Contents
1. Q MLL Online UPS PowerWalker VFI 1000R 1U Manual EN Uninterruptible Power Supply System VSM Table of Contents he MMV OPEAM ES ACL Et E 1 1 1 Transportation 2 0 0 0 ccc cece ccnnnnnnseeeeeeeeeeeeeeeeeeeeeeeeeeeeaaeaeeeeeeeseeeeeeeeeeeeeeeeeeeeaaaaaaaaeeeeeeeeees 1 LE RE 1 ESD E O E A 1 E 07 EE 1 1 5 Maintenance service and faute 2 Z MANS CAN e md GI ee E E E E T 3 We Kear Pane lV E 3 E Er he D E E E E ES 4 3 1 Button operation EE 6 3 2 LED ut Ve ODES ss crises srcctosesttecoiycaisoetacen bats coilsers tuntoaeat E 7 3 3 Audible Alarm 8 G Power Walker 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation e Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation e Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment e Do not install the UPS system near water or in moist environments e Do not install the UPS system where it would be exposed to direct sunligh
2. and amperage in order to avoid fire hazards e Do not dismantle the UPS system G Power Walker 2 Installation and setup 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K IKL AC input Output receptacle connect to mission critical loads Programmable outlets connect to non critical loads USB RS 232 serial communication port ROO RPO function connector SNMP intelligent slot Dry contact External battery connector CON ODO OFA Go N G Power Walker 2 2 Setup the UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords The power cord is attached to the UPS The input plug is a NEMA 5 15P Step 2 UPS output connection There are two kinds of output receptacles programmable outlets and general outlet Please connect non critical devices to the programmable outlets and critical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices Step 3 Communication connection Communication port USB port RS 232 port Dry contact Intelligent slot oae oo i t To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one
3. unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous e Before carrying out any kind of service or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors e Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries e Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present e Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles e When changing batteries install the same number and same type of batteries e Do not attempt to dispose of batteries by burning them This could cause battery explosion e Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic e Please replace the fuse only with the same type
4. 5 audible warning 105 130 UPS shuts down in 10 seconds at battery mode or transfers to Overload bypass mode after 2min when the utility is normal gt 130 UPS shuts down immediately at battery mode or transfer to bypass mode after 10s when the utility is normal Current Crest Ratio 5 1 for 110 120 VAC system or 3 1 for 220 230 240 VAC systems Harmonic Distortion E a 4 ms Typical Waveform Bat Mode EFFICIENCY BATTERY Lithium iron battery or Sealed Lead acid battery Battery voltage 4 hours recover to 90 capacity 48VDC PHYSICAL Dimension D X W X H mm Net Weight kg r ENVIRONMENT 20 90 RH 0 40 C non condensing MANAGEMENT 1KL is only available in 220 230 240VAC system 10
5. OM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock G Power Walker 3 Operations 3 1 Button operation LK View LED indicators On Off button Turn on the UPS Press and hold button for at least 2 seconds to turn on the UPS Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS UPS will be in standby mode when utility power is normal or transfer to bypass mode if bypass mode is enabled via software ON OFF Button 1KL View OO AC MODE O BATT MODE OFF O Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS ON Mute Mute the alarm When the UPS is on battery Button mode press and hold this button for at least 5 seconds to disable or enable the alarm system But it s not applied to the situations when warnings or errors occur Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS in OFF Enter battery mode UPS will be in standby mode Button under power normal or transfer to Bypass mode if
6. d Remove excess loads every second from UPS output After repetitive overloads Remove excess loads the UPS is locked in the from UPS output first Bypass mode Connected Then shut down the UPS devices are fed directly by and restart it the mains 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer ee Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration G Power Walker 6 Specifications MODEL CAPACITY 1000 VA 800 W INPUT 80VAC 70VAC 60VAC 55VAC 5 or 160VAC 140VAC 120VAC 110VAC 5 Low Line Transfer based on load percentage 100 80 80 70 70 60 60 0 Voltage Lon Line Comeback 85VAC 75VAC 65VAC 60VAC 5 or 170VAC 150VAC 130VAC 120VAC 5 Range Low Line Comeback Ao based on load percentage 100 80 80 70 70 60 60 0 N 150 VAC 5 or 300 VAC 5 140 VAC 5 or 290 VAC 5 OUTPUT Frequency Range Bat Mode 60Hz 0 3 Hz 100 10
7. end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The pin assignment for dry contact is listed as below Condition Yes NO Low battery Pin 3 and Pin 9 are connected Pin 3 and Pin 1 are connected Output is abnormal Pin 7 and Pin 8 are connected Pin 7 and Pin 5 are connected Battery mode Pin 2 and Pin 6 are connected Pin 2 and Pin 4 are connected The UPS is equipped with intelligent slot perfect for SNMP card When installing with SNMP card in the UPS it will provide advanced communication and monitoring options Q MLL Step 4 Disable Enable ROO RPO function Contact open UPS shuts down ROO Contact closed UPS start up UPS is connected to AC power and AC power is available Note The local ON OFF control by pressing On Off button overrides the remote control function RPO Contact open UPS shuts down and Fault LED 3 will be ON To return to normal operation de activate external remote contact Fault LED 3 will be OFF and restart the UPS by pressing button Step 5 Turn on off the UPS Press the ON OFF button on the front panel for two seconds to power on the UPS Step 6 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD R
8. t or near heater e Do not block ventilation holes in the UPS housing 1 3 Installation e Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets e Place cables in such a way that no one can step on or trip over them e Do not connect domestic appliances such as hair dryers to UPS output sockets e The UPS can be operated by any individuals with no previous experience e Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system e When installing the equipment it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3 5mA 1 4 Operation e Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads e The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet e Prevent no fluids or other foreign objects from inside of the UPS system G MLL 1 5 Maintenance service and faults e The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel e Caution risk of electric shock Even after the
9. the Bypass enable setting by pressing this button QO PowerWalker 3 2 LED Indicators 1K View LED7 LEDS POWER ON OFF LED3 LED1 LED2 LED UPS Status Lighting Flashing LED Lighting LED4 to LED7 indicate load level during line mode Line Mode LED4 gt 75 load level a Green Lighting LED5 50 75 load level LED6 25 50 load level LED7 0 25 load level LED4 to LED7 indicate battery Capacity during battery mode Battery Mode LED4 battery voltage gt 26V Green Lighting LEDS battery voltage gt 24 5V LED6 battery voltage gt 23V LED 7 battery voltage gt 21V Low battery LED7 Flashing Battery replacement LEDS Red Flashing LEDS Red Lighting G Power Walker 1KL View Three indicators to display UPS status UPS Status Off mode charging 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Sounding twice every second Continuously sounding Bypass Mode Sounding every 10 seconds 290 G Power Waker 4 Troubleshooting If the UPS system does not operate correctly please solve the problem by using the table below No indication and alarm even The AC input power is not Check if input power cord though the mains is normal connected well firmly connected to the mains The AC input is connected Plug AC input power cord to the UPS output to AC input correctly The alarm is sounding twice UPS is overloa