Riello Vision Dual 1500
Contents
1. 5 Battery pack connector 6 Battery pack retention panel REAR VIEW 000000 N 2 A SP Y Model 1100VA 1500VA Communication port RS232 USB communication port IEC 16A output socket Communication Card Slots Cooling fans Remote control terminal board J99 G AOE e e OOG e Model 2200VA 3000VA Battery expansion connector optional IEC 10A output socket IEC 16A input plug IEC 10A input plug Circuit breaker DISPLAY PANEL VIEW 9 IN OUT BATT LOAD TEMP FAULT LOCK SET anu m OO 12 nh gt LOAD c DOM SEL button Select ON button STAND BY button Regular operation Mains operation Battery operation AVR active Battery charge indicator 49 42 IN OUT BATT LOAD TEMP FAULT LOCK SE seas AO 2 12 VAN Hz min Load level indicator Configuration area Maintenance request Timer Measurement display area Stand by alarm EnergyShare BATTERY BOX ACCESSORY NOT SUPPLIED WITH THE UPS The BATTERY BOX is an optional accessory for this range of UPS same dimensions and aesthetic appearance The BATTERY BOX contains batteries which allow the operating time of the uninterruptible power supplies to be increased during extended blackouts The numb
2. 4 Slip off the battery pack pulling it towards the outside as shown in the figure below Be careful when extracting and lifting up the battery pack as it is heavy ATTENTION the new battery pack must contain the same number and type of batteries see the label located on the battery pack near the connector 5 Insert the new battery pack into the compartment sliding it into the UPS Put the battery pack retention panel back in position and secure it with the two screws removed previously Connect the battery pack cable to the UPS and close the front panel Set the UPS to normal operation mode by pressing ON SEL for at least 4 seconds 6 Make sure that the display does not show the code C02 7 Press the ON key for 5 seconds to start the battery status verification procedure 24 TROUBLESHOOTING Irregular UPS operation is not always an indication of a fault and can be due to minor or easy to resolve issues It is therefore advisable to consult the table below as it contains information which is useful for solving the most common UPS problems PROBLEM POSSIBLE CAUSE SOLUTION ON OFF SWITCH NOT PRESSED Press the ON OFF switch on the front panel MAIN CONNECTION CABLE MISSING Check that the power cable is connected correctly THE DISPLAY DOES NOT LIGHT UP NO MAINS
3. INSTALLATION INITIAL CONTENT CHECK INSTALLATION ENVIRONMENT BATTERY BOX INSTALLATION SETTING THE NOMINAL BATTERY CAPACITY TOWER VERSION TOWER VERSION WITH BATTERY BOX RACK VERSION USE CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME SWITCHING ON FROM THE MAINS SWITCHING ON FROM THE BATTERY SWITCHING OFF THE UPS DISPLAY PANEL MESSAGES UPS STATUS MESSAGES MEASUREMENT DISPLAY AREA CONFIGURING THE OPERATING MODE POSSIBLE SETTINGS ADDITIONAL FUNCTIONS SOFTWARE MONITORING AND CONTROL SOFTWARE CONFIGURATION SOFTWARE UPS CONFIGURATION COMMUNICATION PORTS RS232 CONNECTOR COMMUNICATION SLOT N 0 Q 10 10 11 11 11 12 13 14 15 15 15 15 15 16 16 17 18 18 18 20 20 20 21 22 22 22 BATTERY PACK REPLACEMENT TROUBLESHOOTING ALARM CODES FAULT Lock TECHNICAL DATA 23 25 27 27 28 29 PRESENTATION The VISION DUAL series is the ideal solution for high end users who require high security and versatility from their power systems The VISION DUAL is the best protection system available for network devices servers and conventional storage systems The VISION DUAL series is a range of UPS which utilises the very latest Line Interactive technology and sinusoidal output voltage waveforms This technology allows high efficiency and reduced energy consumption whilst guaranteeing a high level of protection against disturbances from the mains supply This family was designe
4. 450 87 x 625 x 450 Weight Kg 28 15 5 31 5 16 5 For additional details regarding technical data refer to website www riello ups com Protection devices 7 rated load rated voltage of 220 Vac battery charging To maintain output voltage within the accuracy range specified recalibration may be necessary after a long period of operation 99 20 25 C for longer battery life The dimensions listed in the table refer to the tower version taking into account the support feet The rack version is suitable for being housed in 19 cabinets with an overall size of 2U 29 BATTERY BOX MODELS JSDH072 NPA JSDH072 NPM Battery rated voltage Vdc 72Vdc Dimensions W x D x H mm 87 x 625 x 450 The symbol replaces an alphanumeric code for internal use If the UPS is connected to a battery box the maximum active power is derated from PF 0 9 to PF 0 8 30 RIELLO ELETTRONICA Fl rielloups www riello ups com RPS SpA Riello Power Solutions Viale Europa 37045 Legnago VR Italy OMNVSD1K1RUENUA
5. for at least 4 sec The code C02 appears on the display To return to the normal operation mode press the ON and SEL keys again for at least 4 sec PROGRAMMABLE AUXILIARY SOCKET EnergyShare The EnergyShare sockets are outlets that allow for the automatic disconnection of the load applied to them in certain operating conditions The events that determine automatic disconnection of the EnergyShare sockets can be selected by the user through the UPSTools configuration software For example it is possible to select disconnection after a certain period of battery operation or when the pre alarm threshold for battery discharge has been reached or when an overloading event occurs By default the Energyshare sockets are not configured and therefore function as other outlets The EnergyShare function is associated with an icon on the display whose meaning is explained in the paragraph entitled Display panel indications The presence and the number of these sockets depend on the UPS type and they are distinguished by a different colour with respect to other sockets 18 REMOTE CONTROL TERMINAL BOARD The remote control terminal allows for implementation of the REPO function Remote Emergency Power Off and to remotely switch on off the UPS The UPS is provided by the manufacturer with the REPO terminals short circuited For installation remove the short circuit and connect to the device s normally closed contact In case of an emergency if t
6. longer than 10 metres CAUTION do not connect equipment which absorbs more than 10A to the IEC 10A sockets For equipment which exceeds this level of absorption use the IEC 16A socket only available on the 2200 3000VA version 6 Check which operating mode is set on the display and if necessary see the Configuring operating modes paragraph to set the required mode For advanced UPS configurations execute the software UPSTools which can be downloaded from the web site www riello ups com SWITCHING ON FROM THE MAINS 1 Press the ON button for 1 second After pressing it all the icons on the display light up for 1 second and the UPS beeps 2 Switch on the equipment connected to the UPS When switching on for the first time only after 30 seconds check that the UPS is operating correctly 1 Simulate a blackout by disconnecting power to the UPS 2 The load must continue to be powered the icon on the display must light up and there must be a beep every 4 seconds 3 When power is reconnected the UPS must go back to operating from the mains SWITCHING ON FROM THE BATTERY 1 Press the ON OFF switch located on the front panel 2 Hold down the ON button for at least 5 seconds All the icons on the display light up for 1 second 3 Switch on the equipment connected to the UPS SWITCHING OFF THE UPS In order to switch off the UPS hold down the STBY button for at least 2 seconds The UPS goes back to stand by mo
7. not exceed 40 C THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES F53 L53 THERE IS A FAULT ON ONE OR MORE OF THE UTILITIES POWERED BY THE UPS Disconnect all the utilities switch the UPS off and back on again reconnect the utilities one at a time to identify which one is faulty THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS THE UPS IS If possible disconnect the power to the load switch the ONE OF THE FOLLOWING MALFUNCTIONING UPS off and back on again if the problem occurs again CODES F60 L05 L07 call the support centre L13 L20 L21 L40 L41 L42 L43 THE DISPLAY SHOWS ONE THE FOLLOWING A REMOTE COMMAND IS If unwanted check the status of the command inputs on CODES C01 C02 C03 ACTIVE any optional contact card THE DISPLAY SHOWS THE BATTERY SWAP To exit from the battery swap mode press and hold the 02 IS ACTIVATED ON SEL buttons for at least 4 seconds ATTENTION The UPS in case of a permanent failure will be not able to supply the load To ensure total protection of your equipment we suggest you install an ATS device Automatic Transfer Switch or an external automatic by pass For more information visit www riello ups com 26 s ALARM CODES Using a sophisticated self diagnosis system the UPS is able to check its own status for any anomalies and or faults which may occur during normal operation and display them on the dis
8. special housing Wl 3 At this point with the UPS or battery box in the horizontal position secure the handles using the screws provided as shown in the figure NOTE Given the heavy weight the use of support brackets is mandatory during rack installation guide with L shaped support For the same reason it is recommended that the UPS and battery box be installed in the lower part of the rack cabinet 14 SE ___ CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 1 Check that there is a protection device against overcurrents and short circuits in the system upstream from the UPS The recommended protection value is 10A for the 1100VA and 1500VA versions and 16 for the 2200VA 3000VA and ER versions with a B or C trip curve 2 Power the UPS using the input cable provided 3 Press the ON OFF switch located on the front panel 4 After a few moments the UPS will switch on the display will light up there will be a beep and the A icon will start to flash The UPS is in stand by mode meaning that it is only consuming a small amount of power The microcontroller supervising the self diagnoses is powered the batteries are charging and everything is ready for UPS activation Battery operation is also in stand by mode provided that the timer is active 5 Connect the equipment to be powered into the sockets on the back of the UPS using the cable supplied or a cable no
9. www riello ups com 20 UPS CONFIGURATION The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for individual requirements It is possible to perform these operations using the UPStools software FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS e 50 Hz e 60 Hz e Auto automatic learning of the input frequency Output voltage e the nominal output 230V 220 240 in 1V steps e L I ECO OTHER MODE Output Selects the nominal output frequency frequency Select one of the available Operating mode operating modes Automatic UPS power off in battery operation mode if Disabled sedes the charge is lower than 596 Autonomy limit Maximum battery operation Disabled x complete battery discharge time 65000 sec in 1 sec steps Estimated autonomy time remaining for the battery in 1 255 min in 1 min steps low warning Interval of time for the e Disabled automatic battery test e 1 1000 h in 1 hour steps Maximum charge Selects the user overcharge Disabled uer alarm threshold limit 103 in 196 steps e Always connected e Disconnection after no seconds of battery Select the auxiliary socket Always operation operating mode connected e Disconnection after no seconds of the battery discharge pre alarm signal e see UPStools manual Power off due to minimum charge Battery low warning EnergyShar
10. TCP IP HTTP and SNMP protocols e JBUS MODBUS protocol converter card e PROFIBUS protocol converter card e Card with relay isolated contacts TA To check the availability of other accessories visit the website www riello ups com 22 BATTERY PACK REPLACEMENT The UPS is also equipped with a dedicated battery pack that allows for easy replacement of batteries hot swap in complete safety thanks to the protected connection system e WHEN THE BATTERY PACK IS DISCONNECTED THE LOADS CONNECTED TO THE UPS ARE NOT PROTECTED IN THE EVENT OF A MAINS FAILURE e THE BATTERY PACK IS VERY HEAVY USE EXTREME CAUTION WHEN REPLACING IT Set the UPS to battery swap mode manually by pressing the ON SEL buttons for 4 seconds see paragraph entitled USE Configuration of Operating Mode The display should show the message C02 NOTE in this condition the load is powered from mains 4 sec Sel 2 The battery pack is positioned behind the UPS front panel Remove the front panel as shown in the figure below A Remove the screws from the battery pack s retention panel B Disconnect the connector that connects the battery pack to the UPS 23 3 Remove the battery pack s retention panel carrying out the operations shown in the figure below
11. UZZER SOUNDS CONTINUOUSLY AND Reduce the load to within the threshold of 100 or user THE DISPLAY SHOWS THE LOAD APPLIED TO threshold in the case of code A54 ONE OF THE FOLLOWING THE UPS IS TOO HIGH If the display shows a lock remove the load and switch CODES A54 F50 F51 the UPS off and back on again F52 L50 L51 L52 THE DISPLAY SHOWS THE FOLLOW CODE A61 REPLACE THE BATTERIES Contact the support centre for battery replacement On the versions with an additional battery charger in place of the batteries check that the Battery Box is inserted and connected to the UPS correctly THE DISPLAY SHOWS BATTERY MISSING OR NOT THE FOLLOW CODE A62 CONNECTED THE BATTERIES ARE FLAT THE UPS IS WAITING FOR Wait until the batteries have recharged or force power THE BATTERY VOLTAGE on manually by holding down the ON button for at least TO EXCEED THE SET 2 seconds THRESHOLD THE DISPLAY SHOWS THE FOLLOW CODE A63 THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS THE FOLLOW CODE F38 THE UPS IS If possible disconnect the power to the load switch the MALFUNCTIONING IT WILL UPS off and back on again if the problem occurs again PROBABLY LOCK SOON call the support centre THE BUZZER SOUNDS CONTINUOUSLY THE TEMPERATURE OF THE DISPLAY SHOWS THE HEATSINKS INSIDE ONE OF THE FOLLOWING THE UPS IS TOO HIGH CODES F04 L04 Check that the temperature of the environment in which the UPS is located does
12. VOLTAGE Check that the power reaches the socket where the UPS BLACKOUT is connected try it with a table lamp for example If present reset the circuit breaker by pressing the INTERVENTION OF THE button on the back of the UPS INPUT CIRCUIT BREAKER CAUTION Check that there is no output overload to the UPS THE UPS IS IN STAND BY Press the ON button on the front panel to power the MODE loads THE DISPLAY IS ON BUT THE LOAD IS NOT POWERED NO CONNECTION TO THE LOAD Check the connection to the load THE INPUT VOLTAGE IS OUTSIDE THE PERMITTED Problem with the mains Wait until the input mains TOLERANCE RANGE FOR voltage returns within the tolerance range The UPS will THE UPS IS OPERATING MAINS OPERATION automatically return to mains operation FROM THE BATTERY us Nei If present reset the circuit breaker by pressing the INTERVENTION OF THE button on the back of the UPS INPUT CIRCUIT BREAKER CAUTION Check that there is no output overload to the UPS THE UPS DOES NOT COME ON AND THE DISPLAY SHOWS THE CODE A06 A08 THE TEMPERATURE OF Check the temperature of the environment in which the THE UPS IS LOWER THAN UPS is located if it is too low bring it past the minimum 0 C threshold 0 C THE DISPLAY SHOWS THE FOLLOW CODES INPUT RELAY FAULTY L11 Switch off and disconnect the UPS from the power supply and contact the support centre 25 PROBLEM POSSIBLE CAUSE SOLUTION THE B
13. apter describes the steps for preparing the UPS and battery box for tower version use ATTENTION For your safety and that of the product you must carefully follow the instructions given here below BEFORE YOU CARRY OUT THE FOLLOWING SEQUENCE OF OPERATIONS MAKE SURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD Once removed from the packaging the UPS is already preset for installation in the tower configuration To complete the configuration simply mount the UPS on the two support feet Each leg consists of two parts connecting to each other at joints To put a leg together proceed as shown in the figure Assemble two legs and secure the UPS on top of them as shown in the figure below TETETETETETSTETETETE LAI E d MA 12 TOWER VERSION WITH BATTERY BOX BEFORE CARRING OUT THE FOLLOWING SEQUENCE OF OPERATIONS ENSURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD e THE BATTERY BOX IS DISCONNECTED FROM THE UPS FROM ANY OTHER BATTERY BOXES AND WITH THE BATTERY ISOLATOR OPEN For the battery box version each foot is composed of three parts two supports and an extension Assemble two feet as ind
14. d with versatility in mind allowing for installation in both tower and rack positions The following shows how the product can be installed in the two different positions The UPS is also equipped with a dedicated battery pack that allows for easy battery replacement hot swap in complete safety thanks to the protected connection system It is possible to use one or more autonomy expansion units known as BATTERY BOXES optional accessories with the same dimensions and aesthetic appearance as the UPS ER series models are fitted with upgraded battery charges for long runtime and business continuity applications For these versions the batteries are housed in separate cabinets UPS VIEWS FRONT VIEW
15. de and the A icon starts to flash 1 Ifthe mains power is present the ON OFF switch must be pressed to completely turn off the UPS 2 During battery mode operation with the timer not set the UPS automatically switches off after 30 seconds However if the timer is set press and hold down the STBY key for at least 5 seconds to turn off the UPS For complete shutdown press the ON OFF switch 15 DISPLAY PANEL MESSAGES This chapter describes in detail the various information that can be displayed on the LCD UPS STATUS MESSAGES ICON STATUS DESCRIPTION Indicates a fault Flashing The UPS is in stand by mode Indicates regular operation Flashing The UPS is in Battery swap mode The UPS is operating from the mains The UPS is operating from the battery In this condition the UPS emits Fixed da an acoustic signal beep at regular 4 second intervals Low battery pre alarm Indicates that battery autonomy is coming to an Flashing end In this condition the UPS emits a beep at regular 1 second intervals AVR active Indicates that the timer is active programmed switch on and switch off The timer can be activated deactivated using the software provided The EnergyShare sockets are not configured Always active Using UPSTools software an event associated with the EnergyShare Continuous sockets was configured e g end of discharge pre alarm threshold but the sockets are active at this time Flash
16. e Select the required input frequency range for normal t 3 10 in 1 steps operation Waiting time for automatic Disabled Power on delay switching back after 5 sec 1 255 in 1 mains power returns sec did Select the feature Pin 1 2 REPO Remote Switch e Pin 1 2 REPO associated with the remote Pin 2 3 Remote i on off feature contol termina board e Pin 2 3 Remote ON Remote ON OFF Input frequency tolerance range 21 I COMMUNICATION PORTS On the back of the UPS see UPS Views the following communication ports are present e RS232 connector e USB connector e Expansion slot for additional communication cards RS232 CONNECTOR RS232 CONNECTOR Programmable output default UPS in lock TXD Opto isolated contact max 30Vdc 35mA RXD These contacts can be associated with other events using GND the software provided Power supply DC Imax 20mA Programmable output For further information about interfacing with the UPS refer to default low battery pre alarm the manual provided Programmable output default battery operation COMMUNICATION SLOT The UPS is equipped with an expansion slot for optional communication cards see figure on right which allows the device to communicate using the main communication standards Some examples e Second RS232 and USB port e Serial duplicator e Ethernet network card with
17. er of batteries contained can vary according to the type of UPS for which the BATTERY BOX is intended It is therefore necessary to take great care to ensure that the battery voltage of the BATTERY BOX is the same as the voltage permitted by the UPS Several battery boxes can be connected in series to achieve a longer extended runtime If the UPS is connected to a battery box the maximum active power is derated from PF 0 9 to PF 0 8 REAR VIEW P wami as 18 FS ap op ay SEIT 19 20 o N Front view Front view Rear view without panel Extractable rotatable battery box plate Battery isolator Removable front panel Battery expansion connector INSTALLATION INITIAL CONTENT CHECK After opening the packaging it is first necessary to check the contents The package must contain UPS Schuko power cable IEC 10A IEC 16A only for models 2200 3000VA USB cable RS232 cable i SN KDB ES Handles for rack installation A re A x y fe AN OS U _ 0 AS Y gt o x e NO ES d Nu em SN NON n YI Do N L Y Battery expan
18. erious persistent overloads and short circuits CODICE DESCRIZIONE L04 j Heatsink over temperature S LO Temperturesensorifauty S L07 Temperature sensor2 faulty L21 Capacitor bank overvoltage S Inverter overvoltage L51 L52 L53 Inverter undervoltage Overload load 10396 Overload load 11096 Overload load 15096 Short circuit 28 TECHNICAL DATA VSD 2200 VSD 3000 INPUT Nominal voltage Vac 220 230 240 Nominal frequency Hz 50 60 Rated current 1 A 10 6 12 1 14 2 15 8 BATTERY Recharge time standard versions h lt 4h for 80 of the recharge No of internal batteries Recharge current OUTPUT Nominal voltage 2 Vac Selectable 220 230 240 Frequency Hz Selectable 50 60 or self learning Nominal power VA 1100 1500 2200 3000 Nominal power wi 990 130 1980 1760 2700 2400 From mains locked after 5 min Overloading 100 lt load lt 110 From battery locked after 60 sec From mains locked after 10 sec Overloading 110 lt load lt 150 From battery locked after 5 sec From mains locked after 1 sec Load overload gt 150 From battery locked 0 5 sec OTHER DATA Room temperature Humidity lt 90 without condensation excessive battery discharge over current short circuit over voltage under voltage thermal Dimensions W x D x H 4 mm 87 x 425 x
19. he stop device is used the REPO control is opened and the UPS goes into stand by mode and the load is completely disconnected Attention before restarting the UPS reset the stop device The circuitry of the remote control terminal board is self powered with SELV circuits Therefore an external voltage supply is not required When a contact is closed a maximum current of 15mA circulates All connections with the remote control terminal board are made through a cable which guarantees a double insulation connection Logic of the connections e PIN 1 2 REPO The function is activated when the contact is opened n REPO e PIN 2 3 REMOTE ON REMOTE ON OFF The feature is activated by closing the contact Set by default as REMOTE ON also configurable as REMOTE ON OFF using UPSTools software ON ON OFF 19 I SOFTWARE MONITORING AND CONTROL SOFTWARE The PowerShield software guarantees effective intuitive UPS management displaying all the most important information such as input voltage applied load and battery capacity It is also able to perform shutdown operations and send e mails text messages and network messages automatically when certain events selected by the user occur INSTALLATION OPERATIONS 1 Connect one of the UPS s commu
20. icated in the figure below Slide the UPS and the battery box into the two supports l f l Fa L M P hi il E pl P PP al E E Z m T m Rm n E SY a n I z Al Fl Al A EN E m FT FA 5 J F N J For any additional battery boxes repeat the sequence of operations shown above 13 RACK VERSION The sequence of operations to be followed in order to transform the UPS or battery box into rack version are described below BEFORE CARRING OUT THE FOLLOWING SEQUENCE OF OPERATIONS ENSURE THAT e THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD e THE BATTERY BOX IS DISCONNECTED FROM THE UPS FROM ANY OTHER BATTERY BOXES AND WITH THE BATTERY ISOLATOR OPEN 1 Pickup the panel from the sides and gently pull it away from its position just enough to be able to rotate it PN nn ATTENTION The panel must be removed carefully P i DO NOT ATTEMPT IN ANY WAY TO REMOVE THE PANEL FROM THE UPS 2 Rotate the panel 90 counter clockwise and reinsert it carefully into the IB
21. igure displays the active operating ECO mode and allows the user to choose other modes directly from the display panel MODE HOW TO PROCEED e To access the configuration area hold down the SEL button for at least 3 seconds e The icon corresponding to the mode currently set lights up e To change the mode press the ON button e To confirm the mode chosen hold down the SEL button for at least 3 seconds POSSIBLE SETTINGS The UPS is designed to be configured in various operating modes e L l normal operating mode e is the mode with which the UPS consumes the least amount of power and is therefore the most efficient e MODE using the UPSTools software it is possible to customise the UPS operational characteristics ADDITIONAL FUNCTIONS MODE BATTERY SWAP The battery swap mode ensures that the UPS remains in normal operation from the mains supply In this condition the load is powered directly by the input mains any disruption in the mains directly affects the load ATTENTION PRIOR TO PERFORMING THE FOLLOWING PROCEDURE ENSURE THAT THE UPS IS NOT IN BATTERY OPERATION MODE Attention even when the UPS is switched on the load is disconnected in the event of a mains blackout If the input mains deviates from the established tolerances the UPS automatically switches to Stdby mode and disconnects the load To force the UPS into battery swap mode press and hold the ON and SEL keys at the same time
22. ina The associated event occurred the EnergyShare outlets have been 9 disconnected For more information about the configuration of the EnergyShare sockets see Additional Features 16 MEASUREMENT DISPLAY AREA The front panel can be used to display important UPS operating information When the UPS is switched on the display shows the main voltage value To display a different measurement press the SEL button repeatedly until the desired measurement appears In the event of a fault alarm FAULT or a lock LOCK the display will automatically show the type and code of the corresponding alarm Some examples are shown below GRAPHIC EXAMPLE DESCRIPTION GRAPHIC EXAMPLE DESCRIPTION Battery charge Mains voltage percentage BATT IID Mains frequency H 2 V Total battery voltage UPS output voltage Applied load percentage Current absorbed by the Output voltage frequency load Temperature of the electronics cooling Residual battery autonomy system inside the UPS _ _ AU Z 2 Lock the Li l corresponding code is L corresponding code is 1 LL displayed A la displayed The values shown in the images in the table are purely as an indication The FAULT LOCK codes can only be displayed if they are active presence of a fault alarm or a lock 17 CONFIGURING THE OPERATING MODE The area of the display shown in the f
23. l management system developed by the company in compliance with applicable standards No hazardous materials such as CFCs HCFOs or asbestos are used in this product When evaluating packaging the choice of material has been made favouring recyclable materials For correct disposal please separate and identify the type of material of which the packaging is made according to the table below Dispose of all material in compliance with applicable standards in the country in which the product is used DESCRIPTION MATERIAL Packaging corner Stratocell Protective bag Polythene Accessories bag Polythene DISPOSING OF THE PRODUCT The UPS and the Battery Box contain electronic PCBs and batteries which are considered TOXIC and HAZARDOUS waste When the product reaches the end of its operating life dispose of it in accordance with applicable local legislation Disposing of the product correctly contributes to respecting the environment and personal health The reproduction of any part of this manual in whole or in part is forbidden without the prior consent of the manufacturer In order to make improvements the manufacturer reserves the right to modify the product described at any moment and without notice CONTENTS PRESENTATION UPS VIEWS FRONT VIEW REAR VIEW DISPLAY PANEL VIEW BATTERY BOX ACCESSORY NOT SUPPLIED WITH THE UPS REAR VIEW
24. manuale d installazione ed uso installation and use manual installations und bedienungsanleitung manuel d installation et d utilisation e manual de instalaci n y uso VISION DUAL RIELLO ELETTRONICA ZA riello Gps A INTRODUCTION Congratulations on purchasing a UPS Vision Dual product and welcome to Riello UPS To use the support service offered by Riello UPS visit the site www riello ups com Our Company is a specialist in the design development and manufacturing of uninterruptible power supplies UPS The UPS described in this manual is a high quality product which has been carefully designed and built in order to guarantee the highest levels of performance This device can be installed by anyone on the condition that they have READ THIS INSTALLTION AND USER MANUAL CAREFULLY The UPS and the Battery Box generate DANGEROUS internal electrical voltages All maintenance operations must be carried out by suitably qualified operators This manual contains detailed instructions for using and installing the UPS and any additional Battery boxes For information on how to use and maximise the performance of your device please retain the CD containing this manual and read it carefully before operating the equipment ENVIRONMENTAL PROTECTION In the development of its products the company devotes abundant resources to analysing the environmental aspects All our products pursue the objectives defined in the environmenta
25. nication ports to one of the PC s communication ports using the cable supplied 2 Download the software from the web site www riello ups com selecting the specific operating system 3 Follow the installation program instructions 4 For more detailed information please read the user manual which can be downloaded from www riello ups com CONFIGURATION SOFTWARE The UPStools software allows the configuration and full display of the status of the UPS via USB or RS232 For a list of possible configurations available to the user refer to the UPS Configuration paragraph INSTALLATION OPERATIONS 1 Connect one of the UPS s communication ports to one of the PC s communication ports using the cable supplied 2 Follow the installation instructions shown within the software manual which can be located in the UPSTools directory or downloaded from the web site www riello ups com CAUTION If the RS232 communication port is used it is not possible to communicate with the USB port and vice versa It is advisable to use a cable which is shorter than 3 metres for communication with the UPS To obtain additional communication ports with different functions independent from the standard USB and RS232 ports on the UPS various accessories are available which can be inserted into the communication card slot To check the availability of new more updated software versions and for more information about the accessories available consult the website
26. play panel If there is a problem the UPS signals the event by showing the code and the type of active alarm on the display FAULT and or LOCK FAULT FAULT alerts can be divided into three categories gt Anomalies these are minor problems which do not cause the lock of the UPS but reduce performance or prevent certain functions from being used CODICE DESCRIZIONE Sensor1 temperature under 0 C Sensor2 temperature under 0 C Replace batteries Batteries missing or Battery Box missing or not connected Waiting for battery charging A54 Load percentage greater than the user threshold set Alarms these are more critical problems than anomalies because if they persist they could cause the UPS to lock in a very short time CODICE DESCRIZIONE Heatsink over temperature Temperature sensor1 faulty Temperature sensor2 faulty Battery charger faulty Overload load 11096 Overload load 15096 Short circuit F50 Overload load 10396 Battery overvoltage 27 gt Active commands Indicates the presence of an active remote command CO Remote control 1 Switch On Off 2 _ Remote control 2 Load supplied by the mains Remote control 3 Switch On Off Battery test in progress Lock LOCK alerts are normally preceded by an alarm signal and their scale leads to the powering off of the inverter with the load being powered by the bypass line this procedure is excluded for locks due to s
27. sion plug ER version only 10 Support feet 2 IEC 10A connection cables User manual CD Safety manual Safety Handle screws IEC 16A male plug For 2200 3000VA models only INSTALLATION ENVIRONMENT The UPS and the Battery Box must be installed in ventilated clean environments which are sheltered from bad weather The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table The ambient temperature whilst the UPS is in operation must remain between 0 and 40 and the UPS must not be positioned in places which are exposed to direct sunlight or to hot air The recommended operating temperature for the UPS and the batteries is between 20 and 25 The actual operating life of the batteries is 5 years on average with an operating temperature of 20 C If the operating temperature reaches 30 C the operating life is halved This is a category C2 UPS product In a residential environment this product may cause radio interference in which case the user may be required to take additional measures gt gt BATTERY BOX INSTALLATION ATTENTION CHECK ON THE DATA PLATE THAT THE VOLTAGE OF THE BATTERY BOX IS THE SAME AS THAT ALLOWED BY THE UPS Battery boxes can be installed in series for extended runtimes Connect the Battery Boxes in series as shown in the figure below If the UPS is connected to a battery box the maximum active power is dera
28. ted from PF 0 9 to PF 0 8 10 Urs a EP rg ug 10 el E r ud Um ABA an 57 9 p 43 f Ue 8 an Gourd BATTERY BOX SETTING THE NOMINAL BATTERY CAPACITY Before installing one or more Battery Boxes the UPS must be configured in order to update the nominal capacity value total An UPS s internal batteries external batteries using the dedicated configuration software UPSTools contained on the CD ROM supplied with the UPS The battery box must only be installed while the UPS is switched off and disconnected from the mains power supply CAUTION The connection cables cannot be extended by the user After connecting the UPS to its Battery Boxes insert the fuses and turn the Battery Box battery isolators SWBATT to the ON position It is not possible to connect more than one UPS to a single battery box or to several Battery Boxes connected in a series A To check the avallability of a new version of the latest software visit the website www riello ups com 11 TOWER VERSION This ch