1. D w inthe replacement battery packing material REMOVING BATTERY MODULES 1 2 15 REPLACING BATTERY MODULES Disconnecting the Battery for Transport Always DISCONNECT THE BATTERY s before shipping in compliance with U S Department of Transportation DOT and IATA regulations The battery s may remain in the UPS 1 Shut down and disconnect any equipment attached to the UPS 2 Shut down and disconnect the UPS from the power supply 3 Unplug the battery connectors Refer to Replacing Battery modules in this manual For shipping instructions contact APC at the Web site www apc com T ROUBLESHOOTING SERVICE AND WARRANTY INFORMATION Use the table below to solve minor installation and operation problems Refer to the APC Web site Wwww apc com for assistance with complex UPS problems PROBLEM AND POSSIBLE CAUSE SOLUTION UPS WILL NOT TURN ON Battery not connected properly button not pushed UPS not connected to utility power supply Very low or no utility voltage Check that the battery connectors are fully engaged Press the button once to power the UPS and the connected equipment Check that the power cable from the UPS to the utility power supply is securely connected at both ends Check the utility power supply to the UPS by plugging in a table lamp If the light is very dim have the utility voltage checked UPS WILL NOT TURN OFF button not pushed
2. Internal UPS fault Press the button once to turn the UPS off Do not attempt to use the UPS Unplug the UPS and have it serviced immediately UPS BEEPS OCCASIONALLY Normal UPS operation when running on battery None The UPS is protecting the connected equipment UPS DOES NOT PROVIDE EXPEC TED BACKUP TIME The UPS battery s are weak due to a recent outage or battery s are near the end of their service life Charge the battery s Battery modules require recharging after extended outages They wear faster when put into service often or when operated at elevated temperatures If the battery s are near the end of their service life consider replacing the battery s even if the Replace Battery LED is not illuminated FRONT PANEL LEDs FLASH SEQ UENTIALLY The UPS has been shut down remotely through software or an optional accessory card None The UPS will restart automatically when utility power returns ALL LEDs ARE OFF AND THE UPS IS PLUGGED INTO A WALL OUTLET The UPS is shut down and the battery is discharged from an extended outage None The UPS will return to normal operation when the power is restored and the battery has a sufficient charge BYPASS AND OVERLOAD LEDs ILLUMINATE UPS EMITS A SUSTAINED ALARM TONE The UPS is overloaded The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site www apc com The
3. If circuit standard cannot be confirmed use a contact closure switch Use one of the following cable types to connect the UPS to the EPO switch e CL2 Class 2 cable for general use e CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air e CL2R Riser cable for use in a vertical run in a floor to floor shaft e CLEX Limited use cable for use in dwellings and for use in raceways e Por installation in Canada Use only CSA certified type ELC extra low voltage control cable 11 TERMINAL MODE TO CONFIGURE UPS PARAMETERS 3000 VA models Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing to use PowerChute software or an optional Network Management Card Connect the serial cable to the serial com connector on the back of the UPS If PowerChute software is not installed do not perform steps and 7 1 For Windows users STOP the PowerChute Server using the following steps e From the Desktop go to Start gt Settings gt Control Panel gt Administrative Tools gt Services e Select APC PowerChute Server right click the mouse and select Stop la For Linux users STOP the PowerChute Server using the following steps e Change directory to etc init d e Initiate the command PowerChute stop 2 Open a terminal program Example HyperTerminal e From the Desktop go to Start gt Programs gt Accessories gt Communication gt HyperTermin
4. Last Battery Manufacture date Date of Reset this date when you replace Replacement battery replacement the battery modules Minimum Run time 0 seconds 0 to 3600 s of run time Specify the minimum run time Before Return from following a low battery Shutdown shutdown before powering connected equipment Audible Alarm ON ON OFF Enable or disable all alarms Setting permanently Simple Shutdown 90 seconds 0 to 1800 s Set the interval between the time Delay when the UPS receives a simple shutdown command and the actual shutdown Simple Low Run 150 seconds 0 to 1800 s Change the warning interval Time Warning default to a higher setting if the operating system requires a longer interval for shutdown The low battery warning beeps are continuous when 150 seconds of run time remain High Bypass Point Output Voltage Setting Maximum voltage that the UPS 255 VAC 200 VAC will pass to connected 210 280 VAC equipment during internal 208 VAC bypass operation 220 280 VAC 220 VAC 235 280 VAC 230 VAC 245 280 VAC 240 VAC 255 280 VAC NOTE SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE FACTORY USER SELECTABLE DESCRIETION DEFAULT CHOICES FUNCTION Low Bypass Point Output Voltage Output Frequency Number of External Battery Packs Bypass Acceptable 160 VAC XLJ models 200 VAC XLT models 208 VAC XLTW models 220 VAC XLI
5. 5000 VA 200 240 VAC Tower Rack Mount 3U English 2010 APC by Schneider Electric APC the APC logo Smart UPS and PowerChute are owned by Schneider Electric Industries S A S American Power Conversion Corporation or affiliated companies All other trademarks are the property of their respective owners 990 2690B 06 2012 Introduction The APC by Schneider Electric Smart UPS RT is a high performance uninterruptible power supply UPS that provides protection for electronic equipment from utility power blackouts brownouts sags and surges The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged INSTALL ATION Read the Safety Guide before installing the UPS Unpacking Inspect the UPS upon receipt Notify the carrier and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Check the package contents UPS with battery modules disconnected m XLT XLI XLTW models m Front bezel PowerChute software CD m Literature kit containing m Serial cable m Product documentation m 3000 VA XLI models two output power cords m Smart UPS RT User Manuals CD two input power cords gr Watney Information m 3000 VA models conversion faceplate for acco
6. Arc SS H by Schneider Electric a I Stallation and Operation SC Smart UPS RT Uniterruptible Power Supply SURTD3000 5000 XL 200 240 VAC Tower Rack Mount 3U This manual and the safety guide are available in English on the enclosed CD and the APC Web site www apc com cy z TDL bann CD D APC Wii Cep apc com Lak AHS ZEH PARAR KROJ DAEBEMTAY CD 9 APC EA www apc com FISAF E Ha PTH SHAR U ivatelsk p ru ka a bezpe nostn pokyny jsou k dispozici v e tin na p ilo en m CD a na webov ch str nk ch APC www apc com Denne vejledning og sikkerhedsvejledningen er tilg ngelige pa dansk pa den vedlagte CD og pa APC s websted www apc com Deze handleiding en het veiligheidshandboek staan in het Nederlands op de bijgevoegde cd en op de APC website www apc com Ce manuel et le guide de s curit sont disponibles en frangais sur le CD ROM ci inclus et sur le site Web d APC www apc com Dieses Handbuch sowie die Sicherheitsrichtlinien sind in deutscher Sprache auf der beiliegenden CD und auf der Website von APC unter www apc com verf gbar To eyyeipidio avtd Kal o o ny aopdAEias siva goung OTA EAANVIKG oto CD mov EoMKAsisTAl Kat Om LOTOGEAIS TG APC www apc com A haszn lati utas t s s a biztons gi tmutat megtal lhat magyarul a csatolt CD n s az APC honlapj n www apc com Panduan dan petunjuk keselamatan ini tersedia dalam
7. Bahasa Indonesia pada CD terlampir dan pada Situs web APC www apc com Il presente manuale e la corrispondente Guida per la sicurezza sono disponibili in italiano sul CD ROM allegato e sul sito Web di APC all indirizzo www apc com EROZEHA FOARE AHO CD RU APC O Web 47 b www apc com 265 CHERRIES DI WFS OA BOISE SSE CD St APC WAE www apc com AA H282 OSS USUC En norsk versjon av denne handboken og sikkerhetsveiledningen finnes pa den vedlagte CD en og pa APCs webomrade www apc com Instrukcja obs ugi oraz przewodnik bezpiecze stwa w j zyku polskim dost pne s na za czonej p ycie CD i na stronie internetowej APC www apc com Este manual e o guia de seguran a est o disponiveis em portugu s no CD incluso e no website da APC www apc com Pycckaa BepcHa JaHHOro pyKOBOJCTBA H PyKOBOCTBA DO TeEXHUKe Oe30NaCHOCTH HMEETCA Ha MpHJIATaAeMOM KOMIaKT JUCKe a Taloke Ha calite komnannn APC www apc com Este manual y la guia de seguridad estan disponibles en espa ol en el CD adjunto y en el sitio Web de APC www apc com Denna manual och sakerhetsguide finns tillg nglig pa svenska pa medf ljande CD och pa APC s webbsida www apc com Anuunthdruanmnaastuuasdiletiiunralne mungli Auau APC www apc com Bu k lavuzun ve g venlik k lavuzunun T rk e versiyonu r nle birlikte verilen CD de ve www apc com adresindeki APC web sitesinde bulunmaktad r Smart UPS RT Uninterruptible Power Supply SURTD 3000
8. ECTING EQUIPMENT AND POWER TO THE UPS 2 Connect equipment to the UPS cables not included for XLJ XLT XLTW models Avoid using extension cords e 3000 VA XLJ XLT XLI XLTW and 5000 VA XLJ XLT XLTW models Using a power cord plug the UPS into a two pole three wire grounded receptacle only e 5000 VA XLJ models To draw full 5000 VA from the UPS have a qualified electrician cut off the input plug and hardwire the UPS to the appropriate power panel 3 Turn on all connected equipment To use the UPS as a master ON OFF switch ensure all connected equipment is switched ON The equipment will not be powered until the UPS is turned on 4 To power up the UPS press the button on the front panel The UPS battery charges when it is connected to utility power The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period 5 For additional computer system security install PowerChute Server Smart UPS monitoring software OPTIONS Refer to the APC Web site www apc com for available accessories SI Q Q LI External Battery Pack SURT192XLBP Rail Kit SURTRK2 Isolation Transformer Service Bypass Panel OPERATION SMART UPS RT FRONT DISPLAY Load Battery Charge 085 H d 096 068 072 051 Z Se 048 034 o Q 024 017 0 lt 24 T DG ove Indicator Description Online The
9. NNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL Basic CONNECTORS KA serial com The serial connector is to be used for interfacing with APC PowerChute software and terminal emulation software Use only cables approved by APC Any other interface cable will be incompatible with the UPS connector O i normal bypass Manual bypass enables the user to manually put connected equipment into bypass mode Emergency Power Off terminal allows the user to connect the UPS to the central EPO system EPO terminal The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lead on surge suppression devices such as telephone TVSS screw and network line protectors When connecting grounding cable disconnect the unit from the utility power outlet i Ba peyi hag r external battery pack connector Optional external battery packs provide extended run time during power outages These units support up to ten external battery packs See the APC Web site www apc com for the information on the external battery pack SURT192XLBP 5000 VA XLI models output circuit IEC 320 C19 IEC 320 C13 16 A per 10 A per Receptacle Receptacle a lt a breakers 3000 5000VA XLJ XLT XLTW L6 No Circuit Breaker aS 250 V 20 A L6 30 x2 250 V 30 A x2 ben output circuit breakers CONN
10. Online LED illuminates when the UPS is drawing utility power and performing A double conversion to supply power to connected equipment On Battery The UPS is supplying battery power to the connected equipment Bypass The Bypass LED illuminates indicating that the UPS is in bypass mode Utility zie power is sent directly to connected equipment during bypass mode operation Bypass mode operation is the result of an internal UPS fault an overload condition or a user initiated command either through an accessory or the manual bypass switch Battery operation is not available while the UPS is in bypass mode Refer to Troubleshooting in this manual The UPS detects an internal fault Fault ee X Refer to Troubleshooting in this manual Overload An overload condition exists See Troubleshooting Replace The battery is disconnected or must be replaced See Troubleshooting Battery Feature Function Power On Press this button to turn on the UPS See below for additional capabilities Power Off Press this button to turn off the UPS Feature Function Cold Start When there is no utility power and the UPS is off press and hold the button to power up the UPS and connected equipment The UPS will emit two beeps During the second beep release the button Self Test Automatic The UPS performs a self test automatically when turned on and every two weeks thereafter by default During t
11. S emits short beeps for one minute and the Replace Battery LED illuminates The UPS repeats the alarm every five hours Perform the self test procedure after the battery has charged for 24 hours to confirm the Replace Battery condition The alarm stops and the LED clears if the battery passes the self test UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS Very high low or distorted line voltage Inexpensive fuel powered generators can distort the voltage Move the UPS to a different outlet on a different circuit Test the input voltage with the utility voltage display DIAGNosTic UTILITY VOLTAGE All five LEDs are illuminated The line voltage is extremely high and should be checked by an electrician There is no LED illumination If the UPS is plugged into a properly functioning utility power outlet the line voltage is extremely low ONLINE LED There is no LED illumination The UPS is running on battery or it is not turned on The LED is blinking The UPS is running an internal self test 18 Service If the UPS requires service do not return it to the dealer Follow these steps 1 Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems 2 Ifthe problem persists contact APC Customer Support through the APC Web site www apc com e Note the model number of the UPS the serial number located on the back of the unit a
12. ainst harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference The user is responsible for correcting the interference Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits CORB SRUBRES SRS ALAR BAVCCIOBEC EIR AAR RiRECt CORBGRERRCGATSCRRMSRCERCTCEABWET COBSCAEAEAMYSWReBTSASERENSCEMSBWET VCCI A APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways e Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests e www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information e www apc com support Global support searching APC Knowledge Base and using e support e Contact an APC Customer Support center by telephone or e mail Local country specific centers go to www apc com support contact for information Contact the APC representative or other distributor from whom you purchased your APC
13. al 3 Double click on the HyperTerminal icon e Follow the prompts to choose a name and select an icon Disregard the message must install a modem if it is displayed Click OK e Select the COM port that is connected to your UPS The port settings are v bits per second 9600 data bits 8 parity none stop bit 1 flow control none e Press ENTER Press 1 to modify the UPS parameters BE RR Follow the prompts Exit the terminal program SON R For Windows users START the PowerChute Server using the following steps e From the Desktop go to Start gt Settings gt Control Panel gt Administrative Tools gt Services e Select APC PowerChute Server right click the mouse and select Start 7a For Linux users START the PowerChute Server using the following steps e Change directory to etc init d e Initiate the command PowerChute start 5000 VA models Terminal Mode is a menu driven interface that enables configuration of the UPS by users not using PowerChute software or the installed Network Management Card interfaces Connect the serial cable to the serial port on the back of the UPS If PowerChute software is not installed do not perform steps and 5 1 For Windows users STOP the PowerChute Server using the following steps e From the Desktop go to Start gt Settings gt Control Panel gt Administrative Tools gt Services e Select APC PowerChute Server right click the mous
14. alarm remains on until the overload is removed Disconnect nonessential equipment from the UPS to eliminate the overload condition 17 PROBLEM AND POSSIBLE CAUSE SOLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory If bypass is the chosen mode of operation ignore the illuminated LED If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS to the normal position FAULT AND OVERLOAD LEDs ILLUMINATE UPS EMITS A SUSTAINED ALARM TONE The UPS has ceased sending power to connected equipment The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site www apc com Disconnect nonessential equipment from the UPS to eliminate the overload condition Press the OFF button then the ON button to restore power to connected equipment FAULT LED ILLUMINATES Internal UPS fault Do not attempt to use the UPS Turn the UPS off and have it serviced immediately REPLACE BATTERY LED ILLUMINATES Replace Battery LED flashes and short beep is emitted every two seconds to indicate the battery is disconnected Weak battery Failure of a battery self test Check that the battery connectors are fully engaged Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery The UP
15. e and select Stop la For Linux users STOP the PowerChute Server using the following steps e Change directory to etc init d e Initiate the command PowerChute stop 2 Open a terminal program Example HyperTerminal e From the Desktop go to Start gt Programs gt Accessories gt Communication gt HyperTerminal 3 Double click on the HyperTerminal icon e Follow the prompts to choose a name and select an icon Disregard the message must install a modem if it is displayed Click OK e Select the COM port that is connected to your UPS The port settings are v bits per second 9600 v data bits 8 v parity none v stop bit 1 v flow control none e Press ENTER 4 Example for setting the number of external battery packs SURT192XLBP Once the blank terminal window is open follow these steps to enter the number of battery packs e Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User Name is displayed Follow the prompts Type slowly waiting until each character appears on the screen prior to typing the next character Network Management Card defaults e User Name apc e Password apc e Press 1 and ENTER to select Device Manager e Select the model by entering the corresponding number then press ENTER e Press 3 and ENTER to select Configuration e Press 1 and ENTER to select Battery 13 Sa e Press 2 and ENTER to change the Battery Settings e Type in the number
16. er from customer support Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise 19 RADIO FREQUENCY WARNINGS This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection ag
17. he self test the UPS briefly operates the connected equipment on battery Manual Press and hold the button for a few seconds to initiate the self test 220V 0256 0238 0219 0200 0181 200V 0 236 0217 0199 0180 0161 Diagnostic Utility Voltage 208V 0245 0226 0207 0189 0170 ELE 230V 240V 0266 0276 0248 0258 0229 0210 0192 0239 0220 0202 EE E The UPS has a diagnostic feature that displays the utility voltage Plug the UPS into the normal utility power The UPS starts a self test as part of this procedure The self test does not affect the voltage display Press and hold the button to view the utility voltage bar graph display The five LED Battery Charge L_ display on the right of the front panel shows the utility input voltage Refer to the figure at left for the voltage reading values are not listed on the UPS The display indicates the voltage is between the displayed value on the list and the next higher value USER CONFIGURABLE ITEMS NOTE SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE FACTORY USER SELECTABLE FUNCTION DEFAULT CHOICES DESCRIPTION Automatic Self Test On start up and On start up and every 7 Set the interval at which the every 14 days days thereafter UPS will execute a self test thereafter On start up and every 14 days thereafter On start up only No self test Date of
18. mmodating a Network Management Card m 5000 VA XLI models four output power cords Network Management Card documentation Specifications TEMPERATURE This unit is intended for indoor use only OPERATING 32 to 104 F 0 to 40 C Select a location sturdy enough to STORAGE 5 to 113 F 15 to 45 C charge the UPS handle the weight battery every six months Do not operate the UPS where there is Maximum excessive dust or the temperature and ELEVATION humidity are outside the specified limits OPERATING 10 000 ft 3 000 m Ensure that the air vents on the front STORAGE 50 000 ft 15 240 m and rear of the UPS are not blocked HumiDITy 0 to 95 relative humidity WEIGHT bA UPS 120 Ibs 55 kg UPS WITH 140 lbs 64 kg PACKAGING Wiring and Connecting the UPS 5000 VA XLI MODELS ONLY HARDWIRING INSTRUCTIONS ZS 5 6 Wiring must be performed by a qualified electrician Install a high magnetic 30 32 A utility circuit breaker Adhere to all national and local electrical codes Use 10 AWG gauge 5 mm wire Switch the utility circuit breaker OFF Remove the input access panel Remove circular knockout Run 10 AWG gauge 5 mm wire through the access panel and connect the wires to the terminal block Green Ground Brown Hot Blue Neutral Use an appropriate strain relief not included Switch the utility circuit breaker ON Check line voltages Replace the access panel CO
19. models 230 VAC Automatic 50 3 Hz or 60 3 Hz Not required Output Voltage Setting 200 VAC 160 185 VAC 208 VAC 160 190 VAC 220 VAC 160 195 VAC 230 VAC 160 200 VAC 240 VAC 160 205 VAC 200 208 220 230 240 VAC 50 3 Hz 50 1 Hz 60 1 Hz 50 0 1Hz 60 0 1 Hz 50 3 Hz or 60 3 Hz 60 3 Hz 0 to 100 Required Not required 10 Minimum voltage that the UPS will pass to connected equipment during internal bypass operation Allows the user to select the on on line output voltage Sets the allowable UPS output frequency Whenever possible the output frequency tracks the input frequency Defines the number of external connected battery packs for proper run time prediction Phase and frequency lock required not required before the UPS will switch to bypass CONNECTING THE EPO EMERGENCY POWER OFF OPTION The output power can be disabled in an emergency by closing a switch connected to the EPO Adhere to National and local electrical codes when wiring the EPO EPO switch The EPO switch is internally powered by the UPS for use with non powered switch circuit breakers The EPO circuit is considered a Class 2 circuit UL CSA standards and a SELV circuit IEC standard Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV
20. nd the date purchased If you call APC Customer Support a technician will ask you to describe the problem and attempt to solve it over the phone If this is not possible the technician will issue a Returned Material Authorization Number RMA e Ifthe UPS is under warranty repairs are free e Procedures for servicing or returning products may vary internationally Refer to the APC Web site for country specific instructions 3 Pack the UPS in its original packaging e Ifthe original packing is not available refer to the APC Web site www apc com for information about obtaining a new set e Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transit is not covered under warranty Always DISCONNECT THE BATTERY S before shipping in compliance with U S Department of Transportation DOT and IATA regulations The battery s may remain in the UPS 4 Mark the RMA on the outside of the package 5 Return the UPS by insured prepaid carrier to the address given to you by Customer Support Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a Returned Material Authorization RMA numb
21. of external battery packs four battery modules per pack and press ENTER Number of packs 1 1 SURT192XLBP 2 2 SURT192XLBP etc e Press 3 and ENTER to accept the changes e Press ESC multiple times 5 to return to the main menu e Press 4 and ENTER to log out For Windows users START the PowerChute Server using the following steps e From the Desktop go to Start gt Settings gt Control Panel gt Administrative Tools gt Services e Select APC PowerChute Server right click the mouse and select Start For Linux users START the PowerChute Server using the following steps e Change directory to etc init d e Initiate the command PowerChute start MAINTENANCE AND TRANSPORT Replacing the Battery Module This UPS has an easy to replace hot swappable battery module Replacement is a safe procedure isolated from electrical hazards You may leave the UPS and connected equipment on during the procedure See your dealer or contact APC at the Web site www apc com for information on replacement battery modules The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack s Once the battery s are disconnected the connected equipment is not protected from power outages Be careful during battery replacement the battery modules are heavy Sei Be sure to deliver spent batteries to a recycling facility or ship to the manufacturer Go
22. product for information on how to obtain local customer support 20