Honeywell T7147 User's Manual

image

Contents

1. Honeywell 17147 Remote Sensor and Override Module PRODUCT DATA FEATURES Locking cover e Override key Warmer Cooler keys on some models 3 HOUR eo eo WARMER e Key lock override security available e APPLICATION The T7147 Remote Sensor and Override Module is for use with the T7300 Q7300 Programmable Commercial Thermostat system The T7147 provides space temperature sensing switch initiation and indication of overrides from a remote location Contents Application ast seen 1 ESTOS rn im TE nen 1 SA ER 2 Ordering Information 224s4s0ernnennnnnnnennnnnnnnnnnen nn 2 InstallatiO oca 3 WING ESE fe 4 Operation su een lee 6 Eneko U aia ken iphone 6 U S Registered Trademark HII 634065 1 Copyright 2001 Honeywell All Rights Reserved T7147 REMOTE SENSOR AND OVERRIDE MODULE SPECIFICATIONS IMPORTANT The T7147 is factory calibrated It does not require field calibration and cannot be field adjusted 1 13 16 46 gt Models 4 anoun T7147A1002 Remote Temperature Sensor amp Override 3 1 4 EOOLER OCCUPIED WARMER Module Connects to Q7300 Contains remote sensor 83 DAR 2 LED and push button switch to invoke 3 Hour Occupied O OB B from remote location a T7147A1010 Remote Temperature Sensor amp Override Module Connects to Q7300 Contains remote sensor LED 3 3 4 and 3 push button switches to invoke 3 Hour Occupied and 96 Warme
2. Occupied LED and Warmer or Cooler LED remains on for the duration of the 3 hour override This override may be performed at any time regardless of whether the thermostat system is operating in the occupied or unoccupied mode NOTES For additional details consult the T7300 Q7300 Specification sheet form 63 4038 Premature exit from either override can be achieved by pressing the 3 Hour Occupied key again The T7300 then returns to normal operation 63 4065 1 6 o CHECKOUT 1 Allow the sensor to stabilize to ambient conditions before taking a resistance measurement The sensor resistance measurement should be in accordance with the device temperature curve see Fig 2 Check operation of the 3 Hour Occupied key a Press the 3 Hour Occupied key once b The LED above the key turns on Go to the T7300 thermostat and check it to see that the display arrow indicator points to 3 Hr Occupied On models with Warmer and Cooler keys Press the Warmer key once The LED above the Warmer key comes on Press the Cooler key The LED above the Warmer key turns off and the LED above the Cooler key turns on Press the 3 Hour Occupied key once The LED above this key turns off as well as those above either the Warmer or Cooler keys Go to the T7300 thermostat and check to see that the arrow indicator on the display no longer points to 3 Hr Occupied and has returned to its currently programmed occupied or unoccupied pe
3. TION Erratic System Operation Hazard Failure to follow proper wiring practices can introduce disruptive electrical interference noise Keep wiring at least one foot away from large inductive loads such as motors line starters lighting ballasts and large power distribution panels Shielded cable is required in installations where these guidelines cannot be met Ground shield only to grounded controller case IMPORTANT All wiring must comply with local codes and ordinances NOTES Terminal screws are provided on the device for wiring connections Wiring to device is low voltage and need not be in conduit unless required by code 1 Connect correct control wires from the Q7300 subbase to the T7147 see Fig 4 and 5 2 Ensure that Q7300 subbase switch 5 local remote sensor select switch is in the OFF position Refer to the T7300 Q7300 Specification sheet form 63 4038 for details IMPORTANT The ground GND connection at the T7147 is required Use the junction box or conduit for a convenient grounding location 3 Ensure all connections are tight and secure Loose or intermittent wire connections cause inconsistent system operation 4 When installation is complete perform the checkout procedure see the Checkout section 63 4065 1 4 Averaging Sensors When the controlled zone is a large area it can be advantageous to use a T7147 and several remote temperature sensors dispersed throughout the a
4. age Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Location Select a location on an inside wall away from drafts or dead air spots behind doors and corners hot or cold air ducts radiant heat from the sun or electrical equipment unheated areas behind the thermostat wall Locate the T7147 about 5 ft 1 5 m above the floor in an area with good air circulation within easy reach of users Mounting 1 P PYN SN Loosen the cover locking screw with the Allen wrench provided and remove the T7147 cover Run wire to the selected location Thread wire through T7147 base semicircular hole Make connections to T7147 see Wiring section If air drafts occur through the wall opening eliminate them with suitable insulation material Four mounting screws are provided a 2 self tapping type for wall mounting b 2 for outlet box mounting Select the proper screws for the application Fasten the T7147 to the wall or outlet box with screws through the T7147 base assembly mounting holes See Fig 3 Replace the cover assembly and tighten the cover locking screw WALLPLATE MOUNTING SCREW 2 MOUNTING TAB 2 INSIDE COVER MOUNTING TAB SLOT 2 WIRING TERMINALS 4 Ne THERMOSTAT COVER LOCKING SCREW M17884 Fig 3 Mounting the T7147 63 4065 1 T7147 REMOTE SENSOR AND OVERRIDE MODULE WIRING CAU
5. aging application 5 63 4065 1 T7147 REMOTE SENSOR AND OVERRIDE MODULE OPERATION Sensor The remote sensor control element is a negative temperature coefficient NTC thermistor As room temperature increases the resistance of the thermistor decreases As room 2 temperature decreases the resistance of the thermistor increases The T7300 detects the thermistor resistance change and controls the space temperature by sequentially staging the heating cooling equipment on and off NOTE The T7047C1025 uses the same sensor element 3 Hour Occupied When correctly wired pressing the 3 Hour Occupied key sends a signal from the T7147 to the T7300 Q7300 Upon receipt of this signal the T7300 Q7300 proceeds into the 3 Hour Occupied override In response the T7300 Q7300 sends a signal back to the T7147 to turn on the 3 Hour 5 Occupied LED The 3 Hour Occupied LED remains on for the duration of the 3 hour override NOTE For additional details consult the T7300 Q7300 Specification sheet form 63 4038 3 Hour Setpoint Adjust When wired correctly pressing the 3 Hour Occupied key followed by the Warmer or Cooler key sends a signal from the T7147 to the T7300 Q7300 The T7300 Q7300 upon receipt 6 of this signal proceeds into the 3 Hour Setpoint Adjust override In response the T7300 Q7300 sends a signal back to the T7147 that turns on the 3 Hour Occupied LED and the appropriate Warmer or Cooler LED The 3 Hour
6. r Cooler setpoint adjustments from remote location Honeywell T7147A1028 Remote Temperature Sensor amp Override Module Connects to Q7300 Same as T7147A1010 except T L 171 vo includes key lock switch to enable disable remote override l operation gt 1 18 29 1 5 8 41 1 4 gt 2 13 16 71 e 6 je 3 5 8 92 e Mounting Mounts on wall or 2 x 4 inch vertical outlet box with not ALL MODELS HAVE WARMER COOLER FUNCTION M17881 screws provided Dimensions See Fig 1 Fig 1 17147 dimensions in in mm Table 1 Temperature Offset for Remote Sensor Wiring En cable length between 17300 07300 and T7147 Temperature Monitored 18 AWG 20 AWG 22 AWG ee 50 i a oe sensor wire 50 to 90 F weed aaa Oe cable 1000 ft 305 m total length See Table 1 10 to 32 C 0 3 C 0 4 C 0 6 C Temperature Sensor Thermistor resistor NTC element ee Sensor Resistance oo o Resistance decreases as temperature increases Fig 2 1420 ohms nominal at 75 F 24 C resistance changes 15 ohms for each 1 F 0 6 C temperature change iedo Temperature Ratings 1400 Ambient 40 to 110 F 4 to 43 C Shipping 30 to 150 F 34 to 66 C 1200 Humidity Ratings 5 to 90 RH non condensing Accessories 230492A Keys for T7147A1028 10 0 10 20 30 40 TEMPERATURE DEGREES M4034 Fig 2 T7174 Remote Sensor Resistance change wi
7. rea to obtain an average zone temperature signal See Fig 6 and 7 NOTE Only one T7147 can be used in any one T7300 Q7300 system Cpe DOODOW LOIS A CONNECTIONS TO CA3 AND CA4 NOT REQUIRED ON T7147A2000 A ROUTE EXCESS WIRING AWAY FROM SENSOR ELEMENT FOR OPTIMUM PERFORMANCE M17880 Fig 4 Connecting wires to T7147 T7147 REMOTE SENSOR AND OVERRIDE MODULE T7300 Q7300 y 4 Gas WARMER COOLER FUNCTIONS ARE NOT AVAILABLE WITH THE T7147A1002 SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS A THE GROUND GND CONNECTION TO THE 17147 IS REQUIRED USE THE JUNCTION BOX OR CONDUIT A l FOR A CONVENIENT GROUNDING LOCATION mo Fig 5 Typical wiring diagram for T7147 used with T7300 Q7300 Thermostat Subbase T7300 Q7300 09 to tO Cr Arte GROUND GND CONNECTION A TO THE 77417 IS REQUIRED USE THE onty ONE T7417 ALLOWED PER SYSTEM JA SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS oO yo Ex Ged Grd Cad Gad Grd JUNCTION BOX OR CONDUIT FORA CONVENIENT GROUNDING LOCATION M10194 onty ONE T7417 ALLOWED T7300 PER SYSTEM JA SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS THE GROUND GND CONNECTION PETE ae ET y il Am THE 17417 IS REQUIRED Q AE C 7 EE C USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT ERA it GROUNDING LOCATION 5 A M10195 Fig 7 Wiring for T7174 used in a nine temperature sensor aver
8. riod aoop mo NOTE Ifthe T7147 does not check out review the wiring and connections between the Q7300 and the T7147 Replace the T7147 if wiring continuity checks out If the new T7147 does not check out replace the Q7300 Check operation of the complete control system as directed in the T7300 Q7300 Specification sheet form 63 4038 63 4065 1 Honeywell Home and Building Control Home and Building Control Honeywell Asia Pacific Inc Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limit e Room 3213 3225 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario No 30 Harbour Road Belgium Suite 200 MIV 429 Wanchai Sunrise FL 33325 Hong Kong 63 4065 1 B B Rev 3 01 amp pd onan los www honeywell com post consumer paper fibers
9. th change in temperature ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor refer to the TRADELINE Catalog or price sheets for complete ordering number If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Home and Building Control Sales Office check white pages of your phone directory 2 Home and Building Control Customer Relations Honeywell 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 800 328 5111 In Canada Honeywell Limited Honeywell Limit e 35 Dynamic Drive Scarborough Ontario M1V 4Z9 International Sales and Service Offices in all principal cities of the world Manufacturing in Australia Canada Finland France Germany Japan Mexico Netherlands Spain Taiwan United Kingdom U S A 63 4065 1 2 T7147 REMOTE SENSOR AND OVERRIDE MODULE INSTALLATION alla Installing this Product Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions AN CAUTION Electrical Shock or Equipment Dam