Home

American Sensor SA379 User's Manual

image

Contents

1. Pause period will shorten As the level of smoke density approaches 4 per cent per foot obstruction a very heavy concentration of smoke the smoke alarm will override the Alarm Pause mode and sound an alarm NOTE If powered only by battery the level of battery voltage will also affect the length of the Alarm Pause period If the battery voltage is low the Alarm Pause will be activated for approximately 10 minutes If the battery voltage is high the Alarm Pause will be activated for a shorter period of time approximately 4 minutes B Operation How to Test Before Installation 1 Connect battery Ensure that the battery is correctly installed Positive terminal to positive contact and negative terminal to negative contact as indicated in the battery drawer Reversing the battery in the compartment should not cause any damage to the smoke alarm If the drawer is pushed all the way in a low battery beep will sound when the AC power is applied after installation if the battery is improperly installed Storage in low humidity and certain transportation conditions may cause electrostatic charges to build up in the alarm system housing Although harmless these charges may increase the length of time during which the horn sounds upon battery insertion or test button operation The condition may be cleared by gently wiping the outside of the plastic cover with a clean damp cloth 2 Check that the red operating light flashe
2. Your local fire department or insurance company may be able to give you further advice on the best smoke alarm locations in your home Call them and ask Dining Kitchen Bedroom Bedroom Dining Kitchen Bedroom O I o ojo o O TV Room j e O tiving Room fo Living Room Bedroom e L Bedroom o e fo l ial Bedroom Hall Bedroom bedroom Figure 2 O e o Figure 1 Ling Room Kitchen Smoke alarms for limited protection e 0 Figure 3 O Additional smoke alarms for better coverage Basement Fumace These diagrams show smoke alarm locations as recommended as above in 3a 3b WHERE TO LOCATE SMOKE ALARMS IN MOBILE HOMES AND RECREATIONAL VEHICLES RV s Note Power supply must be 120 Volts AC for model SA379 In mobile homes and RV s built after 1978 locate the smoke alarm as described above Older mobile homes and RV s may have little or no insulation compared to the ones built post 1978 These uninsulated exteriors can disrupt airflow around the smoke alarm in hotter or colder weather Locate the alarm only on interior walls 4 to 6 10 to 15 cm from ceiling 1 if you own an older mobile home or RV or 2 if you notice the exterior walls and or ceiling are noticeably cold or warm or 3 if you are uncertain about the quality of insulation Regardless of the age of t
3. LIMITATIONS OF SMOKE ALARMS American Sensors smoke alarms are designed to provide early warning of fire and smoke at reasonable cost Early warning can mean the difference between a safe escape and no escape at all While smoke alarms can provide invaluable protection for you and your family they do have limitations e Smoke alarms cannot work without power Battery operated alarms will not work without proper batteries with dead batteries or if batteries are not properly installed AC powered alarms will not work if their AC power supply is cut off by an electrical fire an open fuse a circuit breaker or any other reason If you are concerned about the reliability of either batteries or your AC power supply for any of the above reasons you should install in your home both AC and battery powered smoke alarms for added security This American Sensors Smoke Alarm model SA379 is AC powered with battery back up and offers superior protection from the dangers of smoke and fire Smoke alarms are incapable of sounding the alarm until smoke reaches the sensing chamber Anything preventing smoke from reaching the alarm may delay or prevent an alarm A smoke alarm cannot detect fire in the walls chimney or roof unless and until a significant amount of smoke reaches the alarm A closed door may prevent smoke from reaching an alarm on the other side of the door A smoke alarm may not sense a fire on another floor of a home For example a baseme
4. Use of a non recommended battery may be detrimental to the proper functioning of the alarm 8 MAINTENANCE amp TROUBLESHOOTING VACUUM EVERY SIX MONTHS Your smoke alarm should be cleaned every six months to help keep it working efficiently REMOVE POWER TO ALARM Gently vacuum through the vents of the alarm with a soft brush attachment Keep vacuum nozzle from touching the unit RE ESTABLISH POWER TO ALARM Problems are indicated by these events 1 The alarm does not sound upon pressing the test button 2 The green operating light does not remain steadily on when the unit is AC powered 3 The red operating light remains steadily on or off i e does not flash once every 45 seconds when the unit is not in alarm Try the following Inspect breaker or use in power circuit to alarm Check that the unit contains recommended battery type Check the battery is properly connected Observe polarity Gently vacuum as recommended above Replace battery Call a trained experienced serviceman to inspect house wiring and connection to alarms Dm WNre If these procedures do not correct the problem do NOT attempt repairs If the smoke alarm is within warranty period and terms indicate the nature of the problem and return the unit with proof of purchase to the point of purchase distributor or manufacturer See below for instructions Units beyond warranty cannot be economically repaired FALSE ALARMS Model SA379 Press th
5. alarm may not be effective DO NOT PLACE SMOKE ALARMS e In turbulent air from fans doors windows etc The rapid air movement may prevent combustion particles from entering the alarm e In dead air spaces such as at the peak of an A frame ceiling Dead air at the top may prevent smoke from reaching the alarm in time to provide early warning In rooms with simple sloped peaked or gabled ceilings install smoke alarms on the ceiling 3 feet 90 cm from the highest point of the ceiling Note For complex ceiling structures consult a safety expert for the number of alarms required and the best locations e In very hot or cold areas where the temperature exceeds 100 F 38 C or falls below 40 F 5 C e Less than 6 inches 15 cm from the wall when mounted on the ceiling Nuisance alarms could result when smoke alarms are located where interference may occur with the sensing chamber To avoid nuisance alarms DO NOT place smoke alarms e In high humidity areas such as bathrooms and attics Place smoke alarms at least 10 feet 3 meters away from bathrooms e In insect infested areas e In poorly ventilated kitchens or garages e In very dusty and dirty areas e Near fluorescent lights Place smoke alarms at least 5 feet 1 5 meters from fluorescent lights This smoke alarm is suitable for residential AWARNING use It is not to be connected to a commercial or industrial fire alarm panel 6 INSTALLATION A
6. in Operation section 8 Connect black and white wires color to color from power connector to AC power leads 9 For multiple station use the orange wire for interconnection If unit is not to be interconnected cap unused wire 10 Loosen or remove screws from junction box 11 Attach flat side of mounting plate and tighten screws to fit snugly against junction box and ceiling or wall quick disconnect Smoke alarm power connector mounting plate paper gasket not shown fits in between 12 Bring power connector through center opening 13 Slip the paper gasket supplied with the alarm over the power connection and then onto the mounting plate so that the four plastic tabs on the mounting plate will hold the gasket in place The gasket will prevent downward air currents from entering the smoke alarm through holes in the back of the alarm Unless blocked off downward air currents prevent smoke from entering the alarm WARNING IT IS IMPERATIVE THAT YOU INSERT THE GASKET WHEN INSTALLING YOUR SMOKE ALARM 14 Plug wire connector into the back of the alarm 15 Align the plug area on the smoke alarm with the cut out in the gasket and place the smoke alarm in the mounting plate turn clockwise to fasten it to the mounting plate 16 If auxiliary lock is desired insert either key 1 or 2 into the slot marked Key Slot in the base of the alarm just below the battery drawer Locking key s
7. AMERICAN SMOKE ALARM MANUAL lonization Type Model 120 VAC Hardwire with Battery Back Up amp Alarm Pause Feature e Model SA379 Professional Multi Location 120 Volt AC Hardwire Smoke Alarm with Battery Back Up and Alarm Pause feature This smoke alarm is also interconnectable with up to 11 other units Important information about your smoke alarm e Install alarms outside of every bedroom area and on every floor of your home Please refer to Section 3 Where to Locate Smoke Alarms for details e Install the alarm as close as possible to the center of the ceiling e Your Smoke Alarm is packaged with the back up battery reversed Connect it before mounting the unit Ensure proper polarity of the battery Alarm will beep if battery is reversed and the unit is receiving AC power e Replace the back up battery if the smoke alarm beeps approximately once every 45 seconds low battery warning e Test the alarm weekly by pressing and holding the test button for up to 20 seconds until the alarm sounds e The model described in this manual is designed for single family residences including homes and apartments Smoke Alarm Safety Features e Battery Back Up 120VAC operation with battery back up included to power your smoke alarm in the event of a power interruption e Alarm Pause Silencer Silence your alarm for approximately 10 minutes by momentarily pressing the Alarm Pause Silencer button Ideal for u
8. Battery Hall and Stairways Model with Emergency Light Ionization 2 9V Batteries Ionization Extended Life Extended Life Multi Location with Battery with Ionization Alarm Pause Model 3 Year Warranty Long Life Multi Long Life Lithium Location with battery with 10 Ionization Alarm Pause Model year warranty Professional Hardwire 120 Volt AC Multi Location Model Ionization Professional Hardwire 120 Volt AC with with Battery Back Up 9 Volt Back Up Ionization and Alarm Pause Battery Model AMERICAN SENSORS CARBON MONOXIDE ALARMS American Sensors also offers a complete line of Carbon Monoxide Alarms including CO800 Plug In Carbon Monoxide Alarm CO810 120 Volt AC Hardwire Carbon Monoxide Alarm CO900 Plug In Carbon Monoxide Alarm with Battery Back Up CO910 Plug In Carbon Monoxide Alarm with Digital LED Display CO920 Plug In Carbon Monoxide Alarm with Digital LED and Back Up Power Source CO1100 Battery Powered Carbon Monoxide Alarm for Table Top Travel or Wall Mount AMERICAN TM IONIZATION SMOKE ALARM with Battery Back Up PUSH amp HOLD T0 TEST WEEKLY Bhawen
9. IMITED WARRANTY CONTAINED HEREIN IS THE REPAIR OR REPLACEMENT OF THE DEFECTIVE PRODUCT AT DICON GLOBAL INC S OPTION IN NO CASE SHALL DICON GLOBAL INC S LIABILITY UNDER ANY OTHER REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE YOUR SMOKE ALARM IS NOT A SUBSTITUTE FOR PROPERTY DISABILITY LIFE OR OTHER INSURANCE OF ANY KIND APPROPRIATE COVERAGE IS YOUR RESPONSIBILITY CONSULT YOUR INSURANCE AGENT This warranty gives you specific legal rights and you may also have other rights which vary from province to province Units may be returned to point of purchase according to retailers exchange return policy Or call 1 800 387 4219 for shipping instructions and a returned goods authorization number RGA number to return to Dicon Global Inc Returned goods must be shipped prepaid A cheque for 5 00 is also required for return postage Please mark the RGA number on the exterior of your package Date code located on back of smoke alarm Dicon Global Inc 20 Steelcase Road West Unit 3 Markham Ontario Canada L3R 1B2 email info diconglobal com 10 AMERICAN SENSORS PRODUCTS AMERICAN SENSORS SMOKE ALARMS American Sensors offers a complete line of smoke alarms Select from this group of quality products to ensure your home is fully protected in case of fire Model Description Power Source Smoke Alarm Technology Basic Model 9V Battery lonization General Purpose Model with Alarm Pouse Feature 9V
10. ND TESTING Locking Keys Optional This model has optional locking keys to better secure either the alarm and or the alarm and back up battery to inhibit unauthorized removal See point 16 in this section for more details on this feature A Installation Mount to any standard or rectangular junction box with a minimum depth of 1 inch 25mm 120V AC 55mA operation WARNING Wiring should only be installed by a licensed electrician in accordance with the National Electrical Code and local codes WARNING The circuit used to power the alarm must be a 24 hour voltage circuit that cannot be turned off by a switch or a ground fault interrupter It is highly recommended that smoke alarms be wired on a separate circuit one with no other lights or appliances to ensure maximum reliability of AC power supply For installation of Smoke Alarms in Dwelling Units it is important to follow the National Electrical Code and local codes 1 Electricity must be turned off at service entrance before beginning installation to prevent electrical shock or equipment damage 2 Location must comply with applicable building codes 3 Install a junction box where you plan to install the alarm Use standard 14 gauge wire 4 Grasp the tab on the battery drawer and slide it straight out 5 Reposition the battery in its compartment as shown on the markings in the drawer 6 Push the drawer straight in until it is flush with the housing 7 Test as recommended
11. aterials properly Never smoke in bed e Keep matches and cigarette lighters away from children e Store flammable materials in proper containers Never use them near an open flame or sparks e Keep electrical appliances in good condition Do not overload electrical circuits e Keep stoves fireplaces chimneys and barbecue grills grease free Make sure they are properly installed and away from any combustible materials e Keep portable heaters and open flames such as candles away from combustible material e Do not allow rubbish to accumulate e Keep a supply of extra batteries on hand for your battery powered smoke alarms e Do not stand too close to the alarm when the unit is in alarm as the loud horn could damage your hearing AWARNING Never disconnect the battery or the AC power on any type of smoke alarm to silence a nuisance alarm Clear the area of smoke by opening doors or windows or fanning the smoke away Use the Alarm Pause button on model SA379 to silence nuisance alarms Most important when fire strikes a prepared and practiced escape plan can make the difference between life and death Develop an escape plan and practice it with the entire family including small children e Ensure all family members are familiarized with the alarm signal e Prepare an escape plan Draw a Floor Plan of Your Home and determine two exits from each room There should be a way to get out of each bedroom without opening the
12. door e Have Fire Drills Often Practice your Escape and BE PREPARED e Decide on a meeting place at a safe distance from your home IN CASE OF FIRE e Don t waste time collecting possessions after a fire starts e Arouse all occupants and leave the building Your most valuable possession is your life e Doors can mean escape or death Never open doors without first checking for heat Test them with your hands if they feel warm fire may be walled up behind them leave closed and find another escape route e Call the fire department from OUTSIDE the building e If trapped inside stay close to the floor cover mouth with cloth conserve breath as you crawl to safety e Keep all doors and windows closed except for escape purposes e NEVER re enter a burning building e Keep your family in a pre arranged meeting place after your escape Your local fire department may be able to offer you additional ideas for safety and escape plans in the home 3a WHERE TO LOCATE SMOKE ALARMS As a minimum smoke alarms should be located between sleeping areas and potential sources of fire such as a kitchen heated garage or basement In single storey homes with one sleeping area an alarm should be installed in the hallway outside the bedrooms see Figure 1 In single storey homes with two separate sleeping areas a minimum of two alarms are required one outside each sleeping area see Figur
13. e 2 In multi level or split level homes as a minimum an alarm should be installed outside each sleeping area in the basement and at every level of the home see Figure 3 e In every room of your home except the bathroom Research indicates that substantial increases in warning time can be obtained with each properly installed additional alarm e In bedrooms In anticipation of fires originating within these rooms caused by faulty wiring lamps appliances smoking or other hazards e In hallways At a distance no greater than 13 feet 4 meters from the farthest wall and no greater than 26 feet 8 meters from the next alarm e In the center of a room or hallway As it is impossible to predict the source of a fire If it is necessary to place the alarm on a wall always locate the top of the smoke alarm 4 6 inches 10 15 cm from the ceiling e As needed To compensate for closed doors and other obstacles that may interfere with the path of smoke to an alarm They may also prevent occupants on one side of a closed door from hearing a alarm on the other side of the door Model SA379 Professional Multi location Hardwire with Battery Back Up Model can be located in any area of the home Its Alarm Pause feature makes it ideal in the kitchen area to silence nuisance alarms Do not install it directly over a stove toaster or dishwasher READ CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS in Section 1 of this manual
14. e Alarm Pause button to silence nuisance alarms Abnormal air conditions may cause the highly sensitive smoke alarm to give a false alarm If no fire is apparent ventilate the room and or blow fresh air into the unit until the alarm stops Once cleared the smoke alarm will automatically reset DO NOT DISCONNECT THE AC POWER OR THE BACK UP BATTERY Dust can lead to excess sensitivity Vacuum as recommended above 9 LIMITED WARRANTY Your American Sensors SA379 Smoke Alarm excluding the battery is warranted for ten years from the date of purchase against defect in material and workmanship Units returned to Dicon Global Inc with proof of purchase date during this period as a result of such defects will be repaired or replaced at Dicon Global Inc s option This warranty only covers defects in material or workmanship in normal residential use and does not cover the battery nor does this warranty cover damage resulting from negligent handling misuse or lack of reasonable care This warranty is in lieu of any other warranty either expressed or implied READ CAREFULLY AND SAVE This manual contains important information A copy of this manual must be left with the end user 2502 2507 REV 0 DICON GLOBAL INC SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE OR ANY SPECIAL INCIDENTAL CONTINGENT OR CONSEQUENTIAL DAMAGE OF ANY KIND RESULTING FROM A FIRE THE EXCLUSIVE REMEDY FOR BREACH OF THE L
15. he mobile home or RY locate alarms throughout to ensure maximum protection Follow the location instructions in this manual 4 NFPA RECOMMENDATIONS For your information the National Fire Protection Association s Standard 72 Section 2 2 1 1 1 reads as follows 2 2 1 1 1 Smoke alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional storey of the family living unit including basements and excluding crawl spaces and unfinished attics In new construction a smoke alarm also shall be installed in each sleeping room A 2 5 2 1 Smoke Detection Are More Smoke Alarms Desirable The required number of smoke alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms For this reason it is recommended that the householder consider the use of additional smoke alarms for those areas for increased protection The additional areas include the basement bedrooms dining room furnace room utility room and hallways not protected by the required smoke alarms The installation of smoke alarms in kitchens attics finished or unfinished or garages is not normally recommended as these locations occasionally experience conditions that can result in improper operation 5 LOCATIONS TO AVOID Avoid locations where smoke may not reach the alarm in time to provide early warning or where the
16. hould click into position and be flush with the alarm housing keys are enclosed with the alarm in plastic wrapper To secure To secure smoke alarm smoke alarm to to mounting plate and mounting plate also secure back up battery CAUTION Do not attempt to remove alarm or open battery drawer without first removing locking key If key is not first removed damage may result see below 17 Test alarm operation after installation in accordance with Operation How to Test instructions NOTE Maximum interconnect wiring length is 150 feet 50 meters BLACK WHITE 120VAC 60Hz __ Cap Unused Wire __ Twist Connectors Outlet Box MODEL SA379 120VAC Dual lonization c w 9VDC Battery Back Up Incl 4 e e tua eae lt Supplied Gasket Must Be c Installed In Mounting Plate Oto atm SINGLE STATION T Quick Disconnect Smoke Alarm Power Connector BLACK g J L J L P l J WHITE 120VAC 60Hz MULTIPLE STATION Ceiling ORANGE interconnect IMPORTANT The SA379 is not interconnectable with any other model produced by another manufacturer The SA379 may be interconnected only with the following UL listed smoke alarm models American Sensors COS2010 American Sensors SA379 American Sensors SA360 ASI Electronics American Sensors ESA5010 ASI Electronics American Sensors ESA5011 Dicon Safe
17. ities for up to 11 other units using only three wires including AC power When one alarm sounds all properly interconnected smoke alarms follow NOTE Interconnect only to the models specified in Section 6 Alarm Source Indicator Only the red operating light in the unit originating the alarm will flash rapidly in the event of an alarm With interconnected units an easy check to determine the originator Locking Keys Two auxiliary locking keys provided Use key 1 to lock mounting plate to smoke alarm Use key 2 to lock mounting plate and battery drawer to the smoke alarm to prevent opening of the battery drawer Reduced risk of unauthorized removal Sensitivity Test Button Tests sensitivity as well as circuitry battery and horn With interconnected units activating test button on one unit will cause all units to sound An important and convenient check of system integrity e Quick Disconnect Power Connection For easy installation Connect the wires separately from the unit and then plug into back of the unit e Detachable Base Plate For easily securing the alarm to the junction box CONTENTS OF THIS MANUAL CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS SAFETY TIPS WHERE TO LOCATE SMOKE ALARMS NFPA RECOMMENDATIONS LOCATIONS TO AVOID INSTALLATION AND TESTING BATTERY REPLACEMENT MAINTENANCE AND TROUBLESHOOTING LIMITED WARRANTY 10 OTHER AMERICAN SENSORS PRODUCTS SO Pe ON ee Se P 1 CAPABILITIES AND
18. nt smoke alarm may not detect a fire which started on the first or second floor Smoke alarms may not be heard The loudness of the horn in your alarm meets current standards However the sound may be blocked by distance closed doors or ambient noise such as traffic or a stereo Smoke alarms may not be heard by persons who are hard of hearing For these reasons a smoke alarm should be installed in every room or at least on every level of your home American Sensors recommends that hardwire AC Powered smoke alarms be interconnected so that one alarm will trigger all other Smoke alarms to sound their alarms Smoke alarms are not fool proof Smoke alarms may not always sense every kind of fire They cannot be expected to sense fires caused by carelessness or by safety hazards They may not give early warning of fast growing fires caused by smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits natural causes such as lightning children playing with matches or arson Smoke alarms are not substitutes for property disability life or other insurance of any kind Home owners and renters should continue to insure their lives and property Consult your insurance agent Smoke alarms have limited lives One or more of the many components could fail at any time Therefore test your smoke alarm weekly Clean and take care of it as described in this manual Repair or replace the
19. s approximately every 45 seconds 3 Press and hold the test button until the alarm sounds NOTE It may be necessary to press the test button for up to 20 seconds for an alarm to sound An alarm is indicated by 3 constantly repeating beeps every 4 seconds with the red LED flashing intermittently An alarm may continue to sound for up to 10 seconds after the button is released After Installation 1 Check to see that the green operating light is on The operating light is visible behind the slotted case and confirms that the smoke alarm is receiving AC power 2 At least once a week press the test button until the alarm sounds then release NOTE Multiple Station Only 4 Test each alarm separately in the system 5 Determine that the initiating alarm triggers other alarms in the system 7 BATTERY REPLACEMENT The Eveready 216 522 1222 Duracell MN1604 MX1604 and the Gold Peak 1604P are the only acceptable back up batteries for use in this smoke alarm The back up battery will power the smoke alarm for at least one year under normal use When the back up battery reaches the end of its normal life a low battery warning intermittent beeping for up to 30 days will indicate the need for back up battery replacement NOTE If the battery drawer is open the low battery warning beep is disabled The battery drawer is designed to resist closing when the back up battery is removed thereby ensuring visual warning A WARNING
20. se when non emergency smoke causes nuisance alarms Automatically resets after 10 minutes During Alarm Pause the unit will beep every 45 seconds to remind the household that the alarm has been silenced In the event of a heavy build up of smoke during the pause period the alarm will resume sounding For interconnected units only the alarm which had the Alarm Pause Silencer button activated will be in Alarm Pause Dual Ionization Chambers Advanced design responds to visible or invisible particles of combustion smoke to sense fires in their earliest stages Compensates for changes in humidity and temperature to virtually eliminate nuisance alarms caused by normal atmospheric changes in the home Operating Lights LED s A continuous green light located behind the slotted case indicates the smoke alarm is receiving AC power A red light that flashes approximately every 45 seconds confirms that the battery is operational Low Battery Warning If powered only by battery the unit beeps approximately every 45 seconds for up to 30 days when the battery needs replacing If the unit is receiving continuous AC power the low battery beep will continue indefinitely Battery Removal Indication Battery compartment drawer is designed to resist closing when the battery is removed A visual reminder to replace the battery Low battery warning beep is disabled with the drawer open Interconnection Interconnection facil
21. smoke alarm when it fails to test properly Your smoke alarm should be replaced if it is ten years old Ionization Technology vs Photoelectronic Technology Smoke Alarms There are two different types of smoke alarm technology currently in general use ionization and photoelectronic While both types of technology are suitable for general residential use an ionization alarm will normally respond faster to fast flaming fires while a photoelectronic alarm may be more sensitive to detecting slow smoldering fires Because home fires develop in different ways and are often unpredictable in their growth it is impossible to predict which type of alarm will provide the earliest warning For best home protection install at least one photoelectronic and one ionization smoke alarm on each level of your home Model SA700 is a 2 in 1 smoke alarm utilizing both ionization and photoelectronic technology Model SA379 is an ionization type smoke alarm A photoelectronic smoke alarm senses smoke using an electronic photo receptor to sense the scattering of light by smoke particles The American Sensors model SA388 is a photoelectronic type smoke alarm 2 SAFETY TIPS Properly installed and maintained smoke alarms are an essential part of a good home fire safety program Your fire safety program should also include a review of fire hazards and the elimination of dangerous conditions whenever possible Consider the following tips e Use smoking m
22. ty Products Inc 670L Dicon Safety Products Inc 670LR Dicon Safety Products Inc 370LBX Note This equipment should be installed in accordance with the National Fire Protection Association Standard 72 National Fire Protection Association Batterymarch Park Quincy MA02269 To Remove Locking Key To remove the locking key insert a small screwdriver into the small hole at the top of the battery drawer Apply pressure at the tip of the screwdriver pushing up on the locking key The locking key will pop out To Activate the Alarm Pause Feature Simply press the Alarm Pause button on the cover of the smoke alarm for a minimum of 5 seconds then release to activate the Alarm Pause feature In this mode the unit should not respond to smoke by sounding an alarm for a period of approximately 10 minutes unless the level of smoke concentration becomes very heavy approaching 4 per cent per foot obstruction During the Alarm Pause period the smoke alarm should beep approximately once every 45 seconds to alert the household that the smoke alarm has been silenced Variations in Length of Alarm Pause Period The Alarm Pause period will vary in length depending upon the amount of smoke present When there is no smoke the Alarm Pause will be activated for the longest period of time approximately six to ten minutes after releasing the Alarm Pause button If the level of smoke density increases the length of the Alarm

Download Pdf Manuals

image

Related Search

Related Contents

取扱説明書 - TECHNO GREEN, LIMITED  Dale Tiffany 10084/3LTF Installation Guide  RuggedSwitch® RS900GP  Samsung GT-I6410 User Manual    Génie climatique  

Copyright © All rights reserved.
Failed to retrieve file