1. There are two and alarm is continuously possible results sounding 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value charged least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon Aand the warning code FA flashing on LCD display Fan is locked or not Check fans and notify and alarm is sounding every working dealer second 5 Storage and Maintenance 5 1 Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 259C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer 80 Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 40 C 45 C Every 2 months 15
2. function You may choose the following two options ENA ECO mode enable DIS ECO mode disable Parameter 2 amp 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode in parameter 2 For 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage For 110 115 120 127 VAC models the setting range in parameter 3 is from 3V to 12V of the nominal voltage LLS Low loss voltage in ECO mode in parameter 2 For 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage For 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage e 06 Bypass enable disable when UPS is off Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Parameter 2 amp 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 208 220 230 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 208 220 230 240 VAC models 170 220 setting the low volta
3. pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in stand by mode or bypass mode Up key Press this button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute Select ON Mute and Select buttons simultaneously for 5 seconds Then UPS Button will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range ON Mute Button OFF Enter Button Select Button 3 2 LCD Panel Backup Timelnfo Faultinfo Input amp Battery Mute Operation Voltage Info Output amp Battery PR F Voltage Info il earr utr 7 OVER LOAD Battery Info _ mE i gt Load Info i J es CE I Display Backup time information Indicates the backup time in pie chart Indicates the backup time in numbers H hours M minute S second Indicates that the warning and fault occurs Indicates the warning and fault codes and the codes are listed in details in 3 5 section Mute operation Indicates that the UP
4. A alar alda ENA DIS ESC HLS LLS BAT CF EP FA TP CH ma X 3 5 UPS Setting There are three parameters to set up the Parameter 1 UPS Parameter 1 It s for program alternatives There are 8 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program Parameter 2 Parameter 3 e 01 Output voltage setting Parameter 3 Output voltage For 208 220 230 240 VAC models you may choose the following output voltage 208 presents output voltage is 208Vac 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac 240 presents output voltage is 240Vac For 110 150 120 127 VAC models you may choose the following output voltage 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac 127 presents output voltage is 127Vac Parameter 2 amp 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Parameter 2 amp 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz Parameter 3 Enable or disable ECO
5. RS 232 Port Intelligent slot To allow for unattended UPS il ikin and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 4 Network connection Network Fax Phone surge port IN OUT Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipment with another modem fax phone line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 It s in closed status for UPS normal operation Step 6 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 7 Install software For optimal computer system protection install UPS monitoring software to fully configure
6. S alarm is disabled Output amp Battery voltage information mye Indicates the output voltage frequency or battery voltage L LL z Vac output voltage Vdc battery voltage Hz freguency OUTPUT Lit Cit Fault information if Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 amma SHORT Indicates the load or the UPS output is short circuit lt gt o rr yg rogrammable outlets information Indicates that programmable management outlets are working ode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working lt E C O Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is working Battery information x Indicates the Battery level by 0 25 26 50 51 75 and 76 100 es LOW BATT Indicates low battery level and low battery voltage Input amp Battery voltage information HAHA Vde Indicates the input voltage or freguency or battery voltage ee ME Vac Input voltage Vdc battery voltage Hz input frequency 8 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Sounding twice every second Continuously sounding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index l OLION lt IJ LO D mpd ni pa nd LE a da a LL
7. Sa SS YS 2 2 Setup the UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords e For 208 220 230 240VAC models The power cord is supplied in the UPS package e For 110 115 120 127VAC models The power cord is attached to the UPS The input plug is a NEMA 5 15P for 1K 1KL 1 5K and 1 5KL models NEMA 5 20P for 2K and 2KL models Note for Low voltage models Check if the site wiring fault indicator lights up in LCD panel It will be illuminated when the UPS is plugged into an improperly wired utility power outlet Refer to Troubleshooting section a 2 UPS output connection For socket type outputs there two kinds of outputs programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices e For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 imm power cords Suggest using WG12 10 or 3 3mm 5 3mm power cords for NEMA type c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 3 Communication connection Communication port USB port
8. UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock Step 8 External battery connection for long run models only Follow the right chart to make external battery connection To external battery 3 Operations 3 1 Button operation gt Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm After the UPS is on battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But it s not applied to the situations when warnings or errors occur Down key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press ON Mute buttons simultaneously for 5 seconds to enter UPS self testing while in AC mode ECO mode or converter mode Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by
9. UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet e In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance service and faults e The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel e Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries e Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shoc
10. ge point in parameter 3 from 170Vac to 220Vac For 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac e 08 Programmable outlets enable disable e 00 Exit setting Parameter 3 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Parameter 3 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode 11 3 6 Operating Mode Description Operating mode LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving Frequency Converter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by fron
11. k and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries e Do not attempt to dispose of batteries by burning them This could cause battery explosion e Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not dismantle the UPS system 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use NOTE There are two different types of online UPS standard and long run models 2 1 Rear panel view NEWTECH PRO 1KVA NEWTECH PRO 2 KVA NEWTECH PRO 3 KVA G E ox Programmable outlets connect to non critical loads Output receptacles connect to mission critical loads AC input Input circuit breaker Network Fax Modem surge protection Emergency power off function connector EPO USB communication port RS 232 communication port SNMP intelligent slot 10 External battery connection only available for L model e
12. shown as 27 and the Battery voltage is too high Contact your dealer BATT FAULT or the charger is fault icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the Battery voltage is too low Contact your dealer BATT FAULT or the charger is fault icon is lighting on LCD display and alarm is continuously sounding The icon A OVER LoAd UPS is overload eae loads from pale erk imi pl hedi UPS is overloaded Devices Remove excess loads from connected to the UPS are UPS output fed directly by the electrical network via the Bypass After repetitive overloads Remove excess loads from the UPS is locked in the UPS output first Then shut Bypass mode Connected down the UPS and restart devices are fed directly by it the mains Fault code is shown as 43 and The The UPS shut down Remove excess loads from icon LOVER LOM ic pi ghting on LCD automatically because of UPS output and restart it i l overload at the UPS display and alarm is continuously output sounding Fault code is shown as 14 and the The UPS shut down Check output wiring and if icon is lighting on LCD automatically because connected devices are in 14 display and alarm is continuously short circuit occurs on the short circuit status sounding UPS output Fault code is shown as 1 2 3 4 A UPS internal fault has Contact your dealer 11 12 13 and 41 on LCD display occurred
13. t panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply power but still can charge batteries 3 7 Faults Reference Code Fault event Battery voltage too high 12 3 BATT FAULT Inverter soft start fail Over temperature Inverter voltage high 12 o x Overload 43 12 3 8 Warning indicator a Sounding every second Over Charge Sounding every second 13 4 Troubleshooting If the UPS system does not operate correctly please solve the problem by using the table below Symptom No indication and alarm even The AC input power is not Check if input power cord though the mains is normal connected well firmly connected to the mains The AC input is connected Plug AC input power cord to the UPS output to AC input correctly The icon Pani the warning EPO function is activated Set the circuit in closed code EF flashing on LCD position to disable EPO display and alarm is sounding neU every second l AN l Line and neutral Rotate mains power socket The icon Aand ve flashing on conductors of UPS input by 180 and then connect LCD display and alarm is sounding sre reversed to UPS system every second The Gn A and flashing The external or internal Check if all batteries are battery is incorrectly connected well on LCD display and alarm is p ay connected sounding every second Fault code is
14. tuncmatik www tuncmatik com iyi elektrik NEWTECH PRO 1 2 3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL info tuncmatik com www tuncmatik com Table of Contents 1 Important Safety Warning ccsssccssescesnscessnneeenss 1 1 Transportation 1 2 Preparation 1 3 Installation 1 4 Operation 1 5 Maintenance service and faults 2 Installation and SCCUP cccceeceseceescceesneenneeennenens 2 1 Rear panel view 2 2 Setup the UPS 3 ODES ACIONS Karara se ala rn a faa 3 1 Button operation 3 2 LCD Panel 3 3 Audible Alarm 3 4 LCD display wordings index 3 5 UPS Setting 3 6 Operating Mode Description 3 7 Faults Reference Code 3 8 Warning indicator 4 Troubleshooting s11u5u8815u8181100 n anana aaa 5 Storage and Maintemance sccsseseessesessuseesenees 6 Specifica tiO NS az ri a a EE NNNN 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation e Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dr
15. y before being installed Please allow at least two hours for the UPS system to acclimate the environment e Do not install the UPS system near water or in moist environments e Do not install the UPS system where it would be exposed to direct sunlight or near heater Do not block ventilation holes in the UPS housing 1 3 Installation e Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to connect the loads to the UPS system When installing the equipment it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3 5mA 1 4 Operation e Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads The