deal of site experimentation may have to be done making this a difficult task with no guarantee of success Honeywell will only support daisy chain configurations SE DAISY CHAIN CONFIGURATION M32571 STAR CONFIGURATION BUS CONFIGURATION Fig 1 Three different network configurations star bus and daisy chain Only the daisy chain configuration is correct for an EIA 485 network Maximum Number of Devices A maximum of 64 nodes is allowed on a single daisy chain segment A node is defined as any device controller thermostat repeater connected to the RS485 network Terminators do not count as a node NOTE Biasing is not required with this series of devices To determine the number of nodes on a network add the following One node for each device including controller One node for each repeater on the chain For the example in Fig 2 we have one node for the controller plus 4 for the thermostats for a total of 5 nodes END OF LINE RESISTOR DOES NOT COUNT ASANODE m NODE2 NODE3 NODE4 NODES NODE 1 LEGEND EOL END OF LINE RESISTOR SC SUPERVISORY CONTROLLER M32572 Fig 2 Five nodes network example If you have more than 64 devices then repeaters are required t
16. cation baud rate of the module Display the temperature or humidity calibration value Sensor Offset 1005 REAL The range is 5 0 deg F to 5 0 deg F for a temperature and 15 to 15 for humidity 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Property Value Range Restrictions for Al and AV objects Table 8 Property Value Range Restrictions for Al and AV objects Object name 7 40 F 40 C 122 F 50 C N A Outdoor Temperature AV 9 40 F 40 C 122 F 50 C N A Room Humidity AV 11 0 100 N A Supply Temp Al 16 40 F 40 C 122 F 50 C N A Supply RH AV 17 0 100 N A PI Heating Demand AV 20 096 10096 N A PI Cooling Demand AV 21 096 10096 N A Economizer Output AV 22 096 10096 N A Occupied Heat Setpoint AV 42 40 F 4 5 C 90 F 32 C 72 F 22 C Occupied Cool Setpoint AV 43 54 F 12 C 100 F 37 5 C 75 F 24 C Unoccupied Heat Setpoint AV 44 40 F 4 5 90 F 32 C 62 F 16 5 C Unoccupied Cool Setpoint AV 45 54 F 12 C 100 F 37 5 80 F 26 5 C Heating Setpoint Limit AV 48 40 F 4 5 C 90 F 32 C 90 F 32 C Cooling Setpoint Limit AV 49 54 F 12 C 100 F 37 5 54 F 12 C Heating Lockout Temperature AV 50 15 F 26 C 120 F 49 C 120 F 49 C Cooling Lockout Temperature AV 51 40 F 40 C 95
17. ce s instructions regarding the End Of Line resistors 2 Other devices are installed at both ends of the MS TP net work Follow the other device s instructions regarding the End Of Line resistors Maximum number of nodes per segment 64 Honeywell devices only Maximum number of nodes per network 128 Baud rate 9600 19200 38400 76800 Auto detect Cable Type Honeywell recommends the use of balanced 22 24 AWG twisted pair with a characteristic impedance of 100 130 ohms capacitance of 30 pF ft or lower A braided shield is also recommended Impedance A value based on the inherent conductance resistance capacitance and inductance that represent the impedance of an infinitely long cable The nominal impedance of the cable should be between 100Qand 1200 However using1200 will result in a lighter load on the network Capacitance pF ft The amount of equivalent capacitive load of the cable typically listed in a per foot basis One of the factors limiting total cable length is the capacitive load Systems with long lengths benefit from using low capacitance cable i e 17pF ft or lower 3 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS NETWORK CONFIGURATION EIA 485 networks use a daisy chain configuration A daisy chain means that there is only one main cable and every network device is connected directly along its path Fig 1 illustrates two improper network configur
18. emOVR Filter Service DI2 Configuration MV66 None Fan lock 2F 0 6C 3F 1 2C 4 1 7 5 2 2 2 2 8 3 3 8 8F 3 9 C Proportional Band MV 67 NI 0 oc Rilo hd 2 Events 2 Event AI 0 aA R O MLA Event Display MV71 4 Events 21 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Table 10 Property Enumeration Sets for MV Objects Object Name Object Type and instance BACnet Index Text Default value 1 1 Stage Heating Stages MV73 2 Stages 2 2 Stages 1 1 Stage Cooling Stages MV74 2 Stages 2 2 Stages 1 1 Stage Heat Pump Stages MV75 5 2 Stages 2 Stages 63 4523 01 22 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS 23 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limit e 35 Dynamic Drive Toronto Ontario M1V 479 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 63 4523 01 M S 04 11 Printed in U S A Honeywell
19. et thermostat series supports the following BACnet Interoperability Building Blocks BIBBs Application Service Designation Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B Data Sharing Write Property B DS WP B Device Management Device Communication Control B DM DCC B Device Management Dynamic Device Binding B DM DDB B Device Management Dynamic Object Binding B DM DOB B NOTE The thermostat does not support segmented requests or responses NOTE Time synchronization can be made through a network even if the thermostat does not support the full date Therefore the device cannot claim conformance to the DeviceManagement TimeSynchronization B DM TS B service The device object does not have the Local Time or Local Date properties 63 4523 01 12 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS BACNET OBJECTS SUPPORTED Device Objects Table 4 Device Objects T Object Name Object Property Thermostat Parameter Instance TB76xxX5x14B Device Object Identifier Unique ID number of a device on a network Property 75 R W Object Name Unique name of a Device on a network Property 77 R W Model Name Thermostat Model number Property 70 R Firmware Revision Current BACnet firmware revision used by the Property 44 R thermostat Protocol Version Current BACnet firmware protocol
20. ision under the board number Fig 5 Correct MS TP connections and location of a Status LED on a BACnet module IMPORTANT NOTE The Ref terminal should NEVER be used to wire shields The 2 shields from each feed of the network connection to a thermostat should be wired together in the back of the thermostat and properly protected to prevent any accidental connection to the ground The joined shield connection should then be grounded at a SINGLE point on the whole segment More than one ground connection to a shielded wire may induce ground loop noises and affect communication 63 4523 01 6 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Network Adapter Status LED Table 3 shows the different possibilities with the Status LED behavior of the BACnet module Table 3 Status LED condition and possible solutions Condition of the Status LED Possible Cause Solution 1 short blink BACnet communication NOT active at default MAC address 254 Change MAC address to another value from 0 to 127 2 short blinks no wires connected to the module The BACnet module is recognized on the thermostat and has been installed on the right thermostat model N A 2 short blinks wires connected to the module Module is not at the same baud rate as the network Power off and on the thermostat 2 short blinks and a longer blink wires connected to the module The module has detected the presence of
21. ler and one for a repeater A repeater is required if more than 64 devices are on a bus TIPS AND THINGS YOU NEED TO KNOW Each TB7600 Series thermostat is delivered from the factory with the default MAC address set at 254 referred to as the Com Addr in the parameters at the thermostat At this value BACnet communication is NOT active and the device will not participate in the token pass either The local LED status for the communication adapter at this point is one short flash only To enable BACnet communication set the local MAC address configuration property of the thermostat to any valid value from 0 to 127 Afterthe initial configuration of your device and if your BAS allows you to remove objects we suggest that you remove all the configuration objects to prevent unnecessary polling of unused objects and to help speed up the network All configuration objects are available and accessible locally from the device itself using the local configuration routine Please refer to the TB7600 Series form number 62 2016 or TB7600 Series with Humidity Control form number 62 2017 installation instructions for details In its default mode of operation the device will automatically match its baud rate to the baud rate of the network Automatic baud rate detection will occur when the MS TP communication port is initialized on power up If the network speed is changed the device will keep listening at the previously detected speed for 10 minu
22. lue R W Y Y Proportional MV 67 Present_Value R W Y Y AV 68 Present_Value R W 20 1 1 Wesel Y Configuration Options Progressive Recovery BV 70 Present Value R W Y V V Event Display MV 71 Present_Value R W vwe t llas lalalalala Options Heating Stages MV 73 Present_Value R W V V Cooling Stages MV 74 Present_Value R W Heatpump Stages MV 75 Present_Value R W Y Economizer Model Configuration Options FREG 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Table 5 Objects m m m m m m m m m m zx x zx x x x zx x zx x x x x x x x x x x Object Name penne Object Property lt lt Instance S e S S S 5 S D N N N N N N N m m m m m m m m m m Economizer Changeover Setpoint AV 77 Present_Value R W Y Economizer Minimum Present Value Position Cooling BV 79 Present_Value R W Enabled Mixed Air Setpoint AV 80 Present_Value R W Y Heatpump Model Configuration Options CORE abel y 1 High Balance Point AV 82 Present Value
23. mal Override Normal Outdoor Temp Override BV 10 Normal Override Normal AUX BI 24 Off On Off G Fan BI 25 Off On Off Y1 Cool BI 26 Off On Off Y2 Cool 27 Off On Off W1 Heat BI 28 Off On Off W2 Heat 29 Off On Off Reversing Valve BI 30 Off On Off DI 1 Status BI 31 Not Activated Activated Not Activated DI 2 Status BI 32 Not Activated Activated Not Activated Local Motion BI 33 No Motion Motion No Motion Frost Alarm BI 36 Off On Off Clock Alarm BI 37 Off On Off Filter Alarm BI 38 Off On Off Service Alarm BI 39 Off On Off Fan Lock Alarm BI 40 Off On Off Temperature Scale BV 47 F F Frost Protection BV 55 Off On Off Aux Contact BV 56 N O Menu Scroll BV 57 No Scroll Scroll Active Scroll Active Fan Control BV 62 Off On On Fan Purge Delay BV 64 Off On Off Progressive Recovery BV 70 Off Active Off Mechanical Cooling Enabled BV 79 Off On Off Comfort Mode BV 84 Comfort Economy Comfort Reversing Valve Configuration BV 85 ae 0 An ra n cip ne n Compressor Interlock BV 86 Off On Off RH Display BV 88 Disabled Enabled Disabled ears BV 92 Disabled Enabled Enabled eem Output BI 93 Off On N A 19 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Property Enumeration Sets for MV Objects Table 10 Property Enumeration Sets for MV Objects Object Name Object Type and instance BACnet Index Text Default value Occupancy Command MV12 Local Occupancy Occupied Unoccu
24. ntegration is the Device object of the Supervisory Controller and the Operator s Workstation This object contains the 2 following required properties Retry Timeout and Number of APDU Retries 1 The Retry Timeout property specifies the time between re transmissions if the acknowledgement has not been received When you are experiencing problems with controllers dropping off line increasing this value may help 2 The Number of APDU Retries property specifies the number of times unsuccessful transmissions will be repeated If the receiving controller has not received the transmission successfully after this many attempts no further attempts will be made For example if one of the thermostats does not reply to a Supervisory Controller SC request and the SC s Retry Timeout is set to 2000 msec and the Number of APDU Retries is set to 1 still at the SC level then the SC will send one other request 2 sec later If the MS TP device does not reply it will be considered Off line by the workstation So having a Retry Timeout value of 10000 msec and a Number of APDU Retries property set to 3 at the SC level may prevent device from dropping Off line These properties should also be changed at the Workstation level since the workstation will likely issue requests to any MS TP devices when the graphics are used 63 4523 01 10 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS TROUBLESHOOTING Error Trouble Condition Possible
25. o extend the network 63 4523 01 4 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Maximum Cable Length The maximum length of a chain is related to its transmission speed The longer the chain the slower the speed Using proper cable the maximum length of an EIA 485 daisy chain is 4000 ft 1200 m This will only work reliably for data rates up to 100 000 bps TB7600 themostats maximum data rate is 76 800 bps If you require a maximum network length of more than 4000 feet then repeaters are required to extend the network EIA 485 Repeaters If you have more than 64 devices or require a maximum network length of more than 4000 feet repeaters are required to extend the network The BASRT B repeater by Contemporary Controls can be used if a repeater is needed The best configuration is to daisy chain the repeaters to the controller From each of these repeaters a separate daisy chain will branch off Fig 3 demonstrates a valid use of repeaters in an EIA 485 network LEGEND EOL END OF LINE RESISTOR R RS485 REPEATER SC SUPERVISORY CONTROLLER M32573 Fig 3 Correct usage repeaters are daisy chained to the supervisory controller and separate daisy chains branch from each repeater Do not install repeaters in series as this may result in network reliability problems Fig 4 demonstrates an incorrect use of a repeater in an EIA 485 network DO NOT ADD SECOND REPEATER IN SERIES LE
26. pied Local Occupancy System Mode HPU MV13 Off Auto Cool Heat Emergency Auto System Mode RTU MV 14 Off Auto Cool Heat Auto Fan Mode MV15 On Auto Smart Smart Keypad Lockout MV18 Level 0 Level 1 Level 2 Level 0 Effective Occupancy MV 34 Occupied Unoccupied Temporary Occupied Depends on local occupancy Heating CPH MV53 3 CPH 4 CPH 5 CPH 6 CPH 7 CPH 8 CPH 4 CPH Cooling CPH MV54 3 CPH 4 CPH 4 CPH 63 4523 01 20 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Table 10 Property Enumeration Sets for MV Objects Object Type BACnet Index Text Default value and instance Object Name 0 hour 1 hour 2 hours 3 hours 4 hours 5 hours Temporary Occupancy MV61 Time 6 hours 3 hours INIIAI OINI 7 hours 8 hours 9 hours 10 hours 11 56 wo 12 hours 0 minute 1 minute 2 minutes Anticycle MV63 2 minutes 3 minutes 4 minutes 5 minutes None RemNSB RemOVR Filter Service DI1 Configuration MV65 None Fan lock None RemNSB R
27. rties can be renamed from any BACnet network management tool as long as the tool itself gives access to write to these properties 63 4523 01 2 WIRING GUIDELINES Overview BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Honeywell uses EIA 485 as the physical layer between their devices and supervisory controllers For clarity we will use the term Device to represent any product with an active EIA 485 network connection including Honeywell and non Honeywell thermostats Table 2 Summary of Specifications for a Honeywell EIA 485 Network Parameter Details Media Twisted pair 22AWG 24 AWG shielded recommended Characteristic Impedance 100 130 ohms Distributed capacitance Less than 100 pF per meter 30 pF per foot Maximum length per segment 1200 meters 4000 feet Polarity Polarity sensitive Multi drop Daisy chain no T connections Terminations TB7600 TB7300 and or TB7200 Series thermostats are installed at both ends of the MS TP network 120 Ohms resistor should be installed at each end To reduce issues with other BACnet devices we recommended keeping like devices on the same bus TB7600 TB7300 and TB7200 Series thermostats can be installed on the same bus 1 ATB7600 TB7300 or TB7200 device is installed at one end of the MS TP network and another device is installed at the other end Install an End Of Line resistor value that matches the other devi
28. tes before resuming auto bauding Re powering the devices will force right away auto bauding If the device should go off line the following binded thermostat parameters will be released Room Temperature Outdoor Temperature Occupancy The BACnet Data Link layer has two key parameters the device object name and the device object ID The device object name must be unique from any other BACnet device object name on the BACnet network i e not just the MS TP sub network The device object ID must be unique from any other BACnet device object ID on the entire BACnet network i e not just the MS TP sub network On models with scheduling time synchronization can be made through a network even if the thermostat does not support the full date Therefore the device cannot claim conformance to the DeviceManagement TimeSynchronization B DM TS B service The device object does not have the Local Time or Local Date properties Programmable models with scheduling are intending for stand alone applications where the thermostat may be added to the network at a later time Once a programmable thermostat is added to a network all schedule must be done through the Workbench Local control of network settings is not supported To hide the scheduling option from the local thermostat use one of the 815 and set to Rem NSB if a BI is not being used Device Name and Device ID properties are writable in Honeywell device object Both prope
29. ut a factory installed PIR cover More Information The additional following documentation is available on http customer honeywell com TB7600 Series Installation Instructions form number 62 2016 TB7600 Series with Humidity Control Installation Instructions form number 62 2017 The PIR Application Guide for TB7600 Series form number 63 4525 Contents 01161 61016 cect 1 Compatibility ceto 2 Tips and Things You Need to Know 2 Wiring guidelines 2 oett 3 Network Configuration 2 2 2 4 Network Adapter 6 Integration 7 Troubleshooting 11 12 TB7600 Series Protocol Implementation Conformance Statement PICS 12 BACnet Objects Supported 13 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS COMPATIBILITY Honeywell TB7600 Series thermostat compatiblity information is provided in Table 1 Table 1 TB7600 Thermostat Compatibility Information WEBs AX Controller Thermostats Per Controller WEBStation AX WEB 2xx 126 3 0 or later WEB 6xx 126 3 0 or later WEB 7xx 126 3 5 128 total devices supported One node used by control
30. version Property 98 R Default is Version 1 Protocol Revision Current BACnet firmware protocol revision Property 139 R Default is Version 2 Max ADPU Length Maximum ADPU Length accepted Property 62 R Default is 244 ADPU Timeout ADPU timeout value Property 10 R Default is60 000 ms Application Software Thermostat base application software version Version Default is based on current released version Property 12 R Max Master R W Maximum master devices allowed to be part of the network 0 to 127 default is 127 MS TP Address BACnet MS TP MAC Address Proprietary attribute Property 1001 RW Default is as assigned by configuration MS TP Baud Rate BACnet MS TP Baud Rate Proprietary attribute Property 1002 R W Range is 1 9 6 KBps 2 19 2 KBps 3 38 4 KBps 4 76 8 KBps and 5 Auto Baud Rate Index 5 is Write only Reading attribute will state current Baud rate used Writing index 1 to 4 will fix the Baud rate to the desired value 13 63 4523 01 BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS Objects Table Table 5 Objects 3 r Type and x x x Object Object Property m a a a a a Instance S E e S 7 S 5 D 1 see cee oE EEM 8 8 Room Temperature 7 Present_Value R W
Download Pdf Manuals
Related Search
Related Contents
Le Bulletin Municipal -STUDIO 15 R/C LightMasterTM USER MANUAL Brunet, Roger (1987) La carte, mode d`emploi. Paris, Fayard/Reclus Manual - OMEGA Engineering Copyright © All rights reserved.
Failed to retrieve file