Home

APC NetShelter SX 48U

image

Contents

1. ns1758b 2 Disconnect the ground wire and any other wire connections Remove the door from the frame See Door Removal on page 11 for more information 3 Locate the upper hinge on the cabinet frame Remove the two screws holding the hinge in place Install the hinge onto the other side of the cabinet frame Repeat this step for the lower hinge 4 Rotate the door Remove the hinges from the door and install them to the alternate hole location The hinges on door should now align with the hinges on the cabinet 5 Install the door to the hinges now on the reverse side of the cabinet frame See Door Removal on page 11 for instruction Connect the ground wire and any other wire connections previously disconnected 12 NetShelter SX Cabinet Installation and Customization Manual 6 Locate the lock handle Remove the cam screw cam washer Rotate the cam washer 90 degrees and the latch 180 degrees Install the handle on the door ns1766b 7 Remove the nameplate if equipped from the door Install the nameplate at the l
2. ns1725a NetShelter SX Cabinet Installation and Customization Manual 17 Remove the Cable Cutout Covers For NetShelter SX 750 mm 29 5 in wide cabinets that include equipment requiring side airflow on the side of the cabinet nearest the air intake for the equipment right side in the example below remove the cable cutout covers from the front vertical mounting flange Reinstall the covers in the cable cutout holes on the rear vertical mounting flange on the same side of amp the cabinet ns1071b Cable Management The NetShelter SX cabinet has multiple cable access openings including on the roof sides and bottom Route secure and organize cables using these openings In addition two rear vertical OU cable organizers or accessory channels are included with the cabinet Further cable management accessories are available Please see www apc com or contact a Schneider Electric re seller for more information Accessory Channel The accessory channels provide toolless mounting capabilities for Rack Power Distribution Units and ca
3. ns1633a NetShelter SX 7700 Attaches externally to the rack Stabilizer Plate Optional and floor to provide additional stability 5 50702 8 NetShelter SX Cabinet Installation and Customization Manual Ground the Cabinet DANGER HAZARD OF ELECTRIC SHOCK Connection of the cabinet to building Common Bonding Network CBN is required Failure to follow these instructions will result in death or serious injury Each cabinet should be bonded directly to a common ground using one of the designated grounding locations two M6 threaded inserts at the top or bottom of the cabinet Use a Common Bonding Network Jumper kit for example Listed KDER Panduit amp RGCBNJ660PY or equivalent Use paint piercing washers between the ground terminal and the cabinet frame or remove the paint on the frame under the ground terminals per NEC 70 Article 250 12 Torque the screws to 6 9 Nem 60 ns1617a Bonding Locations on the Cabinet NetShelter SX Cabinet Installation and Customization Manual Install Side Panels Roof and Doors Side Panels Roof 10 NetShelter SX Cabinet Installation and Customization Manual Door Removal 1 Unlock the cabinet front door handle and open the door
4. 5 Gabinet IrstalldtOrizzu an oso ai dee Feo Ancona ee itd d 6 Move the 6 Level the 7 Join the es P Se Sees 7 Secure the 8 Ground the Gabinet ree mere yee d wees Ex 9 Install Side Panels Roof and 4 4 0 0040 nnn 10 Side Panels ET aste de deed de RR E CAT ea Ei 10 ROOT is s ta ute uae dece 10 Door Removal xu evi vue ed Spe Taxi PUR MEER 11 Doorilnstallatioh eer exe tix ener iti ars ol wie E et 11 Reverse the Front Door 12 EQUIPMENT Istalldtigfis a etch Obat centes 14 Adjust the Vertical Mounting 14 Position the Vertical Mounting Flanges 14 Vertical Mounting Flange 15 Install the 17 To install rack mount equipment in the cabinet 17 Gage nuts aid edad alee ea rupe ope rk eke E d 17 Cable Containment Bracket 2
5. 54U 2525 99 4 540 models have not been evaluated by UL Door Perforation pattern 69 open area Clearance for wiring between front 60 96 mm 2 40 in door and vertical rail Weight rating static load 1363 6 3 000 Ib Weight rating rolling 1022 7 kg 2 250 Ib 1 Lower the leveling feet if the static weight is over 1022 7 kg 2 250 Ib Rolling rating valid only for rolling the cabinet into position NOTE Additional packaging is required if the cabinet is being shipped with equipment installed See the NetShelter SX product family page at www schneider electric com for details on cabinets with shock packaging NetShelter SX Cabinet Installation and Customization Manual 19 Limited Factory Warranty The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business Terms of Warranty Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of five years two years in Japan from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its sole discretion any such defective products This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way Repair or replacement of a defective produ
6. 2 Disconnect the ground wire and any other wire connections that may interfere with the removal of the doors ns2283a 3 The hinges come apart by lifting upward and outward Slowly lift and pull the door from the cabinet until the hinge pins on the door are free of the hinges on the cabinet frame ns1604b Door Installation 1 The doors self align on hinge pins when properly installed With the door at a 90 degree angle to the front of the cabinet position the door over the hinge pins 2 Slowly lower the door into the cabinet frame ensuring that the door hinges correctly align to the cabinet frame hinges ns2284a 3 Connect the ground wire and any other wire connections ns2285a NetShelter SX Cabinet Installation and Customization Manual 11 Reverse the Front Door Note The front door can be reversed so that the door opens in the other direction This procedure assumes that initially when facing the cabinet the hinges are on the left and the door is opening from right 1 Remove the handle by removing the screw plate Pull the handle from the door 1
7. install rack mount equipment in the cabinet Review the equipment manufacturer s installation instructions Locate the top and bottom U space on the vertical mounting rails Every third hole on the mounting rails is numbered to indicate the middle of a U space Install the cage nuts on the interior of the vertical mounting rail then install the 1U equipment Cage nuts Installation Schneider Electric offers a cage nut hardware kit AR8100 for use with square holes Note Install cage nuts horizontally with ns0014a the ears engaging the sides of the square hole Do NOT install cage nuts vertically with the ears engaging the top and bottom of the square hole nut assembly through the far side of the hole ns1768a flange Place the cage nut tool on the other side of the cage nut and pull to snap it into position Removal Remove any attached screw Grasp the cage nut and squeeze the sides to release it from the square hole Note Install the cage nuts on the interior of the vertical mounting Insert the cage nut into the square hole by hooking one ear of the cage gen0188a Cable Containment Bracket 24U Models Only The rear door cable containment bracket is installed within the cabinet under the left hand door The bracket has 4 lobes for attaching cables with hook and loop fasteners provided and cable ties not provided
8. 4U M dels Only a eas Son UE SE a eR 17 Remove the Cable Cutout Covers 18 Cable WAS ITS I ae sae ttl testa Merle Lu Lu E 18 Accessory Chantiel c std REDDE Eb e ede e 18 haunt 19 Limited PFacteryoVatrabiby inet he 20 Terms or Warranty Pee De Sea ione 20 Non transferable Warranty 1 20 EEXCIUSIONS ee wate Gane Paw 20 Warranty Claims 4 20 NetShelter SX Cabinet Installation and Customization Manual Introduction The Schneider Electric NetShelter SX cabinets are high quality cabinets for storage of industry standard EIA ECA 310 19 in 483 mm rack mount hardware which includes servers and voice data networking internetworking and power protection equipment This manual covers the general installation and the customization of the NetShelter SX with Premium Datacenter Cabinets Refer to the NetShelter SX specification manual for detailed measurements and ratings of specific models These cabinets are available on 600 mm 23 6 in and 750 mm 29 5 in widths Optional vertical mounting flanges are available f
9. FACTION AND FITNESS FOR A PARTICULAR PURPOSE SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES IN NO EVENT SHALL SCHNEIDER ELECTRIC ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY OF SUCH DAMAGES SPECIFICALLY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWARE LOSS OF DATA COSTS OF SUBSTITUANTS CLAIMS BY THIRD PARTIES OR OTHERWISE NO SALESMAN EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY WARRANTY TERMS MAY BE MODIFIED IF AT ALL ONLY IN WRITING SIGNED BY AN SCHNEIDE
10. Installation and Customization NetShelter SX Cabinet 990 2183G 001 Publication Date February 2015 Schneider Schneider Electric Legal Disclaimer The information presented in this manual is not warranted by Schneider Electric to be authoritative error free or complete This publication is not meant to be a substitute for a detailed operational and site specific development plan Therefore Schneider Electric assumes no liability for damages violations of codes improper installation system failures or any other problems that could arise based on the use of this Publication The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction This Publication has been compiled in good faith by Schneider Electric However no representation is made or warranty given either express or implied as to the completeness or accuracy of the information this Publication contains IN NO EVENT SHALL SCHNEIDER ELECTRIC OR ANY PARENT AFFILIATE OR SUBSIDIARY COMPANY OF SCHNEIDER ELECTRIC OR THEIR RESPECTIVE OFFICERS DIRECTORS OR EMPLOYEES BE LIABLE FOR ANY DIRECT INDIRECT CONSEQUENTIAL PUNITIVE SPECIAL OR INCIDENTAL DAMAGES INCLUDING WITHOUT LIMITATION DAMAGES FOR LOSS OF BUSINESS CONTRACT REVENUE DATA INFORMATION OR BUSINESS INTERRUPTION RESULTING FROM ARISING OUT OR IN CONNECTI
11. ON WITH THE USE OF OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT EVEN IF SCHNEIDER ELECTRIC HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES SCHNEIDER ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE Copyright intellectual and all other proprietary rights in the content including but not limited to software audio video text and photographs rests with Schneider Electric or its licensors All rights in the content not expressly granted herein are reserved No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information This Publication shall not be for resale in whole or in part Table of Contents atc E 1 Unpack the CabllWlpl adde d Mines 2 2 InSpectlOri e a e ir etr teet uei ree i e s reist 2 Please Recycle 2 Important Safety Information 2 Safety Instructions 3 Eabels s reete asta le dor Sed bee Re te Glow ec Reed 3 Component Identification no e re e Detto race UP 4 ette er er T 4 Hardware xe peat Ait eee eds Oe RARE
12. R ELECTRIC OFFICER AND LEGAL DEPARTMENT Warranty Claims 20 Customers with warranty claims issues may access the Schneider Electric worldwide customer support network by visiting www schneider electric com Select your country from the country selection pull down menu Open the Support tab at the top of the web page to obtain contact information for customer support in your region NetShelter SX Cabinet Installation and Customization Manual Worldwide Customer Support Customer support for this or any other product is available at no charge in any of the following ways Visit the Schneider Electric Web site to access documents in the Schneider Electric Knowledge Base and to submit customer support requests www schneider electric com Corporate Headquarters Connect to localized Schneider Electric Web sites for specific countries each of which provides customer support information www Schneider electric com support Global support searching Schneider Electric Knowledge Base and using e support e Contact the Schneider Electric Customer Support Center by telephone or e mail Local country specific centers go to www schneider electric com Support Operations around the world for contact information For information on how to obtain local customer support contact the representative or other distributors from whom you purchased your product 2015 Schneider Electric All Rights Reserved APC the logo
13. Schneider Electric and NetShelter are trademarks owned by Schneider Electric Industries SAS or its affiliated companies All other trademarks are property of their respective owners 990 2183G 001 02 2015
14. adly sloped surface Ensure the cabinet is in its intended location Remove the front and rear doors See Door Removal on page 11 for instruction Note Before removing the front door unplug the ground wires and any other wire connections that may interfere with the removal of the doors Insert a Phillips head screwdriver into the screw above the leveling foot Turn the screw clockwise to extend the leveling foot until it makes firm contact with the floor Notes 1 If loaded with equipment a 13 mm open ended wrench can also be used to lower the leveling feet 2 This method works best with an empty or near empty cabinet 3 Door removal is not required if using the 13 mm open ended wrench Adjust each foot and using a level adjust the feet until the cabinet is level and plumb Do not install the doors until after the cabinet is joined to others in the row Join the Cabinets Join cabinets with the provided brackets to provide alignment and added stability Cabinets may be joined with or without the side panels installed WARNING TIP HAZARD Joining cabinets provides limited stability to the cabinets Secure the cabinet to the floor before installing equipment Failure to follow these instructions can result in death serious injury or equipment damage If installed remove the front and rear doors See Door Removal on page 11 for instructions Choose bet
15. ble management accessories There are four Accessory Channels included with the 1200 mm 47 24 in deep cabinet There are two included with all other cabinets The factory default position for the accessory channels is in the rear of the cabinet as shown in the graphic to the right The channels also provide tie off locations for cables as well as other specific holes for managing cables with many NetShelter brackets fasteners and toolless mounting equipment Similar to the mounting flanges the accessory channel can be moved anywhere along the side braces See Adjust the Vertical Mounting Flanges on page 14 for more instruction Note If needed the accessory channels be removed Additional vertical OU accessory channels are available for order ns1923a 18 NetShelter SX Cabinet Installation and Customization Manual Specifications General specifications for SX cabinets for detailed dimensions and weights refer to the NetShelter SX Specification manuals Height by U dimension Width Depth U mm in mm in mm in 24U 1199 47 2 600 23 6 1070 42 1 42U 1991 78 4 700 27 6 1200 47 2 45U 2124 83 6 750 29 5 48U 2258 88 9 700 mm models in Japan only 50U 2347 92 4 52U 2436 95 9
16. corresponding hole at both the top and the bottom of the flange 4 When the vertical mounting flange is in the desired location at the top middle and bottom raise the flat bracket to the lock position The teeth in the bracket will engage fully with the teeth in the side brace Tighten the TORX screws ns0718a E N 9m Note the 750 mm rack there circle symbols 476 mm 18 75 in behind the front mounting flange These circle symbols designate rear vertical mounting flange positions required for installation of particular networking and telecommunications equipment ns2292a 16 NetShelter SX Cabinet Installation and Customization Manual Install the Equipment WARNING TIP HAZARD This cabinet is easily tipped Make sure you have secured the cabinet to the floor before installing equipment Install the heaviest equipment first and toward the bottom of the cabinet to prevent the cabinet from becoming top heavy Do not extend equipment on sliding rails until you have installed 158 kg 350 Ib of equipment into the bottom of the cabinet for stability or until you have installed the stabilizer plate or bolt down brackets Do not extend more than one piece of equipment on sliding rails at a time Failure to follow these instructions can result in death serious injury or equipment damage To
17. ct or part thereof does not extend the original warranty period Any parts furnished under this warranty may be new or factory remanufactured Non transferable Warranty This warranty applies only to the original purchaser who must have properly registered the product Product may be registered at www schneider electric com Exclusions Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user s or any third person s misuse negligence improper installation or testing Further Schneider Electric shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection inappropriate on site operation conditions corrosive atmosphere repair installation start up by non Schneider Electric designated personnel a change in location or operating use exposure to the elements Acts of God fire theft or installation contrary to Schneider Electric recommendations or specifications or in any event if the Schneider Electric serial number has been altered defaced or removed or any other cause beyond the range of the intended use THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE OF PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY SATIS
18. ese instructions can result in death serious injury or equipment damage Labels Look for additional safety information affixed to the cabinet See Labels on page 6 for more information NetShelter SX Cabinet Installation and Customization Manual 3 Component Identification Cabinet eT EE TE i M em La e Adjustable vertical OU accessory channel Removable and reversible front door Removable rear split doors Nameplate if equipped Removable side panel with lock Key for doors and side panels Cabinet frame Vertical mounting flanges Adjustable leveling feet 1070 mm 42 13 in roof Q Hardware bag see page 5 1200 mm 47 24 in roof Casters 1200 mm 47 24 in deep cabinets include four vertical OU Accessory Channels NetShelter SX Cabinet Installation and Customization Manual Hardware Plastic cup Mex16 Phillips 5 12 Cage nut 60 7 mm 0 28 in washer 60 slot screw 60 screw 4 hole plug 4 dili HE TORX T30 2 Phillips tool Cage nut tool NetShelter SX Cabinet Installation and Customization Manual Cabinet Installation Move the Cabinet WARNING TIP HAZARD This cabinet is easily tipped Use extreme caution when unpacking or moving at least two people to unpac
19. esult in death or serious injury WARNING WARNING indicates a potentially hazardous situation which if not avoided can result in death or serious injury CAUTION CAUTION indicates a potentially hazardous situation which if not avoided can result in minor or moderate injury CAUTION CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided can result in equipment damage NOTICE NOTICE addresses practices not related to physical injury including certain environmental hazards potential damage or loss of data 2 NetShelter SX Cabinet Installation and Customization Manual Safety Instructions This manual contains important instructions that must be followed during the installation and customization of the cabinet AWARNING TIP HAZARD This cabinet is easily tipped Use extreme caution when unpacking or moving Use at least two people to unpack and move the cabinet Before moving the cabinet on its casters load 158 kg 350 Ib of equipment into the bottom of the cabinet for extra stability When moving on its casters make sure the leveling feet are up and push the cabinet from the front rear Failure to follow these instructions can result in death serious injury or equipment damage A WARNING HEAVY EQUIPMENT Use at least two people to unpack the cabinet Failure to follow th
20. k and move the cabinet Before moving the cabinet on its casters load 158 kg 350 Ib of equipment into the bottom of the cabinet for extra stability When moving on its casters make sure the leveling feet are up and push the cabinet from the front rear Failure to follow these instructions can result in death serious injury or equipment damage Labels The following labels can be found on the cabinet and serve to communicate the following information Casters Label Generic Tip Hazard 2250 lbs Max 1020 kg Label Extend Slide Mounted Hardware One Piece at a Time Casters The cabinet can be moved on its casters with up to 1021 kg 2 250 Ib of equipment installed Once in place lower the Leveling Feet leveling feet With the leveling feet lowered the static cabinet can be loaded to 1364 kg 3 000 Ib Note Some labels on cabinet indicate caster related information See label to right Eye bolts The cabinet can be lifted using eye bolts with up to 567 kg 1 250 Ib of equipment installed Use M10 eye bolts with a shoulder rated for 181 kg 400 Ib Note Use appropriate lifting hardware to assure straight line pull on lifting eye bolts ns2378a 6 NetShelter SX Cabinet Installation and Customization Manual Level the Equipment The leveling feet at the corners of the equipment provide a stable base if the floor is uneven but they cannot compensate for a b
21. n in 8025 in PA 750 mm 1200 mm 112900 1221 14 NetShelter SX Cabinet Installation and Customization Manual Vertical Mounting Flange Adjustment WARNING FALLING EQUIPMENT Remove all equipment installed on the vertical mounting flanges before performing any adjustments Failure to follow these instructions can result in serious injury or equipment damage 1 Use the provided TORX T30 tool to loosen the top middle and bottom TORX screws holding the vertical mounting flange in place The brackets all held in place by the TORX screws will now be loose Move all three brackets to the designated unlocked position JG O O OA ie 600 mm wide cabinet ns1622b ns0715b 750 mm wide cabinet NetShelter SX Cabinet Installation and Customization Manual ns0977a 15 2 Move the mounting flange to the desired location Vertical mounting flanges adjust in 6 mm 1 4 in increments 3 To align the vertical mounting flange note the symbol for example a diamond visible through one of the three holes Only one symbol will be visible In the factory standard position a circle symbol is visible Make sure the same symbol is visible through the
22. ocation shown in the illustrations below 307 mm 12 in ns2010a ns1612b NetShelter SX Cabinet Installation and Customization Manual 13 Equipment Installation Note NetShelter SX cabinets are intended for use with Listed equipment If you install un Listed equipment you should evaluate the safety of your configuration Adjust the Vertical Mounting Flanges melee ee ee ee Position the Vertical Mounting Flanges Configuration 1 The Accessory Channel is installed The Vertical Mounting Flanges can be installed a minimum distance of a and can extend as far as b Configuration 2 The Accessory Channel is removed The Vertical Mounting Flanges can extend as far as c Vertical mounting flanges come factory installed at 737 mm 29 in the proper location for use with rack mountable equipment The mounting flanges are adjustable towards the front or the rear of the cabinet to accommodate different rails or equipment with other depths A common application for the 750 mm 29 5 in wide cabinet is to move the flanges to a depth of 476 mm 18 75 in to accommodate networking and telecommunications equipment Accessory Channel I3 E r b T7714 ns2293a Top View Cabinet Cabinet Width W Depth D a b 600 mm 7 in 1 in 86 251 in 750 mm TE PRI 2n ee in in 600 mm 1200 mm
23. or the 750 mm 29 5 in cabinet to accommodate 23 in EIA ECA telecommunications equipment NetShelter SX Cabinet Installation and Customization Manual 1 Unpack the Cabinet Disclaimer Schneider Electric is not responsible for damage sustained during reshipment of this product Inspection Inspect the packaging and contents for shipping damage Make sure that all parts are accounted for Report any damage immediately to the shipping agent Report missing contents damage or other problems immediately to Schneider Electric or your reseller Please Recycle 5 The shipping materials are recyclable Save them for later use or dispose of them appropriately Important Safety Information Read the instructions carefully to become familiar with the device before trying to install operate service or maintain it The following messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death A DANGER DANGER indicates an imminently hazardous situation which if not avoided will r
24. ween 24 in centers or 600 mm centers see the detail view below Align the cabinets and locate the joining brackets There are two brackets on the front and two brackets on the back of each cabinet Cabinets are joined using a M5 x 12 countersunk screw provided in the hardware bag Using the Phillips head end of the provided tool or a similar tool insert the screw into the designated hole and tighten Install the doors See Door Removal on page 11 for instructions NetShelter SX Cabinet Installation and Customization Manual ns1594b ns1632b Secure the Cabinet 4 WARNING TIP HAZARD Secure the cabinet to the floor before installing equipment Failure to follow these instructions can result in death serious injury or equipment damage To secure the cabinet to the floor use fastener locations on the outside or inside of the cabinet and choose from the accessories shown below Accessory Part Number Description Pallet Bolt down provided with the Attaches to the rack internally Brackets cabinet or externally to secure the rack the floor This provides additional stability without blocking cable access With the appropriate mounting hardware meets IBC CBC seismic requirements Bolt down kit AR7701 Attaches to rack and floor Optional internally or externally to provide additional stability without blocking cable access

Download Pdf Manuals

image

Related Search

Related Contents

Copyright © All rights reserved.
Failed to retrieve file