EAST EA300PRO-800 uninterruptible power supply (UPS)
Contents
1. Line Interactive Sinewave UPS 800 1 1K 1 5K 2K 2 5K 3K VA Uninterruptible Power Supply System Table of Contents 1 Important Safety WarnlnG cccsescessnccesnnsecesnneeeanseesnnsensnnseneass 1 1 Transportation 1 2 Preparation 1 3 Installation 1 4 Operation 1 5 Maintenance Service And Faults 2 Installation And Se tUp csccsecccssncceessceeenseeenceeennneeenuenennneneass 2 1 Rear Panel View 2 2 Install The UPS 2 3 Setup The UPS 2 4 Battery Replacement 2 5 Battery Kit Assembly Option 5 OPTa ONSA EE 3 1 Button Operation 3 2 LCD Panel 3 3 Audible Alarm 3 4 LCD Display Wordings Index 3 5 UPS Setting 3 6 Operating Mode Description 3 7 Faults Reference Code 3 8 Warning Indicator A TFOUDICSNOOUNG cosir Ra 5 Storage And MaintenanCe sssssssssussss22 s GO SPECITIGCAUIONS croa 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely d
2. Fault code is shown as 27 and the Battery voltage is too high Contact your dealer E or the charger is fault icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the Battery voltage is too low Contact your dealer k or the charger is fault icon is lighting on LCD display and alarm is continuously sounding The icon AN and the icon UPS is overload Remove excess loads from are flashing on LCD UPS output display and alarm is sounding twice every second Fault code is shown as 43 and The The UPS shut down Remove excess loads from icon MAMAA is lighting on LCD automatically because of UPS output and restart it display and alarm is continuously overload at the UPS sounding output Fault code is shown as 14 and The UPS shut down Check output wiring and if alarm is continuously sounding automatically because connected devices are in short circuit occurs on the short circuit status UPS output 16 Fault code is shown as 1 2 3 4 A UPS internal fault has Contact your dealer 11 12 13 and 41 on LCD display occurred and alarm is continuously sounding Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value charged least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon and the warning code FAI flashin
3. UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance Service And Faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shoc
4. to download and install monitoring software 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 2 4 Battery Replacement NOTICE This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads hot swappable battery design Replacement is a safe procedure isolated from electrical hazards CAUTION Consider all warnings cautions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 ia Pull out the battery box by removing two screws on the front panel Step 5 Step 7 a Remove the top cover of After replacing the Re connect the battery wires battery box and replace the batteries put the battery inside batteries box back to original location and screw it tightly Step 8 Put the front panel back to the unit 2 5 Battery Kit Assembly option NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals b
5. 25 26 50 51 75 and EE 76 100 Indicates overload Indicates the load or the UPS output is short circuited Indicates that programmable management outlets are working Indicates that the UPS alarm is disabled il gt J Indicates the UPS powers the output directly from the mains f Indicates the battery charger is working Q A Indicates the UPS is working in boost mode RS Indicates the UPS is working in buck mode 5 ER L Battery information Indicates the Battery level by 0 25 26 50 51 75 and BATTERY 76 100 LOW BATT Indicates low battery B Indicates there is something wrong with battery 3 3 Audible Alarm Sounding every 4 seconds Sounding every second Sounding twice every second Continuously sounding 11 3 4 LCD Display Wordings Index m feoeo Towera O sooo js Stere 3 5 UPS Settinc TOE SF Parameters 2 ANTEE LY NOLE There are two parameters to set up the LOW BATT mca UPS a ur Parameter 1 It s for program L lt m EE m alternatives There are 4 programs to me Ele OO Co set up output voltage setting Parameters 1 programmable outlets enable disable 5 29 ee programmable outlets setting LCD display direction and exit 01 Output voltage setting For 208 220 230 240 VAC models you may choose the following output voltage 208 presents output voltage is 208Vac 220 presents output voltage is 220V
6. P or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 4 Network connection Network Fax Phone surge port IN OUT Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipment with another modem fax phone line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 It s in closed status for UPS normal operation Step 6 External battery connection for long run models only Connect one end of external battery cable to UPS unit and the other end to battery box Use supplied battery detection wire in detection port of UPS unit and plug the other end to battery bank See below chart for detailed connection NOTE Maximum connected external battery boxes up to 4 units Baten Boxe Box Step 7 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown Please follow steps below
7. Y Mode Recharge Time 4 hours recover to 90 capacity Long run Charging Current 4 A 8A 4 A 8A 4 A 8A Model N A N A N A one Charging Voltage 27 4 VDC 1 54 8 VDC 1 82 1 VDC 1 PROTECTION Full Protection ALARM Battery Mode Overload short discharge and overcharge protection Sounding every 10 seconds Low Battery Sounding every second Overload Sounding every 0 5 second Battery Replacement Alarm Fault PHYSICAL ii voel nerweoh wo E ENVIRONMENT Operating Humidity 0 90 RH 0 40 C non condensing Less than 45dB Sounding every second Continuously sounding Noise Level MANAGEMENT Smart RS 232 USB Optional SNMP Derate capacity to 80 of capacity when the output voltage is adjusted to 208VAC Product specifications are subject to change without further notice Supports Windows 2000 2003 XP Vista 2008 Windows 7 Linux Unix and MAC Power management from SNMP manager and web browser 19
8. ac 230 presents output voltage is 230Vac 240 presents output voltage is 240Vac For 110 120 VAC models you may choose the following output voltage 110 presents output voltage is 110Vac 120 presents output voltage is 120Vac ENA Programmable outlets enable DIS Programmable outlets disable 12 03 Programmable outlets setting Setting the backup time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode RAC the LCD display is horizontal TOE the LCD display is vertical 00 Exit setting Steps for setting programmable outlet Step 1 Before entering setting mode the UPS should be in Stand by mode off charging and make sure the battery is connected The LCD display is shown as right Step 2 Press and hold the Selection button for 5 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Press the Up button to change the value to ENA to enable the programmable outlet function Then press Enter button again to confirm the setting 13 Step 4 Press the Up button ON MUTE again to switch to 03 of program list Then press Enter button for setting programmable outlet time Push Up button to change the value of backup time according your demand Then press Enter to confirm the
9. amp model 11 External battery pack numbers detection port 12 Input terminal 13 Output terminal 2 2 Install The UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Put the front panel back to the re connect battery wires unit Rack mount Installation Step 1 f Step 2 Tower Installation 2 3 Setup The UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords Step 2 UPS output connection There two kinds of outputs programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices Step 3 Communication connection Communication ports USB port RS 232 port Intelligent slot To allow for unattended UPS py a eel and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNM
10. g on LCD display Fan is locked or not Check fans and notify and alarm is sounding every working dealer second 17 5 Storage and Maintenance 5 1 Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer he Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 252C 40 C Every 3 months 40 C 45 C Every 2 months 18 6 Specifications 800 VA 1100 VA 1500 VA 2000 VA 2500 VA 3000 VA 640 W 880 W 1200 W 1600 W 2000 W 2400 W 81 145 VAC or 162 290 VAC MODEL CAPACITY INPUT Acceptable Voltage Range Frequency Range 60 50 Hz auto sensing OUTPUT Transfer Time Voltage Regulation Batt Mode 3 before battery alarm Frequency Range Batt Mode 50 Hz or 60 Hz 1 Hz 8 max 100 linear load 15 max 100 non linear load before alarm Transfer Time Typical 2 6 ms 10ms max Waveform Batt Mode Pure Sine Wave EFFICIENCY AC Mode 97 97 Buck amp Boost Mode 90 90 Battery Mode BATTER
11. k and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not dismantle the UPS system 2 Installation And Setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear Panel View 800 1 1K 1 5K 2K Schuko Type O amp 6 a __ TN ss HH sv T ay M A s 6 E O Ka E al E aAA H WEY SSA 2 6 SAS Eaei 1 Programmable outlets connect to non critical loads Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 8 9 1 N USB communication port RS 232 communication port SNMP intelligent slot 0 External battery connector only available for L DOOO
12. ry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near heater Do not block ventilation holes in the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to connect the loads to the UPS system When installing the equipment it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3 5mA 1 4 Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads The
13. setting Step 5 Press Up button ON MUTE to switch to 00 of program list Then press Enter button to exit setting menu Step 6 Disconnect AC input and wait until the LCD display is off The new setting will be activated when turning on the UPS again 3 6 Operating Mode Description ECO mode When the input voltage is within voltage regulated range UPS will power the output directly from the mains ECO is an abbreviation of Efficiency Corrective Optimizer In this mode when battery is fully charged the fan will stop working for energy saving Buck mode When the input voltage is higher than the when AC is voltage regulation range but lower than normal high loss point the buck AVR will be activated Boost mode When the input voltage is lower than the when AC is voltage regulation range but higher than normal low loss point the boost AVR will be activated Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 seconds UPS will backup power from battery 14 Operating mode LCD display Standby mode UPS is powered off and no output supply oap power but still can charge batteries 3 7 Faults Reference Code Fault event Fault code Fault event Bus start fail x Inverter output short x Battery voltage too high X x Bus under aa Battery voltage too low Inverter soft start fail Over temperature Inverter voltage high In
14. turn OFF ENTER off the UPS Button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency SELECT Button Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is off Down key Press this button to display next selection in UPS setting mode ON MUTE Button 3 2 LCD Panel Rack Display Tower Display Load info z5 Battery into Input output EN EE ME EP and Battery N info Battery info Warning amp Fault info Input outpu BATTERY art Setting operation and Battery an inter info Setting operation UPS status Backup UPS status time info LOAD Load info EE Backup time info 10 Display Backup time information Indicates the backup time in pie chart Indicates the backup time in numbers H hours M minute Warning amp Fault information Indicates that the warning and fault occurs Indicates the warning and fault codes and the codes are listed in details in 3 5 section Bg HM ji SS Setting Operation bs Indicates the setting operation Input Output amp Battery information Indicates the output input voltage output input frequency or battery voltage V voltage Hz frequency AHD o Indicates the external battery pack numbers Load information Indicates the load level by 0
15. verter voltage Low 3 8 Warning Indicator Waning O rentas a O wee aA Soraa sod ovas mma Sounding wie every second Battery is not connected aA l o a a ee Overcharge Sounding every second BATTERY Site wiring fault Sounding every second EPO enable EPN Sounding every second Over temperature LP Charger failure CH Fault code Icon OVER LOAD Jo Sounding every second P N Sounding every second H Sounding every second 15 4 Troubleshooting If the UPS system does not operate correctly please solve the problem by using the table below Symptom No indication and alarm even The AC input power is not Check if input power cord though the mains is normal connected well firmly connected to the mains The AC input is connected Plug AC input power cord to the UPS output to AC input correctly EPO function is activated Set the circuit in close position to disable EPO function The icon and the warning code EP flashing on LCD display and alarm is sounding every second Line and neutral Rotate mains power socket conductors of UPS input by 180 and then connect are reversed to UPS system The icon and SF flashing on LCD display and alarm is sounding every second mo a The external or internal Check if all batteries are l 10 melon and flashing battery is incorrectly connected well on LCD display and alarm is connected sounding every second
16. y following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells and insert one below chart Then battery kit is assembly well more defect battery on the space 4 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells below chart Then battery kit is assembly well 3 Operations 3 1 Button Operation Lewmure ff secer h ferrem o o gt Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS gt Mute the alarm After the UPS is turned on in battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But its not applied to the situations when warnings or errors occur Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON Mute button for 5 seconds to enter UPS self testing while in AC mode Turn off the UPS Press and hold this button at least 2 seconds to