Honeywell Smoke Alarm IPGSM-DPC User's Manual
Contents
1. 3 inches Transformer 1451 UL9 Primary 120VAC 60Hz 850mA Secondary 18VAC 72VA Battery 12V 7Ah sealed lead acid type not supplied Use a Honeywell 712BNP Yuasa NP7 12 or equivalent Battery Charging Current maximum 1A Supervision The Radio communicator battery and AC power conditions are monitored by the cabinet indicator LEDs RADIO TROUBLE lights when any of these conditions exist e Both IP and GSM communication paths are lost e Communicator radio is not registered e Old Alarm Time has been exceeded Message has not been delivered within the fixed 10 minute window LOW BATTERY lights when the battery voltage is less than 11 5VDC AC LOSS lights when the AC power is less than 90VAC _14 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide NOTES _15 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide NOTES _16 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide NOTES _17 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide NOTES 18 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide NOTES 19 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide NOTES 20 Wiring Diagram The wiring diagram below is depicted for point to point electrical connection checks used for troubleshootin
2. 8 a iGSM Comm oc 5 O re Module AC ON GRA our JE DRE oc 5 k ge STATUS mm Nu n rit MESSAGE Soon MIMO ONL S FAULT BATTERY PE A H b TESES cc ven FUSE 7720P Pr PROGRAMMER _ sete sona rene tona sone PORT PN 100 02415 1 jovin RSSI MODE i GND Honeywell INDICATORS Li ns ECP In MODE amp STATUS BATTERY 6 ECP Out SWITCH 7 TAMPER 7AH o8 SWITCH 9 o not supplied 10 INTERNET Use a Honeywell 712BNP CONDUIT M FET OUt CONNECTIVITY y os INDICATORS Yuasa NP7 12 or equivalent To Router CS To Fire Panel To Fire Panel IPGSM DPC 007 V1 NOTES All circuits are power limited except the backup battery which is non power limited e Non power limited wiring must be separated from the power limited wiring by at least 1 4 inch e If desired use a Honeywell 955WH Tamper Switch with the 28 2 bracket IC STATEMENT Notice This Class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme la norme NMB 003 du Canada IC STATEMENT This device complies with RSS 210 of IC Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause unde
3. as shown ON 12345 Switch handle white AC LED P INDICATOR d ACTIVE LED INDICATOR iPGSM COM 003 VO _11 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide iGSM Communications Module Information iPGSM DPC 012 VO ON NOT registered with AlarmNet OFF Registered with AlarmNet FAST BLINK Download session with Compass in progress Ca m SLOW BLINK In unison with yellow LED RUE BOWS S ABS VRE registration in progress Bees nie BATTERY 8V 5 1 AH FOR 24 Hr BACKUP FOC XXXXXXXXXX IC YYYYYYYYYY ON Message transmission pending QUICK PERIODIC BLINK Normal FAST BLINK Message waiting for network ACK RSSI Mode SLOW BLINK Idle power abnormal ig and SLOW BLINK In unison with green LED Honeywell 14 status LEDs registratration in progress HRE ya Tamper 000000 Switch Lhe Mode Switch ON No contact with network OFF Normal SLOW BLINK Loss of communication with the Dialer Capture Module ECP fault FAST BLINK No network contact AND loss of communi cation with the Dialer Capture Module Note If all LEDs FAST BLINK in unison with the RSSI LEDs this indicates a Hardware Error ON 100 MB S link to Internet Link Speed OFF 10 MB S link to Internet GREEN ON Ethernet Link detected Ethernet Link Activity OFF No link detected GREEN FAST BLINK Transmitting Receiving Data M
4. e LED Display board is fully seated e All wiring terminals and connectors are tight e All wiring has been completed and secured with cable ties Install the battery not supplied Apply power to the 1451 UL9 Wired Transformer and attach the battery cable IPGSM DPC Commercial Fire Communicator Installation and Setup Guide ANTENNA 1451 UL9 WIRED WIRES MUST BE TRANSFORMER RUN IN CONDUIT NUT TO 24 HR 155 WASHER FACILITY POWER n 120VAC 60Hz 850mA ANTENNA MOUNTING TO Cabinet Ground Post GND ADAPTER i TO PowerBoost1 Ft H DO NOT REMOVE these knockouts Ae CABINET DOOR w O g x 5 D Fa l a amp i O 2 s g 2 N GREEN 8 2 Dialer Capture Module TO Facility I Ground FUSE PN 100 02415 5568 CONDUIT BATTERY 8 7 AH CT iGSM Comm Module not supplied 6 a Wiring for Grounds Power and RF IPGSM DPC Commercial Fire Communicator Installation and Setup Guide Wiring the 659EN Line Fault Monitor if required The IPGSM DPC is compatible with the Honeywell brand FACP s listed on page 1 when the model 659EN Lin
5. fixed 10 minute window Buzzer Upon loss of AC power this will beep once every 10 Violet Note If a wire pulled out of the LED Board Connector LED Board refer to the diagram on right and reinsert wire ensuring Black Connector the connector pin is locked in gt White Red Brown Yellow Gray 10 m RADIO TROUBLE O buzzer LOW BATTERY O seconds LOW BATTERY Yellow ON when battery is low lt 11 5VDC not used LO Yellow not used AC Loss LO AC LOSS Yellow ON when no AC is present lt 90VAC AC ONLO AC ON Green ON when AC is present IPGSM DPC Commercial Fire Communicator Installation and Setup Guide PowerBoost1 Module Information LED Indicator STATUS AC green AC power available ACTIVE green Cyclical flashing normal communications Repetition of 3 flashes loss of communications LOW BATT yellow Missing or low battery TROUBLE yellow One or more trouble conditions exist such as overload output supervision ground fault or charger failure Notes e If AC power is lost and the battery voltage falls below 10v the module s output voltage will be turned off The output power is turned back on when AC power is restored e You must use the DIP switch settings shown below LowpattLep PowerBoostt TROUBLE LED INDICATOR op il INDICATOR a Confiure DIP switch
6. surrounds the PowerBoost1 Mount the PowerBoost1 on the three unused standoffs Use the plastic screw prevents shorting to secure the upper right corner of the PowerBoost1 and the two metal screws and lock washers to fasten the left side of the circuit board Ensure the lock washers are located between the circuit board and the head of the two metal screws Use the 1451 UL9 Wired Transformer directly connected to un switched facility power Connect and route 14AWG minimum insulated wire from facility ground to the 1451 UL9 enclosure ground post and through the conduit to the IPGSM DPC cabinet ground post Route 16AWG wire from the transformer secondary through the conduit Pass the wires through the Ferrite Filter then loop the wires back through again making a loop Ensure the wire ends that connect to the PowerBoost1 Module are tinned Connect the wires to the PowerBoost1 AC terminals At this time DO NOT apply power Ensure all ground connections are tight Connect the Ethernet cable and the Telco 1 and Telco 2 lines If you choose to use an optional Cabinet Tamper Switch if the control panel supports it mount and wire it Note The Ethernet cable Telco 1 Telco 2 lines and the optional cabinet Tamper Switch if used must be run through conduit Verify the PowerBoost1 module DIP switches are configured as shown below PowerBoost1 ON 12345 Switch handle white iPGSM COM 008 VO Ensure the following
7. CT MS 5UD 7C FR family one requires UDACT NSP 25C family four MS 9050UDC family two SFP 10UDC family three MS 9050UDC FR family two SFP 10UDC FR family three MS 9200UDLSC family three SFP 5UDC family three MS 9200UDLSC FR family three SFP 5UDC FR family three MS 9600LSC family three Use the DACT UD2 product to interface the IPGSM DPC IPGSM DPC Commercial Fire Communicator Installation and Setup Guide Operation The IPGSM DPC replaces the fire panel s POTS communications path When an event occurs the fire panel goes off hook to dial the central station The IPGSM DPC detects the off hook condition and provides the fire panel with a dial tone When the fire panel detects the dial tone it begins dialing the central station The IPGSM DPC considers the three second period after dialing as the number dialing has been completed After the dialing is completed the Dialer Capture Module returns a handshake to the fire panel The fire panel then sends the contact ID reports to the IPGSM DPC which in turn sends a kiss off after the report is successfully received from the fire panel Within the IPGSM DPC the Dialer Capture Module sends the contact ID reports over the ECP bus to the iGSM Communications Module When all the reports are sent the fire panel goes on hook The IPGSM DPC then transmits the messages to the central station either over the internet or the GSM network IPGSM DPC Commercial Fire Communic
8. Honeywell IPGSM DPC Commercial Fire Communicator Installation and Setup Guide IPGSM DPC Commercial Fire Communicator C RADIO TROUBLE LOW BATT AC Loss AC ON 800 09370 6 11 Rev A Contents General Information 5 te sn intel josie net es ae ia ae GNI eS 1 Package Content Sienie a iE a e OE Ea E a a EESE act ter 1 Compatible Fire Panels ss iceieods aate nine tent ere ei th 1 Op rAUON ren mien E cde ula en 0 E E ie nn nd tasse ere nets Sent 2 Installation atin imitant ins nina limite 3 UEC Compliance seis thin te At ah Ra PSs ho REE ARS AS RE et tie RASS 3 STEP 1 Setup the Customer Account 3 STEP 2 Register the Communications Module with AlarmNet cccscccccessscceeesseeeeeeeaes 3 STEP 3 Determine the Signal Strength and Select a Location 4 STEP 4 Mount and Wire prinose asa AE EAA A AAEREN ASS AAAS 4 Wiring the 659EN Line Fault Monitor if required ssssssssssssssssesssessessssesesersessssssesresess 7 STEP 5 Program the Communications Module ccccccccesssssccceccecsesesssceceeeceeeenenssaeeeeeceeess 8 STEP 6 Configure the Fire Panel 9 STEP 7 Test the Systems ii Rd means ne te re RD 9 Dialer Capture Module Information suis 10 LED Display Informations ss msn tosses bau min nent Sin nn canted van site 10 PowerBoost1 Module Information 11 1GSM Communications Module Information cccccccccssccecesssececessseeeceesneceecessaeeeesssuee
9. ODULE S RECEIVED SIGNAL STRENGTH RSSI When the Mode Switch is NOT depressed LED 1 will illuminate red e The remaining LEDs indicate RSSI Received Signal Strength all MODULE S OPERATION MODE When the Mode Switch IS depressed LED 1 will be OFF e LEDs 2 and 3 indicate the module s communication mode with the Dialer Capture Module LED lo Zone NOT USED ON 4204 NOT USED 2 4204 NOT USED MODULE S STATUS When the Mode Switch IS depressed LED 1 will be OFF e LEDs 4 5 and 6 indicate the module s Status LED 4 green LED 5 green LED 6 green ON Connected to ON GPRS service ON Module registered no second Internet available site available OFF Not connected OFF No GPRS service OFF Module not registered with to Internet available network carrier FAST BLINK GPRS in SLOW BLINK Module registered second use site available and low signal strength NORMAL BLINK Module registered second site available acceptable signal strength FAST BLINK Module registered second site available excellent signal strength _12 IPGSM DPC Commercial Fire Communicator Installation and Setup Guide RF Specifications FLIP IPF III III PIII III PIII III PIII III III I III SI IIS SSII IIS SI IIS SSII IIS SSII ISSN IIIS III PII III IP IIIIIIPIS Specific to RESIDENTIAL COMMERCIAL Control Panels
10. Such as the VISTA 10P 15P and 20P series UL The information provided in this section for the VISTA 10P 15P and 20P series control panels has not been evaluated with this communications module Communicator Trouble low battery ECP bus E353 C0803 R353 C0803 network Possible Compromise Indication Radio Fault E353 C0103 R353 C0103 Pa ee ee ee ee ee ee ee Pe ee SSII ESIIIIS A A Aaa Ea a a a a a EE a a EF Specific to COMMERCIAL Control Panels Such as the VISTA 128 250 series Communicator Trouble low battery ECP bus E333 C0803 R333 C0803 network Possible Compromise Indication Radio Loss of Signal E357 C0803 R357 C0803 or Possible Compromise Indication R380 C0803 Radio Fault low battery tamper ECP Bus E333 C0803 R333 C0803 AlarmNet Messages Communication failure 5555 1555 6 5555 3555 6 Possible Compromise Indication Authorized Radio Substitution 00D0 010C 0 N A Unauthorized Radio Substitution Attempt 00D0 010E 0 N A Service Termination 00D0 020E 0 N A 13 Transmission Transmit Receive Receive Number Channel Duplex Band Frequency Power Frequency Sensitivity of Spacing Separation MHz dBm MHz dBm Channels wuz kHz GSM 850 824 849 33 869 894 107 124 200 45 GSM 900 890 915 33 935 960 107 124 200 45 GSM 1800 1710 1785 30 1805 1880 106 374 200 95 GSM 1900 1850 1910 30 1930 1990 105 5 299 200 80 Central Station Messages Alarm Con
11. Try Again Y N_ Press Y Failed to Update Network problem or you answered N Initiate the Force Server Update Root File to Cannot Upload Try Again prompt Command by pressing the 0 key Setting Factory Defaults To reset the programming options to factory default values at the Exit Prog Mode prompt press Shift plus ESC Note setting the factory defaults will also erase any password that may have been entered Set Default Press Y to reset factory default values YIN_ Press N to cancel this function Press Shift then Y then The Create Password prompt appears follow the prompts then exit STEP 6 Configure the Fire Panel 1 Ensure the Telco Fault on the panel is enabled Then choose a setting that is no higher than 90 seconds or as close to that as the panel allows 2 Ensure no more than 1 pause character usually a comma is programmed into the dialing string usually 2 seconds Note this is necessary since the Dialer Capture Module waits only 3 seconds after the phone number is dialed Having more than 3 seconds of pause time will cause it to think the phone number is complete and cause it to generate the high low tones at an incorrect moment STEP 7 Test the System 1 Close and lock the cabinet cover 2 Refer to the fire panel s installation operation guide for the testing procedure 3 Notify the monitoring station that a test will be conducted Test the sy
12. ator Installation and Setup Guide Installation ULC Compliance To meet Canadian ULC compliance ensure the following e IPGSM DPC must be installed in accordance with Canadian Electrical Code Part 1 e IPGSM DPC must be mounted in the same room and within 20 feet of the fire panel The wiring must be routed through conduit e IPGSM DPC and all equipment used for the IP connection such as the router hub modem etc shall be listed must be powered from an un switched branch circuit and be provided with appropriate standby power e IPGSM DPC must use a 7AH battery not supplied to provide 24 hour backup capability STEP 1 Setup the Customer Account The communicator requires a subscriber account customer account to be setup with AlarmNet Direct This is accomplished by registering the communicator s iGSM communications module with AlarmNet Registering enables the fire panel to send reports To setup the customer account you will need to contact the central monitoring station to get account information and have access to the AlarmNet Direct website To access the AlarmNet Direct website visit https services alarmnet com AlarmNetDirect If you do not wish to use the AlarmNet Direct website you may call AlarmNet to setup the account just phone 800 222 6525 then select option 1 Monday Friday 8 00 am to 9 00 pm Saturday 9 00 am to 5 30 pm EST Have the following information ready e Primary City ID two
13. digits obtained from your e Primary Subscriber ID four digits obtained monitoring station from your monitoring station e Primary Central Station ID two digits obtained e Communication Module s MAC ID and MAC from your monitoring station CRC number located on outside of box and inside of the module Note The SIM supplied for the IPGSM DPC is already activated Therefore no SIM activation is necessary STEP 2 Register the Communications Module with AlarmNet Registering the module activates the account with AlarmNet and enables the fire system s control panel to send reports There are three methods that can be used to register the communications module e Register the module by logging into AlarmNet Direct and choosing Show Programmed Devices GSM T Search for the account using the Account Information or MAC ID Under the Actions column use the pulldown menu and choose Register OR e After the IPGSM DPC is installed and programmed you can register the module by clicking the Tamper Switch 3 times OR e After the IPGSM DPC is installed and programmed you can register the module using the 7720P Programming tool Simply Press Shift then press M Please wait for Registration SUCCESS message IPGSM DPC Commercial Fire Communicator Installation and Setup Guide STEP 3 Determine the Signal Strength and Select a Location IMPORTANT Do Not mount this device outdoors RF Expos
14. dition Alarm Code Restore Code Power On Reset E339 C0803 N A Power Loss E337 C0803 R337 C0803 Low Battery E338 C0803 R338 C0803 Battery Charger Failure E314 C0803 R314 C0803 ECP Supervision Compromise Indication E355 C0000 R355 C0000 Primary Communication Path Supervision E350 C0951 R350 C0951 Secondary Communication Path Supervision E350 C0952 R350 C0952 Periodic Comm Test Fail E358 C0803 R358 C0803 Test 5555 5555 9 N A IPGSM DPC Commercial Fire Communicator Installation and Setup Guide IPGSM DPC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM DPC and Telco 2 is used by the IPGSM DPC to report faults to the Fire Panel If Telco 1 is not operational the Fire Panel will use Telco 2 to report events if there are no faults in the iGSM Communications module Fault Condition Indication to Fire Panel PowerBoost1 fault Telco 2 is cut iGSM Communications Module fault e Failure of the communications path when Telco 2 is cut IP_only or GSM only is programmed as a communications path e Failure of both communications paths Telco 1 and 2 are cut when IP amp GSM is programmed as a communications path Dialer Capture Module buffer is full Hang up Panel will retry giving the buffer a chance to empty IPGSM DPC Specifications ITEM SPECIFICATION Cabinet Dimensions Width 12 3 4 inches Height 14 7 8 inches Depth
15. e then press Follow the prompts DNS Serv IP Addr 255 255 255 255 Review Y N Enter choice then press Follow the prompts Enter choice then press Follow the prompts Create Password Y N Enter choice then press Follow the prompts Eii Prog Moce WN Press Shift then Y then press DONE Notes Ifan error in programming occurs set the factory defaults see next topic and reprogram e The IP Fault Time and the GSM Fault Time are each fixed at 1 minute and are not programmable IPGSM DPC Commercial Fire Communicator Installation and Setup Guide To exit the programming mode press N in response to the Review prompt Then press Y to the Exit Prog Mode prompt Upon exiting the root file is updated to log the changes made A message is displayed telling the user that this step is being executed When complete the message DONE is displayed to indicate the file was successfully uploaded Note If critical configuration changes were made such as the mode of operation the communications module will reset to ensure that the programming features are enabled If the file is not successfully uploaded one of the following prompts will be displayed Follow the steps shown below until the upload is successful Display Description What to do Cannot Upload Module is not yet initialized Wait for RSSI indicator LEDs to be lit
16. e Fault Monitor is installed 1 Refer to the installation guide for the 659EN 2 Mount the 659EN on the lower left side of the IPGSM DPC cabinet 3 DO NOT cut the 659EN s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper 4 Complete the interface wiring as shown below YEL gt to Dialer Capture Module Terminal Tip 2 ORG to Dialer Capture Module Terminal Ring 2 RED to Power Boost 1 Terminal OUTPUT 1 DC BLK gt to Power Boost 1 Terminal OUTPUT 1 DC GRN to Power Boost 1 Terminal ERTH GND Wire toa Zone on the Fire Panel YY IPGSM DPC 013 VO IPGSM DPC Example wiring for an addressable fire control panel IPGSM DPC FIRE LITE Addressable Fire Alarm Control Panel Commercial Fire Communicator MS 9050UD To next device YEL gt to Dialer Capture Module Terminal Tip 2 on SLC Loop TOP MMF 300A a i ORG gt to Dialer Capture Module Terminal Ring 2 Monitor Module oil abide RED gt to Power Boost 1 Terminal OUTPUT 1 DC BLK gt to Power Boost 1 Terminal OUTPUT 1 DC 6789 14 GRN gt to Power Boost 1 Terminal ERTH GND yi Fy 15 DE l TENS ONES 2 ADDRESS r 4 7K 1 2 watt l l Shield bekibbkbk ae B A B A A B NO NC C RELAY 1 SLC Loop ALARM CONTACTS IPGSM DPC 014 VO IPGSM DPC Commercial Fire C
17. eessseeeeees 12 RE Specilica tion sen RE aos a eR MR EB SR ER 13 Central Station Messages cccccccccccsssssssssscssccsessssssenecesecsesessseessececssesnseaeessecsesensnsaaeeesecsesennaeas 13 IPGSM DPC Trouble Detection Information 4 14 IPESM DPC Specifications oc ss Mint nn te cede e sees ns nee nd nt adresses pete e an een nt 14 Mairies Diag ANS MU A A AE ND ra Inside of Back Cover IPGSM DPC Commercial Fire Communicator Installation and Setup Guide General Information The IPGSM DPC Commercial Fire Communicator henceforth referred to as IPGSM DPC includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path and uses a GSM cellular reporting path as a backup In addition this communicator utilizes a sophisticated power module PowerBoost1 that monitors and reports AC power loss low battery and missing battery conditions Package Contents e Red Fire Cabinet and Back Plate e Cam Lock with Key e Dialer Capture Module e Antenna and Mounting Adapter e Mounting Rails for above e Hardware Bag e Transformer 18VAC 1451 UL9 e PowerBoost1 e Battery harness fuse 100 02415 e Ferrite Filter e LED Display board iGSM Communications Module e 50 ohm cable assembly Compatible Fire Panels The IPGSM DPC works with e All Fire Panels that are listed in the table below e All Fire Panels that use t
18. g or component replacement It is not intended to show the physical routing of wires When replacing a wire or component ensure the wire is routed in the same manner as the original factory wire 1451 UL9 WIRED ANTENNA TRANSFORMER WIRES MUST BE RUN IN CONDUIT TO 24 HR FACILITY POWER 120VAC 60Hz 850mA TO Cabinet Ground Post GND BLU TO PowerBoost1 Er poi DO NOT REMOVE these knockouts Buzzer OPTIONAL CABINET WHT LO BATT TAMPER SWITCH LED Display CABINET DOOR E ale AIS Buzzer PowerBoost1 TE EE STB Low TROUBLE Es Fe gt om BATT Dal Bec oO a OBS LOW BATT HD 6 o SE ITT m A not used 8 12345 o S aa AC LOSS 2 l m GREEN d 8 AC ON CD Dialer Capture Module GE 2 0 2 N O ERTH GND Q RADIO TROUBLE BLK JO Z O o LT ES Le l YEL g out RED J E E l pc w T D LE Rs go BLK De 10 2 0S N U BES UT o 3 D i E
19. he Contact ID communication format as described in the SIA DC 05 Standard IMPORTANT For a fire panel that has more than 9 active partitions the first 9 partitions are reported to the central station uniquely Beyond 9 partitions only the 2nd digit of the partition is reported along with a leading zero example partition 14 is reported as 04 The installer must inform the central station of this condition The IPGSM DPC is compatible with the Honeywell brand FACP s listed below when the model 659EN Line Fault Monitor is installed Honeywell Fire Panel Communicator Honeywell Fire Panel Communicator 411 family two MS 9600LSC FR family three 411UD family two Use the DACT UD2 product to interface the IPGSM DPC 411UDAC family two NFS2 3030 family one requires UDACT FireWarden 100 2C family three NFS2 3030 FR family one requires UDACT FireWarden 100 2C FR family three NFS2 640 family one requires UDACT FireWarden 50C family two NFS2 640 FR family one requires UDACT FireWarden 50C FR family two NFS 320 family one requires UDACT MS 10UD 7C family three NFS 320C family one requires UDACT MS 10UD 7C FR family one requires UDACT NFS 320C FR family one requires UDACT MS 25C family four NFS 320SYS family one requires UDACT MS 5UD 7C family three NFS 320SYS FR family one requires UDA
20. k that mounting position Disconnect the battery STEP 4 Mount and Wire e For ULC compliant installations refer to the topic on ULC Compliance in this manual e For Dry Indoor use only e External cabinet wiring MUST be routed in conduit This communicator comes partially assembled with all the components mounted except the Antenna LED Display board and PowerBoost1 To protect certain components on the PowerBoost1 it is shipped un mounted but fully wired Note Refer to the diagram on page 6 and to the Wiring Diagram on the inside of the back cover of this manual for wiring and component identification 1 Remove knockouts from cabinet to accommodate the power input wires and wiring to the control panel DO NOT REMOVE the two knockouts directly above the PowerBoost1 module Then mount the cabinet securely to the wall using 4 screws or bolts Use mounting screws or bolts that are suitable for the material being anchored to 2 Ensure the cabinet door lock is installed 3 Install the two plastic mounting rails for the LED Display board They simply snap into the back plate holes IPGSM DPC Commercial Fire Communicator Installation and Setup Guide 10 11 12 13 Connect the LED Display board to its connector then slide the board into the mounting rails Refer to the LED Display Information topic if a wire is detached from its connector Carefully remove the packaging material that
21. ommunicator Installation and Setup Guide STEP 5 Program the Communications Module You must use the 7720P Programming tool to program the IPGSM DPC When using the 7720P Programming tool the values given below are for most installations Press the key to accept the displayed default value xxx or enter the new value and press the key for the next prompt Use the Space key to scroll through a list of options no display Connect the 7720P 7720P PROGRAMMER Press Strt Prog Mode Y N Program Device Y N Com Path Choice IP amp GSM Press Shift then Y then Press Shift then Y then Press Space to scroll choices IP amp GSM IP or GSM At choice press Primary City ID Enter number 01 99 then press Primary CS ID 2 Enter number 01 FE then press Files en 20 Enter number 0001 9999 then press Note If a Com Path Choice of IP amp GSM or IP was selected prompt 9 will appear Use DHCP YIN Y If your router is configured for DHCP press Shift then Y then press Note If DHCP is not selected your router is set for a static IP prompts 10 through 13 will appear NIC IP Address 255 255 255 255 Subnet Mask 255 255 255 255 Enter choice then press Follow the prompts Enter choice then press Follow the prompts Gateway IP Address 255 255 255 255 Enter choic
22. sired operation Cet appareil est conforme a la RSS 210 des Industries Canada Son fonctionnement est soumis aux conditions suivantes 1 Cet appareil ne doit pas causer d interferences nuisibles 2 Cet appareil doit accepter toute interference regue y compris les interferences causant une reception ind sirable DOCUMENTATION AND ONLINE SUPPORT For the latest documentation and online support information please go to http www security honeywell com hsc resources MyWebT ech WARRANTY For the latest warranty information please go to http www security honeywell com hsc resources wa Honeywell 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 IA HT Il Copyright 2011 Honeywell International Inc 800 09370 6 11 Rev A www honeywell com security
23. stem to ensure it is operating 4 Verify communications with the central station is successful by sending several events Also get confirmation that these events were received IPGSM DPC Commercial Fire Communicator Installation and Setup Guide Dialer Capture Module Information LED Indicator STATUS RED Steady ON Messages exist in buffer RED Flashing No messages to be sent Waiting for messages GREEN Steady ON Normal Indication GREEN Blinks every 2 sec PowerBoosti communication problem GREEN Blinks twice every sec Communication Module connection is lost GREEN Blinks 10 times every sec PowerBoost1 and Communications Module connection is lost D 5 fe s La a O O GREEN Telco 2 Telco 1 Dialer Capture Module LED Display Information Note Telco ports 1 primary dialer and 2 secondary dialer may be used instead of the terminal board Whichever connection method is used both Telco paths must be connected to the Fire Panel iPGSM COM 004 VO Panel Status LED Indicator RADIO TROUBLE Yellow ON when radio trouble is present e Both IP and GSM communication paths are lost e Communicator radio is not registered e Old Alarm Time has been exceeded Message has not been delivered within the
24. ure Warning The antenna s used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be collocated or operating in con junction with any other antenna or transmitter When choosing a suitable mounting location understand that signal strength is very important for proper operation For most installations using the supplied antenna mounting the unit as high as practical and avoiding large metal components provides adequate signal strength for proper operation In this procedure you will use the iGSM Communications Module to determine signal strength in order to find a suitable mounting location Note Since the SIM is already activated the RSSI signal strength indicators will indicate signal strength 1 You will need a fully charged 12V battery 2 Attach the Antenna see illustration on page 6 3 Temporarily wire the battery s negative terminal to TB1 4 on the iGSM communications module then wire the battery s plus terminal to TB1 2 on the communications module Wait about one minute for the module to initialize 4 Position the assembly near a suitable mounting position and observe the RSSI display 5 Look for a mounting position that yields at least 3 bars lit solid Four O J searsmin R Y Y GGG or five bars are better 7845 GSM 025 VO 6 Verify the signal strength remains steady for a few minutes then mar