Honeywell 301c User's Manual
Contents
1. Device GP2 301IRF 301EM 201T2 vulbus 90DM3R GAZ GAZ GAZ GAZ GAZ Amin Amin Amin Amin Alrm Amax Amax Amax Amax Bmin Bmin Bmin Bmin Bmax Bmax Bmax Bmax Cmin Cmin Cmin Cmin Cmax Cmax Cmax Cmax rel1 rel1 rel1 snsr1 rel1 rel2 rel2 rel2 snsr1 rel3 rel3 snsr1 rel4 snsr1 out snsr1 out2 a snsr1 3 out3 8 snsr1 M 510324 301C User Manual 95 7 10 Honeywell BACnet IP MODULE Object Table For Honeywell Network Devices Objects residing in Honeywell network devices Device 301AP 301C 301R 301ADI 901T rel1 rel1 rel1 AN to Al16 GAZ rel2 rel2 rel2 BI1 to BI12 Amin rel3 rel3 rel3 Amax buzz rel4 rel4 Bmin buzz rel5 Bmax rel6 Cmin rel7 Cmax rel8 v O Ko Ko O 96 301C User Manual Honeywell M 510324 7110 Object Table For Honeywell Network Devices BACnet IP MODULE Objects residing in Honeywell network devices Device ECF9 S301RLC 301W 301RW Std Device GAZ GAZ GAZ rel1 GAZ Amin Amin Amin rel2 Amin Amax Amax Amax rel3 Amax Bmin Bmin Bmin rel4 Bmin Bmax Bmax Bmax rel5 Bmax Cmin Cmin Cmin rel6 Cmin Cmax Cmax Cmax rel7 Cmax rel8 2 O QUE WH O Std Device refers to the following products S301M 420MDBS an
2. Wireless Network gt Consolidate Route Consolidate Route 6 Reset Network VAL 00060 Enter to confirm 7 Status Log NoLog MAX 65535 gt Esc to cancel 8 Consolidate Route MIN 00000 M 510324 301C User Manual 89 7 10 Honeywell System Programming Wireless Network Menu 90 301C User Manual M 510324 Honeywell 7 10 BACnet IP MODULE BACnet IP MODULE BIP option Specifications Ethernet Port 10 100 compatible with 10 Base T interface RJ 45 Visual Indicators GreenLED LINK Yellow LED ACT Network Configuration See 301C BACnet menu section BACnet IP protocol UDP Port 47808 This value is not modifiable using the 301C The module has been developed as per ANSI ASHRAE Standard 135 2001 BACnet A Data Communication Protocol for Building Automation and Control Networks The Data Link Layer option is per BACnet IP Annex J http www ashrae org BACnet Objects BACnet objects represent any information available through the 301C sub network Each available value is represented by one object of a specific type There are currently 6 object types supported Analog Input represented by Al Analog Value represented by AV Binary Input represented by BI Binary Output represented by BO Binary Value represented by BV Device represented by DEV M 510324 301C User Manual 91 7 10 Honeywell BACnet IP MODULE Analog Input The Analog Input object type
3. 192 168 1 100 OxBACO Consulter la norme ASHRAE 135 2001 Annex J section J5 pour de plus amples informations sur ce sujet 78 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu reseau sans fil Menu reseau sans fil Le r seau sans fil disponible seulement dans le 301C W version 3 et plus du 301C permet de configurer les param tres de communication sans fil de consulter les diagnostics du r seau et de travailler avec les divers aspects des noeuds sans fil sondes Reseau sans fil Parametres 1 Parametres 4 7B7177EFACEOO Menu Systeme 2 Diagnostics _ 2 WC Version Option Invalide 3 Noeuds _ 3 PANID 4 Nouveau noeud 4 CanalRF Mod Log 5 Hiberner 5 Mode Log No Log 6 RAZ reseau 6 Association Ena 7 Log Statut NoLog 7 Noeuds 8 Consolider acc s 8 Max noeuds 9 Max sauts Association 10 Puissance 11 AHFO 12 BO mae E VAL 00000 15 119 MAX 65535 16 MMO 9 MIN _00001 17 BMO 0 Ny 18 KNSRO 0 MAC Tere partie 19 ENSRO 0 VAL 00155F00 20 Clone WC MAX FFFFFFFF MIN 00000000 Diagnostics Menu Systeme 1 Rprt liens faibles gt gt be 2 Rprt liens perdus Aucun n ud trouve GE Noeu
4. START of system log dump 2007 04 18 13 19 05 2007 04 04 18 42 06 Accessing menu 2007 04 04 18 43 47 Event 1 definition modified 2007 04 04 18 48 12 Exiting menu 2007 04 04 18 54 49 System power down 2007 04 04 18 56 40 System power up 2007 04 04 19 02 44 Accessing menu 2007 04 04 19 03 07 Event 6 definition modified 2007 04 04 19 03 21 Exiting menu 2007 04 05 10 51 28 Accessing menu 2007 04 05 10 54 59 Database reset 2007 04 05 10 55 18 Tx 25 parameters modified 2007 04 05 10 55 29 Group 0 definition modified 2007 04 05 10 55 36 Group 0 definition modified 2007 04 05 10 55 46 Group 0 definition modified 2007 04 05 10 55 55 Group 4 definition modified 2007 04 05 10 55 57 Exiting menu 2007 04 05 10 56 02 Accessing menu 2007 04 05 10 56 19 Tx 24 parameters modified M 510324 301C User Manual 55 7 10 Honeywell System Programming Config Menu Config Menu The Config menu contains several main configuration screens and is used to program the controller display mode adjust the date and time select the display language change the controller access password modify the Slave Port configuration set the Relay Configuration and select the AP Broadcast mode Each main screen offers further programming options as shown MENU gt 5 Copy 7 Network 3 6 Config 8 Tests 6 Config Manual scroll mode Set Date and Time Menu francais Date and Time gt gt 2005 11 21 11
5. 321 days 301C User Manual Honeywell gt M 510324 7 10 System Programming Tx Info Menu Status Code These screens display transmission or node status and sensor status for the selected transmitter This read only information can assist service personnel in troubleshooting The XNX and XCD gas detectors will report the warning or fault number iFaultWarnNumber in hexidecimal on the third line These transmitters will also report the monitoring state iMonitoringState in the fourth line See the transmitter documentation for interpretation of fault numbers and monitoring states lt 1 Tx INFO 001 gt Status Codes Tx Status 0000h Monitor State 0001h Typical display for XNX or XCD lt 1 Tx INFO 001 gt Status Codes Tx Status 0000h Snsr Status 0000h Typical display for other transmitters Erase Current Tx This function allows the configuration to be erased or the Tx address for the displayed component to be changed Note Selecting erase current Tx only erases the current device entry Tx Info configuration No other data is erased 1 Tx Info 001 erase current Tx Change Tx Address M 510324 301C User Manual 35 7 10 Honeywell System Programming Tx Info Menu Change Tx Address Selecting Change Tx Address allows users to move a device from one TX address to another e Use the arrows to scroll to Change Tx Address and press Enter to select e Inthe next screen
6. Does the BBMD support registrations by Foreign Devices 0O Yesi No Jeux de caract res support s L indication du support de multiples jeux de caract res ne signifie pas qu ils peuvent tous tre support s simultan ment M ANSI X3 40 IBM Microsoft DBCSO ISO 8859 1 O ISO 10646 UCS 2 0 ISO 10646 UCS 4 D JIS C 6226 Si ce produit est un point d acc s de communication d crire les types d quipements ou r seaux non BACnet support s par le point d acc s M 510324 Manuel de l utilisateur 301C 109 7 10 Honeywell Sp cifications Sp cifications Alimentation 301C 17 27 Vca 50 60 Hz 8 64 VA 18 36 Vcc 350MA O 24 Vcc 8 4 VA Plage de temp rature de fonctionnement Plage d humidit relative de fonctionnement Altitude de fonctionnement Jusqu 3 000 m 9843 pi Capacit mise en r seau Jusqu a 96 transmetteurs 32 par port Ports 1 2 Modbus et Vulbus Port 3 Modbus seulement Port 4 Communication esclave c d pour option BACNet Communication Jusqu a 609 m 2 000 feet par port longueur de lignes D rivation maximum 20 m 65pi par d rivation 40 m au total 130 pi 20 C a 50 C 4 F to 122 F 0 a 95 RH sans condensation Port e communication sans fil 30 m 98 5 pi Interface utilisateur Affichage graphique matrice 122 x 32 points r tro clairage clavier convivial Indicateurs visuels Alimentation DEL vert Alarme A B C DEL rouge Faute DEL jaune
7. n est lanc 16 MMO 0 D fini la bande passante de la mesure de la relance de message 17 BMO 0 D fini la bande passante de la mesure des balises manqu es 18 KNSRO 0 D fini la fr quence a laquelle le noeud met a jour les informations de voisins connus 19 FNSRO 0 D fini la fr quence a laquelle le noeud cherchera de nouveaux voisins 20 Clone WC Quoique ce menu est accessible il n effectue aucune fonctions Il servira pour des fonctions avanc es a venir M 510324 Manuel de l utilisateur 301C 83 7 10 Honeywell Programmation du syst me Menu reseau sans fil Diagnostics Le menu diagnostics permet de consulter des rapports de liens faibles et de liens perdus Lors de la s lection d une de ces options l cran affiche une liste d information pour le noeud cette liste est identique a celle de l option 3 Noeuds du menu principal Sans fil S il n y a pas de liens faibles ou de liens perdus l cran affiche bri vement Menu Systeme Aucun noeud trouve Si le rapport de lien faible ou de lien perdu contient plus d un noeud utiliser les fl ches de gauche ou de droite pour naviguer d un noeud l autre et ensuite utiliser les fl ches haut et bas pour d rouler la liste d informations pour le noeud Diagnostics Menu Systeme 1 Rprt liens faibles 2 Rprt liens perdus Aucun n ud trouve Noeuds 1 1D 121 79h 2 7B7177EFACE0049 3 Produit VA301W 84 Manuel de l utilisateur 301C M 510324 Honeywell
8. rel4 snsr1 out1 snsr1 out2 snsr1 3 out3 3 snsr1 M 510324 Manuel d utilisateur 301C 100 7 10 Honeywell Objets pour les dispositifs de r seau Honeywell Objets BACNet Objets pour les dispositifs de r seau Honeywell Dispositif 301AP 301C 301R 301ADI 901T rel1 rel1 rel1 Al to Al16 GAZ rel2 rel2 rel2 BI1 to BI12 Amin rel3 rel3 rel3 Amax buzz rel4 rel4 Bmin buzz rel5 Bmax rel6 Cmin rel7 Cmax rel8 ao D Q O M 510324 Manuel d utilisateur 301C 101 7 10 Honeywell Objets pour les dispositifs de r seau Honeywell Objets pour les dispositifs de r seau Honeywell Dispositif ECF9 S301RLC 301W 301RW Std Device GAZ GAZ GAZ rel1 GAZ Amin Amin Amin rel2 Amin Amax Amax Amax rel3 Amax Bmin Bmin Bmin rel4 Bmin Bmax Bmax Bmax rel5 Bmax Cmin Cmin Cmin rel6 Cmin Cmax Cmax Cmax rel7 Cmax rel8 2 a Std Device comprend les produits suivants S301M 420MDBS and 90DM4 Les valeurs Cmin et Cmax s appliquent uniquement au 90DM4 Objets BACNet Exemples d objet Exemple 1 Voici une repr sentation de l entr e de sonde d un dispositif de r seau VA301D2 de Vulcain Name 301D2 CO2 AD 14 CQ2 Value 600 Units PPM Object 1 A12 Description Analog Input 1 est l instance de dispositif unique du 301C
9. represents a group created in the Groups Menu in the controller When scrolling through the available product type list this name will appear as many times as there are groups created in the controller example Group 1 Group 2 Group 3 etc If a group is selected as the product type then the sensor type options are limited to MIN MAX and MEAN 28 301C User Manual M 510324 Honeywell 7 10 System Programming Tx Info Menu COM Menu This screen displays the selected communication protocol for device addresses from 1 to 96 Each transmitter s protocol is defined by the controller see Network Auto configuration section 1 TxiInfo D 001 COM Mdbs RTU 8D 1S EP 9600 bauds If a transmitter is compatible with several different protocols it can be modified using to one of the following options Vulbus Mdbs ASCII 7D 2S NP 9600 bauds Mdbs RTU 8D 2S NP 9600 bauds Mdbs RTU 8D 1S NP 9600 bauds Mdbs RTU 8D 1S OP 9600 bauds When a transmitter is configured with the Modbus communication protocol the transmitters automatically sends the programmable parameters to the controller Note Vulbus transmitter parameters must be programmed manually M 510324 301C User Manual 29 7 10 Honeywell System Programming Tx Info Menu Scale Menus 1 and 2 These menus appear only for certain devices Scale 1 allows the detection range minimum and maximum to be defined for the selected device Whatever value is specified is
10. tre configurer manuellement 30 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu INFO Tx Echelle 1 et 2 Ces menus appara ssent uniquement pour certains dispositifs Echelle 1 permet de modifier la plage de d tection minimum et maximum pour l appareil s lectionn 1 INFO TxD Echelle 1 Max 00250 Min 00000 Echelle 2 permet de configurer le facteur de division de la plage entre 0 et 65535 et de modifier l unit de mesure pour la plage s lectionn e 1 INFO Tx 121 Echelle 2 gt Facteur 00001 Le facteur permet des limites de plages plus pr cises pour la d tection En divisant la valeur de plage maximum dans le premier cran Echelle 250 dans cet exemple par 10 il est possible de d tecter une valeur de plage de 25 0 Les Unit s permettent de r gler l unit de mesure de chaque appareil F R gle l unit de mesure en degr s Farenheit C Regle l unit de mesure en degr s Celcius RH R gle l unit de mesure au pourcentage d humidit relative mV R gle l unit de mesure du point en millivolts V R gle l unit de mesure du point en volts mA R gle l unit de mesure du point en milliamps R gle l unit de mesure du point au pourcentage du gaz ppm R gle l unit de mesure du point en parties par million du gaz M 510324 Manuel de l utilisateur 301C 31 7 10 Honeywell Programmation du syst me Me
11. 12 BO 0 13 SUO 0 14 LCO 18 PAN ID 15 LTO o VAL 1805 16 MMO 0 MAX FFFF 17 BMO o MIN 0001 le no gt MAG ist part On Gn aie es gt VAL 00155F00 i MAX FFFFFFFF MIN 00000000 Diagnostics System Menu 1 Weak Link Report 2 Lost Link Report gt gt No Node Found oF Lef Nodes 1 1D 121 79h 2 7B7177EFACE0049 a Nodes ar 3 Product VA301W e y The Nodes menu earing under 2 7B7177EFACE0049 both Weak and Lost ink reports is 3 Product VA301W identical to the Nodes option 3 in 4 Link Quality 1 the Wireless Network menu 5 Op Mode Log 6 Net Addr 9 7 SW slot 1 8 of parents 1 9 DP id 0 10 DP Net Addr 0 11 DP LOI 2 12 DP Retries 2 13 DP BM 0 14 DP LC 256 15 API ID 0 16 API Net Addr System Menu 17 APL LOL 16 Pp Invalid Option 18 APL Retries 128 19 API BM 2 20 APL LC 27132032 21 AP2 1D 2 22 AP2 Net Addr 31756 23 AP2 LQL 198 24 AP2 Retries 190 25 AP2 BM 0 26 AP2 LC 56320 27 LSU 661 28 Status Alive 29 Freshness 2 30 Version Al4 Hibemate ai cH bernate J Enter to confirm 32 Replace gt Esc to cancel 33 Remove J 34 Consolidate Route 35 Failsafe ON New Node VAL 121 MAX 180 MIN 121 Hibernate Enter to confirm p Esc to cancel Status Log Status Log Enter to confirm gt gt No Log A Esc to cancel Consolidate Route Conslidate Route VAL 00060 Entertocontirm PP MAX 65535 Esc to cancel MIN 00000 M 5103
12. Indicates the number of errors in the response for the last 16 requests Timeouts Indicates the number of timeouts no response for the last 16 requests 62 301C User Manual M 510324 Honeywell 7 10 System Programming Network Menu Remote Calibration The network menu also offers a Calibration option for use with devices that support network calibration 7 Network Statistics 3 Calibration The Calibration screen contains four 4 lines of information Calib 007 S301M Status Normal Set Zero Set Span 246 PPM Line 1 Indicates the mode Calib meaning calibration the Modbus address of the device to calibrate 001 and the type of device to calibrate 301D2 Line 2 Indicates the status Normal or In calib of the specified device Line 3 Displays the function to perform Set Zero Line 4 Displays the function to perform Set Span and the span gas concentration value 246 ppm 5 On the first line scroll to the device address and press Enter 6 Scroll through the devices to display the desired device and press Enter to select 7 The second line displays the device s status 8 Scroll to select the desired function Set Zero to set the device s zero and press Enter to select 9 Upon pressing Set Zero the controller requests confirmation Calib 007 S301M Status Normal gt Set Zero Set Span 246 PPM The device must be configured in the 301C s database in order to be incl
13. Tx DEL jaune Rx DEL vert Sorties 4 relais DPDT 5A 30Vcc ou 250 Vca charge r sistive Alarme sonore 65dBA 1 m 3 pi D lais D lais configurables Avant Apr s Pile Pile au lithium 3 V Bo tier NEMA 4X ABS polycarbonate int rieure Dimensions h I p 28 x 20 3 x 7cm 7 99 x 11 02 x 2 76 Poids 1 1 Kg 2 4 Ibs Certifications conforme a ANSI UL 61010 1 CAN CSA C22 2 No 61010 1 ETL 116662 M 510324 Manuel de Putilisateur 301CW 111 8 10 Honeywell Garantie limit e Garantie limit e Garantie limit e Honeywell Analytics Inc garantie l Acheteur d origine et ou au client final Acheteur de produits Vulcain Produit que si une pi ce quelconque du produit s av re d fectueuse soit en mat riel ou en main d oeuvre dans douze 12 mois cette pi ce sera r par e ou remplacer sans frais la discr tion d Honeywell Analytics si exp di port pay a Honeywell Analytics at 4005 Matte Blvd Unit G Brossard Quebec J4Y 2P4 dans l emballage d origine ou l quivalent Le Produit sera retourn au client port pay si Honeywell Analytics d termine que la pi ce est d fectueuse en raison de d faut mat riel ou de main d oeuvre La r paration ou le remplacement d une telle pi ce d fectueuse repr sente la seule et exclusive responsabilit d Honeywell Analytics sous cette garantie limit e Politique de Retour Les frais suivants seront applicables lors de retour de produi
14. connexion du c blage la centrale Le c blage inclut l alimentation la communication la connexion BACNet et les relais chacun avec une position et un chiffre assign e sur la carte J22 Alimentation J23 J24 Entr es Communication Sorties relais 1 4 Cavalier SHDN EOL Resistors 1 4 Connecter l alimentation la centrale voir Connexions d alimentation pour les d tails Connecter les c bles de communication aux canaux 1 3 Le canal 4 est utilis pour communication esclave de Modbus Selon la configuration d sir e connecter le c blage soit aux bornes N O ou N C Placer le cavalier d interruption d alimentation sur les connecteurs pour r initialiser le syst me Placer le cavalier sur les connecteurs pour cr er une connexion et att nuer les chos de communication M 510324 7 10 Manuel de lutilisateur 301C 15 Honeywell D tails de connexion Connexions d alimentation Connexions d alimentation La centrale 301C n cessite une plage d alimentation de 17 27 Vca 50 60 Hz 8 64 VA 18 36 Vcc 350 mA 24 Vcc 8 4 VA La polarisation n importe pas que ce soit en mode CA ou CC Le syst me doit tre mis a la terre sur le transformateur et un circuit d di doit tre utilis Connexions de communication Les c bles de communication doivent tre mis la terre sur le terminal blind avec les fils torsad s et blind s paire Belden 2 24 AWG 9841 ou quivalent Le c
15. normal 2004 01 23 17 57 25 001_CO_ppm 0 normal 002_NO2_ppm 1 0 normal 003_CO_ppm 0 normal 2004 01 23 17 58 25 001_CO_ppm 0 normal 002_NO2_ppm 1 5 normal 003_CO_ppm 0 normal La premi re colonne affiche la date aaaa mm jj et heure hh mm ss de l enregistrement Cet exemple indique un d lai configur un intervalle d une minute La troisi me colonne affiche l adresse du transmetteur et le type de sonde et la quatri me colonne indique la concentration et l unit de mesure Les colonnes se r p tent pour chaque transmetteur s par es par des traits d union La liste continue ainsi jusqu au dernier transmetteur dans la liste M 510324 Manuel de l utilisateur 301C 51 7 10 Honeywell Programmation du syst me Menu acquisition D buter et arr ter log even Le menu Acquisition offre l option d enregistrement d v nements L enregistrement d v nements enregistre les transactions de la centrale les v nements les avertisseurs de Tx et d alarmes et le statut de relais Lorsque Debuter log even est affich le mode acquisition enregistrement est inactif Lorsque Arreter log even est affich les donn es sonten cours d enregistrement Appuyer sur Enter pour d buter ou arr ter l enregistrement Lorsque les donn es d v nements sont enregistr es le syst me cr e un fichier evaammjj log Ce registre indique la date l heure et l v nement Voici un exemple d un
16. seau et efface les donn es du noeud de la m moire du coordonnateur et de la base de donn es de la centrale Option 34 Consolider acces permet de forcer le noeud de trouver le meilleur chemin vers la centrale en utilisant un parent alternatif M 510324 Manuel de l utilisateur 301C 89 7 10 Honeywell Programmation du syst me Menu reseau sans fil Nouveau noeud Le menu Nouveau noeud permet d ajouter un nouveau noeud dans le r seau et de pr ciser le num ro d identificateur assign a l adresse MAC Reseau sans fil Nouveau noeud 4 Nouveau noeud VAL 09 5 Hiberner MAX 3A 6 RAZ reseau MIN 09 MAC ere partie VAL 00155F00 MAX FFFFFFFF MIN 00000000 gt MAC 2e partie VAL 80000024 MAX FFFFFFFF MIN 00000000 e D rouler l option Nouveau noeud puis appuyer sur Enter pour s lectionner e Dans l cran Nouveau noeud changer le num ro d identificateur dans le champs VAL puis appuyer sur Enter Appuyer sur Enter pour confirmer e Dans l cran MAC tere partie inscrire les 8 premiers chiffres de l adresse MAC puis appuyer sur Enter Appuyer sur Enter pour confirmer Dans l cran MAC 2e partie inscrire les 8 derniers chiffres de l adresse MAC puis appuyer sur Enter e Appuyer sur Enter pour confirmer Ladresse MAC du noeud est imprimer sur le bo tier du noeud Note Si le num ro d identificateur existe d j cette fonction ne sera pas compl
17. zones Receiving and Unpacking Upon receiving the controller unit e Check that the package is undamaged e Carefully open the package e Locate the packing slip or purchase order and verify that all items on the order are present and undamaged Note If the package or any of its contents are damaged please refer to the Warranty section at the back of the manual for instructions M 510324 301C User Manual 11 7 10 Honeywell Introduction Installation Instructions Installation Instructions Basic Guidelines Follow these instructions to the letter to ensure that the equipment will function properly Failure to respect these guidelines will release Honeywell Analytics from any responsibility in the event of improper functioning e Locate all units in areas easily accessible for service e Avoid locations where instruments are subject to vibrations e Avoid locating units near sources of electromagnetic interference e Avoid locating units in areas subject to significant temperature swings e Verify local requirements and existing codes that may impact choice of location 12 301C User Manual M 510324 Honeywell 7 10 Introduction Installation Instructions Surface Mount Installation It is recommended that controllers be installed 5 feet 1 5 m above the floor at approximate eye level 5cm y 17 4 cm 613 32 Mark the holes as shown e Height markers 6 13 32 apar
18. 2005 04 27 11 06 02 1_C02 ppm 503 normal 2005 04 27 11 06 15 1_CO2_ppm 562 normal 2005 04 27 11 06 28 1_C02 ppm 645 normal 2005 04 27 11 06 39 1_C02 ppm 557 normal 2005 04 27 11 30 45 1 CO2 ppm 715 normal 50 Manuel de Putilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu acquisition Debuter et arreter log Tx L tape pr c dente traitait la fr quence d enregistrement de donn es Maintenant il faut d buter le processus Lorsque Debuter log Tx est affich le mode acquisition enregistrement est inactif Lorsque Arreter log Tx est affich les donn es sont en cours d enregistrement Un message d enregistrement est affich l cran et le DEL de la carte SD s allume Appuyer sur Enter pour D buter ou Arr ter l enregistrement Lorsque les donn es Tx sont enregistr es le syst me cr e des fichiers taaammij log thbaammij log et tcaammijj log Ces fichiers contiennent respectivement le tiers des donn es des transmetteurs Le registre comprend la date et l heure l adresse du transmetteur le type de sonde la concentration a la lecture ainsi que le statut de Palarme Voici un exemple d un registre de log Tx 2004 01 23 17 54 25 001_CO_ppm 0 normal 002_NO2_ppm 1 5 normal 003_CO_ppm 0 normal 2004 01 23 17 55 25 001_CO_ppm 0 normal 002_NO2_ppm 0 5 normal 003_CO_ppm 0 normal 2004 01 23 17 56 25 001_CO_ppm 0 normal 002_NO2_ppm 0 5 normal 003_CO_ppm 0
19. 7 10 Programmation du syst me Menu reseau sans fil Noeuds Le menu Noeuds contient toutes les informations sur un noeud Utiliser les touches de clavier gauche et droite pour naviguer entre les noeud puis les fl ches haut et bas pour d rouler les informations de chaque noeud Noeuds 1 1D 121 79h 2 7B7177EFACE0049 3 Produit VA301W Chaque ligne repr sente une information pr cise tel qu indiqu dans l image ci haut Ligne 1 affiche l identification du dispositif les deux derniers chiffres d un identificateur hexad cimal exemple 09 et le num ro de r f rence de la centrale 121 pour le transmetteur en question Ligne 2 affiche l adresse MAC du dispositif Ligne 3 affiche le type de produit 301W L cran peut seulement afficher trois lignes d information la fois il est n cessaire d utiliser les fl ches haut et bas pour d rouler la liste Consulter le tableau des informations du menu Noeuds ci dessous pour conna tre les informations et leurs descriptions M 510324 Manuel de l utilisateur 301C 85 7 10 Honeywell Programmation du syst me Menu reseau sans fil Le tableau suivant contient la liste des donn es affich es pour chaque noeud Utiliser les fleches de gauche ou de droite pour naviguer de noeud en noeud ensuite utiliser les fleches haut et bas pour d rouler la liste pour le noeud s lectionn Titre Valeur Description 4 Qualit lien 1 Pourcentage de la puissance
20. 7cm 7 99 x 11 02 x 2 76 Certifications ANSI UL 61010 1 CAN CSA C22 2 No 61010 1 ETL 116662 M 510324 301C User Manual 105 8 10 Honeywell Limited Warranty Limited Warranty Limited Warranty Honeywell Analytics Inc warrants to the original purchaser and or ultimate customer Purchaser of Vulcain products Product that if any part thereof proves to be defective in material or workmanship within twelve 12 months such defective part will be repaired or replaced free of charge at Honeywell Analytics discretion if shipped prepaid to Honeywell Analytics at 4005 Matte Blvd Unit G Brossard Quebec J4Y 2P4 in a package equal to or in the original container The Product will be returned freight prepaid and repaired or replaced if it is determined by Honeywell Analytics that the part failed due to defective materials or workmanship The repair or replacement of any such defective part shall be Honeywell Analytics sole and exclusive responsibility and liability under this limited warranty Re Stocking Policy The following restocking fees will apply when customers return products for credit e 15 restocking fee will be applied if the product is returned within 1 month following the shipping date e 30 restocking fee will be applied if the product is returned within 3 months following the shipping date A full credit less restocking fee will only be issued if the product is in perfect working condition If repairs are
21. AP1 BM Affiche le nombre de balises de parent alternatif 1 manqu sur la derni re p riode de balise 20 AP1LC 27132 Affiche le temps depuis la derni re 032 communication avec le parent alternatif 1 en millisecondes 21 AP2ID 2 Affiche l identificateur associ au parent alternatif 2 22 AP2Adrres 31756 Affiche l adresse r seau du parent alternatif 2 23 AP2LQI 198 Affiche la qualit du lien avec le parent alternatif 2 0 pas de lien 1 lien faible 2 lien fort 24 AP2Retries 190 Affiche le nombre de relancements du parent alternatif 2 25 AP2BM 0 Affiche le nombre de balises de parent alternatif 2 manqu sur la derni re p riode de balise 26 AP2LC 56320 Affiche le temps depuis la derni re communication avec le parent alternatif 2 en millisecondes 27 LSU 661 Affiche l heure de la derni re mise jour du syst me 28 Statut Actif Indique si le noeud est actif ou inactif 29 Freshness 2 Affiche le nombre de mise a jour de statut qui peuvent tre manqu sans qu un leave indication n est lanc 30 Version A14 Version du micrologiciel de l appareil M 510324 Manuel de l utilisateur 301C 87 7 10 Honeywell Programmation du syst me Menu reseau sans fil 31 32 33 34 35 Titre Valeur Hiberner Remplacer Enlever Consolider acc s Failsafe N A Description La s lection d une de ces options ouvre un cran de confirmation Lors de la confirmation l appareil est msi en so
22. Activer ou Desactiver DHCP Consulter votre service de TI pour de plus amples informations sur le DHCP M 510324 Manuel de l utilisateur 301C 75 7 10 Honeywell Programmation du syst me Menu BACNet Le prochain cran principale BACNet permet de modifier l adresse du serveur SNTP et de configurer la fr quence a laquelle le systeme effectuera des requ tes de serveur SNTP Honeywell offre ces options pour que nos produits s adaptent mieux a vos protocoles de r seau cependant nous ne offrons ni la configuration ni le soutien technique pour ces options SNTP Simple Network Time Protocol 9 BACNet SNTP Client D Serveur SNTP Requete SNTP L option Serveur SNTP ouvre un cran secondaire permettant de modifier l adresse IP du serveur SNTP Consulter votre service de TI pour de plus amples d tails sur cette configuration Adresse IP D 10 4 1 12 Les options Requete SNTP activent le champs et permettent de d rouler la liste de 0 60 minute et de r gler la fr quence laquelle le syt me effectuera des synchronisations de serveur SNTP 76 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu BACNet Le prochain cran est l cran Fuseau horaire Cet cran permet de d finir le fuseau horaire de votre syst me S il y a une diff rence entre celui de votre syst me et le temps universel et si le syst me est dans une zone utilisant l heure avanc e La s le
23. DDB B O Device Management Dynamic Object Binding A DM DOB A O Device Management Dynamic Object Binding B DM DOB B O Device Management DeviceCommunicationControl A DM DCC A M Device Management DeviceCommunicationControl B DM DCC B O Device Management Private Transfer A DM PT A O Device Management Private Transfer B DM PT B O Device Management Text Message A DM TM A O Device Management Text Message B DM TM B O Device Management TimeSynchronization A DM TS A M Device Management TimeSynchronization B DM TS B O Device Management UTCTimeSynchronization A DM UTC A O Device Management UTCTimeSynchronization B DM UTC B M 510324 301C User Manual 101 7 10 Honeywell Protocol Implementation Conformance Statement O Device Management ReinitializeDevice A DM RD A M Device Management ReinitializeDevice B DM RD B O Device Management Backup and Restore A DM BR A O Device Management Backup and Restore B DM BR B O Device Management List Manipulation A DM LM A O Device Management List Manipulation B DM LM B O Device Management Object Creation and Deletion A DM OCD A O Device Management Object Creation and Deletion B DM OCD B O Device Management Virtual Terminal A DM VT A O Device Management Virtual Terminal B DM VT B Segmentation Capability O Segmented requests supportedWindow Size O Segmented responses supportedWindow Size Take maximum Windows size supported by the other device Standa
24. Journal Sys permet d enregistrer les informations de journal du syst me en format texte sur la carte de m moire flash SD card e 5 Copie Journal Sys Journal vers SDcard Lorsque s lectionn e cette option cr un registre de toutes les derni res actions de la centrale sur la carte de m moire dans un fichier nomm slaammij log Ce fichier peut contenir jusqu 64Ko d information en format texte Lorsque la carte de m moire atteint sa capacit les nouvelles informations remplacent les plus vieilles qui sont effac es Voici un exemple du fichier de journal START of system log dump 1980 01 22 17 23 51 1980 01 19 22 07 26 Accessing menu 1980 01 19 22 07 41 Chargement config depuis carte SD 1980 01 19 22 07 45 Sortie du menu 1980 01 19 22 13 05 Acc s au menu 1980 01 19 22 13 16 Edition param tres Tx 1 1980 01 19 22 18 29 Sortie du menu 1980 01 19 23 07 14 Acc s au menu 1980 01 19 23 07 40 dition v nement 1 1980 01 19 23 07 43 Sortie du menu 1980 01 19 23 08 10 Acc s au menu 1980 01 19 23 09 07 dition v nement 2 1980 01 19 23 09 13 Sortie du menu 1980 01 20 00 06 42 Acc s au menu 1980 01 20 00 06 52 Sortie du menu 1980 01 20 00 07 49 Acc s au menu 1980 01 20 00 07 55 Sortie du menu 1980 01 22 17 23 46 Acc s au menu END of system log dump 1980 01 22 17 23 51 M 510324 Manuel de l utilisateur 301C 55 7 10 Honeywell Programmation
25. M 510324 Manuel de l utilisateur 301C 73 7 10 Honeywell Programmation du syst me Menu BACNet Le premier cran permet de configurer l identification et l adresse BACnet ID Adresse Statique IP 9 BACNet Appareil BACnet ID 1 Adresse statique IP Building Automation and Control Networks est le num ro assign a une centrale sur le r seau lt 9 BACNet gt Static IP Address D gt 192 168 1 254 Ceci est une adresse qui est toujours assign e a une centrale en particulier plut t que recycl et r assign lorsque la centrale ne l utilise plus Changer les valeurs BACNet e Utiliser les fl ches pour d placer le curseur gauche du param tre d sir puis appuyer sur Enter pour le s lectionner e La s lection de BACnet ID active le mode dition du champs Utiliser les fl ches pour augmenter ou diminuer la valeur ID 0 419303 La s lection de l option Adresse statique IP ouvre l cran de modification de l adresse IP Toutes les centrales sont configur es avec une adresse par d faut 74 Adresse IP D 192 168 1 254 Masque du reseau 255 255 255 0 Manuel de Putilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu BACNet Le deuxi me cran permet d activer ou de d sactiver le protocole DHCP Dynamic Host Configuration Protocol 9 BACNet DHCP desactive D Active DHCP Appuyer sur la touche Enter pour basculer le champs
26. Tx000 Includes only the specified transmitter connected to the con troller Clock Includes only information gathered between the specified times Selecting clock sets a condition that is applied only between the start and end time frame It is possible to set one condition screen to specific parameters and the second to clock which means that the specified condition will trigger an event only if it occurs during the set time period Note Clicking on the magnifying glass to the right of a Group number on the display opens a view of the Group for consultation or editing Press Esc to close the group view and return to the Event condition screen M 510324 301C User Manual 47 7 10 Honeywell System Programming Event Menu The bottom right portion contains the operand which defines what device or group of devices on which the Event will be based The list provides the following options OFF Used for status on binary inputs ex used with 301ADI ON Used for status on binary inputs ex used with 301ADI Fault Bases trigger on maintenance alarm communication failure or device failure Alrm A If the chosen device or group has an Alarm A or Alarm 1 an event will be triggered Alrm B If the chosen device or group has an Alarm B or Alarm 2 an event will be triggered Alrm C If the chosen device or group has an Alarm C an event will be triggered The Coverage Period screen allows the period that will be covered by the Ev
27. Viewing and Modifying Trends Internal B T VMT I B O Trending Viewing and Modifying Trends External B T VMT E B O Trending Automated Trend Retrieval A T ATR A O Trending Automated Trend Retrieval B T ATR B 106 Manuel de Putilisateur 301C M 510324 Honeywell 7110 nonc de conformit d impl mentation de protocole Gestion de r seau O Network Management Connection Establishment A NM CE A O Network Management Connection Establishment B NM CE B O Network Management Router Configuration A NM RC A O Network Management Router Configuration B NM RC B Gestion d alarme et d v nement O Alarm and Event Notification A AE N A O Alarm and Event Notification Internal B AE N I B O Alarm and Event Notification External A AE N E B O Alarm and Event ACK A AE ACK A O Alarm and Event ACK B AE ACK B O Alarm and Event Alarm Summary A AE ASUM A O Alarm and Event Alarm Summary B AE ASUM B O Alarm and Event Enrollment Summary A AE ESUM A O Alarm and Event Enrollment Summary B AE ESUM B O Alarm and Event Information A AE INFO A O Alarm and Event Information B AE INFO B O Alarm and Event LifeSafety A AE LS A O Alarm and Event LifeSafety B AE LS B Gestion de dispositif O Device Management Dynamic Device Binding A DM DDB A M Device Management Dynamic Device Binding B DM DDB B O Device Management Dynamic Object Binding A DM DOB A O Device Management Dynamic Object Binding B DM DOB B O Device
28. and erases the node data from the coordinator memory and from the 301C database Option 34 Consolidate Route allows the user to force the node to find the best route to the controller using an alternate parent 86 301C User Manual M 510324 Honeywell 7 10 System Programming Wireless Network Menu New Node Menu The New Node menu allows users to add new nodes to the existing network assigning a specific ID number to its MAC address Wireless Network New Node 4 New Node VAL 121 5 Hibernate MAX 180 6 Reset Network MIN 121 MAC 1st part VAL 00155F00 MAX FFFFFFFF MIN 00000000 MAC 2nd part VAL 80000024 MAX FFFFFFFF MIN 00000000 e Scroll to highlight New Node and press Enter to select Inthe New Node window enter the desired ID value in the VAL field and press Enter e Press Enter to confirm When the MAC 1st part screen appears enter the first 8 digits of the new node s MAC address and press Enter e Press Enter to confirm When the MAC 2nd part screen appears enter the last 8 digits of the new node s MAC address and press Enter e Press Enter to confirm The node s MAC address is printed on the node s housing Note If an ID number that already exists is assigned this function will not be completed M 510324 301C User Manual 87 7 10 Honeywell System Programming Wireless Network Menu Hibernate Menu The hibernate menu allows users to shut down the entire network
29. components and on the network communications It also allows the system to be operated in four different modes which in turn provide different functionalities MENU gt 5 Copy 7 Network 6 Config 8 Tests 8 Tests gt Test sequence Start Sim Sequence Maximum load Test sequence Relays activated Any o continue Esc to quit 2 Test sequence BUZZER activated Any key to continue Esc to quit 3 Test sequence LEDs activated Any key to continue Esc to quit Test sequence Press left Esc to quit 5 Test sequence Display test Any key to continue Esc to quit 6 Test sequence Test Network comm 9600 bauds Channel 1 PASSED Test sequence Test done ly Any key to continue Simulation Sequence gt Start with Tx001 Confirm 4 8 Tests Oprt Mode normal M 510324 301C User Manual 65 7 10 Honeywell System Programming Tests Menu The Tests menu provides four main options divided between two screens Each of these options offers different capabilities The first screen presents three options 8 Tests Test sequence Start Sim Sequence Maximum load Test sequence Enables each output to be activated and validates operation of each controller keypad buttons display pixels and various communication protocols Start Sim Sequence This options starts or stops the Simulation mode which allows a simulation of a gas concentr
30. composante le type de sonde et l adresse Les tiquettes de transmetteur Vulbus contiennent 20 espaces blancs 1 INFO Tx gt 001 Affichage edition 20 car max 301D2 CH4 Ad001 M 510324 Manuel de l utilisateur 301C 33 7 10 Honeywell Programmation du syst me Menu INFO Tx Alarme A B et C Puisque les crans d affichage sont identiques pour chacun des alarmes ils ont t regroup s aux fins de ce manuel Cependant chaque alarme doit tre configur s par ment selon vos besoins Cette option permet de configurer des niveaux d alarme minimum et maximum pour les alarmes A B et C Ceci cr e une plage de tol rance o aucune action n est effectu e Toutefois si les concentrations de gaz d passent le niveau maximum un alarme est activ Lalarme ne sera pas d sactiv avant que la concentration de gaz revienne en dessous du niveau minimum pr cis e Utiliser les fl ches du clavier pour d placer le curseur la gauche de soit MIN ou MAX e Appuyer sur Enter pour s lectionner le champs modifier e Utiliser les fl ches haut et bas pour augmenter ou diminuer la valeur e Appuyer sur Enter pour valider la valeur affich e Ceux ci sont des crans typiques 1 INFO Tx D026 gt Alarme B Level 60 0 SLEL Typiques de screen pour la visualisation des alarmes A ou B de XCD et XNX transmetteurs 1 INFO Tx 001 gt Alarme A MIN MAX 0 00 0 00 Typiques de scre
31. des relais peut tre modifi e depuis le menu de programmation de la centrale SORTIES RELAIS 6 4 2 Z DOE 4 Normalement 1 3 1 ferm 2 4 Normalement 3 5 ouvert 4 6 A RISQUE DE CHOC ELECTRIQUE Si le relais est r gl Normalement ferm le relais est mis sous tension en m me temps que la centrale et le dispositif connect au relais est en fonction Le relais se fermera lorsque la condition d alarme pr cis e est atteinte Si le relais est r gl Normalement ouvert le relais demeure ferm lors de la mise sous tension de la centrale Le dispositif connect au relais fonctionnera seulement lorsque la condition d alarme pr cis e est atteinte Note Ces fonctions sont invers es lorsque le mode de s curit int gr e Failsafe est activ sur la centrale M 510324 Manuel de l utilisateur 301C 17 7 10 Honeywell Instructions pour cavaliers Instructions pour cavaliers Les divers cavaliers de la carte PCB permettent d effectuer certaines op rations manuellement EOL 1 4 Permet l ajout de cavaliers de fin de ligne pour am liorer les signaux de communication Mettre le cavalier en position R pour activer la terminaison fin de ligne Position R offre une terminaison r sistance tandis que RC offre une terminaison de condensateur SHDN Permet de r initialiser ou de temporairement couper l alimentation de la centrale Cette fonction est utile pour effectuer des ajustements au c blage
32. du syst me alimentation interrompue pour s curit Relays Permettent d effectuer des tests sur les relais sans aucun J29 J32 impact sur les v nements 18 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 D marrage Enregistrement de donn es sdcard D marrage Quoique la centrale est configurer selon vos besoins la programmation peut toujours tre modifi e par l entremise de ses menus Cette section du manuel vous guidera dans les options du menu de programmation Premier d marrage Assurer que tout le cablage est termin et effectu selon les sp cifications et les d tails de connexion avant de mettre la centrale sous tension Lorsque tout est s curitaire enlever le connecteur du cavalier SHDN pour alimenter l unit il y aura un d lai de quelques secondes Enregistrement de donn es sdcard Loption d enregistrement de donn es DLC de la centrale collecte automatiquement les donn es et les enregistre sur une carte m moire Flash SDcard Si la m moire de la carte atteint sa capacit e L enregistrement des donn es s arr te e Aucun avis n est affich l cran Le DEL de la carte clignote le bo tier doit tre ouvert pour le voir Consulter la section Acquisition pour de plus amples d tails sur le d marrage et l arr t de la fonction enregistrement de donn es Toujours d sactiver la fonction d enregistrement de donn es ATTENTION avant d enlever la carte m moire Jamai
33. est chang e une adresse d j associ un dispositif les donn es existantes seront cras es Les clients doivent conna tre les adresses attribu es de leurs r seaux et porter une attention sp cial lors de changement d adresse Ne pas oublier de supprimer l adresse d origine pour viter toutes duplications de donn es M 510324 Manuel de l utilisateur 301C 37 7 10 Honeywell Programmation du syst me Menu groupes Menu groupes La programmation de groupes de transmetteurs permet de regrouper des unit s ce qui permet d agir v nements en r ponse un groupe d unit s plut t que sur chaque unit individuellement MENU 1 InfoTx 3 Evene 2 Groupes 4 Acqui vider les groupes Un groupe est un bloc contenant les adresses de chaque transmetteurs du groupe Les groupes sont affich s sur une seule ligne si le groupe contient plus de quatre composantes il faudra utiliser les fl ches gauche et droite pour visionner la liste de tous les transmetteurs du groupe puisque un cran peut contenir seulement 20 caract res Le curseur de l cran Groupe est repr sent par les parenth ses clignotantes lt fin gt Les informations entre les parenth ses peuvent tre modifi es 38 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu groupes Cr er des groupes e Utiliser les fl ches pour d placer le curseur la gauche du num ro de groupe e Appuyer sur Ente
34. etes Rene tnt cethsatgaae CARRE R TR RSR BR te sie 21 System Operation ss nt init an 21 SYSTEM PROGRAMMING mnnnnnns 22 TIO MEN ina ratita 25 Ident Menu 523228 ata a 26 Product and Sensor Types ccccoccconocccconcccnancnanonnnananacananacaninos 27 COM Men sico cia 29 Scale Menus 1 and 2 30 Detection Men tintos 31 Display Menu sic ierant earna eana Oaoa ei aia aa E a 32 Alarm A Band C Menus ess 33 Servicing and Operating Menus eeceeseeeceeeeeeeeeeeeeeeeeeeeneeseaeeeeensaee 34 Status COd ire Gia aie diner eine ed ate 35 Erase Gurrent Rx Men nr een te elas 35 Change TX Address Are Stuns a es e 36 Groups Menu nue nent dada 37 Creating Groups nonin heeled et Ah dirt RM ria Bellew 38 Deleting Groups cocina 39 M 510324 301C User Manual vii 7 10 Honeywell Event M TU tencia nel PR caia 40 ActioniMenu teca ne nes en HE Man o el me Are 42 Delays Menu vilken hii A a nee is 43 Late MOGs rico lidia 44 Conditions ccoo a ci 45 Status iaa 49 Database iris la 49 Acquisition Menu asii aa 50 Starting and Stopping Tx Logging oooccccoccccnocccccnacininacininnccnano 51 Starting and Stopping Event Logging eessen 52 Copy Menu asii A ae aie anh aie ae 53 Configuration ui 53 Parameters iii Rat eee a 54 System Log Men vies emma rn dice 55 Config MOM sisi arica 56 Network Menu kereme it ici a 61 Remote Calibration ii 268 eee tes eR ed o 63 Tests Men scsi ceil A ee a 65 Test Sequence cial ride 67 Norma
35. o LCD screen NA MESA L 4 Ra 2 2 z sue End of line jumper L JJ cH N position E Me x x ENTER yee 3 E End of ine specification Eg gt a a The E O L jumper for lt ES channels 1 2 3 4 must AN ES always be in E O L pRa FAULP ES sition T a e de SHDN Y as mIRC El coe 1 m amp g 5 TX a ql ESC z Leon n E R Esc 7 E w RC AN Vin Vout ig 4 R 324 7 422 ah Ga SZ a GD GD CATA 2 1 pe fl SHIELD A383 Aa B4 i BZ 4 RELAY OUTPUTS ym menus a 2 Channel 2 a 4channel 4 not used AE V ma eg B3 Normally 3 5 Channel 1 A 3 Channel 3 open 4 6 m l 143 Normally ie Grounding screw 1 closed 2 4 Always respect minimum voltage requirements at device A RISK OF ELECTRIC SHOCK 14 COMMUNICATION Communication Wire Gauge 2 24 AWG Belden 9841 Twisted and shielded cable 2000 feet 600 m per channel T tap 65 feet 20 m T tap 130 feet 40 m total Channel Specifications Channel 1 2 Modbus Vulbus protocol Channel 3 Modbus protocol only Communicates only with Vulcain transmitters Wireless Communication ISM worldwide Indoor range 30m 301C User Manual Honeywell A RISK OF ELECTRIC SHOCK BacNet IP MODULE BIP option Ethernet 10 100 compatible with 10Base T interface RJ 45 Visual Indicators Green LED LINK Yellow LED ACT M 510324 7 10 Introduction Wiring Details The connectors or ports on the PCB allow various wiring to be connected to the c
36. of wireless nodes to prevent any damage when maintenance is needed Wireless Network gt Hibernate 4 New Node Enter to confirm 5 Hibernate Esc to cancel 6 Reset Network Reset Network Menu This function which should only be used by authorized fully qualified technicians resets the wireless network parameters to zero enabling nodes to look for a new controller in Association mode Wireless Network gt Reset Network 4 New Node Enter to confirm 5 Hibernate Esc to cancel 6 Reset Network CAUTION This function resets the nodes once reset nodes may change IDs and thus render controller Events and Groups inoperable 88 301C User Manual M 510324 Honeywell 7 10 System Programming Wireless Network Menu Status Log Menu The Status Log file named wyymmddq log that will be recorded on the SD card contains 27 columns of information as in the sample above that correspond to each of the first 27 fields in the Nodes Menu Wireless Network gt Status Log Status Log 5 Hibernate Enter to confirm 6 Reset Network Log Esc to cancel 7 Status Log NoLog The resulting file can then be copied to a computer and consulted or printed as needed Consolidate Route Menu Although nodes will always look for the best route to the controller this command forces all nodes to search for the shortest communication route with the least hops to the controller using an alternate parent
37. required on the returned product the cost of these repairs will be deducted from the credit to be issued No credits will be issued beyond the three month period M 510324 301C User Manual 107 7 10 Honeywell Limited Warranty Exclusions A If Gas sensors are part of the Product the gas sensor is covered by a twelve 12 month limited warranty of the manufacturer B If gas sensors are covered by this limited warranty the gas sensor is subject to inspection by Honeywell Analytics for extended exposure to excessive gas concentrations if a claim by the Purchaser is made under this limited warranty Should such inspection indicate that the gas sensor has been expended rather than failed prematurely this limited warranty shall not apply to the Product C This limited warranty does not cover consumable items such as batteries or items subject to wear or periodic replacement including lamps fuses valves vanes sensor elements cartridges or filter elements Warranty Limitation and Exclusion Honeywell Analytics will have no further obligation under this limited warranty All warranty obligations of Honeywell Analytics are extinguishable if the Product has been subject to abuse misuse negligence or accident or if the Purchaser fails to perform any of the duties set forth in this limited warranty or if the Product has not been operated in accordance with instructions or if the Product serial number has been removed or alte
38. using wireless communication protocols Settings for Specific Transmitters Honeywell Sensepoint XCD Transmitters must be configured for 9600 baud no parity and a unique address Honeywell XNX Universal Transmitters must be configured for 9600 baud and a unique address Information on configuring each transmitter is in the associated technical manual 16 301C User Manual M 510324 Honeywell 7 10 Introduction Relay Output Relay Output The relay output can withstand up to 5A at 30Vdc or 250Vac resistive load only Relays can be used to activate horns and strobes Although each relay is programmed with a default setting below they can be configured using the controller programming menu RELAY OUTPUTS Normally open Normally closed If relays are set to Normally closed the relay is powered up with the controller and the device linked to the relay is functioning The relay will shut down when the specified alarm condition is reached If the relay is set to normally open the relay will remain off when the controller is powered up and the device connected to the relay will only be activated when the specified alarm condition is reached Note These functions are reversed if the controller Failsafe mode has been activated M 510324 301C User Manual 17 7 10 Honeywell Relay Output Jumper Use Instructions The jumpers on the controller PCB allow a variety of operations to be performed manually EOL 1 4 Enables
39. 04 01 23 17 58 25 001_CO_ppm 0 normal 002_NO2_ppm 1 5 normal 003_CO_ppm 0 normal The first column of the Tx log displays the date yyyy mm dd and the time hh mm ss of the log In this example the Delay mode was set to one minute intervals The third column of the Tx log displays the transmitter address and the fourth displays the gas type gas concentration and unit of measurement The display then lists the next transmitter address with its gas type concentration and unit of measurement and so on until all the transmitters have been listed M 510324 301C User Manual 51 7 10 Honeywell System Programming Acquisition Menu Starting and Stopping Event Logging The Acquisition menu offers an event logging option Event Logging records controller transactions events Tx and alarm flags and relay status When Start Event logging appears on the display it indicates that the acquisition or logging mode is inactive When Stop Event logging appears it indicates that Event data is being logged Press the Enter keypad button to stop or start Event logging When Event data is logged the system creates a file named evyymmdd log The record includes the date time and the event Here is a sample of what an Event log looks like 2004 01 23 17 54 25 Event logging enable 2004 01 23 17 55 25 Event logging enabled 2004 01 23 19 05 47 Simulation sequence activated 2004 01 23 19 05 48 Tx 6 communication n
40. 1 The second option is SDcard to 301C allows the configuration and parameters of the config ini file on an SDcard to be copied to the controller Note The config ini file contents can be modified at any time and from any computer 1 When transferring data the system will automatically search for an existing config ini file before proceeding If one exists the system searches for a config bak file If found the file is deleted Then the pre existing config ini file is renamed config bak making it possible to save the new config ini file and keep a backup copy of the previ ous one After inserting an SD card into the controller the controller s system looks for an exist ing config ini file that contains an autoload tag equal to 1 yes If the tag is found the system loads the contents of the file and resets autoload to 0 no This is a useful feature for editing the file on a computer without having any impact on the controller such as recorded Events M 510324 301C User Manual 53 7 10 Honeywell System Programming Configuration Parameters The parameters function allows one transmitter s configuration to be copied to another or one event s parameters to be copied to another event This allows several devices that share identical or similar parameters to be quickly configured 5 Copy parameters gt Txinfo to TxInfo Event to Event The
41. 24 7 10 301C User Manual Honeywell 77 System Programming Wireless Network Menu Parameters Menu When Parameters is selected from the Wireless Network main menu options all the coordinator parameters are displayed in order The screen can only display three items at one time Use the up or down arrows to scroll through the list of parameters Parameters gt 7B7177EFACE0049 WC Version PAN ID RF channel 7 Association Ina Lo Nodes 1 2 3 4 5 Log Mode No Log 6 E 8 0 Max nodes 0 9 Max hops 0 10 Power 0 11 AHFO pps 12 BO 0 13 SUO 0 14 LCO 18 15 LTO A PP 16 MMO 0 17 BMO 0 0 0 A _ TT A 18 KNSRO 19 FNSRO 20 Clone WC gt VAL 00155F00 MAX FFFFFFFF MIN 00000000 System Menu Invalid Option Log Mode Association MAC 1st part Note When data is provided for information purposes only it is not editable When an item that is not editable is selected the screen will briefly display the System Menu Invalid Option screen as shown above 78 301C User Manual Honeywell M 510324 7110 System Programming Wireless Network Menu Changing PAN ID or RF Channel When the PAN ID or the RF channel is changed using the Parameters menu option within the Wireless Network menu the system needs confirmation at more than one option as described below To change the
42. 47 36 ISO 8601 standard 6 Config Set User Password 2967 Slave Port Cnfg_ 77 Slave Port Cnfg gt p p D Address 001 38400 bauds Mdbs RTU 8D 2S NP 6 Config gt Relay Configuration AP Brdcst auto Honeywell gt Relay Configuration gt Failsafe gt Allrelays Inactive Relay Configuration Silence 1 2 3 4 dis ena dis dis 6 Config Day definition Week definition Day definition Daytime sta D 08 00 end 17 00 Week definition Working Days sta Monday end Frida 56 301C User Manual M 510324 Honeywell 7110 Config Menu Selecting the first line of the first screen allows selection from three display modes Manual scroll 3 second scroll 5 second scroll If Manual scroll mode is chosen the screen will only advance if you press on the arrow keypad buttons If either 3 or 5 second scroll mode is chosen the screens will automatically scroll display readings for all devices connected to the controller after 3 or 5 seconds 6 Config Manual scroll mode Set Date and Time Menu francais 3 or 5 second scroll modes do not prevent the keypad arrows to be used to return to a previous screen or move ahead through the screens manually Selecting the second line allows the date and time in a new screen to be adjusted Date and Time When a number is flashing the value can be changed using the up down keypad
43. 5 Hiberner 6 RAZ reseau Log Enter pour confirmer 7 Log Statut NoLo Esc pour annuler Le fichier g n rer peut ensuite tre consult sur un ordinateur ou imprim selon les besoins Menu Consolider Acces Quoique les noeuds recherchent toujours le meilleur chemin de communication avec la centrale cette fonction active immediatement la recherche Les noeuds rechercheront donc le meilleur chemin avec le moins de sauts vers la centrale en utilisant un parent alternatif Reseau sans fil gt Consolider acces Consolider acces 6 RAZ reseau VAL 00060 7 Log Statut NoLog gt MAX 65535 Enter pour confirmer 8 Consolider acces MIN 00000 Esc pour annuler 92 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu reseau sans fil M 510324 Manuel de l utilisateur 301C 93 7 10 Honeywell MODULE BACNET IP option BIP Sp cifications Port Ethernet 10 100 compatible avec 10Base T interface RJ 45 Indicateurs DEL vert LINK DEL jaune ACT Configuration de r seau Voir section du menu VA301C BACnet Protocole BACnet IP Port UDP IP 47808 non modifiable depuis la centrale VA301C Le module est d velopp selon la norme 135 2001 ANSI ASHRAE BACnet A Data Communication Protocol for Building Automation and Control Networks L option de couche liaison de donn es Data Link Layer est selon le BACnet IP Annexe J http ww
44. 7 11 06 15 1_CO2_ppm 562 normal 2005 04 27 11 06 28 1_CO2_ppm 645 normal 2005 04 27 11 06 39 1_CO2_ppm 557 normal 2005 04 27 11 30 45 1_CO2_ppm 715 normal 50 301C User Manual M 510324 Honeywell 7 10 System Programming Acquisition Menu Starting and Stopping Tx Logging In the previous step Acquisition the frequency at which Tx logs would be recorded can be configured To start the logging function When Start Tx logging appears on the display it indicates that the acquisition or logging mode is inactive When Stop Tx logging appears it indicates that Tx data is being logged The log message is displayed on the screen according to the chosen mode and LED 1 will light up Press the Enter keypad button to stop or start Tx logging When Tx data is logged the system creates files named tayymmdd log tbyymmdd log and tcyymmdd log each representing one third of the network The record includes the transmitter s date time and address the sensor type the concentration read as well as the alarm status Here is a sample of what a Tx log looks like 2004 01 23 17 54 25 001_CO_ppm 0 normal 002_NO2_ppm 1 5 normal 003_CO_ppm 0 normal 2004 01 23 17 55 25 001_CO_ppm 0 normal 002_NO2_ppm 0 5 normal 003_CO_ppm 0 normal 2004 01 23 17 56 25 001_CO_ppm 0 normal 002_NO2_ppm 0 5 normal 003_CO_ppm 0 normal 2004 01 23 17 57 25 001_CO_ppm 0 normal 002_NO2_ppm 1 0 normal 003_CO_ppm 0 normal 20
45. ACE0049 Coordinator MAC address 2 WC Version A10 Wireless coordinator firmware version 3 PAN ID FFO7 The hexadecimal ID number assigned to the coordinator 4 RF channel 11 Radio frequency channel 5 Log Mode No Displays whether debug mode is Log activated 6 Association Ina Defines whether new nodes can join the network 7 Nodes 0 Displays the number of nodes associated to the wireless coordinator 8 Max nodes 0 Defines the maximum nodes that can reside in the network 1 60 9 Max hops 0 Defines the maximum number of hops a node can make on a communication route to the wireless coordinator 10 Power 0 Sets the transmission power amplifier value 11 AHFO 0 Defines the time between wake up cycles 12 BO 0 Sets the time between transmission of two consecutive beacons by a node to establish and maintain synchronization 13 SUO 0 Defines the status update period time between 2 consecutive status update packets sent from node to coordinator 14 LCO 18 Packet sent from the coordinator to the node confirming to the node that it is registered on the network at the coordinator 15 LTO 0 The number of status update packets that can be missed before a leave indication is triggered 80 301C User Manual M 510324 Honeywell 7 10 System Programming Wireless Network Menu Title Value Description 16 MMO 0 Defines the bandwidth of the message retry measurement 17 BMO 0 Defines the bandwidth of the missed be
46. Al est le type d objet et 2 est l instance unique de l objet dans ce dispositif Cet objet est identifi Entr e analogique 2 du dispositif BACNet 1 Exemple 2 Voic une repr sentation du statut de sortie du relais 2 du m me dispositif de r seau de Vulcain avec un label d affichage de dispositif diff rent Name Floor 01 Sensor 02 rel2 Value OFF Units Object 1 BO4 Description Binary Output Cet objet est identifi Sortie binaire 4 du dispositif BACNett Exemple 3 Voici une repr sentation du premier statut de sortie 24V d un dispositif de r seau de Vulcain 301EM Name 801EM CO AD 25 out1 Value OFF Units Object 1 BV1 Description Binary Value Cet objet est identifi Valeur binaire 1 du dispositif BACNet 1 M 510324 Manuel d utilisateur 301C 103 7 10 Honeywell nonc de conformit d impl mentation de protocole nonc de conformit d impl mentation de protocole NORMATIF nonc de conformit d impl mentation de protocole BACnet Date ao t 1 2005 Nom du vendeur Honeywell Analytics Nom du produit 301C BIP Num ro de mod le du produit N A Version de logiciel d application 1 0 R vision de micro logiciel 1 0 R vision de protocole BACnet 1 0 Description du produit Le 301C BIP comporte un module utilisant la communication BACnet Comme tel les composantes d un r seau Vulcain peuvent tre connect es sur le r s
47. CP is disabled Changing BACNet values e Use the keypad arrows to scroll down to select the desired line and press Enter to select it e Selecting BACnet ID activates the field The ID value 0 4194303 can be increased or decreased using the up or down keypad arrows If the Static IP address option is selected the following screen appears All controllers are shipped with a preset IP address as shown in the example below IP address D 192 168 1 254 Network mask 255 255 255 0 72 301C User Manual M 510324 Honeywell 7 10 System Programming Bacnet Menu The next screen allows the device DHCP Dynamic Host Configuration Protocol to be enabled or disabled 9 BACNet gt DHCP disabled Enable DHCP e Simply press Enter to change the field value Consult the IT department for details concerning this option M 510324 301C User Manual 73 7 10 Honeywell System Programming Bacnet Menu The next main BACNet screen allows modification of the SNTP Simple Network Time Protocol server IP address and configure the frequency at which the system will make SNTP server requests Honeywell has made these options available to better adapt to the building s network protocol however Honeywell does not provide configuration or support for these options 9 BACNet gt SNTP Client D SNTP server SNTP request 1min Selecting Server request activate the minute The SNTP server option opens another
48. Centrale Controller Manuel de l utilisateur 301C User Manual M 510324 7 10 Controller Unit 301C User Manual M 510324 7 10 Notices and Trademarks Copyright by Honeywell International Inc July 2010 While this information is presented in good faith and believed to be accurate Honeywell disclaims the implied warranties of merchantability for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice This manual covers software version 3 086 Honeywell Analytics 405 Barclay Boulevard Lincolnshire Illinois 60069 M 510324 301C User Manual iii 7 10 Honeywell Symbol Definitions The following table lists the symbols used in this document to denote certain conditions Symbol Definition ATTENTION Identifies information that requires A special consideration TIP Identifies advice or hints for the user often in terms of performing a task REFERENCE _ INTERNAL Identifies an additional source of information within the bookset Indicates a situation which if not avoided may CAUTION result in equipment or work data on the system being damaged or lost or may result in the inability to properly operate the process CAUTION Indicat
49. MENT 3 001 Base de donnee D Effacer evenement Eff Tous les even Les valeurs par d faut du syst me pour les actions effectuer e Relais No 1 sera activ lorsque le niveau d alarme A est atteint sur n importe quel transmetteur connect au r seau e Relais No 2 sera activ lorsque le niveau d alarme B est atteint sur n importe quel transmetteur connect au r seau e Relais No 3 sera activ lorsque le niveau d alarme C est atteint sur n importe quel transmetteur connect au r seau e Appuyer sur la touche Silence pour reconnaitre les v nements et arr ter l alarme sonore e Relais No 4 sera activ lorsque n importe quel transmetteur connect au r seau est en faute M 510324 Manuel de l utilisateur 301C 41 7 10 Honeywell Programmation du syst me Menu v nement Action Les Actions comprennent deux param tres 3 EVENEMENT 3 001 Action Cible Ctrl Relais 01 Cible Indique quelle composante est responsable de l action effectuer soit Tx transmetteur Re relais annonciateur Ctrl centrale Relais Indique quelle des trois sorties sera activ lorsque l v nement est vrai XX active le relais xx de la composante Alarme sonore active l alarme sonore de la composante ALL active tous les relais et les alarmes sonores 42 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu v nement D lais Cette option permet de configurer l
50. Management DeviceCommunicationControl A DM DCC A M Device Management DeviceCommunicationControl B DM DCC B O Device Management Private Transfer A DM PT A O Device Management Private Transfer B DM PT B O Device Management Text Message A DM TM A O Device Management Text Message B DM TM B O Device Management TimeSynchronization A DM TS A M Device Management TimeSynchronization B DM TS B O Device Management UTCTimeSynchronization A DM UTC A O Device Management UTCTimeSynchronization B DM UTC B O Device Management ReinitializeDevice A DM RD A M Device Management ReinitializeDevice B DM RD B O Device Management Backup and Restore A DM BR A O Device Management Backup and Restore B DM BR B M 510324 Manuel de Putilisateur 301C 107 7 10 Honeywell nonc de conformit d impl mentation de protocole O Device Management List Manipulation A DM LM A O Device Management List Manipulation B DM LM B O Device Management Object Creation and Deletion A DM OCD A O Device Management Object Creation and Deletion B DM OCD B O Device Management Virtual Terminal A DM VT A O Device Management Virtual Terminal B DM VT B Capacit de segmentation O Segmented requests supported window Size O Segmented responses supported window Size Take maximum Windows size supported by the other device Types d objets normalis s support s Entr gt ntre Pour tout objet Analog analogique Input S
51. NFO Tx Menu Ident Le menu Ident ou identification permet de consulter ou de modifier l identification de r seau de la composante s lectionn e La partie sup rieure droit de l cran affiche l adresse de r seau de la composante S lectionner le champs pour inscrire l adresse consulter si elle est connue e Utiliser les fl ches pour d placer le curseur la gauche de l adresse Appuyer sur Enter l adresse est en mode dition lorsqu elle clignote e Utiliser les fl ches haut et bas pour augmenter ou diminuer la valeur e Appuyer sur Enter pour valider l adresse et afficher les informations de cette composante La partie inf rieure de gauche affiche le nom du transmetteur ex 301D2 nom du produit et le type de sonde ex CH4 m thane Ces valeurs peuvent galement tre modifi es pour le type de produit Vulbus ou groupe Programmer ou modifier le type de produit ou de sonde e Utiliser les fl ches pour d placer le curseur la gauche du champ de produit ou de sonde e Appuyer sur Enter pour s lectionner le champ en mode dition lorsque le champs clignote e Utiliser les fl ches pour d rouler la liste de types de produit ou de sondes et appuyer sur Enter lorsque le produit ou la sonde appropri est affich M 510324 Manuel de l utilisateur 301C 27 7 10 Honeywell Programmation du syst me Menu INFO Tx Types de produit et types de sondes Voici une liste de tous les types d
52. NSI X3 40 IBM Microsoft DBCS O ISO 8859 1 O ISO 10646 UCS 2 0 ISO 10646 UCS 4 O JIS C 6226 If this product is a communication gateway describe the types of non BACnet equipment networks s that the gateway supports M 510324 301C User Manual 103 7 10 Honeywell Specifications Specifications Power requirements 301C Operating temperature range Operating humidity range Operating altitude Network capacity Communication length of lines Wireless communication range Wireless communication User interface Visual indicators Outputs Output rating Audible alarm 17 27 Vac 50 60 Hz 8 64 VA 18 36 Vdc 350mA 24 Vdc 8 4 VA 20 C to 50 C 4 F to 122 F 0 to 95 RH non condensing Up to 3000 m 9843 ft Up to 96 transmitters 32 per channel Channels 1 2 Modbus and Vulbus Channel 3 Modbus only Channel 4 slave communication i e BACNet use Up to 609m 2 000 ft per channel T tap maximum 20m 65 ft per t tap overall total of 40m 130 feet 30m 98 5 ft ISM worldwide range 30 m indoor Graphic 122 x 32 dot matrix backlit display User friendly keypad Power Green LED Alarm A B C Red LED Fault Amber LED Tx Amber LED Rx Green LED 4 DPDT relays 5A 30Vdc or 250 Vac resistive load 65dBA at 1 m 3 ft Time delays Programmable Before and After delays Battery 3 volt lithium battery Enclosure NEMA 4X ABS polycarbonate indoor use Dimensions HxWxD 28 x 20 3 x
53. NU gt 1 Txinfo 3 Events gt 2 Groups 4 Acqui 2 Groups 0013 gt lt end gt 1 E bl El El E empty all groups A group is a stack containing the addresses from each of the transmitters included in the group Groups are displayed in a single line if a group contains more than four components the arrows must be used to scroll left and right of the display window to view all members of a group The cursor in the Group screen is represented by the blinking brackets lt end gt Any information between the brackets can be edited M 510324 301C User Manual 37 7 10 Honeywell System Programming Groups Menu Creating Groups e Use the arrows to move the cursor to a group line and press Enter e The field can be edited when the brackets stop blinking and the word end blinks e Use the up or down arrows to scroll through the list of all units connected to the 301C until the desired address is displayed e Press Enter again to validate the address e The address is added to the group and the lt end gt bracket is shifted one position to the right The process can be repeated until all the desired transmitters in the group up to 126 have been added The address for each transmitter added in the Tx Info menu is available when creating groups Note Groups created in the Groups menu will appear in the product type list Tx Info Ident screen as Group xx the number assigned to the group when it wa
54. P subnet address different from those on the BACNet IP network it seeks to join The TTL Time To Live parameter is the registration duration supplied to the BBMD at the time of registration Devices must re register within this specified interval to remain connected The BBMD Info screen lets users specify the address for the BBMD to which the device will try to connect or register 9 BACNet BBMD Info gt IP 192 168 1 100 Port OxBACO For more information on this subject please consult the ASHRAE standard number 135 2001 Annex J section J5 76 301C User Manual M 510324 Honeywell 7 10 Wireless Network Menu The wireless menu allows wireless communication parameters to be set wireless network diagnostics to be consulted and the various System Programming Wireless Network Menu aspects of the wireless nodes sensors to be accessed Wireless Network Parameters gt 1 Parameters 1 7B7177EFACE0049 System Menu 2 Diagnostics 2 WC Version Invalid Option 3 Nodes 3 PAN ID 4 New Node 4 RF channel Tog Mode 5 Hibernate 5 Log Mode No Log 6 Reset Network 6 Association Ina 7 Status Log NoLog 7 Nodes o 8 Consolidate route 8 Max nodes 0 9 Max hops 0 Association 10 Power 0 11 AHFO 0
55. PAN ID e Select Parameters from the Wireless Network menu e Scroll down using the arrows to hightlight option 3 PAN ID e Press Enter to select e Change the PAN ID values as desired and press Enter The next screen requests either confirmation or cancellation Press Enter to confirm If Esc is pressed no changes will be made and the screen returns to the main Wireless Network menu e The system displays the RF channel screen press Enter to proceed or to record changed values The next screen requests confirmation or cancellation Press Enter to confirm If Esc is pressed at this point the changes to the PAN ID will not be made Parameters 1 7B7177EFACE0049 2 WC Version 3 PAN ID y PAN ID PAN ID RF channel RF Channel VAL FF07 Enter to confirm VAL 011 Enter to confirm MAX FFFF Esc to cancel EN MAX 255 Esc to cancel MIN _0001 MIN 001 Note Whenever changes are made to the PAN ID or the RF channel the network must rebuild itself Losing the network entire network in Fault mode during this process is normal and should only last approximately 10 minutes M 510324 301C User Manual 79 7 10 Honeywell System Programming Wireless Network Menu The following table provides the list of parameters displayed for the coordinator wireless communication module Use the up or down keypad arrows to navigate the entire list Title Value Description 1 7B177A7EF
56. RANTY 2 eeeeeeeeeeeeeeeeeeeeeeeeneneeees 107 Limited Warranty iii 107 Re Stocking POC Vaticana tein niet tide iti eho 107 EXxclUSiIONS rt e Lt 108 Warranty Limitation and Exclusion 108 Disclaimer of Unstated Warranties oooonocinnnccononccononnnnnonnnnnnrncnnnnnannnnos 109 Limitation of Liability smsy ss ie eein init ds 109 M 510324 301C User Manual ix 7 10 Honeywell Introduction Introduction The 301C controllers act as nerve centers for gas detection networks providing continuous monitoring for up to 96 connected units plus 1 301ADI Since the controllers are factory programmed to the owners specifications installation is limited simply to mounting and connecting them Once installed and connected the controllers allow the user to monitor adjust or reconfigure an entire network of units The 301C has a supplementary option of the wireless coordinator that enables this controller to communicate with and manage up to 25 wireless gas detection devices in addition to its regular capabilities Intended Use The controller is intended to monitor an entire gas detection network around the clock The unit offers logging capabilities creating log files of all transmitter concentrations and alarms for analysis The unit is also equipped with grouping or zoning capabilities that allow users to query and monitor specific groups of transmitters or specific transmitter
57. Scheduling A SCHED A O Scheduling Internal B SCHED I B O Scheduling External A SCHED E B Trending O Viewing and Modifying Trends A T VMT A O Trending Viewing and Modifying Trends Internal B T VMT I B O Trending Viewing and Modifying Trends External B T VMT E B O Trending Automated Trend Retrieval A T ATR A O Trending Automated Trend Retrieval B T ATR B 100 301C User Manual M 510324 Honeywell 7110 Protocol Implementation Conformance Statement Network Management O Network Management Connection Establishment A NM CE A O Network Management Connection Establishment B NM CE B O Network Management Router Configuration A NM RC A O Network Management Router Configuration B NM RC B Alarm and Event Management O Alarm and Event Notification A AE N A O Alarm and Event Notification Internal B AE N I B O Alarm and Event Notification External A AE N E B O Alarm and Event ACK A AE ACK A O Alarm and Event ACK B AE ACK B O Alarm and Event Alarm Summary A AE ASUM A O Alarm and Event Alarm Summary B AE ASUM B O Alarm and Event Enrollment Summary A AE ESUM A O Alarm and Event Enrollment Summary B AE ESUM B O Alarm and Event Information A AE INFO A O Alarm and Event Information B AE INFO B O Alarm and Event LifeSafety A AE LS A O Alarm and Event LifeSafety B AE LS B Device Management O Device Management Dynamic Device Binding A DM DDB A M Device Management Dynamic Device Binding B DM
58. Toute la journ e Jour ou Nuit Champ de d finition de semaine permet de s lectionner soit Toute la semaine Jours ouvrables ou Fin de semaine 3 EVENEMENT 3 001 Periode couverte Toute la journee Toute la semaine 1 Utiliser les touches de fl ches haut ou bas pour naviguer soit a Toute la journee ou Toute la semaine 2 Appuyer sur Enter pour s lectionner 8 Utiliser les touches de fl ches haut ou bas pour d rouler les options 4 Appuyer Enter pour s lectionner l option affich e 48 Manuel de l utilisateur 301C M 510324 Honeywell 8 10 Programmation du syst me Menu v nement Statut Cet cran affiche le statut de l venement s lectionn et permet soit d activer ou de d sactiver selon le statut actuel Active Appuyer sur Enter pour s lectionner Active evenement evenement ou Desactive evenement 3 EVENEMENT 3 001 Statut desactive D Active evenement Lorsque tous les d tails d un v nement sont inscrits le dernier cran de configuration affiche Active evenement Appuyer sur Enter pour valider les param tres et activer l v nement Lors de consultation d un v nement existant la premi re ligne de cet cran afficherait D sactive evenement Appuyer sur Enter sur cette ligne permet de basculer entre l activation et la d sactivation Lappui sur la touche Enter pour d sactiver ferme simplement l v nement et ne supprime pas l v nement L v nement ser
59. a aes 56 Not Ment R SEAU iaa 62 TMenU Tests sure tant e Sakti ie tana eed eta ako as 67 Sequence detesta nement nn 69 Mode Normal iii 71 Mode TX UNIQUE 225515 nn arica cani bee se egieneyee 71 Mode d bogage cion cian aii bahar 71 Mod Simulation ciar ii an donne ic 72 PiMenu BACNET A4 tre a aa a ate i a 73 Changer les valeurs BACNet sssesseeseeeeeiiesrreerrsereesrrnene 74 Menu reseau sans fil o k a e eea A aa a a A 79 Parametr s A E e EN E T BL 80 Modifier le PAN ID ou le Canal RF c00sseeeeeeeeeeeeeeeeeees 81 Diagnostics rica RY eed 84 NOTAE e EE AE T E A A AT 85 NOUVEAU nde Ud tio P aa 90 Menu Hiberner iii 91 Menu RAZ escala is A MM nn E me ies 91 Menu Log Statut i 4 rte a en hate aan ii 92 Menu Consolider ACCES riens 92 Sp cifications reteset ede ci eA eee pete oe entra ad 95 Configuration de r seau o eceeeceeeeeceseeeseeteeeeaeeenaeeeseeteaeeeaeeseeenaeeeaeess 95 Protocole BACnet IP Coi A e eA eR 95 Objets BACNet xica 96 viii Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Entr e analogique oooccconccccnoncccnoncconanacanonncnnannnananncnnana na an e 96 Valeur analogique eiieeii ie a T rancia 96 Entr e Dinale iii id 97 SOME binaire rl E E A cusses deacons 97 ValCUEDINAIO omita tte 97 DISPOSE sorser sN EA 98 Produits Vulcain et objets BACnet oo eee eeeceeeeeeeeeeeeeeeeeeeeeeeeeeeeteeeeeees 98 NONC DE CONFORMIT D IMPL MENTATION DE PROTOCOLE iii aan 105 Descript
60. a toujours disponible pour r activation M 510324 Manuel de l utilisateur 301C 49 7 10 Honeywell Programmation du syst me Menu acquisition Menu acquisition Le mode Acquisition est seulement disponible lorsque la centrale est munie d une carte SD option d enregistrement de donn es Cette fonction permet d activer ou de d sactiver l enregistrement des v nements du syst me ou les informations des transmetteurs Linformation est enregistr e sur une carte de m moire SD Lutilisateur doit configurer les intervales et les conditions d enregistrement n cessaires cette fonction 4 Acquisition Mode seuil 10 Debuter log Tx Debuter log La premi re ligne de l cran Acquisition permet de s lectionner soit Mode delai Permet de pr ciser des intervalles d enregistrement de 10 59 secondes ou de 1 60 minutes Mode seuil Permet de configurer l enregistrement selon les seuil de variation depuis la derni re lecture soit de 3 ou plus 5 ou plus ou de 10 ou plus de la derni re concentration d tect e La s lection du seuil 3 ne signifie pas qu une variation de 3 sera d tect e mais qu une variation 3 1 le sera La fr quence de saisie fr quence de rafra chissement peut affecter l enregistrement de donn es Voici un exemple de l enregistrement en mode seuil Ces fichiers sont des fichiers textes s par s par des points virgules 2005 04 27 11 05 20 1_C02 ppm 574 normal
61. acons measurement 18 KNSRO 0 Defines the frequency at which a node updates information from known neighbors 19 FNSRO 0 Defines the frequency at which a node will scan for new neighbors 20 Clone WC Although accessible this option is not available will be used for future advanced use features M 510324 301C User Manual 81 7 10 Honeywell System Programming Wireless Network Menu Diagnostics Menu The diagnostics menu allows both Weak Link and Lost Link reports to be consulted These reports consist of the multiple item node information list as it appears in the Nodes menu If there are no weak or lost links the system will return the message System Menu No Node Found If more than one node appears in this section use the left or right keypad arrows to scroll through nodes Diagnostics 1 Weak Link Report 2 Lost Link Report Nodes 1 1D 121 79h 2 787177EFACE0049 3 Product VA301W 82 301C User Manual M 510324 Honeywell 7 10 System Programming Wireless Network Menu Nodes Menu The Nodes menu displays a multiple item node information list Use the left and right keypad arrows to scroll between nodes and then use the up or down keypad arrows to scroll through the information list for each node Nodes 1 1D 121 79h 2 7B7177EFACE0049 3 Product VA301W Each line represents specific information as shown in the screen above Line 1 displays the device s network identification the last tw
62. age M 510324 Manuel de l utilisateur 301C 57 7 10 Honeywell Programmation du syst me Menu config Le deuxi me cran principale de configuration permet de modifier le mot de passe et de modifier la configuration du port esclave 6 Config 3 Mot de passe usage 2967 Cnfg port esclave Le mot de passe par d faut est 2967 S lectionner Mot de passe usager pour modifier le mot de passe e Lorsque le premier chiffre clignote utiliser les fl ches pour augmenter ou diminuer la valeur ensuite e Utiliser les fl ches droite et gauche pour d placer le curseur une espace et r p ter le processus de changement pour chaque chiffre d sir e Lorsque le mot de passe d sir est afficher appuyer sur Enter pour le valider et quitter le mode d dition Note Communiquer avec le soutien technique de Honeywell pour assistance concernant les mots de passe perdus au 1 800 563 2967 58 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu config Pour changer l adresse le d bit en bauds ou pour visionner le protocole de communication du port esclave D placer le curseur gauche de Cnfg port esclave et appuyer sur Enter Cnfg port esclave gt gt Adresse 001 38400 bauds Mdbs RTU 8D 2S NP e D placer le curseur la gauche du param tre d sir adresse ou d bit en bauds e Appuyer sur Enter pour s lectionner le param tre e Utiliser les fl ches pour d
63. arrows The year month day and the hour minute and second values can be changed The controller does not manage Daylight Savings Time therefore users must manually adjust any time changes Date and Time gt 2005 11 21 11 47 36 ISO 8601 standard Selecting the third line allows the display language to be changed If the display is already in English it will then display the Menu fran ais option and vice versa Simply scroll to the line and press Enter to change the language M 510324 301C User Manual 57 7 10 Honeywell Config Menu The second main screen in the Config menu allows a new user password to be set and the slave port configuration to be modified 6 Config gt Set User Password 2967 Slave Port Cnfg The default password is 2967 Select Set User Password to change the password e When the first digit blinks change the value by using the up down keypad arrows to increase or decrease the number e Use the left right keypad arrows to move from one digit to the next When the desired password has been set press Enter to validate it and exit the editing mode Note Contact Honeywell technical support for help with lost passwords at 1 800 563 2967 58 301C User Manual M 510324 Honeywell 7 10 System Programming Config Menu Scroll through the main Config menu screens using the left previous or right next keypad arrows The third main screen in the Config menu allows the rela
64. ation over an associated scale range on all transmitters The simulated gas concentration values are local on the controller and do not affect logging functions Events will be activated for the simulation but detection devices are not affected Maximum load Activates all controller components The second screen option is Oprt Mode which offers three separate operation settings Normal Single Tx or Debug e 8 Tests D Oprt Mode normal Normal Normal controller operation mode Single Tx Activates the polling mode on a single transmitter Debug Activates the service mode to perform a calibration and to test Events without triggering actions 66 301C User Manual M 510324 Honeywell 7 10 System Programming Tests Menu Test Sequence When test sequence is selected from the main Tests menu the controller will display the Test sequence screen Test sequence Relays activated Any key to continue Esc to quit If Esc is pressed on the keypad the main Tests menu screen will be displayed However to perform system tests press any key to proceed to the first test screen Test sequence BUZZER activated Any key to continue Esc to quit This screen tests each component individually and will advance only to the next component when a key is pressed This option will display 13 screens Screens 1 2 and 3 test Relays BUZZER and LEDs The following six screens prompt the user to press the keypad buttons in
65. blage de r seau peut atteindre jusqu 609 m 2000 pi par canal La longueur d une d rivation peut atteindre 20 m 65 pi jusqu a un maximum de 40m 130 pi pour toutes les d rivations Note Canal 4 est le port de communication esclave aucun transmetteur ne peut y tre connect Ex Canal 4 peut tre utilis pour la connexion esclave BACnet Tous les dispositifs sans fils associ s a la centrale seront automatiquement d tect s et utiliseront les protocoles de communication sans fils pour communiquer avec la centrale Param tres d metteurs sp cifiques Les metteurs Sensepoint XCD de Honeywell doivent tre configur s pour un d bit de 9 600 bauds avec une adresse unique et sans aucune parit tandis que les metteurs universels XNX de Honeywell doivent tre configur s pour un d bit de 9 600 bauds et avec une adresse unique la parit tant toujours paire pour ce type d metteurs Vous trouverez des informations sur la configuration de chaque metteur dans le manuel technique associ 16 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 D tails de connexion Sortie relais Sortie relais La sortie relais supporte jusqu a 5A a 30 Vcc ou 250 Vca charge r sistive seulement Les relais peuvent activer les alarmes sonores et les lampes stroboscopiques Consulter le dessin pour instructions de connexion Chaque relais est configur avec des valeurs par d faut cependant la configuration
66. changes will be lost 70 301C User Manual M 510324 Honeywell 7 10 System Programming BACnet Menu BACnet Menu The BACNet menu offers several main menu screens to configure the BACNET IP connection DHCP server time zone information and more MENU BACNet Wireless Network 9 BACNet gt Device BACnet ID 3141592 9 BACNet DHCP disabled Enable DHCP BACNet Static IP Address 123 123 123 123 9 BACNet Static Netmask ZOD 20 OW ZOO e o 9 BACNet Static Gateway 123 123 123 1 L T lt 9 BACNet gt SNTP Server SNTP Client 123 122 121 120 SNTP server SNTP request Omin lt DST BACNet Time Zone Zone 0 00 OFF lt adit 9 BACNet Device Name 20char max Blaise_Pascal BACNet ForeignDevReg dis Enable FDR TTL 43200 sec BACNet BBMD Info IP 123 124 125 126 Port OxBACO M 510324 8 10 301C User Manual Honeywell 71 System Programming Bacnet Menu The first of these screens allows the identification and address to be configured 9 BACNet Device BACnet ID 1 Static IP address BACnet ID Building Automation and Control Networks is the device ID number assigned to this particular controller on a network lt 9 BACNet gt Static IP Address 123 123 123 4123 Static IP address This is an address that is used when DH
67. copied from the controller configuration to parameters Config Allows system parameters and password to be set Network Allows actions on the network to be performed communication statistics to be consulted and remote calibrations to be performed Tests Allows each device to be tested sequentially inputs outputs communications events etc and operation of various parameters to be validated BACNet Allows a device s BACNet parameters to be set Wireless Allows a network of wireless gas detection devices to be configured monitored and modified Note Access to the programming functions is password protected The default password is 2967 The screen display shown below appears initially This display can be configured to scroll among the information screens for each device connected to the controller Ver 3 00 Ev 0 2007 01 17 13 18 18 If one or more of the connected devices is in an alarm mode the controller will only scroll between the main information screen and the screens for device s in alarm mode In this case you must scroll manually to view screens for other devices 22 301C User Manual M 510324 Honeywell 7 10 System Programming Programming Interface The information screen also displays icons representing certain system functions Here is a list of possible icons and their meaning Icon Description E Tai xT BACNet Indicates that there is a BACNet module present and that it
68. ction du champs fuseau permet d utiliser les fl ches pour d rouler dans une liste d heures disponibles de 0 00 13 00 et 12 00 a 0 00 9 BACNet Fuseau horaire Fuseau 0 00 HA INACT Le dernier cran du menu BACNet permet de pr ciser un nom pour l appareil BACNet 9 BACNet Nom Appareil D edition 20car max 301C 1 Les crans suivants permettent de configurer la communication BACNet entre les diff rents systemes sous r seaux sur un r seau en utilisant le Foreign Device Registration et le BBMD M 510324 Manuel de l utilisateur 301C 77 7 10 Honeywell Programmation du syst me Menu BACNet L cran Foreign Device Registration FDR permet d activer le FDR et de pr ciser une dur e de vie TTL ou Time To Live en secondes 9 BACNet ForeignDevReg des Active FDR TTL 43200 sec Un Foreign Device est un dispositif BACNet dont l adresse IP du sous r seau est diff rente du r seau BACNet IP auquel le dispositif veut se joindre Le param tre TTL Time To Live ou dur e de vie est la dur e de vie et l intervalle de l enregistrement envoy au BBMD lors de l inscription Les enregistrements des dispositifs doivent tre refaits avant l expiration de la dur e de vie pour que ceux ci demeurent connect s au r seau L cran BBMD Info permet de pr ciser l adresse du BBMD auquel le dispositif se connectera ou s enregistrera 9 BACNet BBMD Info
69. ctivate datalogging function before removing the CAUTION SDcard Never remove the card when its LED is on M 510324 301C User Manual 19 7 10 Honeywell Getting Started Programming Interface Programming Interface The front panel of the 301C provides a programming keypad buttons and LEDs 301C front panel Keypad Alarm A Silence Alarm B Alarm C Tx www honeywellanalytics com Rx 1 800 563 2967 Controller 301C Keypad Functions Each unit has 7 keypad keys or buttons Arrows Used to move the cursor through the various programming fields Up Down Left and Right or to adjust the display contrast press and hold the up or down arrow until desired contrast is reached and release ESC Used to exit the programming menu or to cancel a change or input Enter Used to access the programming menu and to modify programming fields Silence Turns off the controllers buzzer 20 301C User Manual M 510324 Honeywell 7 10 Getting Started Programming Interface LED Definitions The controller is equipped with 7 LEDs that provide a status for each function related to that indicator Alarm A A blinking red light indicates that an event has been activated A constant red light indicates that one or more transmitters has reached Alarm A or Alarm 1 Alarm B When the red indicator is on one or more transmitters has reached Alarm B or Alarm 2 Alarm C When the red indicator is on one or more transmitters has r
70. d 90DM4 The values Cmin and Cmax apply only to the 90DM4 M 510324 7 10 301C User Manual Honeywell 97 BACnet IP MODULE Object Examples In the first example we see the CO gas sensor input for a 301D gt Vulcain network device Name 301D2 CO2 AD 14 CQ2 Value 600 Units PPM Object 1 Al2 Description Analog Input 1 is the 301C unique device instance Al is the object type and 2 is the unique instance of the object in this device We identify this object as Analog Input 2 of BACnet device 1 In this example we can see the output status for relay 2 of the same Vulcain network device but with a different device display label Name Floor 01 Sensor 02 rel2 Value OFF Units Object 1 BO4 Description Binary Output We identify this object as Binary Output 4 of BACnet device 1 Example 3 where we can see the first 24V output status of a 301EM Vulcain network device Name 301EM CO AD 25 out1 Value OFF Units Object 1 BV1 Description Binary Value We identify this object as Binary Value 1 of BACnet device 1 98 301C User Manual M 510324 Honeywell 7 10 Protocol Implementation Conformance Statement Protocol Implementation Conformance Statement Normative BACnet Protocol Implementation Conformance Statement Date August 1 2005 Vendor Name Honeywell Analytics Product Name 301C BIP Product Model Number N A Appl
71. d activer ou de d sactiver la fonction d enregistrement de donn es Copy Permet de copier des donn es ou des param tres de la centrale a un ordinateur et vice versa ou de transmetteur a transmetteur Config Permet de r gler les param tres du syst me et de modifier le mot de passe Network Permet d ffectuer des actions sur le r seau Vulcain et de consulter les statistiques de communication Tests Permet d ffectuer un essais sur les entr es et sorties communication v nement etc et de valider l op ration de divers param tres BACNet Permet de configurer les param tres BACNet d un dispositif Wireless Permet de configurer monitorer et de modifier un r seau de d tecteurs de gaz sans fil Note L acc s aux fonctions est prot g par mot de passe par d faut est 2967 22 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Operation du syst me Lorsqu en op ration normale le syst me affiche l cran ci dessous et d roule des crans d informations pour chaque dispositif connect la centrale 301C Ver 3 0 Ad 1 Gr 0 Ev 0 e 0 2006 05 17 13 18 18 Si un ou plusieurs appareils connect s a la centrale sont en mode d alarme la centrale affichera seulement l cran principal et les crans pour les appareils en mode d alarme Le cas ch ant il est n cessaire d utiliser les fl ches pour d rouler les crans de tout autre dispositi
72. de signal 0 100 d un noeud relatif a la qualit de signal du parent 5 Mode d op Log Enregistre toutes les donn es d activit du dispositif sans fil s lectionn dans le coordonnateur 6 Adrreseau 0009 Affiche l adresse de r seau hexad cimale du noeud 7 Fenetre 1 Affiche la fen tre SWU utilis e pour SWU transmettre la balise 8 deparents 1 Affiche le nombre de parents actuels pour le noeud de 0 3 9 DP Id 0 Affiche l identificateur associ au parent par d faut 10 DP Adr res 0 Affiche l adresse r seau pour le parent par d faut 12 DPLQAI 2 Affiche la qualit du lien avec le parent par d faut 0 pas de lien 1 lien faible 2 lien fort 12 DP Retries Affiche le nombre de relancements du parent par d faut 13 DP BM 0 Affiche le nombre de balises de parent manqu sur la derni re p riode de balise 14 DPLC 256 Affiche le temps depuis la derni re communication avec le parent par d faut en millisecondes 15 AP1ID Affiche l identificateur associ au parent alternatif 1 16 AP1Adrres Affiche l adresse r seau du parent alternatif 1 86 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu reseau sans fil Titre Valeur Description 17 AP1LQI 16 Affiche la qualit du lien avec le parent alternatif 1 0 pas de lien 1 lien faible 2 lien fort 18 AP1Retries 128 Affiche le nombre de relancements du parent alternatif 1 19
73. defines a standardized object whose properties represent the externally visible characteristics of an analog input such as a gas sensor Supported properties for the Analog Input object type are Object_Identifier Object_ Name Object_Type Status_Flags Event_State Reliability Present_Value Out_of_Service and Units Analog Value The Analog Value object type defines a standardized object whose properties represent the externally visible characteristics of an analog value An analog value is a control system parameter residing in the memory of the BACnet Device such as a gas alarm level Supported properties for the Analog Value object type are Object_Identifier Object_ Name Object_Type Status_Flags Event_State Reliability Present_Value and Units Binary Input The Binary Input object type defines a standardized object whose properties represent the externally visible characteristics of a binary input A binary input is a physical device or hardware input that can be in only one of two distinct states such as the 301ADI digital inputs Supported properties for the Binary Input object type are Object_Identifier Object_ Name Object_Type Status_Flags Event_State Reliability Present_Value Polarity Inactive_Text and Active_Text and Out_of_Service 92 301C User Manual M 510324 Honeywell 7 10 BACnet IP MODULE Binary Output The Binary Output object type defines a standardized object whose properties represent
74. ds Lipp Noeuds 1 ID TxRef 9 121 gt 1 ID TxRef 9 121 2 7B7177EFACE0049 2 7B7177EFACE0049 3 Produit VA301W 3 Produit VA301W 4 Qualit lien 1 Le menu N uds affich dans les 5 Mode d op Log rapports de liens faible et de liens 6 adr reseau 9 perdus est identique au menu 7 Fenetre SWU 1 Noeuds option 3 du menu Reseau 8 de parents aeii 9 DP Id 0 10 DP Adr res 0 11 pr Lal 2 12 DP Retries 2 13 DP BM 0 14 DP LC 256 15 AP1 ID 2 Niort Sih 16 APL adr res 7 y eee 17 AP1 Lal 16 Option Invalide 18 AP1 Retries 128 19 AP1 BM 2 20 AP1 LC 27132032 21 AP2 ID 2 22 AP2 Adr res 31756 23 AP2 LQl 198 24 AP2 Retries 190 25 AP2 BM 0 26 AP2 LC 56320 27 LSU 661 28 Statut Alive 29 Fraicheur 2 30 Version Al4 31 Hiberner J Hibemer 32 Remplacer Enter pour confirmer 33 Enlever gt Esc pour annuler 34 Consolider acces 35 Failsafe N A Nouveau noeud VAL 09 MAX 3A MIN _09 RAZ reseau Enter pour confirmer W Esc pour annuler Log Statut Log Statut R Enter pour confirmer Log Esc pour annuler Consolider acces Consolider acces VAL 00060 Enter pour confirmer gt MAX 65535 Esc pour annuler MIN _00000 5 dis M 510324 Manuel de l utilisateur 301C 79 7 10 Honeywell Programmation du syst me Menu reseau sans fil Parametres Lors de la s lection de l option Parametres depuis le menu Sans fil les param tres sont affich s en ordre Puisqu
75. du coordonnateur 2 WC Version A10 Version du micrologiciel du coordonnateur sans fil 3 PAN ID FFO7 Lindificateur hexad cimal assign au coordonnateur 4 Canal RF 11 Canal de radiofr quence du coordonateur 5 Mode Log Log Indique si le mode d bogage est activ 6 Association Ina D termine si de nouveaux noeuds peuvent se joindre au r seau 7 Noeuds 0 Affiche le nombre de noeuds dans le r seau 8 Max noeuds 0 D termine le nombre maximum de noeuds permis sur le r seau 1 60 9 Max sauts 0 D termine le nombre maximum de sauts permis a u noeud pour atteindre un coordonnateur sans fil 10 Puissance 0 R gle la valeur d amplification de puissance de transmission 11 AHFO 0 D termine le lapse de temps entre les cycles de r veil 12 BO 0 R gle le lapse de temps entre la transmission de deux balises cons cutives par un noeud pour tablir et maintenir la synchrinisation 13 SUO 0 D fini la p riode de mise jour de statut temps entre 2 paquets de mise jour de statut cons cutifs envoy s par un node au coordonnateur 14 LCO 18 Paquet envoy du coordonnateur au 82 Manuel de l utilisateur 301C noeud pour indiquer au noeud qu il est enregistr sur le r seau au coordonnateur M 510324 Honeywell 7 10 Programmation du syst me Menu reseau sans fil Titre Valeur Description 15 LTO 0 Le nombre de paquets de mise a jour de statut qui peuvent tre manqu s sans qu un leave indication
76. du syst me Menu config Menu config Le menu Config avec quatres crans principaux permet de configurer le mode d affichage de la centrale d ajuster la date et heure de s lectionner le langage d affichage de changer le mot de passe d acc s a la centrale de modifier le port esclave r gler la configuration des relais s lectionner le mode d mission AP Chaque cran principale offre des options de programmation suppl mentaires MENU gt 5 Copie 7 Reseau 3 6 Config 8 Tests 6 Config gt p Defilement manuel Regle Date et heure English menu Date et heure gt 2005 11 21 11 47 36 norme ISO 8601 6 Config p Mot de passe usage 2967 Cnfg port esclave gt Cnfg port esclave Adresse 001 38400 bauds Mdbs RTU 8D 2S NP 6 Config gt gt Configurat relais Emission AP auto Honeywell Configuration relais gt Configuration relais Failsafe Silence gt Tous les relais 1 2 3 4 Inactif ina__act ina ina 6 Config gt Definition jour Definition semaine Definition Jour Jour deb 08 00 fin 17 00 Definition semaine jours ouvrables deb Lundi fin Vendredi 56 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu config La s lection de la premi re ligne du premier cran offre le choix de trois m
77. e which subsequently has its information updated This mode does not interfere with Event Evaluation functions Debug Mode This mode allows complete system operation to be evaluated and tested without affecting operations outside of debug mode Events are evaluated and displayed as necessary but no action is triggered M 510324 301C User Manual 69 7 10 Honeywell System Programming Tests Menu Simulation Mode This mode deactivates network communication Information Updates It can be combined with any of the three previous modes example using the Simulation mode when in Debug mode allows the user to test the entire system groups events etc without triggering any actions or using any additional material such as gases It allows gas concentrations to be simulated over an associated scale for each transmitter sequentially Alarm levels A B and C are evaluated according to the simulated gas concentration and events are evaluated and actions are taken This type of alarm simulation at the controller does not work with certain transmitters with falling alarms In these cases an alarm can be simulated at the transmitter While in simulation mode the controller is unaware of the device s actual network status This mode can be stopped at any time in the Test menu see Normal System Operation If one of these modes has been activated the system will automatically return to Normal Mode after 12 hours of inactivity No
78. e gaz sans fil 301W Les d tails de c blage alimentation capacit s etc se trouvent la section Sp cifications de ce guide FE SO Wireless eo 9 communication module Q fo xe 7 n 00 pl 510 l 29 a Ols 90 APIE CIE E l ON io eee L gt ns de fin de lign RELAY 1 RELAY 2 2 M a OE os OF 8009 e SHIELG 3 a SORTIES RELAIS _ H Canal 4 ne pas tse Pa noue eg ouvert 4 0 procera Legs Ls carats e 008 normalement 112 a Vis de mise la a on V terre gt AX risque ve choc LECTRIQUE AX RISQUE DE cuoc LECTRIQUE Toujours respecter les eigenes minimales Taimentaton rappare COMMUNICATION MODULE BacNet IP BIP option Calibre de c ble de Communication Communic ation sans fils Ethemet 10 100 compatible avec 2 24 AWG Belden 9841 ISM woridwide 10 Base T interface RJ 45 c ble torsad et blind Port e intiriawe 30m 600 m 2000 pi par canal Indicateurs visuels T tap 20 m 65 pi T tap DEL vert LINK 40 m 130 pi total DEL jaune ACT SSS RP 14 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 D tails de connexion Instructions d installation Les connecteurs ou ports de la carte PCB permettent d effectuer la
79. e l cran peut seulement afficher 3 items la fois il est n cessaire de d rouler la liste de param tres en utilisant les fl ches haut et bas Parametres 7B7177EFACE0049 7 Menu Systeme WC Version 4 Option Invalide PAN ID Canal RF i Medias gt gt Association Ena 4 F Log Noeuds O t 4 1 2 3 4 5 ModeLog NoLog 6 7 8 Max noeuds 9 Max sauts Association 10 Puissance 11 AHFO 12 BO 13 SUO PANID 14 LCO 00000 15 LTO 65535 16 MMO 00001 17 BMO TORO MAC 1ere partie JS PNEBO 00155F00 20 Clone WC FFFFFFFF 00000000 Note Certaines donn es sont affich es aux fins d information seulement et ne ne sont pas modifiables Lors de la s lection d une de ces donn es l cran affiche bri vement Menu Systeme Option invalide tel qu indiqu ci haut 80 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu reseau sans fil Modifier le PAN ID ou le Canal RF Lorsque le PAN ID ou le Canal RF est modifi depuis l option Parametres du menu Reseau sans fils il est n cessaire de confirmer les modifications plusieurs tapes Les instructions ci dessous sont identiques que ce soit pour modifier le PAN ID ou le Canal RF S lectionner Parametres depuis le menu Reseau sans fil D rouler avec les fl ches pour surligner l option 3 PAN ID ou 4 Canal RF Appuyer sur Enter pour s lec
80. e produits preprogramm s disponibles partir de l option Ident du menu INFO Tx 1 INFO Tx 001 gt Ident gt 301W CO2 IR Types de produit Adresses 1 96 VA301D2 VA301AP XNX 90DM3R VASQN8X XCD VA301IRF VA301EM VA201R IRT100 VA301EMRP VA201T EC F9 GsPnt2 90DM2 VA201T2 S301RLC VA201D VA301T Std Device VA301D GsPnt VA901T NotVul RgRt3 Types de produit Adresses 97 120 Adresses 121 170 301ADI 301W 301 RW 301RPT Le produit Std Device comprend les produits suivants S301M 90DM4 420MDBS et 301ADI Note Lorsque le type de produit est un groupe les autres crans INFO TX ne seront pas disponibles puisque chaque produit d j t configur dans la centrale Seul les crans Ident Affichage et Effacer Tx courant seront disponibles 28 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu INFO Tx Voici une liste de tous les types de sondes preprogramm s disponibles partir de l option Ident du menu INFO Tx Types de sondes CH4 CO NH3 NO2 HCL R11 R12 R22 R134A R125 R123 F2 HF Comb CH4 CO CO H2 SO2 H2S ETO NO CI2 SIH4 HCN O3 HBr BCI3 COCI2 R123 IR B2H6 Comb IR H2 CO2 IR AsH3 CO2 IR CIO2 R245A IR PH3 FE227 IR CO R404A IR Unknown IR sensor R507A IR Comb IR R401A IR R11 IR R13B1 IR R12 IR R23 IR R22 IR No sensor R134A IR R125 IR La
81. eached Alarm C Power Green indicates that the unit is powered up and functional Fault When the amber LED is on it indicates a fault i e a communication maintenance or device problem TX When the amber LED is blinking it indicates that the controller is sending information or requests on the communication channel Rx When the green LED is blinking it indicates that the controller is receiving information Each of these functions is linked to parameters programmed in the control unit which we will discuss in the following section System Operation The system operates in four different modes that allow it to use analyze debug and simulate the actions that the system can perform These modes are Normal Single Tx Debug and Simulate The default system operation mode is Normal The other modes are available through the Tests menu option 8 from the Main Menu Note Systems services may be disrupted by some menu operations M 510324 301C User Manual 21 7 10 Honeywell System Programming Programming Interface System Programming The system s Normal programming mode offers several menu options that are accessible from the main menu screen Tx Info Allows transmitter parameters to be programmed Groups Allows groups of transmitters to be set up Events Allows events and event behavior to be programmed Acqui Allows the datalogging feature to be activated or deactivated Copy Allows data or parameters to be
82. eau BACnet par la centrales 301C Profil de dispositif normalis BACnet Standardized Device Profile O BACnet Operator Workstation B OWS _ O BACnet Building Controller B BC O BACnet Advanced Application Controller B AAC _ O BACnet Application Specific Controller B ASC M BACnet Smart Sensor B SS MBACnet Smart Actuator B SA M 510324 Manuel de Putilisateur 301C 105 7 10 Honeywell nonc de conformit d impl mentation de protocole Liste de toutes les unit s de structure d interop rabilit BACnet support es Annexe K Partage de donn es O Data Sharing ReadProperty A DS RP A M Data Sharing ReadProperty B DS RP B O Data Sharing ReadPropertyMultiple A DS RPM A M Data Sharing ReadPropertyMultiple B DS RPM B O Data Sharing ReadPropertyConditional A DS RPC A O Data Sharing ReadPropertyConditional B DS RPC B O Data Sharing WriteProperty A DS WP A M Data Sharing WriteProperty B DS WP B O Data Sharing WritePropertyMultiple A DS WPM A O Data Sharing WritePropertyMultiple B DS WPM B O Data Sharing COV A DS COV A O Data Sharing COV B DS COV B O Data Sharing COVP A DS COVP A O Data Sharing COVP B DS COVP B O Data Sharing COV Unsolicited A DS COVU A O Data Sharing COV Unsolicited B DS COVU B Planification O Scheduling A SCHED A O Scheduling Internal B SCHED I B O Scheduling External A SCHED E B Tendances O Viewing and Modifying Trends A T VMT A O Trending
83. ecuted After The time to wait after an event has returned to normal before returning action output to normal state The after delay also offers a Latch option described below 3 Events 0013 Delays Before D 99min After 01min Before and After delays can be configured at either 30 or 45 seconds or from 1 to 99 minutes in one minute increments Five dashes indicates that no delay has been programmed e Use the keypad arrows to scroll to the desire option e Press Enter to select the option e Use the keypad arrows to scroll through the second or minute settings e Press Enter at the desired setting The delay is set M 510324 301C User Manual 43 7 10 Honeywell System Programming Event Menu Latch Mode e The Latch function is executed on an Event state e It is possible to select the Latch mode by changing the after delay to e The Event stays active until the Silence keypad button is pressed e The Silence keypad button has two functions Silence the buzzer and unlatch the event e When the Silence keypad button is pressed events in Latch mode are unlatched and reevaluated If the Event condition persists the Event remains active and returns to Latch mode If the condition does not persist the event is deactivated Note If the Event has a Before delay and the Silence button is pressed while the Event conditions are still true the buzzer will be silenced only for the length of the programmed dela
84. en pour la visualisation ou changer des alarmes A B ou les seuils C seuils sur d autres transmetteurs 34 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu INFO Tx Entretien et Exploitation des Menus Ces fonctions varient selon le type d metteur Ces crans montrent le temps total du dispositif a t mis en service et le temps restant jusqu la prochaine calibration n cessaires ou de remplacement 1 INFO Tx 001 Entretien 4002h en fonction 15514h avant entr 1 INFO Tx gt 121 Temps d Operation Temps de Vie 00000 Depuis calib 00730 lt 1 INFOTx 026 P Temps d operation Sensor life left 1804 days M 510324 Manuel de l utilisateur 301C 35 7 10 Honeywell Programmation du syst me Menu INFO Tx Code d Etat Cet cran affiche l tat de la transmission Tx ou du noeud seulement pour les appareils sans fil et l tat de la sonde pour l adresse du dispositif s lectionn en valeurs hexad cimales Cet cran est aux fins d informations seulement les donn es affich es ne peuvent pas tre modifi es 1 INFO Tx D026 gt Code d Etat Etat Tx 0000 Etat Monitor 0001 L talage typique pour X ou Y 1 INFO Tx 121 Code d Etat Etat Tx 12FAh Etat Sonde 4407h talage typique pour d autres transmetteurs Note L cran Code d Etat contient des informations importantes pour les technicien
85. ent L v nement demeure actif jusqu au moment de pression sur la touche Silence Cette touche arr te l alarme sonore et rel che l v nement Lors de l appui sur la touche Silence les v nements sont rel ch s et r valu s Si la condition de l v nement est toujours vrai l v nement demeure actif et revient en mode Latch Si la condition ne persiste pas l v nement est d sactiv Note Si un v nement est configur avec un d lais Avant et que la touche Silence est enfonc e lorsque les conditions de l v nement sont toujours vraies l alarme sonore sera ferm seulement pour la dur e du d lais pr cis 44 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu v nement Conditions Les Conditions sont les param tres de d finition de calculs qui d cident si un v nement est vrai ou non Chaque condition est d finie par quatres l ments Il est galement possible de lier deux conditions pour obtenir une plus grande flexibilit Une condition d fini Si au moins 1 3 du groupe 36 d tecte des concentrations sup rieures 2 01 du gaz pr cis ET tout les l ments du groupe 03 d tectent une concentration sup rieure 2 99 de gaz l action pr cis e configur e dans le premier cran v nement pour cette v nement sera d clencher Puisque l affichage offre une espace limit e il est n cessaire de naviguer gauche et droite pour configur
86. ent d op rer le syst me dans quatre modes diff rents chacun offrant des fonctionalit s particuli res MENU 5 Copie 7 Reseau 6 Config D 8 Tests 8 Tests gt Sequence de test Debuter sequ Sim Charge maximum Sequence de test Relais actives Appuyez une touche ESC quittter 2 Sequence de test Alarme sonore Appuyez une touche ESC pour quitter Sequence de test DEL active Appuyez une touche ESC pour quitter Sequence de test Presser gauche ESC pour quitter Sequence de test Test affichage Pressez une touche ESC pour quitter Sequence de test Test comm reseau 9600 bauds Channel 1 SUCCES Sequence de test Test termine Pressez une touche Sequence simulation gt Debuter avec Tx001 Confirmer me 8 Tests Mode fct normal M 510324 Manuel de l utilisateur 301C 67 7 10 Honeywell Programmation du syst me Menu Tests Le menu Tests offre quatre options principales disponibles sur deux crans Chacune de ces options offres des fonctionnalit s suppl mentaires Le premier cran pr sente trois options 8 Tests Sequence de test Debuter sequ Sim Charge maximum Sequence de test Permet d activer chaque sortie et de valider l op ration de chaque touche de clavier des pixels d affichage et les divers protocoles de communication de la centrale Debuter sequ sim D marre ou arr te le mode de simulation pe
87. ent to be defined The time frames for each of these periods can be defined in the controller Config menu This option provides two further selection fields Day definition field allows All day Daytime or Nighttime to be selected Week definition field Weekend Working Days All week 3 Events D 0013 Coverage Period All day All week 1 Use the keypad up or down arrows to scroll to either All day or All week 2 Press Enter to select The value can now be changed 3 Use the keypad up ro down arrows to scroll through options see above 4 Press Enter to select 48 301C User Manual M 510324 Honeywell 8 10 System Programming Event Menu Status This screen displays the current event status and allows it to be either enabled or disabled depending on the current status Enable event This is a toggle switch press Enter to change the value from Enable to Disable and vice versa 3 EVENT gt 001 Status disabled D Enable event After going through all the steps and programming an event this screen will display Enable event Press Enter to activate all the parameters and enable the Event If an existing Event is being consulted this screen would display Disable event Press Enter to disable an Event it will not be deleted but will not function The programming of this Event is always present which means that it easily can be reactivated by scrolling to this screen and pressing Ent
88. er Database This screens displays the options linked to the database Erase current event Lets user erase the current event Erase all events Lets user erase all events 3 Events Database D Erase current event Erase all events M 510324 301C User Manual 49 7 10 Honeywell System Programming Acquisition Menu Acquisition Menu The Acquisition mode is only accessible when there is an SD card present controllers with the Data Logging or DLC function It is used to enable or disable the logging of system Events or transmitter information The information is logged or recorded on an SD card Intervals or conditions must be defined before using this option 4 Acquisition 10 threshold mode Start Tx logging Start event logging The first line of the Acquisition screen offers either Delay mode Allows for delay intervals of 10 to 59 seconds or 1 to 60 minutes Threshold mode Allows log values to be set according to set variation thresholds based on last reading of 3 or more 5 or more or 10 or more of last detected concentration If a 3 threshhold is selected the system will not log a value at 3 but will log a value of 3 1 Remember that the sampling rate system refresh rate may have an impact on logging Here is an example of threshold logging The logs a semi colon delineated text files 2005 04 27 11 05 20 1_CO2_ppm 574 normal 2005 04 27 11 06 02 1_CO2_ppm 503 normal 2005 04 2
89. er ou consulter tous les param tres de condition crans de programmation de conditions 3 EVENEMENT gt 001 1 3 Gr036 gt 2 01 ET 3 EVENEMENT 001 tous Gr003 ET gt 2 99 La partie de l cran de condition v nement entre parenth ses est divis e en quatres champs ditables M 510324 Manuel de l utilisateur 301C 45 7 10 Honeywell Programmation du syst me Menu v nement La partie sup rieur de gauche contient le quantificateur de statistique disponible seulement pour les groupes Cette option permet de choisir quelle partie du groupe inclure dans l quation Les options de ce champs sont tous moy max min 1 4 1 3 1 2 2 3 3 4 1or 46 inclus tous les transmetteurs du groupe inclus la concentration moyenne des transmetteurs du groupe inclus la concentration maximum du groupe inclus la concentration minimum du groupe inclus au moins un quart des transmetteurs du group ayant atteint les conditions inclus au moins un tiers des transmetteurs du group ayant atteint les conditions inclus au moins la moiti des transmetteurs du group ayant atteint les conditions inclus au moins deux tiers des transmetteurs du group ayant atteint les conditions inclus au moins trois quarts des transmetteurs du group ayant atteint les conditions au moins un ou plusieurs des transmetteurs du groupe ayant atteint les conditions Manuel de l utilisateur 301C M 510324 Ho
90. es a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices A CAUTION Symbol on the equipment refers the user to the product manual for additional information The symbol appears next to required information in the manual WARNING Indicates a potentially hazardous situation which if not avoided could result in serious injury or death A WARNING symbol on the equipment refers the user to the product manual for additional information The symbol appears next to required information in the manual M 510324 301C User Manual 7 10 Honeywell INTRODUCTION saosciiraoniaaaritada anna 11 Intended USE ini RE apre 11 Receiving and Unpacking ss 11 Installation Instructions ooononcnnnnncoccoccccnncnnccnnnnnnananonnnccnnnnncncnnnannnnns 12 Basic Guidelines ironia 12 Surface Mount Installation craneo 13 Wiring Details cional 14 Power Connections miccional 16 Communication CONNECTIONS ccoooocccncononcnnncconnnnnnnonononcnncnonnnnnnnnnnnnnos 16 Settings for Specific Transmitters ooocnnnicinniconncccnnnccnninncnonacanannncnnns 16 Relay Output nieta ici ere ment sens 17 Jumper Use INStructions oooonococonnccnnnnccnnnoccnnscecnnnnnnnnrncnnnnn carnero 18 GETTING STARTED sonic aia 19 Initial Startup ico LE LE IE 19 Datalogger SDcard ss 19 Programming Interface 20 Keypad Functions sisi nn da ata 20 E D D finitions
91. es param tres Avant et Apr s qui retardent l activation ou la d sactivation d une action Avant Retarde une action pour la dur e de temps pr cis e Si la condition persiste apr s le d lai pr cis un alarme est activ et l action pr cis e est effectu e Apr s Retarde la d sactivation d une action l action continuera jusqu l puisement du temps de d lais pr cis et si l v nement n est plus vrai Il est galement possible de s lectionner l option latch dans le champs de d lais apr s 3 EVENEMENT 3 001 Delais Avant D 99min Apres 01min Les d lais Avant et Apr s peuvent tre programm s soit 30 ou 45 secondes ou de 1 99 minutes en incr ment de 1 minute L option a cing traits d union indique qu il n y a aucun d lai configur e Utiliser les fl ches pour d placer le curseur l option d sir e e Appuyer sur Enter pour s lectionner l option e Utiliser les fl ches pour d rouler dans la liste de secondes ou minutes e Appuyer sur Enter pour valider le d lais d sir M 510324 Manuel de l utilisateur 301C 43 7 10 Honeywell Programmation du syst me Menu v nement D lais mode latch La fonction Latch disponible depuis le menu d roulant du d lais Apr s est ex cut sur un tat d v nement Essentiellement c est un circuit de verrouillage c est a dire qu une intervention humaine est n cessaire pour d verrouiller l action de l v nem
92. f M 510324 Manuel de l utilisateur 301C 23 7 10 Honeywell Programmation du syst me Operation du syst me L cran d information affiche galement des ic nes repr sentant certaines fonctions Voici la liste des ic nes et leurs descriptions Ic ne Description BACNet Indique la pr sence d un module BACNet en a communication avec la centrale Erreur BACNet Indique la pr sence d un module BACNet mais que la communication avec la centrale est en faute erreur E D bogage Indique que la centrale est en mode d bogage t modes de TX unique D bogage ou Simulation SIM appara t avec cette ic ne lorsque en mode de simulation Log Indique que soit le Log Tx ou le Log even est activ Erreur de log Indique qu une erreur est survenue lors de El Penregistrement de Tx ou Even Toutes fonctions d enregistrements sont arr t es SDC Indique la pr sence d une carte m moire SDcard en o fonction Lic ne se rempli de blanc noir selon la quantit de m moire utilis e Une ic ne blanche indique une m moire vide et une ic ne noire indique une m moire pleine Erreur SDC Si ce symbole persiste pendant plus de 5 Fi secondes une carte SD est pr sent mais ne fonctionne pas correctement R seau sans fil Indique qu un coordonnateur de r seau sans fil Ta module de communication sans fil est pr sent et en communication avec la centrale R seau sans fil Indique qu un co
93. holds are combined in this manual There will be either two or three levels depending on transmitter type If present separate MIN and MAX levels permit manual control of the hysteresis of each alarm Normally the MAX level is set greater than MIN However alarms can be made to trigger on falling concentration as with oxygen by setting the MAX threshold smaller than the MIN threshold With certain transmitters only one threshold will be displayed Additionally with certain transmitters the alarm thresholds are read only at the controller These thresholds can be set only at the transmitter These are typical screens lt 1 Tx INFO 001 gt Alarm B Level 20 0 ppm Typical screen for viewing alarms A or B on XCD and XNX transmitters lt 1 Tx INFO 001 Alarm C MIN 60 0 Typical screen for viewing or changing alarm A B or C thresholds on other transmitters M 510324 301C User Manual 33 7 10 Honeywell System Programming Tx Info Menu Servicing and Operating Menus These functions vary depending on the transmitter type These displays show the total time the device has been in service and the amount of time remaining until the next required calibration or replacement 34 lt 1 Tx INFO 001 Operating Times Lifetime Since Calib 1 Tx INFO 001 Servicing 1234 Hours on 15514 before cal lt 1 Tx INFO 001 Operating Times Sensor life left
94. ibles les valves les aubes les lements de sonde les cartouches ou les l ments de filtres Limitation et exclusion de la garantie Honeywell Analytics n aura aucun autre responsabilit sous cette garantie limit e Toutes responsabilit s de garantie d Honeywell Analytics sont annul es si le Produit a subi des abus de la n gligeance un accident ou si l Acheteur est en d faut de ses obligations tels que d crit dans cette garantie ou si le Produit n a pas t utilis selon les instructions ou si le num ro de s rie du Produit t enlev ou modifi M 510324 Manuel de l utilisateur 301C 114 7 10 Honeywell Garantie limit e D n gation de responsabilit d autres garanties La garantie ci haut est la seule garantie applicable a cet achat Toutes autres garanties soit implicites ou expres incluant mais pas limit a les garanties tacites de qualit marchande ou de l aptitude un emploi particulier sont d n gu es par le pr sent document Limitation de responsabilit Il est entendu que la responsabilit d Honeywell Analytics soit en contrat en d lit civil sous n importe quelle garantie de responsabilit en n gligence ou autrement n exc dera pas le prix d achat pay par l Acheteur pour le produit Honeywell Analytics ne sera pas responsable sous aucune circonstance pour des dommages sp ciaux ou indirectes Le prix d clar pour le produit est une consid ration limitant la responsab
95. ications Software Version 1 0 Firmware Revision 1 0 BACnet Protocol Revision 1 0 Product Description The 301C BIP has a module that uses BACnet communication As such the components of a Vulcain network can be connected to a BACnet network via the 301C controller BACnet Standardized Device Profile Annex L O BACnet Operator Workstation B OWS _ O BACnet Building Controller B BC O BACnet Advanced Application Controller B AAC O BACnet Application Specific Controller B ASC M BACnet Smart Sensor B SS MBACnet Smart Actuator B SA M 510324 301C User Manual 99 7 10 Honeywell Protocol Implementation Conformance Statement List all BACnet Interoperability Building Blocks Supported Annex K Data Sharing O Data Sharing ReadProperty A DS RP A M Data Sharing ReadProperty B DS RP B O Data Sharing ReadPropertyMultiple A DS RPM A M Data Sharing ReadPropertyMultiple B DS RPM B O Data Sharing ReadPropertyConditional A DS RPC A O Data Sharing ReadPropertyConditional B DS RPC B O Data Sharing WriteProperty A DS WP A M Data Sharing WriteProperty B DS WP B O Data Sharing WritePropertyMultiple A DS WPM A O Data Sharing WritePropertyMultiple B DS WPM B O Data Sharing COV A DS COV A O Data Sharing COV B DS COV B O Data Sharing COVP A DS COVP A O Data Sharing COVP B DS COVP B O Data Sharing COV Unsolicited A DS COVU A O Data Sharing COV Unsolicited B DS COVU B Scheduling O
96. ilit d Honeywell Analytics Aucune action en quelle forme que soit survenant des transactions sous cette garantie peuvent tre entreprises par l Acheteur plus d un an apr s l occurence de la cause de ces actions M 510324 Manuel de l utilisateur 301C 115 7 10 Honeywell
97. ion du Produit oooocoonccconocccnoncncancnonanonononononnnnnonnna corran nnrnnn rca 105 Options Couche liaison de donn es seenen 109 Association d adresse de dispositif 109 Options de r seautage 109 Jeux de caract res support s conccincccccnccccnonnccnancnnnananananacanas 109 SPECIFICATIONS is iccccssestessesscctcadtcccteccstvisasicustessnecerast 111 GARANTIE LIMIT E ssssssscticicntcinviccicessssetnastnnsnnnnensrsctes 113 Garantie limit e 22 ae ee ds en nr aie O EEES Sasi 113 Politique de Retour urine Hite tee 113 ExclUsiONS Lit des senile HR As 114 Limitation et exclusion de la garantie aeeie 114 D n gation de responsabilit d autres garanties 115 Limitation de responsabilit ee eeeeeeeeeeeeeeeeeseeeeeeeeeeeeteeeseeeenaeeee 115 M 510324 Manuel de l utilisateur 301C ix 7 10 Honeywell Introduction Utilisation Introduction La centrale 301C agit de centrale pour r seaux de d tection de gaz offrant une surveillance continue sur un maximum de 96 unit s avec un 301ADI connect es Puisque la centrale est configur selon vos besoins l installation demande simplement le montage et la connexion Aussit t install e la centrale vous permet de monitorer d ajuster ou de configurer un r seau complet d unit s Le 301C comporte l option du coordonnateur sans fil qui permet la centrale de com
98. is communicating with the controller BACNet error Indicates that a BACNet module is present but communication with the controller has failed error Debug Indicates whether the controller is in debug mode Single TX Debug or Simulation modes When in simulation mode SIM appears next to this icon Log Indicates that either Tx Logging or Event logging is enabled Log error Indicates that an error occured during TX or Event logging All logging functions are stopped SDC Indicates that an SDcard is present and functionning The icon fills from white to black progressively as memory is used A white icon indicates empty memory and black indicates full memory SDC error If this symbol persists for more than 5 seconds an SD card card is present but not functioning properly Wireless network Indicates that the wireless network coordinator wireless communication module is present and communicating with the controller Wireless network error Indicates that the wireless network coordinator wireless communication module is present but is not communicating with the controller M 510324 7 10 301C User Manual 23 Honeywell System Programming Programming Interface Since the controller s programming functions are password protected it is necessary to access the login screen e Press Enter to access the programming options The password screen appears e Use the keypad Up or Down arrows t
99. ist Max_APDU_Length_Accepted Segmentation_Supported APDU_Timeout Number_Of_APDU_Retries Device_Address_Binding Database_Revision Local_Time Local_Date UTC_Offset Daylight_Savings_Status and Out_of_Service M 510324 301C User Manual 93 7 10 Honeywell BACnet IP MODULE Honeywell Products and BACnet Objects Object Names Object names are constructed in two parts as follows Part one Part two The device display label product name for the network in which the object resides This value is editable only when using the 301C controller Unique tag label among all the objects for the same device Ex 301D2 CO2 AD 14 CO2 where 301D2 CO2 AD 14 is the device display label and CO2 is the unique tag label that identifies the object as a CO2 sensor Vulcain Object Tag Labels 94 Honeywell Table 1 Tag Labels Description ae Gas label Gas sensor Al Alrm Simple alarm level AV Amin Amax Alarm level A and hysteresis AV Bmin Bmax Alarm level B and hysteresis AV Cmin Cmax Alarm level C and hysteresis AV relx Relay output X 1 to 8 BO buzz Buzzer output BO outx Output X 1 to 3 BO or BV AIX Analog input X 1 to 16 Al BIx Binary Input X 1 to 12 BI RH Relative Humidity sensor Al Temp Temperature sensor Al 301C User Manual M 510324 7110 Object Table For Honeywell Network Devices BACnet IP MODULE Objects residing in Honeywell network devices
100. itif de r seau o r side l objet La deuxi me partie est son tiquette rep re unique parmi tous les objets du m me dispositif Ex 301D2 CO2 AD 14 C02 o 301D2 CO2 AD 14 est le label d affichage du dispositif et CO2 est le label rep re unique qui identifie l objet comme une sonde CO2 98 Manuel d utilisateur 301C M 510324 Honeywell 7 10 Objets BACNet Labels rep res d objets Vulcain Labels rep res Description Type d objet Gas label Capteur de gaz Al Alrm Niveau d alarme simple AV Amin Amax Niveau d alarme AGI AV hyst r sis Bmin Bmax Niveau d alarme Bet AV hyst r sis Cmin Cmax Niveau d alarme Cet AV hyst er sis relx Sortie relais X 1 8 BO buzz Sortie alarme sonore BO outx Output X 1 to 3 BO ou BV AIX Analog input X 1 to 16 Al BIx Binary Input X 1 to 12 BI RH Relative Humidity sensor Al Temp Temperature sensor Al M 510324 Manuel d utilisateur 301C 99 7 10 Honeywell Objets pour les dispositifs de r seau Honeywell Objets BACNet Objets pour les dispositifs de r seau Honeywell Dispositif GP2 301IRF 301EM 201T2 vulbus 90DM3R GAZ GAZ GAZ GAZ GAZ Amin Amin Amin Amin Alrm Amax Amax Amax Amax Bmin Bmin Bmin Bmin Bmax Bmax Bmax Bmax Cmin Cmin Cmin Cmin Cmax Cmax Cmax Cmax rel1 rel1 rel1 snsr1 rel1 rel2 rel2 rel2 snsr1 rel3 rel3 snsr1
101. ition avec des param tres particuliers et l autre cran de condition avec une plage horaire la condition pr cis e d clenchera un v nement seulement si elle se produit dans la plage pr cis e Note Cliquer sur la loupe droite d un groupe pour acc der l cran du groupe consultation ou modification Appuyer sur ESC pour fermer l cran et revenir l cran de condition M 510324 Manuel de l utilisateur 301C 47 7 10 Honeywell Programmation du syst me Menu v nement La partie inf rieure droite de l cran contient l op rande qui d fini quel statut d clenchera un v nement Les options disponibles dans ce champ sont OFF Utilis pour le statut des entr es binaires ex utilis avec le 301ADI ON Utilis pour le statut des entr es binaires ex utilis avec le 301ADI Faute Base le d clenchement sur un alarme d entretien de commu nication ou de faute d unit Alrm A Si le dispositif ou le groupe choisi prouve une Alarme A ou Alarme 1 un v nement sera d clench Alrm B Si le dispositif ou le groupe choisi prouve une Alarme B ou Alarme 2 un v nement sera d clench Alrm C Si le dispositif ou le groupe choisi prouve une Alarme C un v nement sera d clench L cran P riode couverte permet de d finir la p riode couverte par l v nement Ce champ offre deux options suppl mentaires Champ de d finition de jour permet de s lectionner soit
102. l Mode vaa iaa tn ni ceed 69 Single TX Mode sais Snagit ei GU ne ES ested id 69 Debug Mode viccot aire drid 69 Simulation Mode ads 70 Bachet Menu da 72 Changing BACNet values cooococcnoccccnonccconaccnonacanonncnanananinncnnan 75 Wireless Network Menu oooocccccccccccncnnnonanonnncncnnnnccnonnnnnnnnnnnoncccnnnnnncnnns 77 Parameters Menu uc ada ete ike iria 78 Changing PAN ID or RF Channel sesers 80 Diagnostics Menu ad ved aie rennes trie et 82 Nodes Menu cer Sen atesipcettcttetaeristedisseneuttedeses sated area ties net nn este 83 New Node Men s oretan aae lt ida ay eve 87 Hibernate Men cuicos 88 Reset Network Menu ccccccscceeeeeeceeeeeeeeeeeneeeeeeeceneeeeeesenaeeeeeessneeeees 88 Status Log Menu 552 ceases nds eit tae iento 89 Consolidate Route Menu cccescceeeeeeeeeeeeeesseeeeseneeessneeessaeeesseeessaeees 89 BACneUIP MODULE srair eRe a a AEE S EAE SAN einen di 91 Specifications uta tai citada 91 BACnet Objects iria ha aii aun ea eee 91 Analog NP Men nn heed Lente MR hash artes 92 viii 301C User Manual M 510324 Honeywell 7 10 Analog VUE droit tati 92 Binary Input females 92 Binary Output sita a Ari Mes 93 Binary VAMO Ai aia 93 DOVICO iia 93 Object Names rr 94 Protocol Implementation Conformance Statement 99 BACnet Protocol Implementation Conformance Statement 2 99 Specifications csi nin ne eine dt ieee ace ese 105 LIMITED WAR
103. le ne connait pas l tat actuel de la composante de r seau Il est possible d arr ter ce mode en tout temps depuis le menu Tests voir Mode Normal Si l un de ces modes est activ mais qu il n y a aucune activit le syst me retourne son op ration normal apr s douze heures d inactivit de clavier Auncune information n est perdue 72 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu BACNet Menu BACNet Le menu BACNet offre plusieurs crans d options permettant de configurer la connexion IP de BACNet l information du serveur et l information du fuseau horaire lt MENU D 9 BACNet 10 Reseau sans fil y 9 BACNet Appareil DBACnet ID 1 4 9 BACNet DHCP desactive DActive DHCP y 4 9 BACNet Static IP Address D192 168 1 254 4 9 BACNet gt Static Netmask D255 255 255 0 4 9 BACNet gt Static Gateway D192 168 1 1 y 4 9 BACNet Serveur SNTP SNTP Client FO D 10 4 1 12 DServeur SNTP ty Requete SNTP Omin y 4 9 BACNet gt Fuseau horair P Fuseau 0 00 HA INACT 9 BACNet Nom Appareil Dedition 20car max VA301C 1 vy 4 lt 9 BACNet gt ForeignDevReg des P Active FDR TTL 43200 sec y 4 lt 9 BACNet BBMD Info PIP 192 168 1 100 Port OxBACO
104. liste de type de sonde s applique aux adresses 1 96 et ne d pend pas de la s lection de type de produit Les dispositifs dans la plage d adresses de 97 170 affichent un identificateur BACNet Un type de produit suppl mentaire intitul Groupe repr sente les groupes cr s dans le menu Groupe de la centrale Lors du d roulement dans la liste de types de produits disponible ce type appara tra pour chaque groupe cr Groupe 1 Groupe 2 Groupe 3 etc Si le type de produit s lectionn est un groupe les types de sondes disponibles seront uniquement MIN MAX et MOY M 510324 7 10 Manuel de l utilisateur 301C 29 Honeywell Programmation du syst me Menu INFO Tx COM Cet cran affiche le protocole de communication de la composante s lectionn e pour les adresses de 1 a 96 Le protocole de chaque transmetteur est d fini par la centrale voir la section Auto configuration du r seau 9600 bauds Si un transmetteur est compatible avec plusieurs protocoles il est possible de s lectionner un autre protocole parmi les options suivantes e Vulbus Mdbs ASCII 7D 2S NP 9600 bauds Mdbs RTU 8D 2S NP 9600 bauds Mdbs RTU 8D 1S NP 9600 bauds e Mdbs RTU 8D 1S OP 9600 bauds Lorsqu un transmetteur est configur avec le protocole de communication Modbus le transmetteur envoi automatiquement les param tres de programmation la centrale Note Les param tres de transmetteurs Vulbus doivent
105. ll through the list of product types and press Enter when the desired product or sensor appears 26 301C User Manual M 510324 Honeywell 7 10 System Programming Tx Info Menu Product and Sensor Types This is a list of all the preprogrammed product types available from the Identification option in the Tx Info menu 1 Tx Info 121 Ident gt 301W CO2 IR The order of the products below is not necessarily the order in which they will appear in the controller Product Types Addresses 1 96 VA301D2 VA301AP XNX 90DM3R VASQN8X XCD VA3011 RF VA301EM VA201R IRT100 VA301EMRP VA201T EC F9 GsPnt2 90DM2 VA201T2 S301RLC VA201D VA301T Std Device VA301D GsPnt VA901T NotVul RgRt3 Product Types Addresses 97 120 Addresses 121 170 301ADI 301W 301RW 301RPT E3Point and 420MDBS are examples of standard devices Note When Group is selected as a product type the remaining Tx INFO screens are not accessible because each product in the group has already been individually programmed Only the Ident and Erase current Tx screens will be available 301C User Manual 27 Honeywell M 510324 7 10 System Programming Tx Info Menu The sensor type list applies to address ranges 1 96 and is not dependent on the type of product selected Devices in the address range from 97 170 will display a BACNet object identifier rather than a sensor type An additional Product Type simply called Group
106. logique sont Object_Identifier Object_ Name Object_Type Status_Flags Event_State Reliability Present_Value Out_of_Service et Units 96 Manuel d utilisateur 301C M 510324 Honeywell 7 10 Objets BACNet Entr e binaire Le type d objet Entr e binaire d finit un objet normalis dont les propri t s repr sentent des caract res externes visibles d une entr e binaire Une entr e binaire est un appareil ou un mat riel physique qui peut tre seulement en un de deux tats possibles tels les entr es num riques du VA301ADI Les propri t s support s pour un objet entr e binaire sont Object_Identifier Object _ Name Object_ Type Status_Flags Event_State Reliability Present_ Value Polarity Inactive_Text Out_of_Service et Active_Text Sortie binaire Le type d objet Sortie binaire d finit un objet normalis dont les propri t s repr sentent des caract res externes visibles d une sortie binaire Une sortie binaire est un appareil ou un mat riel physique qui peut tre seulement en un de deux tats possibles tels les relais ou les puissances de sorties commutables Les propri t s support s pour un objet entr e binaire sont Object_Identifier Object _ Name Object_ Type Status_Flags Event_State Reliability Present_Value Polarity Inactive_Text Active_Text Priority_Array Out_of_Service et Relinquish_Default Valeur binaire Le type d objet Valeur binaire d finit un objet normalis dont les
107. mmeil profond hors tension pour pouvoir effectuer des r parations pour effectuer des r parations pour remplacer ou pour enlever le noeud Cette option force le noeud d emprunter le meilleur chemin vers la centrale en utilisant un parent alternatif Cette option est seulement disponible lorsqu il y a un module de relais dans le r seau Permet de pr ciser la configuration de relais s curis pour une module de relais sans fil Les options 1 29 sont aux fins d information seulement et ne sont pas modifiables Les options 16 21 sont affich es seulement si le noeud s lectionn a un deuxi me parent un parent est un noeud auquel un autre noeud peut se connecter pour cr er un lien la centrale Les options 22 27 sont seulement affich es si le noeud a un troisi me parent 88 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu reseau sans fil Les options 31 33 permettent de mettre le d tecteur en mode hibernation hors tension pour effectuer des r parations pour remplacer ou pour enlever le noeud Hiberner Met le noeud en hibernation hors tension Ce mode est utilis aux fins d entretien ou de remplacement de pile Remplacer Permet de remplacer un noeud sans changer l adresse MAC ni l identificateur permet un noeud libre avec une adress MAC diff rente ou identique de se mapper a l identificateur du noeud actuel Enlever Enl ve le noeud du r
108. muniquer avec et de g rer les d tecteurs de gaz sans fil jusqu 60 tout en conservant toutes ses fonctionnalit s pr c dentes Utilisation Le 301C est une centrale cr e pour monitorer la totalit d un r seau de d tection de gaz vingt quatre heures sur vingt quatre La centrale offre la possibilit d enregistrement de donn es de cr ation de fichiers journal pour toutes les concentrations et alarmes de transmetteurs aux fins d analyse Ces unit s sont galement munies de fonctions de groupes et de zones qui vous permettent d interroger et de monitorer certains groupes ou certaines zones de transmetteurs R ception et v rification Lorsque vous recevez votre commande e V rifiez le colis pour assurer qu il n y a aucun dommage e Ouvrez le colis avec soin e Trouvez le bordereau de marchandise ou le bon de commande et v rifiez que tout les articles apparaissant sur la liste sont bien dans le colis et ne sont pas endommag s Note Si le colis ou la marchandise est endommag veuillez vous r f rer la section Garantie la fin de ce guide M 510324 Manuel de l utilisateur 301C 11 7 10 Honeywell Introduction Instructions d installation Instructions d installation Directives de base Suivre les instructions minutieusement pour assurer le bon fonctionnement de l quippement d faut de respecter les directives Honeywell Analytics sera lib r de toute responsabilit Installer le
109. neywell 7 10 Programmation du syst me Menu v nement La partie inf rieure gauche de l cran contient le quantificateur de logique ou l op rateur qui d termine comment les conditions sont calcul es Les options disponibles dans ce champs sont ae Description Aucun op rateur gal lt gal ou inf rieur lt Plus petit que gt gal ou sup rieur gt Plus grand que Pas gal Lorsque la valeur maximum est atteinte une action est max min d clench e Laction ne sera pas d sactiver sans que les niveaux baissent en dessous de la valeur minimum Lorsque que les concentrations descendent plus bas que la valeur minimum une action est d clench e L action ne sera pas d sactiv sans que les niveaux remontent au dessus de la valeur maximum pr cis e La partie sup rieure droite de l cran contient la source ce qui d fini sur quel unit ou groupe d unit s l v nement sera bas Les options disponibles dans ce champs sont GrTous Inclus tous les transmetteurs voir note Gr000 Inclus seulement les unit s dans le groupe pr cis voir note Tx000 Inclus seulement le transmetteur pr cis connecte a la centrale Heure Inclus seulement les informations recueillies dans la plage horaire pr cis e La s lection de l horloge configure une con dition applicable seulement entre l heure de d but et l heure de fin Il est possible de configurer un cran de cond
110. nno 21 Operation du syst me c ocooccccinoccconocccnoncconanoconano nana n canon rana n cn canr cnc 21 PROGRAMMATION DU SYST ME rene 22 eMenu INFO TX coooccccnccnnnnncccncnononanacanonononaccnnnnnonnnancnnnnnnnanccnncnnnananinnns 26 Menu dentaria ion 27 Types de produit et types de sondes cccocccccoccccnoncccnoncnnnananonancnnnannnnnnos 28 OOM e ee e A 30 LANES E 31 D tection ener a A i id 32 Affichage diem nn eme le tr di O 33 Alarme Bet une en ni mere nur Ne A ex 34 Entretien et Exploitation des Menus ocoooocccononcccnoncnnnancnonananonnnonanannnnnnns 35 Code d Etat anaa e 36 Effacer TX COUrant miii 36 M 510324 Manuel de lutilisateur 301C vii 7 10 Honeywell Note Menu groupes is 38 Cr er des groupes iii 39 Supprimer des groupes c cccoccccocccnccconcnnnnncnncnnnn non nannnn conca nan n cnn na rra ranc cnn 39 MENU v nement coccccccncncnccnnnononononononononananananananonnnnnnnnnananononononcnnnnnos 40 ACM a las as Nues 42 Dela BE Or a Pe Tea 43 D lais mode latch winnie 44 GONGILIONS asini ario 45 Salta ita 49 A Meni aCQUISITION ieee darrere E EE E E E A ET 50 D buter et arr ter log even ooo eeeceeeeeeeseeeseeteseeseeeeeaeeeaeeteaeeeaeeesaeeeaeetaes 52 Note Menu copie cee 53 COMPQUPATION AEA ETETE ten nr nat ele 53 Parametr s 2 88 unir E a E tar Pet dial ent nr eo 54 JOUFMAl SVS ER LE LES A Ain rent hel AA FRERES RSS cesses PENSER APRES RSR RES 55 MENU CONO nn ln L nat e
111. ns interruption de services Toute modification est valid e et effectu e lors du retour l cran principale Mode Tx unique Ce mode permet d effectuer l analyse de transmetteurs un la fois La centrale interroge seulement le transmetteur pr cis ce qui met jour seulement les donn es de ce transmetteur Ce mode n entrave pas les fonctions d valuation d v nements Mode d bogage Ce mode permet d valuer et d effectuer des essais complets d op ration de syst me sans affecter les op rations hors le mode d bogage Les v nements sont valu s et affich s si n cessaire mais aucune action n est activ e M 510324 Manuel de l utilisateur 301C 71 7 10 Honeywell Programmation du syst me Menu Tests Mode Simulation Ce mode d sactive les mises a jour d information de communication de r seau Ce mode peut tre employ peu importe quel est le mode d op ration actuel du syst me exemple l emploi du mode Silumlation simultan ment avec le mode D bogage permet d valuer le syst me au complet groupes v nements etc sans d clencher des actions ou sans utilisation de mat riel suppl mentaire II permet de simuler des concentrations de gaz sur une plage associ e chaque transmetteur en s quence Les niveaux d alarme A B et C sont valu s selon la concentration de gaz et les v nements sont valu s et les actions sont d clench es Penrant la simulation la centra
112. nu INFO Tx D tection Le menu D tection disponible uniquement pour les adresses de 1 96 affiche la plage de d tection plage O 0 00 ainsi que l unit de mesure unit pour le transmetteur s lectionn La plage de d tection est entre O et la valeur maximale 0 00 et l unit de mesure est soit ppm ou pourcent Si le transmetteur utilise le protocole Modbus les param tres de d tection sont d finis de fa on automatique lors de la configuration du r seau et ne peuvent tre modifi s Les protocoles Vulbus doivent tre d finis par une programmeur Le menu de d tection n est pas disponible pour les appareils 301R ou 301AP 1 InfoTx 001 gt Detection D plage 0 0 00 unite Programmer ou modifier la plage ou l unit de d tection e Utiliser les fl ches pour d placer le curseur l option plage ou unit e Appuyer sur Enter et utiliser les fl ches haut et bas pour augmenter ou diminuer la valeur e Appuyer sur Enter pour valider la valeur d sire 32 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu INFO Tx Affichage Cette option permet de donner une tiquette ou un nom la composante s lectionn e transmetteur relais et annonciateurs L tiquette peut contenir jusqu 20 caract res incluant les espaces ex CHAMBRE GICLEURS Les tiquettes de transmetteurs Modbus sont assign s par d faut et sont compos s du nom de la
113. o digits of a hexadecimal ID example 79 and controller reference number 121 for the specific transmitter Line 2 displays the device s MAC address Line 3 displays the type of product VA301W The screen can display only three items at one time so the up or down arrows must be used to scroll through the list M 510324 301C User Manual 83 7 10 Honeywell System Programming Wireless Network Menu The following table provides the list of data displayed for each node Use the right or left keypad arrows to navigate the possible nodes then use the up or down keypad arrows to navigate the entire list of data for the selected node Title Value Description 4 Link Quality 1 Percentage of signal strength 0 100 for a node relative to parent signal quality 5 Log Mod Log Indicates whether the node is in debug mode 6 Net Addr 0009 Displays the node s hexadecimal network address seen in 1st screen 7 SWU slot 1 Displays the SWU slot used to transmit beacon 8 of Parents 1 Displays the number of current parents for a given node from 0 3 9 DP Id 0 Displays the ID associated to the default parent 10 DPNetAddr 0 Displays the default parent network address 11 DPLQI 2 Displays the link quality with the default parent 0 no useful link 1 weak link 2 strong link 12 DP Retries Displays the number of default parent retries 13 DP BM 0 Displays the number of parent beacons missed over last beac
114. o increase or decrease the value one digit at a time starting with the first digit When all the digits of the password are correct press Enter to access the programming functions The first MENU options screen appears Use the keypad arrows to navigate through multiple screens to the desired function and press Enter to access it MENU gt D 1 Tx Info 3 Events 2 Groups 4 Aqui lt MENU gt 5 Copy 7 Network 6 Config 8 Tests MENU gt 9 BACNet 10 Wireless 24 301C User Manual M 510324 Honeywell 7 10 Tx Info Menu Tx Info is the menu option that is dedicated to transmitter information and contains several sub menu options The exact list of screens will vary depending on the transmitter type A summary is presented below with details on the following pages System Programming Tx Info Menu Ident Allows the network components lt ZE identification information to be COMB a viewed COM Allows the communication ng Pe ee ne protocol to be viewed or changed Ydbs RTU 8D 28 NP lt 1 Tx INFO 001 Detection Scale 0 1 00 A A Units Detection Allows the detection range and Bra or Scale 1 the unit of measurement i SEE TENPOUOOL and parameters to be viewed and Here bo Scale 2 changed ER baa 1 Tx INFO 001 Scale 2 Factor 00010 Units Display Allows the label or name of a e s specific component to be E Se chard mar changed lt 1 Tx INFO Alarm A Alarms Allo
115. o more in fault 2004 01 23 19 05 48 Tx 8 communication no more in fault The first column of the Event log displays the date yyyy mm dd and time hh mm ss of the log Column A displays the date and time of the log In this example the event s Delay mode was set to one minute intervals The system logs the following types of events e Event Log e Event status changed e Alarm A B C Fault and X status changed Note New log files are created when the existing files reach 32 000 lines or at the start of a new week 0h00 Sunday 52 301C User Manual M 510324 Honeywell 7 10 System Programming Copy Menu Copy Menu The Copy menu allows programmed parameters to be copied and transferred Data from the SD card can be transferred to a controller or from a controller to the SD card or copy parameters from one device to the next The Copy option offers three screens Configuration Parameters and System Log Configuration If the controller is equipped with an SD card the configuration function allows data to be transferred either from the 301C to the SD card or the reverse This makes it possible to transfer the controllers programming to a computer or from a computer to the controller 5 Copy Configuration Config to SDcard SDcard to Config The first option in the configuration screen is 301C to SDcard Selecting this option copies the controller s configuration and parameters into a config ini file
116. odes d affichage Defilement manuel Defilement 3 sec Defilement 5 sec Ces r glages contr lent la pr sence et la fr quence d affichage des donn es l cran de la centrale Le mode de d filement manuel signifie que l utilisateur doit appuyer sur les fl ches pour visionner le statut de chaque unit connect e la centrale Les mode de d filement 3 secondes et 5 secondes effectuent le d roulement automatique des donn es en fr quence de changement d cran de soit 3 ou 5 secondes 6 Config Defilement manuel Regle Date et heure English menu Note Il est toujours possible de d rouler dans les crans d affichage en appuyant sur les fl ches peut importe le mode s lectionn La deuxi me ligne permet d ajuster la date et l heure depuis un nouvel cran Date et heure Lorsqu un chiffre clignote il est en mode dition Utiliser les fl ches pour d rouler la valeur d sir e Il est possible de modifier l ann e le mois le jour et l heure les minutes et les secondes La centrale ne g re pas les changement d heure telle l heure avanc e Tout changement d heure doit tre effectu manuellement Date et heure gt 2005 11 21 11 47 36 norme ISO 8601 La troisi me ligne du premier cran Config permet de changer le langage d affichage Si le menu est en anglais l cran indiquera Menu frangais et vice versa D placer le curseur a la gauche du champ et appuyer sur Enter pour changer le lang
117. of status updates that can be missed before a leave indication is triggered 30 Version A14 Node device firmware version 31 Hibernate Selecting these options displays a 32 Replace confirmation screen If confirmed the 33 Remove selected function will be executed see descriptions below 34 Consolidate Route Enabling this option forces the node to take the best route to the controller using an alternate parent 35 Failsafe ON This option is only available only when there is a relay module in the network It allows users to specify relay failsafe settings for a wireless relay module M 510324 301C User Manual 85 7 10 Honeywell System Programming Wireless Network Menu Options 1 through 29 are for information purposes only and cannot be modified Options 16 through 21 are only displayed if the selected node has a second parent a parent is any other node to which a node may connect to create a link to the controller Option 22 through 27 are only displayed if the node has a third parent Options 31 through 33 allow the Hibernate Replace or Remove nodes to be selected Hibernate Places the node in hibernation power down This mode is used for maintenance or to change the battery Replace Allows a node to be replaced by another without changing the MAC address or node ID enables a free node with a different or same MAC address to be mapped to the current node ID Remove Removes the node from the network
118. on period 14 DPLC 256 Displays the time since lasct communication to default parent in milliseconds 15 AP1ID Displays the ID associated to the alternative parent 1 16 AP1NetAddr Displays the alternative parent 1 network address 17 AP1LQI 16 Displays the link quality with alternative parent 1 0 no useful link 1 weak link 2 strong link 84 301C User Manual M 510324 Honeywell 7 10 System Programming Wireless Network Menu Title Value Description 18 AP1 Retries 128 Displays the number of alternative parent 1 retries 19 AP1 BM Displays the number of alternative parent 1 beacons missed over last beacon period 20 AP1LC 27132 Displays the time since last communication 032 to alternative parent 1 in milliseconds 21 AP2ID 2 Displays the ID associated to alternative parent 2 22 AP2NetAddr 31756 Displays the alternative parent 2 network address 23 AP2LQI 198 Displays the link quality with alternative parent 2 0 no useful link 1 weak link 2 strong link 24 AP2 Retries 190 Displays the number of alternative parent 2 retries 25 AP2BM 0 Displays the number of alternative parent 2 beacons missed over last beacon period 26 AP2LC 56320 Displays the time since last communication to alternative parent 2 in milliseconds 27 LSU 661 Displays the time at which the system was last updated 28 Status Alive Displays whether the node is activated or off 29 Freshness 2 Displays the number
119. ontroller The wiring includes power communication BACNet and relays each with an assigned position and number on the board J22 Power Input Connect the power supply to the controller see Wiring Details for cabling diagrams J23 J24 Communication inputs Connect communication cables to channels 1 through 3 Relay Outputs 1 4 Depending on the desired configuration connect the relay cables to either N O or N C SHDN jumper Place the jumper over the Shutdown header pins to reset or restart the system EOL Resistors 1 4 Place the jumper over the header pins to create the connection to attenuate communication echoes M 510324 301C User Manual 15 7 10 Honeywell Introduction Power Connections Power Connections The 301C requires a power range of 17 27 Vac 50 60 Hz 8 64 VA 18 36 Vdc 350 mA 24 Vdc 8 4 VA Polarization is not important in either AC or DC mode The system must be grounded on the transformer and a dedicated circuit breaker must be used Communication Connections Communication cables must be grounded using the shield terminal using twisted and shielded pair Belden 2 24 AWG 9841 cable or equivalent The network cabling can extend up to a limit of 2000 feet 609 m per channel The length of a T tap can reach 65 feet 20 m up to a maximum of 130 feet 40 m for all T taps All wireless devices associated to the controller will automatically be detected and communicate with the controller
120. options within this screen are Tx Info to Tx Info copies transmitter parameters from one device to another Event to Event copies parameters from Event to Event The process is identical for both options e Select source the data to be copied using the up down keypad arrows and press Enter e When the transmitter address is flashing use the up down keypad buttons to search for the desired device address e Press Enter to select the new address e Select the target address where the data is to be copied to in exactly the same way as source e Select COPY and press Enter The parameters have been copied TxInfo to TxInfo source tx001 target tx113 COPY Event to Event p source 001 target 013 COPY 54 301C User Manual M 510324 Honeywell 7 10 System Programming Configuration System Log Menu The controller will record log information to its internal memory If the controller is equipped with an SD card the system log function allows users to save system log information to the memory card in text format 5 Copy System Log SysLog to SDcard When this option is selected a log of all the last actions performed on the controller is copied to the SDcard with the filename slyymmdd log This file can contain up to a maximum of 64Kb of information in text format Once the memory card is full the oldest log entries are erased and replaced by new entries Here is an example of a system log
121. ordonnateur de r seau sans fil xT module de communication sans fil est pr sent mais que la communication avec la centrale est en faute 24 Manuel de l utilisateur 301C M 510324 Honeywell 8 10 Programmation du syst me Operation du syst me Puisque les fonctions de programmation de la centrale sont prot g es par mot de passe il est n cessaire d acc der l cran de mot de passe e Appuyer sur Enter pour afficher l cran Mot de passe e Utiliser les fl ches haut ou bas pour augmenter ou diminuer la valeur du premier chiffre e Utiliser la fl che de droite pour passer au prochain chiffre e Lorsque tous les chiffres sont exactes appuyer sur Enter pour valider le mot de passe et acc der aux fonctions de programmation Mot de passe Le premier des crans MENU appara t Utiliser les fl ches pour naviguer les divers crans Lorsque la fonction d sir e est affich e d placer le curseur petite fl che l cran a gauche de l option puis appuyer sur Enter pour y acc der MENU gt 1 InfoTx 3 Evene 2 Groupes 4 Acqui MENU gt 5 Copie 7 Reseau 6 Config 8 Tests MENU gt 9 BACNet 10 Reseau sans fil M 510324 Manuel de Putilisateur 301C 25 7 10 Honeywell Programmation du syst me Menu INFO Tx Menu INFO Tx INFO Tx est l option de menu d di e aux informations de transmetteurs et contient plusieurs autres options qui peuvent varier selon l adresse ou le
122. ore et des DEL Les six prochains crans demande la pression sur les touches gauche droite haut bas Silence Enter et ESC Le syst me avance seulement lors de la pression sur une touche Sequence de test Presser gauche ESC pour quitter Le syst me essaye ensuite l cran d affichage un cran en blanc est affich Appuyer n importe quelle touche pour proc der l cran suivant M 510324 Manuel de l utilisateur 301C 69 7 10 Honeywell Programmation du syst me Menu Tests Sequence de test Test affichage Pressez une touche ESC pour quitter Le dernier test est l essais de communication de r seau Sequence de test Test comm reseau 9600 bauds Channel 1 SUCCES Assit t ces essais commenc s il n est pas possible de les interrompre ou de les arr ter Le systeme essaye chacun des cing bauds vitesse de communication 9600 19200 38400 57600 115200 et chacun des quatre canaux par baud Aussit t les essais termin s le syst me affiche l cran de sortie du mode S quence de test Appuyer sur n importe quelle touche pour revenir l cran principale du menu Tests Sequence de test Test termine Pressez une touche 70 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu Tests Mode Normal Ceci est le mode d op ration normal par d faut du syst me Lorsque le syst me est en mode normal certaines valeurs peuvent tre modifi es sa
123. ortie 1 ne peut tre cr dynamiquement Analog analogique avec le service CreateObject Output Valeur 2 ne peut tre supprimer Analog analogique dynamiquement avec le service Value DeleteObject Entr e binaire 3 eee ques PIOPH ISS Binary Input inscriptibles n existent Der cd Sr re Binary rtie binair 4 ne propri t Sortie binaire aucune propri t propri taire existe Output Valeur binaire 5 aucune restriction de plage Binary Value Dispositif Device 108 Manuel de Putilisateur 301C M 510324 Honeywell 7 10 nonc de conformit d impl mentation de protocole Options Couche liaison de donn es Data Link Layer M BACnet IP Annex J O BACnet IP Annex J Foreign Device O ISO 8802 3 Ethernet Clause 7 O ANSI ATA 878 1 2 5 Mb ARCNET Clause 8 O ANSI ATA 878 1 RS 485 ARCNET Clause 8 baud rate s O MS TP master Clause 9 baud rate s O MS TP slave Clause 9 baud rate s O Point To Point EIA 232 Clause 10 baud rate s O Point To Point modem Clause 10 baud rate s O LonTalk Clause 11 medium O Other Association d adresse de dispositif L association de dispositif statique est support En ce moment ceci est n cessaire pour la communication bidirectionnelle avec les esclaves MS TP et certains autres dispositifs DYesM No Options de r seautage O Router BACnet Modbus O Annex H BACnet Tunneling Router over IP O BACnet IP Broadcast Management Device BBMD
124. propri t s repr sentent des caract res externes visibles d une valeur binaire Une valeur analogique est un param tre de syst me de contr le dans la m moire du dispositif BACNet Les propri t s support s pour un objet entr e binaire sont Object_Identifier Object _ Name Object_ Type Status_Flags Event_State Reliability Present_Value Inactive_ Text Active_ Text Priority_Array Out_of_Service et Relinquish_Default M 510324 Manuel d utilisateur 301C 97 7 10 Honeywell Objets BACNet Dispositif Le type d objet Dispositif d finit un objet normalis dont les propri t s repr sentent des caract res externes visibles d un dispositif BACNet II y a seulement un objet Dispositif pour repr senter le module BACNet Les propri t s support s pour un objet dispositif sont Object_Identifier Object Name Object_ Type System_Status Vendor_Name Vendor_Identifier Model_Name Firmware _Revision Application_Software_Version Protocol_Version Protocol_ Revision Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Max_APDU_Length_Accepted Segmentation_Supported APDU_Timeout Number_Of_APDU_Retries Device_Address_Binding Database_Revision Local_Time Local_Date UTC_Offset and Daylight_Savings_Status Produits Vulcain et objets BACnet Nom d objets Les noms d objets sont compos s en deux parties ainsi La premi re partie est compos e du label d affichage nom du produit du dispos
125. que une situation potentiellement dangereuse qui peut entra ner des blessures majeures ou la mort si pas vit AVERTISSEMENT Un symbole sur l quipement qui r f re l utilisateur la documentation pour de plus amples informations Ce symbole appara t c t des informations n cessaires dans le manuel M 510324 Manuel de l utilisateur 301C 7 10 Honeywell INTRODUCTION susrscicinianadsaniadas tr 11 UtiliSation oa a il dire 11 R ception et v rification ooooconncccnncccnnncccnnccncnnncncnnrncananonnnnnn nn rnnncannn 11 Note Instructions d installation eo0eannnnooennnnnsnennnnensnnnnrnrssenrnreenn 12 Directiv s de base tual iiada 12 Installation murale 13 D TAILS DE CONNEXION serarererereeneeneerenrse 14 Connexions d alimentation iii 16 Connexions de communication iii 16 Note Param tres d metteurs sp cifiques 16 Note Sortie relais a a Ta a e A Oa TAR 17 Note Instructions pour cavaliers ooonooocccnnnncocccocnnoccccnnnoncnaccnnnnnancnnnnns 18 D MARRAGE aaa 19 Premier d marrage nn cnn eaa aai 19 Note Enregistrement de donn es sdcard eseese 19 elnterface de programmation ooccccccnnccccccononnncncnonancnnnnnanencnncnanncnnncnanos 20 eFonctions du Clavier a e a a ae E 20 Definitions des DEL oo onnnnnnnccccnnccccnnncccnnnancnonancnnnancno nana n canaria nnnacan
126. r puis changer le num ro e Appuyer sur Enter pour valider cr er e Utiliser les fl ches pour placer le curseur sur une ligne de groupe et appuyer sur Enter Le champ est en mode dition lorsque le lt fin gt clignote e Uitliser les fl ches haut et bas pour d rouler dans la liste d unit s connect es la centrale jusqu l obtention de l adresse appropri e Appuyer sur Enter pour valider l adresse e L adresse est ajouter au groupe et le curseur est d plac vers la droite R p ter le processus pour ajouter tous les transmetteurs d sir s jusqu 126 par groupe L adresse de chaque transmetteur configur dans le menu InfoTx est disponible pour cr er des groupes Note Les groupes cr s dans ce menu apparaitront dans la liste de types de produits menu INFO Tx option Ident et seront identifi s Groupe xx xx est le num ro assign au groupe lors de la cr ation Supprimer des groupes La commande vider les groupes permet de supprimer tous les groupes configur s dans la centrale Pour supprimer des groupes individuellement e Afficher le premier transmetteur du groupe e S lectionner le transmetteur l adresse clignote et utiliser les fl ches pour d rouler les options et s lectionner lt del gt l option lt del gt supprime l entr e et l option lt fin gt indique la fin du bloc Appuyer sur Enter et le groupe est vid Cette proc dure permet de supprimer un plusieurs ou to
127. rd Object Types Supported Analog Input For all objects 1 cannot be dynamically createable using Create Object service 2 cannot be dynamically deletable using DeleteObject sercice Binary Input 3 No additionnal writable properties exist Binary Output 4 No proprietary properties exist Binary Value 5 No range restriction Device Analog Output Analog Value Data Link Layer Options M BACnet IP Annex J O BACnet IP Annex J Foreign Device O ISO 8802 3 Ethernet Clause 7 O ANSI ATA 878 1 2 5 Mb ARCNET Clause 8 O ANSI ATA 878 1 RS 485 ARCNET Clause 8 baud rate s O MS TP master Clause 9 baud rate s 102 301C User Manual M 510324 Honeywell 7 10 Protocol Implementation Conformance Statement O MS TP slave Clause 9 baud rate s O Point To Point EIA 232 Clause 10 baud rate s O Point To Point modem Clause 10 baud rate s O LonTalk Clause 11 medium O Other Device Address Binding Is static device binding supported This is currently necessary for two way communication with MS TP slaves and certain other devices Yes M No Networking Options O Router BACnet Modbus O Annex H BACnet Tunneling Router over IP O BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices O Yes M No Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously M A
128. red 108 301C User Manual M 510324 Honeywell 7 10 Limited Warranty Disclaimer of Unstated Warranties The warranty printed above is the only warranty applicable to this purchase All other warranties express or implied including but not limited to the implied warranties of merchantability or fitness for a particular purpose are hereby disclaimed Limitation of Liability It is understood and agreed that Honeywell Analytics liability whether in contract in tort under any warranty in negligence or otherwise shall not exceed the amount of the purchase price paid by the purchaser for the product and under no circumstances shall Honeywell Analytics be liable for special indirect or consequential damages The price stated for the product is a consideration limiting Honeywell Analytics liability No action regardless of form arising out of the transactions under this warranty may be brought by the purchaser more than one year after the cause of actions has occurred M 510324 301C User Manual 109 7 10 Honeywell Centrale 301C Manuel de l utilisateur M 510324 7 10 Avis et marques de commerce Tous droits r serv s par Honeywell International Inc Juillet 2010 Quoique cette information est pr sent e en bonne foi et est pr sum e exacte Honeywell d cline la garantie tacite de la qualit marchande pour un emploi particulier et offre aucune garantie expr s l exception des conventions crites avec et po
129. registre d v nement 2006 01 23 17 54 25 Log evenement active 2006 01 23 17 55 25 Arr t syst me 2006 01 23 19 05 47 Sequence de simulation active 2006 01 23 19 05 48 Tx 6 communication n est plus en faute 2006 01 23 19 05 48 Tx 8 communication n est plus en faute La premi re colonne du registre indique la date aaaa mm jj et l heure hh mm ss de l enregistrement L exemple ci haut d montre des intervalles de d lais d une minute Le syst me enregistre ces types d v nements e Journal v nement e Changement de statut d v nement e Changement de statut pour alarmes A B C faute Note De nouveaux fichiers log seront cr s lorsque le fichier actuel atteint 32 000 lignes ou le dimanche Oh 52 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu copie Menu copie L option Copie du menu Info TX permet de copier ou de transf rer les param tres programm s ll est possible de transf rer des donn es d une carte SD de la centrale un ordinateur et vice versa ou de copier des param tres d un transmetteur un autre L option Copie offre trois crans Configuration Param tres et Journal Sys Configuration Si la centrale est munie d une carte m moire la fonction Configuration permet de transf rer les donn es soit du 301C la carte SD ou vice versa Ceci permet de transf rer la programmation de la centrale sur un ordinateur ou d un ordinate
130. resse Modbus de l unit talonner 007 et le type d unit talonner 301D2 Ligne 2 Indique le statut Normale ou En Etalon de l unit s lectionn e Ligne 3 Affiche la fonction effectuer Etal Zero Ligne 4 Affiche la fonction effectuer Etal Plage et la valeur de concentration de gaz d talonnage 246 ppm 64 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu R seau 1 D placer le curseur la gauche de l adresse de l unit sur la premi re ligne et appuyer sur Enter Etalon 001 301D2 Statut Normal Etal Zero Etal plage 246 2 D rouler la liste pour afficher l adresse de l unit d sir e puis appuyer sur Enter pour s lectionner 3 La deuxi me ligne affiche le statut de l unit 4 D placer le curseur la gauche de la fonction d sir e Etal Zero pour talonner le z ro de l unit et appuyer sur Enter pour s lectionner 5 Lors de la s lection d Etal Zero la centrale demande la confirmation Calib 001 301D2 Etalonner Zero Etal Zero Etal plage 246 L unit doit tre configur e dans la base de donn e du 301C pour figurer dans la liste d adresses d unit s affich e l cran M 510324 Manuel de l utilisateur 301C 65 7 10 Honeywell Programmation du syst me Menu R seau 6 Appuyer sur Enter pour confirmer ou Esc pour annuler Si confirm la centrale proc de l talonnage du z ro de l unit Le processu
131. rmettant de simuler une concentration de gaz sur la plage associ e a chaque transmetteur l un apr s l autre Les concentrations simul es sont locales dans la centrale Les v nements seront activ s pour la simulation mais les unit s de d tection ne sont pas affect es Charge maximum Active toutes les composantes de la centrale L option au deuxi me cran Mode fct permet de s lectionner le mode de fonctionnement soit Normal Tx unique or debogage 8 Tests D Mode fct normal Normal Mode d op ration normal de la centrale Tx unique Active le mode d interrogation d un seul transmetteur Debogage Active le mode de service permettant d effectuer l talonnage et de tester les v nements sans d clencher des actions 68 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu Tests Sequence de test Lors de la s lection de cette option la centrale affiche l cran de S quence de test Appuyer sur ESC n importe quelle tape pour revenir l cran principale du menu Tests Sequence de test Relais actives Appuyez une touche ESC pour quittter Appuyer sur n importe quelle touche pour proc der aux tests du syst me Sequence de test Alarme sonore Appuyez une touche Cette fonction comprend treize crans de test pour chaque composante de la centrale Les trois premiers crans effectuent l essais des relais de l alarme son
132. rouler dans la liste de configurations disponibles e Appuyer sur Enter pour valider le nouveau param tre et quitter le mode dition Naviguer dans les crans du menu Config avec les fl ches gauche pr c dent et droite suivant M 510324 Manuel de l utilisateur 301C 59 7 10 Honeywell Programmation du syst me Menu config Le troisi me cran principale permet de r gler la configuration des relais le mode d mission AP et de choisir parmi quatre fabricants pour la centrale 6 Config Configurat relais Emission AP auto Honeywell La s lection Configurat relais offre deux options suppl mentaires pour la configuration des relais La premi re option Failsafe permet d activer ou d sactiver tous les relais en appuyant sur la touche Enter Cette fonction est utilis e en cas de panne d lectricit en cas de panne le relais d clenche le dispositif connect ex une lampe pour signaler un probl me Configuration relais gt Failsafe gt Tous les relais Inactif La deuxi me option Silence permet d activer ou d sactiver l option Silence de chaque relais D placer le curseur gauche du relais et appuyer sur Enter pour basculer la valeur act ou ina Configuration relais Silence 1 2 3 4 ina act ina ina 60 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu config Le quatri me cran de configuration permet de programmer
133. s n cessite seulement quelques instant puis l cran affiche de nouveau l cran d talonnage Note Ne jamais talonner le z ro de l unit avec de l air ambiante seulement Toujours utiliser de l azote N au port d talonnage pour talonner le z ro 7 Pour effectuer l talonnage de l unit d placer le curseur la gauche de Etal Plage et changer la valeur d talonnage avec la proc dure suivante Calib 001 301D2 Statut Normal Etal Zero Etal plage D 246 a Utiliser la fl che droite pour d placer le curseur la gauche de xxx ppm champ de valeur d talonnage Appuyer sur Enter pour s lectionner le champ la valeur est ditable lorsqu elle clignote b Utiliser les fl ches haut et bas pour augmenter ou diminuer la valeur Appuyer sur Enter pour valider c D placer le curseur la gauche de la fonction Etal Plage et appuyer sur Enter pour d marrer l talonnage L talonnage de la plage d marre L cran affiche le statut de l unit En etalon jusqu la terminaison de l talonnage Lors de la s lection d Etal Plage assurer que l unit est expos e au gaz d talonnage appropri avant et pendant le processus d talonnage 66 Manuel de l utilisateur 301C M 510324 Honeywell 7 10 Programmation du syst me Menu Tests Menu Tests Le menu Tests permet d effectuer une gamme de v rifications sur les composantes et sur les communications de r seau Ce menu permet ga