Tripp Lite MODBUS Management Accessory Card for UPS Remote Monitoring and Control

image

Contents

1. Description Address Value Unit Parallel Master ID 0x0482 0 99 Available Event Log Description Address Value Unit UPS Event Log 0x0483 0 500 Event Log Report Format 0x0484 0 1 Event Reporting Method 0x0485 0 1 Event Log Report Format 0 NT 9 byte format 1 NH 8 byte format Power Module Attribute Description Address Value Unit Power Module ID Attribute 0x0486 Lo ID 1 4 Hi Attribute Power Module ID Attribute 0x0487 Power Module ID Attribute 0x0488 Power Module ID Attribute 0x0489 Reserved Ox048A Reserved 0x048B Power Module Attribute which is used to identify the attribute of the power module BO Bl B2 B3 B4 B5 B6 B7 PFC Rectifier Charger Inverter Bypass TBD TBD TBD 0 pe ratio N continued Power Module General Status Description Address Value Unit Power Module ID General Status 0x048C Lo ID 1 4 Hi Status Power Module ID General Status 0x048D Power Module ID General Status 0x048E Power Module ID General Status 0x048F Reserved 0x0490 Reserved 0x0491 Power Module General Status BO The power module exists or the power module is powered Bl B2 B3 B4 B5 B6 B7 Fault shutdown Power Module PFC Status Description Address Value Unit Power Module ID 0x0492 1 4 PFC Status 0 1 0x0493 Lo Status 0 Hi Status 1 Power Module
2. N w 62 8 N ON A Q O ORO N ESN amp Owner s Manual Programmable MODBUS Card Model MODBUSCARD Introduction Installation Configuration Operation Warranty amp Warranty Registration TRIPP LITE 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2010 Tripp Lite All rights reserved Introduction The MODBUSCARD provides UPS systems with the functionality of communication with PCs through MODBUS protocol e Implements MODBUS RTU protocol e Provides MODBUS functions including Read Coils Discrete Inputs Holding Registers Input Registers Write Single Coil and Single Register e Provides RS 422 485 and RS 232 interfaces PC communicates with UPS via RS 422 485 or RS 232 or both at the same time Installation The MODBUSCARD should be installed in the accessory slot intended for Tripp Lite s SNMPWEBCARD Remove your UPS system s SNMPWEBCARD from its accessory slot Align the MODBUSCARD with the guides in the accessory slot and push the card into the slot until the ports are nearly even with the rear surface of the UPS If your UPS system does not have an SNMPWEBCARD installed use a screwdriver to remove the accessory slot cover from the UPS While the UPS is turned on align the MODBUSCARD with the guides in the accessory slot and push the card into the slot until the ports are nearly even with the rear surface of the UPS Important Installation Note
3. Manufacture Byte 12 13 0x04FE Lo Byte 12 Hi Byte 13 Manufacture Byte 14 15 0x04FF Lo Byte 14 Hi Byte 15 Reserved 0x0500 Reserved 0x0501 Reserved 0x0502 0 pe ratio N continued Model Description Address Value Unit Model Byte 0 1 0x0503 Lo Byte 0 Hi Byte 1 Model Byte 2 3 0x0504 Lo Byte 2 Hi Byte 3 Model Byte 4 5 0x0505 Lo Byte 4 Hi Byte 5 Model Byte 6 7 0x0506 Lo Byte 6 Hi Byte 7 Model Byte 8 9 0x0507 Lo Byte 8 Hi Byte 9 Model Byte 10 11 0x0508 Lo Byte 10 Hi Byte 11 Model Byte 12 13 0x0509 Lo Byte 12 Hi Byte 13 Model Byte 14 15 0x050A Lo Byte 14 Hi Byte 15 Reserved 0x050B Reserved 0x050C Reserved 0x050D Firmware Version Description Address Value Unit Firmware Version Byte 0 1 0x050E Lo Byte 0 Hi Byte 1 Firmware Version Byte 2 3 0x050F Lo Byte 2 Hi Byte 3 Firmware Version Byte 4 5 0x0510 Lo Byte 4 Hi Byte 5 Firmware Version Byte 6 7 0x0511 Lo Byte 6 Hi Byte 7 Firmware Version Byte 8 9 0x0512 Lo Byte 8 Hi Byte 9 Firmware Version Byte 10 11 0x0513 Lo Byte 10 Hi Byte 11 Firmware Version Byte 12 13 0x0514 Lo Byte 12 Hi Byte 13 Firmware Version Byte 14 15 0x0515 Lo Byte 14 Hi Byte 15 Reserved 0x0516 Reserved 0x0517 Reserved 0x0518 CPU Description Address Value Unit CPU Byte 0 1 0x0519 Lo Byte 0 Hi Byte
4. When requesting compliance information for this product always refer to the series number The series number should not be confused with the marking name or model number of the product Tripp Lite has a policy of continuous improvement Product specifications are subject to change without notice TRIPP LITE 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 18 201003113 93 2987
5. 1 CPU Byte 2 3 0x051A Lo Byte 2 Hi Byte 3 Reserved 0x051B UPS Connection Status Description Address Value Unit UPS Connection Status 0x051C 0 Disconnection 1 Connection Note Filed value OxF FFF in Input Registers represents that field is not supported by UPS Warranty amp Warranty Registration LIMITED WARRANTY Seller warrants this product if used in accordance with all applicable instructions to be free from original defects in materials and workmanship for a period of 2 years except internal UPS system batteries outside USA and Canada year from the date of initial purchase If the product should prove defective in material or workmanship within that period Seller will repair or replace the product in its sole discretion Service under this Warranty can only be obtained by your delivering or shipping the product with all shipping or delivery charges prepaid to Tripp Lite 1111 W 35th Street Chicago IL 60609 USA Seller will pay return shipping charges Visit www tripplite com support before sending any equipment back for repair THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW ALL IMPLIED WARRANTIES INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS ARE LIMITED IN DURATION TO THE WARRANTY PERIOD
6. 9600 ON ON 19200 SW3 3 OFF Disable Parity Check Default i ON Enable Parity Check Parity Check OFF Even Parity Default SW3 4 ON Odd Parity SW3 5 SW3 6 OFF OFF MODBUS Protocol Default Protocol ON OFF Regular Protocol OFF ON 3 Phase Protocol SW3 7 OFF Disable RS 485 422 Termination Resistor Default oo ON Enable RS 485 422 Termination Resistor Termination Resistor E SW3 8 OFF Disable RS 422 Termination Resistor Default ON Enable RS 422 Termination Resistor LED Indicators LED Status Description OFF UPS disconnected RED Flashing 1 second UPS connected GREEN Illuminated 0 2 seconds Receiving PC request Discrete Inputs Range 0x0100 0x012F Read Function 0x02 The Read Discrete Inputs function code is used to read 1 2000 contiguous status of Discrete Inputs in a remote device The starting address and number of inputs is specified by the request Protocol Data Unit Addresses start at 0 and Discrete Inputs numbered 1 16 would address as 0 15 Description Address Value 0 Value 1 Alarm Temperature 0x0100 OK Over Temperature Alarm Input Bad 0x0101 OK Input Bad Alarm Output Bad 0x0102 OK Output Bad Alarm Overload 0x0103 OK Overload Alarm Bypass Bad 0x0104 OK Bypass Bad Alarm Output Off 0x0105 Output On Output Off Alarm UPS Shutdown 0x0106 OK Shutdown Ala
7. INV 0x04BA 0 9999 0 1 Voltage Temperature INV R 0x04BB 0 9999 0 1 Voltage Temperature INV S 0x04BC 0 9999 0 1 Voltage Temperature INV T 0x04BD 0 9999 0 1 Voltage Power Module ID 0x04BE 1 4 Temperature PFC 0x04BF 0 9999 0 1 Voltage Temperature TBD 0x04C0 0 9999 0 1 Voltage Temperature INV 0x04C1 0 9999 0 1 Voltage Temperature INV R 0x04C2 0 9999 0 1 Voltage Temperature INV S 0x04C3 0 9999 0 1 Voltage Temperature INV T 0x04C4 0 9999 0 1 Voltage Power Module ID 0x04C5 1 4 Temperature PFC 0x04C6 0 9999 0 1 Voltage Temperature TBD 0x04C7 0 9999 0 1 Voltage Temperature INV 0x04C8 0 9999 0 1 Voltage Temperature INV R 0x04C9 0 9999 0 1 Voltage Temperature INV S 0x04CA 0 9999 0 1 Voltage Temperature INV T 0x04CB 0 9999 0 1 Voltage Reserved 0x04CC Reserved 0x04CD Reserved 0x04CE Reserved 0x04CF Reserved 0x04D0 Reserved 0x04D1 Reserved 0x04D2 Reserved 0x04D3 Reserved 0x04D4 Reserved 0x04D5 Reserved 0x04D6 Reserved 0x04D7 Reserved 0x04D8 Reserved 0x04D9 0 pe ratio N continued Power Module Inverter Voltage Description Address Value Unit Power Module ID 0x04DA 1 4 Inverter Voltage R 0x04DB 0 9999 0 1 Voltage Inverter Voltage S 0x04DC 0 9999 0 1 Voltage Inverter Voltage T 0x04DD 0 9999 0 1 Voltage Power Module ID 0x04DE 1 4 Inverter Voltage R 0x04DB 0 9999 0 1 Voltage Inverter Voltage S 0x04DC 0 9999 0 1 Voltage
8. Inverter Voltage T 0x04DD 0 9999 0 1 Voltage Power Module ID 0x04DE 1 4 Inverter Voltage R 0x04DF 0 9999 0 1 Voltage Inverter Voltage S 0x04E0 0 9999 0 1 Voltage Inverter Voltage T 0x04E1 0 9999 0 1 Voltage Power Module ID 0x04E2 1 4 Inverter Voltage R 0x04E3 0 9999 0 1 Voltage Inverter Voltage S 0x04E4 0 9999 0 1 Voltage Inverter Voltage T 0x04E5 0 9999 0 1 Voltage Power Module ID 0x04E6 1 4 Inverter Voltage R 0x04E7 0 9999 0 1 Voltage Inverter Voltage S 0x04E8 0 9999 0 1 Voltage Inverter Voltage T 0x04E9 0 9999 0 1 Voltage Reserved 0x04EA Reserved 0x04EB Reserved 0x04EC Reserved 0x04ED Reserved 0x04EE Reserved 0x04EF Reserved 0x04F0 Reserved 0x04F1 Battery Cabinet Temperature Description Address Value Unit Battery Cabinet 1 Temperature 0x04F2 0 999 Degrees Celsius Battery Cabinet 2 Temperature 0x04F3 0 999 Degrees Celsius Battery Cabinet 3 Temperature 0x04F4 0 999 Degrees Celsius Battery Cabinet 4 Temperature 0x04F5 0 999 Degrees Celsius Reserved 0x04F6 Reserved 0x04F7 Manufacture Description Address Value Unit Manufacture Byte 0 1 0x04F8 Lo Byte 0 Hi Byte 1 Manufacture Byte 2 3 0x04F9 Lo Byte 2 Hi Byte 3 Manufacture Byte 4 5 0x04FA Lo Byte 4 Hi Byte 5 Manufacture Byte 6 7 0x04FB Lo Byte 6 Hi Byte 7 Manufacture Byte 8 9 0x04FC Lo Byte 8 Hi Byte 9 Manufacture Byte 10 11 0x04FD Lo Byte 10 Hi Byte 11
9. SET FORTH ABOVE AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES Some states do not allow limitations on how long an implied warranty lasts and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations or exclusions may not apply to you This Warranty gives you specific legal rights and you may have other rights which vary from jurisdiction to jurisdiction WARNING The individual user should take care to determine prior to use whether this device is suitable adequate or safe for the use intended Since individual applications are subject to great variation the manufacturer makes not representation or warranty as to the suitability or fitness of these devices for any specific application Not compatible with PoE Power over Ethernet applications WARRANTY REGISTRATION Visit www tripplite com warranty today to register the warranty for your new Tripp Lite product You ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product No purchase necessary Void where prohibited Some restrictions apply See website for details Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and identification your Tripp Lite product has been assigned a unique series number The series number can be found on the product nameplate label along with all required approval markings and information
10. 0 Off 1 On Reserved 0x046F Reserved 0x0470 0 pe ratio N continued Select Voltage Description Address Value Unit Selected Output Voltage 0x0471 0 999 Voltage Select Output Voltage 1 0x0472 0 999 Voltage Select Output Voltage 2 0x0473 0 999 Voltage Select Output Voltage 3 0x0474 0 999 Voltage SRAM Exist Description Address Value Unit SRAM EXIST 0x0475 0 Doesn t Exist 1 Exists Note Currently this field is not supported by UPS TempStatus Description Address Value Unit TempStatus Byte 1 2 0x0476 Low Byte 1 Hi Byte 2 TempStatus Byte 3 4 0x0477 Low Byte 3 Hi Byte 4 TempStatus Byte 5 6 0x0478 Low Byte 5 Hi Byte 6 TempStatus Byte 7 8 0x0479 Low Byte 7 Hi Byte 8 TempStatus Byte 9 10 0x047A Low Byte 9 Hi Byte 10 TempStatus Byte 11 12 0x047B Low Byte 12 Hi Byte 12 TempStatus Byte 13 14 0x047C Low Byte 13 Hi Byte 14 TempStatus Byte 15 16 0x047D Low Byte 15 Hi Byte 16 TempStatus Byte 17 18 0x047E Low Byte 17 Hi Byte18 TempStatus Byte 19 20 0x047F Low Byte 19 Hi Byte 20 Reserved 0x0480 Reserved 0x0481 Temp Byte 1 Lo R Phase Inverter Temperature Temp Byte 8 Hi BO Power Fail Temp Byte 2 Hi BO Temperature Warning gt 75C B1 EPO Happened B1 High Temperature Shutdown gt 85C B2 MB_ON To Bypass B2 Inverter Voltage Too Low B3 Low Battery Warning B3
11. 0 9999 0 1 Amp Input Power 1 0x0434 0 65534 10 Watt Input Frequency 2 0x0435 0 999 0 1 Hz Input Voltage 2 0x0436 0 9999 0 1 Voltage Input Current 2 0x0437 0 9999 0 1 Amp Input Power 2 0x0438 0 65534 10 Watt Input Frequency 3 0x0439 0 999 0 1 Hz Input Voltage 3 0x043A 0 9999 0 1 Voltage Input Current 3 0x043B 0 9999 0 1 Amp Input Power 3 0x043C 0 65534 10 Watt Input Voltage 12 0x043D 0 9999 0 1 Voltage Input Voltage 23 0x043E 0 9999 0 1 Voltage Input Voltage 31 0x043F 0 9999 0 1 Voltage Reserved 0x0440 Reserved 0x0441 Output Status Description Address Value Unit 0 Normal 1 Battery 2 Bypass Reserve 3 Reducing Output Source 0x0442 4 Boosting 5 Manual Bypass 6 Other 7 None Output Frequency 0x0443 0 999 0 1 Hz Output Number Lines 0x0444 0 9 Output Voltage 1 0x0445 0 9999 0 1 Voltage Output Current 1 0x0446 0 9999 0 1 Amp Output Power 1 0x0447 0 65534 10 Watt Output Load 1 0x0448 0 999 Output Voltage 2 0x0449 0 9999 0 1 Voltage Output Current 2 Ox044A 0 9999 0 1 Amp Output Power 2 0x044B 0 65534 10 Watt Output Load 2 0x044C 0 999 KA Output Voltage 3 0x044D 0 9999 0 1 Voltage Output Current 3 0x044E 0 9999 0 1 Amp Output Power 3 0x044F 0 65534 10 Watt Output Load 3 0x0450 0 999 Output Voltage 12 0x0451 0 9999 0 1 Voltage Output Voltage 23 0x0452 0 9999 0 1 Voltage Output Voltage 31 0x0453 0 9999 0 1 Voltage Reserved 0x04
12. 0x0209 Clear SRAM Clear SRAM Cancel Shutdown Restart 0x020A Cancel Shutdown Restart Cancel Shutdown Restart Set Output On Off 0x020B OFF ON Reserved 0x020C Reserved 0x020D Reserved 0x020E Reserved 0x020F Note Your UPS may not support all fields Holding Register Range 0x0300 0x0321 Read Function 0x03 Write Function 0x06 The Read Holding Registers function code is used to read contents of a contiguous block of Holding Registers in a remote device Starting register address and number of registers is specified by the request Protocol Data Unit Addresses start at 0 and registers numbered 1 16 address as 0 15 The Write Single Register function code is used to write a Single Holding Register in a remote device The address of the register to be written is specified by the request Protocol Data Unit Addresses start at 0 and registers numbered 1 address as 0 Description Address Value Unit Shutdown Action 0x0300 0 999 0 Abort Seconds Shutdown Restart 0x0301 0 65535 Minutes 0 Abort Test 1 General Test Test 0x0302 2 BTV Test 3 Test for 10 seconds 4 Test until battery low UPS Identification 0x0303 0 99 Low Transfer Voltage 0x0304 0 999 Voltage High Transfer Voltage 0x0305 0 999 Voltage 0 Normal Voltage Sensitivity 0x0306 1 Reduced 2 Low Last Battery Replace Date Year 0x0307 0 9999 Last Battery Replace Date Month 0x0308 1 12 Last Battery Replace Date Da
13. 54 Reserved 0x0455 0 pe ratio N continued Bypass Status Description Address Value Unit Bypass Frequency 0x0456 0 999 0 1 Hz Bypass Number Lines 0x0457 0 9 Bypass Voltage 1 0x0458 0 9999 0 1 Voltage Bypass Current 1 0x0459 0 9999 0 1 Amp Bypass Power 1 0x045A 0 65534 10 Watt Bypass Voltage 2 0x045B 0 9999 0 1 Voltage Bypass Current 2 0x045C 0 9999 0 1 Amp Bypass Power 2 0x045D 0 65534 10 Watt Bypass Voltage 3 0x045E 0 9999 0 1 Voltage Bypass Current 3 0x045F 0 9999 0 1 Amp Bypass Power 3 0x0460 0 65534 10 Watt Bypass Voltage 12 0x0461 0 9999 0 1 Voltage Bypass Voltage 23 0x0462 0 9999 0 1 Voltage Bypass Voltage 31 0x0463 0 9999 0 1 Voltage Bypass STS Temperature 0x0464 0 999 Degrees Celsius Reserved 0x0465 Reserved 0x0466 Test Status Description Address Value Unit 0 No Test Performed 1 Test Passed 2 Test In Progress Test Result 0x0467 3 General Test Fault 4 Battery Test Fault 5 Deep Battery Test Fault 6 Test Aborted Output Relay Description Address Value Unit 0 Not Available Number of Output Relay 0x0468 F gt 0 Available lt 99 Environment Description Address Value Unit Temperature 0x0469 0 999 Degrees Celsius Humidity 0x046A 0 999 Relay 1 0x046B 0 Off 1 On Relay 2 0x046C 0 Off 1 On Relay 3 0x046D 0 Off 1 On Relay 4 0x046E
14. Be sure to fully configure all your MODBUSCARD s switches to match your configuration before installation Al MODBUS Card ID Configuration Switch E RS 232 Port Configuration Switch RS 422 485 Port Configuration Switch D RS 422 485 Selection Switch E RS 422 485 amp RS 232 Communication Port a Diagnostic LEDs Configuration Configuration of RS 232 Port Use SW2 to configure the RS 232 interface Pin Function 6 Card TxD transfer data to PC Card RxD receive data from PC 8 GND Function Switch Value SW 1 SW 2 ON OFF OFF OFF MODBUS OFF ON ON MODBUS ON SW2 1 SW2 2 OFF OFF 2400 Default Baud Rate ON OFF 4800 OFF ON 9600 ON ON 19200 OFF Disable Parity Check Default SW2 3 gt ON Enable Parity Check Parity Check OFF Even Parity Default SW2 4 ON Odd Parity SW2 5 SW2 6 OFF OFF MODBUS Protocol Default Protocol ON OFF Regular Protocol OFF ON 3 Phase Protocol SW2 7 Reserved SW2 8 Reserved Configu ration continued Configuration of RS 422 485 Port Use SW3 to configure the RS 422 485 interface Pin Function 1 Card D T 2 Card D T 3 Card R 4 Card R Switch Setting Function RS 485 Enable RS 485 SW4 RS 422 Enable RS 422 Function Switch Value SW3 1 SW3 2 OFF OFF 2400 Default Baud Rate ON OFF 4800 OFF ON
15. ID 0x0494 PFC Status 0 1 0x0495 Power Module ID 0x0496 PFC Status 0 1 0x0497 Power Module ID 0x0498 PFC Status 0 1 0x0499 Reserved 0x049A Reserved 0x049B Reserved 0x049C Reserved 0x049D PFC Status BO PFC fuse open shutdown B1 PFC over temperature warning B2 PFC over temperature shutdown B3 DC bus over voltage warning B4 DC bus over voltage shutdown B5 DC bus under voltage warning B6 DC bus under voltage shutdown B7 PFC circuit general fault B8 Fan failure B9 TBD B10 TBD B11 TBD B12 Inner communication failure B13 TBD B14 TBD B15 Not calibrated used to indicate whether the power module has been calibrated 0 pe ratio N continued Power Module Inverter Status Description Address Value Unit Power Module ID Status 0 0x049E Lo ID 1 4 Hi Status 0 Inverter Status 1 2 0x049F Lo Status 1 Hi Status 2 Power Module ID Status 0 0x04A0 Inverter Status 1 2 0x04A1 Power Module ID Status 0 0x04A2 Inverter Status 1 2 0x04A3 Power Module ID Status 0 Ox04A4 Inverter Status 1 2 0x04A5 Reserved 0x04A6 Reserved 0x04A7 Reserved 0x04A8 Reserved Ox04A9 Inverter Status BO Inverter Fuse Open B1 Inverter Over Temperature Warning B2 Inverter Over Temperature Shutdown B3 Fan Failure B4 B5 Inverter Short Circuit B6 Inverter STS Failure B7 Inverter Voltage Abnormal B8 Inverter Circuit General Fault B9 DC Bus Over Voltag
16. Inverter Voltage Too High B4 Battery Low Shutdown B4 Overload Warning B5 Master UPS Output Synch B5 Overload Shutdown B6 Inverter DC Bus Abnormal Shutdown B6 Inverter Fuse Fail Shutdown B7 Short Circuit Shutdown B7 Inverter PCB Communication Abnormal Temp Byte 9 Lo Heatsink Temperature Temp Byte 3 Lo S Phase Inverter Temperature Temp Byte 4 Hi BO Temperature Warning gt 75C Bl B2 B3 B4 B5 B6 B7 High Temperature Shutdown gt 85C Inverter Voltage Too Low Inverter Voltage Too High Overload Warning Overload Shutdown Inverter Fail Shutdown Parallel Communication Abnormal Temp Byte 5 Lo T Phase Inverter Temperature Temp Byte 6 Hi BO Temperature Warning gt 75C Bl B2 B3 B4 B5 B6 B7 High Temperature Shutdown gt 85C Inverter Voltage Too Low Inverter Voltage Too High Overload Warning Overload Shutdown Inverter Freq Abnormal Shutdown Parallel Communication Fail Temp Byte 7 Lo B3 B0 The Summary of UPS Run at Inverter Test Mode B7 B4 The Summary of UPS at Inverter Mode Temp Byte 10 Hi B0 Bypass Voltage Over B1 B2 B3 B4 B5 B6 B7 Temp Byte 11 Lo Bypass Voltage Under Bypass Freq Abnormal Bypass Phase Abnormal Rectifier Voltage Over Rectifier Voltage Under Rectifier Freq Abnormal Rectifier Phase Abnormal Ambient Temperature Temp Byte 12 Hi BO Bypass Voltage Over Bl B2 B3 B4 B5 B6 B7 Bypass Volt
17. UPS In Sleep Mode Reserved 0x0127 Alarm Bypass Volt Freq Bad 0x0128 OK Bypass Volt Freq Bad Alarm Bypass Phase Sequence Bad 0x0129 OK Bypass Phase Sequence Bad Alarm Bypass STS Overload 0x012A OK Bypass STS Overload Alarm Bypass STS Over 0x012B OK Bypass STS Over Alarm Bypass STS Fault 0x012C OK Bypass STS Fault Reserved 0x012D Reserved 0x012E Reserved 0x012F Note Your UPS may not support all fields 0 pe ratio N continued Coils Range 0x0200 0x020F Read Function 0x01 Write Function 0x05 The Read Coils function reads 1 2000 contiguous status of coils in a remote device The starting address and number of coils is specified by the request Protocol Data Unit Addresses start at 0 and Coils numbered 1 16 would address as 0 15 The Write Coils function writes a single output to ON OFF in a remote device A specified constant in the data field requests the ON OFF state Addresses start at 0 and Coils numbered would address as 0 Description Address Value 0 Value 1 UPS Buzzer 0x0200 Silence Alarm Shutdown Type 0x0201 UPS Output UPS System Economy Mode Setting 0x0202 Disable Enable ATX PC Reboot Function 0x0203 Disable Enable AC Fail amp Restore Auto Reboot 0x0204 Disable Enable ATX PC Resume Function 0x0205 Disable Enable Enable Disable Inverter 0x0206 Disable Enable EPO Setting 0x0207 Disable Enable Enable Disable Inverter 0x0208 Disable Enable Clear SRAM
18. age Under SSW at Bypass Side SSW at Inverter Side Rectifier Voltage Over Rectifier Voltage Under Rectifier Input Over Current Rectifier Input Current Unbalanced 0 pe ratio N continued TempStatus continued Temp Byte 13 Lo Battery Temperature Temp Byte 14 Hi BO Bypass Voltage Over Bl B2 B3 B4 BS Bo B7 Temp Byte 15 Lo BO Bypass Voltage Under Low Battery Shutdown Low Battery Warning Rectifier Voltage Over Rectifier Voltage Under Rectifier Fail DC Bus Over Voltage TR1 Over Temperature O P TR Over Heat Shutdown Bl B2 B3 B4 BS B6 B7 Parallel Master ID TR2 Input Choke Over Heat I P TR Over Heat Shutdown Rectifier Over Temperature Warning gt 75C Rectifier Over Temperature Shutdown gt 85C Static Switch Over Temperature Warning gt 75C Static Switch Over Temperature Shutdown gt 85C Static Switch Overload Static Switch Fail Temp Byte 16 Hi BO Converter Board Power Abnormal Bl B2 B3 B4 EPO Happened Manual Bypass On Converter Board Communication Error Battery Cabinet Over Temperature Warning gt 75C B5 Battery Ground Fault B6 Battery Test in Progress B7 Battery Test Fail Temp Byte 17 Reserved Temp Byte 18 Reserved Temp Byte 19 Reserved Temp Byte 20 Hi B5 Ambiance Over Temperature B7 Auxiliary Power Fail Note Currently TempStatus is not supported by UPS
19. e Shutdown B10 Inverter Overload B11 B12 Inner Communication Loss includes the communication to system or other modules B13 EPO Shutdown B14 Inverter Parallel Communication Loss B15 Inverter Parallel Failure which may due to any of ID or rating setting conflict etc B16 TBD B17 TBD B18 TBD B19 TBD B20 TBD B21 TBD B22 TBD B23 Not calibrated used to indicate whether the power module has been calibrated Power Module Charger Status Description Address Value Unit Power Module ID Charger Status Ox04AA Lo ID 1 4 Hi Status Power Module ID Charger Status 0x04AB Power Module ID Charger Status 0x04AC Power Module ID Charger Status 0x04AD Reserved 0x04AE Reserved Ox04AF Charger Status BO Charger Circuit General Fault B1 B7 Reserved 0 pe ratio N continued Power Module Temperature Status Description Address Value Unit Power Module ID 0x04B0 1 4 Temperature PFC 0x04B1 0 9999 0 1 Voltage Temperature TBD 0x04B2 0 9999 0 1 Voltage Temperature INV 0x04B3 0 9999 0 1 Voltage Temperature INV R 0x04B4 0 9999 0 1 Voltage Temperature INV S 0x04B5 0 9999 0 1 Voltage Temperature INV T 0x04B6 0 9999 0 1 Voltage Power Module ID 0x04B7 1 4 Temperature PFC 0x04B8 0 9999 0 1 Voltage Temperature TBD 0x04B9 0 9999 0 1 Voltage Temperature
20. r Bound 0x0417 0 999 Voltage Bypass Voltage Max Tolerance Bypass Low Tx Voltage Lower Bound 0x0418 0 999 Voltage Bypass Voltage Set Tolerance Bypass High Tx Voltage Upper Bound 0x0419 0 999 Voltage Bypass High Tx Voltage Lower Bound 0x041A 0 999 Voltage Reserved 0x041B Reserved 0x041C Reserved 0x041D Battery Status Description Address Value Unit 0 Good Battery Condition Ox041E 1 Weak 2 Replace 0 OK Battery Status 0x041F 1 Low 2 Depleted 0 Floating 1 Charging Battery Charge 0x0420 2 Resting 3 Discharging Seconds on Battery 0x0421 0 65534 Seconds Estimated Minutes Remaining 0x0422 0 999 Estimated Charge Remaining 0x0423 0 999 Battery Voltage 0x0424 0 9999 0 1 Voltage Battery Current 0x0425 0 9999 0 1 Amp Temperature 0x0426 0 999 Degrees Celsius Battery Level 0x0427 0 999 External Battery Pack 0x0428 0 10 Negative Battery Voltage 0x0429 0 9999 0 1 Voltage Negative Battery Current 0x042A 0 9999 0 1 Amp Negative Battery Temp 0x042B 0 999 Degrees Celsius Negative Battery Level 0x042C 0 999 Reserved 0x042D Reserved 0x042E Reserved 0x042F 0 pe ratio N continued Input Status Description Address Value Unit Input Number Lines 0x0430 0 9 Input Frequency 1 0x0431 0 999 0 1 Hz Input Voltage 1 0x0432 0 9999 0 1 Voltage Input Current 1 0x0433
21. registers numbered 1 16 address as 0 15 Description Address Value Unit 0 T Series 0x0400 ra 2 NT 3 NH Rating Input Voltage 0x0401 0 999 Voltage Rating Input Frequency 0x0402 0 999 0 1 Hz Rating Output Voltage 0x0403 0 999 Voltage Rating Output Frequency 0x0404 0 999 0 1 Hz Rating VA 0x0405 0 65534 10 VA Rating Output Power 0x0406 0 65534 10 Watt Low Battery Time 0x0407 0 99 Minutes Low Tx Voltage Point 0x0408 0 999 Voltage High Tx Voltage Point 0x0409 0 999 Voltage Low Tx Voltage Upper Bound 0x040A 0 999 Voltage Low Tx Voltage Lower Bound 0x040B 0 999 Voltage High Tx Voltage Upper Bound 0x040C 0 999 Voltage High Tx Voltage Lower Bound 0x040D 0 999 Voltage 0 pe ratio N continued Input Register Range 0x0400 0x051C Read Function 0x04 Rating Value continued Description Address Value Unit 0 On Line 1 Off Line 2 Line Interactive UPS Type 0x040E 3 3 Phase 4 Split Phase 5 Others Rating Battery Voltage 0x040F 0 999 Voltage Low Tx Frequency Point 0x0410 0 999 0 1 Hz High Tx Frequency Point 0x0411 0 999 0 1 Hz Bypass Rating Frequency 0x0412 0 999 0 1 Hz Bypass Freq Max Tolerance 0x0413 5 50 0 1 Hz Bypass Freq Set Tolerance 0x0414 5 50 0 1 Hz Bypass Low Tx Voltage Point Bypass 0x0415 0 999 Voltage Rating Voltage Bypass High Tx Voltage Point 0x0416 0 999 Voltage Bypass Low Tx Voltage Uppe
22. rm Charger Failure 0x0107 OK Charger Failure Alarm System Off 0x0108 System On System Off Alarm Fan Failure 0x0109 OK Fan Failure Alarm Fuse Failure 0x010A OK Fuse Failure Alarm General Fault 0x010B OK General Fault Alarm Awaiting Power 0x010C OK Awaiting Power Alarm Shutdown Pending 0x010D OK Shutdown Pending Alarm Shutdown Imminent 0x010E OK Shutdown Imminent Buzzer Status 0x010F Silence Alarm Economy Mode 0x0110 No Yes Alarm Inverter Bad 0x0111 OK Inverter Bad Emergency Power Off 0x0112 Off On Buzzer State 0x0113 Disable Enable Battery Ground Fault 0x0114 OK Battery Ground Fault Reserved 0x0115 Reserved 0x0116 Reserved 0x0117 Alarm Rectifier Main Fail 0x0118 OK Rectifier Main Fail Alarm Rectifier Hi DC Stop 0x0119 OK Rectifier Hi DC Stop Alarm Over Temp or Fuse Fail OxO11A OK Over Temp or Fuse Fail Alarm Battery Low 0x011B OK Battery Low Alarm Battery Low Stop Ox011C OK Battery Low Stop Alarm Battery Ground Fault 0x011D OK Battery Ground Fault Inverter On OxO1L1E Inverter Off Inverter ON Alarm Inverter Overload 0x01 1F OK Inverter Overload Alarm Inverter Abnormal 0x0120 OK Inverter Abnormal Alarm Load on Reserve 0x0121 Load Not On Reserve Load on Reserve Alarm Reserve Mains Fail 0x0122 OK Reserve Mains Fail Alarm Reserve Freq Abnormal 0x0123 OK Reserve Freq Abnormal Alarm Test In Progress 0x0124 No Test In Progress Test In Progress Alarm Test Error 0x0125 No Test Error Test Error UPS In Sleep Mode 0x0126 UPS Not In Sleep Mode
23. y 0x0309 1 31 Next Battery Replace Date Year 0x030A 0 9999 Next Battery Replace Date Month 0x030B 1 12 Next Battery Replace Date Day 0x030C 1 31 0 pe ratio N continued Holding Register Range 0x0300 0x0321 Read Function 0x03 Write Function 0x06 continued Description Address Value Unit 1 Disable 2 Daily UPS Periodic Auto Test 0x030D 3 Weekly 4 Bi Weekly 5 Monthly Buzzer Test 0x030E 1 99 Seconds UPS Boot Delay 0x030F 0 999 Seconds Bypass Freq Tolerance 0x0310 5 50 0 1 Hz Select Output Voltage 0x0311 0 999 Voltage Test Time 0x0312 1 60 Minutes Test Voltage 0x0313 0 999 Voltage Reserved 0x0314 Reserved 0x0315 External Battery Pack 0x0316 0 10 Dry Contact W1 0x0317 Dry Contact W2 0x0318 Dry Contact W3 0x0319 Dry Contact W4 0x031A Dry Contact W5 0x031B Dry Contact W6 0x031C Bypass Low Transfer Voltage 0x031D 0 999 Voltage Bypass High Transfer Voltage 0x031E 0 999 Voltage Bypass Voltage Tolerance 0x031F 0 999 Voltage Dry Contact Input Status 1 0x0320 Dry Contact Input Status 2 0x0321 Note Your UPS may not support all fields Input Register Range 0x0400 0x051C Read Function 0x04 Rating Value The Read Input Registers function code is used to read 1 125 contiguous input registers in a remote device The starting register address and number of registers is specified by the request Protocol Data Unit Addresses start at 0 and