        Emerson Type 1190 Low-Pressure Gas Blanketing Regulator Installation Guide
         Contents
1.  avoid such  injury and damage  install the regulator ina  safe location     Clean out all pipelines before installation of the regulator and  check to be sure the regulator has not been damaged or has  collected foreign material during shipping  For NPT bodies   apply pipe compound to the external pipe threads  For flanged  bodies  use suitable line gaskets and approved piping and bolting  practices  Install the regulator in any position desired  unless  otherwise specified  but be sure flow through the body is in the  direction indicated by the arrow on the body     Note    It is important that the regulator be installed so that  the vent hole in the spring case is unobstructed at  all times  For outdoor installations  the regulator  should be located away from vehicular traffic and  positioned so that water  ice  and other foreign  materials cannot enter the spring case through the  vent  Avoid placing the regulator beneath eaves or  downspouts  and be sure it is above the probable  snow level     1  The pressure temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded     Table 1  Body Sizes and End Connection Styles                         BODY SIZES END CONNECTION STYLES  DN NPS Cast Iron WCC Steel or CF8M Stainless Steel  NPT  SWE  BWE  CL150 RF  CL300 RF   25  50 1 2 NPT  CL125 FF  or CL250 RF flanged CL600 RF  or PN 16 25 40 flanged  80  100  150 3 4 6 CL125 FF  or CL250 RF flanged BWE  CL150 RF  CL300 RF  CL
2.  installation completed and relief valves properly adjusted  slowly 5to 17 2to7  open the upstream and downstream shut off valves  12 to 40 5to 16  0 03 to 0 08 bar 0 5 to 1 2 psig    0 07 to 0 17 bar 1 1 to 2 5 psig  Adjustment 0 17 to 0 31 bar 2 5 to 4 5 psig  f 0 31 to 0 48 bar 4 5 to 7 0 psig  To change the outlet pressure  remove the closing cap or 1  Outlet pressure ranges based on pilot being installed with the spring case  loosen the locknut and turn the adjusting screw clockwise pointed down  Do not use Fluorocarbon  FKM  diaphragm with this spring at  to increase outlet pressure or counterclockwise to decrease diaphragm temperatures lower than 16  C   60  F     Table 3  Maximum and Minimum Differential Pressures Main Valve Spring Selection                                                          BODY SIZES MAIN VALVE MAXIMUM ALLOWABLE MINIMUM DIFFERENTIAL PRESSURE  DIFFERENTIAL PRESSURE REQUIRED FOR FULL STROKE  SPRING PART NUMBER SPRING COLOR   Q    DN NPS bar psig bar psig  14A9687X012 Green 4 1 60 0 17 2 5  25 1 14A9680X012 Blue 8 6 125 0 28 4  14A9679X012 Red 20 0 bar   300  peig or body rating 0 34 5  limit  whichever is lower  14A6626X012 Green 4 1 60 0 21 3  50 2 14A6627X012 Blue 8 6 125 0 34 5  14A6628X012 Red 20 7 bat 7300  psig or body rating 0 69 10  limit  whichever is lower  14A6629X012 Green 4 1 60 0 28 4  30 3 14A6630X012 Blue 8 6 125 0 41 6  14A6631X012 Red 20 7 bar   300 psig or body rating 0 76 11  limit  whichever is lower  14A6632X012 Green 4 1 6
3. 0 0 34 5  100 4 14A6633X012 Blue 8 6 125 0 55 8  14A6634X012 Red 20 7 bar   300  psig or body rating 0 90 13  limit  whichever is lower  14A9686X012 Green 4 1 60 0 66 9 5  a we 6 8x6  14A9685X012 Blue 8 6 125 0 97 14  x        300 x 150 12 x6 45A2615X012 Red 20 7 bar   300 psig or body rating 13 19  limit  whichever is lower 4                            Parts List    Type EGR Parts List    Key Description    Type 1098 Parts List    Valve Body   Body Flange   Cap Screw   Gasket   Lower Indicator Fitting  O Ring Retainer  Indicator Stem O Ring  Indicator Hex Nut  Spring   Travel Indicator Stem  Cage   Port Seal   Seat Ring   Piston Ring   Upper Seal   Valve Plug   Cage O Ring  Indicator Scale    Key Description    Lower Diaphragm Case  Upper Diaphragm Case  Bonnet   Cap Screw   Casing O Ring   Stem O Ring  Diaphragm   Diaphragm Plate   Stem Cap Screw   Cap Screw   Hex Nut   Stem   Nameplate   Vent Insert   Grease Fitting   NACE Tag   NACE Tag Wire  Bearing   Wiper    Key Description  19 Indicator Protector  20 Plug O Ring  21 Indicator Fitting O Ring  22 Flange Nut  23  E Ring  24 Drive Screw  25 Flow Arrow  27 Indicator Plug  28 Spring Seat  31 Pipe Plug  32 Travel Stop  33 NACE Tag  34 Tag Wire  35 Indicator Fitting  36 Back up Ring  37 O Ring  38 Pipe Plug    Type Y191A Parts List    Key Description    1    NO OBR WN    10  11  12  13  14  15  16  17  18  21    Body   Cap Screw   Spring Case Assembly  Lower Diaphragm Casing  Orifice   Spring   Diaphragm Head  Pusher Post  Di
4. 19 0611    Middle East and Africa  Dubai  United Arab Emirates  Tel   971 4811 8100    For further information visit www fisherregulators com    15    11       17                            32A4715_A                                                             Figure 4  Type 95H Supply Pressure Regulator    Natural Gas Technologies    Emerson Process Management  Regulator Technologies  Inc     USA   Headquarters   McKinney  Texas 75069 1872  USA  Tel  1 800 558 5853   Outside U S  1 972 548 3574    Asia Pacific  Singapore 128461  Singapore  Tel   65 6770 8337    Europe   Bologna 40013  Italy   Tel   39 051 419 0611  Gallardon 28320  France  Tel   33 2 37 33 47 00    TESCOM    Emerson Process Management  Tescom Corporation    USA   Headquarters  Elk River  Minnesota 55330 2445  USA  Tels   1 763 241 3238    1 800 447 1250    Europe  Selmsdorf 23923  Germany  Tel   49 38823 31 287    Asia Pacific  Shanghai 201206  China  Tel   86 21 2892 9499    The Emerson logo is a trademark and service mark of Emerson Electric Co  All other marks are the property of their prospective owners  Fisher is a mark owned by Fisher Controls  Inc      a business of Emerson Process Management     The contents of this publication are presented for informational purposes only  and while every effort has been made to ensure their accuracy  they are not to be construed as warranties  or guarantees  express or implied  regarding the products or services described herein or their use or applicability  We res
5. 600 RF  or PN 16 flanged  200 x 150  8x6   300 x 150 12x6      BWE  CL150 RF  CL300 RF  CL600 RF  or PN 25 flanged             FISHER       www fisherregulators com         EMERSON     D101644XUS2    167D Series    pressure  Monitor the outlet pressure with a test gauge during  the adjustment  Replace the closing cap or tighten the locknut to  maintain the desired setting     Overpressure Protection    The recommended pressure limitations are stamped on the regulator  nameplate  Some type of overpressure protection is needed if the  actual inlet pressure exceeds the maximum operating outlet pressure  rating  Overpressure protection should also be provided if the  regulator inlet pressure is greater than the safe working pressure of  the downstream equipment     Taking Out of Service  Shutdown     To avoid personal injury resulting from sudden  release of pressure  isolate the regulator from all  pressure before attempting disassembly     Regulator operation below the maximum pressure limitations does  not preclude the possibility of damage from external sources or  debris in the line  The regulator should be inspected for damage  after any overpressure condition                          Startup Table 2  Outlet Pressure Ranges  The regulator is factory set at approximately the midpoint of the OUTLET PRESSURE RANGE     spring range or the pressure requested  so an initial adjustment mbar inches w c   may be required to give the desired results  With proper 0 6 to 6 0 25 to 2 5 
6. Installation Guide  English     June 2011    Introduction    This installation guide provides instructions for installation  startup   and adjustment  To receive a copy of the instruction manual  contact  your local Sales Office or view a copy at www fisherregulators   com  For further information refer to  Type 1190 Instruction Manual     form 5307  D101644X012     P E D  Categories    This product may be used as a safety accessory with pressure  equipment in the following Pressure Equipment Directive 97 23   EC categories  It may also be used outside of the Pressure  Equipment Directive using sound engineering practice  SEP  per  table below     PRODUCT SIZES CATEGORIES FLUID  DN NPS TYPE    25 1 SEP  50  80  100  150 2 3 4 6 Il                            Specifications  Body Size and End Connection Styles  See Table 1    Main Valve Maximum Inlet Pressure     27 6 bar   400 psig or body rating limit whichever  is lower  DN 150   NPS 6 main valve is limited to  19 0 bar   275 psig and the DN 200 x 150    NPS 8 x 6 is limited to 16 0 bar   232 psig for PED  Category Il     Maximum Operating Inlet Pressure      13 8 bar   200 psig with cast iron construction  or 20 7 bar   300 psig with a steel or stainless  steel construction     Maximum Outlet  Casing  Pressure     5 2 bar   75 psig    Outlet Pressure Ranges     See Table 2    Maximum and Minimum Differential Pressures     See Table 3    Proof Test Pressure  All Pressure Retaining Components have been  proof tested per Direc
7. aphragm   Body Seal O Ring  Insert Seal   Disk Assembly   Stem   Cotter Pin   Lever Assembly  Machine Screw   Insert Guide   Hex Nut    Key Description    22  23  24  25    31  33  35  37  38  39  40  48  49  50  51    Closing Cap   Hex Nut   Cap Screw   Closing Cap Gasket   use with steel and stainless  steel closing caps    Throat Seal   Machine Screw   Adjusting Screw   Spring Holder   Machine Screw   Overpressure Spring   Pusher Post Connector   Post Seal   Back up ring   Connector Seal O Ring   Lower Diaphragm   Head Assembly    35A3167_E    34A5692_C    4    S 6        50  40    8  16       47B9749_C             APPLY SEALANT  S        167D Series    4 9                                           NA  pai                                                                            Figure 3  Type Y191A Assembly                      167D Series    Type 95H Parts List    Key Description    1 Body   2 Spring Case   3 Orifice   4 Valve Plug   5 Valve Plug Guide  6 Stem Assembly   7 Stem Guide Bushing  8 Lower Spring Seat  9 Upper Spring Seat  10 Valve Plug Spring  11 Spring   12 Diaphragm   15 Adjusting Screw  16 Cap Screw   17 Locknut   18 Drive Screw   56 NACE Tag   57 Tag Wire    Industrial Regulators    Emerson Process Management  Regulator Technologies  Inc     USA   Headquarters   McKinney  Texas 75069 1872  USA  Tel   1 800 558 5853   Outside U S   1 972 548 3574    Asia Pacific  Shanghai 201206  China  Tel   86 21 2892 9000    Europe  Bologna 40013  Italy  Tel   39 051 4
8. erve the right to modify or improve the designs or specifications    of such products at any time without notice     Emerson Process Management does not assume responsibility for the selection  use or maintenance of any product  Responsibility for proper selection  use and maintenance of any  Emerson Process Management product remains solely with the purchaser       Emerson Process Management Regulator Technologies  Inc   2002  2011  All Rights Reserved    m4  ERSON     SS   Mar nage ament       
9. tive 97 23 EC   Annex 1   Section 7 4     Maximum Temperature Capabilities     Nitrile  NBR    29   to 82  C    20   to 180  F  Fluorocarbon  FKM   4   to 149  C   40   to 300  F  Ethylenepropylene  EPDM    29   to 149  C    20   to 300  F  Perfluoroelastomer  FFKM    29   to 149  C    20   to 300  F    Type 1190    Installation    Only qualified personnel should install or service  a regulator  Regulators should be installed   operated  and maintained in accordance   with international and applicable codes and  regulations  and Emerson Process Management  Regulator Technologies  Inc  instructions     If the regulator vents fluid or a leak develops in  the system  it indicates that service is required   Failure to take the regulator out of service   immediately may create a hazardous condition     Personal injury  equipment damage  or leakage  due to escaping fluid or bursting of pressure   containing parts may result if this regulator   is overpressured or is installed where service  conditions could exceed the limits given in the  Specifications section  or where conditions  exceed any ratings of the adjacent piping or  piping connections     To avoid such injury or damage  provide  pressure relieving or pressure limiting devices   as required by the appropriate code  regulation   or standard  to prevent service conditions from  exceeding limits     Additionally  physical damage to the regulator  could result in personal injury and property  damage due to escaping fluid  To
    