ATD Tools Blower ATD-36750 User's Manual

image

Contents

1. Model ATD 36750 Refrigerant Gas Leak Detector Detects all CFC HFC HCFC HFO Refrigerants including blends User Manual C 4 Design certified by NN ASCI and Intertek to NAA meet SAE J2791 J2913 amp EN14624 INTRODUCTION The ATD 386750 features a patented 3 LED UV that emits the optimum wavelength for A C dye fluorescence The UV light can be used simultaneously with the heated sensor or independently The D440A UV does not require rechargeable batteries The ATD 36750 features a long life solid electrolyte semiconductor sensor technology that is designed to detect the more current and difficult HFC refrigerants such as R 134a R 410a R 407c R 507 and R 404c in addition to the new HFO 1234yf and all HCFC R 22 and CFC R 12 refrigerants including SNAP approved hydrocarbon blends The ATD 36750 s unique digital leak size indicator takes the guesswork out of whether or not to repair a small leak The digital display is independent from the audio alarm and sensitivity level allowing the precise pinpointing of the leak source FEATURES e Patented 3 LED UV lights e Long life stable sensor e Unique numeric leak size Indicator e R 134a sensitivity 05 oz yr R 22 sensitivity 025 oz yr e Designed Certified to meet Automatic calibration and SAE J2791 J2913 and reset to ambient EN14624 e Visual LED leak alarm near e 3 adjustable sensitivity levels sensor e Low battery indicator e True mechanical
2. Remove the Plastic Seal Cap on the top of the Leak Test Vial by pulling it off see fig below Also remove and discard the circular Leak Test Cap Seal Turn on the leak detector and allow the unit to complete the warm up cycle Place the sensor close to the small hole in the top of the Leak Test Vial The beep rate should increase and the Digital Leak Size Indicator should display a number from 4 6 indicating that the sensor and electronics are working properly Remove the Plastic Seal _ Capto Test the Leak Detector lt Leak Test Cap Seal 4 Leak Test Vial NOTE Remember to replace the Plastic Seal Cap after the leak test is completed Replace the Leak Test Vial when the green media color is no longer visible and the leak media has evaporated Remove the threaded cap on the Vile to confirm the status of the leak test media After the leak test media has evaporated it is normal for there to be a green film on the wall of the Leak Test Vial 5 Maintenance Batteries Install Batteries Remove screw located at rear end of unit and pull down hinged battery door to open as shown Always insert all four batteries into the battery compartment in the same direction Note polarity mark on the inside of the battery door for proper battery orientation Polarity Mark Sensor Replace Filter Unscrew sensor tip as shown to replace filter Replace filter whenever it becomes visibly dirty or every 2 to 3 months de
3. See manufacturer s specifications for proper dye charge b Run the A C system long enough to thoroughly mix and circulate the dye with the refrigerant and lubricating oil Turn on UV light by pressing the UV light ON OFF button See control panel on page 2 Holding the leak detector approximately 10 to 14 away shine the UV light beam slowly over the components hoses and metal lines that make up the A C system When the UV light shines on the fluorescent dye that has escaped from the system the dye will glow a bright yellow green J3 3 UV LED s Replacement Parts tem O O ooo o o oO Pat Number Sensor with Filter PRT3700 01 Sensor filters 5 pack PRT3700 02 Leak Test Vial PRT3700 03 Carrying Case PRT3699 CASE RETURN FOR REPAIR POLICY Every effort has been made to provide reliable superior quality products However in the event your instrument requires repair forward unit to Service Center freight prepaid to the address below with return address phone number and or email address SERVICE CENTER 2651 W 81st Street Hialeah FL 33016 WARRANTY POLICY The ATD 36750 Refrigerant Gas Leak Detector is warranted to be free of defects in materials and workmanship for a period of two years from the date of purchase This warranty applies to all repairable instruments that have not been tampered with or damaged through improper use including unauthorized opening of the unit Please ship warranty unit
4. Oil heated to 160 deg F N Leak Size Indicator The digital leak size indicator remains off normally but once a leak is detected a number from 1 9 will be displayed for all HFC and HCFC refrigerants regardless of the sensitivity setting The number will continue to increase or decrease depending on the amount of refrigerant sensed The maximum value will be displayed once the leak source has been located The table below can be used to approximate the size of leak Maximum displayed Leak Size oz yr 1 3 lt 0 1 0 1 to 0 5 Low Battery Indicator Replace the 4 AA Alkaline batteries when the red LED on the control panel is lit Follow battery installation instructions under Maintenance section Audio Mute Function To silence or mute the audio beep and alarm signal press the MUTE button To restore the audio sound press the MUTE button again Note a few seconds is required to restore sound if the mute button is pressed in rapid succession Adjusting Sensitivity Levels The Leak Detector will default to the NORM sensitivity level automatically once the unit comes out of the warm up cycle and the green LED will turn on To change sensitivity levels press the SENS once for HI sensitivity red LED will turn on and again for LO sensitivity yellow LED will turn on Leak Test Vial The leak detector comes with a Leak Test Vial that allows the user to make sure the detector is performing properly To test 1
5. pending on use Replace Sensor Remove sensor by pulling out of socket Install the new sensor by aligning the Keyway notch in sensor cover with the raised keyway on sensor socket holder see figure below Note Do not force sensor into socket Misalignment can damage the sensor pins Push straight on do not Unscrew tip to fiter twist to install sensor _ Keyway alignment replace filter Pull straight out do not twist to remove sensor IMPORTANT The instrument s software is designed to alert the user if the sensor is dislodged or defective If the sensor is not fully inserted into the six pin socket or if it is defective the instrument will not come out of the Warm Up mode for proper operation when the power button is turned on Additionally if the instrument becomes unstable during its operation it is an indication that the sensor may be defective 6
6. pump e Audio mute function e Uses 4 AA alkaline batteries e CE Certified e Comfortable Sanoprene grip e 2 year warranty includes e Made in USA sensor NOTES NOTES 1 ATD 36750 Control Panel ATD 36750 Digital Leak Size Indicator Low Battery Low Bat 4 o Indicator o lt UV Light Power On Off lt Sensitivity Level LO Norm Hi Audio Mute amp Mute Sens Sensitivity Level Power lt On Off Operating Instructions TURN ON Press the ON OFF button once to turn on and again to turn off NOTE Hold button down for approximately 1 second to turn unit off WARM UP The detector automatically starts heating the sensor During the heating cycle the digital leak size indicator will flash O and the detector will sound a slow beep Warm up is usually less than 20 seconds READY The detector is ready to begin searching for leaks when the flashing 8 stops and the green sensitivity LED turns on The audio beep increases in frequency and probe LED begins to blink steadily 1 UV Light Operation CAUTION EMITS ULTRAVIOLET RADIATION _ This UV ultraviolet LED during operation radiates UV light Avoid direct eye and skin exposure to UV light if viewing the UV light is necessary please use UV filtered glasses to avoid damage by the UV light Before leak checking with the UV light a Make sure the A C system is properly charged with sufficient dye
7. s that require repair freight prepaid to Service Center along with proof of purchase return address phone number and or email address Product Specifications Model ATD 36750 Name _ Leak Detector Refrigerant Gas Sensitivity 05 oz yr R134a 025 oz yr R22 Weight Ibs 1 5lbs S 2 years includes sensor EN14624 2005 Test Specifications Minimum Maximum Sensitivity 1 gm yr minimum gt 50 gm yr maximum Threshold fixed Minimum Maximum Sensitivity 3 gm yr minimum gt 50 gm yr maximum Threshold moving Minimum Detection Time 1gm yr Clearing Time Approx 9 seconds after exposure to gt 50 gm yr Exposure Atmosphere Cross Sensitivity to Automotive Chemicals Some automotive solvents and chemicals have similar hydrocarbon properties as R134a and may elicit a positive response Before leak checking clean up any chemicals in the list below that elicit a positive response Chemical Name Brand Response Ford Spot Remover We OSY i O Ford Rust Inhibitor _ S SY O Ford Gasket Adhesive Wet CY Loctite Natural Blue degreaser diluted Y Ford Brake Parts Cleaner ae re Ford Silicone Rubber uncured Motorcraft Antifreeze heated to 160 deg F Y partial Gunkliquidwrench CY Gunk liquid wrench Ford silicone lubricant Ford Pumice lotion with solvent Y Ford Motorcraft brake fluid YS Ford Carburetor Cleaner CY Dextron Transmission fluid heated to 160 deg F Quaker State Motor