ATEN Technology PE7216 User's Manual

image

Contents

1. Bl elk sw 8 w Note There is a pre installed administrator account It can be used to set up the device and to begin creating users and groups The Username for this account is administrator the password is password For security purposes we strongly recommend changing these to something unique Administrator Information This section is used to set the Administrator name and password Only Administrators can view this section For details see Changing the Administrator Login page 40 51 Chapter 6 User Management User Information To add a user do the following 1 2 3 4 5 Select the user type in the Management drop down menu Key in a name and password in the Name and Password fields Set the outlet by outlet permissions of the user in the Outlet field Set the Management field to Enable Click Save to save your settings Note Values must be entered in both the Name and Password fields in order to enable an account The various options are explained in more detail in the following table Field Description Management The Management field allows you to Enable or Disable a user s account Enable stores the user account Disable disables the user account Name From 1 to 16 characters are allowed Password From 1 to 16 ch
2. V Note The PE7324 PE8324 PE9324 unit components are identical except for the outlet LEDs the PE7324 has none the PE8324 has 24 and the PE9324 has 16 as shown by number 5 above 21 Chapter 1 Introduction No Item Description Power Outlets Port and LED Panel 24 in total 21 x IEC 320 C13 3 x IEC 320 C19 Bank 1 1 Outlet 1 8 7 C13 1 x C19 Bank 1 2 Outlet 9 16 7 x C13 1 x C19 Bank 2 Outlet 17 24 7 x C13 1 x C19 The Port and LED panel contains Readout Section and LEDs Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 23 Circuit Breakers As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Power Cord Plug the cord into an AC power source B models connect to a NEMA L6 30P source G models connect to an IEC 60309 32A source Outlet Status LEDs PE8324 x 24 and PE9324 x 16 only These LEDs indicate outlet status Lights ORANGE for powered on Off for powered off Note Holes for ATEN Lok U Plug cable holders are located around the outlets
3. 55 Chapter 8 Setup Service Ports As a security measure if a firewall is being used the Administrator can specify the port numbers that the firewall will allow If a port other than the default is used users must specify the port number as part of the IP address when they log in Ifan invalid port number or no port number is specified the eco PDU will not be found Select whether to allow only secure browser logins as show below Service Ports O Only HTTPS HTTP HTTPS HTTP 80 HTTPs 443 An explanation of the fields is given in the table below Field Explanation HTTP The port number for a browser login The default is 80 HTTPS The port number for a secure browser login The default is 443 Note 1 Valid entries for all of the Service Ports are from 1 65535 2 The service ports cannot have the same value You must set a different value for each one 3 If there is no firewall on an Intranet for example it doesn t matter what these numbers are set to since they have no effect eco PDU PE Series User Manual IPv4 Configuration The PDU s IPv4 IP and DNS addresses the traditional method of specifying IP addresses can either be assigned dynamically DHCP or a fixed IP address can be specified IPv4 Configuration Obtain IP address automatically DHCP o Set IP address manually Fixed IP IP Address 10 3 52 61 Subnet Mask 255 255 254 0 Default Gateway 10 3
4. Item Description Check Main Firmware Version If you enable Check Main Firmware Version the eco PDU s current firmware level is compared with that of the upgrade file If the current version is equal to or higher than the upgrade version a popup message appears to inform you of the situation and stops the upgrade procedure Name Lists all of the eco PDU devices Click to put a check in the checkbox of the device s whose firmware you want to upgrade F W Version Displays the eco PDU s current firmware version Filename As new versions of the firmware become available they are posted on our website and can be downloaded to a convenient location on your computer Click the Browse button to select the downloaded upgrade file Upgrade Click this button to upgrade the firmware of the selected devices 73 Chapter 9 PDU Upgrading the Firmware To upgrade the firmware refer to the screenshot on the preceding page and do the following 1 Go to our website and download the new firmware file to a convenient location on your computer 2 Click the Browse button navigate to where the firmware file is located and select it 3 Click Upgrade to start the upgrade procedure Ifyou enabled Check Main Firmware Version the current firmware level is compared with that of the upgrade file If the current version is equal to or higher than the upgrade version a popup message appears to inform you of the situ
5. 1 ID Section The ID of the selected PDU Phase Bank Outlet appears in the LED display window When PDU Phase LED is lit the LED display window will show P1 When BANK LED is lit use the Up and Down buttons to move forward or backward through the following sequence 0102 Bank1 gt Bank2 When the Outlet LED is lit use the Up and Down buttons to move forward or backward through the outlets 01 gt 02 gt 03 gt 01 Outlet1 gt Outlet2 gt 0utlet3 gt Outlet1 2 Readout Section When PDU Phase Bank Outlet is selected readouts for Current Voltage Power and IP address appear in the display window Press the button next to the LED display window to cycle the selection between the items the LEDs next to the items indicate which one the display relates to When a sensor is selected the display shows temperature humidity differential pressure according to the sensor type 3 Status LEDs Power Lights when the unit is powered up and ready to operate Door sensor Lights Red when the door is open See Door Sensor page 9 for details 29 Chapter 1 Introduction No Item Description 4 Sensor External sensors plug into these four RJ 11 ports See Ports Environment Sensors page 9 and Securing the Sensors page 36 for further information 5 Reset This switch is recessed and must be pushed with a thin object Switch such as the end of a paper clip
6. the eco PDU waits for the amount time set in the Power On Delay field then sends power to the server When the server receives the power it turns itself on Note For Safe Shutdown and Reboot the computer must be running Windows 98 or higher or Linux and the Safe Shutdown program available by download from our website must be installed and running on the computer Continues on next page 49 Chapter 5 Energy Heading Meaning Remote Turn Kill the Power If this option is selected the eco PFDU waits for the ON Method amount time set in the Power Off Delay field and then turns the Outlet s power Off Turning the power off performs a cold non safe shutdown MAC Address In order to use either of the Safe Shutdown and Restart methods the MAC address of the computer connected to the outlet must be filled in here When you have finished making your configuration settings click Save 50 Chapter 6 User Management Overview When you select the User tab the screen comes up with the Accounts menu and the Administrator Information and User Information displayed in the main panel Administrator information Name administrator Password eeeeeeee SNMPv3 account information Name administrator Auth password sesssses Priv Password eeeeeceeee SNMPv1 v2c community Read community administrator Write community administrator
7. 4 pin dry sensor port on the units front panel Note See Door Sensor page 9 for further information 6 Depending on your model connect the eco PDU s built in power cord to an AC power source or use the power cord provided to connect the eco PDU s power socket to an AC power source Once you have finished these installation steps you can turn on the eco PDU and the connected devices 33 Chapter 2 Hardware Setup Installation Diagram 10000000 34 eco PDU PE Series User Manual Securing the Cables For added safety use ATEN Lok U Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit Secure the cable holders using the specially designed holes around the individual power outlets as shown below Note 1 Cable holders are an optional accessory See Cable Holders page 10 2 Use only the ATEN Lok U Plug cable holders that have been specifically designed to work with the eco PDU Using any other kind of cable securing device could be highly dangerous 35 Chapter 2 Hardware Setup Securing the Sensors Connect the sensors to the eco PDU s front panel sensor ports and secure them using sensor mounts tie wraps and adhesive cable tie holders If you use a tie wrap to secure the sensor tighten the tie wrap over t
8. 7 x C13 1x C19 Port and LED Panel Circuit Breaker Pushbutton The Port and LED panel contains Readout Section and LEDs Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 23 As a safety measure if there is an over current situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Power Inlet The power cord that connects the unit to an AC power source plugs into this socket B models connect to a NEMA 6 20P 208V source G models connect to an IEC 60320 C20 source Outlet Status LEDs These 8 LEDs indicate outlet status Lights ORANGE for powered on Off for powered off Output Power Indicator This LED lights steady to indicate output power for the related bank Note Holes for ATEN Lok U Plug cable holders are located around the outlets See Securing the Cables page 35 for further information 20 eco PDU PE Series User Manual PE7324 PE8324 PE9324 PE7324 PE8324 PE9324 CO asa COSA aaa aa hal Es Cpo f lod
9. A e rido nda a ee ect ae Sasi eee et ey 1 Comparison Chart lt a sar ee nr cece cette 3 Feature ohorere bee ee itd ease ee eae fog Eta Pe a dA bate Saye Ea 5 Power Distribution snes encer ateni an erateds piotr Aiii Ea 5 Remote ACCESS 4 250 eA o e Dt ah 5 Operation erie iea aa E N eco apta ee UE 5 Management 6 SECU Va A Me ND eau Dea Decal ee deat one aa 6 eco Sensors Energy Management Software o o o o 7 Proactive Overload Protection POP 200 0055 7 Requirements 00 00 ce tees 8 Optional Accessories ss upa is eee See RED Ge 9 Environment Sensors 00 000 c cece eee eee eee 9 Door Sensor ssa eevee Aas Ad Be Bde Bae ee al a 9 Cable HolderS us asse a e rep eae eee ty yates ober 10 Components ssa a ane ae a eo eo ad E 11 PE7214B PET214G iret sodas A Sh Sasha ee 11 PE7216 PE8216 PE9216 1 kee 13 PESITOS pienine ap aie dg whe te ls ini Barato us 15 PEBIZIKS chee ceili ee i Ae Raa de ee a 17 RE9222B PE92226 disser pa Ae a o e Sa id 19 PE7324 PE8324 PEDIDA 21 PE8324A PE8324JA sir neun e ia na a a a ae e aaa i 23 PEI La spa Ni o A A A e q leds 25 RE9330 ise e A sh tie ee A aE de 27 Port and LED Panel All models 0 00 00 e eee eee 29 Chapter 2 Hardware Setup Before You Begin 0000 c ete eae 31 Rack Mounting ie sms a pec tee ce eee eee ee eee aie 31 eco PDU PE Series User Manual PDU Placement cieo 460 ao oe Sa sp GE
10. Login Username Password Language EFI Login Provide a valid Username and Password set by the eco PDU administrator Select your preferred Language from the drop down menu Then Click Login to bring up the browser Main Page 41 Chapter 4 Logging In The eco PDU Main Page After you have successfully logged in the eco PDU Main Page comes up with the Energy Connections page displayed Note The screen depicts an Administrator s page Depending on a user s type and permissions and your PE model not all of these elements appear 42 eco PDU PE Series User Manual Page Components The web page screen components are described in the table below No Item Description 1 Tab Bar The tab bar contains the eco PDU s main operation categories The items that appear in the tab bar are determined by the user s type and the authorization options that were selected when the user s account was created 2 Menu Bar The menu bar contains operational sub categories that pertain to the item selected in the tab bar The items that appear in the menu bar are determined by the user s type and the authorization options that were selected when the user s account was created 3 Sidebar The Sidebar provides a tree view listing of outlets that relate to the various tab bar and menu bar selections 4 Help Connects to on line help at the ATEN website for the device s conf
11. Press and release to reboot the device Press and hold for more that three seconds to reset the eco PDU to its factory default settings 6 LAN Port The cable that connects the unit to the Internet LAN or WAN plugs in here 7 Door Sensor This 4 pin dry contact port is for a door sensor support allows the monitoring of rack mount enclosure door access to notify users when a door has been opened See Door Sensor page 9 for details 30 Chapter 2 Hardware Setup Before You Begin 1 Important safety information regarding the placement of this device is provided on page 76 Please review it before proceeding 2 Make sure that power to all the devices you will be connecting have been turned off You must unplug the power cords of any computers that have the Keyboard Power On function 3 See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Rack Mounting The eco PDU can be mounted in a OU configuration on the side of a rack To rack mount the device use the rack mounting brackets that came with your device The brackets can be mounted either near the top and bottom of the back panel or the top and bottom ends of the device as shown in the diagram below Ny 31 Chapter 2 Hardware Setup PDU Placement For safety reasons the eco PDU should not be installed with the power sockets facing direc
12. See Securing the Cables page 35 for further information 22 eco PDU PE Series User Manual PE8324A PE8324JA 23 Chapter 1 Introduction No Item Description 1 Power Outlets 2 Port and LED Panel 24 in total 24 x NEMA 5 15R Bank 1 1 Outlet 1 8 Bank 1 2 Outlet 9 16 Bank 2 Outlet 17 24 The Port and LED panel contains Readout Section and LEDs Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 28 3 Circuit Breakers As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker 4 Power Cord Plug the cord into an AC power source A models connect to a NEMA L5 30P UL source JA models connect to an NEMA L5 30P PSE source 5 Outlet Status LEDs These 24 LEDs indicate outlet status Lights ORANGE for powered on Off for powered off Note Holes for ATEN Lok U Plug cable holders are located around the outlets See Securing the Cables page 35 for further information 24 eco PDU PE Series User Manual PE7328 25 Chapter 1 Introduction
13. The device should be operated from the type of power source indicated on the marking label If you are not sure of the type of power available consult your dealer or local power company To prevent damage to your installation it is important that all devices are properly grounded The device is equipped with a 3 wire grounding type plug This is a safety feature If you are unable to insert the plug into the outlet contact your electrician to replace your obsolete outlet Do not attempt to defeat the purpose of the grounding type plug Always follow your local national wiring codes The equipment should be installed near the wall socket outlet and the disconnect device appliance coupler on detachable power supply cord or plug on non detachable power supply cord should be readily accessible 76 eco PDU PE Series User Manual Do not allow anything to rest on the power cord or cables Route the power cord and cables so that they cannot be stepped on or tripped over To help protect your system from sudden transient increases and decreases in electrical power use a surge suppressor line conditioner or uninterruptible power supply UPS Position system cables and power cables carefully Be sure that nothing rests on any cables When connecting or disconnecting power to hot pluggable power supplies observe the following guidelines Install the power supply before connecting the power cable to the power supply Unpl
14. chapter For further setup information continue with this chapter 38 eco PDU PE Series User Manual Network Configuration To set up the network do the following 1 Click the Setup tab 2 This opens on the Device Configuration page A screen similar to the one below appears POU Name PESI2GA MAC Address 00 10 74 A2 00 00 Firmware Version FM Ver 1 0 061 Rack Location name PE9324A Service Ports Only HTTPs HTTP HTTPs HTTP 80 HTTPs 443 IPv4 Configuration Obtain IP address automatically DHCP Set P address manually Fixed IP P Address 10 3 5261 Subnet Mask 255 255 254 0 Default Gateway 10 3 53 254 opyright 2012 ATEN International Co Lt 3 Fill in the fields according to the information provided under Device Configuration page 55 39 Chapter 3 Basic Operation and First Time Setup Changing the Administrator Login To change the default Administrator username and password do the following 1 Click the User tab Once users have been added to the system the Accounts page displays a detailed list of users with more information about them in the large central panel Administrator information Name administrator Password essssese SNMPv3 account information Name administrator Auth password eeeeeeee Priv Password eeweeeeeee SNMPv1 v2c community Read community administrator Write community administ
15. in order to generate a complete energy efficient data chart Higher sensor installation density is helpful to generate more accurate data 8 16 port models have 4 sensor ports Higher sensor installation density is helpful to generate more accurate data To get the most complete eco Sensors Dashboard data the recommended 4 sensor setup is show in the table below Port Location Part Number Sensor Sensor 1 Intake EA1140 or Temperature or ora EKE EA1240 Temperature Humidity Sensor 3 Exhaust Sensor 4 Exhaust or Floor EA1340 Differential Pressure Door Sensor All models in the PE7xxx PE8xxx PE9xxx range feature a 4 pin dry contact port for door sensors that supports the monitoring of rackmount enclosure door access to notify users when a door has been opened See the table below for information about the two available door sensors Please contact your ATEN dealer for purchasing information Port Part Number Sensor Door Sensor EA1440 Photo Sensor EA1441 Inductive Proximity Sensor Sensor Management Sensors can be managed via the eco PDU s built in graphical user interface GUI or with the NRGence eco Sensors software that can be downloaded from the ATEN website The download link can be found on the software CD provided with the eco PDU package Chapter 1 Introduction Cable Holders Cable holders are optional accessories For added safety use ATEN Lok U Plug cab
16. its original name In the Password field key in the same password that you used to save the file Note If you did not set a password when you created the backup file you can omit this step Select as many of the options that are presented as you wish to restore Click Restore After the file is restored a message appears to inform you that the procedure succeeded 75 Appendix Safety Instructions General Ad This product is for indoor use only Read all of these instructions Save them for future reference Follow all warnings and instructions marked on the device Do not place the device on any unstable surface cart stand table etc If the device falls serious damage will result Do not use the device near water Do not place the device near or over radiators or heat registers The device cabinet is provided with slots and openings to allow for adequate ventilation To ensure reliable operation and to protect against overheating these openings must never be blocked or covered The device should never be placed on a soft surface bed sofa rug etc as this will block its ventilation openings Likewise the device should not be placed in a built in enclosure unless adequate ventilation has been provided Never spill liquid of any kind on the device Unplug the device from the wall outlet before cleaning Do not use liquid or aerosol cleaners Use a damp cloth for cleaning
17. to generate more accurate data See Optional Accessories page 9 for further information 2 eco PDUs are primarily designed for access via Intranet extra network security protection is suggested for Internet access usage 3 Not all models support all features See Comparison Chart page 3 and Specifications page 83 for full details eco PDU PE Series User Manual Comparison Chart Meteri Outlet Model Inlet Cord Outlets Esse SLET PE7214B NEMA6 20P 14 12x IEC320 C13 PDU No Outlet PE7214G IEC 60320 C20 14 12 x IEC320 C13 PDU No 2 x IEC320 C19 1 x Bank Outlet PE7216B NEMA6 20P 16 14x IEC 320C13 PDU No 2 x IEC 320 C19 1x Bank PE8216B Oullet Yes 16 16 PE9216B Yes 8 16 PE7216G IEC 60320 C20 No PE8216G Yes 16 16 PE9216G Yes 8 16 PE8316G IEC 60309 32A 16 10 x IEC 320C19 PDU Yes 16 16 6 x IEC 320 C13 2 x Bank Outlet PE8121kJ NEMA L6 15P 21 21 x IEC 320 C13 with PDU 1x Yes 21 21 lock Bank Outlet PE9222B NEMA6 20P 22 19x EC320C13 PDU 1x Yes 8 22 208V 3 x IEC320 C19 Bank Outlet PE9222G IEC 60320 C20 22 19x 1EC320C13 PDU 1x Yes 8 22 3 x IEC320 C19 Bank Outlet PE8324A NEMALS5 30P 24 24 x NEMA 5 15R PDU 2x Yes 24 24 UL Bank Outlet PE8324JA NEMAL5 30P 24 24 x NEMA 5 15R PDU 2x Yes 24 24 PSE Bank Outlet PE7324B J NEMA L6 30P 24 21 x IEC 320 C13 PDU No 3 x IEC 320 C19 2 x Bank P
18. 0 Power Distribution Unit 1 Power Cord 14 port 16 port 21 port and 22 port models only excluding PE8316G 1 Mounting Kit 1 CD ROM 1 User Instructions Check to make sure that all of the components are present and in good order If anything is missing or was damaged in shipping contact your dealer Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU installation Features may have been added to the eco PDU since this manual was published Please visit our website to download the most up to date version Copyright 2013 ATEN International Co Ltd Manual Date 2013 12 23 NRGence and the NRGence logo are registered trademarks of ATEN International Co Ltd All rights reserved All other brand names and trademarks are the registered property of their respective owners eco PDU PE Series User Manual Contents FCG Informationy iss A tan E dE RR aa E AA ii SJ P 11364 2006 ii A Ta e ii User Information oooocooccccoooo iii Online Registration 0 2 ee a iii Telephone Support eisini a e a eee iii User NOTICE ai morig ma A a e iii PE Device Safety Notice coooocoooo conoser iii Package Contents 223020219 beds apro Pe es ML ee es iv Conventions xana id ia oe bid Pia eater ee Lc Ena viii Product Information ooooccooooccoooo eee ix Chapter 1 Introduction Overview
19. 09 32A Power IEC Total 6 x IEC320 C13 10 x IEC320 C19 Outlets Bank 1 Outlet 1 8 3 x C13 5 x C19 Bank 2 Outlet 9 16 3x C13 5 x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status 16 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Outlet Power Indicator 1 Red Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet 2 x Pushbutton Select Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal Input Power 100 240V 50 60Hz 32A Nominal Input Output Voltage 100 240 VAC Power Capacity 7360W Nominal Output Power Per Port C13 100 240V 50 60Hz 10A C19 100 240V 50 60Hz 15A TUV de rated 16A Max Total 100 240V 50 60Hz 30A TUV de rated 32A Max Environment Operating Temperature 0 50 C UL 60950 EN 60950 de rated 0 30 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 5 2 kg Dimensions L x W x H 135 9 x 6 60 x 4 40 cm 88 eco PDU PE S eries User Manual PE8121kJ Fu
20. 15 22 7 x C13 1 x C19 Bank 2 Outlet 23 30 7 x C13 1x C19 The Port and LED panel contains Readout Section and LEDs Environmental Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 28 Circuit Breaker As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Power Cord The power cord that connects the unit to an AC power source plugs into this socket B models connect to a NEMA L6 30P source G models connect to an IEC 60309 32A source Output Power Indicator This LED lights steady to indicate output power for the related bank Outlet Status LEDs PE9330 x 16 only These LEDs indicate outlet status Lights ORANGE for powered on Off for powered off 28 eco PDU PE Series User Manual Port and LED Panel All models Pou IPHASE O BANK O outLET Simultaneously press sec to toggle PDU Phase Bank Outlet O O1 CURRENT A O VOLTAGE V O POWER kW Osa 9 2 READOUT Je TOO 3 4 DOOR SENSOR J NAGefce PE8216G SENSOR DOOR 1 2 LAN SENSOR 12 D D G RESET O No Item Description
21. 16G Power Outlets Direct 16 Connectors Power Inlet 1 x IEC 320 C20 Power NEMA NA Outlets TEC Total 14 x IEC 320 C13 2 x IEC 320 C19 Bank 1 1 Outlet 1 8 7 x C13 1x C19 Bank 1 2 Outlet 9 16 7 x C13 1x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status NA 8 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 1 x Non fuse Breaker Nominal Input Power 100 240V 50 60Hz 16A Power Capacity 4 60kW Nominal Per Port IEC 320 C19 100 240V 50 60Hz 15A TUV 16A Max Output Power IEC 320 C13 100 240V 50 60Hz 10A Total 100 240V 50 60Hz 15A TUV 16A Max Environment Operating Temperature 0 40 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 3 8 kg Dimensions L x W x H 132 48 x 6 60 x 4 40 cm 87 Appendix PE8316G Function PE8316G Power Outlets Direct 16 Connectors Power Cord 1 x IEC 603
22. 2 168 0 200 then click OK A second dialog box similar to the one below appears The page at https 172 17 17 6 says xl Y Enter the end IP address for example 192 168 1 255 67 Chapter 8 Setup 3 To filter a single IP address key in the same address as the start IP To filter a continuous range of addresses key in the end number of the range for example 192 168 0 225 4 After filling in the address click OK Repeat these steps for any additional IP addresses you want to filter To add a MAC filter do the following 1 Click Add A dialog box similar to the one below appears The page at https 172 17 17 6 says q xi u Enter the MAC address for example 004854655511 PP La cana 2 Specify the MAC address in the dialog box for example 001074670000 then click OK Repeat these steps for any additional MAC addresses you want to filter IP Filter MAC Filter Conflict Ifthere is a conflict between an IP filter and a MAC filter for example where a computer s IP address is allowed by the IP filter but its MAC address is excluded by the MAC filter then that computer s access is blocked In other words if either filter blocks a computer then the computer is blocked no matter what the other filter is set to Modifying Filters To modify a filter select it in the IP Filter or MAC Filter list box and click Modify The Modify dialog box is similar to the Add dialog bo
23. 3 10 x IEC320 C19 Bank 1 Outlet 1 8 3 x C13 5 x C19 Bank 2 Outlet 9 16 3 x C13 5 x C19 Port and LED Panel Circuit Breakers The Port and LED panel contains Readout Section and LEDs Environmental Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 28 As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Power Cord Plug the cord into an AC power source B models connect to a NEMA L6 30P source G models connect to an IEC 60309 32A source Outlet Status LEDs These 16 LEDs indicate outlet status Lights ORANGE for powered on Off for powered off Note Holes for ATEN Lok U Plug cable holders are located around the outlets See Securing the Cables page 35 for further information 16 eco PDU PE Series User Manual PE8121kJ e gt ee o a 17 Chapter 1 Introduction No Item Description Power Outlets Port and LED Panel 21 in total 21 x IEC 320 C13 Bank 1 1 Ou
24. 53 254 Obtain DNS server address automatically Set DNS server address manually Preferred DNS Server 0 0 0 0 Alternate DNS Server 0 0 0 0 For dynamic IP address assignment select the Obtain IP address automatically radio button This is the default setting To specify a fixed IP address select the Set IP address manually radio button and fill in the IP address with values appropriate for your network For automatic DNS Server address assignment select the Obtain DNS Server address automatically radio button To specify the DNS Server address manually select the Set DNS server address manually radio button and fill in the addresses for the Preferred and Alternate DNS servers with values appropriate for your network Note 1 Ifyou choose Obtain IP address automatically when the device starts up it waits to get its IP address from the DHCP server If it hasn t obtained the address after one minute it automatically reverts to its factory default IP address 192 168 0 60 2 If the device is on a network that uses DHCP to assign network addresses and you need to ascertain its IP address see P Address Determination page 81 for information 3 Specifying the Alternate DNS Server address is optional 57 Chapter 8 Setup IPv6 Configuration IPv6 is the new 128 bit format for specifying IP addresses The PDU s IPv6 IP and DNS addresses can either be assigned dynamically DHCP or a fixed IP
25. 6 PE9216G Yes 8 16 PE8316G IEC 60309 32A 16 10 x IEC 320 C19 PDU Yes 16 16 6x IEC 320013 2x Bank Outlet PE8121kJ NEMA L6 15P_ 21 21 x IEC 320 C13 PDU 1x Yes 21 21 with lock Bank Outlet PE9222B NEMA 6 20P 22 19 x IEC320 C13 PDU 1x Yes 8 22 PE9222G IEC 60320 C20 22 19 x IEC320 C13 PDU 1x Yes 8 22 PE8324A NEMA L5 30P 24 24 x NEMA 5 15R PDU 2x Yes 24 24 UL Bank Outlet PE8324JA NEMA L5 30P 24 24 x NEMA 5 15R PDU 2x Yes 24 24 PSE Bank Outlet PE7324B J NEMA L6 30P 24 21 x IEC 320 C13 PDU No ae ees 3 x IEC 320 C19 2xBank Dn PE8324B J Oii Yes 24 24 PE9324B J Yes 16 24 PE7324G IEC 60309 32A No PE8324G Yes 24 24 PE9324G Yes 16 24 83 Appendix Outlet Model Inlet Cord Outlets Metering Level Switching PE7328B J NEMA L6 30P 28 24 x IEC 320 C13 PDU 2x No 4 x IEC 320 C19 Bank Outlet PE7328G IEC 60309 32A PE9330B J NEMA L6 30P 30 26 x IEC 320 C13 PDU 2x Yes 16 30 4 x IEC 320 C19 Bank Outlet PE9330G IEC 60309 32A Note The J models are identical to their B model counterparts but have power cords designed for the Japanese market 84 eco PDU PE Series User Manual PE7214B PE7214G Function PE7214B PE7214G Power Outlets Direct 14 Connectors Power Cord 1 x NEMA 6 20P 208V 1 x IEC 320 C20 Power IEC Total 12 x IEC320 C13 2 x I
26. 6 in total 14 x IEC 320 C13 2 x IEC 320 C19 Bank 1 1 Outlet 1 8 7 C13 1 x C19 Bank 1 2 Outlet 9 16 7 x C13 1 x C19 2 Port and LED Panel The Port and LED panel contains Readout Section and LEDs Environmental Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 28 3 Circuit Breaker As a safety measure if there is an overcurrent Pushbutton situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker 4 Power Inlet The power cord that connects the unit to an AC power source plugs into this socket B models connect to a NEMA 6 20P source G models connect to an IEC 60320 C20 source 5 Outlet Status LEDs PE8216 x 16 and PE9216 x 8 only These LEDs indicate outlet status Lights ORANGE for powered on Off for powered off Note Holes for ATEN Lok U Plug cable holders are located around the outlets See Securing the Cables page 35 for further information 14 eco PDU PE Series User Manual PE8316G Chapter 1 Introduction No Item Description Power Outlets Total 6 x IEC320 C1
27. 90 PE7324B J PE8324B J PE9324BN 1 eee 91 PE8324A PE8324JA 2 et ttt 92 PE7324G PE8324G PE9324G 1 ee 93 PE7328B J PE 3286 sussa sue wad ete ee Eee BR eS 94 PE9330B J J PE9330G ar esd Ante EE EO ae ei eo Barend Be 95 Administrator Login Failure 0 0 cece eee eee 96 Limited Warranty ass ci ele ee ae etic bark eed 97 vii eco PDU PE Series User Manual Conventions This manual uses the following conventions Monospaced 1 Indicates text that you should key in Indicates keys you should press For example Enter means to press the Enter key If keys need to be chorded they appear together in the same bracket with a plus sign between them Ctrl Alt Numbered lists represent procedures with sequential steps Bullet lists provide information but do not involve sequential steps Indicates selecting the option on a menu or dialog box for example that comes next For example Start Run means to open the Start menu and then select Run Indicates critical information viii eco PDU PE Series User Manual Product Information For information about all NRGence products and how they can help you save money in the data center visit NRGence on the Web or contact an ATEN Authorized Reseller Visit ATEN on the Web for a list of locations and telephone numbers International http www aten com North America http www aten usa com Chapter 1 Introducti
28. AC power source plugs into this socket B models connect to a NEMA 6 20P 208V source G models connect to an IEC 60320 C20 source Output Power Indicator This LED lights steady to indicate output power for the related bank Note Holes for ATEN Lok U Plug cable holders are located around the outlets See Securing the Cables page 35 for further information 12 eco PDU PE Series User Manual PE7216 PE8216 PE9216 PE721 o PE8216 PE9216 E z 3 KOLO E y 000000 D 60 Ed Beed bed Opa fs ey je com cem cem Ee CON oN eo Co eens eo i Ty Note The PE7216 PE8216 PE9216 unit components are identical except for the outlet LEDs the PE7216 has none the PE8216 has 16 and the PE9216 has 8 as shown by number 9 above Chapter 1 Introduction No Item Description 1 Power Outlets 1
29. ATEN eco PDU PE Series PE7214 PE7216 PE7324 PE7328 PE8121kJ PE8216 PE8316G PE8324 PE8324A PE8324JA PE9216 PE9222 PE9324 PE9330 Power Distribution Unit User Manual www aten com eco PDU PE Series User Manual FCC CE Information FEDERAL COMMUNICATIONS COMMISSION INTERFERENCE STATEMENT This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 ofthe FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense FCC Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate this equipment CE Warning This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures NOTE The KJ and J model series do not meet or qualify for FCC or CE certification as they are produced for countries outside the FCC s jurisd
30. BLE FOR WITHOUT LIMITATION LOSS OF DATA LOSS OF PROFITS DOWNTIME GOODWILL DAMAGE OR REPLACEMENT OF EQUIPMENT OR PROPERTY AND ANY EXPENSES FROM RECOVERY PROGRAMMING AND REPRODUCTION OF ANY PROGRAM OR DATA ATEN makes no warranty or representation expressed implied or statutory with respect to its products contents or use of this documentation and all accompanying software and specifically disclaims its quality performance merchantability or fitness for any particular purpose ATEN reserves the right to revise or update its product software or documentation without obligation to notify any individual or entity of such revisions or update For details about extended warranties please contact one of our dedicated value added resellers 97
31. E8324B J Outlet Yes 24 24 PE9324B J Yes 16 24 PE7324G IEC 60309 32A No PE8324G Yes 24 24 PE9324G Yes 16 24 Chapter 1 Introduction Model Inlet Cord Outlets al ias PE7328B J NEMA L6 30P 28 24x1EC 60320 C13 PDU 2x No 4 x IEC 60320 C19 Bank PE7328G IEC 60309 32A Outlet PE9330B J NEMA L6 30P 30 26 x IEC 60320 C13 PDU 2 x Yes 16 30 4 x IEC 60320C19 Bank PE9330G IEC 60309 32A Outlet Note For the complete specifications of individual models including bank by bank outlet details please reference Specifications page 83 eco PDU PE Series User Manual Features Power Distribution Space saving OU rack mount design with rear mounting Various IEC outlet models 2 digit 7 segment front panel LED shows PDU Phase Bank Outlet ID 3 digit 7 segment front panel LED shows Current Voltage Power Dissipation IP address and readings from up to 4 environment sensors Safe shutdown support Separate power for the unit s own power and its power outlets the user interface is still accessible even when an overload condition trips the devices circuit breaker Dedicated 8 14 outlet bank for critical load devices PE9 models only PE9216 PE9324 8 outlets PE9222 PE9330 14 outlets always powered on Proactive overload protection POP PE8 PE9 models only automatically powers off the last outlet that caused
32. EC320 C19 Outlets Bank 1 Outlet 1 14 12 x C13 2 x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status NA PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt Power 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt Power 7 Green Sensor1 Sensor4 Door Open 1 Red Outlet Power Indicator 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 1 x 20A Non fuse Breaker 1 x 16A Non fuse Breaker Nominal Input Power Power Capacity 100 240V 50 60Hz 16A UL 20A Max 4160W 100 240V 50 60Hz 16A 4600W Nominal Per Port IEC 320 C13 100 240V 50 60Hz 100 240V 50 60Hz Output Power 12A UL 15A Max 10A IEC 320 C19 100 240V 50 60Hz 100 240V 50 60Hz 16A UL 20A Max 16A 15A TUV Total 100 240V 50 60Hz 100 240V 50 60Hz 16A UL 20A Max 16A 15A TUV Environment Operating Temperature 0 50 C 0 40 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight TBD Dimensions L x W x H 132 5 x 6 6 x 4 4 cm 85 Appendix PE7216B PE8216B PE9216B Function PE7216B PE8216B PE9216B Power Outlets Direc
33. L et CLAD apa LS dna 32 Installation aria e ts ci ete 33 Installation Diagram o oooooccccocoo 34 Securing the Cables oooooccccccccocco eee 35 Securing the Sensors simio a es 36 Chapter 3 Basic Operation and First Time Setup Operation MethodS oooocccocccoo teas 37 BrOWSer Custa a a e rca a tada ig 37 CCOO ami A it 37 SNMP ca ad A A E da 37 First Time Setup io pios a a eee bees 38 Network Configuration 0 0 cece eee 39 Changing the Administrator Login 0 0020005 40 MOVING LON ara desire tinto a Tr de RG PESAR UF ear AL Means 40 Chapter 4 Logging In Logging Ih ias e va Reece hee Bate caida cited 41 The eco PDU Main Page 0 cee a 42 Page Components bc bee ei a res a aaa 43 Chapter 5 Energy Energy sia Dado dol ao gs st to dl did db de 44 Connections ses id mia 8 rosas apa hed ee Be ok DE E ee ae 44 Configuration y cs sum eee a or a 48 Chapter 6 User Management OVEVIE WA AAA Bia od ee 51 Administrator Information 0000 0c eee eee eee 51 User Information 0 0 000 cece eee 52 Chapter 7 Log WOO Ae valid eet ee ee Ae ee eae aio eee ea tow Repeat 53 The System Log Event List 0000200 c ee eeeee 54 Chapter 8 Setup Device Management 0000 ccc eee eee 55 Device Configuration s asas asana aaaea 55 Date IM cd lao 62 vi eco PDU PE Series User Manual SO CUT acia A A 64 Login Failures sje eo
34. No Item Description Power Outlets 28 in total 24 x IEC 320 C13 4 x IEC 320 C19 Bank 1 Outlet 1 14 12 C13 2 x C19 Bank 2 Outlet 15 28 12 x C13 2 x C19 Port and LED Panel Circuit Breaker The Port and LED panel contains Readout Section and LEDs Environmental Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 28 As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Power Cord Output Power Indicator The power cord that connects the unit to an AC power source plugs into this socket B models connect to a NEMA L6 30P source G models connect to an IEC 60309 32A source This LED lights steady to indicate output power for the related bank 26 eco PDU PE Series User Manual PE9330 27 Chapter 1 Introduction No Item Description Power Outlets Port and LED Panel 30 in total 26 x IEC 320 C13 4x IEC 320 C19 Bank 1 1 Outlet 1 14 7 C13 1 x C19 Bank 1 2 Outlet
35. Priv Password 1 Receiver IP 2 0 0 0 0 Service Port 2 162 Community 2 User name 2 Auth password 2 Priv Password 2 Up to four SNMP management stations can be specified If you want to use SNMP trap notifications do the following 2 3 Check Enable SNMP Trap Select which version of SNMP you want to use Key in the IP address es and the service port number s of the computer s to be notified of SNMP trap events The valid port range is 1 65535 The default port number is 162 Note Make sure that the port number you specify here matches the port number used by the SNMP receiver computer Key in the community value s if required for the SNMP version Key in the auth privacy password s that correspond to each of the stations 60 eco PDU PE Series User Manual E Syslog Server Syslog Server ww Enable Syslog Server Server IP 0 0 0 0 Service Port 514 To record all the events that take place on eco PDU devices and write them to the eco PDU Syslog server do the following 1 Check Enable Syslog Server 2 Key in the IP address and the port number of the Syslog server The valid port range is 1 65535 The default port number is 514 61 Chapter 8 Setup Date Time The Date Time dialog page sets the eco PDU time parameters Time Zone GMT 08 00 Taipei v E Daylight Savings Time Manual Input Date Ee YYYY MM DD Time HH MM SS Sync v
36. address can be specified IPv6 Configuration Enable autoconfiguration 2 Set configuration manually IP Address A Static Prefix Length Default Gateway E Use DHCPV6 to obtain DNS Server Addresses 4 5 Set DNS server address manually Preferred DNS Server Alternate DNS Server For dynamic IP address assignment select the Obtain IP address automatically radio button This is the default setting To specify a fixed IP address select the Set IP address manually radio button and fill in the IP address with values appropriate for your network For automatic DNS Server address assignment select the Obtain DNS Server address automatically radio button To specify the DNS Server address manually select the Set DNS server address manually radio button and fill in the addresses for the Preferred and Alternate DNS servers with values appropriate for your network Note 1 Ifyou choose Obtain IP address automatically when the device starts up it waits to get its IP address from the DHCP server If it hasn t obtained the address after one minute it automatically reverts to its factory default IP address 192 168 0 60 2 If the device is on a network that uses DHCP to assign network addresses and you need to ascertain its IP address see P Address Determination page 81 for information 3 Specifying the Alternate DNS Server address is optional 58 eco PDU PE Series User Manual Eve
37. allowing users to switch each device On Off The eco PDU also offers comprehensive power analysis reports which can separate departments and locations providing precise measurements of current voltage power and watt hour in a real time display Installation and operation is fast and easy plugging cables into their appropriate ports and user friendly browser based configuration and management is all that is entailed Since the eco PDU firmware is upgradeable over the Net you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors eco PDU Manager Software eco Sensors provides you with an easy method for managing multiple devices offering an intuitive Chapter 1 Introduction and user friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it With its advanced security features and ease of operation the eco PDU is the most convenient most reliable and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible Note 1 Sensors are optional accessories A sensor enabled installation is required to generate a more complete energy efficient data and chart Higher sensor installation density is helpful
38. aracters are allowed Outlet This field allows you to set the outlet by outlet permissions of the user Click on the user port icon to cycle through the three permissions options as follows User has complete access to this outlet User has read only access to this outlet User has no access to this outlet ex Save Click this button to save your operation or changes 52 Chapter 7 Log Log The eco PDU keeps a record of transactions that take place on its installation and stores up to 128 events at one time Setup E PE9324A Page 1 of 4 Event s per Page Date Ti Descriptio E e Category 001 2012 11 19 13 28 30 Authentication Information administrator administrator 10 3 41 141 logged in 002 2012 11 19 13 06 33 Authentication Information administrator administrator 10 3 41 101 logged out 003 2012 11 19 13 03 22 Authentication Information administrator administrator 10 3 41 101 logged in Joos 2012 11 19 12 50 25 Authentication information administrator administrator 10 3 41 141 session timed out Joos 2012 11 19 12 00 11 Authentication Information administrator administrator 10 3 41 141 logged in m Joos 2012 11 19 11 48 22 Device Information Device was rebooted 007 2012 11 19 11 47 14 Device Information Device was rebooted 008 2012 11 18 11 35 19 Authentication information administrator administrator 10 3 52 73 lo
39. ation and stops the upgrade procedure Ifyou didn t enable Check Main Firmware Version the upgrade file is installed without checking what its level is Once the upgrade completes successfully the switch resets itself 4 Log in again and check the firmware version to be sure it is the new one E Firmware Upgrade Recovery Should the eco PDU s firmware upgrade procedure fail and the device becomes unusable the following firmware upgrade recovery procedure will resolve the problem 1 Power off the device 2 Press and hold the Reset Switch in see page 11 3 While holding the Reset Switch in power the switch back on This causes the switch to use the original factory installed main firmware version Once the switch is operational you can try upgrading the main firmware again 74 eco PDU PE Series User Manual Backup To backup the device s settings do the following 1 In the Password field key in a password for the file Note Entering a password is optional If you do enter a password make a note of it since you will need it to be able to restore the file 2 Click Save 3 When the browser asks what you want to do with the file select Save to disk then save it in a convenient location Restore To restore a previous backup do the following 1 Click Browse navigate to the file and select it Note If you renamed the file you can leave the new name There is no need to return it to
40. ck rests on the floor Install front and side stabilizers on a single rack or front stabilizers for joined multiple racks before working on the rack Always load the rack from the bottom up and load the heaviest item in the rack first Make sure that the rack is level and stable before extending a device from the rack Use caution when pressing the device rail release latches and sliding a device into or out of a rack the slide rails can pinch your fingers After a device is inserted into the rack carefully extend the rail into a locking position and then slide the device into the rack Do not overload the AC supply branch circuit that provides power to the rack The total rack load should not exceed 80 percent of the branch circuit rating Make sure that all equipment used on the rack including power strips and other electrical connectors is properly grounded Ensure that proper airflow is provided to devices in the rack Ensure that the operating ambient temperature of the rack environment does not exceed the maximum ambient temperature specified for the equipment by the manufacturer Do not step on or stand on any device when servicing other devices in a rack The eco PDU s Main Power Cord Use the power cord supplied with this package If it becomes necessary to replace the cord supplied with this package be sure to use a cord of at least the same standard as the one provided Securing the Pow
41. e Lower Case C One Number C Disable Duplicate Login Check a policy and enter the required information in the appropriate fields Item Description Minimum Username Length Sets the minimum number of characters required for a username Acceptable values are from 1 16 Minimum Password Length Sets the minimum number of characters required for a password Acceptable values are from 1 16 Password Must Contain At Least Checking any of these items requires users to include at least one of the specified items in their password Note This policy does not affect existing user accounts Only new user accounts created after this policy has been enabled and users required to change their passwords are affected Disable Duplicate Login Check this to prevent users from logging in with the same account at the same time 65 Chapter 8 Setup Login String IP Filter Mac Filter Login String IP Filter Login String C IP Filter Enable O Include O Exclude Delete J MAC Filter Enable O Include O Exclude Gea os Dose E Login String The Login String entry field is used to specify a login string in addition to the IP address that users must include when accessing the eco PDU device with a browser For example 192 168 0 126 abcdefg The following characters are allowed 0 9 a z A Z _ The following characters are not allowed a
42. ensor INZA EEAO Inductive Proximity EA1441 Temperature N A E Sensor 1 Humidity IN A ON Reboot Pressure N A OFF Temperature N A Sensor 2 Humidity N A Pressure N A Temperature N A Sensor 3 Humidity N A Pressure N A Temperature N A Sensor 4 Humidity IN A PDU Threshold Settings These fields are used to set the maximum minimum and fluctuation threshold settings for Aggregate Current Voltage Power and Aggregate Power Dissipation If a range falls below the minimum setting or exceeds the maximum setting an alarm is triggered Voltage Frequency is displayed here in Hz On Off Reboot You can manually turn the device On and Off from this page by clicking the radio buttons To Reboot the device enable the Reboot checkbox and click on Save located at the bottom of the page Door Sensor This section allows you to select the type of door sensor that is being used in the installation See Door Sensor page 9 for further information Sensor 1 4 If you have sensors installed in your installation use these fields to set the maximum minimum and fluctuation threshold settings for Temperature Humidity and Pressure Note Sensors are optional accessories Check with your dealer for information about NRGence eco Sensors software 45 Chapter 5 Energy Bank Status Alleco PDU models support Bank level monitoring The Bank Status section allows you to set up a
43. er Cables To secure the cables in the eco PDU s power outlets use only the ATEN Lock Your Plug cable holders that have been specifically designed to work with the eco PDU Using any other kind of cable securing device could be highly dangerous Please contact your ATEN dealer for information about ATEN Lock Your Plugs 78 eco PDU PE Series User Manual Resetting the Circuit Breaker Before switching the circuit breaker to reset a trip power down and disconnect all devices connected to the eco PDU s power outlets to prevent damage caused by a sudden power surge Ifa power surge causes the eco PDU s circuit breaker to switch off the power and it needs to be reset follow the instructions below Recovery Procedure 1 Safely power down and disconnect all devices connected to the eco PDU s power outlets 2 Switch off the circuit breaker for the source that is providing power to the eco PDU 3 Switch the eco PDU s circuit breaker to reset the trip 4 Switch on the circuit breaker for the source that is providing power to the eco PDU 5 Reconnect the devices to the eco PDU s power outlets and power them on 79 Appendix Technical Support International For online technical support including troubleshooting documentation and software updates http eservice aten com For telephone support see Telephone Support page iii North America Email Support support aten usa c
44. er IEC Total 19 x IEC320 C13 3 x IEC320 C19 Outlets Ban1 1 Outlet 1 14 12 x C13 2 x C19 Bank1 2 Outlet 15 22 7 x C13 1 x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status 8 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt Power 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt Power 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Outlet Power Indicator 1 Red Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select Reset Power Nominal Input Power 2 x Pushbutton 1 x Semi recessed Pushbutton 1 x 20A Non fuse Breaker 1x 16A Non fuse Breaker 100 240V 50 60Hz 100 240V 50 60Hz 16A UL 20A Max 16A Power Capacity 4160 VA Max 3328 VA UL de rated 4600W Nominal Per Port IEC 320 C13 100 240V 50 60Hz 100 240V 50 60Hz Output Power 12A UL 15A Max 10A IEC 320 C19 100 240V 50 60Hz 100 240V 50 60Hz 16A UL 20A Max 16A Max 15A TUV Total 100 240V 50 60Hz 100 240V 50 60Hz 16A UL 20A Max 16A Max 15A TUV Environment Operating Temperature 0 50 C 0 40 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight TBD Dimensions L x W x H 132 5 x 6 6
45. erature 0 50 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 6 5 kg Dimensions L x W x H 177 50 x 6 60 x 4 40 cm 92 eco PDU PE S eries User Manual PE7324G PE8324G PE9324G Function PE7324G PE8324G PE9324G Power Outlets Direct 24 Connectors Power Cord 1 x IEC 309 32A Power IEC Total 21 x IEC 320 C13 3 x IEC 320 C19 Outlets Bank 1 1 Outlet 1 8 7 x C13 1x C19 Bank 1 2 Outlet 9 16 7 x C13 1 x C19 Bank 2 Outlet 17 24 7 x C13 1x C19 Environment Sensors 4x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status NA 24 Orange 16 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet 2 x Pushbutton Select Reset 1 x Semi recessed Pushbutton Power 2 x Non fuse Breaker Nominal Input Power 100 240V 50 60Hz 32A Nominal Input Output Voltage 200 240 VAC Power Capacity 7 36kW Nominal Per Port IEC 320 C19 100 240V 50 60Hz 15A TUV 16A Max O
46. ff from this page by clicking the radio buttons To Reboot the outlet enable the Reboot checkbox and click on Save located at the bottom of the page 47 Chapter 5 Energy Configuration The Configuration page is used to configure the settings of the eco PDU at the bank and individual power outlet level V Enable POP Mode Proactive Overload Protection POP Threshold 9 Same as Bank Max Current 19 A D User Define 7 Bank Configuration Bank Bank Name 01 Outlet Configuration Delay Time sec Outlet Outlet Name contento Remote Turn ON Method ads Power ON Power OFF Method Kill the Power X jon a 0 15 MAC Address G Method Kill the Power X 02 0 15 MAC Address Method Kill the Power 03 E 0 15 MAC Address Method Kill the Power X 04 E o 15 MAC Address Method Kill the Power X pos 0 15 MAC Address popopo Method Kill the Power mar m a 416 POP Setting This section allows you to configure the settings for NRGence s exclusive Proactive Overload Protection POP technology Effective on all non critical outlets this added safety feature automatically powers off the last outlet that caused the current overload Enable POP Mode by clicking the radio button Make your selection for the POP Threshold options are Same as Bank Maximum Current or User Defined Enter a
47. gged out Joos 2012 11 19 11 25 00 Authentication Information administrator administrator 10 3 52 73 logged in 010 2012 11 19 11 27 58 Authentication Information administrator administrator 10 3 5273 logged out 014 2012 11 19 11 27 37 Authentication information administrator administrator 10 3 52 73 logged in 012 2012 11 19 11 27 21 Device Information Device was rebooted D13 2012 11 19 10 40 00 Authentication Information administrator administrator 10 3 52 73 logged out 014 2012 11 19 10 38 34 Authentication Information administrator administrator 10 3 52 73 logged in 015 2012 11 19 10 37 50 Device Information Device was rebooted 016 2012 11 19 10 35 11 Device Information Device was rebooted 017 2012 11 19 10 34 08 Device Information Device was rebooted Char FrstPage Previous Page Next Page LastPage Save international Co Ltd 53 Chapter 7 Log The System Log Event List Clicking on a device in the Sidebar displays its log events in the main panel s log event list Clicking the Refresh button brings the log list up to date with the latest events The entry box to the right of the Refresh button lets you set the number of events to display per page Simply key in the number of your choice The top right of the main panel shows the total number of pages in the log file and what page you are currently viewing The buttons on the bottom row functi
48. he recessed channel on the sensor as shown in the following diagram Note 1 The sensors shown in the above diagram are for reference purposes only The sensors for the eco PDU may look slightly different 2 Depending on the model and type of sensor sensor mounts tie wraps and adhesive cable tie holders may or may not be provided in the package 36 Chapter 3 Basic Operation and First Time Setup Operation Methods NRGence eco PDU models provide three methods to access and manage your installation Browser eco Sensors eco PDU Management Software and SNMP Note The following sections of this chapter contain information concerning Browser operation For eco Sensors operation please reference the separate eco Sensors User Manual The eco Sensors software and User Manual can be downloaded from the ATEN website Browser NRGence eco PDUs can be accessed and controlled via any supported Internet browser from any platform See First Time Setup page 38 and the following sections in this chapter for full details eco Sensors All eco PDUs support eco Sensors eco PDU Manager Software NRGence eco Sensors provides you with an easy method for managing multiple devices offering an intuitive and user friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it NRGence eco Sensors can be downloaded from the ATEN website alo
49. iction RoHS This product is RoHS compliant SJ T 11364 2006 The following contains information that relates to China E ABSEMRUTE MEC a Ate SME ZR EM Beet O O O O O mae O O O O O O EFA SA SIDA EA RARE EEST 11363 200 MENBEERZ TO O RTHAKENMRAR EXATAS PRE MAERADER R HAMA AMA E BY S T 11363 20064 REEK X RNAZASAS RED ERM EWR YAMA See tHSJ T 11363 2006 REEK e eco PDU PE Series User Manual User Information Online Registration Be sure to register your product at our online support center International http eservice aten com Telephone Support For telephone support call this number International 886 2 8692 6959 China 86 10 5255 0110 Japan 81 3 5615 5811 Korea 82 2 467 6789 North America 1 888 999 ATEN ext 4988 United Kingdom 44 8 4481 58923 User Notice All information documentation and specifications contained in this manual are subject to change without prior notification by the manufacturer The manufacturer makes no representations or warranties either expressed or implied with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose Any of the manufacturer s software described in this manual is sold or licensed as is Should the programs prove defective following their purchase the buyer and not the ma
50. iguration and operation 5 Logout Click this button to log out of your eco PDU session 6 Interactive Display Panel This is your main work area The screens that appear reflect your menu choices and Sidebar node selection The Energy page has two tabs Connections and Configuration as described in the chapters that follow 43 Chapter 5 Energy Energy Connections When you log in to the eco PDU the interface opens with its default selection ofthe Energy tab and the Connections menu The contents ofthe PDU Status Bank Status and Outlet Status sections are displayed in the main panel Power liogregate power dissipation o Door Sensor Type ot instale Photo EA1440 Inductive Proximty EA1441 Note Only enabled eco PDU models will display the Bank Status and or Outlet Status submenu section 44 eco PDU PE Series User Manual PDU Status All eco PDU models support PDU device level monitoring The PDU Status section allows you to set up a power management configuration for the PDU device as a whole PDU Status PDU Name Measurement Min Threshold Max Threshold PDU Status laggregate current 0 00 A oltage p 00 v Power 0000 w Aggregate power dissipation 0 0000 KWH oltage frequency jo 00 HZ Door Sensor Type 9 not installed Door S
51. ite to apply for an SSL certificate After the CA sends you the certificate and private encryption key save them to a convenient location on your computer Importing the Private Certificate To import the private certificate do the following 1 Click Browse to the right of Private Key browse to where your private encryption key file is located and select it 2 Click Browse to the right of Certificate browse to where your certificate file is located and select it 3 Click Upload to complete the procedure Note 1 Clicking Restore Default returns the device to using the default ATEN certificate 2 Both the private encryption key and the signed certificate must be imported at the same time When you have finished making your settings on this page click Save 71 Chapter 9 PDU PDU The PDU function is used to upgrade the eco PDU s firmware and to backup and restore the device s configuration settings Firmware File When you click the PDU tab the display opens with the Upgrade Main Firmware menu page which looks similar to the one below Firmware File V Check Main Firmware Version Energy Box Name F W Version PE6216G FAW Ver 1 0 062 Filename Browse Upgrade Backup Password Restore Filename Browse Password Restore 72 eco PDU PE Series User Manual A description of the items shown in this panel are given in the table below
52. ith PC Network Time Y Enable auto adjustment Preferred time server AU ntp1 cs mu OZ AU X Preferred custom server IP F Alternate time server AU ntp1 cs mu OZ AU Alternate custom server IP Adjust time every 1 days Adjust Time Now Set the parameters according to the information described below Time Zone To establish the time zone that the eco PDU is located in drop down the Time Zone list and choose the city that most closely corresponds to where it is at If your country or region employs Daylight Saving Time Summer Time check the corresponding checkbox 62 eco PDU PE Series User Manual Manual Input Use this section to specify the eco PDU s date and time manually Click the calendar icon and click the calendar entry for the date Key the time into the Time field using the HH MM SS hours minutes seconds format Note This section is only enabled when auto adjustment in the Network Time section is disabled the checkbox is unchecked As an alternative to specifying the date and time by entering them into the date and time fields you can click to put a check in the Sync with PC checkbox in which case the eco PDU will take its date and time settings from the locally connected PC Network Time To have the time automatically synchronized to a network time server do the following 1 Check the Enable auto adjustment checkbox 2 Drop down the time serve
53. le holders to secure the cables from your attached devices in place on the eco PDU unit Use only the ATEN Lok U Plug cable holders that have been specifically designed to work with the eco PDU Using any other kind of cable securing device could be highly dangerous Part Number Description 2X EA07 Lok U Plug Cable Holder 10 pcs 2X EA08 Lok U Plug Installation Tool 4 pcs eco PDU PE Series User Manual Components PE7214B PE7214G E a B 11 Chapter 1 Introduction No Item Description Power Outlets 14 in total 12 x IEC320 C13 2 x IEC320 C19 Bank 1 1 Outlet 1 14 12 x C13 2 x C19 Port and LED Panel The Port and LED panel contains Readout Section and LEDs Environmental Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 23 Circuit Breaker Pushbutton Power Inlet As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker The power cord that connects the unit to an
54. mp lt gt 2 Space Compound characters fi etc Note 1 There must be a forward slash between the IP address and the string 2 If no login string is specified here anyone will be able to access the eco PDU device login page using the IP address alone This makes your installation less secure For security purposes we recommend that you change this string occasionally 66 eco PDU PE Series User Manual E IP Filter MAC Filter If any filters have been configured they appear in the IP Filter and or MAC Filter list boxes IP and MAC Filters control access to the eco PDU based on the IP and or MAC addresses of the client computers attempting to connect A maximum of 5 IP filters and 5 MAC filters are allowed To enable IP and or MAC filtering click to put a check mark in the P Filter Enable and or MAC Filter Enable checkbox Ifthe include button is checked all the addresses within the filter range are allowed access all other addresses are denied access Ifthe exclude button is checked all the addresses within the filter range are denied access all other addresses are allowed access Adding Filters To add an IP filter do the following 1 Click Add A dialog box similar to the one below appears The page at https 172 17 17 6 says x oe Enter the start IP address for example 192 168 0 1 2 Specify the filter address in the dialog box for example 19
55. n condensing Physical Housing Metal Properties Weight 6 5 kg Dimensions L x W x H 177 50 x 6 60 x 4 40 cm 91 Appendix PE8324A PE8324JA Function PE8324A PE8324JA Power Outlets Direct 24 Connectors Power Cord 1 x NEMA L5 30P UL 1 x NEMA L5 30P PSE Power IEC Total 24 x NEMA 5 15R Outlets Bank 1 1 Outlet 1 8 Bank 1 2 Outlet 9 16 Bank 2 Outlet 17 24 Environment Sensors 4x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status 24 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 2 Green Current Volt P D Sensor1 Sensor4 FW Upgrade 3 digit 7 segment Orange Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x 20A UL489 Breaker Nominal Input Power 100 120V 50 60Hz 100 120V 50 60Hz 24A UL 30A Max 24A UL 30A Max Nominal Input Output Voltage 100 120 VAC Power Capacity 3600W Nominal Per Port NEMA 100 120V 50 60Hz 12A UL 15A Max Output Power Total 100 120V 50 60Hz 24A UL 30A Max Environment Operating Temp
56. nction PE8121kJ Power Outlets Direct 21 Connectors Power Inlet 1 x NEMA L6 15P Power IEC Total 21 x IEC 320 C13 with lock Outlets Bank 1 1 Outlet 1 7 Bank 1 2 Outlet 8 14 Bank 1 3 Outlet 15 21 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status 21 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet 2 x Pushbutton Select Reset 1 x Semi recessed Pushbutton Power 1 x 16A Pushbutton Breaker Nominal Input Power 100 240V 50 60Hz 15A Max Nominal Input Output Voltage 200 VAC Power Capacity 3kwW Nominal Per Port IEC 320 C13 100 240V 50 60Hz 14A PSE 15A Max Output Power Total 100 240V 50 60Hz 14A PSE 15A Max Environment Operating Temperature 0 50 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 6 5kg Dimensions L x W x H 177 50 x 6 60 x 4 40 cm 89 Appendix PE9222B PE9222G Function PE9222B PE9222G Power Outlets Direct 22 Connectors Power Cord 1 x NEMA 6 20P 208V 1 x IEC C20 Pow
57. ng with a separate eco Sensors User Manual SNMP NRGence eco PDUs support any 3rd party V1 V2 V3 SNMP Manager Software SNMP Management Information Database MIB files for the eco PDU device can be found on the software CD provided with the eco PDU package or can be downloaded from the ATEN website 37 Chapter 3 Basic Operation and First Time Setup First Time Setup Once the eco PDU installation has been cabled up the next task the Administrator needs to perform involve configuring the network parameters changing the default Administrator login settings and adding users The easiest way to accomplish this is to log in over the Net with a browser Note 1 Since this is the first time you are logging in use the default Username administrator and the default Password password For security purposes we recommend changing them to something unique see Changing the Administrator Login page 40 2 For remote methods of getting logged in to the network see ZP Address Determination page 81 After you successfully log in the eco PDU Energy Connections page appears Min Threshold p 00 A 00 V 0000 W laggregate power dissipation 0 0000 KWH Power factor 00 jaltage Frequency 00 HZ remperature n a Bank Status 2012 ATEN International Co Ltd Note Operation details are discussed in the next
58. nput Power 100 240V 50 60Hz 100 240V 50 60Hz 24A UL 30A Max 32A Nominal Input Output Voltage 100 240 VAC Power Capacity 7 40kW Nominal Per Port IEC 320 C19 100 240V 50 60Hz 100 240V 50 60Hz Output Power 12A UL 15A Max 15A TUV 16A Max IEC 320 C13 100 240V 50 60Hz 100 240V 50 60Hz 12A UL 15A Max 10A Total 100 240V 50 60Hz 100 240V 50 60Hz 24A UL 30A Max 30A TUV 32A Max Environment Operating Temperature 0 50 C 0 40 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 6 40 kg Dimensions L x W x H 177 50 x 6 60 x 4 40 cm 95 Appendix Administrator Login Failure Ifyou are unable to perform an Administrator login because the Username and Password information has become corrupted or you have forgotten it for example you can clear the login information with the following procedure 1 Power off the eco PDU and remove its housing 2 Short the jumper labeled J1 PINS and PIN6 E J1 Le halha Power on the eco PDU After the beep indicates successfully powered on power off the switch Remove the jumper cap from J1 NH vn A W Close the housing and start the eco PDU After you start you can use the default Username and Passw
59. nt Notification The Event Notification section is divided into three sections SMTP Settings SNMP Trap Receivers and Syslog Server Each section is described below Note SMTP communications are supported on Port 25 EH SMTP Settings Event Notification SMTP Server C Enable report from the following SMTP Server SMTP Server My server requires authentication Account Name Password From To To have the eco PDU device email reports from the SMTP server to you do the following 1 Enable the Enable report from the following SMTP server and key in the IP address of your SMTP server 2 If your server requires authentication put a check in the My server requires authentication checkbox 3 Key in the appropriate account information in the Account Name Password and From fields Note Only one email address is allowed in the From fields and it cannot exceed 64 characters 4 Key in the email address addresses of where you want the event reports sent to in the To field Note If you are sending the report to more than one email address separate the addresses with a semicolon or comma depending on the specified mail server The total cannot exceed 256 characters 59 Chapter 8 Setup EH SNMP Trap Receivers SNMP Trap Receiver Y Enable SNMP Trap O snmPv3 O SNMPv2c O SNMPv1 Receiver IP 1 0 0 0 0 Service Port 1 162 Community 1 User name 1 Auth password 1
60. nufacturer its distributor or its dealer assumes the entire cost of all necessary servicing repair and any incidental or consequential damages resulting from any defect in the software The manufacturer of this system is not responsible for any radio and or TV interference caused by unauthorized modifications to this device It is the responsibility of the user to correct such interference The manufacturer is not responsible for any damage incurred in the operation of this system ifthe correct operational voltage setting was not selected prior to operation PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE PE Device Safety Notice Set the maximum permissible breaker protection in the building circuitry to the A current rating specified on the rating plate Observe all national regulations and safety codes as well as deviations for breakers Only connect the PE Device to a grounded power outlet or a grounded system Make sure that the total current input of the connected systems does not exceed the current rating specified on the rating plate of the PE Device There is a risk of explosion if the battery is replaced with an incorrect type Dispose of used batteries according to the relevant instructions eco PDU PE Series User Manual Package Contents The eco PDU PE Series package consists of 1 PE7214 PE7216 PE7324 PE7328 PE8121kJ PE8216 PE8316G PE8324 PE8324A PE8324JA PE9216 PE9222 PE9324 or PE933
61. om Online Technical Support Troubleshooting Documentation Software Updates http www aten usa com support Telephone Support 1 888 999 ATEN ext 4988 When you contact us please have the following information ready beforehand Product model number serial number and date of purchase Your computer configuration including operating system revision level expansion cards and software Any error messages displayed at the time the error occurred The sequence of operations that led up to the error Any other information you feel may be of help 80 eco PDU PE Series User Manual IP Address Determination Ifyou are an administrator logging in for the first time you need to access the eco PDU in order to give it an IP address that users can connect to There are two methods to choose from In each case your client computer must be on the same network segment as the eco PDU After you have connected and logged in you can give the device its fixed network address See Device Management page 49 Method 1 For computers running Windows an IP address can be determined and or assigned with the IP Installer utility The utility can be obtained from the Download area of our web site or from the software CD Look under Driver SW and the model of your device After downloading the utility to your computer do the following 1 Unzip the contents of PInstaller zip to a directory on you
62. on Overview As part of its NRGence line ATEN has developed a new generation of green energy power distribution units eco PDUs to effectively increase the efficiency of data center power usage The NRGence PE7214 PE7216 PE7324 PE7328 PE8121kJ PE8216 PE8316G PE8324 PE8324A PE8324JA PE9216 PE9222 PE9324 PE9330 eco PDUs are intelligent PDUs that contain 14 16 21 22 24 28 or 30 AC outlets and are available in various IEC socket configurations Models in the advanced PE9 range feature a dedicated 8 14 outlet bank for critical load devices and both the PE8 and PE9 ranges feature NRGence s proactive overload protection which automatically powers off the last outlet that caused the current overload NRGence eco PDUs provide secure centralized intelligent power management power on off cycle of data center IT equipment servers storage systems KVM switches network devices serial data devices etc as well as the ability to monitor the center s health environment via sensors The basic characteristics of each model are shown in the table on page 3 NRGence eco PDUs offer remote power control combined with real time power measurement allowing you to control and monitor the power status of devices attached to the PDUs either at the PDU device bank or outlet level depending on the model from practically any location via a TCP IP connection The power status of each outlet can be set individually
63. on as follows Ad Clear click to erase the contents of the log event list First Page click to go to the first page of the log event list Previous Page click to move to the previous page of the log event list Next Page click to move to the next page of the log event list Last Page click to move to the last page of the log event list Export Log click to save the contents of the log event list to file 54 Chapter 8 Setup Device Management The Setup page allows administrators and users with device management permission to configure and control overall eco PDU operations Device Configuration This page presents information about the selected device as described in the following sections General General PDU Name PE9324A MAC Address 00 10 74 A2 00 00 Firmware Version FW Ver 1 0 061 Rack Location name PE9324A Item Meaning PDU Name This field lets you give the device a unique name Simply delete whatever is in the text box and key in the name of your choice Click Save located at the bottom of the page to save the new name MAC Address This item displays the eco PDU s MAC address Firmware Version This item displays the current firmware version number You can reference it to see if there are newer versions available on the ATEN website Rack Location This field lets you give the rack location a unique name for easy Name reference
64. or numbers except 60 192 168 0 60 is the default address of the eco PDU Specify the device s default IP address 192 168 0 60 in your browser and you will be able to connect Assign a fixed IP address for the device see Pv4 Configuration page 51 that is suitable for the network segment that it resides on After you log out reset your computer s IP address to its original value Once you have logged in go to Network Settings to set up the permanent IP environment see Pv4 Configuration page 51 Method 3 NRGence eco Sensors allows you to determine assign an IP address in order to configure a PDU device and monitor power status of the equipment connected to it NRGence eco Sensors can be obtained from the Download area of the ATEN web site 82 eco PDU PE Series User Manual Specifications There are 24 models in the PE7xxx PE8xxx PE9xxx range They are available in 14 16 21 22 24 28 or 30 port versions with power inlet cord variations A basic comparison is show in the table below Basic Comparison Outlet Model Inlet Cord Outlets Metering Level Switching PE7214B NEMA 6 20P 14 12 x IEC320 C13 PDU 1x No PE7214G IEC 60320 C20 14 12 x IEC320 C13 PDU 1 x No PE7216B NEMA 6 20P 16 14 x IEC 320 C13 PDU No aa 2 x IEC 320 C19 1xBank D PE8216B Oust Yes 16 16 PE9216B Yes 8 16 PE7216G IEC 60320 C20 No PE8216G Yes 16 1
65. ord to log in 96 eco PDU PE Series User Manual Limited Warranty ATEN warrants this product against defects in material or workmanship for a period of one 1 year from the date of purchase If this product proves to be defective contact ATEN s support department for repair or replacement of your unit ATEN will not issue a refund Return requests can not be processed without the original proof of purchase When returning the product you must ship the product in its original packaging or packaging that gives an equal degree of protection Include your proof of purchase in the packaging and the RMA number clearly marked on the outside of the package This warranty becomes invalid if the factory supplied serial number has been removed or altered on the product This warranty does not cover cosmetic damage or damage due to acts of God accident misuse abuse negligence or modification of any part of the product This warranty does not cover damage due to improper operation or maintenance connection to improper equipment or attempted repair by anyone other than ATEN This warranty does not cover products sold AS IS or WITH FAULTS IN NO EVENT SHALL ATEN S LIABILITY EXCEED THE PRICE PAID FOR THE PRODUCT FURTHER ATEN SHALL NOT BE RESPONSIBLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE USE OF THE PRODUCT ITS ACCOMPANYING SOFTWARE OR ITS DOCUMENTATION ATEN SHALL NOT IN ANY WAY BE RESPONSI
66. ort 30 port and PE8316G models offer 2 bank metering Alert notification for selected events On Off Recycle Failure exceeding threshold settings etc via blinking LEDs locally SMTP SNMP trap notification Supports Management Information Base MIB files for SNMP Environment monitoring supports external temperature humidity differential pressure sensors for rack environment monitoring Door Sensor support allows the monitoring of rackmount enclosure door access to notify users when a door has been opened Current and voltage threshold setting Naming support for outlets User outlet access assignment on an outlet by outlet basis Event logging and syslog support Upgradeable firmware Multilanguage support English Traditional Chinese Simplified Chinese Japanese German Italian Spanish French Russian Korean Portuguese PE8316G has 2 bank metering Security 5 Two level password security Strong security features include strong password protection and advanced encryption technologies 128 bit SSL Remote authentication support RADIUS eco PDU PE Series User Manual eco Sensors Energy Management Software Automatic discovery of all PE devices within the same intranet Remote real time power measurement and monitoring Real time environment sensor monitoring Plotting monitoring of all PE devices Exceed threshold alert through SMTP and System log Power Analysi
67. power management configuration for the individual banks Bank Status Bank Bank Name Measurement Min Threshold Max Threshold Bank Status E Reboot OFF E Reboot ore E Threshold Settings These fields are used to set the maximum minimum and fluctuation threshold settings for Aggregate Current Voltage Power and Power Dissipation If a range falls below the minimum setting or exceeds the maximum setting an alarm is triggered Cay Breaker status ON OFF displays here 46 eco PDU PE Series User Manual Outlet Status If your eco PDU models supports outlet level power management threshold settings and manual On Off Reboot switching can be performed on this page Outlet Status Outlet Outlet Name Measurement Min Threshold Max Threshold Outlet Status urrent 0 00 A oltage 10 00 v kon wer Jo 0000 w Tire wer Dissipation 0 0000 KWH wer factor 0 00 urrent boo A oltage Jo 00 v 02 wer fo o000 w pm Reboot wer Dissipation 0 0000 KWH wer factor 0 00 urrent 0 00 A E Threshold Settings These fields are used to set the maximum minimum and fluctuation threshold settings for Aggregate Current Voltage Power and Power Dissipation If a range falls below the minimum setting or exceeds the maximum setting an alarm is triggered EH On Off Reboot You can manually turn the outlet On and O
68. r hard drive 2 Goto the directory that you unzipped the IPInstaller program to and run IPInstaller exe A dialog box similar to the one below appears Network Device IP Installer EB Device list Device Name Model Name MAC Address IP Address Exit PES Series PE8208G____00 10 74 9d 08 02 152168060 About r Enumerate Protocol IPy4 v Network adapter MAC 00 06 7b 0a c0 1c IP 192 168 52 102 Y Set IP IPv4 settings tting Obtain an IP address automatically DHCP E C Use the following IP address re i j Obtain DNS server address automatically E C Use the following DNS server addresses Ta OGRO 0 Continues on next page 81 Appendix Continued from previous page 3 Select the device in the Device List Note 1 Ifthe list is empty or your device doesn t appear click Enumerate to refresh the Device List 2 If there is more than one device in the list use the MAC address to pick the one you want The eco PDU s MAC address is located on its bottom panel Select either Obtain an IP address automatically DHCP or Specify an IP address If you chose the latter fill the IP Address Subnet Mask and Gateway fields with the information appropriate to your network Click Set IP After the IP address shows up in the Device List click Exit to end the program Method 2 1 Set your computer s IP address to 192 168 0 XXX Where XXX represents any number
69. r list to select your preferred time server Check the Preferred custom server IP checkbox and key in the IP address of the time server of your choice 3 If you want to configure an alternate time server check the Alternate time server checkbox and repeat step 2 for the alternate time server entries 4 Key in your choice for the number of days between synchronization procedures Finishing Up When you have finished making your settings on this page click Save After you have saved your changes if you want to synchronize immediately click Adjust Time Now 63 Chapter 8 Setup Security The Security page controls access to the eco PDU Security Login Failures Allowed 3 Timeout 5 man Working Mode V Enable ICMP Login Failures Allowed sets the number of consecutive failed login attempts that are permitted from a remote user Timeout sets the amount of time a remote user must wait before attempting to login again after exceeding the number of allowed failures Working Mode IfICMP is enabled the eco PDU device can be pinged If it is not enabled the device cannot be pinged The default is Enabled 64 eco PDU PE Series User Manual Account Policy The Account Policy section governs policies in regard to usernames and passwords Account Policy Minimum Username Length Minimum Password Length 0 0 Password Must Contain At Least E One Upper Case C On
70. rator Outlet Eje elzwlels E E E E E E El E 2 In the Administrator Information section at the top reset the name and password fields to something unique then click Save at the bottom of the page Note If you forget the Administrator s name or password short the mainboard jumper to restore the default Administrator account See see Administrator Login Failure page 96 in the Appendix for full details Moving On After setting up the network and changing the default Administrator username and password you can proceed to other administration activities including adding users This is covered in the next chapter 40 Chapter 4 Logging In Logging In The eco PDU can be accessed via a supported Internet browser from any platform Note Browsers must support SSL 128 bit encryption To access the eco PDU do the following 1 Open your browser and specify the IP address of the eco PDU you want to access in the browser s URL location bar Note You can get the IP address from the eco PDU administrator or see IP Address Determination page 81 for information about setting it up yourself Ifa Security Alert dialog box appears accept the certificate it can be trusted The Login page appears PE9324A Please
71. s report Note eco Sensors is designed to work with NRGence PDUs and is bundled with all PE series packages Proactive Overload Protection POP The PE8121kJ PE8216 PE8316G PE8324 PE8324A PE8324JA PE9216 PE9222 PE9324 and PE9330 models feature NRGence s exclusive Proactive Overload Protection POP technology Effective on all non critical outlets this added safety feature automatically powers off the last outlet that caused the current overload POP mode is engaged when the current exceeds the set threshold maximum value powering off the outlet The LED display shows POP and a beeper sounds Press any button for two seconds to clear POP mode and power the outlet back on Chapter 1 Introduction Requirements Browsers accessing the eco PDU unit must support SSL 128 bit encryption For cold booting of attached computers the computer s BIOS must support Wake on LAN or System after AC Back For Safe Shutdown The computer must be running Windows Windows 2000 or higher or Linux The Safe Shutdown program available by download from our website or on the software CD included must be installed and running on the computer eco PDU PE Series User Manual Optional Accessories Environment Sensors For complete energy management of an instrumented data center with the use of the eco PDU and eco Sensors software you should install 4 sensors for each of the racks in your data center
72. s te apes tt a ti 64 Working Mode 0000 a 64 ACCOUNUPOIIGCY id dae 65 Login String IP Filter Mac Filter o oo oooooo oooooo 66 Authentication amp Authorization 0 0 0 0 eee oo 69 Private Certificate spe voc norte cerid des OR pee ee eps d ee bs 71 Chapter 9 PDU PDS asco et Soles Bae e a o oll ated tart O AE con 72 Firmware File 20 5 ese ede bbe ea hepa bee bd eee ak ee ie 72 BACKUP ii A A te kas hte ee 75 Restore asas is e posa E A SG Dat 75 Appendix Safety INStrUCtONS o ooooooocooocooo EEE EER 76 E wig Se Eng SS ee a ee a E 76 Rack Mounting 33 5 ei ques alee a ee Elke ptes 78 The eco PDU s Main Power Cord 0 0 0 e eee eee eee 78 Securing the Power Cables 0 0 e eee eee 78 Resetting the Circuit Breaker 0 0 0 0 cece eee 79 Recovery Procedure 0 0 cette 79 Technical Support sz seitas te Ae Sardis peed Saad paver SaaS 80 International ass dorro pares eet web to eee be ee wee 80 North America epic one eel hee eee ott EE 80 IP Address Determination 0 0 0c eee 81 SPECHICATIONS vuitton pa be ee Bd eee en fee ee OP ee 83 PE7214B PE7214G6 ss alae rip Bees Reedy E ee bees 85 PE7216B PE8216B PE9216B 0 0 eee eee 86 PE7216G PE8216G PE9216G 0 eee eee 87 PES8316G is nth be raei a a ee o bane ra 88 RES 2 kel sis ac Pipes a re eS ape SEDE pide Parton tea a 89 PE9222B PE9222G ss sra ahah Rhee REDES hes
73. stem after AC Back option see below after the delay time expires the eco PDU waits another fifteen seconds then shuts the computer down The default delay time is 15 secs the maximum delay time is 999 secs Remote Turn ON Method Use the drop down menu to select one of the choices below Wake on LAN This is a Safe Shutdown and Restart option If this is selected when an Outlet is turned Off the eco PDU first sends a message to the computer telling it to prepare for a shutdown it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down to standby mode Likewise when the Outlet is turned On the eco PDU waits for the amount time set in the Power On Delay field then sends an Ethernet message to the computer connected to the Outlet telling the computer to turn itself On Note For Safe Shutdown and Restart the computer must be running Windows 98 or higher or Linux and the Safe Shutdown program available by download from our website must be installed and running on the computer System after AC Back This is a Safe Shutdown and Restart option If this is selected when an Outlet is turned Off the eco PDU first sends a message to the computer telling it to prepare for a shutdown it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down When the Outlet is turned On
74. t 16 Connectors Power Inlet 1 x NEMA 6 20P Power NEMA NA Outlets EG Total 14 x IEC 320 C13 2x IEC 320 C19 Bank 1 1 Outlet 1 8 7 x C13 1x C19 Bank 1 2 Outlet 9 16 7 x C13 1 x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status NA 8 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D 1P 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 1 x 16A Branch Breaker Nominal Input Power 100 240V 50 60Hz 16A UL 20A Max Power Capacity 4 16kW Nominal Per Port IEC 320 C19 100 240V 50 60Hz 16A UL 20A Max Output Power IEC 320 C13 100 240V 50 60Hz 12A UL 15A Max Total 100 240V 50 60Hz 16A UL 20A Max Environment Operating Temperature 0 50 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 3 80 kg Dimensions L x W x H 132 48 x 6 60 x 4 40 cm 86 eco PDU PE Series User Manual PE7216G PE8216G PE9216G Function PE7216G PE8216G PE92
75. the character string that you want to use for authentication between the eco PDU device and the RADIUS Server On the RADIUS server set the entry for each user as follows SU XXXX Where xxxx represents the Username given to the user when the account was created on the eco PDU device The user s access rights are the ones assigned for the eco PDU device as well See Device Management page 55 Note su user supports view ports only su administrator supports all eco PDU functions 70 eco PDU PE Series User Manual Private Certificate When logging in over a secure SSL connection a signed certificate is used to verify that the user is logging in to the intended site For enhanced security the Private Certificate section allows you to use your own private encryption key and signed certificate rather than the default ATEN certificate There are two methods for establishing your private certificate generating a self signed certificate and importing a third party certificate authority CA signed certificate Generating a Self Signed Certificate Ifyou wish to create your own self signed certificate a free utility openssl exe is available for download over the web Obtaining a CA Signed SSL Server Certificate For the greatest security we recommend using a third party certificate authority CA signed certificate To obtain a third party signed certificate go toa CA Certificate Authority webs
76. the current overload see Proactive Overload Protection POP page 7 Remote Access Remote power control via TCP IP and a built in 10 100 Ethernet port Network Protocols TCP IP UDP HTTP HTTPS SSL SMTP DHCP NTP DNS auto sense Ping Remote users can monitor outlet status via web pages on their browsers eco PDU Power Management software eco Sensors Supports SNMP Manager V3 Operation Local and Remote power outlet control On Off Power Cycle by individual outlets PE8 PE9 models Supports multiple power control methods Wake on LAN System after AC Back Kill the Power Power on sequencing set the power on sequence and delay time for each outlet to allow equipment to be powered on in the correct order Easy setup and operation via a browser based user interface Multibrowser support IE Mozilla Firefox Chrome Safari Opera Chapter 1 Introduction RTC support to keep the timer running during times of no power Up to 8 user accounts and 1 administrator account Management 5 5 Power metering and monitoring at the PDU Bank Outlet level LED indicators for current voltage power dissipation at the PDU Bank Outlet levels Real time aggregate current voltage and power and power dissipation displayed in a browser based UI for monitoring at the PDU bank and outlet level 14 port 16 port 21 port and 22 port models offer 1 bank metering 24 port 28 p
77. tlet 1 7 Bank 1 2 Outlet 8 14 Bank 1 3 Outlet 15 21 The Port and LED panel contains Readout Section and LEDs Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 23 Circuit Breaker Pushbutton As a safety measure if there is an over current situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation Warning See Resetting the Circuit Breaker page 79 for important information about resetting a tripped circuit breaker Power Inlet The power cord that connects the unit to an AC power NEMA L6 15P source plugs into this socket Outlet Status LEDs These 21 LEDs indicate outlet status Lights ORANGE for powered on Off for powered off 18 eco PDU PE Series User Manual PE9222B PE9222G OOO OOO oc 00 0 0 Gp Gp aior D ow E E o pasooo J Es E E e Chapter 1 Introduction No Item Description Power Outlets 22 in total 19 x IEC320 C13 3 x IEC320 C19 Bank 1 1 Outlet 1 14 12 x C13 2 x C19 Bank 1 2 Outlet 15 22
78. tly up or down and thus should only be installed with the power sockets facing out from a vertical position as shown below Right Floor Wrong Floor Note The eco PDU models shown in the diagrams are for rack mount reference purposes only 32 eco PDU PE Series User Manual Installation To set up your installation refer to the installation diagram on the next page the numbers in the diagram correspond to the numbered steps and do the following 1 Ensure that the eco PDU unit is properly grounded Note Do not omit this step Proper grounding helps to prevent damage to the unit from surges of static or electricity 2 For each device you want to connect use its power cable to connect from the device s AC socket to any available outlet on the eco PDU Use ATEN Lok U Plug cable holders to secure them Note See Securing the Cables page 35 for details 3 Plug the cable that connects the eco PDU to the LAN into the eco PDU s LAN port 4 Optional If you are using environmental sensors in your eco PDU installation connect up to four to the RJ 11 sensor ports on the unit s front panel Note Sensors are optional Please see Optional Accessories page 9 and the installation diagrams later in this chapter for further information 5 Optional If you are using a door sensor in your eco PDU installation connect it to the
79. ug the power cable before removing the power supply Ifthe system has multiple sources of power disconnect power from the system by unplugging all power cables from the power supplies Never push objects of any kind into or through cabinet slots They may touch dangerous voltage points or short out parts resulting in a risk of fire or electrical shock Do not attempt to service the device yourself Refer all servicing to qualified service personnel If the following conditions occur unplug the device from the wall outlet and bring it to qualified service personnel for repair The power cord or plug has become damaged or frayed Liquid has been spilled into the device The device has been exposed to rain or water The device has been dropped or the cabinet has been damaged The device exhibits a distinct change in performance indicating a need for service The device does not operate normally when the operating instructions are followed Only adjust those controls that are covered in the operating instructions Improper adjustment of other controls may result in damage that will require extensive work by a qualified technician to repair Do not connect the RJ 11 connector marked Sensor to a public telecommunication network 77 Appendix Rack Mounting Before working on the rack make sure that the stabilizers are secured to the rack extended to the floor and that the full weight of the ra
80. utput Power 12A UL 15A Max 15A TUV 16A Max IEC 320 C13 100 240V 50 60Hz 100 240V 50 60Hz 12A UL 15A Max 10A Total 100 240V 50 60Hz 100 240V 50 60Hz 24A UL 30A Max 30A TUV 32A Max Environment Operating Temperature 0 50 C 0 40 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 4 10 kg Dimensions L x W x H 135 90 x 6 60 x 4 40 cm 94 eco PDU PE Series User Manual PE9330B J PE9330G Function PE9330B J PE9330G Power Outlets Direct 30 Connectors Power Cord 1 x NEMA L6 30P 1 x IEC 60309 32A Power IEC Total 26 x IEC 320 C13 4 x IEC 320 C19 Outlets Bank 1 1 Outlet 1 14 12 x C13 2 x C19 Bank 1 2 Outlet 15 22 7 x C13 1 x C19 Bank 2 Outlet 23 30 7 x C13 1x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status 16 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal I
81. utput Power IEC 320 C13 100 240V 50 60Hz 10A Total 100 240V 50 60Hz 30A TUV 32A Max Environment Operating Temperature 0 40 C Storage Temperature 20 60 C Humidity 0 80 RH Non condensing Physical Housing Metal Properties Weight 6 5kg Dimensions L x W x H 177 50 x 6 60 x 4 40 cm 93 Appendix PE7328B J PE7328G Function PE7328B J PE7328G Power Outlets Direct 28 Connectors Power Cord 1 x NEMA L6 30P 1 x IEC 60309 32A Power IEC Total 24 x IEC 320 C13 4 x IEC 320 C19 Outlets Bank 1 Outlet 1 14 12 x C13 2 x C19 Bank 2 Outlet 15 28 12 x C13 2 x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status NA PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal Input Power 100 240V 50 60Hz 100 240V 50 60Hz 24A UL 30A Max 32A Nominal Input Output Voltage 100 240 VAC Power Capacity 7 40kW Nominal Per Port IEC 320 C19 100 240V 50 60Hz 100 240V 50 60Hz O
82. value in the field Note This feature is available on the PE8121kJ PE8216 PE9216 PE9324 and PE9330 models only See Proactive Overload Protection POP page 7 for more details Bank Configuration Each bank can be given a distinctive name The maximum number of characters is 15 48 eco PDU PE Series User Manual Outlet Configuration This page lets you set up the power management configuration for the selected outlet The meanings of the field headings are given in the following table Heading Meaning Outlet Name Each outlet can be given a distinctive name The maximum number of characters is 15 Confirmation lf this option is enabled there is a check in the checkbox a dialog box Required comes up asking you to confirm a power operation before it is performed If it is disabled there is no check in the checkbox the operation is performed without confirmation Power ON Sets the amount of time the eco PDU waits after the Power Button is Delay clicked see Bank Status page 46 before it powers on the outlet Note The default delay time is O seconds the maximum is 999 seconds When a series of outlets are scheduled to be powered up they turn on in sequence with a default delay of 10 milliseconds between each outlet Power OFF Sets the amount of time the eco PDU waits after the Power Button is Delay clicked see Bank Status page 46 before it turns off the power to the outlet For the Sy
83. x When it comes up simply delete the old address es and replace it with the new one s Deleting Filters To delete a filter select it in the IP Filter or MAC Filter list box and click Delete 68 eco PDU PE Series User Manual Authentication amp Authorization The Authentication amp Authorization page is used to set up login authentication and authorization management from external sources Authentication amp Authorization RADIUS Settings C Enable RADIUS Preferred RADIUS Server IP Preferred RADIUS Service Port Alternate RADIUS Server IP Alternate RADIUS Server Port Timeout sec Retries Shared Secret at least 6 characters 69 Chapter 8 Setup RADIUS Settings To allow authentication and authorization for the eco PDU device through a RADIUS server do the following 1 2 Check Enable Fill in the IP addresses and service port numbers for the Preferred and Alternate RADIUS servers The default port number for the Preferred server is 1812 the default port number for the Alternate server is 1645 Note Make sure that the port numbers you specify here match the port numbers used by the RADIUS servers Inthe Timeout field set the time in seconds that the eco PDU device waits for a RADIUS server reply before it times out In the Retries field set the number of allowed retries for attempting to connect to the RADIUS server Inthe Shared Secret field key in
84. x 4 4 cm 90 eco PDU PE Series User Manual PE7324B J PE8324B J PE9324B J Function PE7324B J PE8324B J PE9324B J Power Outlets Direct 24 Connectors Power Cord 1 x NEMA L6 30P Power IEC Total 21 x IEC 320 C13 3 x IEC 320 C19 Outlets Bank 1 1 Outlet 1 8 7 x C13 1x C19 Bank 1 2 Outlet 9 16 7 x C13 1 x C19 Bank 2 Outlet 17 24 7 x C13 1x C19 Environment Sensors 4 x RJ 11 Female Black Door Sensor 1 x 4 pin Dry Contact LAN 1 x RJ 45 Female Silver LEDs Orange Green LEDs Outlet Status NA 16 Orange PDU Bank Outlet 2 digit 7 segment Orange PDU Bank Outlet 3 Green Current Volt P D 3 digit 7 segment Orange Sensor1 Sensor4 FW Upgrade Current Volt P D IP 7 Green Sensor1 Sensor4 Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal Input Power 100 240V 50 60Hz 24A UL 30A Max Nominal Input Output Voltage 200 240 VAC Power Capacity 6 24kW Nominal Per Port IEC 320 C19 100 240V 50 60Hz 12A UL 15A Max Output Power IEC 320 C13 100 240V 50 60Hz 12A UL 15A Max Total 100 240V 50 60Hz 24A UL 30A Max Environment Operating Temperature 0 50 C Storage Temperature 20 60 C Humidity 0 80 RH No