APC SUA2200XL-NETPKG uninterruptible power supply (UPS)

image

Contents

1. S o OOO Pg O tef 0 ie 10 9 9 0 cf exe Eee at Bg f 5 o x o a a j 88 g TEEN Start the UPS 1 Press the button on the front panel to start the UPS The battery charges to 90 capacity during the first four hours of normal operation Do not expect full battery run capability during this initial charge period Refer to the APC Web site www apc com for battery runtimes 2 For optimal computer system security install PowerChute Smart UPS monitoring software Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 7 Communication Ports SERIAL PORT USB PORT Use only the supplied cable to connect to the serial port A standard serial interface cable is incompatible with the UPS Serial and USB ports cannot be used simultaneously Emergency Power Off The emergency power off EPO feature is user configurable EPO provides immediate de energizing of connected equipment from a remote location without switching to battery operation 1 Use the EPO connector supplied with the UPS 2 Use a normally open contact to connect the 24 terminal to the IN terminal External voltage is not required 3 Wire the four pin connector to the EPO system EPO PORT EPO located on rear panel Connector
2. The EPO interface is a Safety Extra Low Voltage SELV circuit Connect it only to other SELV circuits The EPO interface monitors circuits that have no determined voltage potential Such closure circuits may be provided by a switch or relay properly isolated from the utility To avoid damage to the UPS do not connect the EPO interface to any circuit other than a closure type circuit Use one of the following cable types to connect the UPS to the EPO switch e CL2 Class 2 cable for general use e CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air e CL2R Riser cable for use in a vertical run in a floor to floor shaft e CLEX Limited use cable for use in dwellings and for use in raceways e For installation in Canada Use only CSA certified type ELC extra low voltage control cable e For installation in other countries Use standard low voltage cable in accordance with national and local regulations 8 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Operation Display Panels 120 208 V models 120 208 V 096 072 048 024 0 lt 24 Battery Charge 230 V models 230 V 096 072 048 024 0 lt 24 L Display Panel Indicators and Function Buttons Indicator i PEA LED Indicator Title Description On Line The UPS is supplying utility power to the connected equi
3. L Feature Button Feature Title Function Power On Press this button to turn on the UPS Continue reading for additional capabilities Self Test Automatic The UPS performs a self test automatically when tuned on and every two weeks thereafter by default During the self test the UPS briefly operates the connected equipment on battery Manual Press and hold the button for a few seconds to initiate the self test Cold Start When there is no utility power and the UPS is off the cold start feature will switch the UPS and connected equipment onto battery power see Troubleshooting Power Off Press this button to turn off the UPS 10 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Configuration UPS settings Settings are adjusted through PowerChute software or optional SmartSlot accessory cards Factory User Selectable Function Default Choices Description Automatic On startup and e On startup and every Set the interval at which the UPS will execute a Self Test every 14 days 7 days 168 hours self test 336 hours there after there after e On startup and every 14 days 336 hours there after e On startup only e No self test UPS ID UPS_ IDEN Up to eight characters Uniquely identify the UPS i e server name or alphanumeric location for network management purposes Date of Last Manufacture mm dd yy Reset this date when you replace the battery Battery D
4. Ensure rack stability prior to installing devices in the rack The UPS should be installed at or near the bottom of the rack If external battery packs are to be installed in the rack the UPS must be the top unit in the configuration After all of the batteries have been connected tuck the battery cables in between the batteries and the battery doors This will ensure a secure fit of the bezel to the unit Accessories This UPS is equipped with an accessory SmartSlot Refer to the APC Web site www apc com for available accessories If a standard accessory such as a Network Management card is to be installed on this UPS refer to the Utility CD for user documentation Install accessories prior to connecting power to the UPS 6 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Start Up Connect Equipment and Power to the UPS 1 The UPS features a transient voltage surge suppression 7VSS screw located on the rear panel for connecting the ground lead on surge suppression devices such as telephone and network line protectors Prior to connecting the grounding cable ensure that the UPS is NOT connected to utility or battery power 2 Connect equipment to the UPS NOTE This UPS is equipped with an external battery connector on the rear panel of the unit Where appropriate use an APC extension battery cable For ordering details contact your dealer or APC through the Web site www apc
5. Power Conversion APC Power Infrastructure Co Ltd Lot 10 Block 16 Phase 4 1678Ji Xian Road Tong An American Power Conversion PEZA Rosario Cavite Xiamen 132 Fairgrounds Rd Philippines P R China 361100 West Kingston RI 02892 USA American Power Conversion American Power Conversion 1600 Division Rd Lot 3 Block 14 Phase 3 West Warwick RI 02892 USA PEZA Rosario Cavite F Philippines American Power Conversion 40 Catamore Blvd APC India Pvt Ltd East Providence RI 02914 USA 187 3 188 3 Jigani Industrial Area Jigani Bangalore 562106 Karnataka India Importer American Power Conversion A P C b v Ballybritt Business Park Galway Ireland Galway Ireland Ray S Ballard Managing Director Europe ui f fat 5 Jan 06 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 19
6. THE UPS BATTERY before shipping in compliance with U S Department of Transportation DOT and IATA regulations The battery may remain in the UPS 4 Mark the RMA on the outside of the package Return the UPS by insured prepaid carrier to the address given to you by Customer Support Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Two Year Warranty The limited warranty provided by American Power Conversion APC in this statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business Terms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase The obligation of APC under this warranty is limited to repairing or replacing at its sole discretion any such defective products This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way Repair or replacement of a defective product or part thereof does not extend the original warranty period Any parts furnished under this warranty may be new or factory remanufactured Non transferable warranty This warranty extends only to the original purchaser who must have properly registered the product The product may be registered at the APC Web site www apc com Exclusions APC shall not be liable unde
7. com 3 Add optional accessories to the SmartSlot located on the rear panel 4 Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords 230 V models The utility power cord is supplied in the UPS literature kit Prior to connecting the utility power connect the ground lead optional to the TVSS screw 5 120 V models Check the SITE WIRING FAULT LED located on the rear panel The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet see Troubleshooting 6 To use the UPS as a master on off switch be sure all connected equipment is switched on Rear Panels 3000 VA P z F 3000 VA z 000 ao jo o D pisana ie O CO0000000000000 O of g 208 VAC cee ee ee la oe gt eee foyexexe PPE oo o 3 B9 eRe 5 5 LRP e Yo OQO o COO o 120 VAC 2200 VA 2200 VA o 3000 VA P OOO lo Poo OO O G P exe O is fone SA exe O Ot Q lt O cee CO Keres FRO exe COO exes O EE 0 fo Q a006 l aaga l Bg fo o oxexexe O 9099 O loxenene Oo 0 O na Cs yO OOP 120 VAC i 230 VAC fo Q
8. other distributor from whom you purchased your APC product for information on how to obtain local customer support Entire contents copyright 2006 American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC the APC logo Smart UPS and PowerChute are trademarks of American Power Conversion Corporation All other trademarks product names and corporate names are the property of their respective owners and are used for informational purposes only 18 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual APC www apc com 2006 EC Declaration of Conformity pisane da deci ADi We the undersigned declare under our sole responsibility that the equipment specified below conforms to the following standards and directives Harmonized Standards EN55022 EN55024 EN62040 1 1 2 EN61000 3 2 3 3 4 2 4 3 4 4 4 5 4 6 4 8 4 11 EN60950 1 IEC60950 1 Applicable Council Directives 73 23 EEC 89 336 EEC93 68 EEC Type of Equipment Uninterruptible Power Supply Model Numbers SUA2200XLI SUA3000XLI Manufacturers American Power Conversion American Power Conversion APC Suzhou UPS Co Ltd Ballybritt Business Park 2nd Street 339 Suhong Zhong Lu Galway Ireland PEZA Cavite Economic Zone Suzhou Industrial Park pore c P Rosario Cavite Suzhou Jiangsu 215021 oe eee Philippines P R China Breaffy Rd Castlebar Co Mayo Ireland American
9. protected from power outages Refer to the appropriate replacement battery user manual for battery module installation instructions See your dealer or contact APC at www apce com for information on replacement battery modules amp Be sure to deliver the spent battery s to a recycling facility or ship it to APC in the 2 replacement battery packing material Service If the UPS requires service do not return it to the dealer Follow these steps l 2 Review the problems discussed in Troubleshooting to eliminate common problems If the problem persists contact APC Customer Support through the APC Web site www apc com Note the model number of the UPS the serial number located on the back of the unit and the date purchased If you call APC Customer Support a technician will ask you to describe the problem and attempt to solve it over the phone If this is not possible the technician will issue a Returned Material Authorization Number RMA If the UPS is under warranty repairs are free Procedures for servicing or returning products may vary internationally Refer to the APC Web site for country specific instructions Pack the UPS in its original packaging If this is not available refer to www apc com for information about obtaining a new set Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transit is not covered under warranty Always DISCONNECT
10. CH WARRANTIES APC WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES IN NO EVENT SHALL APC ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES SPECIFICALLY APC IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWARE LOSS OF DATA COSTS OF SUBSTITUENTS CLAIMS BY THIRD PARTIES OR OTHERWISE NO SALESMAN EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY WARRANTY TERMS MAY BE MODIFIED IF AT ALL ONLY IN WRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT Warranty claims Customers with warranty claims issues may access the APC customer support network through the Support page of the APC Web site www apc com support Select your country from the country selection pull down menu Open the Support tab at the top of the Web page to obtain contact information for customer support in your region Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 17 Regulatory Information Regulatory Agency Approvals and Radio Frequency Warnings FCC Compliance Notice This equipment has
11. ate module Replacement Minimum Capacity 0 percent 0 60 Specify the percentage to which batteries will Before Return from 15 75 be charged following a low battery shutdown Shutdown 30 90 before powering connected equipment 45 Voltage Sensitivity High sensitivity Brightly Adjust by pressing the VOLTAGE SENSITIVIY The UPS detects Bee illuminated high switch rear panel Use a pointed object such and reacts to line el sensitivity as a pen to do so voltage distortions by transferring to battery operation to protect the Dimly illuminated medium sensitivity No illumination low sensitivity Note In situations of poor power quality the UPS may frequently transfer to battery operation If the connected equipment can operate normally under such conditions reduce connected the sensitivity setting to conserve battery equipment capacity and service life Alarm Delay Enable e Enable Mute ongoing alarms or disable all alarms Control e Mute e Disable Shutdown Delay 90 seconds O0s e 360s Set the interval between the time when the UPS 90s 4505 receives a shutdown command and actual 180s 5405 shutdown e 270s e 630s Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 11 Factory User Selectable Function Default Choices Description Low Battery 2 minutes Brightly The low battery warning beeps are continuous Warning Be Bes illuminated when two minutes of
12. been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy If it is not installed and used in accordance with the instruction manual it may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense 120 208 V models G LISTED 42C2 LR63938 E95463 230 V models CE fG amp CO Quicse NOM APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways e Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information Wwww apc com support Global support searching APC Knowledge Base and using e support e Contact an APC Customer Support center by telephone or e mail Local country specific centers go to www apc com support contact for information Contact the APC representative or
13. d hot neutral polarity reversal and overloaded neutral circuit Contact a qualified electrician to correct the building wiring The input circuit breaker trips The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site Wwww apc com Unplug all nonessential equipment from the UPS Reset the circuit breaker The AVR Boost or AVR Trim LEDs are illuminated The system is experiencing very high or low utility voltage Have a qualified service personnel check your facility for electrical problems If the problem persists contact the utility company for further assistance 14 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Problem and or Possible Cause Solution There is no utility power There is no utility power and the UPS is off Use the cold start feature to supply power to the connected equipment front the UPS battery s Press and hold the button There will be a short beep followed by a longer beep Release the button during the second beep UPS operates on battery although line voltage exists The UPS input circuit breaker trips Unplug all nonessential equipment from the UPS Reset the circuit breaker Your system is experiencing very high low or distorted line voltage Move the UPS to a different outlet on a different circuit Inexpensive fuel powered generators may distort t
14. defined in Specifications on the APC Web site www apc com The alarm remains on until the overload is removed Disconnect nonessential equipment from the UPS to eliminate the overload condition The UPS continues to supply power as long as it is online and the circuit breaker does not trip the UPS will not provide power from batteries in the event of a utility voltage interruption The Replace Battery Battery Disconnected LED is illuminated The Replace Battery Battery Disconnected LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected Check that the battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours and perform a self test If the problem persists after recharging replace the battery Failure of a battery self test Replace Battery Battery Disconnected LED illuminates and the UPS emits short beeps for one minute The UPS repeats the alarm every five hours Allow the battery to recharge for 24 hours Perform the self test procedure to confirm the replace battery condition The alarm stops and the LED clears if the battery passes the self test If the battery fails again it must be replaced The connected equipment is unaffected The Site Wiring Fault LED on the rear panel is illuminated 120 V model only The UPS is plugged into an improperly wired utility power outlet Wiring faults detected include missing groun
15. he voltage Test the input voltage with the utility voltage display see Operation If acceptable to the connected equipment reduce the UPS sensitivity Battery Charge and Load LEDs flash simultaneously The UPS has shut down The internal temperature of the UPS has exceeded the allowable threshold for safe operation Check that the room temperature is within the specified limits for operation Check that the UPS is properly installed allowing for adequate ventilation Allow the UPS to cool down Restart the UPS If the problem persists contact APC at www apc com Diagnostic utility voltage All five LEDs are illuminated The line voltage is extremely high and should be checked by an electrician There is no LED illumination The line voltage is extremely low and should be checked by an electrician On Line LED There is no LED illumination The UPS is running on battery or it must be turned on The LED is blinking The UPS is running an internal self test Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 15 Maintenance Transport and Service Replacing the Battery Module This UPS has easy to replace hot swappable battery modules Replacement is a safe procedure isolated from electrical hazards You may leave the UPS and connected equipment on during the replacement procedure Once the batteries are disconnected the connected equipment is not
16. lity voltage is chronically low set the low transfer point lower if the connected equipment tolerate thi ition eroe eon save ee eo 182 VAC e 178 VAC 170 VAC 230 V models 208 VAC e196 VAC 204 VAC e 200 VAC 208 VAC Output Voltage Set the output voltage of the UPS 230 V models 230 VAC 220 VAC 240 VAC e 230 VAC 12 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Troubleshooting Use this chart to solve minor UPS installation and operation problems Refer to www apce com for assistance with complex UPS problems Problem and or Possible Cause UPS will not turn on Solution The battery is not connected properly Check that the battery connector is fully engaged button not pushed Press the button once to power up the UPS and connected equipment The UPS is not connected to utility power supply Check that the power cable from the UPS to the utility power supply is securely connected at both ends Very low or no utility voltage Check the utility power supply to the UPS by plugging in a table lamp If the light is very dim have the utility voltage checked UPS will not turn off The UPS is experiencing an internal fault Do not attempt to use the UPS Unplug the UPS and have it serviced immediately UPS beeps occasionally Normal UPS operation when running on battery None The UPS is protecting the connected equipment Press the button to
17. nstallation The UPS is shipped in tower configuration Tower Configuration Connect the battery O After the battery has been connected tuck the battery cables in between the battery and the battery door This will ensure a secure fit of the bezel to the unit i i 4 Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Rack Mount Configuration This unit is intended for mounting in a two post rack To order a four post rack mount kit contact your dealer or refer to the APC Web site www apc com Tower to rack mount conversion procedure The UPS and the battery modules are heavy Remove the battery modules to lighten the UPS during installation Pull the battery disconnect strap attached to the battery connector DO NOT pull the battery cables to qi disconnect the battery Disconnect Battery Battery Disconnect Strap Remove the top cover and O Remove and rotate the display panel QO Q Four post rack mount Two post rack mount bracket position bracket position x4 5 8 in A four post rack configuration requires installation of two brackets in the forward position see diagram above two cleats supplied with this unit and the four post rails The rails can be ordered through the APC Web site www apc com Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 5 Install unit in rack
18. pment WU see Troubleshooting AVR Trim The UPS is compensating for a high utility voltage Refer to the APC Web site TY www apc com for AVR settings AVR Boost The UPS is compensating for a low utility voltage Refer to the APC Web site lt www apc com for AVR settings On Battery The UPS is supplying battery power to the connected equipment Overload The connected equipment is drawing more than the UPS power rating allows see Troubleshooting Replace Battery Battery Disconnected BIAR The battery is disconnected or must be replaced see Troubleshooting Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual Indicator LED Indicator Title Description 120V 208 V Diagnostic The UPS has a diagnostic feature that indicates the utility voltage 0133 0246 Utility Voltage The UPS starts a self test as part of this procedure The self test does not affect 0124 0227 the voltage display 0114 0209 a ea Press and hold the button to view the utility voltage bar graph indicator rolled 8 Che After a few seconds this five LED Battery Charge C indicator on the right of 30V the display panel will show the utility input voltage 0266 Refer to the figure on the left for the voltage reading 0248 Values are not listed on the UPS 0229 The indicator on the UPS shows the voltage is between the displayed value on a the list and the next higher value see Troubleshooting
19. r the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse negligence improper installation or testing Further APC shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection inappropriate on site operation conditions corrosive atmosphere repair installation start up by non APC designated personnel a change in location or operating use exposure to the elements Acts of God fire theft or installation contrary to APC recommendations or specifications or in any event if the APC serial number has been altered defaced or removed or any other cause beyond the range of the intended use THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE OF PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE APC EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SU
20. run time remain PowerChute low battery warning To change the default interval setting use a software interface provides automatic unattended shutdown when approximately two minutes of battery operated run time remains LED is located on rear panel level of about 2 minutes Dimly illuminated low battery warning level of about 5 minutes No illumination low battery warning level is about 8 minutes pointed object such as a pen to press the VOLTAGE SENSITIVIY switch rear panel while pressing the button front display Change the low battery warning interval setting to the time that the operating system or system software requires to safely shut down Synchronized 0 seconds 0s e 240s Specify the time the UPS will wait after the Turn on Delay 60s 300s return of utility power before start up to avoid 120s 3608 branch circuit overload e 180s e 420s High Transfer Point 208 V models e225 VAC 233 VAC To avoid unnecessary use of the battery where 225 VAC e229 VAC 237 VAC utility voltage is chronically high set the high transfer point higher if the connected i t tolerate thi ition 120 V models 127y ac 133 yac eWipment can tolerate this condition 127 VAC e 130 VAC 136 VAC 230 V models 253 VAC 253 VAC 261 VAC 257 VAC 265 VAC Low Transfer Point 120 V models 97 VAC e 103 VAC To avoid unnecessary use of the battery where 106 VAC e 100 VAC 106 VAC uti
21. s Edition CD lec Power ao H IEC jumper cables required for four post rack only Safety information Eight 5 8 in 1 6 cm pan head Warranty information screws for attaching rack mount brackets to the unit Specifications Temperature This unit is intended for indoor use Operating 32 to 104 F 0 to 40 C only Select a location sturdy enough Storage 5 to 86 F 15 to 30 C charge the UPS battery every six months s handle the oe ei 86 to 113 F 30 to 45 C charge the UPS battery every three months o not operate te UPS y ae S is excessive dust or the temperature Maxim m or humidity are outside the specified limits Elevation sige factors i b Operatin 10 000 ft 3 000 nvironmental factors impact battery p 8 gt t 3 000 m life High temperatures poor utility Storage 50 000 ft 15 240 m power and frequent short duration discharges will shorten battery life Humidity 0 to 95 relative humidity non condensing Weight 142 Ibs 64 kg with battery module 142 Ibs 64 kg 89 Ibs 40 kg without battery module 27 Ibs 12 kg each battery module Maximum Number of External Battery Packs Supported by the 10 Smart UPS XL NOTE The model and serial numbers are located on a small rear panel label For some models an additional label is located on the chassis under the front bezel Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 3 I
22. silence this alarm UPS is not providing expected backup time The UPS battery s are weak due to a recent power outage or battery s are near the end of their service life Charge the battery s Batteries require recharging after extended outages Batteries can wear faster when put into service often or when operated at elevated temperatures If the battery s are near the end of their service life consider replacing the battery s even if the replace battery LED is not yet illuminated The UPS is experiencing an internal fault All LEDs are illuminated and the UPS emits a constant beeping Do not attempt to use the UPS Unplug the UPS and have it serviced immediately Front panel LEDs flash sequentially The UPS has been shut down remotely through software or an optional accessory card None The UPS will restart automatically when utility power returns All LEDs are off and the UPS is plugged into a wall outlet The UPS is shut down or the battery is discharged from an extended outage None The UPS will restart automatically when utility power is restored and the battery has a sufficient charge Smart UPS 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U User Manual 13 Problem and or Possible Cause Solution The Overload LED is illuminated and the UPS emits a sustained alarm tone The UPS is overloaded The connected equipment exceeds the specified maximum load as
23. www apce com User Manual English APC Smart UPS XL 2200 3000 VA XL 120 208 230 VAC Tower Rack Mount 5U Uninterruptible Power Supply 990 2975 09 2006 Introduction About this UPS The American Power Conversion APC Uninterruptible Power Supply UPS provides protection for electronic equipment from utility power blackouts brownouts sags and surges The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged Unpack Read the Safety Guide before installing the UPS Inspect the UPS upon receipt Notify the carrier and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Check the package contents UPS Front bezel eLiterature kit containing EPO connector _ i Serial cable Eight E DSR eed nuts Additional contents for Two rail cleats required for four post 230 V models USB cable rack only models Eight ornamental screws for Two rack mount brackets APC power cable securing the unit in the rack Alternate input power cord Product documentation Eight 5 16 in 8 cm pan head UK customers Smart UPS User Manuals CD for attachi leats to th ae rails E EE PowerChute Busines