Home

ADT Security Services ADT-UDACT User's Manual

image

Contents

1. Terminal 4 EIA 485 EIA 485 Supervised and Power limited power connections to ADT UDACT E TB1 EE TB1 Terminal 3 RS Terminal 4 RS Install 120 ohm EOL resistor P N 71244 across terminals 3 4 if last or only device on ElA 485 line Note that Terminals 6 amp 7 are not used at this time DO NOT USE SECONDARY ACTIVE UNIVERSAL DIGITAL ALARM COMMUNICAIOR TRANSMITTER POWER COMM FAIL ElA 485 KISS OFF EE box DON III DODDB DECOM TEST CONNECTOR J5 PE ina udac wmf ADT UDACT Figure F 1 EIA 485 Connection to Panel Mounted ADT UDACT Document 50934 RevB 5 15 00 PN 50934 B 63 ADT MNNA cabinet g 308 o mm es o el E mm em Ferrite E E Core 8 ps _ mm mm to 24V0G Nenresettable DO NOT USE 3 Supervised To Phone p e Lines W I Ferrite Core Solid Earth Ground Connection ATTE Install 120 ohm EOL resistor P N 71244 HI Fs across terminals 3 amp 4 if last or only device on ElA 485 line Note that Terminals 6 8 7 are not used at this time Dag KISS OFF Ema 0000 D0000 ADT UDACT in ADT ABS8RF Shown with cover removed ina absu WMF Notes 1 Ferrite cores are recom
2. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled For added protection against tele phone line failure backup radio transmission systems are rec ommended The most common cause of fire alarm malfunction is inade quate maintenance To keep the entire fire alarm system in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA stan dards At a minimum the requirements of Chapter 7 of NFPA 72 shall be followed Environments with large amounts of dust dirt or high air velocity require more frequent mainte nance A maintenance agreement should be arranged through the local manufacturer s representative Maintenance should be scheduled monthly or as required by National and or local fire codes and should be performed by authorized pro fessional fire alarm installers only Adequate written records of all inspections should be kept Installation Precautions WARNING Several different sources of power can be con nected to the fire alarm control panel Disconnect all sources of power before servicing Control unit and associated equip ment may be damaged by removing and or inserting cards modules or interconnecting cables while the unit is energized Do not attempt to install service or operate this unit until this manual is read and understood CAUTION System Reacceptance Test afte
3. 36 Troubleshoot Mode 4 2 2 Zone or Point Supervisory A zone or point must be defined as supervisory to allow the ADT UDACT to identify the correct report to transmit to the central station Follow the programming instructions in the FACP manual to program a zone or point as supervisory Next program the zone or point as a code 2 for supervisory Use the charts in Appendices to enter point and zone definitions Note that the ADT UDACT fire protection and reporting capabilities are inactive while in Type Mode To get into the Troubleshoot Mode press MODE 8768 and ENTER STORE e 8768 spells TROU on a Touch Tone phone Once in this mode the ADT UDACT will e Transmit the UDACT off normal message to the Central Station s e Continue to communicate any events not yet acknowledged at the Central Station prior to entering Troubleshoot Mode The UP Arrow key Down Arrow key and 1st EVENT keys do not function in this mode Telephone Line Testing Pressing C for touchtone dialing or D for rotary dialing followed by ENTER STORE causes seizure of the Primary phone line which in turn lights the red LED signifying Primary phone line active After a delay of three seconds the ADT UDACT goes off hook to acquire a dial tone The ADT UDACT keypad may be used as a telephone touchpad for number dialing Once the first digit is pressed the display will move the C or D character one position to the left while placing the digit to be
4. Document 50934 RevB 5 15 00 PN 50934 B 9 1 5 1 6 10 Circuits e For tone burst or touchtone type formats Discern proper Ack and Kiss off tone s The frequency and time duration of the tone s varies with the transmission format The ADT UDACT will adjust accordingly Communicate in the following formats refer to Section 6 0 for compatible receivers 6 Tone Burst Types 20 pps 3 1 441 4 2 Y 3 Touchtone Types 4 1 Ademco Express 4 2 Ademco Express Ademco Contact ID The ADT UDACT circuit board contains a CPU other primary components and wiring interface connectors 1 5 1 Power Requirements Operating voltage for the ADT UDACT must be power limited filtered nonresettable 21 2 to 28 2 volts The 24 VDC nominal operating power must be supplied by the Control Panel and is connected to TB1 of the ADT UDACT 1 5 2 Communications Communications between the ADT UDACT and the host control panel is accomplished over a two wire EIA 485 serial interface which is power limited and supervised by the control panel and the ADT UDACT The wiring connections are made to the RS RS and Shield terminals of TB1 on the ADT UDACT The EIA 485 circuit cannot be T Tapped and must be wired in a continuous fashion from the control panel to the ADT UDACT and if installed annunciators The wire must be 12AWG to 18AWG twisted shielded pair cable with a Characteristic Impedance of 120 Ohms 20 Limit the total wire resistance
5. JCT A or C are entered for address 16 the following data is automatically programmed for the Primary phone number event codes Enter a 0 for the data setting to disable the report These formats do not support zone point programming For zone point reporting refer to Contact ID Address Description Settings 69 70 Primary General Alarm Code 11 71 72 Primary Zone Point Alarm Code 00 73 74 Primary General Supervisory Code 81 75 76 Primary Zone Point Supervisory Code 00 71 18 Primary General Fault Code Fl 79 80 Primary AC Fault Code F6 81 82 Primary Zone Point Fault Code 00 83 84 Primary Low Battery Fault Code F8 85 86 Primary Telco Primary Line Fault Code FA 87 88 Primary Telco Secondary Line Fault Code FB 89 90 Primary NAC Fault Code FC 91 92 Primary Comm Trouble Primary Number Code FD 93 94 Primary Comm Trouble Secondary Number Code FE 95 96 Primary 485 Comm Trouble Code FE 97 98 Primary System Off Normal Code FF 99 100 Primary ADT UDACT Off Normal Code FF 101 102 Primary General Alarm Restore Code El 103 104 Primary Zone Point Alarm Restore Code 00 105 106 Primary General Supervisory Restore Code E2 107 108 Primary Zone Point Supervisory Restore Code 00 109 110 Primary General Fault Restore Code E3 111 112 Primary AC Fault Restore Code E6 113 114 Primary Zone Point Fault Restore Code 00 115 116 Primary Low Battery Fault Restore Code ES 117 118 Primary Telco Primary Line Faul
6. Programming Reference Sheet 4 Y Y Y Y Y Y Y YU YU OG YU Y LL LL LL LL E LL Sch LL LL Sch LL El LL El LL LL LL ER Sk LL LL Eh LL Sch E al LL LL mA El LL LL El Sch LL LL ah LL E D WS Gi SEHR CES DE RE ER 1 4 ES ES R LL LL ER LL LL LL LL LL LL LL Em LL LL El El LL Sch LL nm LL LL LL aa El LL SI 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 LL Em BR Ep LL LL LL Rn LL Si 199 200 201 202 203 204 205 206 207 208 Document 50934 RevB 5 15 00 PN 50934 B 44 Programming Reference Sheet Factory Default Settings To enter Programming press Mode 77 6 4 Enter EL EL EL EL EL EL EL EL EL EL ER E EL A E D Addresses 00 to 15 store the Primary Phone Number Enter F to represent the end of the number A Primary Comm Format 4 2 Standard 1800 2300 0 o 0 a Primary Account Code 0 Q LO 0 Primary 24 Hour Test Time 0000 12 00 midnight 0 Primary Number Test Time Interval 0 for 24 hour A 6 A A 0 A A A 0 0 A A A 0 0 A Addresses 26 41 store the Secondary Phone Number Enter F to represent the end of the number Al Secondary Comm Format 4 2 Standard 1800 2300 o 0 0 o Secondary Account Code 0 0 Q secondary 24 Hour Test Time 0000 12 00 midnight Secondary Number Test Time Interval 0 for 24 hour S DL Start Monitoring Address La 21 En
7. Restore Code E 167 Secondary Comm Trouble Secondary Restore Code E 168 Secondary 485 Comm Trouble Restore Code E 169 Secondary System Off Normal Restore Code E 170 Secondary ADT UDACT Off Normal Restore Code E 171 Secondary System 24 Hour Test 9 172 Secondary System 24 Hour Test w active event F 173 Secondary Manual Test 9 Note Zero entries prevent the transmission of the report to the Central Station Table 3 5 Event Codes Secondary Number Document 50934 RevB 5 15 00 PN 50934 B 27 4 2 Standard and 4 2 Express Formats If 1 A or C are entered for address 42 the following is automatically programmed for the Secondary phone number event codes Enter a 0 for the data setting to disable the report These formats do not support zone point programming For zone point reporting refer to Contact ID Address Description Setting 139 140 Secondary General Alarm Code 11 141 142 Secondary Zone Point Alarm Code 00 143 144 Secondary General Supervisory Code 81 145 146 Secondary Zone Point Supervisory Code 00 147 148 Secondary General Fault Code Fl 149 150 Secondary AC Fault Code F6 151 152 Secondary Zone Point Fault Code 00 153 154 Secondary Low Battery Fault Code F8 155 156 Secondary Telco Primary Line Fault Code FA 157 158 Secondary Telco Secondary Line Fault Code FB 159 160 Secondary NAC Fault Code FC 161 162 Secondary Comm Trouble Primary Number Code FD 163 164 Secondary Comm Tro
8. Zones 99 are programmed by Entries Addresses 01 99 The factory default code is fire alarm For Point Identification Loop 1 Modules 101 196 are programmed by Type Mode Entries Addresses 01 96 Loop 2 Modules 201 296 are programmed by Type Mode Entries Addresses 101 196 Loop 1 Detectors 101 196 are programmed by Type Mode Entries Addresses 201 296 Loop 2 Detectors 201 296 are programmed by Type Mode Entries Addresses 301 396 System 5000 output modules are programmed by Type Mode Entries Addresses 401 464 CAUTION Addresses 97 100 197 200 and 297 300 must not be programmed Refer to the CAB illustrations below Event Code Report Transmission via Ademco Contact ID Format Only For Zone Reporting Zones 1 99 report as zone numbers 01 99 For Point Reporting Loop 1 Modules 101 196 report as device numbers 01 96 Report defaults to 110 Loop 2 Modules 201 296 report as device numbers 101 196 Report defaults to 110 Loop 1 Detectors 101 196 report as device numbers 201 296 Report defaults to 111 Loop 2 Detectors 201 296 report as device numbers 301 396 Report defaults to 111 Output Modules 1 64 report as device numbers 401 464 Report defaults to 380 trouble only CAUTION Point reports for Loop 1 Modules 197 through 199 Detectors 197 through 199 and point reports for Loop 2 Modules 297 through 299 and Detectors 297 through 299 are omitted However when devices are
9. 1 to disable alarm reporting of any zone or point The digit entered will appear on the far right display Next press the ENTER STORE key This stores the entry into E memory and increments to the next higher address Use the UP DOWN and 1st EVENT keys to move through the list of zones points refer to Appendices similar to the method described in the programming section of this manual To define all zones or points as fire alarm return to original factory default settings enter zone or point 999 and then press the ENTER STORE key The display will change to 01 0 indicating a return to the factory default settings 4 2 1 Disabling of Zones or Points This feature is primarily used when system points have been defined as remote reset acknowledge silence or drill switches Refer to the FACP technical manual for additional information Activation of remote switches appear as alarms on the EIA 485 bus The ADT UDACT will report these points as fire alarm points unless disabled in the Type Mode Disabling zones or points also prohibits the activation shorted or alarm activated condition from being reported by the ADT UDACT Disabling of the zone or point does not affect the reporting of the zone or point trouble condition Note Type Mode 1 for zones 90 99 disables reports for these zones To transmit reports for zones 90 99 use Type Mode entries of 0 or 2 through F Document 50934 RevB 5 15 00 PN 50934 B 35 4 3
10. 2 amp 3 TB3 2 Communicator Failure Power limited circuit An Open Collector type output normally high active low which sinks up to 40 mA TB3 3 21 2 to 28 2 volts power limited Use UL listed relay P N MR 101 C or MR 201 C with this output Earth Ground TB3 Terminal 1 TB3 1 Earth Ground connection Connect this terminal to building earth ground using solid 12 AWG wire to provide lightning protection This connection is not required when the ADT UDACT is mounted in a grounded metal enclosure via the upper right mounting hole 1 8 1 Telephone Circuitry PH1 amp PH2 Ringer Equivalence Number REN 0 6B AC Impedance 10 0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold less than 4 0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive REN s on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of the REN s should not exceed five 5 0 To be certain of the number of devices that may be connected to the line as determined by the total REN s contact the telephone company to determine the maximum REN for the calling area 1 8 2 Digital Communicator Before connecting the ADT UDACT to the public switched telephone network the installation of two RJ31X jacks is necessary The following information is provided if required by the local te
11. 266 316 366 217 267 317 367 218 268 318 368 219 269 319 369 220 270 320 370 221 271 321 371 222 272 322 372 223 273 323 373 224 274 324 374 225 275 325 375 226 276 326 376 227 277 327 377 228 278 328 378 229 279 329 379 230 280 330 380 231 281 331 381 232 282 332 382 233 283 333 383 234 284 334 384 235 285 335 385 236 286 336 386 237 287 337 387 238 288 338 388 239 289 339 389 240 290 340 390 241 291 341 391 242 292 342 392 243 293 343 393 244 294 344 394 245 295 345 395 246 296 346 396 247 297 347 397 248 298 348 398 Do Not Program Do Not Program 249 299 349 399 250 300 350 400 Note Addressable detectors on Loops 1 and 2 may be disabled using Type Mode The Event Code cannot be altered For Unimode 300 use only Loop 1 in the chart Document 50934 Rev B 5 15 00 PN 50934 B 49 Appendix B continued Point Assignments Unimode 300 400 Point No Type of Device Point No Type of Device 401 451 402 452 403 453 404 454 405 455 406 456 407 457 408 458 409 459 410 460 411 461 412 462 413 463 414 464 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 Note Event Code cannot be altered
12. 32 screw Connect the communication line between the EIA 485 terminal block on the Unimode 2020 1010 SIB card and TB 1 terminals 3 and 4 on the ADT UDACT being certain to observe polarity refer to Figure D 3 Recommended wire is 12 AWG to 18 AWG twisted pair If no other devices are connected to the EIA 485 install a 120 ohm EOL resistor across ADT UDACT TB1 terminals 3 and 4 Connect the supplied Ground Strap from the ADT UDACT Earth Ground terminal on TB3 to the CHS 4 chassis Connect 24 VDC filtered regulated power to TB1 terminals 1 and 2 on the ADT UDACT Figure D 2 ADT UDACT Mounting in CHS 4 56 Document 50934 RevB 5 15 00 PN 50934 B Ground Strap Nylon and Aluminum Standoff UDACCHS4 WMF 6708ubs wmf TB5 Terminal 5 ElA 485 Terminal 6 ElA 485 ElA 485 Supervised and Power limited Refer to Figure l 4 for power connections to ADT UDACT E sw1 TB1 SIB Pi ElA 485 Reference d Earth Ground El EIA 485 1 d ElA 485 E ElA 485 3 ElA 485 3 E SIB to DIA cable P N 71046 SIB P4 to DIA P4 O S E 2 P4 o 16 is P3 Terminal 3 RS Terminal 4 RS PRIMARY ACTIVE Install 120 ohm EOL resistor P N 71244 across terminals 3 amp 4 if last or only device on ElA 485 line Note that Terminals 6 amp 7 are not used at this time DO NOT USE SECONDARY
13. chosen options features already programmed Other options features may be programmed if desired If all factory default settings are acceptable programming is complete To enter the Program Mode press the MODE key once the display will go blank you then have ten seconds to start entering the code 7764 7764 spells PROG on a Touch Tone phone If an incorrect key is entered reenter the proper 4 digit code before pressing the ENTER STORE key 7 77 Note that as you enter information into the 776 ADT UDACT the digits will scroll across the 7764 display from right to left You are allowed a pause of up to 10 seconds in between each number while entering the code After pressing the ENTER STORE key the ADT UDACT will be in Program Mode and display 00 F You are allowed up to ten minutes of idle time at this point before starting your programming otherwise the ADT UDACT will go back to Normal Mode You also have a maximum of 10 minutes between any key stroke All entries made prior to the 10 minute time out are valid and stored Once in Programming Mode the ADT UDACT will e Ignore the Test and Clear keys e Continue to communicate any events not previously acknowledged at the Central Station prior to entering Programming Mode Location 56 is factory set to 0 ADT UDACT communications disabled This keeps the communicator off until location 56 is changed to 1 2 3 or 4 Refer to program selection for address 56 in this s
14. have sensing limitations Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires which have little visible smoke Detectors that have ion izing type sensing chambers tend to detect fast flaming fires better than smoldering fires Because fires develop in differ ent ways and are often unpredictable in their growth neither type of detector is necessarily best and a given type of detec tor may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Precau Lg p65 01 18 2000 While a fire alarm system may lower insurance rates it is not a substitute for fire insurance Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire pro tection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys tem for the connection of alarm
15. information received from the FACP via the EIA 485 communications bus Should the communications bus malfunction or be temporarily disabled the ADT UDACT transmits the report 485 comm trouble When the communications bus returns to proper operation the ADT UDACT will report 485 comm trouble restoral Type Mode may be used to disable reports by zone or point and to identify the specific functionality of each zone or point in the system via Ademco Contact ID format Factory default for all zones is Fire Alarm When reporting point information the factory default for addressable monitor modules is Fire Alarm code 110 and the default for addressable detectors is Smoke Detector code 111 The smoke detector default cannot be modified Use Type Mode to identify the function of each zone or point as follows e General fire alarm e Burglary e Supervisory e 24 hour non burglary e Pull stations e High temperature e Heat detectors e Low temperature e Waterflows e Low water pressure e Duct detectors e Low water level e Flame sensor e Pump failure e Smoke zone Note Unimode 2020 1010 and ADT MNNA applications restrict Type Mode program ming to a maximum of 568 points All remaining points above 568 will report as fire alarm points Document 50934 RevB 5 15 00 PN 50934 B To access Type Mode press the MODE key followed by the 4 digit code 8973 and then press the ENTER STORE key The ADT UDACT will display three digits For example init
16. on the EIA 485 circuit is detected Comm Fail This yellow LED turns on to indicate the loss of both telephone lines or that the maximum number of attempts to communicate with both Central Stations has been unsuccessful Note During a comm fail the display will show either a PHI and PH2 or nol and no2 Power On A green LED that remains on while DC power is supplied to the ADT UDACT Jf this indicator fails to light under normal conditions service the system immediately Kiss Off A green LED that blinks when the Central Station has acknowledged receipt of each transmitted message Test A green LED that turns on to indicate that a manual test message is being transmitted Primary Line Active A red LED that indicates the primary phone line is active Secondary Line Active A red LED that indicates the secondary phone line is active Modem A green LED that stays on steady during modem types of communications Document 50934 RevB 5 15 00 PN 50934 B 31 32 Primary Line Modem Primary Active LED RIMAS ACTIVE PH1 POWER ElA 485 O UNIVERSAL DIGITAL ALARM COMMUNICATOR TRANSMITTER O movem H D 24y SECON SHIELD ranarararnmr Secondary Line r e F Secondary J Active LED _ Kiss Off LED KISS OFF UDACTNOT WMF Figure 4 1 ADT UDACT Phone Connectors and LEDs 4 1 3 Normal Mode Operation
17. they will not interfere with battery trans former and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal Though designed to last many years system components can fail at any time This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re moved from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation by authorized personnel Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications Le present appareil numerique n emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada Precau Lg p65 01 18 2000 Table of Contents NFPA Standards NFPA 72 National Fire Alar
18. 00 15 The defaults are also all F s F F F F F F F EF FF F F F F F FE 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Document 50934 RevB 5 15 00 PN 50934 B Secondary Number Communication Format 42 Programming is the same as the primary number s Comm Format at address 16 Default entry is A 4 2 Standard When selecting the Format note that Ademco Contact ID is the only format in the ADT UDACT which identifies the specific zone or point status to the Central Station All other formats report the number of zones or points that are active but do not identify the specific zone or point Choose one entry from the list below 0 4 1 Ademco Express Standard DTMF 1400 2300 ACK 1 4 2 Ademco Express Standard DTMF 1400 2300 ACK 2 3 1 Standard 1800 Hz Carrier 2300 Hz ACK 3 Not Used 4 3 1 Standard 1900 Hz Carrier 1400 Hz ACK 5 Not Used 6 4 1 Standard 1800 Hz Carrier 2300 Hz ACK 7 Not Used 8 4 1 Standard 1900 Hz Carrier 1400 Hz ACK 9 Not Used A 4 2 Standard 1800 Hz Carrier 2300 Hz ACK B Not Used C 4 2 Standard 1900 Hz Carrier 1400 Hz ACK D Not Used E Ademco Contact ID F Not Used Secondary Number Account Code 43 46 is programmed in addresses 43 46 in the same manner as the primary phone number Account Code Default entries are all Us Secondary Number 24 Hour Test Time 47 50 is programmed in addresses 47 50 in the same manner as the primary number 24 Hour Test Time Default is 00 00 12 00 m
19. 29 079 129 179 030 080 130 180 031 081 131 181 032 082 132 182 033 083 133 183 034 084 134 184 035 085 135 185 036 086 136 186 037 087 137 187 038 088 138 188 039 089 139 189 040 090 140 190 041 091 141 191 042 092 142 192 043 093 143 193 044 094 144 194 045 095 145 195 046 096 146 196 047 097 147 197 048 098 Do Not 148 198 Do Not 049 099 Program 149 199 Program 050 100 150 200 Note Use chart to carefully identify all points in the system Take special precaution with any supervisory points and remote switches in the system Use Type Mode refer to Section 4 2 Type Mode to match the function of remaining points in the system for proper reporting For Unimode 300 use only Loop in the chart 48 Document 50934 RevB 5 15 00 PN50934 B Appendix B continued Point Assignments Unimode 300 400 Point No Type of Device Point No Type of Device Point No Type of Device Point No Type of Device Detectors Loop 1 Detectors Loop 1 Detectors Loop 2 Detectors Loop 2 201 251 301 351 202 252 302 352 203 253 303 353 204 254 304 354 205 255 305 355 206 256 306 356 207 257 307 357 208 258 308 358 209 259 309 359 210 260 310 360 211 261 311 361 212 262 312 362 213 263 313 363 214 264 314 364 215 265 315 365 216
20. 4 2 Standard 1800 Hz Carrier 2300 Hz ACK B Not Used C 4 2 Standard 1900 Hz Carrier 1400 Hz ACK D Not Used E Ademco Contact ID F Not Used Note Consult your Central Station for proper selection or consult our factory representatives For any format chosen the ADT UDACT automatically programs all of the event codes See Tables 3 2 3 3 3 4 3 5 3 6 and 3 7 Primary Number Account Code 17 20 Four locations at addresses 17 20 default to all 0 s Valid entries are 0 9 and A F The number of digits entered must match the format selection If programming 2 or 4 into address 16 enter 3 digits location 20 is ignored If programming 0 1 6 8 A C or E into address 16 enter 4 digits Primary Number 24 Hour Test Time 21 24 Use military time when entering the 24 hour test time The 24 hour test report to phone number 1 takes up four locations from addresses 21 24 The default is 00 00 12 00 midnight The limits for each location are as follows 21 enter 0 1 or 2 22 enter 0 9 23 enter 0 5 24 enter 0 9 Note Do not use A F Primary Number 24 12 Hour Test Time Interval 25 The test report sent to the Primary phone number may be sent every 12 or 24 hours If the message is to be sent every 24 hours leave the factory default entry of zero If 12 hour test report time is needed enter 1 12 hours Secondary Phone Number 26 41 Programming is similar to programming the primary phone number located at addresses
21. ACTIVE UNIVERSAL DIGITAL ALARM COMMUNICATOR TRANSMITTER POWER COMM FAIL ElA 485 KISS OFF AC majaa DODOD DELES ECC LIES TEST CONNECTOR J5 PETER Slo udac ADT UDACT Figure D 3 ElA 485 Connection to Panel Mounted ADT UDACT Document 50934 RevB 5 15 00 PN 50934 B 57 Unimode 2020 1010 cabinet SIB in Unimode 2020 1010 Nam LI Ferrite Core p ElA 485 Reference Earth Groun ElA 485 EE ElA 485 ElA 485 A 485 P4 i Solid Earth Ground Connection Ferrite Core Install 120 ohm EOL resistor P N 71244 across terminals 3 amp 4 if last or only device on ElA 485 line Note that Terminals 6 amp 7 are not used at this time ESCORE ODODy FA JOO ajajaja 006 ADT UDACT in ADT ABS8RF Shown with cover removed Notes 1 Ferrite cores are recommended for all applications 2 Recommended wire is 12 AWG to 18 AWG twisted pair 3 Shielded wire is not required unless mandated by local AHJ If shielded wire is used connect only one end of shield a shield may be connected to cabinet earth ground at fire alarm panel or b shield may be connected to TB1 Terminal 5 Shield at ADT UDACT as shown in Figure D 4 NOTE The shield end that is not connected should be insulated to prevent accidental grounding Do not connect both ends of shield und
22. DO fe fe Do fo fm Do fe of DO fe fe Do fo er DO fe fr Do fts o fts Do fo 0 fe DO fa o fa Ds o fa E O ES Do fe fe Document 50934 RevB 5 15 00 PN 50934 B Point Function Appendix C continued Point Assignments ADT MNNA Point Function Point Function E o 2 O E 3 GC O a 360 320 280 53 PN 50934 B RevB 5 15 00 Document 50934 Appendix C continued Point Assignments ADT MNNA Point No Point Function Point Function lt 2 O E 3 ra O a NO DIN IO OD O Io Oo oJo jo o o o ojo pr jr I DIDIMIDINAINAIDAIMIMOM Von 1M oO 480 440 400 PN 50934 B RevB 5 15 00 Document 50934 54 Appendix C continued Point Assignments ADT MNNA Point No Point Function Point No Point Function Point No Point Function mo o fe o mo e po e o fe po 483 63 484 524 64 q al N wo a mo e Else ET ES A e A E AMP E sel Ee 8er 1 peo do ES E es E bbo ae S JR pS E AA 517 s o fe ro E 560 Document 50934 RevB 5 15 00 PN 50934 B 55 Appendix D Unimode 2020 1010 The ADT UDACT is capable of reporting up to 2 040 points when used with the Unimode 2020 1010 1 980 Addressable devices plus 60 zones or 1 800 Addressable devices plus 240 zones The first 568 points can be programmed using the Type Mode feature refer to Section 4 2 All points greater than 568 can be transmitted on
23. EE TB2 1 4 a Ais we Een 24 VDC e pot gt f Nonresettable cm o l2 power SS la 5 S le N S 7 DO NOT USE P ADT UDACT in ADT ABS8RF shown with cover removed Notes 1 Ferrite cores are recommended for all applications 2 Recommended wire is 12 AWG to 18 AWG twisted pair 3 Shielded wire is not required unless mandated by local AHJ If shielded wire is used connect only one end of shield a shield may be connected to cabinet earth ground at fire alarm panel or b shield may be connected to TB1 Terminal 5 Shield at ADT UDACT as shown in Figure E 3 NOTE The shield end that is not connected should be insulated to prevent accidental grounding Do not connect both ends of shield under any circumstance since a ground fault may result 4 Conduit is recommended for external wire runs Consult local building codes 5 Connect Ground Strap supplied with ADT ABS8RF enclosure from Earth Ground terminal on ADT UDACT to a solid building earth ground Conduit alone will not provide a reliable earth ground 6 ADT UDACT may be located up to 6 000 feet away from the host control panel 7 Refer to Specifications for power requirements Figure E 3 Unimode 400 External ADT UDACT Mounting in ADT ABS8RF 60 Document 50934 RevB 5 15 00 PN 50934 B Type Mode Programming To disable or identify a zone or point in Type Mode refer to Section 4 2 the following Entries Addresses are used For Zone Identification
24. Format Loop Number and Device Number do not directly correspond to the SLC Loop or Device Number instead it is a convenient way to transmit data to the Central Station Using the default Loop Number of 00 allows the reporting of a maximum of 999 devices or zones 001 999 To report device addresses or zones higher than 999 the Unimode 2020 can report up to 2 040 addresses the Loop Number is incremented by one to report up to an additional 1 000 device addresses or zones on the same panel Following is an example using the factory defaults of Loop Number and Device Number settings for the ADT UDACT on a single Unimode 2020 control panel Loop Number 00 reports points zones 00 001 to 00 999 Loop Number 01 reports points zones 01 000 to 01 999 Loop Number 02 reports points zones 02 000 to 02 040 If the Loop Number 54 65 is programmed to 10 the devices are reported as Loop Number 10 reports points zones 10 001 to 10 999 Loop Number 11 reports points zones 11 000 to 11 999 Loop Number 12 reports points zones 12 000 to 12 040 In applications which network multiple Fire Alarm Control Panels the group number may be used to help identify each facility being monitored For example each ADT UDACT can report its panel s devices by designating different Loop Numbers for each panel The Loop Numbers assigned to a particular panel must be sequential but the Loop Numbers from one panel to the next need not be sequential i e the Lo
25. MR 201 C Connections must be room within 20 feet in same room as of ADT UDACT and ADT UDACT in conduit Relay Energized LED TB3 ON NC Earth Gnd E SPDT Contacts c 10 Amps Comm Fail 0 O 115 VAC 24 VDC 18 24 NO MR 101 C Note The MR 101 C and MR 201 C include an enclosure UDACTTB3 EPS Figure 2 2 Relay Driver Connections Document 50934 RevB 5 15 00 PN 50934 B 15 Earth Grnd Comm Fail 24 VDC ADT UDACT gt ES 2 E M L S Lodo ot 5 O to LJ LJ M300 Series Monitor Module SLC Loop to Fire Alarm Control Panel Wiring in same room as ADT UDACT All wiring to relay must be in the same room within 20 conduit 3 9K EOL feet of ADT UDACT and in Resistor included 0 18 24 115 230 e E MR 101 C MR 201 C may be used Note M300 Series Monitor Module is used to supervise Normally Closed output of MR 101 C On ADT UDACT trouble and Comm Fail MR 101 C relay contact will open causing the monitor module to transmit trouble condition to FACP 16 Figure 2 3 Monitoring for ADT UDACT Trouble Document 50934 RevB 5 15 00 PN 50934 B 2 3 UL Power limited Wiring Power limited and nonpower limited circuit wiring must remain separated in the cabinet All power limited circuit wiring must remain at least 0 25 away from any nonpower limited circuit wiring Furthermore all powe
26. No Zoe Function Esso MN SRA Edo tl E ENS ln A EST Pl Ss Elo EI Bla EA fog Eli Et l ET AS MA A AS AAA EEB E Esc E El tels A El BO AA de ASA A Note Use chart to carefully identify function of each zone in the system Take special precaution with any supervisory zones in the system Use Type Mode refer to Section 4 2 Type Mode to match the function of remaining zones in the system for proper reporting Caution When selecting burglar zones modify the general supervisory report at addresses 75 77 and 145 147 to report general burglary Document 50934 RevB 5 15 00 PN 50934 B 47 Appendix B Point Assignments Unimode 300 400 Point No Type of Device Point No Type of Device Point No Type of Device Point No Type of Device Modules Loop Modules Loop Modules Loop Modules Loop 001 1 051 1 101 2 151 2 002 052 102 152 003 053 103 153 004 054 104 154 005 055 105 155 006 056 106 156 007 057 107 157 008 058 108 158 009 059 109 159 010 060 110 160 011 061 111 161 012 062 112 162 013 063 113 163 014 064 114 164 015 065 115 165 016 066 116 166 017 067 117 167 018 068 118 168 019 069 119 169 020 070 120 170 021 071 121 171 022 072 122 172 023 073 123 173 024 074 124 174 025 075 125 175 026 076 126 176 027 077 127 177 028 078 128 178 0
27. Normal mode is the standard mode of operation In this mode the ADT UDACT monitors host FACP status power input E A 485 communications and telephone line voltage The four character 7 segment display is normally off and does not annunciate events that are being transmitted The display will only annunciate ADT UDACT trouble conditions in the normal mode The ADT UDACT transmits zone point and system status reports to a Central Station via the public switched telephone network Two supervised telephone line connections are made to interface the ADT UDACT to the telephone lines The ADT UDACT supervises both telephone lines for proper voltage A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble When a fault is detected the 4 character display will show either no 1 or no 2 depending upon which telephone line has the fault no 1 Primary Line no 2 Secondary Line and the trouble condition will be reported to the Central Station over the remaining good phone line The ADT UDACT comes with line seizure capability provided for both the primary and secondary telephone line interfaces Any time that the ADT UDACT needs to make a call to the Central Station line seizure will disconnect any local premises phones sharing the same telephone line All transmission to the Central Station will be sent over the Primary phone line In the event of noisy phone lines transmissions w
28. One Town Center Road J s itv Services Boca Raton FL 33431 A ecurity Services Inc Phone 561 988 3600 FAX 561 988 3675 The ADT UDACT Universal Digital Alarm Communicator Transmitter O 0000000 POWER COMM FAIL ElA 485 KISS OFF Gu HET nos DO ajajaja DO ODE udactnot wmf Product Information Installation Programming and Operation Manual Document 50934 5 15 00 Rev B P N 50934 EC 402 N B 2000 ADT Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors heat detectors manual pull stations audible warn ing devices and a fire alarm control with remote notification capability can provide early warning of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire The Manufacturer recommends that smoke and or heat detec tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 NFPA 72 manufacturer s recommendations State and local codes and the recommendations contained in the Guide for Proper Use of System Smoke Detectors which is made available at no charge to all installing dealers A study by the Federal Emer gency Management Agency an agency of the United States government indicated that smoke detec
29. Physical location is critical to the point number reported 50 Document 50934 RevB 5 15 00 PN 50934 B Appendix C Point Assignments ADT MNNA Note Use the following charts to carefully identify the function of each point in the system Take special precaution with any supervisory points in the system For the ADT UDACT to report a supervisory point to the central station both the FACP and the ADT UDACT must have the point programmed as supervisory Failure to program the panel or ADT UDACT correctly will result in a fire alarm signal being transmitted to the central station All points greater than 568 can only be transmitted as fire alarm points Use Type Mode refer to Section 4 2 Type Mode to match the function of points in the system for proper reporting PointNo Point Function PointNo Point Function PointNo Point Function Eos Bos Pole q ol a o alal a lala alo S oO l N ao al a BO es A q N N oj IN WD oi Gol oi wo WwW W O vj N Jl oi oa E Document 50934 RevB 5 15 00 PN 50934 B 51 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 a ol Oo Ol o al 2 Appendix C continued Point Assignments ADT MNNA Point Function Point Function Point Fanevon romo Point Funcion DO fe 0 fe Do fts o fm DO fa fe Do fe fe
30. Restore 2nd digit TS System Trouble 1st digit TS2 System Trouble 2nd digit RTS System Trouble Restore 1st digit RTS2 System Trouble Restore 2nd digit L Low Battery 1st digit L2 Low Battery 2nd digit RL Low Battery Restore 1st digit RL2 Low Battery Restore 2nd digit P AC Loss 1st digit P2 AC Loss 2nd digit RP AC Loss Restore 1st digit RP2 AC Loss Restore 2nd digit V Supervisory Condition 1st digit V2 Supervisory Condition 2nd digit RV Supervisory Condition Restore 1st digit RV2 Supervisory Condition Restore 2nd digit A Test Report 1st digit X2 Test Report 2nd digit XA Abnormal Test Report 1st digit XA2 Abnormal Test Report 2nd digit Table 5 2 Letter Code Definitions Refer to Table 5 1 Document 50934 RevB 5 15 00 PN 50934 B 39 40 The reporting structure for the Ademco Contact ID format is as follows SSSS 18 QXYZ GG CCC where SSSS Four digit Subscriber ID addresses 17 20 and 43 46 18 Identifies transmission as Contact ID to the receiver at the Central Station Q Event Qualifier 1 New Event 2 New Restore XYZ Event code shown in Tables 3 4 and 3 7 GG Group number or Loop number CCC Device or Zone number For general reports alarm trouble and supervisory the GG and CCC fields are transmitted as 00 and 000 unless changes to addresses 64 65 and 66 68 are made 64 65 Loop number GG factory defa
31. Systems Protected Premises Unit NFPA SE e Automatic Fire Detectors e Installation Maintenance and Use of Notification Appliances for Fire Alarm Systems Inspection Testing and Maintenance for Fire Alarm Systems UL Underwriters Laboratories Documents UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors Single and Multiple Station UL 228 Door Closers Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances Other NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Relevant ADT Manuals Unimode 2020 1010 manual Document 51167 Unimode 300 400 Programming Document 50708 Unimode 300 400 Operating Document 50709 Unimode 300 400 Installation Document 50710 AFM Annunciator Document 15048 ADT ACS Annunciator Document 51353 ADT LCD 80 Document 51354 ADT MNNA Document 50929 6 Document 50934 RevB 5 15 00 PN 50934 B 1 0 Product Description The Universal Digit
32. Zone Point Fault Code 0 76 Primary Low Battery Fault Code F 77 Primary Telco Primary Line Fault Code F 78 Primary Telco Secondary Line Fault Code F 79 Primary NAC Fault Code F 80 Primary Comm Trouble Primary Code F 81 Primary Comm Trouble Secondary Code F 82 Primary 485 Comm Trouble Code F 83 Primary System Off Normal Code F 84 Primary ADT UDACT Off Normal Code F 85 Primary General Alarm Restore Code E 86 Primary Zone Point Alarm Restore Code 0 87 Primary General Supervisory Restore Code E 88 Primary Zone Point Supervisory Restore Code 0 89 Primary General Fault Restore Code E 90 Primary AC Fault Restore Code E 91 Primary Zone Point Fault Restore Code 0 92 Primary Low Battery Fault Restore Code E 93 Primary Telco Primary Line Fault Restore Code E 94 Primary Telco Secondary Line Fault Restore Code E 95 Primary NAC Fault Restore Code E 96 Primary Comm Trouble Primary Number Restore Code E 97 Primary Comm Trouble Secondary Number Restore Code E 98 Primary 485 Comm Trouble Restore Code E 99 Primary System Off Normal Restore Code E 100 Primary ADT UDACT Off Normal Restore Code E 101 Primary System 24 Hour Test 9 102 Primary System 24 Hour Test w active event F 103 Primary Manual Test 9 Note Zero entries prevent the transmission of the report to the Central Station Table 3 2 Event Codes Primary Number Document 50934 RevB 5 15 00 PN 50934 B 4 2 Standard and 4 2 Express Formats
33. al Alarm Communicator Transmitter ADT UDACT may be used with a variety of ADT control panels refer to Appendices The ADT UDACT transmits system status to UL Listed Central Station Receivers via the public switched telephone network The ADT UDACT which is compact in size mounts internally in some panels or externally in a separate enclosure EIA 485 annunciator communications bus and 24 volt nominal connections are required 1 1 Product Features e Dual telephone lines e Dual telephone line voltage detect e Surface mount technology e Compact in size 6 75 x 4 25 e Built in programmer e Built in four character red 7 segment LED display e Manual test report function e Manual master transmission clear function e Mounts in separate ADT ABS 8RF or ADT UBS 1 enclosure e Communicates vital system status including Independent zone point alarm Independent zone point trouble Independent zone point supervisory AC mains power loss programmable Low battery and earth fault System off normal 12 or 24 hour test signal Abnormal test signal per new UL requirements Annunciation of ADT UDACT troubles including loss of phone lines communication failure with either Central Station total communication failure e Troubleshoot mode converts keypad to DTMF touchpad e Individual LEDs for Power EIA 485 loss Manual Test Kissoff Comm Fail Primary Line Seize Secondary Line Seize RE ee AREAS Primary Phone Line S
34. ation on the starting and ending addresses refer to the host FACP Technical Manual Table 3 1 Start and End Monitoring Addresses ADT UDACT Communication Selection 56 Leaving address 56 at 0 disables communications to the Central Station s Enter 1 for zone reporting receive only 2 for zone reporting receive transmit 3 for point reporting receive only or 4 for point reporting receive transmit See Type Mode Section 4 2 for additional information on detailed reporting Note Use receive only selection when using remote annunciators Be certain to set one of the annunciators for receive transmit for EIA 485 communications bus supervision Use the receive transmit entry when annunciators are not installed or when the ADT UDACT receive transmit function is to be used to supervise the EIA 485 communication bus For more information on the receive transmit function refer to annunciator manuals Backup Reporting 57 Leaving address 57 at 0 means that reports will be transmitted to the secondary phone number only if attempts to communicate to the primary phone number are unsuccessful Programming a 1 causes all reports to be transmitted to the secondary phone number Touchtone Rotary Select 58 A 0 programmed in this address by the factory triggers Touchtone dialing over both phone lines Select 1 for rotary dialing Make Break Ratio 59 Use this address only if you have chosen 1 for address 58 The make break ratio
35. cific type of device point used or function of a zone Type Mode is also used to disable the alarm report for any zone point in the system The feature which disables the zone point alarm report must be used for zones points programmed into the host FACP as remote silence reset drill or acknowledge switches Note Unimode2020 1010 and ADT MNNA applications restrict Type Mode programming to a maximum of 568 points All remaining points above 568 will report as fire alarm points only Document 50934 RevB 5 15 00 PN 50934 B 1 9 6 Clear Function When the clear function is activated it causes the ADT UDACT to immediately stop transmissions hang up from the telephone network clear out any messages that were waiting for transmission and reset 1 9 7 Manual Test Function The manual test function allows for a test report message to be sent to both Central Stations upon activation Document 50934 RevB 5 15 00 PN 50934 B 13 2 1 General 2 2 Output Circuits 14 2 0 Installation and Wiring Mounting Options For information on mounting the ADT UDACT in a specific fire alarm control panel refer to the appropriate Appendix Telephone Circuits Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 Primary and PH2 Secondary Telephone line control command is possible via double line seizure as well as usage of an RJ31X style interconnection RJ31X jacks must be ordered
36. cnnnncnnnn nan arrancar cnn nn cannnnanncnnns 4 1 4 Key Report Descriptions ooococnonccnnnsoncnonccnnnnnnonnnnnccnnncennn nro 4 2 Type Mode ee gege ete coals EERSTEN 4 2 1 Disabling of Zones or Points AAA 4 2 2 Zone or Point Supervisory ere ee tir i AoA ee cent 4 3 Troubleshoot Mode i e ieee a hei cts ern A ein eee ST Figure 4 2 Handset Speaker Connection cccceeceeeeeeeeeeeeeneeeeeeeeeneeeeseeeseaeeseeeseeereaes 4 4 Camp TestiMode iisipan nee a ee ee Document 50934 RevB 5 15 00 PN 50934 B 11 11 12 12 12 12 12 13 13 32 Table of Contents 5 0 Reporting Formats sssrinin aenak aaaea aaaea aaan Ea aaa Naana dadan 38 Table 5 1 Data Reporting Structure re cereecerrracaraaeeraraananaa 38 Table 5 2 Letter Code Definitions errar aeaeeerea caraca 39 Table 5 3 Ademco Contact ID Reporting Structure ooooconncccinnccconcccnonncnnnnanancncnnnnnnancnnas 40 6 0 Compatible Receivers cucso stees REESEN deeg 42 Table 6 1 Compatible UL Listed Receivers erra 42 7 0 Programming Reference Sheet ccssccseeeeeeeseeeseeeeeeeeeeseeeeseeeeseeeaseeeeseeeaseeeseeeeaeeeeeeeeeas 43 Appendix A Zone Assignments Unimode 300 400 00 pes es quaa isentas tac ia ege 47 Appendix B Point Assignments Unimode 300 400 ss ss cessseeeeessaerensanena 48 Appendix C Point Assignments ADT MNNA csseeseeeeeseeeeeneeeeseeeseeesaseeens
37. communication 1 for zone reporting receive only communication 2 for zone reporting receive transmit communication 3 for point reporting receive only or 4 for point reporting receive transmit Backup Reporting Enter 0 to have secondary phone number act as backup only 1 to have secondary phone number receive all reports and messages along with primary phone number a q Touchtone Rotary Select Enter 0 for touchtone dialing 1 for rotary dialing a o Make Break Ratio If rotary dialing is selected in Address 58 Enter 0 for a 67 73 make break ratio 1 for a 62 38 make break ratio a o Leave default of 0 o E Leave default of 0 o EE EE 1 o N AC Loss Reporting Delay Enter 0 for no time delay after AC loss 1 for 6 hour delay 2 for 7 hour delay 3 for 8 hour delay 4 for 9 hour delay 5 for 10 hour delay 6 for 11 hour delay 7 for 15 hour delay 8 for 16 hour delay 9 for 17 hour delay A for 18 hour delay B for 19 hour delay C for 20 hour delay D for 21 hour delay E for 22 hour delay or F for 23 hour delay Host Panel ID Enter d for Unimode 2020 1010 and ADT MNNA 8 for Unimode 300 400 all other entries are invalid o 7 E ae Loop Number Factory set to 00 Valid entries are 00 through 97 be LL LL Device Zone Number for General Reports Factory set to 000 Valid entries are 000 through 999 Document 50934 RevB 5 15 00 PN 50934 B 43
38. d Monitoring Address se ADT UDACT Communication Selection 0 for ADT UDACT Communication disabled Backup Reporting 0 for backup ss Touchtone Rotary Select 0 for Touchtone Make Break Ratio 0 for 67 33 make break ratio 59 so Leave default of zero 6 Leave default of zero 62 AC Loss reporting delay 1 for 6 hour time delay Host PANEL ID 8 for Unimode 300 400 63 9 Loop Number For Ademco Contact ID only Loop number 00 o a BBBEBEBEBEBEEBEBESL E A o Lo Device Zone Number for general reports For Ademco Contact ID only Device number 0001 Document 50934 RevB 5 15 00 PN 50934 B 45 Programming Reference Sheet Factory Default ul Di lo o 81 Di o 91 El Di EL el lo a EL SL EL AL EL SL EL CL EL DL EL EL EL EL EL EL EL EL EL D OI HD EL ER OI HP EL ER EL is HR HR EL ig El A EL ER EI a El o El El El El El E E al SI el DL el ER DL DL a a e DL 0 OI EI DOE E a E e d 147 148 149 150 151 152 153 154 155 156 157 158 159 cl E Dl EE E lol 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 el EL AL EL ER EL ER EL ER EL EL EL EL El EL E le le le DO leal e 199 200 201 202 203 204 205 206 207 208 Document 50934 RevB 5 15 00 PN 50934 B 46 Appendix A Zone Assignments Unimode 300 400 Zone No Zoe Function zone no Zoe Function Zone
39. dialed on the farthest right display position Continue to press the phone numbers to be dialed Successive depressions of the ENTER STORE key hangs up and picks up the phone places the phone on or off the hook The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing and then following the same procedure used for the primary phone line A handset may be temporarily connected across transformer T1 as indicated in Figure 4 2 The handset when connected across T1 may be used only as an amplifier speaker or telephone with the ADT UDACT used for number dialing Document 50934 RevB 5 15 00 PN 50934 B Both Primary and Secondary Lines Oo PRIMARY ACTIVE DU m Es GND MO RS ge SECONDARY rs E ACTIVE SHIELD O ns MO ns RY UNIVERSAL DIGITAL ALARM COMMUNICATOR TRANSMITTER TBt O B UDACTNOT WMF Figure 4 2 Handset Speaker Connection 4 4 Lamp Test Mode To perform a Lamp Test press MODE then 5267 followed by ENTER STORE This will test all system LEDs The LEDs will stay on for five seconds then the ADT UDACT will return to normal mode sw 5267 spells LAMP on a Touch Tone phone Document 50934 RevB 5 15 00 PN 50934 B 37 5 0 Reporting Formats Table 5 1 shows the data reporting structure for each of the pulsed formats as well as the Ademco Express formats Ademco Express formats allow a typical data messag
40. e to be transmitted to the Central Station in under 5 seconds Pulsed formats typically require 15 to 20 seconds in comparison Table 5 2 defines each letter code used in Table 5 1 Table 5 3 describes the data reporting structure used for Ademco Contact ID format Do not select any of the pulsed or Ademco Express Formats if identification of the specific zone or point is desired Use Ademco Contact ID for specific zone or point identification Format Format 0 2 4 6 8 1 A Report 3 1 4 1 Standard 4 2 Standard 4 1 Express 4 2 Express ia ns SES SE Zone Trouble SSS S RTZ SSSS TZTZ2 Zone Open Zone Trouble Restore SSS S RTZ SSSS RTZRTZ2 System Trouble SSS S TS SSSS TSTS2 System Trouble Restore SSS S RTS SSSS RTSRTS2 Low Battery Restore SSS S RL SSSS RLRL2 AC Loss Restore SSS S RP SSSS RPRP2 Supervisory Condition SSS S V SSSS VV2 Supervisory Condition SSS S RV SSSS RVRV2 Restore Abnormal Test Report SSS S XA SSSS XAXA2 Table 5 1 Data Reporting Structure Refer to Table 5 2 for an explanation of each letter code in Table 5 1 Refer to Table 6 1 for a list of compatible receivers Document 50934 RevB 5 15 00 PN 50934 B Where SSS Or SSSS Subscriber ID A Alarm 1st digit A2 Alarm 2nd digit RA Alarm Restore 1st digit RA2 Alarm Restore 2nd digit TZ Zone Trouble 1st digit TZ2 Zone Trouble 2nd digit RTZ Zone Trouble Restore 1st digit RTZ2 Zone Trouble
41. e cord must be used with this equipment This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant 1 9 1 Normal Mode Normal mode is the standard mode of operation In this mode the ADT UDACT monitors host FACP status as well as monitoring telephone line voltage The ADT UDACT reports system status information to UL listed Central Stations Information transmitted includes general alarm trouble and supervisory It also transmits either the number of zones or points activated or the specific point s activated depending upon the compatible panel programming selections and transmission format selection Specific system trouble conditions and specific ADT UDACT troubles are also transmitted 1 9 2 Program Mode Program mode is used to program the ADT UDACT While the ADT UDACT is in the program mode it cannot receive host FACP status information See Section 3 0 for complete programming instructions 1 9 3 Lamp Test Mode This mode turns on all segments of the 4 character display plus all LEDs on the ADT UDACT 1 9 4 Troubleshoot Mode Troubleshoot mode may be used for testing the telephone line wiring Connection from the ADT UDACT s modular jacks through RJ31X jacks and into the telephone network may be easily checked In this mode the keypad acts similar to a telephone touchpad 1 9 5 Type Mode Type Mode is used to define the spe
42. econdary i Phone Line Modular Cable Ea P N MCBL 7 HIELO UNIVERSAL DIGIIAL ALAHM COMM UNICAIOR IRANSMII LER T EARTH Man e com e FAIL o Es SECONDARY ACTIVE POWER COMM FAIL ElA 485 KISS OFF CLEAR TEST MODE e Open collector relay driver for Total Communication Failure or ADT UDACT trouble e Real Time Clock e Extensive transient protection e Simple EIA 485 interface to host panel Document 50934 RevB 5 15 00 PN 50934 B udactfea wmf 24VDC Power in use power limited source EIA 485 Connector use power limited source DO NOT USE Primary Phone Line Secondary Phone Line Modular Cables a P N MCBL 7 Order Separately o e O PH1 PH2 EARTH O monem B GND FAIL 24V O SECONDARY o UNIVERSAL DIGITAL ALAHM COMM UNICAIOR RANSMII IER POWER COMM FAIL KISS OFF ElA 485 Frai Er vos ODDS i IODO faelee ee Oe TEST CONNECTOR J5 DEE Figure 1 1 ADT UDACT Assembly Document 50934 RevB 5 15 00 PN 50934 B udactfea wmf Comm Fail Output power limited 24 VDC power limited 1 2 1 3 1 4 Controls and Indicators Compatible Panels Digital Communicator Front Panel S
43. ection Once location 56 is changed from 0 and a valid phone number is entered transmission of the ADT UDACT off Normal report will occur Document 50934 RevB 5 15 00 PN 50934 B 3 2 Switch Functions 3 3 Programming Options Throughout programming mode the first three locations on the left of the display represent the memory address which can range from 00 to 208 Alpha characters are not used The last location farthest right represents the contents of the memory address The first address displayed is shown below 00 F address data The Function of each switch in program mode is shown below No function in this mode Address entry a keys are O to 9 CIEE Data entry keys B gt E 5 Co CE Co Em Figure 3 1 ADT UDACT Keypad Select operating mode Increment memory address Decrement memory address Once First memory address Twice type any address UDACTKEY WMF Save data go to next address Primary phone number 00 15 The first sixteen addresses 00 15 are factory set to F from 00 F to 15 F Programming is typically done as follows If your phone is 484 7161 type 4 the display will read 00 4 press ENTER STORE to save the entry to memory and increment to the next address 01 F Enter the remaining numbers in their respective addresses as shown below 4 8 4 7 1 6 1 F F F F F F F F F 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Valid entries for both the
44. eeenseeeaseeeeneeeeas 51 Appendix D Unimode 2020 1010 ccccnncccnnnccconnnicccnnnancnnnnac nn nn 56 Figure D 1 ADTUBST Foco editada 56 Figure D 2 ADT UDACT Mounting in CHS 4 rrenan 56 Figure D 3 ElA 485 Connection to Panel Mounted ADT UDACT 57 Figure D 4 ElA 485 Connection to Remote ADT UDACT inccccinccccnnccconancnonnnnnancnnnnaninnnos 58 Appendix E Unimode 300 400 oonnccconcccnnnncccnoniccnnnnccncnnccnnannc rn cren 59 Figure E 1 ADT ABSBRE geed ina donas 59 Figure E 2 ADT CPU 400 Module errar arraia 59 Figure E 3 Unimode 400 External ADT UDACT Mounting in ADT ABSBRF 60 AppendtcE APDTMNNA tege Sege ae Seege SES EECH 62 Appendix G Annunciators ccceeeeeeeeeeeeeeeeeeenseeeeeeenseeeneeeenaeasneeeaeeeeaseeeseasaeeeesnesseeeseeesaeeaeneeetaes 65 Document 50934 RevB 5 15 00 PN 50934 B 5 This digital communicator has been designed to comply with standards set forth by the following regulatory agencies e Underwriters Laboratories Standard UL 864 e NFPA Standards 72 National Fire Alarm Code for Local Remote Station and Central Station Fire Alarm Systems Before proceeding the installer should be familiar with the following documents NFPA Standards NFPA 72 National Fire Alarm Code Central Station Fire Alarm Systems Automatic Manual and Waterflow Protected Premises Unit Local Automatic Manual Waterflow and Sprinkler Supervisory Fire Alarm Systems e e Proprietary Fire Alarm
45. een the control panel and ADT UDACT using twisted shielded pair wire Power should be wired from the control panel s main power supply 24 VDC nominal filtered nonresettable output to TB1 on the ADT UDACT Note The ADT UDACT does not support voice and burglar options when used with the ADT MNNA Refer to the ADT MNNA Manual for additional restrictions ADT UDACT mounting in an ADT MNNA Remove all power from the ADT MNNA by disconnecting AC and batteries Install the three supplied nylon support posts for the top and bottom left of the ADT UDACT one aluminum nylon and one aluminum standoff in the CHS 4 chassis slot in which the ADT UDACT is to be installed Position the ADT UDACT on the standoffs and secure on aluminum standoff with a 46 32 screw Connect the communication line between the EIA 485 terminal block on the ADT MNNA and TB 1 terminals 3 and 4 on the ADT UDACT being certain to observe polarity refer to Figure F 1 Recommended wire is 12 AWG to 18 AWG twisted pair If no other devices are connected to the EIA 485 install a 120 ohm EOL resistor across ADT UDACT TB 1 terminals 3 and 4 Connect the supplied Ground Strap from the ADT UDACT Earth Ground terminal on TB3 to the CHS 4 chassis Connect 24 VDC filtered power to TB1 terminals 1 and 2 on the ADT UDACT 62 Document 50934 RevB 5 15 00 PN 50934 B TB1 Terminal 3 ElA 485 77 II Dan Q L 200 LILI D D DOF
46. eeneeeens PEETI e E E ENE EE E EA T A O E EEE KE tee TEE Figure 2 1 Wiring Phone Jacks ooooniococonnccccnnnicccniorcennnnnoncnnnacrnn narran nera Figure 2 2 Relay Driver Connections ereta carnes Figure 2 3 Monitoring for ADT UDACT Trouble a 2 3 UL Power limited Wiring Requirements AAA Figure 2 4 Typical Wiring Diagram for UL Power limited Requirements 3 0 Programming Instructions ss ossos rsssceressaceresaseeneasacenenascennaaaneneaaacanasaaentsannas 3 1 Entering Program Mode us scccsccccieesgacdsgacecetscscesaaiadensacectaptageeeeseeddasuacesndecsennagdcansecSeeenacnazes Ee NS ue el Figure 3 1 ADT UDACT Keypad AE 3 3 Programming K le EE Table 3 1 Start and End Monitoring Addresses A Table 3 2 Event Codes Primary Number see ceeeeeeeeeeaeaneneanea Table 3 3 Event Codes Primary Number ese eeeeeeeeaeeaeaneneeae Table 3 4 Ademco Contact ID Primary Number essere Table 3 5 Event Codes Secondary Number rereeeeeeerereereenea Table 3 6 Event Codes Secondary Number ireeererseaeereenea Table 3 7 Ademco Contact ID Secondary Number 4 0 Operating Instructions cccseeeeeeeeteeeeeeeeeneeneeeenseeeneeeasaeeseaeeaseeeaseeeseeesaeeesseeeeseeeseeeeaseeeaenenaes AT Noma Oe AAV EE aa 00 Y O Figure 4 1 ADT UDACT Phone Connectors and LEDS 0 esceeeeeeeeeeeeeeeeeeeeeeeteeeeeee 4 1 3 Normal Mode Operation oooocccccnnconoccccooccnnnccnnnnconnn
47. energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules which is designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause interference in which case the user will be required to correct the interference at his own expense Adherence to the following will aid in problem free installation with long term reliability Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to light ning induced transients Although no system is completely immune from lightning transients and interferences proper grounding will reduce susceptibility Overhead or outside aerial wiring is not recommended due to an increased sus ceptibility to nearby lightning strikes Consult with the Techni cal Services Department if any problems are anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that
48. er any circumstance since a ground fault may result 4 Conduit is recommended for external wire runs Consult local building codes 5 Connect Ground Strap supplied with ADT ABS8RF enclosure from Earth Ground terminal on ADT UDACT to a solid building earth ground Conduit alone will not provide a reliable earth ground 6 ADT UDACT may be located up to 6000 feet away from the host control panel 7 Refer to Specifications for power requirements Figure D 4 EIA 485 Connection to Remote ADT UDACT Document 50934 RevB 5 15 00 PN 50934 B 58 Appendix E Unimode 300 400 The ADT UDACT is capable of reporting a maximum of 99 zones or 448 points when used with the Unimode 400 The ADT UDACT must be mounted remotely in an ADT ABS8RF or ADT UBS 1 enclosure up to 6000 feet away from the control panel All power must be removed from the Control Panel before making any connections to prevent circuit damage The EIA 485 serial interface is connected between the Control Panel and ADT UDACT using twisted shielded pair wire Power should be wired from the MPS 400 24 VDC nonresettable output to TB1 on the ADT UDACT Remove all power from the control panel by disconnecting AC and batteries Since the Unimode 400 cannot accommodate the ADT UDACT in the control panel enclosure the ADT UDACT must be mounted remotely using an ADT ABS8RF enclosure Ferrite cores are recommended for this application Refer to Figure E 3 and the accompanying notes for
49. grammed for the Secondary phone number event codes Enter a 000 for the data setting to disable the report Address Description Setting Group 6 Sensor No 139 141 Secondary General Alarm Code 110 00 000 142 144 Secondary Zone Point Alarm Code 1104 00 Note 145 147 Secondary General Supervisory Code 200 00 000 2 148 150 Secondary Zone Point Supervisory Code 200 00 Note 151 153 Secondary General Fault Code 300 00 154 156 Secondary AC Fault Code 301 00 157 159 Secondary Zone Point Fault Code 380 00 Note 160 162 Secondary Low Battery Fault Code 302 00 163 165 Secondary Telco Primary Line Fault Code 351 00 166 168 Secondary Telco Secondary Line Fault Code 352 00 169 171 Secondary NAC Fault Code 321 00 172 174 Secondary Comm Trouble Primary Code 354 00 175 177 Secondary Comm Trouble Secondary Code 354 00 178 180 Secondary 485 Comm Trouble Code 300 00 181 183 Secondary System Off Normal Code 308 00 184 186 Secondary ADT UDACT Off Normal Code 350 00 187 189 Secondary System 24 Hour Test 602 00 190 192 Secondary System 24 Hour Test w active event 608 00 193 195 Secondary Manual Test Message 601 00 Notes 1 Note Zero entries prevent the transmission of the report to the Central Station 2 Refer to Contact ID program locations 64 68 3 The identification of the zone device number is automatically transmitted by the ADT UDACT and is added to the mai
50. hree times in rapid succession the ADT UDACT will transmit a test message to both Central Stations The message reported is the same as the automatic test message for all formats except Ademco Contact ID Pressing the Mode Key followed by a valid 4 digit numerical code and ENTER STORE selects one of the four modes of operation e To enter normal mode from any other mode press MODE then 6676 ENTER STORE 6676 spells NORM on a Touch Tone phone Document 50934 RevB 5 15 00 PN 50934 B 1st EVENT DOWN ARROW UP ARROW ENTER STORE This key along with the Up Arrow and Down Arrow keys are used to display ADT UDACT fault conditions Press the 1st Event key at any time to display the first event that occurred Use the Down Arrow key to view other ADT UDACT fault events older that have occurred and are active not cleared yet Use the Up Arrow key to view other ADT UDACT fault events newer that have occurred and are active not cleared yet See individual mode descriptions in other sections 4 1 2 Displays Four 7 segment red LED characters provide visual annunciation of ADT UDACT trouble conditions A list of messages that may appear on the display in normal mode 1s shown below PH 1 Primary Number Communication Fault PH 2 Secondary Number Communication Fault no 1 Primary Phone Line Fault no 2 Secondary Phone Line Fault Individual LEDs are provided for EIA 485 A yellow LED that turns on steady when a fault
51. ial entry will display 01 0 The characters to the left identify the zone or point number In this example 01 identifies zone 01 or point address 01 The character to the right O in this example identifies the type of zone or point as follows O Zone or point defined as fire alarm 1 Disable zone or point report 2 Zone or point defined as supervisory 3 Zone or point defined as pull station 4 Zone or point defined as heat detector 5 Zone or point defined as waterflow 6 Zone or point defined as duct detector 7 Zone or point defined as flame sensor 8 Zone or point defined as smoke zone Use for group of addressable or conventional smoke detectors Also use for addressable monitor modules monitoring conventional smoke detectors 9 Zone or point defined as burglary Unimode 300 400 and ADT MNNA A Zone or point defined as 24 hour non burglary B Zone or point defined as high temperature C Zone or point defined as low temperature D Zone or point defined as low water pressure E Zone or point defined as low water level F Zone or point defined as pump failure Factory default is all zones or points set to 0 for fire alarm The 0 setting for zone reporting allows the mixing of types of devices on a single zone To change the type definition of the zone or point from the factory default of O select 2 to F corresponding to the type of device s used do not mix device types for these settings or select
52. idnight Secondary Number 24 12 Hour Test Time 51 The test message sent to the Secondary phone number may be sent every 12 or 24 hours If the message is to be sent every 24 hours leave the factory default entry of zero If a 12 hour test report time is needed enter 1 12 hours Use the Start and End Monitoring Address programming locations to set the reporting range of the ADT UDACT Start Monitoring Address 52 53 is programmed to indicate the first group of zones or points to be monitored and reported to the Central Station Valid entries are 41 through 19 for the Unimode 300 400 and 01 through 32 for the Unimode 2020 1010 and ADT MNNA The factory default setting is 01 See Table 3 1 End Monitoring Address 54 55 is programmed to indicate the last group of zones or points to be monitored and reported to the Central Station Valid entries are 11 through 19 for the Unimode 300 400 and 01 through 32 for the Unimode 2020 1010 and ADT MNNA Factory default setting is 02 Document 50934 RevB 5 15 00 PN 50934 B 21 22 Zone Reporting Factory Default Point Reporting START END START END Addr 52 53 Addr 54 55 Addr 52 53 Addr 54 55 y f Unimode 2020 1010 Unimode 400 11 12 ADT MNNA 012 322 1 Reports status of up to 99 zones Unimode 400 118 19 2 Reports status of up to 2 040 points 3 Reports status of up to 384 points Note For additional inform
53. ill be sent over the backup Secondary phone line Document 50934 RevB 5 15 00 PN 50934 B Two phone numbers must be programmed the Primary phone number and the Secondary phone number All system reports will be transmitted to the primary phone number Reports will automatically be sent to the secondary phone number if attempts to transmit to the primary phone number are unsuccessful If 10 total attempts to communicate are unsuccessful the Communicator Failure output will be turned on TB3 terminal 2 Note that as an option all reports may also be sent to the secondary phone number Refer to Section 3 0 Programming Instructions The ADT UDACT meets NFPA 72 for Remote Station Protective Signaling Service and Central Station Signaling Service reporting requirements for a the type of signal b condition and c location of the reporting premises Since higher priority events take precedence over lower priority events the ADT UDACT will transmit higher priority events before sending the lower priority events Priorities are as follows Event Activations 1 General Alarm 2 Zone Point Alarm EN 3 General Supervisory 4 Zone Point Supervisory N 5 General System Trouble 6 AC Power Loss 7 Zone Point Trouble EN 8 Low Battery 9 Telco Primary Line Fault 10 Telco Secondary Line Fault 11 NAC Fault Code 12 Communication Trouble Primary Number 13 Communication Trouble Secondary Number 14 EIA 485 Communication Bus T
54. ilure occurs when the maximum number of attempts to reach both central stations has taken place or when both phone lines are disconnected ADT UDACT trouble conditions include loss of telephone line voltage to the primary and or secondary phone lines communication failure to the primary or secondary central stations total communication failure entry into program type and troubleshoot modes Wiring from the ADT UDACT terminal TB3 to the relay must be in the same room no more than 20 feet in length and enclosed in conduit Wiring from the relay output contacts must remain in the same room as the ADT UDACT When the ADT UDACT is programmed for Receive Only typically this occurs when annunciators are also used and are set for Receive Transmit the relay output 1s used to provide a ADT UDACT trouble input to the host control panel For Unimode 2020 1010 applications use a monitor module to supervise the relay closure Refer to Figure 2 3 Program the custom label field to read UDACT Trouble When the ADT UDACT is programmed for Receive Transmit EIA 485 supervision and ADT UDACT trouble status are automatically handled by the host control panel The relay output may however be used for ADT UDACT communications failure if desired Relay Energized LED TB3 ON NO Earth Gnd O i C e S DPDT Contacts 24 VDC 18 24 NC 10 Amps 115 NO 115 VAC 230 C eg NC K All wiring to relay must be in the same
55. installed on either SLC Loop and the device is in alarm or trouble the ADT UDACT will transmit the general alarm and general trouble reports if enabled Following are module locations and their corresponding addresses in various cabinets ADT CAB B3 ADT CAB C3 ADT CAB 400AA AFP 400 CPU 417 424 425 432 AFP 400 CPU AFP 400 CPU 401 408 433 440 441 448 449 456 457 464 401 408 409 416 417 424 425 432 433 440 441 448 449 456 457 464 Document 50934 RevB 5 15 00 PN 50934 B 61 Appendix F ADT MNNA The ADT UDACT is capable of reporting up to 2 040 points when used with the ADT MNNA The first 568 points can be programmed using the Type Mode feature refer to Section 4 2 All points greater than 568 can be transmitted only as fire alarm points For the ADT UDACT to report a supervisory point to the central station both the FACP and the ADT UDACT must have the point programmed as supervisory Failure to program the panel or ADT UDACT correctly will result in a fire alarm signal being transmitted to the central station The ADT UDACT may be mounted in the ADT MNNA control panel using the CHS 4 chassis or remotely in an ADT ABS8RF or ADT UBS 1 enclosure up to 6 000 feet away from the control panel All power must be removed from the control panel before making any connections to prevent circuit damage The EIA 485 serial interface is connected betw
56. is factory set to 0 which is 67 33 but may be changed to 1 which is a 62 38 ratio Address 60 Leave default of 0 Address 61 Leave default of 0 AC Loss Reporting Delay 62 1 is factory default which causes a 6 hour time delay for AC loss reporting Valid entries are O to 9 and A to F corresponding to the following reporting delay times 1 6 hour 2 7 hours 3 8 hours 4 9 hours 5 10 hours 6 11 hours 7 15 hours 8 16 hours 9 17 hours A 18 hours B 19 hours C 20 hours D 21 hours E 22 hours and F 23 hours U entry causes immediate reporting of AC loss Host Panel ID 63 Enter one of the following digits corresponding to the Control Panel in which the ADT UDACT is installed A correct entry is essential for proper operation 0 Do not use 3 Do not use 6 Do not use 1 Do not use 4 Do not use 7 Unimode 2020 1010 ADT MNNA 2 Do not use 5 Do not use 8 Unimode 300 400 9 Do not use Document 50934 RevB 5 15 00 PN 50934 B Loop Number 64 65 For Contact ID format only Factory default is 00 Maximum value is 97 Refer to Section 5 0 for additional information Device Zone Number 66 68 For Contact ID format only These entries apply to the general reports only i e general alarm general trouble general supervisory Factory default is 000 Maximum value is 999 Refer to Section 5 0 for additional information Note For the Contact ID
57. lephone company Manufacturer Notifier Fire Systems One Fire Lite Place Northford CT 06472 1653 Product Model Number ADT UDACT FCC Registration Number IW6USA 20723 AL E Ringer Equivalence 0 6B 1 8 3 Telephone Company Rights and Warnings The telephone company under certain circumstances may temporarily discontinue services and or make changes in its facilities services equipment or procedures which may affect the operation of this control panel However the telephone company is required to give advance notice of such changes or interruptions Document 50934 RevB 5 15 00 PN 50934 B 11 1 9 12 Modes and Special Functions If the control panel causes harm to the telephone network the telephone company reserves the right to temporarily discontinue service Advance notification will be provided except in cases when advance notice is not practical In such cases notification will be provided as soon as possible The opportunity will be given to correct any problems and to file a complaint DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE GROUND START OR PARTY LINE SERVICES When the control panel activates premise phones will be disconnected Two separate phone lines are required Do not connect both telephone interfaces to the same telephone line The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises An FCC compliant telephon
58. ly as fire alarm points For the ADT UDACT to report a supervisory point to the central station both the FACP and the ADT UDACT must have the point programmed as supervisory Failure to program the panel or ADT UDACT correctly will result in a fire alarm signal being transmitted to the central station The ADT UDACT may be mounted in the Unimode 2020 1010 control panel using the CHS 4 chassis or remotely in an ADT ABS 8RF or ADT UBS 1F enclosure up to 6000 feet away from the control panel All power must be removed from the control panel before making any connections to prevent circuit damage The EIA 485 serial interface is connected between the control panel and ADT UDACT using twisted shielded pair wire Power should be wired from the control panel s main power supply 24 VDC nominal filtered nonresettable output to TB1 on the ADT UDACT Note The ADT UDACT does not support voice and burglar options when used with the Unimode 2020 1010 Refer to the Unimode 2020 1010Manual for additional restrictions ADT UDACT mounting in a Unimode 2020 1010 Figure D 1 ADT UBS 1F Remove all power from the FACP by disconnecting AC and batteries Install the three supplied nylon support posts for the top and bottom left of the ADT UDACT one aluminum nylon and one aluminum standoff in the CHS 4 chassis slot in which the ADT UDACT is to be installed refer to Figure D 2 Position the ADT UDACT on the standoffs and secure on aluminum standoff with a 6
59. m Code ooonccncononanonannnnncnnnnnnnnanonnnnnnnnnnnnnnnnnnnnnnnnnnos Underwriters Laboratories Documents oooccccccnncnnnnononnnnnnnnnnnnnnnonononononononononononnnnnononnnnnononnnnnononononos 1 0 Product Description oonnnnnninniccnnncnnnennccccrcnrcn rc VS WR leie e EIER Figure 1 1 ADT UDACT Assembly rece rca nc Controls and Indicators ist Eege eI i Ee Compatible Panels o gescht ee ee etait avis GENEE Aerated attrac and Digital Gomm nicalor EE OR Wh lte EE 1 5 1 Power Requirements 2121 atan SES casado 1 5 2 COMMUNICATIONS unter ida dees det Ee 1 5 3 Primary and Secondary Phone Lines na 1 5 4 Communicator Fail Relay Driver erre ceenaareaanaanas 1 5 5 Barth Langg ege EET TT EE Future Us oia ato eae ET RE Me le EEN Telephone Requirements Silent EE 1 8 1 Telephone Circuitry PH1 amp PH2 rear 1 8 2 Digital Communicator ege dE rita 1 8 3 Telephone Company Rights and Warnings 1 9 Modes and Special Functions er ceraeeeracaraaeecaraaaaranaranaaa 1 91 Normal Mode EEN 1 9 2 Program Mode EE 1 9 3 amp Test Mode lye cee SA ee a Ee E 1 9 4 roubleshootiMode 3 caiessaaarssica rios re raona araa iaaa nnana aarep EAA REENEN 1 9 5 Type Mode ciapi ede eb aaaea a a o e d e 1 9 6 Clear FUNCIONE AE E A AAT 1 9 Manual Test FUNCHON Aisea ali e laa ia Aa 2 0 Installation and WiITING cesses eeeeeeeeeneenenseeeeesseeeeesseeeeaseeeeeenseeeeesseneeeaseeeeeaseneeens
60. mended for all applications 2 Recommended wire is 12 AWG to 18 AWG twisted pair 3 Shielded wire is not required unless mandated by local AHJ If shielded wire is used connect only one end of shield a shield may be connected to cabinet earth ground at fire alarm panel or b shield may be connected to TB1 Terminal 5 Shield at ADT UDACT NOTE The shield end that is not connected should be insulated to prevent accidental grounding Do not connect both ends of shield under any circumstance since a ground fault may result 4 Conduit is recommended for external wire runs Consult local building codes 5 Connect Ground Strap supplied with ADT ABS8RF enclosure from Earth Ground terminal on ADT UDACT to a solid building earth ground Conduit alone will not provide a reliable earth ground 6 ADT UDACT may be located up to 6 000 feet away from the host control panel 7 Refer to Specifications for power requirements Figure F 2 EIA 485 Connection to Remote ADT UDACT 64 Document 50934 RevB 5 15 00 PN 50934 B Appendix G Annunciators The ADT UDACT is connected to the EIA 485 communication bus AFM series and LDM series annunciators may also occupy the same bus Use of an ADT UDACT along with one of the above mentioned annunciators on the same control panel will alter the assignments of the first eight yellow LEDs on the annunciator as follows Unimode 300 400 Unimode 2020 1010 ADT MNNA except AC loss Yellow Annu
61. n event code See Table 5 3 for more information 4 For control panels Unimode 2020 1010 ADT MNNA and Unimode 300 400 the factory default event code is 110 and reprogrammable The Unimode 300 and Unimode 400 are unique in point reporting mode in that only the control module report codes are programmable The factory setting of report code 111 is fixed for addressable smoke detectors and cannot be changed 5 The Group is automatically incremented for Unimode 2020 1010 and ADT MNNA applications Table 3 7 Ademco Contact ID Secondary Number Document 50934 RevB 5 15 00 PN 50934 B 29 4 1 Normal Mode CLEAR TEST MODE 30 4 0 Operating Instructions UNIVERSAL DIGITAL ALARM COMMUNICATOR TRANSMITTER POWER COMM FAIL ElA 485 KISS OFF ean TEST mos pepon JOD NOM oC E UDACTKEY WMF The ADT UDACT has five Modes of operation Normal Program Lamp Test Troubleshoot and Type mode Upon initial power up the system will be in Normal Mode This section discusses operation of the ADT UDACT in the Normal Mode 4 1 1 Keys Below is a description of the function keys in Normal Mode The Clear function will cause the ADT UDACT to e cease transmissions e clear any active or pending transmissions e reset and return to normal system processing To perform the Clear function press the Clear Key followed by 2 5 3 2 then press the ENTER STORE key If the Test Key is pressed t
62. nciator LED Assignment Assignment Without UDACT With UDACT System Trouble System Trouble except AC loss 2 Signals Silenced Signals Silenced 3 Not Used Program Mode 4 Not Used Supervisory 5 Supervisory Bell Trouble Frealarm ee Alert 7 AC Fail Low Battery 8 Panel Trouble AC Fail Yellow Annunciator LED Assignment Assignment Without UDACT With UDACT 1 Progen E ORE amp supv 2 Programmable Not Used 3 Programmable Program Mode 4 Programmable Supervisory 5 Programmable Not Used 6 Programmable Maintenance Alert future use 7 Programmable Low Battery No Battery 8 Programmable AC Fail Note When using a ADT UDACT with the Unimode 2020 1010 or ADT MNNA the first Red LED on an annunciator is used to annunciate alarms while LEDs 2 through 8 are not used Document 50934 RevB 5 15 00 PN 50934 B 65 66 Document 50934 RevB 5 15 00 PN 50934 B Document 50934 RevB 5 15 00 PN 50934 B 67 68 Document 50934 RevB 5 15 00 PN 50934 B
63. ndary Line Fault Code 352 00 99 101 Primary NAC Fault Code 321 00 102 104 Primary Comm Trouble Primary Code 354 00 105 107 Primary Comm Trouble Secondary Code 354 00 108 110 Primary 485 Comm Trouble Code 300 00 111 113 Primary System Off Normal Code 308 00 114 116 Primary ADT UDACT Off Normal Code 350 00 117 119 Primary System 24 Hour Test 602 00 120 122 Primary System 24 Hour Test w active event 608 00 123 125 Primary Manual Test Message 601 00 Notes 1 Note Zero entries prevent the transmission of the report to the Central Station 2 Refer to Contact ID program locations 64 68 3 The identification of the zone device number is automatically transmitted by the ADT UDACT and is added to the main event code See Table 5 3 for more information 4 For control panels Unimode 2020 1010 ADT MNNA and the Unimode 300 400 the factory default event code is 110 and reprogrammable The Unimode 400 is unique in point reporting mode in that only the control module report codes are programmable The factory setting of report code 111 is fixed for addressable smoke detectors and cannot be changed 5 The Group is automatically incremented for Unimode 2020 1010 and ADT MNNA applications Table 3 4 Ademco Contact ID Primary Number Document 50934 RevB 5 15 00 PN 50934 B 3 1 4 1 Express or 4 1 Standard Formats If 0 2 4 6 or 8 are entered for address 42 the following is automatically pro grammed fo
64. nts 99 zones Unimode 400 384 points 99 zones Unimode 2020 1010 568 points ADT MNNA 568 points TYPE ID ACTIVATED DEVICE ZONE POINT REPORT COM EEE o EC Conventional COMINO E CO ETT DO feto EEE DO femme o femme DO femeas ju femme through Limit for Unimode 2020 1010 and ADT MNNA 568 Md Limit for Unimode 400 448 Hj Document 50934 RevB 5 15 00 PN 50934 B 41 42 6 0 Compatible Receivers The chart below shows UL listed receivers compatible with the ADT UDACT 5 e E e ES 6 8 e g E si 28 s s Format amp ED to 2 q 5 SS S do Addresses 16 amp 42 28 23 EN 58 SE 28 58 E O 4 1 Ademco Express vw vw vw 1 4 2 Ademco Express vw vw v 8 vw 2 3 1 Standard 1800 2300 W W 2 Y v 4 v v 56 vw Vv 3 Not Used 4 3 1 Standard 1900 1400 wl v 2 Y Il vw viv 5 Not Used 6 4 1 Standard 1800 2300 W W 2 Y vw 4 wv V 5 v Vv 7 Not Used 8 4 1 Standard 1900 1400 wl 2 Y 9d Vv Vv 9 Not Used A 4 2 Standard 1800 2300 PV Y w i wv lv v Vv B Not Used C 4 2 Standard 1900 1400 wl v 2 V 9 vw Vv Vv D Not Used E Ademco Contact ID Y Y Y Y F Not Used 1 With 685 8 Line Card with Rev 4 4d software 2 With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software 3 Rev 4 0 software 4 FBI CP220FB Rec 11 Line Card with Rev 2 6 software and a memo
65. op Numbers assigned for the ADT UDACT on one Unimode 2020 might be 00 O1 or 02 while the Loop Numbers for another FACP might be 10 11 or 12 or any other set of unused consecutive numbers For additional information on the Unimode 2020 1010 control panels refer to Appendix D Programming Event Codes 69 208 The type of reports and event codes that are sent to the Central Station are in Tables 3 2 through 3 7 The selections made for the Primary Central Station Number Communication Format address 16 and the Secondary Central Station Number Communication Format address 42 automatically program addresses 69 208 with factory default selections Any of the event codes may be changed Consult your Central Station prior to altering the event codes For the 3 1 4 1 and 4 1 Express Formats entering an event code of 0 will cause the communicator to NOT transmit the report Enter two zeroes for 4 2 and 4 2 Express Formats For Ademco Contact ID format enter three zeroes Transmission of reports to either or both Central Station phone numbers may be disabled Note the special System Abnormal Test Report event code This report was added per new UL DACT requirements This report is generated in place of the normal test report when an alarm and or trouble condition exists at the time the test report is due to be sent Document 50934 RevB 5 15 00 PN 50934 B 23 24 Programming the Real Time Clock Entering an address greater than 209 will cau
66. primary and secondary phone numbers are O F with the numeric digits as dialed numbers and hexadecimal digits A F representing the following functions A on a Touchtone phone keypad B on a Touchtone phone keypad C look for secondary dial tone for up to 2 seconds then dial anyway D 3 second pause E 5 second pause F end of phone number Note F must be entered Document 50934 RevB 5 15 00 PN 50934 B 19 20 Primary Number Communication Format 16 One location is needed to select the Communication Format to the primary phone number Address 16 is used for this purpose The default factory setting for this address is 16 A which is 4 2 Standard 1800 Hz Carrier 2300 Hz ack You may enter 0 1 2 4 6 8 Cor Ein place of the default then press ENTER STORE When selecting the Format note that Ademco Contact ID is the only format in the ADT UDACT which identifies the specific zone or point status to the Central Station All other formats report the number of zones or points that are active but do not identify the specific zone or point Choose from the list of formats below 0 4 1 Ademco Express Standard DTMF 1400 2300 ACK 1 4 2 Ademco Express Standard DTMF 1400 2300 ACK 2 3 1 Standard 1800 Hz Carrier 2300 Hz ACK 3 Not Used 4 3 1 Standard 1900 Hz Carrier 1400 Hz ACK 5 Not Used 6 4 1 Standard 1800 Hz Carrier 2300 Hz ACK 7 Not Used 8 4 1 Standard 1900 Hz Carrier 1400 Hz ACK 9 Not Used A
67. r Software Changes To ensure proper system operation this product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site specific soft ware Reacceptance testing is required after any change ad dition or deletion of system components or after any modifica tion repair or adjustment to system hardware or wiring All components circuits system operations or software func tions known to be affected by a change must be 100 tested In addition to ensure that other operations are not inadvert ently affected at least 10 of initiating devices that are not directly affected by the change up to a maximum of 50 de vices must also be tested and proper system operation veri fied This system meets NFPA requirements for operation at 0 49 C 32 120 F and at a relative humidity of 85 RH non condensing at 30 C 86 F However the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and all peripherals be installed in an environment with a nomi nal room temperature of 15 27 C 60 80 F Verify that wire sizes are adequate for all initiating and indicating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage FCC Warning WARNING This equipment generates uses and can radiate radio frequency
68. r limited circuit wiring and Requirements nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the ADT UDACT is shown below Use power limited source Power limited circuits i o TI PH1 d O SECONDARY ACTIVE o DO NOT USE POWER COMM FAIL ElA 485 KISS OFF Ec 00000 00000 O00Da DODDB TEST CONNECTOR JE DEE UDACPWRL WMF Figure 2 4 Typical Wiring Diagram for UL Power limited Requirements Document 50934 RevB 5 15 00 PN 50934 B 17 Programming Mode 3 1 18 Entering Program Mode 3 0 Programming Instructions Programming of the ADT UDACT is possible at any time including while the ADT UDACT is communicating with a Central Station The ADT UDACT has been designed for many different types of applications After examining your specific application review the programming options and choose the entries best suited for your system The ADT UDACT has a built in programmer All programming selections are stored in nonvolatile Electrically Erasable Programmable Read Only Memory EEPROM This ensures that the ADT UDACT will retain all entries made in programming mode even if both AC and battery power are removed The user must program the primary and secondary phone numbers account numbers and 24 hour test report times for each Central Station account and the current time The ADT UDACT comes with factory
69. r the Secondary phone number event codes Enter a 0 for the data setting to disable the report These formats do not support zone point programming For zone point reporting refer to Contact ID Address Description Setting 139 Secondary General Alarm Code 1 140 Secondary Zone Point Alarm Code 0 141 Secondary General Supervisory Code 8 142 Secondary Zone Point Supervisory Code 0 143 Secondary General Fault Code F 144 Secondary AC Fault Code F 145 Secondary Zone Point Fault Code 0 146 Secondary Low Battery Fault Code F 147 Secondary Telco Primary Line Fault Code F 148 Secondary Telco Secondary Line Fault Code F 149 Secondary NAC Fault Code F 150 Secondary Comm Trouble Primary Code F 151 Secondary Comm Trouble Secondary Code F 152 Secondary 485 Comm Trouble Code F 153 Secondary System Off Normal Code F 154 Secondary ADT UDACT Off Normal Code F 155 Secondary General Alarm Restore Code E 156 Secondary Zone Point Alarm Restore Code 0 157 Secondary General Supervisory Restore Code E 158 Secondary Zone Point Supervisory Restore Code 0 159 Secondary General Fault Restore Code E 160 Secondary AC Fault Restore Code E 161 Secondary Zone Point Fault Restore Code 0 162 Secondary Low Battery Fault Restore Code E 163 Secondary Telco Primary Line Fault Restore Code E 164 Secondary Telco Secondary Line Fault Restore Code E 165 Secondary NAC Fault Restore Code E 166 Secondary Comm Trouble Primary
70. reports identified above as item numbers 2 4 7 20 22 and 25 set to zero preventing the reports from being transmitted for the pulsed and Ademco Express formats These reports are factory programmed for active transmission when using the Ademco Contact ID 4 1 4 Key Report Descriptions ADT UDACT OFF Normal Report Removing the ADT UDACT from Normal Mode and placing it into Program or Troubleshoot Mode causes a transmission of an UDACT off normal fault message Returning the ADT UDACT to Normal Mode causes a transmission of a UDACT return to normal restoral message Panel OFF Normal Report The ADT UDACT will report a System off normal report when the host FACP temporarily shuts down the EIA 485 communications bus during various aspects of system programming When the host FACP is returned to normal restoring the fire protection the ADT UDACT will report a system off normal restoral report System Test Report The ADT UDACT will transmit a test message to both Central Stations at programmed intervals typically every 24 hours Should there exist an abnormal condition in the fire alarm system such as an alarm trouble or supervisory condition at the time when the test report is due to be transmitted the ADT UDACT will report the system abnormal test report If the system is normal the report transmitted will be the normal system test report EIA 485 Communications Trouble Report The ADT UDACT supervises the integrity of the
71. rouble 15 System Off Normal Code 16 System Automatic Test Report 17 System Abnormal Automatic Test Report 18 Manual Activated Test Report Event Restorals 19 General Alarm Restoral 20 Zone Point Alarm N Restoral 21 General Supervisory Restoral 22 Zone Point Supervisory N Restoral 23 General System Trouble Restoral 24 AC Power Loss Restoral 25 Zone Point Trouble N Restoral 26 Low Battery Restoral 27 Telco Primary Line Fault Restoral 28 Telco Secondary Line Fault Restoral 29 NAC Fault Code Restoral 30 Communication Trouble Primary Number Restoral 31 Communication Trouble Secondary Number Restoral 32 EIA 485 Communication Bus Trouble Restoral 33 System Off Normal Code Restoral Where N represents the number of zones or devices in alarm or trouble This is valid for all formats except Ademco Contact ID For all formats the general reports are always transmitted unless disabled The zone or point information may follow the general report if enabled Document 50934 RevB 5 15 00 PN 50934 B 33 4 2 34 Type Mode For all pulsed formats and both Ademco Express formats the zone point report is repeated per the total number of zones or points activated once factory default entries of zero are removed See Tables 3 2 3 3 3 4 3 5 3 6 and 3 7 When Ademco Contact ID format is used the actual zone or point activated is identified in the report The ADT UDACT comes factory programmed with the
72. ry card with Rev 3 8 software 5 Model 6500 with Rev 600 software 6 Model 6000 with Rev 204 software 7 With Rev B control card at Rev 1 4 software and Rev C line card at Rev 1 5 software 8 Model 2 only 9 Version 1 62 software Table 6 1 Compatible UL Listed Receivers Document 50934 RevB 5 15 00 PN 50934 B 7 0 Programming Reference Sheets To enter Programming press Mode 77 6 4 Enter 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Addresses 00 to 15 store the Primary Phone Number Enter F to represent the end of the number LL Primary Comm Format Enter O F a O LL LL Primary Account Code Valid keys are 0 F LL LL LL LL Primary 24 Hour Test Time Enter military time i e 1400 for 2 PM LL Primary Number Test Time Interval Enter 0 for 24 hour 1 12 hour mA LL LL SE SE LL SE LL LL LL SE LL aie LL LL ER Addresses 26 41 store the Secondary Phone Number Enter F to represent the end of the number LL Secondary Comm Format Enter 0 F LL LL LL Secondary Account Code Valid keys are 0 F E a Edy LL LL Secondary 24 Hour Test Time Enter military time i e 1400 for 2 PM q Secondary Number Test Time Interval Enter 0 for 24 hour 1 12 hour a LL Start Monitoring Address Valid entries are 01 through 32 a N LL End Monitoring Address Valid entries are 01 through 32 a DODODODDO a o ADT UDACT Communication Selection Enter 0 to disable ADT UDACT
73. se a display of the current time On initial power up the clock will start running from the factory setting of 00 01 military time The far left digit will be flashing indicating that this is the first digit to be programmed Hours Minutes Select a digit then press ENTER STORE The digit 2nd from the left will start flashing Select a digit then press ENTER STORE Hours setting is complete With the digit 2nd from the right flashing select a digit then press ENTER STORE The digit on the far right will start flashing Select a digit then press ENTER STORE Minutes setting is complete End Programming Exit Programming Mode by pressing MODE followed by the 4 digit code corresponding to an alternate mode of operation then press ENTER STORE During Program Mode if no key is pressed within 10 minutes the ADT UDACT will revert to normal mode 3 1 4 1 Express and 4 1 Standard Formats Ir 0 2 4 6 or 8 are entered for address 16 the following data is automatically programmed for the Primary phone number event codes Enter a 0 for the data setting to disable the report These formats do not support zone point programming For zone point reporting refer to Contact ID Address Description Setting 69 Primary General Alarm Code 1 70 Primary Zone Point Alarm Code 0 71 Primary General Supervisory Code 8 72 Primary Zone Point Supervisory Code 0 73 Primary General Fault Code F 74 Primary AC Fault Code F 75 Primary
74. separately Note It is critical that the ADT UDACT be located as the first device on the incoming telephone circuit to properly function Tip Green Wire Ring Red Wire i G Wi Rin o Tip reen mre g Ring Secondary Lines i Red Wire Ne To premise phones Incoming Telco Incoming Ring ted tie lt Ti e Ph Li Telco Phone P Tip PAPES Lines 11213451678 2 3 4 5 6 718 RJ31X RJ31X Jack Jack NE Note Shorting bars it inside RJ31X Jack II removed during male plug insertion MEN 7 foot s Cable Secondary Primary MCBL 7 lt Phone Line Phone Line Order Separately PH 2 PH 1 Male Plug Connectors Modular Female Ei NR pd os os IMAN J9 O RS RS O O PRIMARY aaa PHi EARTH O monem GND 24V d GND 24V Ge SECONDARY RS o SHIELD o e O UDACJAKN WMF Figure 2 1 Wiring Phone Jacks Document 50934 RevB 5 15 00 PN 50934 B Relay Driver The ADT UDACT s open collector output on TB3 terminal 2 is provided for Communicator Failure and ADT UDACT trouble It can be used to drive UL listed relay MR 101 C or MR 201 C The output is rated for 40 mA The normal condition for the output is Off deenergized Communicator Fa
75. t Restore Code EA 119 120 Primary Telco Secondary Line Fault Restore Code EB 121 122 Primary NAC Fault Restore Code EC 123 124 Primary Comm Trouble Primary Restore Code ED 125 126 Primary Comm Trouble Secondary Restore Code EE 127 128 Primary 485 Comm Trouble Restore Code EE 129 130 Primary System Off Normal Restore Code EF 131 132 Primary ADT UDACT Off Normal Restore Code EF 133 134 Primary System 24 Hour Test 99 135 136 Primary System 24 Hour Test w active events 91 137 138 Primary Manual Test 92 Note Zero entries prevent the transmission of the report to the Central Station Table 3 3 Event Codes Primary Number Document 50934 RevB 5 15 00 PN 50934 B 25 26 Ademco Contact ID Format If E is entered for address 16 the following data is automatically programmed for the Primary phone number event codes Enter a 000 for the data setting to disable the report Address Description Setting Group Sensor No 69 71 Primary General Alarm Code 110 00 000 72 74 Primary Zone Point Alarm Code 1104 00 Note 75 77 Primary General Supervisory Code 200 00 000 78 80 Primary Zone Point Supervisory Code 200 00 Note 81 83 Primary General Fault Code 300 00 84 86 Primary AC Fault Code 301 00 87 89 Primary Zone Point Fault Code 380 00 Note 90 92 Primary Low Battery Fault Code 302 00 93 95 Primary Telco Primary Line Fault Code 351 00 96 98 Primary Telco Seco
76. to 100 Ohms on the EIA 485 circuit Do not run cable adjacent to or in the same conduit as 120 volts AC service noisy electrical circuits that are powering mechanical bells or horns audio circuits above 25 volts us motor control circuits or SCR power circuits 1 5 3 Primary and Secondary Phone Lines Modular jacks are used to interface the primary and secondary phone lines to the public telephone network 1 5 4 Communicator Fail Relay Driver Relay driver output for Central Station communication failure is available 1 5 5 Earth Ground An earth ground connection to the ADT UDACT is required for transient protection One option allows connection via TB3 terminal 1 A second option allows connection via the upper right corner mounting hole Using a metal standoff and screws attach to grounded metal cabinet Optional Device Future Use Document 50934 RevB 5 15 00 PN 50934 B 1 7 1 8 Specifications Telephone Requirements and Warnings DC Power TB1 Terminals 1 amp 2 24VDC nominal filtered nonresettable and power limited Voltage range is 21 2 to 28 2 volts DC Power TB1 Terminals 1 2 40 mA in standby 75 mA max while communicating and 100 mA with the open collector output engaged and communicating Data Communications TB1 Terminals 3 7 EIA 485 serial interface TB1 Terminal 3 RS 4 RS 5 Shield 6 Future use 7 Future use Power limited source must be used Auxiliary Output TB3 Terminals
77. tors may not go off in as many as 35 of all fires While fire alarm systems are de signed to provide early warning against fire they do not guar antee warning or protection against fire A fire alarm system may not provide timely or adequate warning or simply may not function for a variety of reasons Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys in or behind walls on roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level or floor of a build ing A second floor detector for example may not sense a first floor or basement fire Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors be cause e Barriers such as closed or partially closed doors walls or chimneys may inhibit particle or smoke flow e Smoke particles may become cold stratify and not reach the ceiling or upper walls where detectors are located e Smoke particles may be blown away from detectors by air outlets e Smoke detectors may be drawn into air returns before reaching the detector The amount of smoke present may be insufficient to alarm smoke detectors Smoke detectors are designed to alarm at various levels of smoke density If such density levels are not created by a developing fire at the location of detectors the detectors will not go into alarm Smoke detectors even when working properly
78. transmission wiring communi cations signaling and or power If detectors are not so lo cated a developing fire may damage the alarm system crip pling its ability to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building Any warning device may fail to alert people with a disability or those who have recently consumed drugs alcohol or medica tion Please note that e Strobes can under certain circumstances cause seizures in people with conditions such as epilepsy e Studies have shown that certain people even when they hear a fire alarm signal do not respond or comprehend the meaning of the signal It is the property owner s responsibil ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals e In rare instances the sounding of a warning device can cause temporary or permanent hearing loss A fire alarm system will not operate without any electrical power If AC power fails the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly Equipment used in the system may not be technically com patible with the control It is essential to use only equipment listed for service with your control panel
79. uble Secondary Number Code FE 165 166 Secondary 485 Comm Trouble Code FE 167 168 Secondary System Off Normal Code FF 169 170 Secondary ADT UDACT Off Normal Code FF 171 172 Secondary General Alarm Restore Code El 173 174 Secondary Zone Point Alarm Restore Code 00 175 176 Secondary General Supervisory Restore Code E2 177 178 Secondary Zone Point Supervisory Restore Code 00 179 180 Secondary General Fault Restore Code E3 181 182 Secondary AC Fault Restore Code E6 183 184 Secondary Zone Point Fault Restore Code 00 185 186 Secondary Low Battery Fault Restore Code E8 187 188 Secondary Telco Primary Line Fault Restore Code EA 189 190 Secondary Telco Secondary Line Fault Restore Code EB 191 192 Secondary NAC Fault Restore Code EC 193 194 Secondary Comm Trouble Primary Restore Code ED 195 196 Secondary Comm Trouble Secondary Restore Code EE 197 198 Secondary 485 Comm Trouble Restore Code EE 199 200 Secondary System Off Normal Restore Code EF 201 202 Secondary ADT UDACT Off Normal Restore Code EF 203 204 Secondary System 24 Hour Test 99 205 206 Secondary System 24 Hour Test w active events 91 207 208 Secondary Manual Test 92 Note Zero entries prevent the transmission of the report to the Central Station Table 3 6 Event Codes Secondary Number Document 50934 RevB 5 15 00 PN 50934 B Ademco Contact ID Format If E is entered for address 42 the following data is automatically pro
80. ult is 00 66 68 Device Zone number CCC for General Alarm Fault or Supervisory messages factory default is 000 A typical printout of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows Revr Time Date LinelD SSSS QXYZ GG CCCC 11 28 03 25 11 7777 E110 00 C000 general alarm 11 28 03 25 11 7777 E111 00 C046 alarm SD46 11 28 03 25 11 7777 E300 00 C000 general trouble 11 28 03 25 11 7777 E380 00 C046 trouble SD46 11 28 03 25 11 7777 R110 00 C000 general alarm restore 11 28 03 25 11 7777 R111 00 C046 alarm SD46 restore 11 28 03 25 11 7777 R300 00 C000 general trbl restore 11 28 03 25 11 7777 R880 00 C046 trouble SD46 restore Table 5 3 Ademco Contact ID Reporting Structure Notes 1 In the sample report SD46 refers to smoke detector at address 46 or on zone 46 2 18 which is used in the reporting structure to identify the transmission as Contact ID is not printed out in the alarm and trouble report 3 Q which is the Event Qualifier for the reporting structure is printed out in the report as an E for New Event or R for New Restore 4 CCCC the first C is not transmitted by the ADT UDACT but is printed by the Central Station Receiver printer output Document 50934 RevB 5 15 00 PN 50934 B By using the Type Mode feature identification of zone point types is possible Limits for the maximum number of zones points reported for each panel are as follows Unimode 300 192 poi
81. wiring alternatives ABS 8R WMF e Figure E 1 ADT ABS8RF Connect the communication line between the EIA 485 terminal block TB4 on the Unimode 300 400 and TB 1 terminals 3 and 4 on the ADT UDACT being certain to observe polarity refer to Figure E 3 Recommended wire is 12 AWG to 18 AWG twisted pair If no other devices are connected to the EIA 485 install a 120 ohm EOL resistor across ADT UDACT TBI terminals 3 and 4 Connect the supplied ground strap from the ADT UDACT Earth Ground terminal on TB3 to a solid building earth ground Connect 24VDC nonresettable power to TB 1 terminals 1 and 2 on the ADT UDACT refer to Figure E 3 ABS 8R WMF Figure E 2 ADT CPU 400 Module Document 50934 RevB 5 15 00 PN 50934 B 59 Install 120 watt EOL resistor PN 71244 on Unimode 400 Cabinet TB1 terminals 3 and 4 if last or only device on Ferrite cores E PN 29090 ElA 485 line To supervised Supervised and Y phone lines Solid eai Power limited olid ear EIA 485 and ADT CPU 400 power wiring ooo booo od AE ea Waal ros ras S ElA 485 ACS Mode TB4 1 TB4 2 H DEE EN
82. witches CLEAR Digits 0 9 TEST MODE Up Arrow Down Arrow 1st EVENT ENTER STORE Displays e EIA 485 yellow LED e COMM FAIL yellow LED e KISS OFF green LED e POWER green LED Four Seven Segment Displays red e Primary Phone Line Active red LED e Secondary Phone Line Active red LED e TEST green LED PRIMARY ACTIVE PHI PH2 MODEM A SECONDARY a UNIVERSAL DIGITAL ALARM COM UNICATORITRANSMITTER 0 D Do DS g O E O E CO m COMM FAIL POWER ElA 485 CLEAR TEST MODE KISS OFF 1700 0 Lo Es MII fe udactfea wmf Figure 1 2 Controls and Indicators The ADT UDACT has been designed to be compatible with the ADT Unimode 2020 1010 Unimode 300 400 and the ADT MNNA Two modular phone jacks allow easy connection to telephone lines Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines Telephone line Primary and Secondary Active red LEDs are provided as well as a green Kissoff LED The integral digital communicator provides the following functions e Line Seizure takes control of the phone lines disconnecting any premises phones Off On Hook perform on and off hook status to the phone lines e Listen for dial tone 440 hertz tone typical in most networks e Dialing the Central Station s number default is Touch Tone programmable to rotary

Download Pdf Manuals

image

Related Search

Related Contents

平成11年仙審第47号 漁船第三十八恵比須丸機関損傷事件 言渡年月  FICHE SIGNALÉTIQUE 1. Identification du produit et de l`entreprise  Lumberg LUM-WKLS40  Easily split and distribute SD/HD/3G-SDI video to six  

Copyright © All rights reserved.
Failed to retrieve file