1. SHO STEP ns1628a Knockout Quantity Conduit Size EMT Knockout Size 2 lin 1 375 in O 4 1 25 in 1 734 in 5 2 2in 2 469 in 3 0 5 in 0 875 in O 3 0 75 in 1 109 in 4 0 625 in 20 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Vertical 0 U Accessory Channels The vertical O U accessory channels provide toolless mounting capabilities for APC Rack Power Distribution Units Rack PDU and APC cable management accessories see page 22 The vertical 0 U accessory channels also provide tie off locations for cables The vertical 0 U accessory channels can be located in the enclosure anywhere along the side braces The standard position for the vertical 0 U accessory channels is in the rear of the enclosure but they can be positioned anywhere along the side braces like the vertical mounting rails see Adjusting the Vertical Mounting Rails on page 16 Accessory SKU Description NetShelter SX AR7511 D
2. NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual 15 Equipment Installation Installing equipment in the NetShelter AV Enclosure may require adjusting the vertical mounting rails to the correct depth for your equipment before installing equipment Adjusting the Vertical Mounting Rails Audio visual equipment is secured to the vertical mounting rails in op the NetShelter AV Enclosure The vertical mounting rails are de MI adjustable to accommodate the depth of your AV equipment The o vertical mounting rails come factory installed for use with AV equipment that has a depth of 508 mm 20 in The vertical mounting rails can be adjusted to be as close together as 191 mm 7 5 in or as far apart as 680 mm 26 8 in when the vertical 0 U accessory channels have been removed rsle2la Accessory SKU Description NetShelter SX AR7503 Allows you to install recessed rail kit another set of rails in either the top or bottom of the enclosure This allows equipment with two different depths to be installed in the enclosure 16 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Perform the following steps to adjust a vertical mounting rail Warning To avoid personal injury or damage to the enclosure
3. 19 inch AR8602 1 U Routes cables horizontally horizontal on the front or back of the cable AR8600 2 U 19 inch EIA enclosure organizers AR8601 2 U double sided AR8603 2 U high density AR8425A dU AR8426A 2U 19 inch 2 U AR8428 Routes cables horizontally horizontal or front to rear cable organizer pass through 19 inch 1 U AR8429 Assists with containing air cable pass in the enclosure and through with providing an aesthetic brush strip solution for cable routing Zero U AR7711 Zero U multi purpose accessory accessory mounting mounting bracket for 1 U and 2 U bracket equipment including Qty 2 Rack PDUs Vertical cable AR7505 Routes cables or attaches organizer center rear mount rack PDUs vertically in the center of the back of the enclosure under the brush strips Installs toollessly in a 42 U or 48 U enclosure 24 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Accessory SKU Description Vertical fiber AR8443A The vertical fiber organizer organizer provides a method to manage fiber cabling within an enclosure and mounts toollessly into the vertical 0 U accessory channel 42 U 48 U AR7600 Fills the gap between the Baying Trim enclosures providing finished look ns1755a NetShelter AV 42 U Enclosure Unpacking Installation and Customization
4. Manual 25 Specifications 26 Specifications Height Width Depth Net weight Total open area front door Total open area rear door Open area per U front door Open area per U rear door Perforation pattern percentage Percent of perforated area front Percent of perforated area rear Clearance for wiring between front door and vertical rail Weight rating static load Weight rating rolling Weight rating shipping Y Lower the leveling feet if the static weight is over 1020 58 kg 2 250 lb NetShelter AV 42 U Enclosure AR3810 1991 mm 78 40 in 600 mm 23 62 in 825 mm 32 48 in 119 3 kg 263 Ib 593 018 mm 919 18 in 669 276 mm 1 037 38 in 14 129 mm 21 90 in 15 935 mm 24 70 in 69 66 74 60 96 mm 2 40 in 1361 kg 3 000 Ib 1021 kg 2 250 1b 567 kg 1 250 lb NetShelter AV 42 U Dos Frame Enclosure AR3812 1991 mm 78 40 in 600 mm 23 62 in 753 mm 29 60 in 71 7 kg 158 Ib n a n a n a n a n a n a n a n a 1361 kg 3 000 Ib 1021 kg 2 250 lb 567 kg 1 250 lb NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual APC Limited Factory Warranty The limited warranty provided by American Power Conversion APC in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business Terms of Warranty American Power C
5. U Enclosure Unpacking Installation and Customization Manual 11 12 8 Reposition and reinstall hinge 9 Reinstall the door 10 Reinstall the door handle assembly with the washer and latch oriented as shown The washer is rotated 90 degrees from its original orientation 1 Reinstall the grounding wire with star washer The star washer must be installed under the grounding wire see step 2 12 Reinstall the APC nameplate on the front door ns1615a NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Securing the Enclosure For additional stabilization secure the enclosure to the floor Use fastener locations on the outside or inside of the enclosure and choose from the accessories shown below Accessory SKU Description Pallet bolt provided Attaches to rack and floor down brackets with the internally or externally to enclosure not provide additional stability available as a without blocking cable purchased access part NetShelter SX AR7700 Attaches externally to the stabilizer plate rack and floor to provide additional stability u Bolt down kit AR7701 Attaches to rack and floor internally or ext
6. Warning To avoid damage or injury do not use the roof as a walkway NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Unpacking the Enclosure Disclaimer American Power Conversion is not responsible for damage sustained during reshipment of this product Receiving inspection Inspect the package and contents for shipping damage and make sure that all parts were sent Report any damage immediately to the shipping agent Report missing contents damage or other problems immediately to APC or your APC reseller Please Recycle The shipping materials are recyclable Save them for later use or dispose of them fs appropriately Procedure 1 Move the shipping pallet to a firm level surface in an open area Inspect for visible signs of shipping damage If you detect shipping damage contact APC Customer Support using the contact information on the back cover of this manual 2 See the label on the packaging to determine where to cut the wrapping Using sturdy shears or a utility knife carefully remove the plastic stretch wrap surrounding the enclosure 3 Remove the four cardboard corner protectors 4 Remove and retain the two pallet mounting brackets with mounting hardware that anchor the enclosure to the shipping pallet Use a 13 mm wrench not provided Note Save the pallet mounting brackets if you plan to bolt the enclosure to the floor 5 With one person on each side of the enclosure carefully
7. roll it toward the rear of the pallet until the rear casters clear the back edge of the pallet Continue to slide the enclosure until the rear casters touch the floor 6 While one person carefully tips the enclosure slightly away from the pallet have the other person pull the pallet away from the enclosure Set the enclosure gently on its casters Warning Use caution when moving an empty enclosure on its casters the enclosure may be unstable when pushed or pulled from the side Push the enclosure from the front or back when moving it on its casters For extra stability load 158 kg 350 Ibs of equipment into the bottom of the enclosure before moving it on its casters 2 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Component Identification Enclosure 000 O 000 Enclosure frame Side brace Adjustable vertical 0 U accessory channel Pallet bolt down bracket Adjustable leveling feet Casters Hardware bag see page 4 Adjustable vertical mounting rails 09808 ns1593a Roof with conduit knockouts and cable access AR7213 Removable rear split doors AR7100 Key for doors and side panels Removable side panels with locks AR7306 T Removable and reversible front door AR7000A f Options fo
8. the APC logo and NetShelter are owned by Schneider Electric Industries S A S American Power Conversion Corporation or their affiliated companies All other trademarks are property of their respective owners 990 3702A 6 2010
9. Arc by Schneider Electric ev ie Unpacking Installation io and Customization A Manual NetShelter AV U Open Frame Enclosures 42 U and 42 AR3810 AR3812 Contents INTFOdUCIIN een en ce Safety Warnings and Cautions 222222000000000000nnn2n Unpacking the Enclosure u2uan00000nnnnnnnnnnnnnnn nun Component Identification 2 22 2222002222200n220n nn Removing and Reinstalling Side Panels Roof and DOM Sia aaa Side Panels nac ne 5 ROOP 2 52 5 DOORS ann ADE A a E Ee 6 Enclosure Installation onnmocccnnacannananananannnannnnnnnnnnnnano Moving the Encl sure u uuuun une na 7 Leveling the Enclosure 00e eee eee eee nn nenn nn 8 JOINING Enclosures i nak Ste nn 9 Reversing the Front Door 2 2 2 cece eee 10 Securing the Enclosure i200 ccc wis ana 13 Grounding the Enclosure 0 20e eee eee eee oo 14 Completing the Installation ooo 15 Equipment Installation cccconnnncicnnnnacoccnnnnnonennannnnnnas 16 Adjusting the Vertical Mounting RailS 16 Installing Equipment 0ooococcccooo 19 Cable Routing and Cable Management 20 HOO rer ee 20 Vertical 0 U Accessory Channels 2000 essen eens 21 NetShelter AV 42
10. RE LOSS OF DATA COSTS OF SUBSTITUANTS CLAIMS BY THIRD PARTIES OR OTHERWISE NO SALESMAN EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY WARRANTY TERMS MAY BE MODIFIED IF AT ALL ONLY IN WRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT Warranty Claims Customers with warranty claims issues may access the APC worldwide customer support network by visiting http www apc com support Select your country from the country selection pull down menu Open the Support tab at the top of the web page to obtain contact information for customer support in your region APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways e Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information www apc com support Global support searching APC Knowledge Base and using e support e Contact the APC Customer Support Center by telephone or e mail Local country specific centers go to www apc com support contact for contact information For information on how to obtain local customer support contact the APC representative or other distributors from whom you purchased your APC product 2010 APC by Schneider Electric APC
11. U Enclosure Unpacking Installation and Customization Manual AECESSofles nn een SPpeciflcallonsamn nee APC Limited Factory Warranty ccccccssssssseeeeseees ii NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Introduction The American Power Conversion APC NetShelter AV Enclosure is a high quality enclosure for storage of industry standard EIA 310 19 inch rack mount hardware which includes servers voice data networking security audio visual and APC power protection equipment The NetShelter AV 42 U Enclosure AR3810 is a complete enclosure with all panels front door rear doors side panels and roof e The NetShelter AV 42 U Open Frame Enclosure AR3812 is a frame only enclosure for which you can purchase side panels roof and doors as required for your unique needs See Component Identification on page 3 Various accessories are mentioned in this manual For complete details on any accessory see the APC Web site www apc com To quickly find a part on the APC Web site enter the part number in the Search field For additional information about this product see the product page on the APC Web site www apc com Safety Warnings and Cautions Observe all Warnings and Cautions in this manual plus the following Tip Hazard This equipment is easily tipped Use extreme caution when unpacking or moving Heavy Use at least two people to unpack the enclosure MN
12. epending on the position 42 U Narrow of the vertical mounting Rey Vertical 0 U Cable rails and the vertical 0 U E Organizer accessory channels E additional vertical 0 U accessory channels may be N Q installed The narrow D Q vertical cable organizer N D complements the standard N N vertical cable organizer by ys offering additional cable management options The Lal ge E narrow channel can be N used in the front of the N enclosure to mount fiber iS cable spools and vertical x cable managers or can be used in the middle of the y enclosure for cable tie off E In addition keyholes are N provided to mount one ie vertical Rack PDU per is rs1754a organizer NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Accessories Accessory SKU Description Copper busbar AR8395 20 U copper busbar for NetShelter AV enclosures Tooless installation in vertical 0 U accessory channel or vertical mounting rail Shelf AR8125 Adjustable reversible shelf 115 VAC roof ACF505 Includes four fans to pull fan tray heated air out of the enclosure Toolless installation NetShelter AV ACF600 Includes four fans for 2 U rack fan cooling AV equipment UL Be TIR panel Accessories include a temperature controller JE o ACF601 vent panel A AS ACAC40001 and vent E panel with temperature Q DO d
13. ernally to provide additional stability without blocking cable access With the appropriate mounting hardware meets UBC Zone 4 seismic requirements ers To secure the enclosure to the floor use the fastener locations on the outside of the enclosure as shown or use the fastener locations on the inside of the enclosure NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Grounding the Enclosure Each enclosure should be grounded directly to the building ground using one of the designated grounding locations two M6 threaded inserts at the top or bottom of the enclosure e Use a Common Bonding Network Jumper kit for example Listed KDER Panduit RGCBNJ660PY or equivalent e Use paint piercing washers between ground terminal and enclosure frame or remove paint on frame under ground terminals per NEC NFPA 70 Article 250 12 e Torque screws to 6 9 N m 60 in Ib e Do not ground one enclosure to another enclosure in a cascading style ns1617a 14 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Completing the Installation Install plugs and covers included in the hardware bag as needed rs1616a
14. ing an empty enclosure on its casters Push the enclosure from the front or back only the enclosure may be unstable if pushed or pulled from the side For extra stability load 158 kg 350 lbs of equipment into the bottom of the enclosure before moving it on its casters Eye bolts The enclosure can be lifted using eye bolts with up to 567 kg 1 250 lbs of equipment installed Use M10 eye bolts with A 3 a shoulder rated for 181 kg 400 lbs ns1596a NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Leveling the Enclosure Required tools Lae Phillips screwdriver Level 13 mm open ended wrench Warning The leveling feet at the corners provide a stable base if the floor is uneven but NM they cannot compensate for a badly sloped surface To adjust the leveling feet after equipment has been installed use a 13 mm open ended wrench not provided 8 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Joining Enclosures Enclosures can be joined with or without side panels installed to provide for alignment and some stability AN Caution Joining enclosures provides limited stability to the enclosures 1 Make sure the leveling feet are down 2 Remove the front and rear doors 3 Choose between 24 in centers or 600 mm centers see the detail view below If enclosures are joined on 24 in centers APC offers baying
15. ions or in any event if the APC serial number has been altered defaced or removed or any other cause beyond the range of the intended use THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE OF PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE APC EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITY AND PURCHASER S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES APC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES IN NO EVENT SHALL APC ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY OF SUCH DAMAGES SPECIFICALLY APC IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWA
16. isplay ACAC40000 22 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Accessory SKU Description Top mount AR7215 Allows option to route conduit access cable into side of unit adapter Includes knock out panels for conduit Toolless installation Toolless hook AR8621 Includes and loop cable ten 457 mm 18 in hook manager and loop black cable Qty 10 straps that install in the HR C N square holes in the vertical zu u 0 U accessory channel or S the vertical mounting rail Cable AR7710 Contains cables along the containment vertical 0 U accessory me brackets channel Installs without Qty 6 tools Y i 0 Vertical cable AR8442 Installs in a vertical 0 U organizer accessory channels to facilitate vertical cable management and eliminate cable stress Takes up zero U of space within the enclosure Consists of two pieces of equal size that when stacked span the height of a 42 U enclosure Can be used in any APC enclosure Toolless installation Cable AR8113A Fastens cables to posts management mounting rails or braces rings Qty 5 cS large and 5 small NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual 23 Accessory SKU Description
17. ng top heavy e Do not extend equipment on sliding rails until you have installed three or more pieces of similar sized equipment or until you have installed the stabilizer plate or bolt down brackets e Do not extend more than one piece of equipment on sliding rails at a time Before getting started make sure you have adjusted the vertical mounting rails as needed To install rack mount equipment in the NetShelter AV Enclosure 1 Review the equipment manufacturer s installation instructions 2 Locate the top and bottom U space on the vertical mounting rails Every third hole on the mounting rails is numbered to indicate the middle of a U space A U space consists of one of these numbered holes and one hole directly above and below it as shown 1O 1U 6 50 ns1595a 3 Install the equipment using the 10 32 screws provided See the manufacturer s instructions provided with the equipment for additional details NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Cable Routing and Cable Management Roof Four removable roof top panels provide knockouts of varying dimensions for conduit For larger cable volumes remove the panels entirely Brush strips cover cutouts in the front and rear of the roof panel which also provide openings for cable routing
18. onversion warrants its products to be free from defects in materials and workmanship for a period of five years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its sole discretion any such defective products This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way Repair or replacement of a defective product or part thereof does not extend the original warranty period Any parts furnished under this warranty may be new or factory remanufactured Non transferable Warranty This warranty applies only to the original purchaser who must have properly registered the product Product may be registered at http www warranty apc com Exclusions APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user s or any third person s misuse negligence improper installation or testing Further APC shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection inappropriate on site operation conditions corrosive atmosphere repair installation start up by non APC designated personnel a change in location or operating use exposure to the elements Acts of God fire theft or installation contrary to APC recommendations or specificat
19. perform this procedure AN without any equipment installed on the vertical mounting rails 1 Unlock the vertical mounting rail Use the TORX wrench provided in the hardware bag to loosen the screw but do not remove NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual 17 18 2 Move the vertical mounting rail to the desired location 3 Check alignment Note symbols circle triangle and square visible through the set of three holes at each location and make sure the symbols match If not realign the vertical mounting rail Vertical mounting rails adjust in 6 mm 1 4 in increments Make sure the vertical mounting rails on both sides of the enclosure are adjusted to the same depth Verify that the same symbols are visible 4 Lock the top middle and bottom of the vertical mounting rail of NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual a amp olti i oy he y rs1624a Installing Equipment A Warning To prevent the enclosure from tipping over after equipment installation e Make sure you have secured the enclosure before installing equipment e Load the heaviest equipment first toward the bottom of the enclosure to prevent the enclosure from becomi
20. r the NetShelter AV 42 U Open Frame Enclosure AR3812 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Hardware bag contents ge we TORX T30 2 Phillips 10 32 MS x 12 7 mmhole 5 mmhole Frame handle wrench 1 screws 60 screws 4 plugs 4 plugs 5 cutout cover 2 4 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Removing and Reinstalling Side Panels Roof and Doors Side Panels Roof NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Doors N Note Doors self align on hinge pins when properly reinstalled 1 With the door at a 90 degree angle to the front of the enclosure position the door over the hinge pins ns1750a ns1751a 3 Connect the ground wire ns1752a 6 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Enclosure Installation Moving the Enclosure Caution To avoid damaging the enclosure and causing a tip hazard make sure the leveling MN feet are up before moving the enclosure Casters The enclosure can be moved on its casters with up to 1021 kg 2 250 lbs of equipment installed Tip Hazard Use caution when mov
21. trim AR7600 to cover the gap between the enclosures The trim can be installed after the units are joined together 4 Align the enclosures and join them using one M5 x 12 flat head screw provided in the hardware bag per bracket two brackets for the front and two brackets for the rear 5 Reinstall the doors See Moving the Enclosure on page 7 600 mm 24 in en k en ns1594a NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual Reversing the Front Door If desired you can reverse the front door so the door opens from the opposite side of the enclosure 1 Remove the APC nameplate from the front door 2 Remove the grounding wire using the TORX wrench provided 3 Remove the door handle assembly ns1613a 10 NetShelter AV 42 U Enclosure Unpacking Installation and Customization Manual 4 Remove the door 5 Remove the hinges from the frame 6 Reinstall the hinges on the opposite side of the enclosure 7 Remove screws securing the hinges in the door frame NetShelter AV 42