Home
        Emerson Fisher C1 Instruction Manual
         Contents
1.                                           NS  o ME   A9    1 5             S             NOTE     KEYS 11  21  29 ARENOT SHOWN    GE28280 B  E1070    Key 5  Bourdon Tube    A  SUBASSEMBLY  KEY NOS   SHOWN IN FIGURE 24 OR 25     PROPORTIONAL ONLY CONTROLLER                      PRESSURE RANGE MATERIAL     kPa Psig Stainless Steel  0 200 0 30 32B1243X012  0 200 0 30 32B1243X212 2   0 400 0 60 32B1243X022  0 400 0 60 32B1243X172 2   0 700 0 100 32B1243X032  0 700 0 100 32B1243X202 2   0 1400 0 200 32B1243X042  0 1400 0 200 32B1243X162 2   0 2000 0 300 32B1244X052  0 2000 0 300 32B1244X1520   0 4000 0 600 32B1244X062  0 4000 0 600 32B1244x1820   0 7000 0 1000 32B1244X072  0 7000 0 1000 32B1244X1920   0 10 000 0 1500 32B1245X082  0 20 000 0 3000 32B1245X092  0 35 000 0 5000 32B1245X102  0 55 000 0 8000 32B1245X112  0 70 000 0 10 000 32B1245X122             1  Bourdon tubes are also available in NACE compliant material  Contact your Emerson Process Management sales office for additional information     2  For oxygen service         Recommended spare parts    43       C1 Controllers and Transmitters  May 2014    Instruction Manual  D103292X012       Figure 23  Typical Reverse Acting Fisher C1 Proportional Plus Reset Assembly     Refer to figure 26 for the Front View of the Case  amp  Cover Assembly     DO          ue                i                                                                    OE n           e                                                                    
2.                           a    SPRING OUT CLEANING WIRE  RELAY ASSEMBLY                                           D d                                                                                                                                                                NOTE   KEYS 11  21  22  29 ARE NOT SHOWN    GE28281 B  E1071             s                       6                                                                                           SUBASSEMBLY  KEY NOS   SHOWN IN FIGURE 24 OR 25     PROPORTIONAL PLUS RESET CONTROLLER  WITHOUT ANTI RESET WINDUP    Key Description    23  Control Tubing Assembly  SST vinyl  used with NACE compliant Bourdon tube  24  Relay Tubing Assembly  304 SST    25  Compensator Tubing  304 SST    26   27     Reset Tubing  304 SST  Compensator Tubing  304 SST  2 req d     28  VentAss y  29 Machine Screw 2   18 8 SST  not shown   2 req d   30 NPT Adaptor  aluminum  31  Link bearing    541600  Bourdon tube instruments only  2 req d     32 Rotary Spring  330400  33  Bellows Stud  brass  not shown     34 Spacer   35 Pressure Set Arm  G10080 carbon steel  zinc pl  36 Calibration Adjuster   37 Reversing Block     233520 zinc die casting  38  Sleeve     POM  polyoxymethylene     44    Part Number    1H3011X0032  GE33948X012    GE28421X012    GE30128X012  GE29222X012    1L379546202    Key    39  40  41  42  43    44  45  46    Description Part Number    Beam  G10080 carbon steel  zinc pl   Flapper    330100 SST   Machine Screw  steel pl 
3.           0    cece eee eee  Calibration  Anti Reset Windup             Startup  Proportional Plus Reset  Controllers             02  cece ee eee eee  Differential Gap Controllers                     Adjustments              cece eee eee eens  Adjustment  Set Point                    Adjustment  Proportional Band            Calibration  Differential Gap Controllers       Startup  Differential Gap Controllers           Transmitter Operation                   00008    Adjustments             0 0c cece cece rre  Adjustment  Zero     Adjustment  Span              e cece ee eee    Figure 1  Fisher C1 Controller Yoke Mounted on  Control Valve Actuator       Calibration  Transmitters                  0   24  Startup  Transmitters                    eee 26  Principle of Operation                 2  eee eee 27  Proportional Only Controllers                   27  Proportional Plus Reset Controllers              28  Controllers with Anti Reset Windup             28  Differential Gap Controllers                    28  Transmitters  22 5 oL EAE PET EVER ER 29  Maintenance           eee eee eee eee eee eee 30  Replacing Gauges           llle  30  Replacing Bourdon Tube                  ee 31  Replacing Bellows Sensing Element              32  Changing Proportional or Reset Valve            33  Changing Anti Reset Windup Differential  Relief Valve    33  Changing Action               2  cece eee eee eee 33  Proportional Only to a Differential  Gap Controller                  0000 eee 33  Re
4.        Table 6  Common Signal Pressure Conversions                                     Mps kg cm2 bar kPa Psi  0 02 0 2 0 2 2  200  3  0 03 0 3 0 3 35 5  0 04 0 4 0 4 400  6  0 05 0 5 0 5 50 7  0 06 0 6 0 6 60 9  0 07 0 8 0 8 75 11  0 08 0 8 0 8 80 12  0 09 1 0 1 0 95 14  0 10 1 00  1 002 1000  15  0 12 1 3 1 2 125 18  0 14 1 4 1 4 140 20  0 15 1 5 1 5 150 22  0 17 1 8 1 7 170 25  0 18 1 9 1 9 185 27  0 20 2 0 2 00  200 1  30  0 22 2 2 2 2 220 32  0 23 2 3 2 3 230 33  0 24 2 5 2 4 240 35  0 34 3 5 3 4 345 50  0 55 5 6 5 5 550 80  0 69 7 0 6 9 690 100  1 03 10 5 10 3 1035 150   1  Values as listed in ANSI S7 4    2  Values as listed in IEC Standard 382    3  Values rounded to correspond with kPa values           Installation    A WARNING    To avoid personal injury or property damage resulting from the sudden release of pressure   e Always wear protective clothing  gloves  and eyewear when performing any installation operations     e Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and  appropriate preventive measures are not taken  Preventive measures may include  but are not limited to  one or more  of the following  remote venting of the unit  re evaluating the hazardous area classification  ensuring adequate  ventilation  and the removal of any ignition sources  For information on remote venting of this controller  transmitter   refer to page 11     e If installing into an existing application  also refer to t
5.    C1 Controllers and Transmitters  May 2014       Parts Kits    Description Part Number    Controller Repair Kits  Kit includes Gasket  Relay Gasket  Bellows Frame  Gasket  and keys 16  20  21  31  37  38  40  46  49   50  54  62  75  76  and 77    Note    Keys 71K  71L  and 71M may also be necessary for repair of C1B and C1D  controllers  Refer to the Common Parts section for part numbers     RC100X00L12  RC100X00H12    Standard Temperature  High Temperature    Relay Replacement Kits  Kit includes keys 19 and 29  the replacement relay  and  2 Machine Screws    Standard Temperature RRELAYXOL22  High Temperature RRELAYXOH22  Case Assembly Seal Kit  Kit includes 3 Manifold Seals  1 Manifold Cover   and 10 Mounting Screws RC100X00012    Parts List    Common Parts  Figures 22  23   24  and 25     Key Description Part Number    Note    Part numbers are shown for recommended spares only  For part  numbers not shown  contact your Emerson Process Management sales  office     1 Case and Cover Assembly  aluminum     Recommended spare parts    Key Description Part Number    Note    Key 2 is used as both a supply gauge and an output gauge on units  without a process pressure gauge  A quantity of 2 is required for these  units  On units with a process pressure gauge  key 106   key 2 is used for  the output gauge  A quantity of 1 is required for these units    Use key 3 for supply pressure indication when a process pressure gauge  is installed  Key 3 installs on the supply pressure regula
6.   Action of a proportional plus reset controller is similar to that of a proportional only controller except that feedback  from the controller output pressure is piped to a reset bellows as well as to the proportional bellows as shown at the  right in figure 13     With an increasing controller output pressure  pressure in the reset bellows increases  Increases in reset bellows  pressure moves the beam and flapper closer to the nozzle  starting another increase of pressure throughout the  system  Pressure buildup continues until the controlled pressure is brought back to the set point  The reset valve is  adjustable to vary the amount of delay in the reset action  Closing the reset valve increases the delay in reset action     Controllers with Anti Reset Windup    During a prolonged difference between set point and the controlled variable  such as encountered with intermittent  control applications  e g   batch temperature control or wide open monitors on pressure control   reset ramps the  controller output to either zero or full supply pressure  this condition is reset windup  When the controlled variable  crosses the set point  there will be a delay before the controller output responds to the change in controlled variable   Anti reset windup minimizes this delay and permits returning the controlled variable to set point more quickly with  minimal overshoot     As shown in figure 14 a proportional plus reset controller with anti reset windup includes a differential relief
7.  100  of the sensing element range  for 0 4 to 2 0 bar  6 to 30 psig     Differential Gap Adjustment    For Differential Gap Controllers   Full output pressure change adjustable from  15  to 100  of sensing element range    Reset Adjustment    For Proportional Plus Reset Controllers  Adjustable  from 0 01 to 74 minutes per repeat  100 to 0 01  repeats per minute     Zero Adjustment  Transmitters Only     Continuously adjustable to position span of less than  100  anywhere within the sensing element range    Span Adjustment  Transmitters Only     Full output pressure change adjustable from 6 to  100  of sensing element range    Performance    Repeatability  0 525 of sensing element range  Deadband  Except Differential Gap Controllers  4    0 1  of sensing element range   Typical Frequency Response at 100  Proportional  Band   Output to Actuator  0 7 Hz and 110 degree phase shift  with 1850 cm   113 inches   volume  actuator at  mid stroke   Output to Positioner Bellows  9 Hz and 130 degree  phase shift with 0 2 to 1 0 bar  3 to 15 psig  output to  33 cm   2 inches   bellows     continued     C1 Controllers and Transmitters  May 2014    Instruction Manual  D103292X012       Table 1  Specifications  continued        Ambient Operating Temperature Limits     Wi Standard Construction   40 to 71  C   40 to 160 F   E High Temperature Construction   18 to 104  C   0 to 220  F   Anti reset windup  differential pressure relief  and  process pressure gauge options are only available in  
8.  4 req d    Flexure Strip  S30200   Flexure Strip Washer  G10200 carbon steel  2 req d     Washer  18 8 SST  2 req d   Washer  steel pl  2 req d   Machine Screw     steel pl    Machine Screw  steel pl  4 req d   Machine Screw  18 8 SST  2 req d   Sealing Screw 1   SST   Reversing Block Screw 1   SST    Cap Screw  18 8 SST  8 req d   Reversing Bellows Ass y  SST  2 req d   Bellows Screw  18 8 SST  2 req d   Nozzle 1   SST   Machine Screw  steel pl  2 req d   Machine Screw  18 8 SST  4 req d   Mounting Base  aluminum    14A5725X022    1U639135132     Recommended spare parts    1  This part is included in the Controller Repair Kit   2  This part is included in the Relay Replacement Kit     Instruction Manual  D103292X012    C1 Controllers and Transmitters    May 2014       Figure 23  Typical Reverse Acting Fisher C1 Proportional Plus Reset Assembly  continued    Refer to figure 26 for the Front View of the Case  amp  Cover Assembly     M  RELAY ASSEMBLY    236  98                                                                                                             r  SPRING OUT CLEANING WIRE    D                                                                                                                                                                                                                         Orne     D sie CE olo   9 4  amp     O P  CACAD y y      o  TK G SS 1b i i A  SSE AA    paces  NOTES  ojo     1   ARROW DOWN   RELIEVES ON DECREASING OUTPUT  OUTPUT   
9.  49  with an O ring in the hole previously covered by the reversing block assembly     7  Check all connections for leaks with a soap and water solution  Perform the appropriate calibration procedures     Relay Replacement  Key numbers used in this procedure are shown in figure 22 or 23 except where indicated     1  Shut off the supply pressure and process pressure line s  to the controller or transmitter   2  Disconnect the tubing  key 24  from the relay    3  Unscrew the output or supply pressure gauge  key 2     4      To remove the relay assembly  unscrew two Phillips head machine screws  key 29  not shown  located behind the  relay on the back of the case     U1      Remove the relay gasket  key 19  figure 22        A new relay can be installed as a replacement  If a new relay is being installed  continue with the next step     N O      Attach the replacement relay and new relay gasket with machine screws inserted through the back of the case   Reinstall the output or supply gauge     8  Connect the tubing  and check all connections for leaks  Perform the appropriate calibration procedures     36    Instruction Manual  D103292X012    C1 Controllers and Transmitters  May 2014       Changing Output Signal Range    Use the following information and subsequent procedures when changing the output signal range of the controller or    transmitter  Use the following procedure     e Foracontroller or transmitter  use this procedure to change from a 0 2 to 1 0 bar  3 to 15 psig  t
10.  above example  this pressure is  5 5 bar  80 psig      b  Increase pressure to the sensing element while monitoring the output pressure gauge  The controller output  pressure should switch from zero to full supply pressure when the upper switching point is reached with rising  input pressure     Note    If the upper switching point is not correct  adjust the nozzle to correct the error  Repeat step 6b until the input pressure and upper  switching point are at the desired setting     22    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       c  With falling input pressure  the output should switch from full supply pressure back to zero when the lower  switching point is reached     Reverse acting controllers produce the opposite response     7  Vary the process pressure and observe the switching points  Widen or narrow the differential gap by rotating the  proportional band adjustment knob  then repeat the above steps     If the output is within the limits stated  refer to the startup procedures in this section  If the output pressure cannot  be adjusted within the limits stated  refer to the maintenance procedures     Startup  Differential Gap Controllers    Calibrate the controller prior to this procedure     1  Besure that the supply pressure regulator is delivering the proper supply pressure to the controller   2  Adjust the proportional band setting for the proper differential gap  see figure 10      3  If the controller is used in conjunction w
11.  accommodate a different control tubing assembly  key 23  with a pressure connection  key 14  for a  process pressure gauge  If a supply pressure gauge is required  a gauge with a 1 4 inch connecting stem  key 3  must  be mounted on the supply pressure regulator     CAUTION    Before performing this procedure  be sure the replacement gauges are the correct range so they are not damaged by  overpressure     30    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Note    Key 2 is used as both a supply gauge and an output gauge on units without a process pressure gauge  A quantity of 2 is required for  these units  On units with a process pressure indicator gauge  key 4   key 2 is used for the output gauge  A quantity of 1 is required  for these units     Use key 3 for supply pressure indication when a process pressure gauge is installed  Key 3 installs on the supply pressure regulator     1  Shut off the supply pressure and process lines to the controller or transmitter   2  Remove the gauge to be replaced     e Unscrew the output or supply gauge  key 2  from the relay base   e Unscrew the process pressure gauge  key 4  from the process connection  key 14    e Unscrew the supply gauge  key 3  from the supply pressure regulator     3  Coatthe threads of the replacement gauge with a sealant   4  Screw the replacement gauge into the relay base  process connection  or supply pressure regulator     5  Check for leaks by applying the correct supply pressu
12.  adjust the controller span by loosening the two  adjusting screws  key 48  and moving the calibration adjuster  key 36  a small distance as indicated in figure 5     10  Repeat steps 4 through 9 until no further adjustment is necessary     11  Proceed to the startup procedure for proportional controllers     Figure 5  Reverse Acting Controller Span Adjustment     Proportional Only Controllers       IF OUTPUT IS   ABOVE BELOW  8TO 10 PSIG 8 TO 10 PSIG   0 6 TO 0 7 BAR   0 6 TO 0 7 BAR   MOVE ADJUSTER ipu     MOVE ADJUSTER  LEFT RIGHT    FLAPPER  NOZZLE    NOTE    3 TO 15 PSIG  0 2 TO 1 0 BAR  OUTPUT SHOWN   FOR 6 TO 30 PSIG  0 4 TO 2 0 BAR  OUTPUT  ADJUST  VALUES AS APPROPRIATE     A6155 1    13    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       For direct acting controllers    4  Apply an input pressure equal to the sensing element lower range value    5  Rotate the pressure setting knob to the minimum value    6  Adjust the nozzle  key 54  until the controller output pressure is between 0 6 and 0 7 bar  8 and 10 psig    7  Apply an input pressure equal to the sensing element upper range value     8  Rotate the pressure setting knob to the maximum value     Note    When performing the span adjustment in step 9  do not watch the output gauge while changing the calibration adjuster  The  change in output is not a good indication of the change in span  While moving the calibration adjuster  the output pressure may  change in the opposite direction
13.  req d   1061 sizes 30  80 and 100  2 req d   Street Elbow  pl galvanized malleable iron  not shown   For mounting on 470  472  480  513  656   657  667  panel  pipe stand  1051  1052 and 1061  w nipple mounted filter regulator    Pipe Nipple  pl galvanized steel  not shown   For mounting on 470  472  480  513  656   657  panel  pipe stand  1051  1052 and 1061  w nipple mounted filter regulator    Clamp  Steel  For pipe stand mounting  2 req d     Bracket Assembly  steel  For panel or wall mounting  2 req d     Cap Screw  steel pl  For panel or wall mounting  4 req d     Specify quantity of fittings     Connector  Brass    1 4 NPT X 1 4 O D  tubing  1 4 NPT X 3 8 O D  tubing    Elbow  Brass    1 4 NPT X 1 4 O D  tubing  1 4 NPT X 3 8 O D  Tubing    Instruction Manual  D103292X012    C1 Controllers and Transmitters  May 2014       51    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Neither Emerson  Emerson Process Management  nor any of their affiliated entities assumes responsibility for the selection  use or maintenance  of any product  Responsibility for proper selection  use  and maintenance of any product remains solely with the purchaser and end user     Fisher is a mark owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co  Emerson Process Management   Emerson  and the Emerson logo are trademarks and service marks of Emerson Electric Co  All other marks are the property of their respective o
14.  than expected  For example  while moving the calibration adjuster to increase span  the output  pressure may decrease  This should be disregarded since even though the output pressure decreases  the span is increasing     Proper controller response depends on nozzle to flapper alignment     When performing span adjustments  carefully loosen both calibration adjuster screws while holding the calibration adjuster in  place  Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver  Verify proper  nozzle to flapper alignment and hold the calibration adjuster in place while tightening both adjustment screws     9  If the output is not between 0 6 and 0 7 bar  8 and 10 psig   adjust the controller span by loosening the two  adjusting screws  key 48  and moving the calibration adjuster  key 36  a small distance as indicated in figure 6     10  Repeat steps 4 through 9 until no further adjustment is necessary   11  Proceed to the startup procedure for proportional controllers   Figure 6  Direct Acting Controller Span Adjustment   Proportional Only Controllers    IF OUTPUT IS        BELOW ABOVE  8TO 10 PSIG 8 TO 10 PSIG   0 6 TO 0 7 BAR   0 6 TO 0 7 BAR   MOVE ADJUSTER ag       JB    MOVE ADJUSTER  LEFT RIGHT    NOZZLE    NOTE    3 TO 15 PSIG  0 2 TO 1 0 BAR  OUTPUT SHOWN   FOR 6 TO 30 PSIG  0 4 TO 2 0 BAR  OUTPUT  ADJUST  VALUES AS APPROPRIATE    A6154    14    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       
15.  the following procedures    For reverse acting controllers    6  Apply an input pressure equal to the sensing element upper range value    7  Rotate the pressure setting knob to the maximum value    8  Adjust the nozzle  key 54  until the controller output pressure is between 0 6 and 0 7 bar  8 and 10 psig    9  Apply an input pressure equal to the sensing element lower range value     10  Rotate the pressure setting knob to the minimum value     Note    When performing the span adjustment in step 11  do not watch the output gauge while changing the calibration adjuster  The  change in output is not a good indication of the change in span  While moving the calibration adjuster  the output pressure may    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       change in the opposite direction than expected  For example  while moving the calibration adjuster to increase span  the output  pressure may decrease  This should be disregarded since even though the output pressure decreases  the span is increasing     Proper controller response depends on nozzle to flapper alignment     When performing span adjustments  carefully loosen both calibration adjuster screws while holding the calibration adjuster in  place  Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver  Verify proper  nozzle to flapper alignment and hold the calibration adjuster in place while tightening both adjustment screws     11  If the outp
16.  transmitter     2  Disconnect the tubing from the mounting base  key 57  and calibration adjuster  key 36   Disconnect the tubing  that connects the pressure block  key 8  figure 22  to the bellows assembly  key 71   at the pressure block end     3  Unscrew the four machine screws  key 41  figure 22 or 23   and remove the pressure sensing subassembly from the  case     4  Remove the bellows yoke machine screws and washers  keys 98 and 99   and move the bellows yoke to the right to  permit access to the link screw     5  Disconnect the link  key 71M  and bearing  key 71L  from the beam  Be careful to avoid losing the bearing    6  Loosen the nuts that secure the bellows assembly  key 71   and remove this assembly from the bellows yoke   key 100     7  Fora gauge pressure sensing element  only one bellows in the assembly   install the proper bellows spring   key 104  into the bellows assembly if the input signal range is being changed    8  Install the new bellows assembly into the bellows yoke     9  Attach the link and bearing to the bellows assembly  Position the bellows yoke  key 100  on the mounting base   key 57   and attach the link and bearing to the beam  Start but do not tighten the four machine screws  key 98   with washers  key 99  that attach the yoke to the mounting base  Slide the yoke up or down as necessary to position  the beam horizontally  as shown in figure 25  Tighten the machine screws     10  Replace the subassembly in the case and secure with the four 
17.  valve   The valve consists of two pressure chambers separated by a spring loaded diaphragm     For the controller shown in figure 14  proportional pressure registers rapidly on the spring side of the relief valve  diaphragm as well as in the proportional bellows  and reset pressure registers on the opposite side of the relief valve  diaphragm  As long as controlled pressure changes are slow enough for normal proportional and reset action  the  relief valve spring will keep the relief valve diaphragm from opening  However  a large or rapid decrease in controller  pressure will cause the relay to exhaust loading pressure from the control device rapidly  and also from the  proportional system and spring side of the relief diaphragm  If this decrease on the spring side of the diaphragm is  greater than the relief valve spring setting  the diaphragm will move off the relief valve orifice and permit the  proportional pressure on the opposite side of the relief valve diaphragm to bleed rapidly into the reset bellows  The  anti reset windup action also can be reversed to relieve with an increasing proportional pressure     Differential Gap Controllers    With a differential gap controller  feedback pressure does not counteract the change in flapper position as it does in a  proportional only controller  Instead  feedback pressure is piped to the bellows located on the side of the beam and  flapper opposite the nozzle  the proportional bellows in figure 13   Then  as controller outpu
18. 00 115 1650  0 to 200 0 to 3000 200 3000 230 3300  0 to 350 0 to 5000 350 5000 380 5500  0 to 550 0 to 8000 550 8000 550 8000  0 to 700 0 to 10 000 700 10 000 700 10 000                            1  If the process can trip to a pressure outside of the operating range of the sensing element  a commercially available device  such as an overpressure protector  may be used to protect  against pressure surges and pulsations    2  Range marked on Bourdon tube may be in kPa  1 bar   100 kPa    3  Bourdon tube may be pressurized to limit shown without permanent zero shift    4  With travel stop set at 110  of the range    5  Bourdon tubes are also available in NACE compliant material  Contact your Emerson Process Management sales office for additional information        Table 4  Bellows Pressure Ranges and Materials                                  MAXIMUM ALLOWABLE STATIC  PRESSURE LIMITS 2   PRESSURE RANGES    Brass Stainless Steel  Construction Construction  Bar Psig Bar Psig  0 to 150 mbar  0 to 60 inch wc  1 4 20 zz E  Vacuum 0 to 340 mbar  0 to 10 inch Hg  2 8 40 E ere  0 to 1 0 bar  0 to 30 inch Hg  2 8 40 6 9 100  75 mbar vac  to 75 mbar  30 inch wc vac  to 30 inch wc  1 4 20          Compound Pressure 500 mbar vac  to 500 mbar  15 inch Hg vac  to 7 5 psig  2 8 40 6 9 100  1 0 bar vac  to 1 0 bar  30 inch Hg vac  to 15 psig  2 8 40 6 9 100  0 to 150 mbar  0 to 60 inch wc  1 4 20 ux um  Gauge Pressure 0 to 250 mbar   0 to 100 inch wc  1 4 20     E  0 to 350 mbar 4   0 to 140 
19. 73604142  bellows sensing instruments only  2 req d  1A331928982 i  71L  Bearing   76  Nozzle O Ring     bellows sensing instruments only  2 req d  1L379546202 Std Temp  nitrile 1E222606992  71M  Link 4  bellows sensing instruments only 1L379641012 High Temp  fluorocarbon 1N838706382     Recommended spare parts    1  This part is included in the Controller Repair Kit   keys 101  102  and 103 if you do not have them   46 4  This part is part of the bellows assembly  key 71     Instruction Manual  D103292X012    C1 Controllers and Transmitters  May 2014       Figure 25  Controller Subassembly with Either Gauge Pressure Bellows or Differential Pressure Bellows Sensing    Element                LINK  KEY 71M   lt 1                 nS  SZZ aal     A        e             Lol  wows       KS       ZS    PS  7     cec    27772222227    SECTION B B    71       CD LINK  KEY 71M           SCREW  KEY71K           BEARING  KEY 711  C         100       47       43 71    SIDE VIEW OF SUBASSEMBLY  WITH GAUGE PRESSURE  BELLOWS SENSING ELEMENT       NOTES    KEYS 33  46 AND 74 ARE NOT SHOWN   KEY 52 IS FEEDBACK BELLOWS    I gt  KEYS 71K  71L   amp  71M ARE PART OF THE BELLOWS ASSEMBLY  KEY 71        GE35161 A  GE34735 C         SCREW  lt 7    KEY 71K     BEARING  lt 1    KEY 71L                 47 100       43       SIDE VIEW OF SUBASSEMBLY WITH DIFFERENTIAL  PRESSURE BELLOWS SENSING ELEMENT    47    C1 Controllers and Transmitters  May 2014    Instruction Manual  D103292X012       Key Descript
20. E INDICATION    SUBASSEMBLY   KEY NOS  SHOWN  IN FIGURE 24 OR 25     Description Part Number  Connecting Link     Bourdon tube instruments only  Std   18 8 SST 1L379641012    Connecting Link  Bourdon tube w optional travel stop   18 8 SST    Lockwasher  steel pl  2 req d   Use w optional Bourdon tube travel stop    Machine Screw  steel pl  2 req d   Use w optional Bourdon tube travel stop    Relay Gasket 1     Std Temp  chloroprene 10897403012  Hi Temp  silicone 1N873804142  O Ring   nitrile 10376206992  Gasket 1   chloroprene   not shown  1C328603012  Mounting Screw for reset restriction valve  1 4 20 UNC  steel pl  not shown   Control Tubing Assembly  304 SST  For Bourdon tube instruments  w o process pressure gauge  Std  1H3011000A2  Oxygen Service 1H3011X0012  w process pressure gauge 1J2530000A2     Recommended spare parts  1  This part is included in the Controller Repair Kit     Instruction Manual    D103292X012    C1 Controllers and Transmitters  May 2014       Figure 22  Typical Reverse Acting Fisher C1 Assembly  continued    Refer to figure 26 for the Front View of the Case  amp  Cover Assembly     SPRING OUT CLEANING WIRE             il eae                                                                                     ig                                                                                                                      Epress CE  AO                                                                                                                 
21. Install the anti reset windup assembly  key 190  with the arrow  pointing in the direction recorded in step 1     14  Proceed to the Startup procedures for proportional plus reset controllers     Figure 9  Direct Acting Controller Span Adjustment    Proportional Plus Reset Controllers       IF OUTPUT IS   BELOW ABOVE  8TO 10 PSIG 8TO 10 PSIG   0 6 TO 0 7 BAR   0 6 TO 0 7 BAR   MOVE ADJUSTER apu     MOVE ADJUSTER  LEFT RIGHT    FLAPPER   NOZZLE    NOTE   3 TO 15 PSIG  0 2 TO 1 0 BAR  OUTPUT SHOWN   FOR 6 TO 30 PSIG  0 4 TO 2 0 BAR  OUTPUT  ADJUST  VALUES AS APPROPRIATE    A6154    Calibration  Anti Reset Windup    Controllers with anti reset windup have a differential relief valve assembly  figure 23   This relief valve is set at the  factory to relieve at a 0 3 bar  5 psi  pressure difference between the reset bellows pressure and the proportional  bellows pressure  The valve can be adjusted to relieve from 0 14 to 0 4 bar  2 to 7 psig      The relief valve can relieve on either rising controller output pressure or falling controller output pressure  If the arrow   on the relief valve points toward the bottom of the controller case as shown in figure 23  the valve will relieve on falling  output pressure  If the arrow points in the opposite direction  the valve will relieve on rising output pressure  The valve  can be removed and reinstalled with the arrow pointing in the opposite direction to change the relief action     C1 Controllers and Transmitters Instruction Manual  Ma
22. Instruction Manual  D103292X012    C1 Controllers and Transmitters  May 2014       Fisher   C1 Pneumatic Controllers and    Transmitters    Contents    Introduction 1 0    ee eee e cece cece eees  Scope of Manual               0 0 cece eee eee  DOSERPEON   ree tte ee etd  Specifications  Sages a aet mn Rene  Educational Services            c cece eee eee ees   Installation  i 2  ker eee RR e aeg  Standard Installation                   00 00 eee  Panel Mounting              c cece cece cece eee  Wall Mounting              cece eee cece e eee  Pipestand Mounting                e eee ee eens  Actuator Mounting                eee eee eee eee  Pressure Connections                 eee eee eee   Supply Pressure               00 cece eee eee  Process Pressure             2s eee e eee eee  Vent Assembly              000 c cece eee ee eee   Controller Operation              0 0  e eee   Proportional Only Controllers                    Adjustments             c cece cece eee ee  Adjustment  Set Point                    Adjustment  Proportional Band            Calibration  Proportional Only Controllers        Startup  Proportional Only Controllers         Proportional Plus Reset Controller               Adjustments             c cece cece e eee  Adjustment  Set Point                    Adjustment  Proportional Band            Adjustment  Reset               00000e  Adjustment  Anti Reset Windup            Calibrations    225 ERE EE RR  Calibration  Proportional Plus Reset  Controllers  
23. May 2014    Instruction Manual  D103292X012       Figure 22  Typical Reverse Acting Fisher C1 Assembly     Refer to figure 26 for the Front View of the Case  amp  Cover Assembly        SPRING OUT CLEANING WIRE  RELAY ASSEMBLY                                                                                                                                                                  NOTE     GE34729 B  GE31719 A    E1069    Key                                                    toe                                                                                                                                              KEYS 11  21  AND 29 ARE NOT SHOWN  TRANSMITTER  Description Part Number  Bourdon Tube See following table    12  13    42    Dial  aluminum  Screw  nylon  transmitters only     Cantilever Spring  330200  3 15 psi range  6 30 psi range  Nameplate  aluminum    GE31702X012  GE31701X012    Control Pressure Block  For gauge pressure instruments  w o process pressure gauge  CF8M FMS 20B58 for standard  NACE and oxygen service  w process gauge  SST  Plug   31600  not shown   used with gauge pressure only  1 req d for standard NACE  2 req d for oxygen service    Machine Screw  steel pl  4 req d   Lockwasher  steel pl zn pl  4 req d     Pressure Connection   31600  Use w process gauge  Pipe Plug  steel pl  not shown   Use w process gauge  not used w Bourdon tube protector    Key    16     16    17    18    19     20   21     22    23           OPTIONAL PROCESS PRESSUR
24. SUPPLY DURING SHUTDOWN    2 gt  ARROW UP   RELIEVES ON INCREASING OUTPUT  OUTPUT   ZERO DURING SHUTDOWN   KEYS 80  81  AND 82 ARENOT SHOWN       GE31718 A    1072    PROPORTIONAL PLUS RESET CONTROLLER WITH                   DIFFERENTIAL RELIEF VALVE ASSEMBLY FOR ANTI RESET WINDUP    Key Description Part Number    58 Knob  PPS  polyphenylene sulfide   59 Knob Spring  steel zinc pl    60 Washer  G10100 carbon steel  zinc pl  61 Machine Screw  steel pl  62 Washer   brass zinc pl  2 req d     63 Gain Adj Bar  A03600  64 Washer  18 8 SST    65 Spring Adjustor  18 8 SST    66  TravelStop Assembly  SST  Use w optional Bourdon tube travel stop  67  Inner Flexure   30200 GE26663X012    68  Outer Flexure  530200 GE26664X012  69 Indicator Scale  aluminum  70 Bias Spring  SST     Recommended spare parts   1  This part is included in the Controller Repair Kit    3  If ordering the bellows  key 71  to change the range of a gauge pressure controller   also order the appropriate bellows spring  key 80   Also order keys 101  102  and 103  if you do not have them     Key Description    71  Gauge Pressure Bellows  input  3   Brass          Part Number    0 150 mbar  0 60 inches wc  positive  0 150 mbar     6 60 inches wc  vacuum  and 75 0 75 mbar   30 0 30 inches wc  compound  0 250 mbar  0 100 inches wc  positive  0 0 35 mbar  0 5 psig  positive and for  0 350 mbar  0 10 inches Hg  vacuum  0 0 5 bar  0 7 5 psig  positive  0 0 7 bar  0 10 psig  positive  0 1 0 bar  0 15 psig  positive  0 1 0 ba
25. Startup  Proportional Only Controllers  General Tuning Guidelines   Calibrate the controller prior to this procedure   1  Besure that the supply pressure regulator is delivering the proper supply pressure to the controller     2  Rotate the pressure setting knob to the desired set point     3  Setthe proportional band adjustment to 100 percent for fast processes  example  liquid pressure or liquid flow   For  slow processes  example  temperature   calculate the percentage from the equation below     For a slow process  determine the initial proportional band setting in percent from the following equation     2 x Allowable Overshoot     100    P B   Pressure Span       For example     2 x 0 14 bar    51 bar x 100    13     2 X 2psig    100    13   30 psig    li    1 3 proportional band setting  4  Proportional Action    Disturb the system by tapping the flapper lightly or change the set point a small amount and check for system cycling   If the system does not cycle then lower the proportional band  raising the gain  and disturb the system again   Continue this procedure until the system cycles  At that point  double the proportional band setting     Note    Proportional band adjustment affects the set point  Proportional only controllers will show some offset from set point depending  upon proportional band setting and process demand  After adjusting the proportional band  re zero by carefully rotating the  nozzle  key 54  until the steady state process pressure equals the pr
26. X012  For proportional plus reset controllers  w  anti reset windup 19A4363X012     Recommended spare parts    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Figure 26  Front View of Case and Cover Assembly    COMPRESSION PLUGS    2 PSIG LABEL   USE WITH 2 PSIG CASE AND COVER  ASSEMBLY  INSIDE COVER                                                                                                                                                                                               CHANGE ACTION  LABEL  INSIDE COVER   SECTION B B  o  B  ojo  BN x   o o O  eee  ON 2X ROLL PIN o  B  L       A ATEX MARKING COVER ASSEMBLY Pa CASE ASSEMBLY  SECTION A A    GE28278 A  E1075    49    C1 Controllers and Transmitters  May 2014    Instruction Manual  D103292X012       Mounting Parts for Panel  Wall   Pipestand  or Fisher Actuator  Mounting  figures 2 and 3     Key Description    Note    Contact your Emerson Process Management sales office for C1  mounting FS number     213 Mounting Plate  steel  For yoke mounting on  470  472  513  656  657 and 667  For yoke mounting on 480  Vertical  For yoke mounting on 1051 and 1052  Size 40  positions 1 and 3 w switch and  Size 60  position 1 w switch  All others  213 Mounting Plate  steel  continued   For yoke mounting on 1061 Size 30   positions 1 and 3 w switch and position 1 w o  switch  Size 40  position 1 w switch and  Sizes 80 and 100  position 3 w o switch  All others  For pipe stand mounting    215 Machin
27. Y 256     RESET VALVE   KEY 256     RESET TUBING RESET TUBING       RELAY TUBING  KEY 27  RELAY TUBING  KEY 27    KEY 24  PROPORTIONAL TUBING ee  PROPORTIONAL   KEY 27  REVERSING BLOCK TUBING  KEY 27   PROPORTIONAL  KEY 37  BELLOWS    BAND ASSY DIRECT ACTING    POSITION    FLAPPER SCREW     KEYS 40 AND 46   KEYS 40 AND 46     REVERSE ACTING  POSITION    REVERSING BLOCK   KEY 37           PROPORTIONAL  BAND ASSY       REVERSE ACTING DIRECT ACTING  PROPORTIONAL PLUS RESET CONTROLLER    GG15992 1    3  Locate the two bellows  key 52   the proportional band assembly  see figure 18   and the reversing block  key 37    4  Disconnect the tubing  refer to figure 18      a  For a proportional only controller or for a transmitter  disconnect the proportional tubing  key 25  from the  mounting base and reconnect them on the opposite side     b  For a proportional plus reset controller  disconnect the proportional tubing  key 27  and reset tubing  key 27   from the mounting base and reconnect them on the opposite side     5  Invert the proportional band assembly  refer to figure 17      a  Turn the proportional band adjustment knob  key 73  to 10     35    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       b  Unscrew the spring adjustor  key 65   removing the bias spring  key 70  and washers  key 64  with it     c  Unclip the lock spring  key 72   Remove the indicator scale  key 69  and proportional band adjustment knob   key 73      d  Remove the gain adjustm
28. ber locations are shown in figure 4     Provide a process pressure source capable of simulating the process pressure range of the controller  If an output  pressure gauge is not provided  install a suitable pressure gauge for calibration purposes     Figure 4  Proportional Only Controller Adjustment Locations          PRESSURE SETTING KNOB   KEY 58    PRESSURE SETTING   DIAL  KEY 6                                         PROPORTIONAL BAND  ADJUSTMENT KNOB                         CALIBRATION ADJUSTER  KEY 36    FLAPPER  KEY 40   NOZZLE  KEY 54     Er ADJUSTER SCREWS  KEY 48     Connect a pressure source to the supply pressure regulator and be sure the regulator is delivering the correct supply  pressure to the controller  The controller must be connected open loop  Open loop  The controller output pressure  changes must be dead ended into a pressure gauge   The following procedures use a 0 2 to 1 0 bar  3 to 15 psig   output pressure range as an example  For a 0 4 to 2 0 bar  6 to 30 psig  output range  adjust the values as appropriate     1  Complete the above connections and provide a process pressure equal to the sensing element range   2  Rotate the proportional band adjustment knob  shown in figure 4  to 1 5  15 percent proportional band    3  Verify that the calibration adjuster screws  key 48  are at mid position in the calibration adjuster  key 36  slots     Depending upon the controller action  perform one or the other of the following procedures     Instruction Manua
29. cket using the four cap screws  key 252  provided  Attach the bracket to the wall  using  suitable screws or bolts     Pipestand Mounting    Refer to figure 2     Use a hammer and punch to knock out the blanks in the two holes indicated in the back view of figure 2  Attach the  spacer spools  key 228  and the mounting plate  key 213  to the controller with cap screws  lock washers  and nuts   keys 215  221  and 216   Attach the controller to a 2 inch  nominal  pipe with pipe clamps  key 250      Actuator Mounting  Refer to figure 3     Controllers specified for mounting on a control valve actuator are mounted at the factory  If the instrument is ordered  separately for installation on a control valve actuator  mount the instrument according to the following instructions     Mounting parts for the different actuator types and sizes vary  Two typical actuator mounting installations are shown  in figure 3  see the parts list for parts required for the specific actuator type and size involved     Use a hammer and punch to knock out the blanks in the two holes indicated in the back view of figure 2  Attach the  spacer spools  key 228  and the mounting plate  key 213  to the controller with machine screws  lock washers  and  nuts  keys 215  221  and 216      Attach the mounting bracket to the actuator yoke with cap screws  key 222  and  if needed  spacer spools  On some  designs  the mounting bracket is attached to the actuator diaphragm casing rather than to the yoke     C1 Contro
30. dial setting  Monitor the process pressure and output pressure to be sure the desired settings  are attained     23    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Figure 11  Transmitter Adjustment Locations          ZERO ADJUSTMENT KNOB   KEY 58    PRESSURE SETTING   DIAL  KEY 6                                     FLAPPER  KEY 40     ADJUSTER SCREWS  KEY 48  NOZZLE  KEY 54   CALIBRATION ADJUSTER  KEY 36     SPAN ADJUSTMENT KNOB    GE34729 B  E1061    Adjustment  Span    The span adjustment is graduated from 0 to 10  A setting of 10 represents a span setting of 100 percent of the process  sensing element range  The transmitter achieves the highest accuracy when the span is 100 percent     The transmitter span adjustment shown in figure 11 is the same as the controller proportional band adjustment     Calibration  Transmitters    The output of each transmitter is checked at the factory before the unit is shipped  The transmitter provides an output  signal that is proportional to the pressure applied to the sensing element  The output pressure has no direct effect on  the process pressure     The transmitter is calibrated at the factory and should not need additional adjustment  Use the following calibration  procedures when the sensing element has been changed or other maintenance procedures have altered the  calibration of the transmitter  The following procedures use a 0 2 to 1 0 bar  3 to 15 psig  output pressure range as an  example  For o
31. e Screw  steel pl  specify quantity req d   5 16 UNC X 1 inch  5 16 UNCX 1 1 2 inches  5 16 UNC X 2 inches    216  HexNut  steel pl  specify quantity req d   For filter regulator mounting on  1051  1052 and 1061  All other types and mountings    220 Mounting Bracket  steel pl  not shown   For casing mounting and casing mounted filter  regulator on 1051 and 1052    221  Lockwasher  steel pl  specify quantity req d   222  CapScrew  steel pl  specify quantity req d    5 16 UNC X 3 4 inch   5 16 UNC X 1 inch   5 16 UNC X 1 1 8 inches   5 16 UNC X 1 1 4 inches   5 16 UNC X 1 3 4 inches   5 16 UNC X 2 1 2 inches   3 8 UNF X 1 1 8 inches       50    Key  223    228    229    238    240    241    242    243    244    250    251    252    Note    Description    Cap Screw  steel pl  1051 and 1052 with either case or  yoke mounted regulator and 1061  with yoke mounted regulator  2 req d     Spacer Spool  steel  specify quantity req d   470  472  480  513  656  657  667   pipe stand 1051  1052 and 1061    Cap Screw  steel pl  not shown   specify quantity req d   1051 and 1052 casing mounted  controller    Mounting Plate  steel  For yoke mounted filter regulator  1051  1052 and 1062 sizes 40 and 60  1061 size 30    Cap Screw  steel  For yoke mounted filter regulator on  1051 and 1052 sizes 40 and  60  2 req d   Spacer Spool  steel  For yoke mounted filter regulators on  1051 and 1052 sizes 40 and 60  2 req d   Spacer Spool  steel  not shown   For yoke mounting on  1051 and 1052 size 40  2
32. e sure that the above measures stay in effect while you work on the equipment   e    Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and  appropriate preventative measures are not taken  Preventative measures may include  but are not limited to  one or  more of the following  Remote venting of the unit  re evaluating the hazardous area classification  ensuring adequate  ventilation  and the removal of any ignition sources  For information on remote venting of this controller  transmitter   refer to page 11     Check with your process or safety engineer for any additional measures that must be taken to protect against process  media     Replacing Gauges  Refer to figures 22 and 23 for key number locations unless otherwise directed   Three gauge configurations are available for C1 units    e Output and supply pressure indications   e Output and process pressure indications   e Output  process  and supply pressure indications    One gauge type  key 2  is used for both output and supply pressure indications when the gauges are installed inside  the controller case  Key 2 features a 1 8 inch connecting stem that matches the threaded gauge boss extending from  the relay base     In some cases  a process pressure gauge  key 4  covers the position of the internal supply pressure gauge  The supply  pressure gauge has been removed and replaced with a pipe plug  key 15   The pressure control block  key 10  is  different to
33. e value     Note  Proper transmitter response depends on nozzle to flapper alignment     When performing the span adjustment in step 8  carefully loosen both calibration adjuster screws while holding the calibration  adjuster in place  Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver  Verify proper  nozzle to flapper alignment and hold the calibration adjuster in place while tightening both adjustment screws     8  If the output pressure is not 15 psig  adjust the span by loosening the two adjusting screws  key 48  and moving the  calibration adjuster  key 36  a small distance as indicated in figure 12     9  Repeat steps 4 through 8 until no further adjustment is necessary   10  Proceed to the startup procedure for transmitters     Startup  Transmitters  1  Besure that the supply pressure regulator is delivering the proper supply pressure to the transmitter   2  Referto the calibration procedures for the transmitter initial settings     3  If the transmitter is used in conjunction with a control valve  slowly open the upstream and downstream manual  shutoff valves  and close the bypass valves     26    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Principle of Operation    The following sections describe the operation of a controller or transmitter using a Bourdon tube sensing element  The  operation is the same for an instrument using a bellows sensing element  key 71  figure 25  except tha
34. e with other applicable European  Community Directives        1  The pressure temperature limits in this document and any applicable standard or code limitation should not be exceeded   2  Normal m3 hr  normal cubic meters per hour  m3 hr  0  C and 1 01325 bar  absolute   Scfh  standard cubic feet per hour  ft3 hr  60  F and 14 7 psig      3  To convert from air flow rate to natural gas flow rate multiply by 1 29     4  An adjustable differential gap  differential gap controllers  is equivalent to an adjustable deadband     Table 2  Available Configurations          DESCRIPTION    Bourdon Tube Sensing Element          Proportional only controller  Without anti reset windup  With anti reset windup             Proportional plus reset controller       Differential gap controller             Transmitter             TYPE NUMBER  Bellows Sensing Element   Gauge Pressure Only  Gauge Pressure Differential Pressure  CID  CIP C1B  C1D                Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Table 3  Bourdon Tube Pressure Range and Materials                         ET MAXIMUM ALLOWABLE STATIC PRESSURE LIMITSG   SEN Standard With Optional Travel Stop 4  MATERIAL 5    Bar Psig Bar Psig Bar Psig  Oto 2 0 Oto 30 2 0 30 33 48  0to4 0 0 to 60 4 0 60 6 6 96  0to 7 0 0to 100 7 0 100 11 160  Oto 14 Oto 200 14 200 19 280  Oto 20 0 to 300 20 300 29 420  0to40 0 to 600 40 600 50 720  0to 70 0 to 1000 70 1000 83 1200 316 stainless steel  0 to 100 0 to 1500 100 15
35. ement to sense the  gauge pressure  vacuum  compound pressure  or differential pressure of a liquid or gas  The controller or transmitter  output is a pneumatic pressure signal that can be used to operate a final control element  indicating device  or  recording device     Unless otherwise noted  all NACE references are to NACE MR0175  15015156  amp  NACE MR0103     Specifications    Specifications for the C1 controllers and transmitters are listed in table 1  Table 2 explains available configurations and  options     Educational Services    For information on available courses for C1 controllers and transmitters  as well as a variety of other products  contact     Emerson Process Management   Educational Services   Registration   Phone   1 641 754 3771 or  1 800 338 8158  e mail  education emerson com  http   www emersonprocess com education    Instruction Manual  D103292X012    C1 Controllers and Transmitters  May 2014       Table 1  Specifications       Available Configurations  See table 2    Input Signal    Type  Bl Gauge pressure  Bl vacuum  Bl compound  pressure  or lil differential pressure of a liquid or gas  Limits  See table 3 or 4    Output Signal    Proportional Only or Proportional Plus Reset  Controllers and Transmitters    W 0 2 to 1 0 bar  3 to 15 psig  or   E 0 4 to 2 0 bar  6 to 30 psig  pneumatic pressure  signal   Differential Gap Controllers    E 0 and 1 4 bar  0 and 20 psig  or   Wi 0 and 2 4 bar  0 and 35 psig  pneumatic pressure  signal   Action  Cont
36. ent bar  key 63   Flip it over so it attaches to the opposite side of the cantilever spring   key 8  as shown in figure 18 and re attach     e  Flip over the indicator scale  key 69  figure 17   install it and the proportional ban knob  key 73  as a unit  Snap in  the lock spring  key 72      f  Tighten down the spring adjustor  key 65  with the bias spring  key 70  and washers  key 64  until it stops against  the gain adjustment bar  key 63      g  Turn the proportional band adjustment knob to the 10 setting  If it cannot be turned  loosen the spring adjustor   key 65      6  Change the reversing block assembly  figure 16 or 18  key 37      a  Remove the sealing screw  key 49  figure 24 or 25   Inspect the O ring  key 77 located in the recessed area under  the sealing screw head  Replace the O ring if necessary     b  Remove the reversing block screw  key 50  figure 24 or 25  and reversing block assembly  key 37   Inspect the  O rings  key 77  located in the recessed area under the reversing block screw head and between the reversing  block assembly and the calibration adjuster  key 36   Replace these O rings if necessary     C  Position the reversing block assembly  with an O ring  on the calibration adjuster  key 36  so that the nozzle is on  the opposite side of the beam  key 39  from which it was removed  Position the reversing block hole in the  calibration adjuster  Install the reversing block screw  key 50  with an O ring  key 77      d  Install the sealing screw  key
37. ential Gap Controller    A proportional only controller may be changed to a differential gap controller  or vice versa  by changing the position  of the proportional tubing and inverting the proportional band assembly     1  Isolate the controller or transmitter from process  control  and supply pressure  Vent any trapped pressure from the  controller or transmitter before proceeding with the following steps     2  Disconnect the proportional tubing  key 25  figure 16  from the mounting base  key 57  figure 24 or 25  and  reinstall it in the other connection in the mounting base     Figure 16  Reverse Direct Acting Tubing Connection for Differential Gap Controller    PROPORTIONAL TUBING   KEY 25     PROPORTIONAL TUBING   KEY 25                        RELAY TUBING   KEY 24     REVERSING BLOCK   KEY 37     RELAY TUBING   KEY 24     PROPORTIONAL   BAND ASSY   DIRECT ACTING  POSITION    FLAPPER SCREW          FLAPPER SCREW   KEYS 40 AND 46   KEYS 40 AND 46   REVERSE ACTING  POSITION PROPORTIONAL BAND ASSY  REVERSING BLOCK   KEY 37     REVERSE ACTING DIRECT ACTING    DIFFERENTIAL GAP CONTROLLER    GE34724 B     33    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       3  Do not invert the reversing block unless also changing the controller action from direct to reverse  or vice versa    4  Invert the proportional band assembly  refer to figure 17      a  Turn the proportional band adjustment knob  key 73  to 10   b  Unscrew the spring adjustor  key 65   
38. ents are 1 4 NPT internal  Use 6 mm  1 4 inch  or 10 mm  3 8 inch  pipe or  tubing for supply and output piping  The pressure connection locations are shown in figure 2     Supply Pressure    A WARNING    Severe personal injury or property damage may occur from an uncontrolled process if the instrument supply medium is not  clean  dry  oil free and noncorrosive  While use and regular maintenance of a filter that removes particles larger than 40  micrometers in diameter will suffice in most applications  check with an Emerson Process Management field office and  industry instrument supply medium quality standards for use with hazardous gas or if you are unsure about the proper  amount or method of air filtration or filter maintenance      to     C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Supply pressure must be clean  dry air that meets the requirements of ISA Standard 7 0 01  A maximum 40  micrometer particle size in the air system is acceptable  Further filtration down to 5 micrometer particle size is  recommended  Lubricant content is not to exceed 1 ppm weight  w w  or volume  v v  basis  Condensation in the air  supply should be minimized  Alternatively  natural gas may be used as the supply pressure medium  Gas must be  clean  dry  oil free  and noncorrosive  H2S content should not exceed 20 ppm     Use a suitable supply pressure regulator to reduce the supply pressure source to the normal operating supply pressure  shown in table 5  C
39. eration    Proportional Only Controllers    This section describes the adjustments and procedures for calibration and startup  Adjustment locations are shown in  figure 4 unless otherwise specified  All adjustments must be made with the cover open  When the adjustments and  calibration procedures are complete  close and latch the cover     To better understand the adjustments and overall operation of the controller  refer to the Principle of Operation  section in this manual for proportional only controllers  Refer also to the schematic diagram in figure 13     Adjustments  Adjustment  Set Point    Adjust the pressure setting knob by turning the knob clockwise to increase the set point and counterclockwise to  decrease the set point  Note that the dial setting and actual process pressure may vary significantly  especially with a  wide proportional band setting     Adjustment  Proportional Band  To adjust the proportional band  rotate the proportional band adjustment knob to the desired value   The proportional band adjustment determines the amount of change in controlled pressure required to cause the    control valve to stroke fully  It may be adjusted from 2 to 100 percent for 0 2 to 1 0 bar  3 to 15 psig  or 4 to 100  percent for 0 4 to 2 0 bar  6 to 30 psig  of the nominal sensing element pressure rating     11    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Calibration  Proportional Only Controllers    Unless otherwise indicated  key num
40. essure setting dial reading     This tuning procedure may be too conservative for some systems  The recommended proportional band setting  should be checked for stability by introducing a disturbance and monitoring the process     Proportional Plus Reset Controllers    This section describes the adjustments and procedures for calibration and startup  The adjustment locations are  shown in figure 7 unless otherwise specified  All adjustments must be made with the cover open  When the  adjustments and calibration procedures are complete  close and latch the cover  To better understand the  adjustments and overall operation of the controller  refer to the Principle of Operation section in this manual for  proportional plus reset controllers  Refer also to the schematic diagram in figure 13     C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Figure 7  Proportional Plus Reset Controller Adjustment Locations    RESET ADJUSTMENT KNOB    PRESSURE SETTING KNOB   KEY 58     PRESSURE SETTING  DIAL  KEY 6                                      CALIBRATION ADJUSTER  KEY 36  fiesta rad 40  PROPORTIONAL BAND  ADJUSTER SCREWS  KEY 48  ADIESTMENTKNOB    GE28281 B  E1060    Adjustments  Adjustment  Set Point    Adjust the pressure setting knob by turning the knob clockwise to increase the set point and counterclockwise to  decrease the set point     Rotate the knob until the indicator points to the desired set point pressure value  The pressure setting dial will re
41. ever machine screws  figure 21  step         c  Remove the inner flexure  figure 21  step     and install it on the new cantilever     10  Install the new cantilever spring  key 8  and reconnect the beam  key 39  to the bellows spacer  key 34  in reverse  sequence of steps 9a and 9b and reattach the bellows to the beam cantilever assembly     11  Compress the bellows and install them into the mounting base  key 57   Align the cantilever spring with the gain  adjustment bar  key 63   For 0 2 to 1 0 bar  3 to 15 psig  and 0 4 to 2 0 bar  6 to 30 psig  output ranges  reverse the  spring spacer  key 245  as shown in figure 19  Install the indicator scale  key 69  and the proportional band  adjustment knob  key 73  as a unit  Snap the lock spring  key 72  onto the indicator scale     12  Install the spring adjustor  key 65  figure 17  and washer  key 64  figure 17  on the bias spring  key 70  figure 17    Tighten down the spring adjustor until it stops against the gain adjustment bar  key 63      38    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       13    15   16     17     Figure 21  Beam Cantilever Spring Assembly      Turn the proportional band adjustment knob to 10  If it cannot be turned to 10 loosen the spring adjustor  key 65      14  Secure the bellows  key 52  with the bellows screws  key 53   making sure that the nozzle  key 54  is centered on    the flapper  key 40    Unscrew the supply and output gauges  figure 22 or 23  key 2  and instal
42. ey 10  figure 22 or 23  to the Bourdon tube or bellows    assembly  key 5 or 52   at the pressure block end     3  Unscrew the machine screws  key 41  figure 22 or 23   and remove the subassembly from the case     4  If the controller or transmitter uses a Bourdon tube sensing element disconnect the Bourdon tube from the beam   key 39  by removing the screw  key 56   Be careful to avoid losing the bearing  key 31   Unscrew the machine  screws  key 55  and remove the washers and Bourdon tube  keys 45 and 5      37    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       5  Unscrew the bellows screws  key 53  from each end of the mounting base  key 57      Note    The bellows screws  key 53  have an O ring  key 77  figure 20  installed beneath the bellows screw head  Remove the O ring and  obtain a replacement when re assembling the bellows     Figure 20  Bellows Screw Detail    O RING   KEY 77         A6281 1    6  Unscrew the spring adjustor  key 65   Unclip the lock spring  key 72  figure 17  and remove the indicator scale   key 69  and the proportional band adjustment knob  key 73      7  Compress the bellows  key 52  so that the end of the bellows  beam  key 39   and cantilever spring  key 8  can be  removed from the mounting base  key 57      8  Unscrew the bellows  key 52  from the bellows cantilever assembly   9  Remove the cantilever spring from the spacer  key 34      a  Remove the beam machine screws  figure 21  step      b  Remove the cantil
43. flect  the desired set point if the controller is accurately calibrated     Adjustment  Proportional Band    To adjust the proportional band  rotate the proportional band adjustment knob to the desired value    The proportional band adjustment determines the amount of change in controlled pressure required to cause the  control valve to stroke fully  It may be adjusted from 3 to 100 percent for 0 2 to 1 0 bar  3 to 15 psig  or 6 to 100  percent for 0 4 to 2 0 bar  6 to 30 psig  of the nominal sensing element pressure rating    Adjustment  Reset    To adjust reset action turn the knob clockwise to decrease the minutes per repeat  Turn the knob counterclockwise to  increase the minutes per repeat  Increasing the minutes per repeat provides a slower reset action     The reset adjustment dial is calibrated in minutes per repeat  By definition  this is the time in minutes required for the  reset action to produce an output change which is equal to the change produced by proportional control action  This is    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       in effect  the time in minutes required for the controller to increase  or decrease  its output pressure by an amount  equal to a proportional increase  or decrease  caused by a change in set point or process pressure     Adjustment  Anti Reset Windup    The externally mounted differential relief valve can be mounted to relieve on increasing or decreasing output pressure     Calibration  Calibratio
44. g the span adjustment in step 11  do not watch the output gauge while changing the calibration adjuster  The  change in output is not a good indication of the change in span  While moving the calibration adjuster  the output pressure may    18    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       change in the opposite direction than expected  For example  while moving the calibration adjuster to increase span  the output  pressure may decrease  This should be disregarded since even though the output pressure decreases  the span is increasing     Proper controller response depends on nozzle to flapper alignment     When performing span adjustments  carefully loosen both calibration adjuster screws while holding the calibration adjuster in  place  Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver  Verify proper  nozzle to flapper alignment and hold the calibration adjuster in place while tightening both adjustment screws     11  If the output pressure is not between 0 6 and 0 7 bar  8 and 10 psig   adjust the controller span by loosening the  two adjusting screws  key 48  and moving the calibration adjuster  key 36  a small distance as indicated in figure 9     12  Repeat steps 6 through 11 until no further adjustment is necessary     13  For C1P and C1B controllers with anti reset windup remove the two machine screws  anti reset windup cover  and  two O rings installed in step 1 of this procedure  
45. he WARNING at the beginning of the Maintenance section in this  instruction manual     e Check with your process or safety engineer for any additional measures that must be taken to protect against process  media     Standard Installation    The instruments are normally mounted vertical with the case cover as shown in figure 1  If installing the instrument in  any other position  be sure that the vent opening shown in figure 2 is facing downward        Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Panel Mounting  Refer to figure 2     Cut a hole in the panel surface according to the dimensions shown in figure 2  Remove the cap screws  key 252    brackets  key 251   and vent assembly  key 28   Slide the controller or transmitter into the cutout and reattach the  brackets  Tighten the cap screw located in the center of each bracket to draw the case snugly and evenly against the  panel  Reinstall the vent unless a remote vent will be used     Wall Mounting    Refer to figure 2     Drill four holes in the wall using the dimensions shown in figure 2  In the bracket  key 251  are 8 7 mm  0 3438 inch   diameter holes  Back out the cap screw located in the center of each bracket   The screws are used for panel mounting  but are not required for wall mounting   If tubing runs through the wall  drill holes in the wall to accommodate the  tubings  Figure 2 shows the pressure connection locations in the back of the case     Mount the controller to the bra
46. ig      7  Setthe input pressure equal to zero     Note  Proper transmitter response depends on nozzle to flapper alignment     When performing the span adjustment in step 8  carefully loosen both calibration adjuster screws while holding the calibration  adjuster in place  Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver  Verify proper  nozzle to flapper alignment and hold the calibration adjuster in place while tightening both adjustment screws     8  If the output pressure is not 15 psig  adjust the span by loosening the two adjusting screws  key 48  and moving the  calibration adjuster  key 36  a small distance as indicated in figure 12     9  Repeat steps 4 through 8 until no further adjustment is necessary     10  Proceed to the startup procedure for transmitters     25    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Figure 12  Transmitter Span Adjustment       IF OUTPUT IS   BELOW ABOVE  15 PSIG 15 PSIG   1 0 BAR   1 0 BAR   MOVE ADJUSTER gjss pe MOVE ADJUSTER  LEFT RIGHT       NOTE    3 TO 15 PSIG  0 2 TO 1 0 BAR  OUTPUT SHOWN   FOR 6 TO 30 PSIG  0 4 TO 2 0 BAR  OUTPUT  ADJUST  VALUES AS APPROPRIATE     A6156    For direct acting transmitters     4  Rotate the zero adjustment knob to zero    5  Setthe input pressure to zero    6  Adjust the nozzle  key 54  until the transmitter output pressure is at 0 2 bar  3 psig    7  Apply an input pressure equal to the sensing element upper rang
47. inch wc  2 8 40 5e eun  0 to 0 35 bar  0 to 5 psig  2 8 40         Positive pressure 0 to 0 5 bar  0 to 7 5 psig  2 8 40 ed inm  0 to 0 7 bar  0 to 10 psig  2 8 40 aes ES  Oto 1 0 bar  0to 15 psig  2 8 40 6 9 100  0 to 1 4 bar  0 to 20 psig  2 8 40 nis Les  0 to 2 0 bar  0 to 30 psig  2 8 40 6 9 100  0 to 300 mbar  0 to 80 inch wc  1 4 20 E ES      0 to 0 7 bar  0 to 10 psi  2 8 40 E     5   Differential Pressure 0 to 1 4 bar  0 to 20 psi  2 8 40 Es zm  0 to 2 0 bar  0 to 30 psi            6 9 100                               1  If the process can trip to a pressure outside of the operating range of the sensing element  a commercially available device  such as an overpressure protector  may be used to protect  against pressure surges and pulsations    2  Bellows may be pressured to limit shown without permanent zero shift    3  Transmitter only    4  Except transmitter    5  The overrange limit for these sensing elements is a differential pressure equal to the maximum allowable static pressure limit        Table 5  Supply Pressure Requirements                      Output Signal Range PPE Supply Maximum UE a To Prevent  0 2 to 1 0 or 0 and 1 4  differential gap  1 4 2 8  par 0 4 to 2 0 or 0 and 2 4  differential gap  2 4 2 8    3to 15 or 0 and 20  differential gap  20 40  Psig 6 to 30 or 0 and 35  differential gap  35 40                   1  If this pressure is exceeded  control may be impaired           C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012
48. ion Part Number    Note    A total of 5 O rings  key 77  are used  1 O ring is used under the sealing  screw  key 49   1 O ring is used under the reversing block screw  key 50    1 O ring is used between the reversing block ass y  key 52  and the  calibration adjuster  key 36   and 1 O ring is used in the recessed area  under the head of each of the bellows screws  key 53      77  O Ring   Std Temp  nitrile  5 req d  1D687506992  High Temp  fluorocarbon  5 req d  1N430406382    Note    Keys 78 through 82 are used for Proportional Plus Reset controllers only     78 Tubing Assembly  SST   79 Tubing Assembly  SST   80  Anti Reset Windup Cover  not shown   81  O Ring  not shown   2 req d    82 Machine screw  not shown   2 req d     1C853806992    48    Key Description Part Number    98 Machine Screw  steel pl  4 req d   Gauge and differential pressure bellow instruments    99 Washer  steel pl  for Bourdon tube instruments  2 req d   for bellows sensing instruments  4 req d   100  Bellows Yoke  zinc  use with gauge and differential pressure bellows    Note    Keys 101 through 105 are used for gauge pressure bellows instruments  only     101  JamNut  steel pl  102 Washer  steel pl  103 Spring seat  pl brass    104 Spring  steel pl  105 Label  bellows sensing instruments only    190  Anti Reset Windup Ass y  For Proportional Plus Reset Controllers only    245 Spring Spacer  A6061    256  ResetRestriction Valve  For proportional plus reset controllers    w o anti reset windup 19A4361
49. ith a control valve  slowly open the upstream and downstream manual  shutoff valves  and close the bypass valves     4  To change the differential gap  perform steps 1 through 5 of the calibration for differential gap controllers  procedure     Transmitter Operation    This section describes the adjustments and procedures for calibration and startup  Refer to figure 11 for the  adjustment locations  All adjustments must be made with the cover open  When the adjustments and calibration  procedures are complete  close and latch the cover     To better understand the adjustments and overall operation of the transmitter  refer to the Principle of Operation  section in this manual for transmitters  Refer also to the schematic diagram in figure 13     Adjustments    Adjustment  Zero    The pressure setting dial is marked ZERO ADJUSTMENT PRESSURE SETTING  Zero is in the center of the dial  and the  pressure values increase to the right and left of the center as shown in figure 11  To set the zero  rotate the pointer  around the pressure setting dial  Rotate the pointer clockwise to increase or counterclockwise to decrease the output  depending on transmitter action and desired setting     For direct acting transmitters  zero adjustment determines the process pressure at which the transmitter output  signal will be at its lower range limit     The dial  key 6  graduations are approximate indications of the transmitter zero setting  When making adjustments   do not rely solely on the 
50. l C1 Controllers and Transmitters  D103292X012 May 2014       For reverse acting controllers     4  Apply an input pressure equal to the sensing element upper range value    5  Rotate the pressure setting knob to the maximum value    6  Adjust the nozzle  key 54  until the controller output pressure is between 0 6 and 0 7 bar  8 and 10 psig    7  Apply an input pressure equal to the sensing element lower range value     8  Rotate the pressure setting knob to the minimum value     Note    When performing the span adjustment in step 9  do not watch the output gauge while changing the calibration adjuster  The  change in output is not a good indication of the change in span  While moving the calibration adjuster  the output pressure may  change in the opposite direction than expected  For example  while moving the calibration adjuster to increase span  the output  pressure may decrease  This should be disregarded since even though the output pressure decreases  the span is increasing     Proper controller response depends on nozzle to flapper alignment     When performing span adjustments  carefully loosen both calibration adjuster screws while holding the calibration adjuster in  place  Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver  Verify proper  nozzle to flapper alignment and hold the calibration adjuster in place while tightening both adjustment screws     9  If the output is not between 0 6 and 0 7 bar  8 and 10 psig  
51. l new gauges with correct ranges     Replace the subassembly in the case and secure with machine screws  figure 22 or 23  key 41   Re install the  Bourdon tube if it was removed  refer to the Replacing the Bourdon Tube section  Reconnect all tubing     Check all tubing connections and the bellows machine screws for leaks  tighten as necessary  Perform the  appropriate calibration procedures     BELLOWS SPACER   KEY 34     INNER FLEXURE             OUTER FLEXURE  KEY 67    KEY 68  CANTILEVER SPRING  MACHINE SCREW  KEY 8    KEY 51     BEAM   KEY 39     MACHINE SCREW   KEY 51  in             GE34726 B    1068    39    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Parts Ordering    Whenever corresponding with your Emerson Process Management sales office about this equipment  mention the  serial number of the unit  The serial number can be found on the nameplate  key 22  figure 22   When ordering  replacement parts  also state the complete 11 character part number of each part required as found in the following  parts list     A WARNING    Use only genuine Fisher replacement parts  Components that are not supplied by Emerson Process Management should  not  under any circumstances  be used in any Fisher instrument  Use of components not supplied by Emerson Process  Management may void your warranty  might adversely affect the performance of the instrument  and could cause personal  injury or property damage     40    Instruction Manual  D103292X012 
52. llers and Transmitters  May 2014    Instruction Manual  D103292X012       Figure 2  Panel  Wall  and Pipestand Mounting         2 INCH   NOMINAL                 VENT ASSEMBLY   KEY 28     PIPESTAND MOUNTING    8 7   11 32   MOUNTING       PANEL MOUNTING    NOTES    1  ALL CONNECTIONS ARE 1 4 NPT INTERNAL    2 gt  HIGH PRESSURE CONNECTION FOR DIFFERENTIAL PRESSURE UNITS    B gt  LOW PRESSURE CONNECTION FOR DIFFERENTIAL PRESSURE UNITS   E1052          WALL MOUNTING    63 5   2 50     63 5   2 50     65 8   2 59        23 1   0 91         KNOCK OUT    218 9   8 62        CUTOUT FOR  FOUR HOLES  PANELMOUNTING     rog WALL  MOUNTING  mm   INCH     Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Figure 3  Actuator Mounting                      SUPPLY PRESSURE  REGULATOR                            216                             215                    223                221                                     SUPPLY PRESSURE  REGULATOR                                                 GE33947 A    GE33946 A    TYPICAL ROTARY ACTUATOR TYPICAL SLIDING STEM ACTUATOR    Pressure Connections  A WARNING       To avoid personal injury or property damage resulting from the sudden release of pressure  do not install any system  component where service conditions could exceed the limits given in this manual  Use pressure relieving devices as  required by government or accepted industry codes and good engineering practices     All pressure connections on C1 instrum
53. machine screws  key 41  figure 22 or 23   Reconnect  all tubing     11  If abellows assembly with a different range is installed  remove the machine screw and washer  keys 61 and 60  and  dial  key 6   and install a new dial having an adjustment range corresponding to the range of the bellows  If an  optional process pressure gauge  key 4  figure 22  is being used  install a new gauge with the appropriate  measurement capability     32    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       12  Check all tubing connections for leaks and the bellows yoke machine screws  tighten as necessary  Perform the  appropriate calibration procedures     Changing Reset Valve    1  Disconnect the appropriate tubing and remove the reset restriction valve assembly  key 256  figure 23  by  removing the screw  key 22  not shown  from the back of the case  Install the desired replacement assembly     2  Connect the tubing  check all connections for leaks and perform the appropriate calibration procedures     Changing Anti Reset Windup Differential Relief Valve  Refer to figure 24 for key number locations     1  Note the controller output pressure  zero or supply  when the process is shut down   2  Remove the differential relief valve assembly     3  Refer to figure 14  Install the replacement relief valve with the arrow positioned so that the controller output will be  as noted in step 1 when the process is shut down     Changing Action    Proportional Only to a Differ
54. n  Proportional Plus Reset Controllers    Unless otherwise indicated  key number locations are shown in figure 7     Before starting this procedure   e Provide a process pressure source capable of simulating the process pressure range of the controller     e  f an output pressure gauge is not provided  install a suitable pressure gauge for calibration purposes  The  controller must be connected open loop  Open loop  The controller output pressure changes must be dead  ended into a pressure gauge      Note  C1P and C1B controllers with anti reset windup are supplied with two O rings  key 81   an anti reset windup cover  key 80   and  two machine screws  key 82   Use these parts in the next step     1  For C1P and C1B controllers with anti reset windup record the direction of the arrow on the anti reset windup  assembly  key 190  in figure 23   Remove the assembly and install the two O rings  key 81   and cover  key 80   supplied with the controller  Secure the cover with the two machine screws  key 82  provided       Connect regulated supply pressure to the controller  Do not exceed the normal operating pressure in table 5      Rotate the reset knob to 0 01 minutes per repeat  fastest setting       Rotate the proportional band adjustment knob to 1 5  15 percent proportional band       Verify that the calibration adjuster screws  key 48  are at mid position in the calibration adjuster  key 36  slots     m A UN    Depending upon the controller action  perform one or the other of
55. n touched  Washers  key 62  are used as shims to set parallelism     9  Check to be sure that the beam is parallel with the bottom of the case and that the link  key 16  is in tension  If the  beam is not parallel with the case  loosen the machine screws  key 55   reposition the Bourdon tube to get the  beam parallel  and retighten the screws     10  If a Bourdon tube with a different range was installed  remove the machine screw and washer  keys 61 and 60  and  dial  key 6   Install a new dial having an adjustment range corresponding to the range of the Bourdon tube  If an  optional process pressure gauge  key 4  figure 22  is being used  install a new gauge with the appropriate  measurement capability     31    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Figure 15  Connecting Link    BOURDON TUBE   KEY 5  BOURDON TUBE   KEY 5     LINK BEARING        KEY 31  WASHER   KEY 62   WASHER  QTY 2    KEY 62  LINK BEARING   KEY 31   BEAM   KEY 39  WASHER   KEY 62   CONNECTING  LINK  KEY 16  BEAM  BINDING CONNECTING LINK PROPERLY ALIGNED  KEY 39    IMPROPERLY ALIGNED  CONNECTING LINK CONNECTING  LINK  KEY 16     GE37119    11  Check all tubing connections for leaks and the Bourdon tube machine screws  tighten as necessary  Perform the  appropriate calibration procedures     Replacing Bellows Sensing Element  Refer to figure 25 for key number locations unless otherwise directed     1  Shut off the supply pressure and process lines to the controller or
56. o a 0 4 to 2 0 bar   6to 30 psig  output signal range or vice versa  also see figure 19      e Fora differential gap controller  use this procedure to change from a 0 and 1 4 bar  0 and 20 psig  to a 0 and 2 4  bar  0 and 35 psig  output signal range or vice versa  also see figure 19      e When changing the supply pressure source to a new range  refer to table 5 for supply pressure requirements for    the output signal range selected     Figure 19  Changing From a 0 2 to 1 0 bar  3 to 15 psig  to a 0 4 to 2 0 bar  6 to 30 psig  Output Signal Range    or Vice Versa    CANTILEVER SPRING                SPRING C  H SPACER      m  KEY 245      KEY 70     WASHER SPRING   KEY 64  ADJUSTER   KEY 65        0 2 TO 1 0 BAR  3 TO 15 PSIG   OUTPUT RANGE    NOTE       GG15991 A    CANTILEVER SPRING   KEY 8                      SPRING  lt 7   SPACER  EN  KEY 245   SPRING   KEY 70   WASHER  SPRING   KEY 64  ADJUSTER  0 4 TO 2 0 BAR  6 TO 30 PSIG   KEY 65     OUTPUT RANGE    LD REVERSE THE SPRING SPACER AS APPROPRIATE TO CHANGE THE BIAS SPRING WORKING LENGTH     Also  make appropriate changes to the nameplate of the controller or transmitter  reflecting the new range selections   Refer to figure 24 or 25 for key number locations unless otherwise directed     1  Shut off the supply pressure and process lines to the controller or transmitter   2  Disconnect the tubing from the mounting base  key 57  and calibration adjuster  key 36      Disconnect the tubing that connects the pressure block  k
57. ocess pressure produces increasing output pressure   or vice versa   Changing the action is accomplished by reversing the positions of the reversing block  proportional band assembly   and bellows tubing s   Refer to figures 16  17  18  and 21 for key number locations unless otherwise directed     1  Isolate the controller or transmitter from process  control  and supply pressure  Vent any trapped pressure from the  controller or transmitter before proceeding with this procedure     2  As shown in figure 18  locate the new tubing  proportional band assembly  and reversing block positions for the  desired action     34    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Figure 18  Reverse Direct Acting Tubing Connections for Proportional Controllers or Transmitter              PROPORTIONAL TUBING PROPORTIONAL TUBING   KEY 25  KEY 25   RELAY betel     RELAY TUBING  KEY 24  BELLOWS      REVERSING BLOCK  KEY 3  KEY 52                      PROPORTIONAL NOZZLE  KEY 54     BAND ASSY  DIRECT ACTING             FLAPPER SCREW cae   KEYS 40 AND 46  FLAPPER SCREW   KEYS 40 AND 46        REVERSING       PROPORTIONAL                ACTING  POSITION BAND ASSY  REVERSING BLOCK  KEY 37   NOZZLE  KEY 54   REVERSE ACTING DIRECT ACTING  TO CHANGE ACTION OF THE CONTROLLER  REPOSITION THE PROPORTIONAL TUBING       REVERSING BLOCK NOZZLE AND PROPORTIONAL BAND ASSY AS SHOWN ABOVE    PROPORTIONAL ONLY CONTROLLER OR TRANSMITTER                             RESET VALVE   KE
58. ollers found on page 12 of this manual     4  When calibration is complete  return the tubing  key 25  and the proportional band assembly to their original  locations and continue on with step 5 of this procedure     Note    After reinstalling the tubing  key 25  and proportional band assembly a slight offset of the output pressure will be noticed due to a  combination of switching from the proportional bellows to the reset bellows and the repositioning of the cantilever spring   Performing step 6b below adjusts for this offset     5  Refer to figure 10 to determine the proportional band dial setting required for the desired differential gap     For example  assume that a 0 to 100 psig sensing element is being used and the controller is to switch from zero to full  supply pressure at a process pressure of 80 psig with rising process pressure and from full supply pressure to zero at 20  psig with falling pressure   This is for a direct acting controller   The differential gap is     5 5 bar     1 3 bar  6 9 bar       x 100    60     80 psig     20 psig  100 psig       x 100    60       From figure 10  the proportional band dial setting should be approximately 4 5  rotate the proportional band  adjustment knob to 4 5     6  Setting the process pressure  For a Direct Acting Controller     a  Rotate the pressure setting knob to the pressure at which the controller output is to switch to the upper  switching point  zero to full supply pressure  with rising process pressure  In the
59. onnect supply pressure to the SUPPLY connection at the back of the case     A WARNING    To avoid personal injury or property damage resulting from the sudden release of process pressure  use a high pressure  regulator system when operating the controller or transmitter from a high pressure source     If operating the controller or transmitter from a high pressure source  up to 138 bar  2000 psig    use a high pressure  regulator system  such as the Fisher 1367 High Pressure Instrument Supply System  For 1367 system installation   adjustment  and maintenance information  refer to the 1367 High Pressure Instrument Supply System with  Overpressure Protection instruction manual  D100343X012     Process Pressure    A WARNING    To avoid personal injury or property damage resulting from the sudden release of pressure when using corrosive media   make sure the tubing and instrument components that contact the corrosive medium are of suitable noncorrosive  material     Also refer to the Installation Warning at the beginning of this section     The pressure connections to the controller depend upon the type of pressure sensing  gauge or differential  Gauge  pressure controllers use either a Bourdon tube or bellows as the sensing element  as indicated in table 2  Differential  pressure controllers use two bellows to sense differential pressure     For gauge pressure instruments  The control pressure block  key 10 in figure 22  has two connections  Process  pressure can be connected ei
60. r   0 30 inches Hg  vacuum  and 500 0 500 mbar   15 0 7 5 psig  compound  0 1 4 bar  0 20 psig  positive  0 2 0 bar  0 30 psig  positive and 1 0 0 1 0 bar   30 0 15 psig  compound    Stainless steel   0 1 0 bar  0 15 psig  positive  0 1 0 bar   0 30 inches Hg  vacuum  and 500 0 500 mbar   15 0 7 5 psig  compound  0 2 0 bar  0 30 psig  positive  1 0 0 1 0 bar   30 0 15 psig  compound       1L3780000A2  1L3788000A2    1L3781000A2    1L3789000A2  1L3782000A2    1L3783000A2    1L3784000A2    1L3785000A2    1L3786000A2    1L3787000A2    45    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Figure 24  Controller Subassembly with Bourdon Tube Sensing Element    64  G4   9     69  G     69 G2        68                                                                                                         GE33918 A   VIEW A A  BOURDON TUBE TRAVEL  STOP SUBASSEMBLY  SECTION A A SECTION B B SECTION C C  NOTE   KEYS 33 AND 74 ARE NOT SHOWN  GE26600 C  Key Description Part Number Key Description Part Number  71  Differential Pressure Bellows  input     Brass 72  Lock Spring  304L SST GE32298X012  0 200 mbar  0 80 inches wc  213790000A2 73 Proportional Band Adjustment Knob  steel PPS  0 0 7 bar  0 10 psi  213791000A2 74 Machine Screw   18 8 SST  2 req d   0 1 4 bar  0 20 psi  213792000A2 2 m  Stainless steel  75  Gasket  0 2 0 bar  0 30 psi  213793000A2 Std Temp  chloroprene  2 req d  1D397003012  71K Machine Screw   steel pl High Temp  silicone  2 req d  1N8
61. re with the nozzle capped to produce full output pressure     Replacing Bourdon Tube  Refer to figure 24 for key number locations unless otherwise directed     1  Shut off the supply pressure and process lines to the controller or transmitter     2  Unscrew the machine screw  key 56  to disconnect the link  key 16  and bearing  key 31  from the beam  key 39    Be careful to avoid losing the bearing  key 31   Washer s   key 62  for the machine screw  key 56  are at times  furnished for insertion at the beam  key 39  connection to ensure alignment of the connecting link  key 16      3  Disconnect the control tubing  key 23  figure 23   Unscrew the two screws  key 55  and washers  key 45   and  remove the Bourdon tube  key 5      4  Unscrew the machine screw  key 56   and remove the link and bearing  keys 16 and 31  from the Bourdon tube  Be  careful to avoid losing the bearing       Attach the link and bearing to the replacement Bourdon tube     Attach the Bourdon tube with two machine screws and washers  keys 55 and 45        Connect the link and bearing to the beam  key 39      oo N OQ    Ul      After connecting the link to the beam  make sure that the link is parallel to the sensing element  key 5  and the  beam  key 39  so that it does not bind against the sensing element of the beam  Figure 15 shows a properly aligned  connecting link  the connecting link is not in contact with the Bourdon tube or or washers  When properly  configured  the connecting link moves freely whe
62. removing the bias spring  key 70  and washers  key 64  with it     c  Undlip the lock spring  key 72   Remove the indicator scale  key 69  and proportional band adjustment knob   key 73      d  Remove the gain adjustment bar  key 63   Flip it over so it attaches to the opposite side of the cantilever spring   key 8   as shown in figure 16  and screw it back down     e  Flip over the indicator scale  key 69   install it and the proportional band adjustment knob  key 73  as a unit  Snap  in the lock spring  key 72      f  Tighten down the spring adjustor  key 65  with the bias spring  key 70  and washers  key 64  until it stops against  the gain adjustment bar  key 63      g  Turn the proportional band adjustment knob to the 10 setting  If it cannot be turned to the 10 setting loosen the  spring adjustor  key 63      5  Check all connections for leaks with a soap and water solution  Perform the appropriate calibration procedure   Figure 17  Proportional Band Assembly    PROPORTIONAL BAND ADJUSTMENT KNOB     KEY 73  oe  iia  LOCK SPRING   ll  Hl   MACHINE SCREW   KEY 72   KEY 56   CANTILEVER SPRING INDICATOR SCALE   KEY 8   KEY 69   SPRING SPACER MACHINE SCREW   KEY 245   KEY 74   BIAS SPRING  GAIN ADJUSTMENT BAR   KEY 70   KEY 63   WASHER   KEY 64     SPRING ADJUSTOR   KEY 65     GE34725 B       Reverse to Direct Action    Use the numbered steps below to change from reverse action  increasing process pressure produces decreasing  output pressure  to direct action  increasing pr
63. rol action is field reversible between   E direct  increasing sensed pressure produces  increasing output signal  and lll reverse  increasing  sensed pressure produces decreasing output signal      Supply Pressure Requirements     See table 5    Supply Pressure Medium  Air or natural gas    Air  Supply pressure must be clean  dry air that meets  the requirements of ISA Standard 7 0 01  A maximum  40 micrometer particle size in the air system is  acceptable  Further filtration down to 5 micrometer  particle size is recommended  Lubricant content is  not to exceed 1 ppm weight  w w  or volume  v v   basis  Condensation in the air supply should be  minimized   Natural Gas  Natural gas must be clean  dry  oil free   and noncorrosive  H2S content should not exceed 20    Steady State Air Consumption 2  3     0 2 to 1 0 bar  3 to 15 psig   0 08 normal m3 hour   3 scfh    0 4 to 2 0 bar  6 to 30 psig   0 12 normal m3 hour   4 5 scfh        Supply and Output Connections  1 4 NPT internal    Common Signal Pressure Conversions  See table 6    Proportional Band Adjustment    For Proportional Only Controllers  Full output  pressure change adjustable from ll 2  to 100  of the  sensing element range for 0 2 to 1 0 bar  3 to 15 psig   or ll 4  to 100  of the sensing element range for 0 4  to 2 0 bar  6 to 30 psig     For Proportional Plus Reset Controllers  Full output  pressure change adjustable from ll 3  to 100  of the  sensing element range for 0 2 to 1 0 bar  3 to 15  psig   or ll 6  to
64. t  Set Point    The position of the pressure setting knob determines the location of the differential gap within the range of the  pressure sensing element  Move the pointer to the desired pressure where the output of the controller should switch  from zero to full supply pressure with rising process pressure  direct acting controllers  or with falling process pressure   reverse acting controllers      Adjustment  Proportional Band    The proportional band adjustment shown in figure 4 determines the width of the differential gap  The width of the gap  is the difference between the process pressures at which the controller output will switch from zero to full supply  pressure  or from full supply pressure to zero  The relationship between the proportional band dial setting and the  differential gap is shown in figure 10     Figure 10  Differential Gap Adjustment for Differential Gap Controllers    LT L S pa  LIT T3 Lem   LI T Las qs   REX         PROPORTIONAL BAND KNOB SETTING    DIFFERENTIAL GAP  PERCENT OF ELEMENT RANGE     A2202 3    Calibration  Differential Gap Controllers    The output of each controller is checked at the factory before the unit is shipped  Before placing the controller in  control of a process loop  check to verify that the controller is calibrated correctly for the application  The controller  must be connected open loop  Open loop  The controller output pressure changes must be dead ended into a  pressure gauge      1  Temporarily convert the differen
65. t movement of  the beam is caused by expansion or contraction of the bellows or differential bellows     Proportional Only Controllers  As shown in figure 13  supply pressure enters the relay and bleeds through the fixed orifice before escaping through    the nozzle  Nozzle pressure also registers on the large relay diaphragm  and loading pressure  controller output  pressure  registers on the small relay diaphragm     Figure 13  Schematic of Reverse Acting Proportional Only and Proportional Plus Reset Controllers    CONSTANT SUPPLY  PRESSURE                   INLET END OF RELAY VALVE    SMALL DIAPHRAGM  LARGE DIAPHRAGM  RESTRICTION    PRESSURE SETTING KNOB  PRESSURE SETTING DIAL         EXHAUST END OF RELAY  BOURDON TUBE             RESET BELLOWS                    FIXED    PIVOT       TO FINAL  CONTROL  ELEMENT       PROPORTIONAL    BELLOWS BELLOWS    VALVE  SENSED  PRESSURE  PROPORTIONAL ONLY E ae ro  CONTROLLER       SENSED PRESSURE    GE23696  GE34724 A  E1062             xJOUTPUT PRESSURE  NOZZLE PRESSURE  RESET PRESSURE       A change in the process pressure moves the beam and flapper with respect to the nozzle by either expanding or  contracting the Bourdon tube arc  An increasing process pressure with direct action  or decreasing pressure with  reverse action  produces a nozzle flapper restriction that increases the loading on the large relay diaphragm and opens  the relay valve  Additional supply pressure flows through the relay chamber to increase the loading press
66. t pressure increases   feedback pressure moves the flapper closer to the nozzle to again increase controller output pressure  This process  continues rapidly until the controller output pressure is at the upper range limit  The action of a differential gap  controller is so rapid that output pressure changes from zero to maximum as soon as the switching point is reached     28    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       The action is similar with falling output pressure  Lower feedback pressure lowers the bellows pressure  which moves    the flapper away from the nozzle  This again reduces the output pressure and continues until the output pressure is  zero     Figure 14  Schematic of Reverse Acting Proportional Plus Reset  Controller with Anti Reset Windup       ARROW UP RELIEVES ARROW DOWN RELIEVES  ON INCREASING OUTPUT ON DECREASING OUTPUT   OUTPUT AT ZERO  OUTPUT AT SUPPLY  DURING SHUTDOWN  DURING SHUTDOWN     CONSTANT SUPPLY  PRESSURE           DIFFERENTIAL  RELIEF VALVE    PRESSURE  SETTING KNOB    PRESSURE  SETTING DIAL                   RESTRICTION    zz  waz  A  RESET BELLOWS         TO FINAL  CONTROL  ELEMENT          CANTILEVER   SPRING  PROPORTIONAL  BELLOWS          SENSED  PRESSURE                     SENSED PRESSURE 22 22  OUTPUT PRESSURE  NOZZLEPRESSURE  RESET PRESSURE       GE23697 A  GE34724 A  E1063    Transmitters    Action of a pneumatic transmitter is similar to that of a proportional only controller  Since the outpu
67. t pressure of the  transmitter has no effect on the process pressure  transmitter output pressure is a proportional measure of the  process pressure  The proportional band adjustment determines the span of the transmitter  and the pressure setting  mechanism determines the zero of the transmitter     29    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Maintenance    If the installation includes a Fisher 67 filter regulator  periodically open the drain on the filter regulator to drain  accumulated moisture  Also  push the spring out cleaning wire on the relay orifice  Check the opening of the vent  assembly  key 28  figure 2  or the opening of the remote vent pipe  if one is used  If necessary  clean the openings     Parts are subject to normal wear and must be inspected and replaced as necessary  The frequency of inspection and  parts replacement depends upon the severity of the service conditions     A WARNING    The following maintenance procedures require taking the controller out of service  To avoid personal injury and property  damage caused by the release of pressure or process fluid  observe the following before starting maintenance     e Always wear protective clothing  gloves  and eyewear    e Provide some temporary means of control for the process before taking the controller out of service    e Provide a means of containing the process fluid before removing any measurement devices from the process       Use lock out procedures to b
68. the standard construction  If the process temperature is outside the ambient  operating range of the controller  the length of the  capillary tube run from the sensor point to the  controller process input may be adjusted to protect  the controller from the process temperature    Typical Ambient Temperature Operating Influence    Proportional Control only      3 0  of output span for each 28  C  50  F  change in  temperature between  40 and 71  C   40 and 160  F   for a controller set at 100  proportional band    Proportional Plus Reset Control       2 0  of output span for each 28  C  50  F  change in  temperature between  40 and 71  C   40 and 160  F   for a controller set at 100  proportional band    Transmitters only     3 0  of output span for each 28  C  50  F  change in       temperature between  40 and 71  C   40 and 160  F   for a transmitter set at 100  span    Hazardous Area Classification    Complies with the requirements of ATEX Group II  Category 2 Gas and Dust    C    o u2ap    Refer to figure 26 for location of ATEX marking    Approximate Weight  8 2 kg  18 pounds     Declaration of SEP    Fisher Controls International LLC declares this  product to be in compliance with Article 3 paragraph  3 of the Pressure Equipment Directive  PED  97   23    EC  It was designed and manufactured in accordance  with Sound Engineering Practice  SEP  and cannot  bear the CE marking related to PED compliance     However  the product may bear the CE marking to  indicate complianc
69. ther output pressure ranges  such as 0 4 to 2 0 bar  6 to 30 psig   adjust the values to match the  application     24    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Provide a process pressure source capable of simulating the process pressure range of the transmitter  If an output  pressure gauge is not provided  install a suitable pressure gauge for calibration purposes  Connect a pressure source to  the supply pressure regulator and be sure the regulator is delivering the correct supply pressure to the transmitter     Note    For stability  some transmitter applications will require additional volume than just the gauge  Provide a minimum volume of  approximately 25 cm   1 5 in3  or greater if stability is a problem     Unless otherwise indicated  key number locations are shown in figure 11     1  Complete the above connections and provide a process pressure equal to the sensing element range   2  Rotate the span adjustment knob to the maximum setting on the dial  100 percent span    3  Verify that the calibration adjuster screws  key 48  are at mid position in the calibration adjuster  key 36  slots     Depending upon the transmitter action  perform one or the other of the following procedures     For reverse acting transmitters    4  Rotate the zero adjustment knob to zero    5  Apply an input pressure equal to the sensing element upper range limit    6  Adjust the nozzle  key 57  until the transmitter output pressure is at 0 2 bar  3 ps
70. ther to the CONTROL connection on the back of the case  or to the connection on the left  side of the case  shown in figure 2  depending on the instrument application  Plug the unused connection     For differential pressure instruments  Connect the low pressure line to the CONTROL connection on the side of the  case and the high pressure line to the CONTROL connection on the back of the case as shown in figure 2     When installing process piping  follow accepted practices to ensure accurate transmission of the process pressure to  the controller or transmitter  Install shutoff valves  vents  drains  or seal systems as needed in the process pressure  lines  If the instrument is located such that the adjacent process pressure lines will be approximately horizontal  the  lines should slope downward to the instrument for liquid filled lines and upward to instruments for gas filled lines  This  will minimize the possibility of air becoming trapped in the sensor with liquid filled lines or of condensation becoming  trapped with gas filled lines  The recommended slope is 83 mm per meter  1 inch per foot      If a controller is being used in conjunction with a control valve to control pipeline pressure  connect the process  pressure line in a straight section of pipe approximately 10 pipe diameters from the valve but away from bends   elbows  and areas of abnormal fluid velocities  For pressure reducing service  the process line must be connected  downstream of the valve  For press
71. tial gap controller to proportional only controller by disconnecting the  proportional tubing  key 25  figure 16  from the mounting base  Reinstall the tubing into the other connection in  the mounting base  Remove the proportional band assembly and invert it as shown in figure 16  Do not invert the  reversing block  key 37  figure 16      2  Temporarily invert the proportional band assembly  refer to figure 17      a  Turn the proportional band assembly  key 73  to 10     b  Unscrew the spring adjustor  key 65   removing the bias spring  key 70  and washers  key 62  with it     21    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       c  Unclip the lock spring  key 72   Remove the indicator scale  key 69  and proportional band adjustment knob   key 73      d  Remove the gain adjustment bar  key 63   Flip it over so it attaches to the opposite side of the cantilever spring   key 8  as shown in figure 16 and screw it back down     e  Flip over the indicator scale  key 69   install it and the proportional band adjustment knob  key 73  as a unit  Snap  in the lock spring  key 72      f  Tighten down the spring adjustor  key 65  with the bias spring  key 70  and washers  key 62  until it stops against  the gain adjustment bar  key 63      g  Turn the proportional band adjustment knob to the 10 setting  If it cannot be turned to the 10 setting  loosen the  spring adjustor  key 65    3  Calibrate using the calibration procedure for proportional only contr
72. tor     2  Supply and Output Pressure Gauge  w o process  pressure gauge  1 8 inch connecting stem    2 req d   Dual scale  Brass Plastic    0 2 0 kg cm  and 0 30 psig 11B8577X042  0 4 0 kg cm  and 0 60 psig 11B8577X052  SST  0 2 0 kg cm  and 0 30 psig 11B8583X032  0 4 0 kg cm  and 0 60 psig 11B8583X052  Triple scale  Brass Plastic  0 2 0 bar  0 0 2 MPa  and 0 30 psig 11B8577X012  0 4 0 bar  0 0 4 MPa  and 0 60 psig 11B8577X022  SST  0 2 0 kg cm  and 0 30 psig 11B8583X012  0 4 0 kg cm  and 0 60 psig 11B8583X022  2  Output Pressure Gauge  w process pressure  gauge  1 8 inch connecting stem   Brass Plastic  Triple scale  0 2 0 bar  0 0 2 MPa  and 0 30 psig 11B8577X012  0 4 0 bar  0 0 4 MPa  and 0 60 psig 11B8577X022  3  Supply Pressure Gauge  w process pressure  gauge  1 4 inch connecting stem   Brass Plastic  Triple scale  0 2 0 bar  0 0 2 MPa  and 0 30 psig 11B8579X022  0 4 0 bar  0 0 4 MPa  and 0 60 psig 11B8579X032    Note    Controllers with bellows sensing element use only the 2 0 bar  0 to 0 2  MPa  and 0 to 0 to 30 psig triple scale brass and stainless steel process  pressure gauges  Differential pressure controllers do not use a process  pressure gauge     4  Process Pressure Indicator Gauge  use only when specified   Triple scale  Stainless steel    0 2 0 bar  0 0 2 MPa  and 0 30 psig 11B8584X022  0 20 bar  0 2 0 MPa  and 0 300 psig 11B8584X012  0 69 bar  0 6 9 MPa  and 0 1000 psig 11B8584X032  High Temp  silicone 1N873804142    41    C1 Controllers and Transmitters  
73. ure on the  control valve actuator  A decreasing process pressure with direct action  or increasing pressure with reverse action   produces a nozzle flapper opening that bleeds off pressure on the large relay diaphragm and opens the relay valve to  exhaust controller output pressure from the actuator     27    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       This controller output pressure change feeds back to the proportional bellows  countering the pressure change in the  nozzle and equalizes the relay diaphragm pressure differential  The relay valve maintains a new loading pressure  according to the change in sensed pressure     If the proportional band adjustment is at its maximum setting  10   the cantilever spring in the proportional band  assembly has a low spring rate  allowing more feedback motion to be transferred from the proportional bellows for a  change in output pressure  As the effective length of the cantilever is reduced  its spring rate increases  causing less  feedback motion from proportional bellows  Setting the cantilever spring to its maximum length results in a  proportional band of 100   The lower the proportional band adjustment  the shorter the effective length of the  cantilever spring  The spring rate of the cantilever spring increases as its length shortens  allowing less motion to be  transferred from the bellows to the beam and flapper for a given change in output pressure     Proportional Plus Reset Controllers  
74. ure relief service  the process pressure line must be connected upstream of the  control valve  Install a needle valve in the process pressure line to dampen pulsations     10    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       Vent Assembly    Personal injury or property damage could result from fire or explosion of accumulated gas  or from contact with hazardous  gas  if a flammable or hazardous gas is used as the supply pressure medium  Because the instrument case and cover  assembly do not form a gas tight seal when the assembly is enclosed  a remote vent line  adequate ventilation  and  necessary safety measures should be used to prevent the accumulation of flammable or hazardous gas  However  a remote  vent pipe alone cannot be relied upon to remove all flammable and hazardous gas  Vent line piping should comply with  local and regional codes  and should be be as short as possible with adequate inside diameter and few bends to reduce case  pressure buildup     CAUTION    When installing a remote vent pipe  take care not to overtighten the pipe in the vent connection  Excessive torque will  damage the threads in the connection     The vent assembly  key 28  figure 2  or the end of a remote vent pipe must be protected against the entrance of all  foreign matter that could plug the vent  Use 13 mm  1 2 inch  pipe for the remote vent pipe  if one is required  Check  the vent periodically to be certain it has not become plugged     Controller Op
75. ut pressure is not between 0 6 and 0 7 bar  8 and 10 psig   adjust the controller span by loosening the  two adjusting screws  key 48  and moving the calibration adjuster  key 36  a small distance as indicated in figure 8     12  Repeat steps 6 through 11 until no further adjustment is necessary     13  For C1P and C1B controllers with anti reset windup  remove the two machine screws  anti reset windup cover  and  two O rings installed in step 1 of this procedure  Install the anti reset windup assembly  key 190  with the arrow  pointing in the direction recorded in step 1     14  Proceed to the Startup procedures for proportional plus reset controllers     Figure 8  Reverse Acting Controller Span Adjustment   Proportional Plus Reset Controllers       IF OUTPUT IS    ABOVE BELOW   8TO 10PSIG 8TO 10 PSIG   0 6 TO 0 7 BAR   0 6 TO 0 7 BAR   MOVE ADJUSTER atus     p    MOVE ADJUSTER  RIGHT  FLAPPER  NOZZLE    NOTE    3 TO 15 PSIG  0 2 TO 1 0 BAR  OUTPUT SHOWN   FOR 6 TO 30 PSIG  0 4 TO 2 0 BAR  OUTPUT  ADJUST  VALUES AS APPROPRIATE     A6155 1    For direct acting controllers     6  Apply an input pressure equal to the sensing element lower range value   7  Rotate the pressure setting knob to the minimum value   8  Adjust the nozzle  key 54  until the controller output pressure is between 0 6 and 0 7 bar  8 and 10 psig    9  Apply an input pressure equal to the sensing element upper range value   10  Rotate the pressure setting knob to the maximum value     Note    When performin
76. verse to Direct Action                   34  Relay Replacement              ce eee eee eees 36  Changing Output Signal Range                 37  Parts Ordering          0c cee ee cece eeeeees 40  es    EMERSON        www Fisher com    Process Management    C1 Controllers and Transmitters Instruction Manual  May 2014 D103292X012       Contents  Continued     Parts  Kits  5  scel c eie Ue  ee RYE 41  partsllst   i e EXPANDS 41  CommonParts arreso ea hae ee EE eee 41  Mounting Parts for Panel  Wall  Pipestand  or Actuator Mounting                2  05  50  Introduction  Scope of Manual    This instruction manual provides installation  operating  maintenance  and parts information for the Fisher C1 pressure  controllers and transmitters shown in figure 1  Refer to separate instruction manuals for information regarding the  control valve  actuator  and accessories     Do not install  operate  or maintain C1 pressure controllers and transmitters without first being fully trained and  qualified in valve  actuator  and accessory installation  operation  and maintenance  To avoid personal injury and  property damage  it is important to carefully read  understand  and follow all the contents of this manual  including all  safety cautions and warnings  If you have any questions about these instructions  contact your Emerson Process  Management sales office before proceeding     Description    The C1 pneumatic pressure controllers and transmitters use a bellows or Bourdon tube sensing el
77. wners     The contents of this publication are presented for informational purposes only  and while every effort has been made to ensure their accuracy  they are not  to be construed as warranties or guarantees  express or implied  regarding the products or services described herein or their use or applicability  All sales are  governed by our terms and conditions  which are available upon request  We reserve the right to modify or improve the designs or specifications of such  products at any time without notice     Emerson Process Management   Marshalltown  lowa 50158 USA   Sorocaba  18087 Brazil F  Chatham  Kent ME4 4QZ UK P  Dubai  United Arab Emirates eS  Singapore 128461 Singapore    www Fisher com EMERSON        Pr ess Manaaement     2008  2014 Fisher Controls International LLC  All rights reserved  Frocess Mana g emen t    
78. y 2014 D103292X012       Startup  Proportional Plus Reset Controllers  General Tuning Guidelines    Calibrate the controller prior to this procedure    1  Besure that the supply pressure regulator is delivering the proper supply pressure to the controller    2  Rotate the pressure setting knob to the desired set point    3  Start with a reset setting of 0 05 minutes per repeat  m r  for fast processes  and 0 5 m r for slow processes     4  Setthe proportional band adjustment to 100 percent for fast processes  example  liquid pressure or liquid flow   For  a slow process  example  temperature   calculate the percentage from the equation below     For a slow process  determine the initial proportional band setting in percent from the following equation     2 x Allowable Overshoot     100    PB   Pressure Span       For example   2 x 0 14 bar  Som   x 100    13   2 1 bar 8  2X2 PSIG y io0x   13   30 psig    1 3 proportional band setting  5  Proportional Action     Disturb the system by tapping the flapper lightly or change the set point a small amount and check for system cycling   If the system does not cycle then lower the proportional band  raising the gain  and disturb the system again   Continue this procedure until the system cycles  At that point  double the proportional band setting and begin tuning  the reset     6  Reset Action     Disturb the system  If the system does not cycle then speed up the reset and disturb the system again  Continue this  procedure until the s
79. ystem cycles  When the system cycles multiply the reset time setting by a factor of three  3  and  slow the reset down to the new value  The reset is now tuned     This tuning procedure may be too conservative for some systems  The recommended proportional band and reset  setting should be checked for stability by introducing a disturbance and monitoring the process as previously  described  For some applications  tighter control may be desirable     Differential Gap Controllers    This section describes the adjustments and procedures for calibration and startup  The adjustment locations are  shown in figure 4 unless otherwise specified  The output of each controller is checked at the factory before the  instrument is shipped     To convert a differential gap controller to a proportional only controller or vice versa  refer to the appropriate  procedure in the Maintenance section     If the process pressure can be varied through all or part of the sensing element range or through the two desired    switching points  use the process pressure for calibration  If not  provide a pressure source to simulate the process  pressure range for calibration procedures     20    Instruction Manual C1 Controllers and Transmitters  D103292X012 May 2014       To better understand the adjustments and overall operation of the controller  refer to the Principle of Operation  section in this manual for differential gap controllers and the schematic diagram in figure 13     Adjustments  Adjustmen
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  Samsung BD-1600-XAC User's Manual    67E  Manual  Tks!EX-93211/93511/93711/93911 Panel PC User Manual  Manuale istruzioni d`uso detettore di movimento      Copyright © All rights reserved. 
   Failed to retrieve file