Home
Honeywell F111 User's Manual
Contents
1. For Series 1 only Be sure the fastener tabs are facing downward and fasten them 8 ForSeries 2 and 3 only Be sure both catches are turned down and filter rests firmly on catches 9 Install 1 startup filter in each end of grill 10 Close and latch the lid On initial startup a small amount of dust can blow from the air cleaner This is normal and stops a few minutes after startup The startup filters will catch all the dust The startup filters are placed in the two exit outlets on the grill After running the unit for 5 minutes turn off the unit Remove and discard the two start up filters F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER PARTS LIST Refer to Fig 9 and Table 5 for replacement part information Table 5 Replacement Parts ence No Description Pack Qty Order Number 1 CPZ sorbent module requires 2 used with only 1 32004078 001 95 HEPA or 95 ASHRAE particle filters Charcoal sorbent module requires 2 used with only 1 32004078 002 95 HEPA or 95 ASHRAE particle filters Zeolite sorbent module requires 2 used with only 1 32004078 003 95 HEPA or 95 ASHRAE particle filters Permanganate sorbent module requires 2 used with 1 32004078 004 only 95 HEPA or 95 ASHRAE particle filters 2 Blower wheel Series 1 1 32000236 Blower wheel Series 2 and 3 1 32002285 3 Motor capacitor 120V 60 Hz Series 1 2
2. reduce the excessive accumulation of the contaminants To eliminate the contamination the source of contamination must be removed 68 0198 2 F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER Local Federal and professional ventilation engineering standards and codes prescribe minimum ventilation rates to dilute air contamination in specific applications The ventilation rates usually assume the injection of outdoor air measured as air exchange rate The use of the F111 series 1 2 3 air cleaner to comply with ventilation requirements is an acceptable alternative to ventilation with outdoor air However at least 20 of a specified ventilation rate or code must be derived from outdoor air The F111 series 1 2 3 air cleaner filtered and recirculated air can be the remaining 80 SERVICE N CAUTION Electrical Hazard Can cause personal injury or equipment damage Turn off power before installing or servicing the air cleaner IMPORTANT Be sure to change filters as recommended to prevent reduced airflow in the air cleaner Stand on a stable platform when working with the air cleaner The useful life of the CPZ sorbent modules may vary from 4 to 24 months depending on the application In most applications the sorbent media life ranges from 12 to 18 months The particle filter life ranges from 6 to 24 months with 12 to 24 months as an average The modules and filters need to be changed more frequently in facilities that operate
3. 24 hours a day Prefilter The disposable prefilter collects large dust particulates and lint type airborne fibers Check the filter every two weeks to determine the replacement frequency 1 Slowly open the lid supporting the lid so the filters do not fall out 2 Remove the dirty prefilter 3 Install the new prefilter in the air cleaner lid Position the metal screen mesh so it is facing upward when the lid is closed 4 Close and latch the lid Particle Filter The particle filter collects particulates that pass through the prefilter The filter life is typically from 1 to 2 years There is decreased air quality and a pulsing sound when the filter is filled with contaminants The filter must be replaced when the pulsing sound is noticed NOTE The filter must be replaced Washing vacuuming or reverse air blasting does not clean it 1 Slowly open lid supporting it so the filters do not fall out 2 Open the securing strips and with both hands Slide the filter toward you 68 0198 2 Revised 5 09 8 3 Place spent filter in a plastic trash bag and dispose of properly 4 Inspect the motor brackets for loose fasteners and tighten as necessary 5 Install the new filter noting the direction of airflow arrow 6 ForSeries 1 and 2 only Fasten the filter tabs Be sure there is a snapping sound when they are fastened The tabs are commercial Velcro and require more force to fasten 7 For Series 3 only Lock and secu
4. ASHRAE N A N A 1250 2120 F111A1063W 3S 120 Vac 60 Hz 7 2A 99 97 HEPA N A N A 950 1610 F111C1073W 3S 120 Vac 60 Hz 7 5A 9596 ASHRAE 85 CPZ modules 1150 1950 F111C1003W 3S 120 Vac 60 Hz 7 0A 99 97 HEPA 85 CPZ modules 825 1400 F111C1012W 3S 120 Vac 60 Hz 8 0A 95 at 0 3 micron 85 CPZ modules 1125 1910 F111A2253W 3S 230 Vac 50 Hz 4 2A 9596 ASHRAE N A N A 1125 1910 F111A2007W 3S 230 Vac 50 Hz 3 5A 99 97 HEPA N A N A 900 1530 F111C2073W 3S 230 Vac 50 Hz 4 0A 95 ASHRAE 85 CPZ modules 1025 1740 F111C2003W 3S 230 Vac 50 Hz 3 2A 99 97 HEPA 85 CPZ modules 825 1400 F111C1053W 3S 230 Vac 50 Hz 3 5A 95 at 0 3 micron 85 CPZ modules 950 1610 F111C1061 same as F111C1012B 3S N A not applicable For single speed and three speed systems set to High bE411C1061 has a new model number F111C1012B To Order F111 with a Black Grill Replace the W with a B to any model number in Table 1 ORDERING INFORMATION If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Commercial Air Products Distributor 2 Air Pure Systems 16873 Fish Point Rd SE Prior Lake MN 55372 www cleanairfacility com Phone 800 998 1919 Fax 800 221 3248 68 0198 2 Release 5 09 Table 2 F111 Air Volume Specifications for 3 Speed Models Series 3 F111 SERIES 1 2 3 IN C
5. be furnished separately 68 0198 2 Revised 5 09 N CAUTION This installation to be performed only by a qualified installer All wiring to comply with local electrical codes Disconnect power to air cleaner at fuse or breaker before beginning work Failure to do so can result in shock hazard endangering equipment and personal safety of installer Only one air cleaner can be connected to a remote switch Disconnect power to air cleaner Mount 4 x 4 outlet box at desired remote location Attach 3 4 extension ring to outlet box Run five conductor color coded 18 gauge wires from the remote switch location to the air cleaner Use three wire nuts to connect three color coded lead wires on the remote switch to three color coded wires from the air cleaner Red Blue Violet Use one wire nut to connect white color coded lead wire from the air cleaner to single color coded wire from the power supply White TO AIR CLEANER R TO POWER ay 4X 4 OUTLET BOX OR EQUIVALENT SUPPLY S TO GIVE TOTAL MIN DEPTH OF 3 INCHES WITH EXTENSION RING RED COVER PLATE FAN SWITCH N OPTIONAL CONNECTION USE IF POWER SUPPLY LEADS ARE RUN IN CONDUIT Fig 6 Wiring 3 Speed Remote Switch Connect the ground wire from the power supply to a ground stud of the outlet box Green Connect the ground wire from the air cleaner to the ground stud of the outlet box Green Use one wire nut to connect the black color coded lead wi
6. the lid and turn the spring loaded plunger onto it Tighten the assembly with wrenches Repeat steps 1 through 4 for the second plunger WRENCH FLAT THREADED NN BARREL gms QN WRENCH FLAT E o S SPRING LOADED PLUNGER X M11994 Fig 7 Lid assembly Opening Closing the Lid To open the lid pull the spring loaded plungers back to disengage the plunger Carefully swing the lid open on the hinges while supporting the filter and or adsorbent modules as required To close swing the lid into the closed position and engage the plungers F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER Removing Replacing the Lid IMPORTANT The lid is heavy Make sure that it is supported before removing To remove the lid swing it into the open position Slide safety catch to off position Move the lid to the side to disengage the hinge pins Reverse the procedure to replace the lid Make sure safety catch is in safe position OPERATION The F111 series 1 2 3 in Ceiling Media Air Cleaner has been engineered to improve indoor air quality for commercial and industrial applications The filters are the most practical and effective filtering system for removing atmospheric dust pollens bacteria viruses mold spores smoke fumes mists and aerosols Refer to Fig 8 cpz cpz SORBENT SORBENT FILTER FILIERE MODULE NI CEILING LINE CEILING LINE lt CLEAN AIR CLEAN AIR DISCHARGE DISCHAR
7. 11995E 3 in Ceiling Media Air Cleaner components 2 Fig 9 Exploded view of F111 series 1 10 68 0198 2 Revised 5 09 F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER NOTES 11 68 0198 2 LIMITED TWO YEAR WARRANTY Air Pure Systems warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service for a period of two 2 years from the date of purchase by the original end user If at anytime during the warranty period the product is defective or malfunc tions Air Pure Systems through the distributor or dealer from which the product was purchased or through an authorized warranty repair station shall at Air Pure Systems option replace or repair the defective product or component This warranty does not cover removal or installation costs This warranty shall not apply if it is shown that the defect or malfunction was caused by damage which occurred during handling or shipment improper electrical connections improper use of the product or abuse Air Pure Systems sole responsibility shall be to repair or replace the product within the terms stated above AIR PURE SYSTEMS SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PROD UCT Some states do not allow the exclusion or limitation of incidental or consequential d
8. EILING MEDIA AIR CLEANER Particulates at Gas V O C and High Medium Low 0 3Micron Odor Control in cfm in cfm in cfm Model Voltage DOP Test Modules 2 m3 hr m3 hr m3 hr F111A1253W 38 120 Vac 60 Hz 8 5A 95 ASHRAE N A 1250 2120 1800 1360 450 760 F111A1063W 3S 120 Vac 60 Hz 7 2A 99 97 HEPA N A 950 1610 775 1310 450 760 F111C1073W 3S 120 Vac 60 Hz 7 5A 9596 ASHRAE CPZ modules 1150 1950 825 1400 450 760 F111C1003W 3S 120 Vac 60 Hz 7 0A 99 97 HEPA CPZ modules 825 1400 700 1190 450 760 F111C1012W 3S 120 Vac 60 Hz 8 0A 95 at 0 3 micron CPZ modules 1125 1910 825 1400 450 760 F111A2253W 3S 230 Vac 50 Hz 4 2A 95 ASHRAE N A 1125 1910 700 1190 475 810 F111A2007W 3S 230 Vac 50 Hz 3 5A 99 97 HEPA N A 900 1530 600 1020 400 680 F111C2073W 3S 230 Vac 50 Hz 4 0A 95 ASHRAE CPZ modules 1025 1740 675 1150 450 760 F111C2003W 3S 230 Vac 50 Hz 3 2A 99 97 HEPA CPZ modules 825 1400 550 930 375 640 F111C1053W S3S 230 Vac 50 Hz 3 5A 95 at 0 3 micron CPZ modules 950 1610 625 1060 425 720 Same for Single Speed Models Series 1 amp 2 TOP VIEW Q 3 8 X 16 INTERNAL THREAD 4 48 1219 H 24 610 46 3 4 1187 22 1 2 572 POWER CONNECTION POINT 17 14 438 i CEILING 114 M11996A Fig 1 Approximate dimensi
9. GE M12651A Fig 8 F111 series 1 2 3 air cleaner operation The air cleaner is either operating power on or off power off There are no other operational options available Even when the area is unoccupied the air cleaner can be operated continuously to prevent buildup of airborne contaminants Operate the air cleaner only when the area is occupied when specific activities produce contaminants The CPZ sorbent module has the ability to collect and hold gas phase compounds and vapors typically found in commercial and light industrial facilities These gases and vapors frequently appear as odors that at times can be annoying and irritating The modules become saturated after collecting 2596 to 5096 of their weight in gaseous odors The quantity of CPZ material provides adequate dwell time to ensure up to 95 collection efficiency in the first pass This also provides a long maintenance free service life The minimum recommended air exchange rate is 2 5 times per hour In a heavily contaminated area up to 15 air exchanges per hour can be necessary The factors that determine what the rate of air exchange should be are generation rates of the various pollutants concentration level of the pollutants desired contamination reduction level Airborne contaminants will always be present in the air where contaminant generations take place Air cleaning systems and ventilators do not eliminate airborne contaminants they
10. Honeywell F111 Series 1 2 3 In Ceiling Media Air Cleaner Wiff VN H 7 WA W Minny W MMi APPLICATION The F111 Series 1 2 3 Ceiling Media Air Cleaner is a media air cleaner that uses either a single speed or three speed direct drive forward curve blower motor with particle filter When equipped with CPZ modules 2 gases and odors are adsorbed from the air passing through the unit The air cleaner removes airborne particles such as dust soot mold spores pollen and some cooking smoke from the air circulated through the filter The Honeywell Trademark is used under license from Honeywell International Inc by Air Pure Systems Honeywell International Inc makes no representations or warranties with respect to this product PRODUCT DATA FEATURES High Efficiency Particulate Air HEPA filter models are 99 97 efficient and the hospital grade particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger There is also a 95 ASHRAE model Circulates up to 1250 cfm Designed to overcome the increase in air flow resistance normally caused by filter loading White or black color cover to complement the ceiling CPZ module removes up to 95 of the space odors for up to 24 months 3 Speed remote wall switch 3 speed models only READ AND SAVE THESE o Contents AppliCatlOn ie eie ttt Rb ERROR 1 FOAtuieS sacs os det
11. S 1 2 3 IN CEILING MEDIA AIR CLEANER TOP OF METAL CABINET f HEX BOLT THREADED o f LOCK ROD EN y WASHER JAM NUT EN CHAIN EYEBOLT JAM NUT 3 8 IN X 16T OR USING OPTIONAL Z BRACKETS TOP OF METAL CABINET 1 9 2 E 3 E 4 5 NOTE 6 FASTEN SECURELY TO STRUCTURAL SUPPORT SYSTEM I E BAR JOIST CONCRETE SLAB OR TIMBER FRAMING BOTTOM FLANGE AGAINST CEILING UNDERSIDE OF TEES TEE BOTTOM VIEW OF UNIT WITHOUT LID ASSEMBLY M10892 SCREW 4 Fig 5 Fasten cabinet to a structural support IMPORTANT Do not touch the pleated filter media Handle only the A100001 filter frame to prevent damage to the filter media 11 Remove CPZ sorbent modules select models from their packaging and install one module into each cavity 7 12 For Series 1 only Be sure the fastener tabs are facing downward and fasten them 8 13 For Series 2 and 3 only Be sure both catches are turned down and filter rests firmly on catches 9 14 Install the prefilter in the air cleaner lid Position the metal screen mesh so it is facing upward when the lid is closed 10 Remote 3 Speed Wall Switch 3 Speed Models only th The 190097C Remote Wall Switch Assembly allows control of 12 the F111 model air cleaners from a a location separate from the air cleaner The assembly includes a remote switch with an outlet box cover outlet box extension ring and a wire harness Wiring to connect the remote switch and air cleaner 13 must
12. alled Over A Tub Or Shower It Must Be Marked As appropriate For The Application and be connected to a GFCI Ground Fault Circuit Inter rupter protected branch circuit Choose Location Choosing the correct location for the air cleaner affects the overall performance of the unit The bidirectional airflow pattern must flow into the longest reaches of the zone being cleaned See Fig 2 NOTE The F111 Has Not Been Investigated For Use In Fire Resistance Rated Construction Fig 2 Correct positioning of the air cleaner for optimum cleaning The air cleaner is designed to be suspended centrally in a space and mounted into or on a ceiling The cleaning footprint of the air cleaner is rectangular with air patterns that move clean air to the corners of the area while drawing contaminated air up from the center of the area See Fig 2 When multiple air cleaners are installed the allotted areas to be cleaned should be equal The air throw in one direction is approximately 55 ft 17m Air velocity at 90 ft per minute 27m per minute is considered end of throw 68 0198 2 Revised 5 09 4 CEILING E RR 1 i CLEANING FOOTPRINT l I i FH l 1 SERIES l 11000 M12652A IMPORTANT Never hang the air cleaner higher than 16 ft 5m above the floor INSTALLATION WARNING Explosion Hazard Possible Can cause personal injury or equipment damage Do not install or use the F111 series 11000 air cle
13. amages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR PURE SYSTEMS EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES WHETHER WRITTEN OR ORAL IMPLIED OR STATUTORY INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABIL ITY WORKMANSHIP OR FITNESS FOR A PARTICULAR USE This warranty gives you specific legal rights and you may have other rights which vary from state to state How to make a warranty claim or have questions answered Should you have a warranty claim or questions about the warranty policy contact the distributor or dealer from which you purchased the product or the authorized warranty repair stations nearest your location NOTE Do not return any products or parts to the factory without a factory issued Returned Warranty Goods Label issued by Air Pure Sys tems In the event you or other persons have any questions concerning the use and care of this product or this warranty please call or write the factory Air Pure Systems 16873 Fish Point Rd SE Prior Lake MN 55372 1714 Phone 800 998 1919 Fax 800 221 3248 Air Pure Systems 16873 Fish Point Rd SE Prior Lake MN 55372 1714 Phone 800 998 1919 Fax 800 221 3248 68 0198 2 Revised 5 09 www cleanairfacility com
14. and 3 1 32000265 Motor capacitor 208 230V 50 60 Hz Series 1 2 1 32000549 Motor capacitor 230V 50 Hz Series 3 1 32000265 4 Motor 120 V 60 Hz Series 1 1 32000270 Motor 208 230V 50 60 Hz Series 1 1 32000263 Motor 120 V 60 Hz Series 2 1 32002415 001 Motor 208 230V 50 60 Hz Series 2 1 32002415 002 Motor 120 V 3 Speed 60 Hz Series 3 1 32002415 004 Motor 230V 3 Speed 50Hz Series 3 1 32002415 005 5 99 9796 HEPA media filter 3 Series 1 and 2 1 32000204 001 99 97 HEPA media filter 4 5 Series 3 1 32000204 002 95 hospital grade filter 1 32000203 9596 ASHRAE particle filter 1 50004739 001 6 Prefilter disposable 1 32002307 7 Lid assembly with hinges and latches in White Color 1 32002308 002 OPTIONAL Parts not shown in Fig 9 Remote Wall 3 Speed Switch Series 3 1 190097C Motor mount bracket 1 32000260 Motor maintenance grommet set 3 32000261 Snap loc Tabs Series 1 1 32000262 001 Snap loc Tabs Series 2 1 32000262 002 Z Sidemount Bracket Kit 4 32002353 Spring Loaded Plunger 2 32002278 Lid assembly with hinges and latches in Black Color 1 32002308 003 NOTE All replacement filters must be provided by Air Pure Systems to maintain U L Certification and Warranty 68 0198 2 F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER ASSEMBLY ua CABINET SORBENT MEDIA MODULE 2 REQUIRED BLOWER WHEEL MOTOR CAPACITOR MEDIA FILTER PREFILTER LID ASSEMBLY WITH HINGES AND LATCHES M
15. aner where there is any danger of gas vapor or dust explosion IMPORTANT This air cleaner has not been investigated for use in the ceilings of fire resistant assemblies N CAUTION Electrical Hazard Can cause personal injury or equipment damage Turn off power before installing or servicing the air cleaner IMPORTANT Stand on a stable platform when working with the air cleaner ne Installing this Product Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condi tion 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions Unpack the Air Cleaner Check that all components are included The unit consists of cabinet and grille door assembly media modules literature latches 2 3 speed switch module 3 Series only bus Opening if Mounting in a Drop Ceiling Size the opening to fit the air cleaner cabinet as closely as possible 2 Frame the opening to provide adequate support for the cabinet The cabinet must fit snugly in the opening allow no more than 1 4 in 6 mm from the opening to each side of the cabinet 3 Cover the framing and any unused portion of the open ing with wallboard plywood or other mater
16. e ie eh Mei db ice teens 1 Specificatioris nee ees 2 Ordering Information seen 2 Planning the Installation eeeeeeee 3 Installatlon 3 pere 4 SUE MEI 7 Serice is n cies Ier ree ceste ri doe evi i ea recien 8 Parts Lstan 5 oit eue tont ben eheu eiue Qu TRUE 9 Limited Two Year Warranty seen 12 e UL us LISTED 68 0198 2 F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER SPECIFICATIONS IMPORTANT Models Refer to Table 1 for model descriptions The specifications given in this publication do not include normal manufacturing tolerances Therefore this unit may not exactly match the listed specifica tions Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed curve Dimensions See Fig 1 for dimensions Table 1 F111 Series 3 Description Grill Color White standard or Black add B to end of model number Blower Motor Single speed standard or three speed add 3S to the end of the model number direct drive forward Efficiency V O C Odor Particulates at Most Gases Gas V O C and Air Volume 0 3 Micron Odors First Pass Odor Control in cfm Model Voltage DOP Test Average Modules 2 m3 hr F111A1253W 3S 120 Vac 60 Hz 8 5A 95
17. eaner Distributor Table 4 Determining the Minimum Number of Air Cleaners Needed for a Space Space Volume Minimum L x W x H in Cubic Number of Number of Air Feet Cubic Meter Persons Present Cleaners 12000 to 18000 30 to 60 1 360 to 540 18001 to 35000 61 to 90 2 540 to 1050 68 0198 2 F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER Space Volume Minimum Lx W x H in Cubic Number of Number of Air Feet Cubic Meter Persons Present Cleaners 35001 to 51000 91 to 120 3 1050 to 1530 51001 to 65000 121 to 180 4 1530 to 1950 65001 to 80000 181 to 240 5 1950 to 2400 80001 to 95000 241 to 300 6 2400 to 2850 A WARNING TO REDUCE THE RISK OF FIRE ELECTRICAL SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING 1 Installation Work And Electrical Wiring Must Be Done By Qualified Person s In Accordance With All Applica ble Codes And Standard Including Fire Rated Con structions 2 When Cutting Or Drilling Into The Wall Or Ceiling Do Not Damage Electrical Wiring And Other Hidden Utili ties 3 Never Place A Switch Where It Can Be Reached From A Tub Or Shower 4 Use This Unit Only In The Manner Intended By The Manufacturer If You have Questions Contact The Man ufacturer 5 Before Servicing Or Cleaning Unit Switch Power Off At Service Panel And Lock Service Panel To Prevent Power From Being Switched on Accidentally 6 If This Unit Is To Be Inst
18. er Cabinet The air cleaner can be mounted in a drop ceiling system or hung in an open area Both mounting methods require the air cleaner to be level and positioned facing downward for correct operation Remove the door grille from the carton and set it aside Remove all filters Fit the cabinet into the prepared ceiling opening or position on the ceiling Use the four 3 8 x 16T internal nuts one at each corner to fasten the cabinet to a structural support bar joist concrete slab or timber framing See Fig 5 A O OPI NOTES All external hardware is furnished by the installer When using the suspension system of mounting be sure to include a means for leveling adjust ment after installation Never rest the air cleaner on the T bar 5 Level the air cleaner 6 Turn the air cleaner power on and check for proper operation for 2 to 3 minutes There should be a smooth powerful blower sound and air discharging from both ends of the air cleaner 7T Turn off the power 8 Install the particle filter Note airflow direction arrows if present Install the filter with the direction arrow pointing towards the motor 9 ForSeries 1 and 2 only Fasten the filter tabs Be sure there is a snapping sound when fastened The tabs are commercial Velcro and require more force than lightly pushing them together 10 For Series 3 only Lock and secure the particle filter into place by closing both latches 68 0198 2 F111 SERIE
19. ial and finish to match the ceiling Electrical Hookup All wiring must comply with applicable codes and ordinances The power source must agree with the model type 120V 60 Hz or 230V 50 Hz 1 Locate the prepunched hole in the side of the cabinet 2 Remove the air cleaner lid 3 For Series 1 and 2 only Remove the connection box cover plate in the center cavity of the air cleaner 4 For Series 3 only Remove the connection box cover plate on the bottom underneath the tray 5 Refer to Fig 3 and 4 for typical electrical diagrams A WARNING Risk of Fire or Electric Shock Can cause personal injury or equipment damage Use only Honeywell 190097C Remote Speed Switch 3 speed models only to regulate air cleaner speed Using a different speed switch may void the warranty ME Be sure the air cleaner is grounded for correct operation and safety e Canadian installation NEVER install in ceilings with thermal insulation value greater than R 40 FACTORY WIRING l BLACK I 1 EXTERNAL WIRING BY INSTALLER i I CAPACITOR M12657 Fig 3 Typical F111 series 1 amp 2 120V 60 Hz or 208 230V 50 60 Hz wiring diagram F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER FACTORY WIRING BLACK BLACK WIRING BY INSTALLER J ITOR REMOTE 3 SPEED 1 I 1 EXTERNAL 1 1 A100002 Fig 4 Typical F111 Series 3 only 120V 60 Hz or 230V 50 Hz wiring diagram Mount Air Clean
20. ons of F111 Series 1 2 3 in in mm Installation Weight Approximately 115 Ib to 155 Ib kg depending on the filter configuration Refer to Table 3 Table 3 Sorbent Module Weight Media Weight in Ib kg CPZ modules 2 43 20 Sound Level at 3 3 ft 1m Low speed 53 dBA 3 speed models only Medium speed 57 dBA 3 speed models only High speed 61 dBA Grille Type Perforated metal Mounting Recesses into opening on the ceiling Approvals Underwriters Laboratories Inc Listed Canadian Standards Association Listed Accessories Black Color Grill Remote 3 Speed Wall Switch Replacement Parts See Parts List Table 5 PLANNING THE INSTALLATION The number of F111 series 1 2 3 air cleaners that are needed is determined by taking into account the number of occupants and the volume of the space Type of contamination outdoor air quality and use of the area are also factors Refer to Table 3 for general guidelines when determining how many air cleaners are needed EXAMPLE One air cleaner can provide 2 5 air changes per hour in a 24 000 cubic feet 720 cubic meters no smoking area Table 3 suggests two air cleaners for a 24 000 cubic feet area because most areas have contaminants that require more units to provide quality air If any questions should arise concerning determining the number of air cleaners needed for an area consult your distributor or local Honeywell Commercial Air Cl
21. re on the remote switch to the black color coded wire from the power supply Fold wires into box and mount remote switch on outlet box Leave switch in OFF position On the air cleaner remove two screws on wiring com partment cover and open Run five conductor color coded 18 gauge wires from the remote switch through the air cleaner access open ing into the wiring compartment Strip ends of remote switch lead wires Connect three wires on air cleaner to remote switch lead wires with wire nuts following color code used at remote switch Red Blue Violet 14 Connect one wire on air cleaner to power supply wire with a wire nut following color code used at remote switch White 15 Connect the ground wire from the remote switch to a ground stud of the wiring compartment cover Green 16 Fold wires into wiring compartment Replace wiring compartment cover 17 Turn on power to air cleaner at fuse or breaker 18 Check operation by turning air cleaner at HIGH MEDIUM and LOW Note that only the remote switch will operate the air cleaner Lid Assembly The F111 lid is held in place by two separable hinges and two spring loaded plungers To install the spring loaded plungers on the lid follow these steps 1 Pull the plunger back and twist a quarter turn to reveal the wrench flat on the body of the spring loaded plunger see Fig 7 Turn the threaded barrel out of the spring plunger Insert the threaded barrel through the hole in
22. re the particle filter into place by closing both latches IMPORTANT Do not touch the pleated filter media Handle only the filter frame to prevent damage to the filter media 8 Close and latch the lid CPZ Adsorbent Module The CPZ adsorbent module is used to collect gases vapors odors and volatile organic compounds V O C from the air that passes through the air cleaner Adsorbents collect and hold 25 to 50 of their weight in odorous gases and vapors The impurities are collected until the adsorbents reach saturation At saturation the adsorbents emit a continuous strong pungent odor If the air cleaner is turned off for 8 to 10 hours there will a temporary odor when it is turned back on If the odor persists for 30 minutes it is time to replace the filters NOTE When tobacco smoke is a contaminant both the particle filter and the adsorbent filter will need to be serviced at the same time 1 Slowly open the lid supporting the lid so the filters do not fall out 2 For Series 1 only Support the adsorbent module with one hand and release the fastener 3 ForSeries 2 and 3 Support the adsorbent module with one hand and turn open the catches 4 Usetwo hands and slide the filter from the housing IMPORTANT The module weighs about 26 Ib 12 kg and can be hard to handle 5 Place the spent module in a plastic trash bag and dispose of properly 6 Remove CPZ sorbent modules from their packaging and install 7
Download Pdf Manuals
Related Search
Related Contents
Frigidaire FFWC35F4LB Product Specifications Sheet 第12回 - 日本原子力学会 Severin BA3299 steam ironing station Edge Thermal Imager User Manual www.bullard.com 写真セミナーのご案内はこちら (PDFファイル:260KB) Samsung SPF-85P Manual de utilizare Dynex 3-Port Quick Setup Guide Copyright © All rights reserved.