Ever Sinline Pro 10 000 - 10kVA, VRLA 1x28x7Ah
Contents
1. backlight Type read Parameters Qak charge level of batteries Uak battery section voltage Owy load handled by the power supply unit Tau anticipated autonomous time of the power supply unit TrybPracy operation mode of the power supply unit i a additional information as per the table Information Alarms Abbreviation Meaning Abbreviation Meaning L Charging ZW Short circuit Overload PC Overload G Overheat PG Overheat Waiting following STANDBY AU Damaged battery N 90 sec of autonomous time EPO EPO remaining Service BW Internal error AP AVR increasing voltage e g a PC AO AVR decreasing voltage eg 1 5 Screen view 1 Thi Main menu 1 Fm TARY FOHTROLA TGURAC TH STATYSTYKA USTAWIENIA ZZ IDEHT F IKAJA 2010 08 24 WWW ever eu 10 Instruction manual for SINLINE PRO 10000 series power supply units The main menu comprises tree screens Switching between screens is effected by means of the A keys A selection is confirmed by pressing the 1 key whereafter a submenu may be selected in the chosen menu also by means of the V A keys The arrow on the left of the submenu name indicates the current position Selections are confirmed by the key To proceed to a higher level press the ESC key MEHI 152 POMIARY KH PROLA Tey MEASUREMENTS
2. PARAMETERS SINLINE PRO 10000 1 10 kVA Output power 8 kW GENERAL DATA Topology Total efficiency for Pmax gt 98 Cooling Forced internal fans Protection level IP20 Working environment Separate rooms with a low level of contamination Working temperature 10 40 Storage temperature 0 40 Relative humidity during operation lt 95 Relative humidity during storage lt 95 Height above sea level 3 1000m NETWORK POWER MODE Input voltage 7150 280 V 165 280 V 2 Input voltage frequency 45 55 Hz 1 Hz Output voltage range 172 5 252 V 190 252 V 2 Switching thresholds mains ups 150 V 290 V 165 V 280 V 2 Output voltage shape As on the input Mains voltage filtration interference filter RFI EMI varistor muffler BATTERY MODE Input voltage effective value 230 V 2 Output voltage shape Sine Output voltage frequency Synchronous 50Hz 0 2 Hz Switching thresholds ups mains 155 V 285 V 170 V 275 V 2 Mains voltage filtration LC Output voltage distortion THDu lt 5 for Pmax linear Peak factor CF 02 01 Short circuit current gt 4 In BATTERIES Battery voltage sum total 336 V DC 1x28 x VRLA 12 V 7 Ah pee alongs 2x 28 x VRLA 12 V 7 Ah option Backup time from internal batteries gt 7 10 15 min 100 80 50 Pmax gt 13 17 30 min Backup time with 1 battery module 1 00 80 50 Pmaw 9 90151792 min
3. 1 NOTE SINLINE PRO 10000 power supply units intended for usage with medical life and or health support systems 2010 08 24 WWW ever eu 21 Instruction manual for SINLINE PRO 10000 series power supply units INSTALLATION NOTE Before installing the appliance you must acquaint yourself A N with the principles of industrial work safety set forward in the previous chapter UNPACKING Carry out a visual inspection of the power supply unit immediately upon delivery Although the product is packaged the appliance could have undergone damage due to inappropriate transport conditions If any damage is determined inform the carrier or seller A N NOTE The device may be delivered with connected batteries The appliance is placed on a wooden pallet which may be moved using a fork lift truck In order to unpack the device you should first cut through the bands attaching it to the pallet Next lift off the cardboard boxes Remove the protective corners NOTE The appliance does not stand directly on the pallet but on A N a layer of polyethylene foam which impairs its stability Falling of the appliance may constitute a threat to health or life If the appliance is delivered with batteries please note that it is very heavy cf the table of technical parameters Use belts and a hoist to remove the appliance from the pallet If the device is delivered wit
4. Maximum internal battery charging time a lt 2h Maximum charging time of 1 module 3h after discharging with a power of 80 Pmax MECHANICAL PARAMETERS Dimensions width x depth x height 340 x 740 x 795 mm UPS weight 200 kg EQUIPMENT Terminals screw terminals max 160 line Input AC safeguards Overcurrent breakers for the Au and the BYPASS line 2 x 63 A ch DC safeguards internal batteries DC safeguards external battery module 30 A 400 V DC cylindrical 10 x 38 gRB 30 400 V DC cylindric 10 x 38 gRB Input safeguards electronic Signalling sound and LED LCD display Communication interface RS 232 USB network management card SNMP HTTP option EPO Included Service BYPASS switch Included Note The manufacturer reserves the right to modify the above parameters without prior notice Notes 7 For standard operation of the power supply unit the load applied to the output not exceed 80 of the value given the table The power margin is necessary to ensure the continuous work of connected devices in the event of instantaneous load current fluctuations Prolonged exposure of the power supply unit to an ambient temperature in excess of 25 will shorten the life of batteries When the height above sea level rises in excess of the specified limit the permitted load power is reduced Charging time to reach 90 of battery capacity preceded by a discharge with a loa
5. 2010 08 24 WWW ever eu 34 Instruction manual for SINLINE PRO 10000 series power supply units Installing a management card 1 Switch on the power supply unit by means of the user interface CONTROL 1 3 UPS 2 Set safeguards and F4 OFF 3 Switch off safeguards F1 F2 and F5 by opening the fusible cut out mounts The safeguards do not have to be switched off in any special order 4 Wait for approx 30 sec in order to discharge the internal capacities of the unit 5 Unscrew the metal grille from the card socket 6 Connect the card cable the cable is located in the card slot 7 Insert the card into the slot 8 Screw the card grille to the rear panel 9 Activate safeguard F1 by closing the mount Wait at least 10 sec Activate safeguard F2 by closing the mount Activate safeguard F5 by closing the mount Set safeguards F3 and F4 ON Switch on the power supply unit by means of the user interface CONTROL 1 3 UPS Zw Figure 5 Installation of the card 2010 08 24 www ever eu 35 Instruction manual for SINLINE PRO 10000 series power supply units INSTALLING AND CONFIGURING POWERSOFT PERSONAL Installing on a Windows system Before installing the PowerSoft software you should e uninstall your current version of PowerSoft and other monitoring software if the user is replacing an emergency power supply unit that protects his PC e you are installing
6. 23 BATTERY MODULE eene 23 Connecting MOd lES ERE 24 Disconmecting n E EE 25 CONNECTING THE POWER SUPPLY UNIT eerte nnne nennen 26 Clements EE 26 system oe Swans gu eben swans 27 STAR TUR EE 27 SWITCHING OFF AND DISCONNECTING THE POWER SUPPLY UNIT ee 28 OPERATING MODES OF THE POWER SUPPLY UNIT esee eene 29 OTHER FUNCTIONAL ELEMENTS 30 PROTECTION er PU RP ER npe e pneri 30 Ped c 33 lo M P 33 Service BYPASS ri ec e tr prr de err utter 33 COOPERATION OF THE POWER SUPPLY UNIT WITH 34 R5232 AND USB COMMUNICA TION 2 erts tete neret eee eere eh eve te eee dee o enean 34 EVER SNMP HTTP NETWORK MANAGEMENT CARD c esee eene 34 Installimg a management card oq err ere pe e va e pe n pater nere deren 35 INSTALLING AND CONFIGURING POWERSOFT cerent 36 Installing erede teris eren Pe ea re PU nere edere 36 Installing oma Linux Unix Systems cepit pere metet eei ien Hr e ne 36 Updating sottwate e U
7. m2 TA Tant mE ANRE LI 111 EE TEMPERATURE 44 nnn Description Temperature parameters The temperature of unit s internal elements Type read Parameters TO temperature of internal elements of the unit T1 temperature of internal elements of the unit Screen view TEMPERATURA 3 4 5606 2010 08 24 WWW ever eu 12 Instruction manual for SINLINE PRO 10000 series power supply units CONTROL submenu The CONTROL submenu is divided into three groups The menu can be navigated in the same way as described above The user may alter the configuration of the power supply unit only if individual items can be changed under specific conditions Cf table hereunder Table 4 Table of control flag changes Operationimode o 5 X change not allowed 5 2 A e only switch on 4 5 Zia o o only switch off a E dm n switching Control flag Saiz S m only switch on switch off o o possible only when waiting for a AwaryjneWylaczenie X e e minimal load UPS X X Ole m o X Buzzer X Czas Wyl EPO X UPS STB STB UPS xX X X e X X X X KasujAwarie xX X X TestAku X Screens are selected using the A V keys and confirmation given by pressing 4 As in the case of par
8. of events connected with a short circuit of the power supply unit s output Screen view Prema aren Pir EEG 2010 08 24 WWW ever eu 18 Instruction manual for SINLINE PRO 10000 series power supply units STATISTICS Description Statistical data Type read Parameters Roztadowan the number of total discharges of the power supply unit s batteries AVR Podw the number of activations of the AVR system resulting in an increase in voltage value AVR Obniz the number of activations of the AVR system resulting in a decrease in voltage value Screen view STRTZTSVER Fozladowan HUF Produ HUE bniz STATISTICS 44 O Description Statistical data Type read Parameters Normalna operating time of the power supply unit in NORMAL mode Rezerwowa operating time of the power supply unit in BACKUP mode Przeciaz operating time of the power supply unit in an overload state Screen view ST H T E A a Hormalna TF Re rer yess Frzeciaz 2010 08 24 WWW ever eu 19 Instruction manual for SINLINE PRO 10000 series power supply units PANEL SETTINGS submenu The PANEL SETTINGS submenu contains a single screen The menu can be navigated in the same way as described above The user can change the values of power supply unit parameters Confirm a screen by pressing select a parameter by means of the A V keys confirm by pressing the 4 key The PANEL
9. particular care when transporting e because of its weight the device has been fitted with rubber wheels e the appliance should be operated and stored in conditions concordant with those set forward in the specification ELECTRICAL SAFETY itis forbidden to work on one s own under conditions constituting a threat to life and or health e during a momentary short circuit the high current may cause serious burns e before connecting the appliance it is necessary to check the technical condition of cables plugs and sockets as well as that of the appliance itself e insofar as possible you should connect and disconnect communication cables using one hand only for in the event of touching two surfaces with different electric potentials you may suffer an electric shock e the device must be connected to a three cable system 1P N PE failure to do so will result in an increased risk of electric shock It is strictly forbidden for the user to perform any repair work as this would constitute a threat to health and or life All repairs and battery replacements must be carried out exclusively by qualified service personnel m NOTE The UPS is completely disconnected from the power network only when the power supply cord is disconnected NOTE The device is equipped with an internal power source A N storage cells and therefore a dangerous voltage may appear on the output even if it is not connected to the mains
10. required This method of cooling activation reduces the noise generated by the unit and helps extend the life of fans The DPC system supports various methods of communication between the unit and a PC over a communication link or a special link for the connection of an EVER management card EVER HTTP telnet SNMP The unit performs precise measurements of its basic parameters including battery voltage power grid input voltage unit output voltage the power of connected loads temperature and of advanced parameters such as the available battery capacity or backup mode operating time under current load The UPS utilises an innovative charging method typically reserve for high end power supply units which is known as CBC COOL BATTERY CHARGING this system utilises elements of the internal converter for cold battery charging In the mains operating mode this function charges the batteries while in battery operation mode it converts the internal energy of the battery to an alternating voltage that supplies the protected devices 2010 08 24 WWW ever eu 6 Instruction manual for SINLINE PRO 10000 series power supply units STRUCTURE Figure 2 Views of the rear panel BYPASS switch cover Fans Adapter card slot plug RS232 communication link EPO link Fusible cut out for internal batteries 4 USB communication link 8 Connection links cover 9 AC input automatic fuses 10 Mechanical cab
11. updates is checked once the user logs on This setting can be checked through the Update configuration item in the system programme menu 2010 08 24 WWW ever eu 37 Instruction manual for SINLINE PRO 10000 series power supply units Linux Unix systems PowerSoft software for systems from the Linux Unix family may be updated using a new version of the package downloaded from www ever eu In the case of CentOS RedHat Suse Linux and Fedora Core systems updates may be performed by means of the following command rpm Uv powersoftlite x x x For Debian and FreeBSD systems we recommend uninstalling the old version of the software and then installing the new version Instructions for this procedure can be found in the instruction manual available at www ever eu COMMENTS REGARDING OPERATION NOTE The power supply unit is intended for commercial and industrialapplications in a secondary environment In order to prevent the emission of interferences it may be necessary to apply additional preventive measures or installation limitations AN NOTE The power supply unit does not contain any end user serviceable parts Damage to the guarantee seal is tantamount to voidance of the appliance s guarantee All repairs should be performed solely by qualified service personnel The power supply unit may function unreliably when the powered equipment takes up considerable surge power In practice this m
12. 10 08 24 WWW ever eu 32 Instruction manual for SINLINE PRO 10000 series power supply units AVR The power supply unit is equipped with an AVR Automatic Voltage Regulation system that immediately corrects small drops AVR increasing and rises in mains voltage so as to ensure that receivers enjoy the proper supply conditions without using up the power gathered in batteries EPO The EPO Emergency Power Off is a mechanism that cuts off the energy supply to receivers at the unit s output in extreme situations e g a fire The UPS then switches to EMERGENCY mode The mechanism can be activated in two ways by opening contacts of the external EPO connector trigger forced from the user interface CONTROL 1 3 AwaryjneWylaczenie Reactivation of the output voltage takes place only when the user manually deletes the failure flag CONTROL 2 3 KasujAwarie and sets the trigger to inactive normal trigger status in the case of external triggering It is possible to temporarily lock the EPO function for the duration of EPO trigger installation The installer can then safely remove the EPO connector without any risk of disconnecting the power supply of receivers The operation may continue for at maximum 1 minute from the moment of setting of the control flag CONTROL 2 3 Czas Wyl EPO Thereafter the lock is turned off automatically The EPO connector pins have a safe voltage that is separated from the remaining device sys
13. EVER POWER SYSTEMS INSTRUCTION MANUAL SINLINE PRO 10000 EVER Sp z 0 0 ul Grudzinskiego 30 62 020 Swarzedz Poland www ever eu ups ever com pl tel 0048 61 6500 400 fax 0048 61 6510 927 a E uL Instruction manual for SINLINE PRO 10000 series power supply units TABLE OF CONTENTS TABLE OF CONTENT Ses ead 2 INTRODUCTION aene OR 3 GENERAL INFORMATION r 8 35 p Hm DOR PEE 3 INTENDED APPLEICATION 5 rh UT rH ORDERED 3 GENERAL DESCRIPTION nene DU RP 4 SIRUGIEIU RE ihe REPRE eme un neo 7 USER INTERFACE DP DEP 8 SCREENS dienen RERO EE e DR PR IE 10 ments ciet D RO n E Rn Rn ODE Re 10 MEASUREMENTS submenl 2 Per REOR E eR Pee 11 CONTROLE submenu ee reE 13 CONFIGURATION subm enu Ue AE 15 ALARMS 17 STATISTICS submenus wet eR erm hi Re eli ee ae 18 PANEL SETTINGS submenu ssc ere ER RW Re PG RH E e REOR 20 IDENTIFICATION SuUDiDeniuJ cepere ere Re ee ai GE GEO die eO ete 20 INDUSTRIAL WORK SAFETY INSTRUCTIONS 21 TRANSPORTE ERES ee ema ER ER OR Se 21 ELECTRICAL els coder PIRE ORO BE RAE QU GREG GERE 21 INST ALLA TION RR RUNG P ROMERO GROS 22 UNPACKING P Lm 22 INSTALLATION OF THE POWER SUPPLY UNIT eere nennen trennen
14. F2 the batteries are connected 9 Switch fuses F3 and F4 ON 10 Set the configuration of the power supply unit when starting up for the first time if modifications are required 11 Switch on the power supply unit by means of the user interface CONTROL 1 3 UPS Points 4 and 5 should be performed only if an additional battery module is connected Once these actions are performed the power supply unit will commence normal operation i NOTE The batteries of the power supply unit attain full power after approx one month of operation in NORMAL mode SWITCHING OFF AND DISCONNECTING THE POWER SUPPLY UNIT In order to completely disconnect the power supply unit perform the following activities in the order mentioned 1 Switch the power supply unit off by means of the user interface CONTROL 1 3 UPS logical switch off 2 Disconnect the safeguards of the main line and the BYPASS in the room building switching station in order to safely uninstall the power supply unit Setsafeguards F3 and F4 in the power supply unit OFF 4 Disconnect safeguards F1 F2 and F5 to this end open them and remove the fuse elements 5 If battery modules are connected to the power supply unit repeat point 4 for safeguards F1 and F2 w in these modules 6 Remove the protective plugs of connecting elements on the power supply unit and on modules if any 7 Disconnect the connecting cables from the switching stations po
15. ID RR DEEP e C DERE T reg ile 37 COMMENTS REGARDING OPERATION peine nint ei tren then 38 COOPERATION OF THE POWER SUPPLY UNIT WITH ELECTRICITY GENERATONRS 39 STORAGE MAINTENANCE AND 5 trennen nennen rennen enne 39 RECYCLDING uten eet Sonera ee Maid Proben 39 TECHNICAL PARAMETBRS 53 dnenab mt ree pum 40 INSTALLATION GUIDELINES 5 timete RH Pee ET D NET SS tees sect tad 40 TECHNICAL DA A ione metere tu a re etal DU ue RH 41 INFORMATION CONCERNING LEGAL PROVISIONS AND THE 42 DECLARATION OF te ehe pe qe p Mp Raum RE 42 GUARANTEE ccc cist unte bete enam n be mb eee Penny 42 NOTES ates Ha PR p mp ed ail b Bee instal aan Signin PPP PRU P RH 42 2010 08 24 WWW ever eu 2 Instruction manual for SINLINE PRO 10000 series power supply units INTRODUCTION Thank you for purchasing the EVER SINLINE PRO 10000 power supply unit It belongs to a series of technologically advanced power supply units intended for servers computer networks and data processing systems The UPS EVER SINLINE PRO 10000 has been designed in such a way as to best meet all your expectations regarding protection against the consequences of power outages The present instruction manual contains information on operating the device and sets forward the principles of safe usage Ple
16. SETTINGS menu contains numerical parameters Their modification consists in increasing or decreasing values by means of the keys and confirming by pressing 1 Confirmation is followed by automatic passage to a screen one level higher in the tree structure To resign from modifying a parameter press the ESC key PANEL SETTINGS Description Settings of user interface parameters Type read save Parameters Kontrast level of contrast of the LCD Podswietlanie level of backlight brightness of the display Blok Kl indicates that the keypad is locked can be changed only from the level of the control programme when the keypad is locked parameters cannot be changed Screen view IDENTIFICATION submenu The IDENTIFICATION submenu contains a single screen with information concerning the device To exit this screen press the ESC key IDENTIFICATION Description Information about the device Type read save Parameters nominal output apparent power of the power supply unit P nominal output active power of the power supply unit VH hardware version VF firmware version VP communication protocol version VFP LCD panel firmware version Screen view I DEHT y 1 JHIA 1 1 UFP 2010 08 24 WWW ever eu 20 Instruction manual for SINLINE PRO 10000 series power supply units INDUSTRIAL WORK SAFETY INSTRUCTIONS TRANSPORT e exercise
17. URATION submenu contains numerical parameters Their modification consists in increasing or decreasing values by means of the keys and confirming by pressing 1 Confirmation is followed by automatic passage to a screen one level higher in the tree structure To resign from modifying a parameter press the ESC key CONFIGURATION 1 4 Description Power supply unit parameters Type read save Parameters UWyjsciowe output voltage of the power supply unit UGornyProg upper limit of the voltage correctness criterion for the supply line UDolnyProg lower limit of the voltage correctness criterion for the supply line Screen view lice 47 t Lbs Description Power supply unit parameters Type read save Parameters AVRGornyProg upper input voltage limit at which the AVR system decreasing is activated AVRDolnyProg lower input voltage limit at which the AVR system increasing is activated Opoz STB delay time when switching to STANDBY mode forced by the user Screen view HU inns yyPr od BurgDpolnmesPro3 STE 2010 08 24 WWW ever eu 15 Instruction manual for SINLINE PRO 10000 series power supply units CONFIGURATION 3 4 Description Power supply unit parameters Type read save Parameters Poj z STB minimal charge level that the batteries must attain in order for the power supply unit to start up following a discharge ProgKas Prz load level a
18. a power supply unit that communicates with the PC by means of a USB connection the USB cable should be disconnected from the PC The installation wizard will inform you of the necessity of connecting the communication cable In order to install PowerSoft on a Windows system the list of operating systems on which the application has been successfully tested may be found on www ever com pl just activate the programme and perform the steps prompted During installation you should select the model of the power supply unit that is connected to the PC on which the software will be installed This setting can also be modified when the application is active In the case of a power supply unit that communicates with the computer over a USB link when the installation of PowerSoft Personal is completed the installer will ask you to connect the USB cable to the PC The operating system will inform that new hardware has been found and propose the installation of a driver Select the option to install a driver from a specific location on the first screen and on the next screen indicate the PowerSoft installation catalogue usually c Program Files PowerSoft to be searched In the next step the operating system will automatically find and install the appropriate driver In the case of Windows Vista the operating system will not automatically initiate driver installation from the disk Once the USB cable is connected to the computer open the control panel
19. acement of the power supply unit BEFORE COMMENCING WORK ON THIS CIRCUIT YOU MUST A N DISCONNECT THE UNINTERRUPTIBLE POWER SUPPLY UPS SYSTEM CHECK FOR ANY VOLTAGE BETWEEN ANY OF THE TERMINALS INCLUDING THE PE TERMINAL RISK OF REVERSE POWER SUPPLY Electrical system The electrical system should be structured in accordance with the installation guidelines elaborated for the power supply unit The guidelines constitute a separate document attached to the product START UP NOTE If no battery module is connected to the power supply unit A N the F5 module fuse should not be installed installation of the fuse would lead to the appearance of a dangerous constant voltage on the connecting strip of the battery module 2010 08 24 www ever eu 27 Instruction manual for SINLINE PRO 10000 series power supply units Once it has been correctly connected start up the power supply unit by performing the following activities in the order mentioned 1 Check whether fuses F3 and F4 are OFF if not set them OFF 2 Open the mounts of fusible cut outs F1 and F2 3 Insert an appropriate fuse element in mount F1 do not close the mount 4 Insert an appropriate fuse element in mount F5 and then close it in order to close the circuit 5 mount of the battery module s fusible cut out and close the circuit by closing the mount 6 Close mount F1 7 Wait at least 10 sec 8 Close mount
20. al or consequential losses resulting from usage of the power supply unit even if a warning was given that such losses could occur The company shall not be held liable for any costs such as the loss of profits or earnings equipment equipment usage software data costs of replacement products claims of third parties or for any other costs NOTES 2010 08 24 WWW ever eu 42
21. ameters selections are made using the A V keys and confirmation given by pressing the 1 key Two types of parameters have been included in the CONTROL submenu Some of them require repeated confirmation of an intended change by pressing or resignation without changing pressing the ESC key e g AwaryjneWylaczenie The modification of others consists in the appropriate placement of a flag by selecting On or Off by means of the AW keys and confirmation by pressing 1 Confirmation is followed by automatic passage to a screen one level higher in the tree structure Once confirmed a parameter is save in the unit s memory The saving process itself is signalled by the following messages Trwa zapis saving in progress Zapis OK saving successfully completed Blad zapisu saving was unsuccessful please try again Zla warto a value outside the permitted range The message appear briefly in the lower line of the screen whereafter the system automatically proceeds to a screen one level higher This principle is used for all modifiable parameters An example of saving screens has been given hereunder EDHTEOLA 1 5 EODHTEOLA 143 RH DESI UPS gt Trwa zapis prd 2010 08 24 WWW ever eu 13 Instruction manual for SINLINE PRO 10000 series power supply units CONTROL 1 3 Description Settings of power supply unit control flags Type read save Parameters AwaryjneWylaczenie f
22. ase read the instruction manual thoroughly before operating the EVER SINLINE PRO 10000 power supply unit for this will surely facilitate correct and trouble free usage The power supply unit has been manufactured in Poland in full accordance with requirements introduced for the CE symbol GENERAL INFORMATION INTENDED APPLICATION Power supply unit of the SINLINE PRO 10000 series are class LINE INTERACTIVE VI devices intended for cooperation with equipment powered from a single phase 230 V power grid NOTE SINLINE PRO 10000 power supply units intended for usage with medical life and or health support systems 2010 08 24 WWW ever eu 3 Instruction manual for SINLINE PRO 10000 series power supply units GENERAL DESCRIPTION e Sinusoidal output voltage generated in battery operation mode DPC Digital Power Control Digital control of the power supply units operating parameters such as output voltage shape output voltage frequency battery charge status battery voltage and current measurement of the capacity of a set of batteries life of batteries temperature of critical elements of the power supply unit e Digital measurement of external parameters such as mains voltage value mains current value mains voltage frequency value of active and apparent power received from the mains coefficient of mains side power value of active a
23. connected you should turn on the power supply unit switch on the computer and install the software proceeding in accordance with the attached instruction or the installation wizard prompts for Microsoft Windows N NOTE Only one link may be used at any one time The RS232 and USB ports are separated galvanically from the remaining blocks of the unit EVER SNMP HTTP NETWORK MANAGEMENT CARD The EVER management card is optional and may be installed by the user It serves to integrate the power supply unit with an Ethernet based computer network The network card is located in a special slot on the rear wall of the unit The card allows the user to manage the unit from any computer in the network This solution is most frequently used in the event of centralised power supply or if it is necessary to manage the power supply system remotely The network card has the following services implemented e SNMP agent the power supply system may be managed by means of SNMP Manager software HTTP server possibility of viewing and modifying power supply unit parameters using an internet browser e Telnet server management by means through a Telnet network terminal More information about the network card may be found in its instruction manual NOTE If the SNMP card is connected communication through the RS232 and USB links is disable while the PowerSoft Personal programme is unavailable
24. ction as disconnectors which are used for example during installation transport or storage The fuse type is specified in the technical parameters table 1 NOTE It is prohibited to use fuses other than set forward the device specification 2010 08 24 WWW ever eu 3 Instruction manual for SINLINE PRO 10000 series power supply units F1 Safeguards must be switched and off in the presenbed order 1 2 Figure 7 Internal battery protection It is necessary to observe the instruction written in the frame below the fuses namely that the fuses must be activated in the appropriate order F1 should be activated first and F2 10 sec later Failure to follow this instruction may damage the power supply unit Fusible cut out F5 protects the terminal of the external battery module and is located to the right of the terminals It disconnects both poles when the mount is open Figure 8 External battery module connectors with fuse Thermal protection The unit is equipped with thermal protection against overheating There are two protection levels If the internal temperature reaches a value close to critical a sound signal is activated and a message appears on the display The UPS remains in the current mode If the temperature continues to grow then once the critical temperature is reached an alarm message is displayed and the power supply unit switches to EMERGENCY mode 20
25. d equal to 80 Pmax Example of a battery module in a typical configuration asgen 2010 08 24 WWW ever eu 41 Instruction manual for SINLINE PRO 10000 series power supply units INFORMATION CONCERNING LEGAL PROVISIONS AND THE GUARANTEE DECLARATION OF CONFORMITY The power supply unit has been manufactured in Poland and its construction is concordant with the provisions of the pertinent standards GUARANTEE The guarantee for the appliance constitutes a separate document which is attached to the product This document must meet all formal requirements e g date of sale stamp of the seller The manufacturer has made every effort to ensure that the offered products are free of defects in materials and workmanship The liability of the company under the guarantee is limited to the repair or replacement of products containing such defects The method of removal of defects shall be determined by the manufacturer The guarantee shall not cover appliances with mechanical damage which were improperly maintained or used or which were modified in any way by the user Apart from the provisions set forward in the guarantee card EVER Sp z 0 0 does not provide any guarantees or warranties including any guarantees of marketability or Suitability for a specific application Apart from the provisions set forward in the guarantee card EVER Sp z o o shall not be held liable for any direct indirect special accident
26. dzony damaged battery EPO signalling of the forced switch of the power supply unit to the EMERGENCY EPO mode BladWewnetrzny internal device error necessary to contact the service shop Screen view ALARMY 2 2 Aiku Uszkodzona Brak EPO Bpak zns Brak 2010 08 24 WWW ever eu 17 Instruction manual for SINLINE PRO 10000 series power supply units STATISTICS submenu The STATISTICS submenu comprises four screens The menu can be navigated in the same way as described above Screens are selected using the keys and confirmation given by pressing 4 The screens display information concerning the operational history of the power supply unit STATISTICS 1 4 Description Statistical data Type read Parameters Zanikow the number of occurrences of events connected with an input voltage decay Spadkow the number of events connected with a fall in voltage to a value below the declared lower input voltage Wzrostow the number of events connected with a rise in voltage to a value above the declared upper input voltage limit Screen view CTATWSTYER 1 4 STATISTICS 2 4 Description Statistical data Type read Parameters Przeciazen the number of events connected with an overload of the power supply unit Przegrzan the number of events connected with an overheat of the power supply unit Zwarc the number
27. eans that although the average power of the powered equipment is within the range approved for the power supply unit the equipment nevertheless shuts down the unit This occurs because the powered equipment temporarily takes up power that considerably exceeds the nominal power of the unit which leads to the detection of an overload and the shutdown of the unit It is recommended that batteries be handled and controlled by competent persons who have been duly trained and observe the required safety measures The batteries should be replaced with products of the same type and the same number of cells or units All batteries should be replaced simultaneously WARNING Protect the batteries against fire risk of explosion WARNING Do not open the batteries protect them against damage Spilt electrolyte is harmful the skin and eyes may also be toxic 2010 08 24 WWW ever eu 38 Instruction manual for SINLINE PRO 10000 series power supply units COOPERATION OF THE POWER SUPPLY UNIT WITH ELECTRICITY GENERATORS SINLINE PRO 10000 series UPS units are class LINE INTERACTIVE devices which synchronise with the voltage of the power grid By definition the unit tolerates mains voltage fluctuations and frequency changes within a certain range with reference to a model frequency of 50 Hz cf table of technical parameters In the event of cooperation with an electricity generator frequency changes wil
28. erload rises to 105 the unit will start signalling this development by a continuous sound and the appropriate message on the display As in the case of BACKUP mode this state will last until the overload falls below the set level CONFIGURATION 3 4 ProgKas Prz In NORMAL mode there is no time limit as opposed to the BACKUP mode In NORMAL mode the parameters of power line fusible cut out F4 function as the upper overload limit Short circuit protection In BACKUP mode there is an electronic short circuit protection which when a short circuit occurs limits the short circuit current to a safe level The occurrence of a short circuit is indicated by the corresponding message and a rapid intermittent sound signal If the short circuit lasts in excess of 100 ms the power supply unit switches to EMERGENCY mode The input power lines primary line and service bypass line are protected by automatic fuses fuses with designations F3 and F4 F3 F4 L L N Figure 6 Input connectors with fuses Surge protection The power supply unit is fitted with surge protection at the input which protects the circuits of receivers and the internal circuitry of the unit against overvoltage caused by atmospheric phenomena and interference in the power grid Battery protection Batteries are protected with fusible cut outs The terminal of the external battery module and the internal batteries are protected separately This safeguards also fun
29. from the start menu and select system properties In the list of equipment find the USB bus branch usually it is an open branch and select the emergency power supply unit Through device properties accessed by right clicking the icon with your mouse update the device driver proceeding in accordance with the screen prompts As the driver location select the PowerSoft installation catalogue typically C Program Files PowerSoft In order to uninstall the PowerSoft software just select the PowerSoft Uninstall icon under the appropriate item in the Start menu You can also uninstall the programme from the Add remove programmes application in the control panel Installing on a Linux Unix system The binary version of the application for Linux Unix systems is delivered in the following forms CentOS RedHat Suse Linux Fedora Core For CentOS RedHat Suse Linux and Fedora Core the software is delivered in the form of an RPM package You can install the software using any package manager in the installed system If you are using a command line the software will be installed once you type in the following command 2010 08 24 WWW ever eu 36 Instruction manual for SINLINE PRO 10000 series power supply units rpm ivh powersoftpersonal x x x i386 rpm Users working with the software must possess system administrator privileges root in order to install and subsequently use the programme Following installation the packa
30. ge is located in the catalogue usr local powersoft In order to uninstall the application write the following command in the command line rpm ev powersoftpersonal X X x Debian For Debian systems the software is delivered in the form of a DEB package Installation is performed by means of the following command dpkg install powersoftpersonal x x x deb In order to uninstall the application write the following command in the command line dpkg remove powersoft FreeBSD For FreeBSD systems the software is delivered in the form of a default package format intended for FreeBSD systems Installation is performed by means of the following command pkg add powersoftpersonal x x x tbz In order to uninstall the application write the following command in the command line pkg delete powersoft NOTE FreeBSD systems do not support power supply unit communication over the USB link Starting Following installation the system service is started automatically while the control panel application is located in usr local powersoft Please note that the system location should be Polish in order to correctly display Polish diacritical marks Updating software Windows systems The software installer for Windows systems has an integrated automatic software updater The PowerSoft software can regularly check whether a new version is available and inform the user thereof By default the availability of
31. he batteries are topped up 2010 08 24 WWW ever eu 29 Instruction manual for SINLINE PRO 10000 series power supply units BACKUP mode BATTERY OPERATION 000000000 If the primary power line does not satisfy the mains correctness criteria the power supply unit switches to the BACKUP mode battery operation mode In BACKUP mode the inverter supplies power to the battery outputs STOP mode The power supply unit is logically switched off from the user interface no voltage satisfying the correctness criteria is present on the primary line This is also an intermediate state when the power supply unit switches from EMERGENCY mode READINESS mode pe The power supply unit is logically switched off from the user interface while the primary line satisfies mains correctness criteria Storage cell preservation mechanisms are active Once the power supply unit switches from STANDBY mode to READINESS mode the battery charge level is checked If the level is below the set threshold CONFIGURATION 3 4 Poj z STB the unit remains in this state until the required minimum is reached The appropriate message is displayed on the panel i O STANDBY mode WAITING Passage to STANDBY mode may be effected solely from the BACKUP mode in the event of battery discharge or forced from the user interface CONTROL 2 3 UPS gt STB Switching occurs after a preconfigured time CONFIGURATION 2 4 Opoz STB The unit remains in t
32. his mode if no voltage satisfying mains correctness criteria is present on the primary line and the power supply unit is logically switched off The logical switching off of the unit causes it to switch to STOP or READINESS mode EMERGENCY mode 0 00000000000 Switching to the EMERGENCY mode may be caused by an overload excess temperature short circuit an internal error or EPO activation The power supply unit is logically switched off and the processing blocks are inactive OTHER FUNCTIONAL ELEMENTS PROTECTION Overload protection An overload state above 105 is indicated by a continuous sound signal and the corresponding message on the display If in BACKUP mode operation the load is maintained at a level of 105 120 the power supply unit will remain in the current operation mode for 10 seconds and thereafter switch to the EMERGENCY mode If the overload exceeds 120 of the rated power of the unit the device immediately switches to EMERGENCY mode The power supply unit remains in this mode until the manual intervention of the user Overload signalling will be switched off and the unit will switch to BACKUP operation mode overload within 105 120 and the unit has not yet switched to EMERGENCY 2010 08 24 WWW ever eu 30 Instruction manual for SINLINE PRO 10000 series power supply units mode only when the overload falls below the set level CONFIGURATION 3 4 ProgKas Prz If in NORMAL operation mode the ov
33. hout batteries installed it should be removed from the pallet by at least 3 people Please check the contents of the package The package should contain the following power supply unit PowerSoft Personal software on a CD disk RS232 communication cable for connecting the power supply unit to a PC USB communication cable for connecting the power supply unit to a PC set of fusible cut outs type 10x38 2 pieces instruction manual installation guidelines guarantee card mounting holders 2 pieces 2010 08 24 WWW ever eu 22 Instruction manual for SINLINE PRO 10000 series power supply units INSTALLATION OF THE POWER SUPPLY UNIT The weight of the device should be considered when selecting the point of installation The unit should be used only in rooms where the levels of dustiness temperature and humidity are concordant with the device specifications Appropriate cooling conditions must be ensured for the unit to work correctly For this reason the unit s ventilation openings must be uncovered at all times while the distance between the unit and other objects should not be less than 30 cm NOTE It is forbidden to install the appliance in the vicinity of flammable materials Detailed information has been given in a separate document containing installation guidelines provided with the product Before placing the power supply unit you should install the two additional mounting holders which impr
34. l have a value variable over time and are strictly dependent on changes in the load value If changes in generator voltage frequency exceed the adopted tolerance the UPS shall consider such a value as incorrect and switch to the appropriate operation mode in accordance with its principles of operation outlined hereabove STORAGE MAINTENANCE AND TRANSPORT The power supply unit should be stored and transported in accordance with the installation guidelines set forward in a separate document attached to the device If these requirements are not satisfied EVER Sp z 0 0 shall not assume any liability for mechanical damage caused during transport RECYCLING The appropriate recycling of used electric and electronic equipment helps protect human health and the natural environment against the negative effects brought about by the presence of hazardous materials and components and the improper storage and processing of such equipment The Act of 29 07 2005 on Waste Electric and Electronic Equipment Article 22 1 Point 1 2 x The crossed out waste container symbol means that in the European Union a used product should be handed over to a special waste handling outlet This concerns both the appliance itself and all accessories marked with this symbol Such products should not be disposed of together with unsorted municipal waste Method of safe removal of batteries from the device The batteries should be removed fr
35. lding Replace the fuse elements in their respective mounts Close the fusible cut out mounts of all connected battery modules in turn if any are still connected Close the F1 mount in the power supply unit Wait at least 10 sec Close the F2 mount in the power supply unit the batteries are connected Switch fuses F3 and F4 ON Set the appropriate battery related parameters of the power supply unit CONFIGURATION 4 4 N NOTE It is forbidden to leave loose cable ends They could be under a voltage that is dangerous to health and or life 2010 08 24 www ever eu 25 Instruction manual for SINLINE PRO 10000 series power supply units CONNECTING THE POWER SUPPLY UNIT Connecting elements WEJ AC F3 F4 t N N O F5 Figure 4 Connecting elements with safeguards F3 safeguard of the service BYPASS line F4 primary line protection WEJ AC input terminals Lg service BYPASS phase line L primary phase line N primary neutral line WYJ AC output terminals L output phase line N output neutral line WEJ DC input terminals of the external battery module positive pole negative pole F5 safeguards of the terminal of the external battery module fusible cut out appliance protective earthing point connection of a cable with an eyehole connector by means of an M6 screw The power supply unit is not
36. le mounting grip 11 Service BYPASS switch UPS 12 Connection link 13 Fusible cut out for external battery packs 14 Device earthing point 15 Mounting holders 2010 08 24 WWW ever eu 7 Instruction manual for SINLINE PRO 10000 series power supply units USER INTERFACE The user interface consists of a four button keypad located on the upper cover of the power supply unit an LCD and three LEDs They allow the user to monitor the unit s operating parameters and also modify some of them The method of using the interface and the meanings of individual parameters have been described hereunder Figure 3 View of the user interface Table 1 Meanings of signalling diodes Graphical symbol Designation Description LED 1 LED indicating the unit s operation mode NORMAL BACKUP AVR LED 2 LED signalling activation of the AVR system AN LED 3 LED signalling activation of the EMERGENCY mode Table 2 Optical diode signalling LED 1 LED 2 LED 3 Operation mode UNKNOWN STANDBY F NORMAL BACKUP READINESS EMERGENCY INIT STOP F the status may be configuration dependent none or red flashes The unit is also equipped with an audible signalling system for its respective states cf table Table 3 Audible signalling Action Audible signalling NORMAL mode None inter
37. matic Voltage Regulation AVR system allows the power supply unit to immediately correct even small drops and rises in mains voltage so as to ensure that receivers enjoy the proper supply conditions without using up the power gathered in batteries What is more the unit has been fitted with an advanced DIGITAL POWER CONTROL DPC system which precisely shapes the course of the unit s output voltage so as to generate a purely sinusoidal voltage During mains operation the system filters the mains voltage in order to eliminate interferences and distortions that could be potentially harmful to receivers 2010 08 24 www ever eu 5 Instruction manual for SINLINE PRO 10000 series power supply units The dedicated DPC system controls the operation of the power supply unit and has an extremely precise and rapidly acting system for detecting overloads and output short circuits during battery operation In mains operation mode short circuit protection is provided by fuses with overloads being brought to the user s attention both audibly and optically A special soft start mode has been introduced which allows trouble free start up with large loads that draw considerably start up power such as laser printers In addition the DPC enables long term battery operation of the power supply unit by allowing the user to connect an additional battery pack and control the internal temperature by means of an active cooling system which is activated as
38. mittent signal rapidity dependent on the charge level of batteries PAONUP MEIE the more rapid the signal the lower the battery charge level Forced switch to the STANDBY mode intermittent signal two successive short signals followed by a pause EMERGENCY mode Event dependent Overload continuous signal Short circuit rapid intermittent 50 50 signal Overheat slow intermittent 50 50 signal EPO activation intermittent sound silence 1s 5s signal All successive screens shown on the LCD are organised in a tree structure as presented in the following figure 2010 08 24 WWW ever eu 8 Instruction manual for SINLINE PRO 10000 series power supply units PE 5911511915 Fe SDILSILYLS SONLLI3S bib 52151415 tit HOLLYUNSIAHOD BE HOLLVUNSISHOD 5 5 TOULHOD tiz HOLLYUNDIAHOD ce TOH1HOD bib fib 1081N02 253 tit 52011511015 SU99J9S Jo eunBiJ HOLLVOIHLLH3I cz Sw gt opas nuauiqns NHIN bib qun vdd w bie AMALIVE zz 104110 fsa cay fea www ever eu 2010 08 24 Instruction manual for SINLINE PRO 10000 series power supply units SCREENS SCREENSAVER Description An information screen that is activated 5 minutes after the last press of a button This is accompanied by the switching off of the LCD panel s
39. nd apparent power connected to the power supply unit s output coefficient of output side power e An automatic voltage regulation system AVR which increases and decreases e Mains voltage filtration e RHS232 and USB serial ports for communication with a PC e Socket for adapter cards e g a management Possibility of connecting additional battery packs Possibility of browsing network event statistics e Calculating the current available emergency operation time e PowerSoft Personal software is used to control the power supply unit and automatically close the system 2010 08 24 WWW ever eu 4 Instruction manual for SINLINE PRO 10000 series power supply units UPS BYPASS service switch OUTPUT Figure 1 Simplified block diagram of the power supply unit The SINLINE PRO 10000 power supply unit is a modern electronic device that serves as an autonomous source of sinusoidal 230 V voltage The device belongs to the LINE INTERACTIVE VI class of UPSs which includes power supply units that synchronize with the power grid The unit is equipped with the unique CLEAR DIGITAL SINUS CDS system that during battery operation generates a precisely stabilised output voltage with a sinusoidal shape which makes it possible to power a broad range of loads that do not tolerate quasi sinusoidal voltages The application of this system increases the reliability of the device guaranteeing its stable operation The Auto
40. om the appliance by an authorised service outlet or by a duly authorised electrician 2010 08 24 WWW ever eu 39 Instruction manual for SINLINE PRO 10000 series power supply units TECHNICAL PARAMETERS INSTALLATION GUIDELINES PARAMETER POWER SUPPLY UNIT SINLINE PRO 10000 10 kVA Apparent active power 8kW POWER SUPPLY PARAMETERS Power supply system topology 1P3W Rated voltage 230 V Rated current 46A Rated frequenc input quency 50 Hz Minimum cable diameter 10 mm Switch fuse 80 A gG Primary and BYPASS line Switch fuse 80 A gG OUTPUT PARAMETERS Output system topology 1P3W Nominal input voltage 230 V Rated current 44 A Minimum cable diameter 10 mm Output line Switch PU 80 A safeguards disconnector Mi ENVIRONMENTAL PARAMETERS Quantity of heat released under 600 BTU nominal work conditions Operating temperature 10 40 Storage temperature 0 400 Humidity lt 95 Height above sea level lt 1000 m MECHANICAL PARAMETERS Device dimensions width x depth x height 340 x 740 x 795 mm Power supply unit weight 200 kg Operating distance front gt 200 mm sides gt 100 mm rear gt 300 mm 2010 08 24 www ever eu 40 Instruction manual for SINLINE PRO 10000 series power supply units TECHNICAL DATA
41. orced passage of the power supply unit to the EPO mode from the user interface level UPS switching the power supply unit on off Buzzer switching on off of battery charge status signalling for the BACKUP mode Screen view KUMTROLH Les a et CONTROL 2 4 Description Settings of power supply unit control flags Type read save Parameters Czas Wyl EPO temporary deactivation 1 min of the EPO link UPS gt STB manual forcing of the STANDBY mode switching after a specified time CONFIGURATION 2 4 Opoz STB KasujAwarie deletion of EMERGENCY mode flags Screen view KOHTROLA FER EE EFO hal Description Settings of power supply unit control flags Type read save Parameters Test Aku permission to update the battery status indicator following the complete discharge of batteries Screen view KOHMTROLA 3 3 TestAak i 2010 08 24 WWW ever eu 14 Instruction manual for SINLINE PRO 10000 series power supply units CONFIGURATION submenu The CONFIGURATION submenu is divided into four groups The menu can be navigated in the same way as described above The user may change the power supply unit parameter values if the keypad is not locked Screens are selected using the A keys and confirmation given by pressing 1 As in the case of parameters selections are made using the A V keys and confirmation given by pressing the 1 key The CONFIG
42. ove its stability and allow it to be screwed to the floor if necessary To do this loosen the 4 M8 screws located in the central bottom part of the appliance Tip the device slightly and slide in the holders Next screw the holders to the device using the 4 M8 screws MOUNTING HOLDERS Figure 2 Mounting holders BATTERY MODULE Additional battery modules can be connected to the SINLINE PRO 10000 series power supply units The modules are attached to the connection terminals on the rear panel of the unit Adding additional battery packs extends the time of battery mode operation The battery modules are connected in a row and are protected by additional fuses located in their rear panels NOTE In the event of a burnt out the fusible cut outs should be replaced with new ones that are fully concordant with the specification 2010 08 24 WWW ever eu 23 Instruction manual for SINLINE PRO 10000 series power supply units UPS SINLINE PRO 10 BATTERY MODUL BATTERY MODUL e TIL 0 3 ai i i D i SUCCESSIVE MODULES COLLECTIVE EARTHING POINT switching station Figure 3 Connecting battery modules Connecting modules Note When the safeguards are active the voltage on the N connection terminals is dangerous to health and or life All safeguards must be switched off before carrying out any installation
43. provided with connection wires with sockets Thus it is connected by screwing the ends of individual cables to the links Next the cables should be protected against tearing out to do this fasten them with bands to the special grips located beneath the connecting elements Cable diameters sizes should be concordant with the installation guidelines The cables should terminate in metal sleeves 2010 08 24 WWW ever eu 26 Instruction manual for SINLINE PRO 10000 series power supply units The system must be structured in such a way as to make possible the disconnection of the power supply unit from the mains e g by the switching of integrated overcurrent cut outs NOTE The UPS should be connected by qualified and authorised personnel only NOTE The UPS is completely disconnected from the power network only when the power supply cord is disconnected It is recommended that protection circuits of the building s electric system be used as one of the protection levels The parameters of the building s electric system protection circuits should be selected in accordance with the type and magnitude of the load connected to the system In extreme cases different characteristics of the building s and power supply unit s protection systems may cause the former to be activated more rapidly NOTE The user is obligated to place the following information on all mains cut outs installed far from the point of pl
44. submenu The MEASUREMENTS submenu is divided into four topical groups INPUT OUTPUT BATTERY TEMPERATURE INPUT 1 4 Description Power supply unit input parameters Type read Parameters U input voltage of the power supply unit input current the power supply unit f input frequency of the power supply unit PF input coefficient of the power supply unit P input active power of the power supply unit input apparent power of the power supply unit Screen view OUTPUT 2 4 Description Power supply unit output parameters Type read Parameters U output voltage of the power supply unit output current of the power supply unit f output frequency PF output power coefficient P output active power output apparent power 2010 08 24 WWW ever eu 11 Instruction manual for SINLINE PRO 10000 series power supply units Screen view DERE ti BATTERY 3 4 Description Battery related parameters Type read Parameters U battery section voltage absolute battery current value Q charge level of batteries calculated for the current load Tau anticipated autonomous time StanAku indicates the degree of wear of the batteries this value is updated following the complete discharge of the batteries if the TestAku parameter is switched on 100 default value means that the batteries are fully efficient Screen view GK UMULAT IR Vi See ace
45. supply units 10 11 Replace the fuse elements in their respective mounts Close the fusible cut out mounts of all connected battery modules in turn 12 13 14 15 16 Close the F1 mount in the power supply unit Wait at least 10 sec Close the F2 mount in the power supply unit the batteries are connected Switch fuses F3 and F4 ON Set the appropriate battery related parameters of the power supply unit CONFIGURATION 4 4 Switch off the power supply unit by means of the user interface CONTROL 1 3 UPS Display data that directly concerns the number of connected batteries will be automatically updated once the batteries are topped up Until this happens the information given may be inaccurate Disconnecting modules 1 c t e 12 13 14 15 Switch off the power supply unit by means of the user interface CONTROL 1 3 UPS Set fuses F3 and F4 in the power supply unit OFF Disconnect the safeguards of the main line and the BYPASS in the room building switching station Disconnect safeguards F1 F2 and F5 in the power supply unit and F1 and F2 all battery modules to do this open the fusible cut out mounts and remove the fuse elements Remove the plugs of connecting elements Disconnect the modules The connecting cables must be fully disconnected Secure the connecting elements by screwing in the protective plug Activate the safeguards in the switching station of the room bui
46. t which the power supply unit ceases to signal an overload Screen view KOHFIGURACIA 364 z STE 1 4 gt mma NL Prz E CONFIGURATION 4 4 Description Power supply unit parameters Type read save Parameters Poj Aku the capacity of batteries used LiczbaSekcji number of battery sections the sum of internal and external battery sections Pr Ladowania sum total of battery charging current Screen view TGURAC Aku Liczhatekcij Pre 1 2010 08 24 WWW ever eu 16 Instruction manual for SINLINE PRO 10000 series power supply units ALARMS submenu The ALARMS submenu comprises two screens The menu can be navigated in the same way as described above Screens are selected using the keys and confirmation given by pressing 4 Alarm screens inform about the type of alarm which caused the power supply unit to switch to EMERGENCY mode ALARMS 1 2 40U 00 00000000 eee Description Power supply unit alarms Type read Parameters Zwarcie short circuit on the output of the power supply unit Przeciazenie excessive load connected to the output of the power supply unit Przegrzanie excessive temperature of the internal elements of the power supply unit Screen view RLARM 1 2 Warcie Brak Praeciazenie trak Frzedrzanie Erak ALARMS 2 2 Description Power supply unit alarms Type read Parameters AkuUszko
47. tems NOTE The EPO circuit must be a separate circuit and it is prohibited to connect it with other systems Service BYPASS The power supply unit is equipped with a service BYPASS line switch which enables direct switching of the BYPASS line to the unit s output terminals bypassing the unit s blocks o o o o x lt gt gt a a Figure 8 Manual BYPASS line switch 2010 08 24 WWW ever eu 33 Instruction manual for SINLINE PRO 10000 series power supply units Switch in the UPS position normal operation of the power supply unit Switch in the BYPASS position the BYPASS line is switched to the input terminals Switching may be performed at any time COOPERATION OF THE POWER SUPPLY UNIT WITH A PC RS232 AND USB COMMUNICATION The user can modify the parameters of the power supply unit not only from the user interface panel but also by means of the dedicated PowerSoft software Please note however that this software does not enable changing all of the configuration parameters available from the device s panel SINLINE PRO 10000 series power supply units have been provided with advanced management options The user has at his disposal two RS232 and USB communication links and the PowerSoft Personal programme which is delivered with unit To maintain the desired cooperation it is necessary to connect the unit to a free computer port by means of the attached cable Once the cable is
48. wer supply unit and modules also between modules It is strictly forbidden to leave any loose wires Reinstall the protective plugs 9 Close the mounts of fusible cut outs F1 F2 and F5 in the power supply unit and of F1 and F2 in the modules if the fuse elements have been removed The fuse elements should not be stored in the power supply unit if it is not installed 2010 08 24 WWW ever eu 28 Instruction manual for SINLINE PRO 10000 series power supply units OPERATING MODES OF THE POWER SUPPLY UNIT POWER SUPPLY OH IH EACH OPERATING MODE IH CASE OF MALFUNCTION EMERGENCY STAHD BY BACKUP Figure 5 Graph presenting the operation modes of the power supply unit UNKNOWN P An intermediate state that occurs when the power supply unit is started up following energisation SII UII CA OO i An intermediate state that occurs following initiation of the hardware platform by means of start up values or during a return from EMERGENCY mode NORMAL mode MAINS OPERATION 1 1 10000 In for the power supply unit to be in NORMAL mode it must by logically switch on from the user interface In addition the input primary power line must satisfy the mains correctness criteria correct value of voltage and frequency The unit then supplies power to the outputs from the abovementioned line with the AVR system making the necessary corrections In this mode t
49. work Switch off the power supply unit by means of the user interface CONTROL 1 3 UPS Set fuses F3 and F4 to OFF Disconnect all battery safeguards F1 F2 and F5 by opening the fusible cut out mounts No specific order has to be observed Remove the fuse elements Disconnect all battery safeguards for already connected and newly connected battery modules to do this open the fusible cut out mounts and remove the fuse elements Disconnect the safeguards of the main line and the BYPASS in the room building switchboard Screw out the protective plugs of connecting elements rear panel of the power supply unit and modules Connect the module to the power supply unit making sure to maintain the correct polarity The modules are connected in a row i e connections are made between the power supply unit and the first module then between the first and second modules between the second and third modules etc The protective earthing cables from each appliance are routed to a common point in the switching station of the building Having checked the correctness of connections secure the connecting elements using the plugs The cables should be secured against tearing out to this end fix them with bands to the special grips located beneath the connectors Activate the safeguards in the switching station of the room building 2010 08 24 WWW ever eu 24 Instruction manual for SINLINE PRO 10000 series power