        Phoenix TRIO-PS/1AC/24DC/2.5
         Contents
1.  24DC 5    Output characteristic curve    The device functions following the U I characteristic curve   Under load  the working point follows this curve  The output  current is limited in the event of a short circuit or overload   Thereby  the device does not switch off  but rather supplies  a continuous output current    The secondary voltage is reduced until the short circuit or  overload on the secondary side has been remedied  The U I  characteristic curve ensures that both heavily capacitive  loads and loads with DC DC converters in the primary circuit  can be supplied  Downstream fuses are triggered  Selectivity  in the design of your system is guaranteed at all times     Uy   24 V  IN 5A  Py   120 W    Thermal behavior    With an ambient temperature of up to  55  C  the device sup   plies the continuous output current of Iy  In the case of ambi   ent temperatures above  55  C  the output current must be  reduced by 2 5  per Kelvin increase in temperature  The de   vice does not switch off at ambient temperatures of  70  C or  thermal overload  The output capacity is reduced as far as  necessary to provide device protection  After it has cooled  down  the output capacity is increased again     PHOENIX CONTACT 12    TRIO PS 1AC 24DC 5    Parallel operation    Devices of the same type can be connected in parallel to en   able both redundancy and an increase in efficiency  No other  alignment is necessary when in the state of delivery    If the output voltage is adjusted  
2.  following minimum  distance to other modules  5 cm in a vertical di   rection and 0 cm in a horizontal direction     The power supply unit can be snapped onto all  DIN rails in acc  with EN 60715  They must be    N 2    mounted horizontally  connecting terminal  blocks top and bottom               TRIO POWER                                        Mounting position  Installation depth 115 mm    DIN rail     102777_02_en PHOENIX CONTACT 8                                                                                                                            Connection to various network forms    TN S TN C       The connection for 100 V AC     240 V AC is made using the  L  N and PE screw connections    The device can be connected to 1 phase AC networks or to  two of the phase conductors of 3 phase networks  TN  TT or  IT networks in acc  with VDE 0100 300 IEC 60364 3  with  nominal voltages of 100 V AC     240 V AC    In the case of input voltages  gt  300 V AC  the device switches  off for its own safety  After the overvoltage has ceased  the  device starts automatically within a few seconds     For operation on two of the phase conductors of a three   phase system  an isolating facility for all poles must be pro   vided     102777_02_en    TRIO PS 1AC 24DC 5    Assembly    Position the module with the DIN rail guide on the upper edge  of the DIN rail  and snap it in with a downward motion     Removing    Pull the snap lever open with the aid of a screwdriver and  slide the
3.  module out at the lower edge of the DIN rail     In order to comply with the UL certification  use  copper cables that are designed for operating  temperatures of  gt  75  C    In order to comply with EN 60950 UL 60950   flexible cables require ferrules  To safely con   nect a device  the ferrules should have a  length of at least 10 mm  To achieve a reliable  and shockproof connection  strip the connect   ing ends according to section  Structure         PHOENIX CONTACT 9    TRIO PS 1AC 24DC 5    Input  Protection of the primary side    The device must be installed in acc  with the regulations as  in EN 60950  It must be possible to disconnect the device  using a Suitable isolating facility outside the power supply   The primary side line protection  for example  is suitable  For  device protection  there is an internal fuse  Additional device  protection is not necessary     Recommended backup fuse for mains protection    Power circuit breaker 6 A  10 A or 16 A  characteristic B  or  identical function      8      SS  S    If an internal fuse is triggered  there is most  probably a malfunction in the device  In this    case  the device must be inspected in the  factory           102777_02_en PHOENIX CONTACT 10    TRIO PS 1AC 24DC 5    Make sure that all output lines are dimen   sioned according to the maximum output cur   rent or are separately protected  The cables on  the secondary side must have sufficiently large  cross sections in order to keep the voltage  drops on th
4. A  characteristic B      lt  3 5 mA    24 V DC  1    22 5V DC    29 5 V DC   5 A  0  C     55  C    Above  55  C  2 5  per Kelvin  Approx  10 A  for short circuit   Unlimited     lt  1   change in load  static 10      90     lt  2    change in load  dynamic 10      90     lt  0 1    change in input voltage  10      18 W   1 1 W    gt  89      lt  2 ms  Ugyt  10      90       lt  20 mVpp    lt  30 mVpp   Yes  for redundancy and increased capacity  No   Yes   lt  35 V DC   35 V DC     DC OK  LED green   Uour  gt  21 5 V  LED lights up    PHOENIX CONTACT 3    102777_02_en    General data    Insulation voltage input output  Insulation voltage input   PE    Insulation voltage output   PE   Degree of protection   Class of protection   MTBF   Housing version   Side element version   Dimensions W   H  D  state of delivery   Weight    Ambient conditions   Ambient temperature  operation    Ambient temperature  storage transport   Max  permissible relative humidity  operation     Vibration  operation     Shock  Pollution degree in acc  with EN 50178    Climatic class    Standards    Electrical Equipment for Machinery  Safety transformers for power supply units    Electrical safety  of information technology equipment     Electronic equipment for use in electrical power installations  SELV    Safe isolation    Protection against electric shock    Protection against electric shock  basic requirements for safe isolation in  electrical equipment    Limitation of mains harmonic currents    A
5. TRIO PS 1AC 24DC 5    Primary switched power supply  1 phase   output current  5A       INTERFACE   Data Sheet   102 777 02 en    PHOENIX CONTACT   06 2007   Description   TRIO POWER is the rail mountable 24 V power supply unit     Reliable power supply unit even at high ambient temper   with basic functions  With an output voltage of 24 V DC and atures   1 phase and 3 phase versions with 60 W or 960 W  itis par      No load and short circuiting resistance    ticularly suited for use in series production in mechanical en  _  gineering  The wide range input and international certifica   tion package allows worldwide implementation    The high MTBF of 500 000 h stands for high supply reliability   The devices can be connected in parallel to increase the ca   pacity and redundancy    The clear LED signaling and the device connection with dou   ble terminal block for plus and minus for fast potential distri   bution are further advantages of this device series  A third  terminal block for minus simplifies the grounding on the sec   ondary side  All power supply units are idle proof and short  circuit proof and provide a regulated and settable output volt   age of 22 5 V DC to 29 5 V DC with output currents of 2 5 A   5 A  10 A  20 Aor 40 A     High dielectric strength        Can be used worldwide in all industrial sectors due to a  wide range input and an international approval package    DANGER OF EXPLOSION   Remove an item only when it is not connected to power or if it is loca
6. a uniform distribution of  power is guaranteed by setting all parallel operated power  supply units to exactly the same output voltage    To ensure symmetrical distribution of power  we recommend  designing all cable connections from the power supply unit to  a busbar of the same length and with the same conductor  cross section  The system makes it advisable to install a pro   tective circuit at the output of each device when more than  two power supply units are connected in parallel  e g  decou   pling diode or DC fuse   This prevents high reverse feed cur   rents in the event of a secondary device fault     Redundant operation    Redundant circuits are suitable for the supply of systems  which make especially high requirements on the operational  safety  If a fault occurs in the primary circuit of the first power  supply unit  the second device automatically takes over the  entire power supply  without interruption  and vice versa  For  this reason  the power supply units to be connected in paral   lel are dimensioned in such a way that the total current re   quirement of all consumers can be completely covered by  one power supply unit  100  redundancy makes external  decoupling diodes necessary  QUINT DIODE 40  Order No   2938963      Increased performance    For n parallel connected devices  the output current can be  increased to n x Iy  Parallel connection to increase efficiency  is used for the expansion of existing systems  It is advisable  to use parallel connecti
7. acteristic B     Screw connection    9mm    24 V DC  1    22 5 V DC     29 5 V DC  5 A  0  C     55  C   Screw connection    9mm     Nm   Torque  0 4   0 5  0 4   0 5    PHOENIX CONTACT    6    TRIO PS 1AC 24DC 5    Block diagram       The power supply units are built in devices  The device may only be installed and put into operation by qual   IRs ified personnel  The corresponding national regulations must be observed     DANGER OF EXPLOSION   Remove an item only when it is not connected to power or if it is located in the non explosive area     DANGER   Components with dangerously high voltage and high stored energy are located in the device   Never carry out work on live parts    Depending on the ambient temperature and the load  the housing can become very hot     Before startup please ensure     The mains connection has been carried out by a competent person and protection against electric  shock is guaranteed     The device can be disconnected outside the power supply unit in accordance with the regulations as  in EN 60950  e g  through primary side line protection      The ground conductor is connected     All feed lines are sufficiently protected and dimensioned     All output lines are dimensioned according to the maximum output current of the device or separately  protected        Sufficient convection is guaranteed     102777_02_en PHOENIX CONTACT 7    TRIO PS 1AC 24DC 5    Installation       In order to guarantee sufficient convection  we  recommend observing the
8. d radio interference in acc  with EN 55011    102777_02_en    TRIO PS 1AC 24DC 5    Level 3  6 kV  8 kV    Criterion B    Level 3  80 MHz     3 GHz  10 V m    Criterion A    4 kV  level 4   asymmetrical  conductor to ground   2 kV  level 3   asymmetrical  conductor to ground     Criterion A    4 kV  level 4   asymmetrical  conductor to ground   2 kV  level 4   symmetrical  conductor to conductor     Criterion A    Level 3   asymmetrical  0 1 MHz     80 MHz  10 V    Criterion A     mains buffering  gt  10 ms     Criterion B    EN 55011  EN 55022  Class B  area of application  Industry and residential  EN 55011  EN 55022  Class B  area of application  Industry and residential    PHOENIX CONTACT    5    TRIO PS 1AC 24DC 5    Structure    S 2  Y  S  Q  SS  E       Input data   Input nominal voltage range  AC input voltage range   AC frequency range   Input fuse  integrated    Recommended backup fuse for mains protection    Type of connection    Stripping length    Output data    Nominal output voltage   Setting range of the output voltage  Output current   Type of connection    Stripping length    102777_02_en       1 AC input  2 DC output  3 Potentiometer 22 5 V DC     29 5 V DC  4  DC OK  LED  5 DIN rail adapter  6 Take up for cable binders   mmz AWG  solid stranded  Input 0 2  2 5 0 2 2 5 24 14  Output 0 2  2 5 02 25 24 14    100 VAC    240 V AC   85 V AC     264 V AC  derating  lt  90 V AC  2 5  per Kelvin   45 Hz    65 Hz   3 15 A  slow blow  internal     6A  10A  16 A  char
9. e lines as low as possible        You can fasten the connection cables to the  housing using cable binders    Ensure that the cable binders and the connec   tion cables are designed for the surface tem   peratures that occur in operation    Make sure that the insulation of the connection  cables is not damaged when tightening the ca   ble binders           TRIO POWER       The connection is made using the     and     screw connec   tions on the screw connection of the DC output  At the time   of delivery  the output voltage is 24 V DC  The output voltage  can be set on the potentiometer           Protection of the secondary side    The device is electronically protected against short circuit  and idling  In the event of a malfunction  the output voltage is  limited to 35 V DC     Signaling    The  DC OK  LED enables evaluation of the function of the power supply directly on site     Output voltage  gt  21 5 V Output voltage  lt  21 5 V or no voltage at the output       Meaning Output voltage and output TRIO POWER is in operation  but there is a fault on the side  current OK of the consumer  the current consumption is greater than ly  or the output is short circuited   TRIO POWER is out of operation because there is no mains  voltage  the fuse on the primary side has been triggered  or  the device is faulty     102777_02_en PHOENIX CONTACT 11    Function    Your  V     Output current  A              102777_02_en    40    lour  A     60  Ambient temperature    C     TRIO PS 1AC
10. i  eo ec cata sera ace acetic gcc et tee vac roca cen orcas 12  OQuiput enge s STE CUNY TT 12  BK Z  venr 1 He Ue ToT 12  STH Rea ee DT 13    102777_02_en PHOENIX CONTACT 2    TRIO PS 1AC 24DC 5    Order data    Description    Primary switched power supply  1 phase  output current  5 A    Technical data    Input data   Input nominal voltage range  AC input voltage range   AC frequency range    Current consumption    Inrush current limitation  It    Power failure bypass    Typical response time  Power factor  cos phi   Protective circuitry   Input fuse  integrated    Recommended backup fuse for mains protection    Discharge current to PE    Output data    Nominal output voltage   Setting range of the output voltage  Output current   Derating   Current limitation   Max  capacitive load    Control deviation    Power loss nominal load max    Maximum power dissipation idling   Efficiency   Ascent time   Residual ripple   Peak switching voltages   Connection in parallel   Connection in series   Surge protection against internal surge voltages    Resistance to reverse feed    Signal output DC OK active  Status display    Type Order No  Pcs  Pkt   TRIO PS 1AC 24DC 5 2866310 1    100 V AC     240 V AC  85 V AC     264 V AC  derating  lt  90 V AC  2 5  per Kelvin   45 Hz     65 Hz    1 65 A  120 V AC   0 9 A  230 V AC      lt 15A  1 1 A2s     gt  20 ms  120 V AC    gt  110 ms  230 V AC      lt 1s   0 72   Transient surge protection Varistor  3 15 A  slow blow  internal     6A  10A  16 
11. on if the power supply unit does not  cover the current requirement of the most powerful con   sumer  Otherwise the consumers should be spread among  individual devices independent of one another  A maximum  of five devices can be connected in parallel        102777_02 en PHOENIX CONTACT GmbH  amp  Co  KG   32823 Blomberg    Germany 13  Phone   49  0  5235 3 00     Fax   49  0  5235 3 4 12 00  www phoenixcontact com    
12. pprovals  UL rating    102777_02_en    TRIO PS 1AC 24DC 5    4 kV AC  Type test   2 kV AC  routine test     2 kV AC  type test   2 kV AC  routine test     500 V DC  type test    IP20   I  with PE connection    gt  500 000 h in acc  with IEC 61709  SN 29500   Steel sheet  zinc plated   Aluminum   40 mm  130 mm  115 mm   0 6 kg     25   C     70   C   gt  55   C derating    40   C    85   C  95    at 25  C  no condensation      lt  15 Hz  amplitude  2 5 mm in acc  with IEC 60068 2 6  15 Hz     150 Hz  2 3g  90 min     15g in all directions in acc  with IEC 60068 2 27  2  3K3  in acc  with EN 60721     EN 60204  EN 61558 2 17    EN 60950 VDE 0805  SELV   EN 61558 2 17    EN 50178 VDE 0160  PELV     EN 60950  SELV   EN 60204  PELV     DIN VDE 0100 410  DIN VDE 0106 1010    DIN 57100 410  DIN VDE 0106 101    EN 61000 3 2    UL C UL Listed UL 508  UL C UL Recognized UL 60950    PHOENIX CONTACT 4    Conformance with EMC directive 89 336 EEC    Immunity to interference in acc  with EN 61000 6 2    Discharge of static electricity  Housing  Contact discharge  Discharge in air  Comments  Electromagnetic HF field  Housing  Frequency range  Field intensity  Comments  Fast transients  burst   Input  Output  Comments  Surge current loads  Surge     Input Output    Comments  Conducted interference   Input output   Frequency range   Voltage   Comments  Voltage dips   Input    Comments    Emitted interference in acc  with EN 61000 6 3  Radio interference voltage in acc  with EN 55011    Emitte
13. ted in the non explosive area     DANGER   Components with dangerously high voltage and high stored energy are located in the device   Never carry out work on live parts    Depending on the ambient temperature and the load  the housing can become very hot     Make sure you always use the the latest documentation   It can be downloaded at www download phoenixcontact com     A conversion table is available on the Internet at  www download phoenixcontact com general 7000 en OO pdf        DOG 0OC DMO0Meleo gt  Lionna 0D E    INSPIRING INNOVATIONS    TRIO PS 1AC 24DC 5    Table of contents    HESS SUMO TTT 1  Tape Or CO tS TTT 2  0  2  i Fz rc ere eee arene Rinne tie emote Nee Pon renee REN eee nea NEUE OU nT ra nn ae en ee ee ere ee eee ae 3     NG Il Mik TTT 3  ee heH 6  BOCKA TTT 7  sale mand  T  aT g   NOl HT 7  HENS VANEAU    Eseries A uae ean cee E eee 8  ates   Fei feta e e le  a ie me eer neers OT yee ee PEP Er aE OS SRE OER ELE Perr ee Tee 8  LT ne  UT 9  KENO II ee L O dasebeaes aaceda sadeenanee 9  Connection to various network fFOPMS 2 0    eee cece cee cesceseceecceeseneceeseseceeseeeceeseuseauseaeseeseeeseseseeseesvarseeesneenesnresseeeneds 9  Ise EN PEE PE E N E E LE EET A EET P EE T EE CEC EAE PE A A E EE E EEA A E E A 10  Protection orthe PRIMARY Side iee a ee a eeraa a Sawaal 10  Recommended backup fuse for mains protection    eee eee eee e 10  9700 ee eE A eae a E A T E a eer ee ee ere 11  Protection of the secondary Side    sse eee 11   0 312     a  6 TTT 11  S
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Gigabyte M1405 Laptop User Manual  el archivo de datos tecnicos en PDF  HP LaserJet M1319 MFP Series Service Manual  System overview  - Motherboards.org    Samsung OL46B Kasutusjuhend  du Rouergue - Villefranche-de  Miele KF 1903 SF Specification Sheet  Samsung RA20FHSS Käyttöopas    Copyright © All rights reserved. 