1. The system is equipped with an audible alarm activated when summary alarm contacts are activated An ON OFF button is provided to silence the alarm and an alarm push to test button to test the alarm function A visible LED confirms whether alarm is on or disabled Both buttons and the audible alarm are located on the panel s front cover Agency Listing The specified unit is UL 1449 Second Edition Listed UL 1283 Listed and CUL Listed Control Concepts Liebert is also company certified ISO 9001 for manufacturing design and service Warranty A full five year parts warranty Form C Dry Contacts Two sets of electronically isolated form C dry contacts are provided two normally open two normally closed for remote monitoring Life Cycle Testing The system is life cycle tested to survive multiple 10kA 20KV IEEE C62 41 Category C3 transients with less than 5 degradation of clamping voltage The minimum numbers of surges the unit shall be able to protect against are 8 000 per phase Optional Features Integral Fused Disconnect A 200k AIC integral disconnect switch located within the system enclosure with an external manual operator Transient Counter The system can be equipped with a transient counter which totals transient surges that deviate from the sine wave envelop by more than 125 volts The counter is located on the unit s front cover and features an 8 digit LCD lithium batteries with 10 year
2. configurations from each column for your application Your completed model number should look similar to the example below or LM250120YARCE Refer to Chart B for LM Series dimensional data Chart A Example LM 250 120 Y A R c E j Model Surge Rating L G Voltage Configuration Modes of Cin Monitoring Options Enclosure L M 60kA mode 060 120 120V Single Phase L N 2W gnd N ALL A WireLug N Standard Monitoring NEMA 12 Standard E ji System LEDs 80kA mode 080 208 208V Single Phase L L 2W gnd L Disconnect R Audible Alarm NEMA 3R R 100kA mode 100 _220 220V Split Phase 3W gnd s DualFom NEMA 4 Li S NEMA 4X X z 5 125kA mode 125 230 230V Three Phase Wye 4W gnd Y LEDs Audible e 150kA model 150 240 240V Three Phase Delta 3W gnd D Alarm Surge Counter Dual 200kA mode 200 277 277V Three Phase Delta Hi leg 3W gnd H Form C Contacts 225kA mode 225 480 480V 250kA mode 250 600 600V ae E ia Chart B LM Series Dimensional Data EE i Dimensions inches Approx Weight ra li Unit Options A B C D E F araya I e aei LMOS0 TT B LM100 All 16 14 8 16 75 12 0 0 31 35 A L n n LM125 LM150 LM200 li j LM225 All 20 16 9 21 25 10 0 31 45 ety w t _ LM250 __ What is Dirty Power Utilities have generated and distributed electrical power the sam
3. life and reset switches Remote Monitor Panel Aself contained UL Listed monitoring panel Input power to the monitoring panel is equipped with a 6 foot power cord with a 3 NEMA 5 15 plug The monitor has an audible alarm red and green LEDs silence switch and a test switch Specifications LM Series Surge Suppression Life Cycle Surge Testing 10kA 20kV IEEE Cat C3 Maximum Continuous Unit Per Mode Per Phase Operating Voltage MCOV 120V 25 all others 15 060 080 8 000 16 000 Fault Current Rating AIC 200 kAIC 100 150 16 000 32 000 Operating Frequency Range 47 63 Hz 200 250 24 000 48 000 Response Time lt 0 5 nanoseconds Operating Humidity 0 to 95 EMI RFI Noise Rejection Status Indication LEDs Dry Contacts Audible Alarm Single Unit Frequency System Installation Certifications UL 1449 amp 1283 CUL NEMA LS1 ISO 9001 34dB 100kHz 51dB Enclosure NEMA 12 51dB 1MHz 94dB Warranty 5 Years Parts 54dB 10MHz 114dB UL 1449 Clamping Data Second Edition as an en System Voltage LN LG LL N G 120 208 400 400 700 400 120 240 400 400 700 400 346 600 1200 1200 2000 1200 277 480 700 700 1500 700 480 X 1500 1500 X 600 X 1800 2000 X How To Specify The Appropriate Model All LM model numbers begin with a LM prefix Use Chart A to build your LM starting with the Surge Rating column Moving left to right choose the correct
4. E Surge Protection For Business Critical Continuity Liebert LM Series Continuous Protection For Your Business n 4 gl EMERSON Network Power The LM Series The most advanced cost effective product line in the industry The LM is a surge protective device SPD that offers continuous protection from damaging transients and electrical line noise The LM utilizes patented circuitry to monitor the status of all protection modes including neutral to ground Should protection be unavailable in any mode the green LED will be extinguished and the red LED will be illuminated In addition high isolation form C dry contacts provide for remote monitoring of suppression system failure under voltage and phase and power loss LM patented suppression integrity monitoring indicates failure for both shorted or opened suppression components Standard LM Series SPD The LM Series can be a facility wide product family and may be installed from service entrances to distribution panels to branch panels m Commercial buildings a Institutional facilities a Industrial plants u Any facility that has an environment with electronics based equipment At A Glance Modular design allows for flexibility Surge suppression range up to 500 kA per phase a Industry s highest surge current repeatability m Internal external monitoring including neutral to ground UL rated 200k AIC with component level fusing for s
5. Kong 852 25722201 Phone 852 28029250 FAX liebert com Technical Support 800 288 6169 Toll Free 607 724 2484 Phone 607 722 8713 Fax While every precaution has been taken to ensure accuracy and completeness in this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2008 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice All names referred to are trademarks or registered trademarks of their respective owners Liebert is a registered trademark of the Liebert Corporation SL 22055 R04 08 Printed in USA Emerson Network Power EmersonNetworkPower com The global leader in enabling Business Critical Continuity E Ac Power E Embedded Computing E Outside Plant E Racks amp Integrated Cabinets j connectivity jl Embedded Power E Power Switching amp Controls E Services E Dc Power E Monitoring j Precision Cooling E surge Protection Business Critical Continuity Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co 2008 Emerson Electric Co
6. afe operation u All modes of protection standard any combination optional Sine wave tracking EMI RFI filtering u UL 1449 second edition UL1283 and CUL listed ANSI IEEE C62 11 C62 41 C62 45 categories A B and C3 tested Tested to NEMA LS1 m NEMA 12 enclosure with 3R 4 and 4X options available 5 year warranty u 2 sets of Form C dry contacts u Audible alarm m Choice of options Disconnect Transient counter Remote monitor panel Test set Standard Features Unit Status Indicators The unit has an integral status circuit that monitors the operational status of all modes of protection including Line to Neutral Line to Ground and Neutral to Ground In the unlikely event that protection is reduced the green LED will go out and the red LED will be lit LED indication shall be provided internal and external to the product Enclosure The unit is housed in a heavy duty steel NEMA 12 dust tight drip tight enclosure Undervoltage Detection System monitoring will indicate an undervoltage at 70 of nominal Phase and Power Loss Monitoring System monitoring will indicate a loss of any phase or loss of power Noise Attentuation The filter provides insertion loss up to 60 dB from 100 kHz to 100 MHz per 50 Ohm Insertion Loss Methodology from MIL Std 220A Overcurrent Protection All components are individually fused and unit is UL rated for 200k AIC for safe operation Audible Alarm
7. e way for decades Unfortunately this unconditioned electrical power can provide abnormalities in the electricity that runs in your facility This is commonly referred to as dirty power But until the advent of sensitive electronic equipment clean power was never an issue In today s world almost every business depends on relatively fragile micro electronics to run everything from computer networks to manufacturing lines Which means that power disturbances can disrupt or cripple equipment causing the loss of data productivity and money In fact downtime and damage caused by dirty power cost North American companies an estimated 26 billion a year Today s industries are looking for cost effective ways to intercept transients provide clean power in their facilities and safeguard their businesses from the astronomical and unnecessary cost of dirty power That s why Liebert designed the LM Series The causes of dirty power are as varied as the names used to describe it dirty power electronic rust surge spike transient fluctuation interruption or noise Fortunately abnormalities typically fall into one of two categories external or internal Hidden Problems Created By Dirty Power Unexplained system disruptions Errors and shutdowns of data transmission or scrambled and unreadable data Numerous unexplained server shutdowns and re boots m Component failure often well a
8. head of projected life span Causes Outside Your Facility Lightning natural disasters and inclement weather can cause high transient power line voltages that can adversely affect your power supply Utility switching and faults on the utility s distribution system can adversely affect the quality of your power before it even reaches your facility Why Many utility systems are aging and few power plants have been built over the last decade With increased demand for power their supply margins are dipping dangerously low The farther away from the source of power the greater the risk of power quality problems Causes Inside Your Facility According to some studies 3 4 of all power disturbances are caused by equipment inside your building If your facility is more then a decade old chances are the wiring was not designed to support the intensive use of electronic equipment In industrial facilities these problems are even more complex In fact any device that runs in cycles can create a drain or a surge when it switches on or off The more power the equipment uses the bigger the affect Even something as small as a copier or a laser printer can cause problems in sensitive equipment that share the same line The Complete Protection Experts Of course you can t control how power is distributed But you can protect the equipment in your facility from power surges and transients by installing equipment such as surge sup
9. pressors and filters The issues affecting each industry are varied In addition to the LM Series we offer a complete array of power conditioning solutions to meet a wide range of applications locations and budgets Influencing the Industry Liebert has received the UL 1449 Second Edition rating for the LM Series The fact that we re one of the first in the industry to receive this rating is proof that Liebert is leading the way with our engineering designs and over 30 years of experience Ensuring The High Availability Of Mission Critical Data And Applications Emerson Network Power the global leader in enabling business critical continuity Liebert Corporation ensures network resiliency and adaptability through a family of technologies EPP be ae Columbus Ohio 43229 including Liebert power and cooling technologies that protect and support Bb E ae ee a business critical systems Liebert solutions employ an adaptive architecture that Canada Only evra mis a z 614 888 0246 Phone Outside U S responds to changes in criticality density and capacity Enterprises benefit 614 841 6022 FAX from greater IT system availability operational flexibility and reduced capital Via leonardo Da tance equipment and operating costs len n dre eg pee Um 35028 Piove Di Sacco PD Italy 39 049 9719 111 Phone 39 049 5841 257 FAX Emerson Network Power Asia Pacific 7 F Dah Sing Financial Centre 108 Gloucester Rd Wanchai Hong