1. from the rack for service without powering down or disconnecting the cables If you are not using the CMA following these procedures will ensure secure attachment and strain relief of the cables behind the system For guidelines on how to route cables within the rack refer to the Dell Best Practices Guide for Rack Enclosures white paper Section 1 Cabling a Dell PowerEdge T610 With a Cable Management Arm CMA This section details how to cable a PowerEdge T610 system using a CMA If you are cabling the system without the optional CMA refer to Section 2 Follow the instructions contained in the Rack nstallation Guide in the rail kit to install the server into the rack Once installed use these instructions to install the cables All illustrations in the following sections were created using a PowerEdge T610 system NOTE PowerEdge T610 systems are compatible with the PowerEdge T710 rails and CMAs 1 1 Connecting the CMA Cables to the System Attach the CMA tray to the back of the rails as described in the CMA nstallation Instructions provided in the CMA kit Connect all applicable cables to the rear of the system and verify that all connections are secure See Figure 1 les Installed ES Figure 1 System with Cab Page 2 Cable Routing Procedures for Dell PowerEdge T610 Systems 1 2 Routing the Power Cables Through the Strain Reliefs After you have installed the tray and cables route the power c
2. Cable Routing Procedures for Dell PowerEdge T610 Systems A Dell Technical White Paper Dell Datacenter Infrastructure Engineering By Chris Kitten and Jose L Flores March 2011 Cable Routing Procedures for Dell PowerEdge T610 Systems THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND TECHNICAL INACCURACIES THE CONTENT IS PROVIDED AS IS WITHOUT EXPRESS OR IMPLIED WARRANTIES OF ANY KIND 2011 Dell Inc All rights reserved Reproduction of this material in any manner whatsoever without the express written permission of Dell Inc is strictly forbidden For more information contact Dell Dell the DELL logo the DELL badge and PowerEdge are trademarks of Dell Inc Page ii Cable Routing Procedures for Dell PowerEdge T610 Systems Contents fapigole Ufed eld MNT o E 2 Section 1 Cabling a Dell PowerEdge T610 With a Cable Management Arm CMA cccccccessseeceeeeeseeeeeeeeeeees 2 1 1 Connecting the CMA Cables to the SySt M cccceccccsssscccessececeesceccescecaeeeecseaeeceseaecesseueeeseaeseeseaecessaeseesaes 2 1 2 Routing the Power Cables Through the Strain Reliefs cccccccssssecceceeseecccceesececeeeeeecesseuesecessueeeeeeesaaanses 3 13 Installation of the CMA 3 Section 2 Cabling a Dell PowerEdge T610 System Without a CMA ccccsseccccesseecceescceee
3. ables through the strain reliefs located on the power supply handles as shown in Figure 2 Figure 2 Routing Power Cables Through the Strain Reliefs par il rui 5 1 3 Installation of the CMA The CMA can be installed on either the rear right or rear left side of the rails Mounting the CMA on the side that is opposite of the power supplies right side mount is recommended otherwise the CMA must be partially disconnected in order to remove the lower power supply Refer to Section 5 for details on power supply replacement NOTE For guidelines on how to route cables within the rack refer to the Dell Best Practices Guide for Rack Enclosures white paper NOTE If you are installing fiber optic cables in the CMA a cable bend radius of at least 1 inch must be maintained throughout the length of the cable It is recommended that fiber optic cables be routed on the exterior of the cable bundle to increase the bend radius of the fiber optic cables through the CMA Additionally a large amount of slack at the entrance and exit of the CMA is recommended 1 Install the CMA on either the rear right or rear left side of the rails by attaching both CMA housings to the attachment brackets on the rails 2 Route the cables through the CMA while avoiding twisting the cables Use the hook and loop straps on the CMA to secure the cables See Figure 5 5 If the cable bundle includes a keyboard video and mouse KVM dongle place the dongle in
4. eeceseuecesseseesaeeseesauees 5 21 Routine the Cables sercis nni EE EE A 5 Section 3 Replacing a Power Supply on a PowerEdge T610 System With a CMA eere 6 Table of Figures Figure E Systemi With C abies Mtae sousse erae F2 ater i Tao aha Rao E FB Can Seri g IUE ru D eRR CE MEA AREE 2 Figure 2 Routing Power Cables Through the Strain Reliefs senes 5 Figure 5 ROUUING the Cables Through the CMA ssocessinskTa nkctte EbnUCBURE Pale butPERREE BST VA E RYMER ERU Dn eiiieaenii 4 Figure 4 Right Side Mounted CMA Installation essen nnne nnn nnn n nnns 4 Fig re 5 Left Side Mounted CMA Installation assess ritas bagpacuit nde Sis la ela ce Mut a nac BRE RH Katina D ER Ruth 5 Figure 6 Cable Routing Without a CMA cccccccccccccsesssssssesssccsessceeseeeeeeeeseesesesnsesaseeeaeeseeeeeeeeseseeesesetsnnseseeeeeetens 5 Figure 7 Replacing the Power SUPPlY sues csontosFoesumutlg tutup bito eE dasuvt I EEEE EEEa E Eea 6 Page 1 Cable Routing Procedures for Dell PowerEdge T610 Systems Introduction This white paper covers recommended cable routing procedures for Dell PowerEdge T610 systems in the following racks e PowerEdge 2410 e PowerEdge 4210 e PowerEdge 2420 e PowerEdge 4220 including wide and deep versions e PowerEdge 4820 including wide and deep versions If you are using the optional CMA following these procedures will allow you to extend the system
5. must be powered down and all cables disconnected before it can be removed from the rack 2 1 Routing the Cables 1 Connect all applicable cables to the rear of the system and verify that all connections are secure 2 Using the hook and loop straps supplied with the rail kit bundle the cables and secure them to either the left or right CMA attachment brackets as described in the Rack nstallation Instructions See Figure 6 for an example of data cables secured to the left CMA bracket and power cables secured to the right CMA bracket 5 tis recommended that the cables be secured to the outer brackets but cables may be secured to the inner brackets as well if desired Figure 6 Cable Pii THUS a gy dh Page 5 Cable Routing Procedures for Dell PowerEdge T610 Systems Section 3 Replacing a Power Supply on a PowerEdge T610 System With a CMA NOTE The steps described below apply to the bottom power supply only when the CMA is installed to the left side If the CMA is attached to the right side both power supplies can be removed without removal of the CMA If the CMA is attached to the left side the top power supply can be replaced with the CMA in its closed retracted position 1 Swing the CMA to its service position 2 Disengage the strain relief and disconnect the power cord from the power supply 5 Disconnect the inner CMA attachment housing from the rail as shown in Figure 8 4 While supporting the CMA with
6. one hand remove and replace the power supply with the other hand as shown in Figure 8 5 Reconnect the CMA attachment housing to the rail 6 Plug in the power cord re engage the strain relief and return the CMA to the closed retracted position Figure 7 Replacing the Power Supply TINE ED SENS Mac vr t Ld g Inner CMA attachment housing has been disconnected Page 6
7. side the CMA basket 4 Once you have routed all the cables through the CMA dress the cable slack between the back of the system and the entrance of the CMA using the tie wraps shown in yellow in all illustrations provided in the CMA kit Page 3 Cable Routing Procedures for Dell PowerEdge T610 Systems 5 Clip off the excess length of material from the tie wraps Make sure that the heads of the tie wraps are positioned so as to avoid interference with adjacent systems Return the CMA to the closed retracted position 6 Extend the system out of the rack to verify that there is sufficient slack in the cables on both ends of the CMA See Figure 4 for an example of a completed right side mounted CMA installation See Figure 5 for an example of a completed left side mounted CMA installation Figure 3 Routing the Cables Through the CMA NOTE Do not store excess cable Slack inside the CMA The cable may protrude through the CMA thus causing binding and potentially damaging the cable Cables entering the CMA should have a small amount of slack to avoid cable strain when the CMA is extended KVM dongle placed inside the basket Page 4 Cable Routing Procedures for Dell PowerEdge T610 Systems Figure 5 Left Side Mounted CMA Installation Section 2 Cabling a Dell PowerEdge T610 System Without a CMA NOTE The CMA on Dell PowerEdge T610 systems is optional Without the CMA installed the system
Download Pdf Manuals
Related Search
Related Contents
SW-200_201 OSD User`s Guide Set & $ave - Hunter Fan Splash Drone Quick Guide EverFocus EZ-VF325NH DT-SCU User Manual Symmons SLW-4412 Instructions / Assembly VQ361412REV00_Functional Arm Brace IFU Digitalanzeige, Typ DI25 Digital indicator, model DI25 Sony Xplod XR-CA650X User's Manual Copyright © All rights reserved.