Home
        SCF 050 CORN FURNACE Installation & Operations Manual
         Contents
1.    A closer look at the Control Board to the  right in figure 14 will explain how the board ON OFF  works  There are five buttons labeled 1  through 5  a slide switch labeled 6 and a  LED Light bar with 5 Heat Settings  The  LED Light bar is also used during the  Diagnostic process  see page 28 for more  details     The buttons on the board function as  follows   Refer to Figure 14  The touch pad  buttons are labeled with the white numbers  1 through 5        1  The Heat Level button  1  will advance  the setting between level 1 and 5  Once you  reach level 5  it will drop back to level 1   Each level has a LED light to indicate where Figure 14  the board is set     SCF 050 Manual  25    Sold and serviced by www PelletKing com   603 424 1183    2  The On Off button  2  turns the Furnace On and Off  It will also reset the board after  the board has sensed a problem and is flashing a Diagnostic code     3  The auger button  3  will allow the customer to manually auger corn into the burn pot  on start up when needed  This is particularly helpful in priming the Auger Tube when it is  empty     4  The Draft Trim button  4  allows for adjusting the Exhaust fan voltage on Heat Level  1 only  Push the button and the all of the LED Lights in the light bar will flash once  This  decreases the voltage approximately 5 volts below the default setting  Push the button a  second time and all of the LED Lights in the light bar will flash twice  This increases the  voltage approximately 5 vol
2.    pe POT BOTTOM  TWO TURNS Es we d H ACCESS COVER     CAUTION   CLEAN OUT RODS  WILL BE HOT    USE HANDLE TOOL    SLIDE END OF  HANDLE TOOL  INTOSLOT _     e PULL COAL RAKE  A FORWARD UNTIL  A IT STOPS                The area shown above is located inside the  Furnace Firebox and must be accessed  through the Firebox door        Figure 21    Burnpot  amp  Slide out Bottom  Removal    To remove the Burnpot from the Furnace the Coal Rake must be pulled back so the pot  will clear it  Open the Firebox door of the Furnace and you will see 2 Hex head screws   Follow steps 1 through 4 in the diagram to the left to remove the Burnpot from the  Furnace  To remove the Slide out Bottom follow steps 1 through 3 in the diagram to the  right     SCF 050 Manual  40    Sold and serviced by www PelletKing com   603 424 1183    3  Clean Out Ports  The Furnace has 3 Exhaust Cleanout Ports located in the LEFT  AND RIGHT lower corners of the firebox and behind the Ashpan  Remove covers  and clean regularly                                 CLEAN OUT PORT  LEFT SIDE SHOWN                            CLEAN OUT  PORT  BEHIND  REMOVE COVERS ASH PAN  REGULARLY AND  CLEAN AS DESCRIBED                                                 Figure 22    Frequency of cleaning depends on the amount of fuel being burnt and the quality of the  Corn Pellets  Failure to clean the ash traps will cause the Furnace to become plugged  with Fly Ash     4  Heat Exchange Baffle  Remove the baffle and clean the ashes that acc
3.   Also make sure you are using clean corn  Otherwise this is mainly caused  by improper combustion  See Damper Adjustment section of the Operations Manual  Besides  the damper adjustment there are several areas that can have an effect on the combustion process     Solution  Check all Gaskets  Doors and door Latching Systems for air leaks  Any leaks in  these areas will negatively affect the burn process and cause the pot to overload  Also make sure  the slide out bottom is closed all the way  If this is left open  combustion air will leak out the  bottom of the pot area instead of being used in the combustion process     3  My Furnace runs for approximately 6 to 10 hours and then overloads the Burnpot  What s  wrong     Solution  This most likely means the combustion process is taking place on top of the    Coal  Rake     During normal burning of corn the    Coal Rake    must be pulled out of the  burnpot  This causes the pot to fill up prematurely and overload  The coal rake  will be damaged if left in the pot for long periods of time     4  My Furnace isn   t burning and the number 2 LED light is blinking  This diagnostic light  indicates the vacuum switch no longer senses negative pressure in the firebox area of the  Furnace  What caused the Furnace to go out     The door of the unit was left open longer than 60 seconds   See solution   The ash pan door was left open for longer than 60 seconds   See solution   The combustion fan is not running   Defective fan or control bo
4.   In this  manual approved venting will be referred to a    PL vent    or    Single wall vent     All single wall  vent adaptors must be stainless steel     NOTE  TYPE    B    GAS VENT MUST NOT BE USED IN THE INSTALLATION OF THIS  FURNACE    Examples of venting system components follow        High temperature ceramic roping reduces potential fly ash escaping through joints     Stainless steel inner liners resist corrosive flue gas damage to the system     Flex pipe should be stainless steel  4 ply construction with a total thickness of approx   07 inches     AN    SCF 050 Manual  10    Sold and serviced by www PelletKing com   603 424 1183    TYPICAL PL VENT COMPONENTS    A       RAIN CAP    VERTICAL OR WALL THIMBLE CHIMNEY  HORIZONTAL ADAPTER         ADJUSTABLE LENGTH SINGLE TEE SINGLE REDUCTION DOUBLE TEE  PIPE w TEE CAP TEE w TEE CAP w TEE CAP    SUPPORT BRACKET       iS  t    5                  PIPE ADAPTER INCREASER    45   ELBOW 90   ELBOW    SCF 050 Manual  11    Sold and serviced by www PelletKing com   603 424 1183    VENTING  DETERMINING MATERIALS    TYPE OF MATERIALS   1  PL Vent must be used     2  Exception  Single wall stainless steel may be used inside an existing chimney   No  clearances to combustibles are needed on single wall stainless steel adaptors  rigid or flex pipe  installed within a chimney      3  A clean out    tee     PL Vent or    Quick Connect Exhaust     must be installed directly to the  furnace and at the bottom of each vertical run of the ex
5.   Proper installation is essential for safety  effective Operation  Warranty Coverage  Insurance  requirements and to meet Local Building Codes  Installation Requirements are described in the first  section of this manual  Verify the installation is correct before firing up the furnace for the first time     When burning corn care should be taken in how the venting system is installed  To burn corn the  moisture content should be 15  or less  This is much higher that the moisture content of wood pellets  and can result in condensation forming in the venting system in certain installations  The chimney  system should stay within the warm envelope of the house as much as possible  Only penetrate the  exterior of the home where the exhaust system will terminate     REMEMBER  Condensation from a corn furnace is detrimental to the venting system  Only buy  venting systems that are warranted with burning corn     PREVENTING CHIMNEY FIRES    Chimney fires can be prevented by properly operating the Furnace and by periodic inspection and  cleaning of the chimney  When wood is burned it produces tar and other organic vapors  which  combine with expelled moisture to form creosote  The creosote vapors condense in the relatively cool  chimney flue associated with a slow burning fire  As a result  creosote residue accumulates on the flue  lining  When ignited this creosote can result in an extremely hot chimney fire     The chimney and chimney connector should be inspected at least once ev
6.  Cycle Time on the Control Board  The 10 second Cycle is the factory  setting    PINS   swe When the jumper cap is on the left hand pins  the Cycle time is 10 seconds  This cycle may  be used with Corn and Pellets     LEFT        When the jumper cap is on the right hand pins  the Cycle time is 10 seconds     This cycle may only be used with Pellets        Before calling your dealer for assistance  please read your Operations Manual and perform  all the maintenance issues covered in the Daily and Periodic Maintenance section of the  Manual  If the Furnace still does not operate correctly call your Dealer for Assistance     SCF 050 Manual  53    Sold and serviced by www PelletKing com   603 424 1183    SCF 050    WARRANTY    The Furnace manufactured by Even Temp  Inc  is warranted for five  5  years  to the original  owner  against defects and workmanship on all steel parts  excluding the burn grate  and two  2   year on electrical components from the date of sale to the original owner  There specifically is no  warranty on the paint  glass  burn grate and all gaskets  There is no written or implied  performance warranty on the Furnace  as the manufacturer has no control over the installation   daily operations  maintenance or the type of fuel burned     This warranty will not apply if the Furnace has not been installed  operated and maintained in  strict accordance with the manufacturer s instructions  Burning other than quality corn may cause  Furnace damage and could void th
7.  Heat Pump furnace  with a minimum rating of 45 000 BTU  The duct work of the furnaces may not be hooked in series  with each other  This means the Warm Supply Air of the SCF 050 may not be hooked the Cold Air  Return of the existing furnace  See example in figure 8 above  The Cold Air return of the SCF 050 is  connected to the Return Air Duct of the existing furnace  The Warm Air Supply of the SCF 050  connects to the Supply Plenum of the existing furnace  Back Draft Dampers must be used in the  SCF 050 Warm Air duct and in the Warm Air Plenum of the existing furnace to prevent the air flow  from reversing  It is recommended to enter the Supply plenum of the existing furnace above the Air  Conditioning A coil  The materials used for the Warm Air supply duct must have a minimum  temperature rating of 250 degrees F  The Plenum of the SCF 050 must be constructed of metal  Once  installed as an Add On furnace check the Static pressures in the ductwork to make sure they do not  exceed the limits on the existing Central furnace or of the SCF 050  Running both furnaces at the same  time should not cause any nuisance tripping of the High Limits in either unit    Follow all instructions when connecting to existing ductwork  Connecting the Warm Air Supply  to the Cold Air return may cause harm to the existing furnace and may void the warranty of  both the existing furnace and the SCF 050     CAUTION  Do not connect an air conditioning system to this unit     SCF 050 Manual  16    Sold
8.  and serviced by www PelletKing com   603 424 1183    Blower Specs    The Blower is a 2 Speed blower   600     800 CFM  When  connecting this unit to a duct system  the high speed  should be used  If the Furnace is to be used as a stand   alone shop heater  the option is available to select the 600  CFM setting or the 800 CFM setting  The slower speed  will produce higher air temperatures because the air  moves slower through the heat exchange system   allowing it to become hotter           Minimum Duct Size    2 SPEED  BLOWER  Round  10    SWITCH  Rectangular  6    x 15      Intake Air Duct should be 10  larger  Maximum Static Pressure   4       Velocity  1400 FPM at the above mentioned duct sizes        A larger duct size will produce less Air Flow noise  the above mentioned sizes are the minimum  allowed     Fan Limit Control    The Furnace uses a Fan Limit Control built into the furnace centered below the 10    plenum opening   The High Limit function of this control is set at a maximum setting of 200 degrees F     CAUTION  DO NOT TAMPER WITH THE HIGH  LIMIT SETTING     There are two adjustable Fan Control Settings  They control  when the Convection Blower turns on  and when the Blower  turns off  This will help control the temperature of the air  coming out of the registers  These settings may be adjusted  to accommodate customer preference  If the air seems too  o cool  simply adjust the Fan Off setting higher to shut the  AWAY   blower down sooner  Factory settings are
9.  difficulty adjusting  the Furnace  contact your dealer or the Technical Support Department for St  Croix at Even Temp Inc     SCF 050 Manual  23    Sold and serviced by www PelletKing com   603 424 1183    OPERATING INSTRUCTIONS    A different type of heater  The SCF 050 is a furnace  FOLLOW THESE OPERATING  INSTRUCTIONS EXACTLY AS STATED TO ENSURE SAFE AND RELIABLE OPERATION     1  Carefully read this    Operation and Maintenance    manual in its entirety BEFORE lighting your  Furnace for the first time     2  Obtain final inspection and approval of installation from local building officials     3  Have your dealer demonstrate all the operational and maintenance steps necessary for proper use of  the furnace  Sign and return the warranty card to the address listed on the back page     4  Some odors may be given off during the first few hours of burning during initial break in  These  odors are normal and not harmful  However  ventilating the room until the odors disappear is  recommended     5  The furnace will become HOT while in operation  Keep children  clothing and furniture away from  all hot surfaces     WARNING  Direct contact with the furnace firebox during operation may cause skin burns     6  To avoid the possibility of smoke and or sparks entering the room always keep firebox and ash pan  doors closed whenever the furnace is operating     7  A certain amount of carbon monoxide may be produced within the Furnace as a by product of  combustion  All exhaust vent con
10.  of  the burn pot  The burning fuel on top and the clinker on the bottom     2  The slide out bottom  This allows the bottom to be pulled out so the clinker can  drop out of the bottom of the burn pot     3  The program on the control board  To drop the clinker you set the board on the  1  setting for a couple of seconds and then return the Furnace to the desired setting   This starts a timed delay in the program allowing the clinker to be removed  the  coals to be dropped to the bottom of the pot  and the Burn pot to become balanced  again before the board resumes on the setting of you choice     NOTE  WHEN YOU FIRST OPERATE YOUR FURNACE  CHECK TO  DETERMINE THE NEEDED CLEANING FREQUENCY  THE FURNACE  REQUIRES A MINIMUM AMOUNT OF DAILY MAINTENANCE  REQUIRED  MAINTENANCE DEPENDS LARGELY UPON THE QUALITY OF  CORN PELLETS BURNED AND THE RATE OF BURN  THE AMOUNT OF  DAILY MAINTENANCE WILL INCREASE IF FUEL QUALITY DECREASES  AND OR THE BURNING RATE OF CORN PELLETS INCREASES     NOTE  FAILURE TO KEEP YOUR FURNACE CLEAN  AS DESCRIBED IN  THIS MANUAL  COULD RESULT IN POOR OPERATION  INEFFICIENT  FUEL USAGE AND A POSSIBLE SAFETY HAZARD  IT IS THE  RESPONSIBILITY OF THE OWNER USER TO DETERMINE THE NEEDED  MAINTENANCE FREQUENCY     CAUTION  THE DOOR AND FRONT PART OF THE FURNACE WILL BE  HOT  DO NOT TOUCH ANY PART OF THE FURNACE THAT IS HOT     SCF 050 Manual  36    Sold and serviced by www PelletKing com   603 424 1183    Daily Maintenance    Example of Schedule for dropping Clinkers 
11.  shown in figure 9        HIGH LIMIT  SETPOINT    The Fan limit has a Break Away Tab that has been removed   When replacing a Fan Limit Control  be sure to remove the  tab as shown in figure 9        Figure 9    SCF 050 Manual  17    Sold and serviced by www PelletKing com   603 424 1183    Mobile Home Installation    Unit must be installed in accordance with the   Manufactured Home and Safety Standard  HUD   CFR 3280  Part 24    The Furnace has been tested and listed for mobile home installations  In addition to all previously  detailed requirements  mobile home installations must observe the following     1  WARNING  DO NOT INSTALL IN A SLEEPING ROOM     2  WARNING  COMBUSTION AIR MUST COME FROM THE OUTSIDE OF THE  MOBILE HOME  FAILURE TO DO SO MAY CREATE NEGATIVE PRESSURE  WITHIN THE MOBILE HOME AND COULD DISRUPT PROPER VENTING AND  OPERATION OF THE PELLET FURNACE     3  CAUTION  THE STRUCTURAL INTEGRITY OF THE FLOORS  WALLS  CEILING  AND ROOF MUST BE MAINTAINED                  FLOOR  PROTECTION    METAL  CHASSIS    GROUND STRAP    Figure 10    SCF 050 Manual  18    Sold and serviced by www PelletKing com   603 424 1183    4  Permanently bolt the Furnace to the floor     5  Electrically ground the Furnace and pedestal to the metal chassis of the home  Use a number eight    8  gauge or larger copper wire     6  Maintain an effective vapor barrier at location where PL vent exits the structure              Check any other local building codes or other codes that may apply   
12.  the Furnace down  Adjust the damper   See Damper Adjustment in the  Operations Manual         The Burnpot being empty will mean the auger quit feeding fuel while there was  still a fire in the burnpot  Check to see if there is fuel in the hopper  If the hopper  is empty  fill the hopper and re light the Furnace     d  If there is fuel in the hopper check to see if there is an obstruction in the auger  system or if the auger set screw is loose     Solution  Remove obstruction and re light the Furnace or tighten the setscrew on the  auger shaft     My Furnace isn   t burning and the  2 and  3 LED lights are blinking  This means the high  Limit has shut the Furnace down  The Convection Blower could be defective or may need  cleaning  The high limit switch may be also defective  It is best to call your dealer for support  when trying to troubleshoot the High Limit Switch  Do not use your Furnace if the High Limit  switch frequently trips     I lit the Furnace and the   2 light started blinking and smoke spills out of the Furnace  How  do I get the Furnace to quit smoking     SCF 050 Manual  50    10     11     Sold and serviced by www PelletKing com   603 424 1183    Cause  The Furnace did not establish a vacuum and shut down  With the fuel in the pot  burning  the smoke finds the path of least resistance and leaks out into the house    See Installation Manual  Minimum vertical height needed  to establish some  natural draft and prevent smoke spillage     Solution  Pull the Slid
13.  the burn pot rapidly turns into glowing coals  If you see a lot of  unburned corn in the pot  an adjustment may be needed  In an unbalanced pot the corn  will quickly stick together and prevent the proper flow of combustion air  The pot will  overload and the fire will go out     When burning pellets make sure to check for the formation of creosote in the unit and  venting system  Constantly running the Furnace on a low setting with too much  combustion air may cause creosote to form  Burn pot temperatures can be    too cool     when burning on low with too much draft  Once the damper is adjusted for your  installation  it should not be necessary to make any further adjustments to the damper   The combustion air is automatically increased every time the feed rate is advanced on the  control board  If you notice a difference in the operation of the Furnace  first check to see  if the Furnace needs cleaning  Then check to see if there is a change in the fuel you are  burning  The moisture content of your corn may be too high or the quality of the pellets  you are burning may have changed  Break in requires the burning of 15 bushel of corn or  15 bags of pellets or a continuous burn for two weeks     0 D     E The setscrew is a useful tool in  Sms making adjustments to the Air  Intake damper  Adjust the  damper by turning the screw one  half turn clockwise and place the  damper blade against the screw   Wait 10 minutes to allow the  burn to adjust to the new setting   Making to
14.  there weren   t enough coals in the pot when the corn started  feeding into the pot during start up  the Furnace should be burning fine and an  adjustment is most likely not needed     b  Advance the heat setting to  2 and let the Furnace burn at this setting for Ya an  hour  Check the burn pot to see if it is balanced  Most likely the Furnace will be  burning fine at this point  because the damper was preset at the factory     c  Advance the heat setting to  3 and let the Furnace burn at this setting for   an  hour  Check the burn pot to see if it is balanced  Remember  Look at the coals in  the pot  not at what the flame looks like  Most likely the damper will not need to  be adjusted     d Advance the heat setting to  4 and let the Furnace burn at this setting for Y an  hour  Check to see if the pot is balanced  This is where a damper adjustment  might need to be made  As the heat setting reaches the higher settings the    Lag  time    can become too long if the air isn   t adjusted correctly  If you notice that the  coals are being covered up with unburned corn  adjust the damper to give it more  air  Remember  Only turn the setscrew one Y turn clockwise to open the damper   You might need to use a screwdriver to break up the clump of corn in the burn  pot to allow for proper airflow   Wait 15 minutes to see if the burn pot becomes  balanced  Repeat this step as many times as needed until the burn pot becomes  balanced     SCF 050 Manual  33    Sold and serviced by www P
15. 03 424 1183    STEP ONE    COAL RAKE    Figure 19 IS  PUSHED IN          Y AS    8       POT BOTTOM SS   amp  IS  PUSHED IN       2  The ash pan  Make sure the Ashpan is not too full to receive a clinker  If the  Ashpan is too full  the clinker may not drop all the way through  This will not  allow the pot bottom to be closed  If this happens  empty the Ashpan and restart  the Furnace     3  The slide out bottom   See figure 20  Now you are ready to drop the clinker from  the burn pot  Pull the bottom out in one quick motion and let the clinker drop into  the ash pan  Quickly push the bottom in again  To pull out the slide bottom use  the Rod Handle tool shown in figure 21 on page 40         THE COAL RAKE  WILL BE PUSHED IN   amp    THE POT BOTTOM  WILL BE PULLED OUT    Figure 20    4  The control board  Set the heat setting to  1 for a few seconds and return to the  setting it was on  This initiates the time delay for dropping the clinker     SCF 050 Manual  38    Sold and serviced by www PelletKing com   603 424 1183    5  Dropping the coals back into the burn pot  At this time pull the coal rake back out  of the burn pot to drop the coals in the pot  See position of Coal Rake  amp  Pot  Bottom in figure 18 on page 37 for normal operation     The time delay in the program will allow a smooth transition back to where the Furnace  was burning before the clinker was dropped     6  Cleaning the Heat exchange tubes  Now you can pull the tube scraper back and  forth a couple of t
16. 2  If the Furnace has been running for an extended period of time on the  5 setting   the clinker will sometimes stick to the burn pot  If that happens  pull the coal rake  back out  Open the door and use a long screwdriver and give the clinker a couple  nudges in the pot   Make sure the burnpot bottom is closed when you do this or  you will lose the coals with the clinker  Then repeat the steps for dropping the  clinker     Remember  The coal rake must be pulled out and the slide bottom pushed in during  normal operation of the Furnace   See Furnace layout on page 6     Remember  The fire door and ash pan doors must be in the latched position during  normal operation of the Furnace   See Furnace layout on page 6     SCF 050 Manual  39    Sold and serviced by www PelletKing com   603 424 1183    Periodic Maintenance    CAUTION  Periodic maintenance should only be done while the Furnace is shut off and  cold     1  Ashpan  Empty the ash pan when it appears full  approximately once a week   The  frequency of cleaning the ash pan will depend on the quality and amount of  Corn Pellets being used  Carefully check to make sure the ash pan door is tightly  closed after each opening     2  Burnpot and Slide Out Bottom  Clean burn grate holes whenever needed  Remove  the Burnpot and use a small metal object  Nail  Drill Bit  etc  to clean out plugged  holes   See Figure 21 below     STEP 4    LIFT POT UP  g TO REMOVE  5 FROM FURNACE    STEP 2   oe La   STEP 2    LOOSEN SCREW  gt      
17. 8  Do no use components other than those specified for use with this unit   9  Floor protection requirement must be followed precisely     10  PL Vent must be used for exhaust venting   Single wall vent is not allowed   Follow PL Vent  manufacturer   s installation directions and observe all listed clearances to combustibles     DO NOT CONNECT THE SCF 050 FURNACE TO A DOWN FLOW FURNACE SYSTEM     Thermostat Hook Up    NOTE  Installers must determine a neutral location of where to mount the Thermostat in order  for accurate room temperature measurements     Wiring Connections    To hook up a thermostat   connect the wires from the  thermostat to the external  Wire Terminal on the left  side of the Furnace  The  external Terminal has been    pre wired to the thermostat  connections on the back of  the control board           For Information on how the  Thermostat operates  please  read the section covering  thermostat operations        THERMOSTAT  WIRE  TERMINAL          Figure 11    SCF 050 Manual  19    Sold and serviced by www PelletKing com   603 424 1183    SCF 050 OPERATION    CAUTION  Operate this unit only with the fuel hopper lid closed  Failure to do so may result in  emission of products of combustion from the hopper under certain conditions  Maintain hopper  seal in good condition    This unit requires 120 volt AC power to operate  In the event on a power failure the unit will shut  down  DO NOT ATTEMPT TO RUN THE UNIT DURING A POWER FAILURE     INSTALLATION CHECK  
18. BLOWER  OR TO A CHIMNEY OR VENT SERVING  A GAS FURNACE OR APPLIANCE    This furnace should only be installed on a furnace duct system and chimney that are  in good operating condition    This furnace is equipped with a direct drive blower motor  This motor should not be  changed with one of lesser speed  A motor with a faster speed may be used  The size  of the blower should not be changed  This equipment should be installed  acceptable  to regulatory authority  by experienced licensed personnel    The installation of this furnace should comply with the requirements of CAN CSA   b365  and changes to the installation should comply with CSA B139  for oil fired    C22 1  for electric   or CAN CGA B149 2  for gas fired      SCF 050 Manual  48    Sold and serviced by www PelletKing com   603 424 1183    TROUBLESHOOTING       FRQUENTLY ASKED QUESTIONS    The Furnace is very trouble free in operation when properly maintained and quality pellets are used   When the Furnace fails to operate properly  troubleshooting by the operator of the Furnace is limited   Please read the following guide for answers to frequently asked questions    1  When first starting the Furnace remember the auger tube is empty  which will delay feeding fuel  to the burn pot  This will in some cases prevent the Furnace from starting     Solution  Prime the burn pot if the auger tube is empty     2  My Furnace keeps overloading the burnpot  First check the moisture content of your corn  It  should be 15  or less
19. D ASH    Do Not Use Chemicals or Fluids to Start The Fire    Do Not Burn Garbage  Gasoline  Naphtha  Engine Oil  or Other Inappropriate  Materials   The Furnace will not operate during a power failure  unless a Battery Back up  system is used during brief power outages  Prolonged Power Outages will require  the use of a Generator to operate the Furnace     SCF 050 Manual  47    Sold and serviced by www PelletKing com   603 424 1183    Additional Canadian Requirements for Supplementary  Add On  Furnaces    See label on the inside front panel of the furnace for additional information     1     2   3     10     11     DO NOT USE DUCT ELBOWS HAVING AN INSIDE RADIUS OF LESS THAN  6    150mm  ON THE FURNACES    DO NOT CONNECT DUCTWORKSO THAT A REVERSE FLOW IS POSSIBLE   OPERATE THE  GAS  OIL OR ELECTRIC  FURNACE PERIODICALLY TO  ENSURE THAT IT WILL OPERATE SATISFACTORILY WHEN NEEDED   CERTIFIED FOR INSTALLATIOS WITH DUCT WORK CONFIGURATIONS  SIMILAR TO THAT SHOWN IN FIGURE 8 ON PAGE 16    DO NOT RELOCATE OR BYPASS ANY OF THE SAFETY CONTROLS IN THE  ORIGINAL  GAS  OIL OR ELECTRIC  FURNACE INSTALLATION    DO NOT CONNECT WITH ANY GAS FURNACE THAT HAS NOT BEEN  CERTIFIED INITIALLY AS COMPLYING WITH CAN CGA 2 3   THE OPERATION OF THE GAS FURNACE MUST BE VERIFIED FOR  ACCEPTABLE OPERATION BEFORE AND AFTER INSTALLATION OF THIS  ADD ON FURNACE BY A GAS FITTER WHO IS RECOGNIZED BY THE  REGULATORY AUTHORITY    DO NOT CONNECT TO ANY GAS FURNACE THAT IS NOT EQUIPPED WITH  A AN AIR CIRCULATING 
20. E DAMPER IN THE EXHAUST SYSTEM OF UNIT    DO NOT CONNECT THIS FURNACE TO A CHIMNEY SYSTEM THAT IS  CONNECTED TO ANOTHER APPLIANCE     DO NOT INSTALL THIS UNIT IN A SLEEPING ROOM    ATTENTION    CONDENSATION  When planning the installation of your Furnace  keep in  mind that condensation is detrimental to exhaust systems  Corn has higher  moisture content than pellets and can be more susceptible to condensation  forming in certain types of installations  Install the Furnace with a minimum of  the system exposed to the cold temperatures outside the envelope of the house   Check with the manufacturer of your venting system that they honor the  warranty of their PL Vent with the use of corn     ATTENTION    BATTERY BACKUP  We strongly recommend using a battery backup system if  the furnace is installed using horizontal venting only  This prevents any smoke  from entering your home in the event of a power failure     SCF 050 Manual  9    Sold and serviced by www PelletKing com   603 424 1183    VENTING  APPROVED MATERIALS    The Furnace requires a venting system approved for pellet Furnaces by a certified testing lab   Approved pellet Furnace venting materials are  1  PL vent  a double wall vent with a stainless  steel liner  and 2  Single wall rigid or flexible stainless steel pipe  PL Vent and Single wall vent  is available through manufacturers such as  Energy Vent LTD  James A  Ryder  Simpson  DuraVent and Selkirk Metalbestos and is carried by many local pellet Furnace dealers
21. E STRICTLY  PROHIBITED     DAMPER       Figure 7    2  Outside air may be drawn from a semi enclosed attic or crawl space or any semi enclosed space   Take care not to draw cold air past water pipes that may freeze     3  Increase the outside air pipe diameter to 3    for runs over ten  10  feet and elevation over 4 000 feet   Note  Long runs should be avoided     4  Terminate the outside air pipe below the exhaust vent outlet     5  5  An open mesh screen should be placed over the outside air pipe opening to prevent birds or  rodents from nesting in the opening  Use an elbow or shield to prevent prevailing winds from  blowing directly into the outside air intake pipe  NOTE  Mesh screen should be no smaller than  one fourth inch  1 4     by one fourth inch  1 4         WARNING  OUTSIDE COMBUSTION AIR IS REQUIRED FOR ALL MOBILE HOME  INSTALLATIONS     SCF 050 Manual  15    Sold and serviced by www PelletKing com   603 424 1183    Connecting To Existing Duct Work  amp  Furnaces    Before installing the furnace  check the Static Pressure in  the duct system              Static Pressure must not  exceed A  IWC in the  duct system     BACK  DRAFT  DAMPER         EXISTING  After Installation check the FURNACE  Static Pressure in the duct  system  If Pressure is more  than  4 IWC the duct system  must be changed to reduce  the pressure below the  maximum rating of  4  IWC     RETURN    AIR    Figure 8    The SCF 050 may be connected to the existing ductwork of a Gas  Oil or Electric
22. ENT REQUIRES A 3   CLEARANCE  TO COMBUSTIBLES  USE UL LISTED  WALL THIMBLES AND FIRESTOPS      I FLOOR JOISTS  VJ NMS  S DS  4    Q  VU    CLEARANCE TO PUBLIC WALKWAY    CLEARANCES TO COMBUSTIBLES  247               CLEARANCE 47    TO GROUND    O    HA    Figure 5    THE EXHAUST TERMINATION LOCATION MUST BE AT LEAST    1     305 mm   T  2 1 m    1      305 mm   2     610 mm     ABOVE the ground level   FROM a public walkway   FROM The wall penetration point   FROM any adjacent combustibles such as   Adjacent buildings  fences  protruding parts  of the structure  roof eaves or overhangs   plants  shrubs  etc     SCF 050 Manual  13    Sold and serviced by www PelletKing com   603 424 1183    Venting into an Existing Chimney    CAP  STORM         COLLAR 24  ALWAYS FOLLOW  PL VENT MANUFACTURERS  CLEARANCES TO COMBUSTIBLES  FLASHING         CEILING LE  OR x T    WALL  THIMBLE               MASONARY  THIMBLE    3    EARANCE TO   OMBUSTIBLE  3     HHH ll    PL VENT  TEE WITH  CLEANOUT       E     E      mi          E       Figure 6    The Furnace may be connected to an existing Class A chimney or a masonry chimney which meets the  minimum requirements of NFPA 211     1  If the Furnace   s exhaust is connected to a masonry chimney  the masonry chimney must be free of  cracks that could leak exhaust gases or fly ash  A relining of the chimney with either PL vent or  single wall stainless steel pipe may be necessary to bring the chimney into compliance    2  When chimneys are relined  
23. ESULT IN POPERTY DAMAGE  BODILY INJURY  OR EVEN DEATH     INSTALLATION CHECK LIST    FOR USE IN THE U S  AND CANADA  MOBILE HOME APPROVED    CHECK WITH LOCAL AUTHORITIES AND OBTAIN NEEDED PERMITS    WE RECOMMEND INSTALLATION BY A QUALIFIED PROFESSIONAL   BEFORE STARTING THE FURNACE FOR THE FIRST TIME  1  Under certain conditions outside combustion air is recommended  Use only approved parts  When using  out side air for combustion check that the outside air inlet is connected to draw fresh air from outside the  building   2  All joints of PL vent and single wall stainless steel pipe should be fastened by at least 3 screws and    correctly installed   Follow vent manufacturer   s instructions   Seal all joints with high temperature silicone  to create an airtight seal     3  WARNING  The high temperature paint on this Furnace may take several hours of burning at a high fuel  setting to cure fully  During this time  an odor that is not harmful may be evident  When odors are present   the area around the Furnace should be well ventilated     4  Caution  The high temperature paint can be easily scratched prior to burning the Furnace     CAUTION    FAILURE TO FOLLOW THE INSTRUCTIONS IN THE INSTALLATIONS MANUAL MAY RESULT  IN A HOUSE FIRE  PLEASE FOLLOW INSTALLATION AND MAINTENANCE INSTRUCTIONS        SCF 050 Manual  5    Sold and serviced by www PelletKing com   603 424 1183  SCF 050    Furnace Layout           200 LBS HOPPER  PLENUM    AUGER ACCESS OPENING    PANEL    FIREBOX  CO
24. MPONENT DOOR    ACCESS COVER                 FAN LIMIT  i CONTROL    VIEWING  DIGITAL GLASS  CONTROLS  e   2 SPEED 2  BLOWER  SWITCH  THERMOSTAT  TERMINAL  AIR  FILTER  CONVECTION ASHIPAN  DOOR SLIDE OUT  FRONT PANEL  BLOWER BOTTOM ROD  ACCESS COVER HANDLE       Figure 1    The SCF 050 has a large Heat Exchange system  allowing for more heat to be exchanged  The  burn system used in the furnace is the St  Croix Patent Pending    Clinker Removal System      This burn pot allows the clinker to be removed without loosing the fire in the pot  This eliminates  the need of having to constantly re light the furnace after removing the clinker     SCF 050 Manual  6    Sold and serviced by www PelletKing com   603 424 1183    Furnace Dimensions       25 25  wel j 33 75  wel                                                                                           Figure 2    Furnace location    When finding a location to install the furnace  several things need to be kept in mind  Consider  the following things  Service Access  Venting  Return air Duct  Supply air Duct and  Electrical     Service Access  The front panel is removable to allow access to the ash pan and the firebox for  regular maintenance  The Control Board is mounted on the left side  There are also 2 access  panels on the left side  The smaller cover gives access to the following components  Combustion  Fan  Vacuum Switch and Proof of Fire Switch  The larger cover allows access to the Convection  Blower for maintenance 
25. NCE SECTION  Using a thermostat will cause variations in the maintenance  Check the  burnpot frequently in the beginning to establish a maintenance schedule based on use of  furnace Contact your dealer for more information on where to get high quality corn to burn in your  new corn furnace     Store corn in a tight container or use other methods to ensure they do not become rain soaked or  absorb moisture from damp or wet floors  This will also prevent rodents from becoming a problem  Do  not store corn within Furnace installation clearances or within the space required for clinker removal   The Furnace is not warranted against damage caused by poor quality corn  incorrect operation  poor  maintenance or incorrect installation     PELLETS    Clinkers and Ash are by products of pellet combustion and are not caused solely by your Furnace   Furnace performance can be quickly and severely reduced if poor quality pellets are used  Contact  your dealer for more information on APFI approved wood pellet fuels     NOTE  Pellets with excessive sawdust should be screened by sifting with 1 4  mesh screening     Store Pellets under cover on a wooden pallet or other methods to ensure they do not become rain  soaked or absorb moisture from damp or wet floors  Do not store pellets within Furnace installation  clearances or within the space required for ash removal     There are 2 ways to burn pellets in the SCF 050 furnace  If the furnace is used with a thermostat and  the burn rate is moder
26. QUENTIAL OR OTHER DAMAGES OF ANY NATURE  WHATSOEVER IN EXCESS OF THE ORIGINAL PURCHASE PRICE OF THIS PRODUCT   ALL WARRANTIES BY MANUFACTURER ARE SET FORTH HEREIN AND NO CLAIM  SHALL BE MADE AGAINST MANUFACTURER ON ANY ORAL WARRANTY OR  REPRESENTATION     Some states do not allow the exclusion or limitation of incidental or consequential damages  or  limitations of implied warranties  therefore the limitations of exclusions set forth in this warranty  may not apply to you  This warranty gives you specific legal rights  and you may have other  rights  which vary from state to state     SCF 050 Manual  54    Sold and serviced by www PelletKing com   603 424 1183    Notes     After the break in period  please note any adjustments that were made to the Feed Trim  and Draft Trim on the control board in the area below  In the event of a power failure or  1f the units gets unplugged the trim settings will be lost     Draft Trim  Circle one  See point 4 on page 24     Default Draft Low Draft High Draft    Feed Trim  Circle one  See point 5 on page 24     Default Pilot Medium Pilot Low Pilot    Serial Number   Date of Purchase     Dealer Information     Even Temp  Inc   P O  Box 127  Waco  NE 68460    PHONE  402 728 5255  FAX  402 728 5379  EMAIL  SUPPORTEEVENTEMPINC COM  WEB ADDRESS  www eventempinc com       SCF 050 Manual  55    
27. Sold and serviced by www PelletKing com   603 424 1183  Installation  amp  Operations Manual    PELLET     CORN SIOVEs    SCF 050  CORN FURNACE          SCF 050 Manual  1    Sold and serviced by www PelletKing com   603 424 1183    TABLE OF CONTENTS    re mre reall Orn Att pax cpr a EE 4  Installation Check Mast 0 oe e ng e dl Ge 5  Furnace  Layout Diagram mitin ias 6  Furnace Dimensions  Location  amp  Clearances       ccccccccnnncncnnnononononononinoninoninininininnononos 7 8  HAUS EV CICS dl re sd onde ae o 10  Venting   Approved Materials vascas add 10  Venting Typical PL Vent Components   ccooccnoccnonnconancnnncnoncnnnnnonn nono ncnnncnnnnnnnn no 11  Venting   Determining Materials sii A dt 12  Venting   Termination Requirements ads 13  Venting  Termination Clearance Requirements cococccnnccnnnnononncnoncnannninnnonnncnnns 14  Venting     Into an existing Chmnen E 15  COMPUSO AA ds 16  Connecting to Existing Duct Work tie eege eegen ege eegen  17  Mobile  Hom   Installation odo apasia 18  Thermostat Hook Up ins 19  SCE 050 Operation  A E a ASA a E E A eee ee 20  Installation EE 20  Preyenting Chimney e A 20   Burning Corn  Pellets cun a 21 23   Control Board  Features iii ts 25  Pre Lighting  amp  Lighting mstructons cnn ncnnnnos 26 28   Sh  ttns OM the jura uns li 28  Diagnostic  amp  Safety Features cuca ir dd 28 30   SCF 050 Manual    2    Sold and serviced by www PelletKing com   603 424 1183    Combustion Air Damper     Location and Adjustments    oooocnnocnnononon
28. a chimney chase cap that reduces the outlet of the chimney to the size  of the liner is required  Extend the exhaust vent above the chimney chase cap and finish it off with  a rain cap  A single wall liner may need to be wrapped with insulation to maintain adequate  exhaust temperatures when outside temperatures drop below freezing  causing the flue  temperatures to become too low    3  Venting into the side of an existing masonry chimney must be done through a masonry thimble   When wall penetration is necessary to access a masonry chimney  use a listed PL vent wall  thimble   Figure 6     4  When venting into a Class A steel chimney use an appropriate PL Vent adapter     SCF 050 Manual  14    Sold and serviced by www PelletKing com   603 424 1183    COMBUSTION AIR    1  Under certain conditions it is recommended that the Furnace be connected to an outside source of  combustion air to improve Furnace performance  Flexible metal hose  such as ClevFlex  or rigid  metal pipe   conduit   must be connected around  NOT INSIDE  the combustion air inlet tube   Figure 11A   Be careful not to pinch or bend the outside air pipe with too small a radius which  may e terminated flush with the outside wall but should be protected from wind and weather by a  hood  Note  The outside air pipe must terminate above the maximum snow line     WARNING    USE THE AIR INTAKE  DAMPER FOR  ADJUSTING  COMBUSTION INLET  AIR ONLY  OTHER       METHODS OF  RESTRICTING OR  BLOCKING  COMBUSTION INLET  AIR AR
29. and Ash from burn pot  This may be  required more than once a day  depending on the burn rate of the Furnace and the quality  of Corn Pellets used  Check the furnace frequently at first to establish a Schedule for  cleaning the burnpot  If Clinker Ash is not removed  the burnpot will overload and  fuel will spill into the Ashpan     1   Continuous burning of the furnace on the Low burn setting  Pilot      Approximately  every 30 hours  This may vary depending on the quality of Corn Pellets used     2   Continuous burning of the furnace at the High burn setting   5      Approximately  every 12 hours  This may vary depending on the quality of Corn Pellets used     The daily maintenance will mainly focus on 4 areas in the Furnace  removing the clinkers  from the ash pan  1f needed   dropping the clinker from the burnpot  cleaning the heat  exchange tubes and cleaning the glass  A break down of this process consists of these  steps     POSITION OF  COAL RAKE   amp   POT BOTTOM  DURING NORMAL  OPERATION             Normal Operation  gt   Figure 18 PULLED OUT  gt  _        POT BOTTOM As de  IS SS      PUSHED IN Sony    1  The coal Rake  The first step is to push the coal rake in and shave the coals off  the top of the clinker  Once this is done open the door and add a  4 cup of pellets  on top of the coals  See figure 19 on page 38   To push in the Coal rake  use the  Rod Handle tool shown in figure 21 on page 40     SCF 050 Manual  37    Sold and serviced by www PelletKing com   6
30. ard    The vacuum switch is defective    The vacuum hose is disconnected   The vent system is plugged with fly ash     S  CH E    Solution  If the fire is out  re light the Furnace  If the fire is still burning make sure all  doors are securely latched and hold down the On Off button  approximately 5    SCF 050 Manual  49    Sold and serviced by www PelletKing com   603 424 1183    seconds  until Furnace starts up again  This will re start the Furnace in the start up  program  Occasionally use the auger button to manually feed fuel until the auto   feed takes over  Auto feed will start 5 minutes after the Furnace has been  restarted      My Furnace isn   t burning and the number 3 LED light is blinking  This diagnostic light  indicates that the Proof of Fire Switch no longer senses a fire in the Furnace  First check to see 1f  there are pellets in the hopper  If there are pellets in the hopper  why did the Furnace go out     a  Unburned fuel in the burnpot means the fire went out before the auger quit  feeding   b  A power Failure could also cause this  If the furnace is still hot when the power    comes back on  the feed system will resume  If the fire had gone out in the pot   the feed would continue to run until the Proof of Fire switch dropped out and shut  the Furnace down     Solution  Too much Combustion Air on the pilot setting  Adjust the air damper   See section  covering an Unbalanced Burnpot   Corn Pellets would still feed until the P O F  switch  eventually shuts
31. ate  not constantly running on the higher settings   simply remove the side  shields as shown in figure 12 on page 22  To burn pellets in the standard burn pot in the furnace   the side shields of the pot must be removed  A maintenance schedule must be established for  removing the ash from this pot  The frequency of removal of ash from the pot should be determined by  the owner user of the furnace  It will vary depending on fuel consumption of the unit   See section  covering the    Clinker Removal    on page 35 for more information   A CONTINUOUS BURN  MAINTENANCE SHEDULE IS PROVIDED AS AN EXAMPLE ON PAGE 36 IN THE DAILY  MAINTENANCE SECTION  Using a thermostat will cause variations in the maintenance  Check the  burnpot frequently in the beginning to establish a maintenance schedule based on use of furnace     SCF 050 Manual  21    Sold and serviced by www PelletKing com   603 424 1183    The Furnace is not warranted against damage caused by using poor pellets  incorrect  operation  improper maintenance or incorrect installation     E    LIFT UP TO  REMOVE  SIDE SHIELDS  Es    Ns    BURNPOT SHOWN OUTSIDE  OF FURNACE  TO REMOVE  SHIELDS  POT DOES NOT  NEED TO BE REMOVED  FROM FURNACE        Figure 12    To burn Pellets  detach the side shields by removing the 2 screws holding the shield in place   Do not discard this part  but save it for future use in the event you switch back to burning  corn  The shields must be removed when burning pellets     A Retrofit pellet pot is a
32. away from the building     4  For termination above the building roofline a rain cap is required     5  The exhaust pipe on all Furnaces is 4    O D  to accommodate a pipe adaptor     SCF 050 Manual  12    Sold and serviced by www PelletKing com   603 424 1183    VENTING  TERMINATION REQUIREMENTS    In determining optimum vent termination  carefully evaluate external conditions especially when  venting directly through a wall  Since you must deal with odors  gases  and fly ash  consider  aesthetics  prevailing winds  distances from air inlets and combustibles  location of adjacent  structures and any code requirements     1  Exhaust must terminate above combustion air inlet elevation     2  Do not terminate vent in any enclosed or semi enclosed area   i e  Carports  garage  attic  crawl space  etc   or any location that can build up a concentration of fumes     3  Vent surfaces can get hot enough to cause burns if touched by children  Non combustible  shielding or guards may be required         EXHAUST  TERMINAL                                   EXHAUST  TERMINAL                          Figure 4  4     1 2 m  BELOW a door  window  cavity  or air vent  4  1 2 m  HORIZONTALLY FROM a door  window  cavity  or air vent  1     305 mm  ABOVE a door  window  cavity  or air vent    SCF 050 Manual  13    Sold and serviced by www PelletKing com   603 424 1183    VENTING  TERMINATION CLEARANCE REQUIREMENTS    PUBLIC WALKWAY             CLEARANCE TO WALL  PENETRATION POINT    12     PL V
33. cnannninnnonancnnnncnnno 30 34  Thermostat Control  amp  Pilot SEM  iia A eae 35  SCF 050 Maintenance ii ection 35   St  Croix Clinker E ii 35   Clinker Ash Removal cocinan ata is 36  Daily Ma eo tte aa EE be Oa T 37 39  Periodic Mani ed tial go ck nel Bees ote ate ae 40 42  Vary VES AICS os cite ec daps pace ects ec once n e a 43 44  Safe Opera EE 44  Wiring Sc A Gee tute 45  Electrical Layos aio aida 46    Canadian Requirements    station  ti a 47   LB Ye EEN 47    gt  Upplementary Furnace dessai dee Eed aeons 48   Troubleshooting  amp  Frequently Asked Questions          ooooooonnccnnnconnncnncccincnconnccnos 49 53   KE LEE 54   Furnace tos a lia 55  SCF 050 Manual    3    Sold and serviced by www PelletKing com   603 424 1183       Save This Installation  amp  Operations Manual    GENERAL INFORMATION  SAFETY PRECAUTIONS    SAFETY NOTICE  The furnace must be properly installed in order to prevent the possibility  of a house fire  These installation instructions must be strictly observed  The Maintenance  schedule must be followed as described in this manual  Failure to follow instructions may  result in property damage  bodily injury or even death     The furnace   s exhaust system works with negative combustion chamber pressure and a slightly  positive chimney pressure  Therefore  it is imperative that the air intake and exhaust system be  airtight and installed correctly  Do not install a flue damper in the exhaust vent of this unit     Do not connect this unit to a chim
34. e Out Bottom out and drop the fuel into the ash pan  This will  minimize the amount of smoke that can spill into the room     I turned the Furnace on with the On Off switch and nothing happens  First check to see if  the Furnace is plugged in and the receptacle has power to it     Solution  Check the fuses on the back of the control board  F2 is the fuse for power in to the  board  Replace with a 250 Volt  5 Amp fuse     I turned the Furnace on with the On Off switch and the board lights up and the fans come  on  but the auger doesn   t feed any fuel     Solution  Check the F1 fuse on the back of the control board  This fuse runs the Auger  circuit only  Replace with a 250 Volt  5 Amp fuse     Why is my glass dirty  Normal operation of your St  Croix Corn Pellet Furnace will produce a  white build up on the glass that wipes off with a dry paper towel  However extended burning on  the low setting only will produce a light tan color  These types of build up on the glass are  normal  A heavy black build up on the glass could indicate a problem     Solution  Adjust the combustion air setting to the proper setting  If this doesn   t seem to  help  make sure the clean out cover plates are installed in the Furnace  It also  could be an indication that the Furnace is getting plugged and needs a good  cleaning  Refer to the section in the manual that covers the Daily  Periodic and  Yearly Maintenance of the Furnace     How do I adjust my Pilot feed rate settings   1 setting   Not all 
35. e warranty     The warranty does not cover damage or breakage due to misuse  improper handling or  modifications     A warranty registration card is provided  The card is to be checked and signed and returned to  factory  by the owner  Appropriate information is to be noted on the card     All claims under this warranty must be made through the dealer where the Furnace was  purchased  If an inspection by the dealer indicates that a warranty claim is justified  and that all  conditions of this warranty have been met  the manufacturer s total responsibilities and liabilities  shall be to repair or replace  at the manufacturer s option  the defective part s   All costs of  removal  shipment to and from the dealer or manufacturer  any losses during shipment and  reinstallation and any other losses due to the Furnace being removed shall be covered by the  owner of the Furnace     NEITHER THE MANUFACTURER  NOR THE SUPPLIERS TO THE PURCHASER   ACCEPT RESPONSIBILITY  LEGAL OR OTHERWISE  FOR THE INCIDENTAL OR  CONSEQUENTIAL DAMAGE TO PROPERTY OR PERSONS RESULTING FROM THE  USE OF THIS PRODUCT  ANY WARRANTY IMPLIED BY LAW  INCLUDING BUT NOT  LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS  SHALL  BE LIMITED TO ONE  1  YEAR FROM THE DATE OF ORIGINAL PURCHASE  WHEN A  CLAIM IS MADE AGAINST THE MANUFACTURER BASED ON THE BREACH OF THIS  WARRANTY OR ANY OTHER TYPE OF WARRANTY EXPRESSED OR IMPLIED BY  LAW  MANUFACTURER SHALL IN NO EVENT BE LIABLE FOR ANY SPECIAL   INDIRECT  CONSE
36. ed by opening a window slightly on  a calm day    The house is sealed with a well sealed vapor barrier and tight fitting windows and  doors and or has any powered devices  which exhaust house air     d  There is excessive condensation on the windows during the winter     e     A ventilation system is installed in the house    Additional Canadian Operation Requirements     1     2     Store Corn Pellets in sealed containers in a dry environment to prevent the fuel from  absorbing moisture and becoming damaged   Creosote formation and Cleaning     a     b     Establish a routine for the storage of fuel  care of the Furnace and Firing  Techniques    Check Daily for Creosote build up until experience shows how often cleaning is  necessary    Be aware that the hotter the fire  the less creosote is deposited  and that weekly  cleaning may be necessary in mild weather  even though monthly cleaning may  be enough in the coldest months  Run the furnace on the hottest setting once a day  for 30     45 minutes to prevent excessive build up in the furnace    Keep the doors closed and all seals in good condition while operating the furnace   INSPECT THE FLUE PIPES  JOINTS AND SEALS REGULARLY TO  ENSURE THAT SMOKE AND FLUE GASES ARE NOT DRAWN INTO   AND CIRCULATED BY THE AIR CIRCULATION SYSTEM    CLEANING OF THE HEAT EXCHANGER  FLUE PIPE  CHIMNEY AND  DRAFT INDUCER IS ESPECIALLY IMPORTANT AT THE END OF THE  HEATING SEASON TO MINIMIZE CORROSION DURING THE SUMMER  MONTHS CAUSED BY ACCUMULATE
37. elletKing com   603 424 1183    e     Advance the heat setting to  5 and let the Furnace burn at this setting for Ya an  hour  Check the burn pot to see if it is balanced  A small damper adjustment  might need to be made at this time to make sure the    Lag time    isn   t too long   Remember  Only turn the setscrew one 1 2 turn clockwise to open the damper   Wait 15 minutes to see if the burn pot becomes balanced  Repeat this step as  many times as needed until the burn pot becomes balanced     If the Furnace has been connected to an existing Chimney system that has good natural  draft  the procedure mentioned in the last 2 points above may actually require that the  damper gets closed slightly instead of opened to compensate for the additional draft in the  chimney system     The process of adjusting the damper when burning Corn will take about 3 hours  but it  only needs to be done once at the initial burn  This will adjust the Furnace to the unique  circumstances of your home     Procedure for adjusting the damper when burning Pellets     When burning pellets in the Furnace  the adjustment to the damper will most likely need to  be made when the Furnace is running in the pilot mode     a     If a heavy black shiny build  difficult to wipe off  up is noticed  on the glass and inner  surfaces  after the furnace runs on the low  pilot  setting for extended periods of time   the damper must be closed some  This may require the Furnace to run in pilot mode  for a while to beco
38. ems too warm  and the  Thermostat is never calling for heat  a lower pilot setting may be a better fit for the home     Remember  Choosing a lower Pilot setting may require the damper to be fine tuned to  match the lower feed rate  Monitor how the furnace is operating after a change is made  and adjust the damper if needed     SCF 050 MAINTENANCE    The St  Croix corn clinker theory  And why we do what we do     Some manufacturers of corn Furnaces use complicated stirring mechanisms to break up  the clinker in the burn pot  We feel that is a mistake     We believe that corn doesn   t burn as well when it is disturbed during the burn process   Corn needs high temperatures and proper airflow in the burn pot to burn properly  That  energy is stored in the clinker that is being formed in the burn pot  It glows red hot and  provides the heat needed to ignite the corn that is being fed into the burn pot  When the  clinker is broken up  that constant source of energy is lost and now it becomes more  difficult to burn corn  When corn is not burning properly it tends to stick together and  form a clump in the burn pot  It is impossible for air to flow through this clump and soon  the pot will overload and the fire goes out  This is where some manufacturers use the  stirring mechanism to break up the clump of corn to maintain proper airflow and others  use large burn pots to handle this problem  Smaller burn pots are better   The truth is  neither is needed  The St  Croix corn burning 
39. enerous amount of starter gel to the pellets     3  This next item is optional  but it will give an immediate boost to the start up  procedure  Crumple up half of a newspaper page with some pellets  light the gel and toss  the paper and pellets on top of the Coal rake in the burn pot     4  Close the door and push the On Off button on the control board   Button  2     If the optional method described in point 3 was used allow the pellets to ignite on top of  the Coal Rake for several minutes and then pull the Coal rake out of the burn pot and  drop the top layer of pellets on top of the burning pellets in the bottom of the pot     At this point all that needs to be done is to monitor the burn pot to make sure the Furnace  starts up properly  Once the On Off button has been pushed the Start Up program takes  over     The Start up Program works as follows   a  The Combustion Fan comes on at high speed and the control board checks to    make sure the Vacuum switch locks in   See section on Diagnostic features on  page 27     SCF 050 Manual  27    Sold and serviced by www PelletKing com   603 424 1183    b  When the board senses the Vacuum switch the exhaust fan speed drops to the  1  setting and runs for 5 minutes     c  After 5 minutes the board checks for    Proof of Fire    and starts feeding corn or  pellets on the  1 setting   See section on Diagnostic Features on page27  If the    board senses P O F  then the Furnace has started successfully     d  If the board fails to se
40. ers have thoroughly cooled     2  Never use Gasoline  gasoline type lantern fluid  Kerosene  charcoal lighter fluid  or similar liquids to start or    freshen up    a fire in this heater  Keep all such liquids  well away from the heater while it is in use     3  Creosote  Soot and Fly Ash  Formation and Need for Removal  The products of  combustion will contain small particles of Fly Ash  The fly ash will collect in the  venting system and restrict the flow of flue gases  Incomplete combustion  such as  occurs during start up and shut down  or incorrect operation of the room heater  will lead to some soot or creosote formation which will collect in the venting  system  The exhaust system should be inspected regurlarly during the heating  season to determine if creosote buildup has occurred  Check more frequently at  first to determine a schedule for cleaning the venting system based on individual  use of this Corn Pellet burning heater  If creosote has accumulated  it should be  removed to reduce the risk of a chimney fire     4  Do not Overfire this unit  Follow all instructions regarding the proper use of this  heater     SCF 050 Manual  44    Sold and serviced by www PelletKing com   603 424 1183    Wiring Schematic                 Black  120 Volt AC  White    Common    Convection  Blower    Proof of Fire  Switch    Wire Colors    1 Orange  2 Gray  3 Open  4 Blue  5 Yellow  6 Open  7 Orange  8 Gray  9 Brown  10 Brown  11 White  12 Black    Normally Open    Combustion Fan B
41. ery two months during the  heating season to determine if a creosote build up has occurred  If a significant layer of creosote has  accumulated  3 mm or more  it should be removed to reduce the risk of a chimney fire  Use of an  appropriately sized chimney brush or the services of a professional chimney sweep are recommended     The chimney and chimney connector should be inspected at least once every two months during the  heating season to prevent the system from getting plugged with Fly ash  Clean the exhaust system 1f  needed  Use of an appropriately sized chimney brush or the Services of a Professional chimney sweep  are recommended     SCF 050 Manual  20    Sold and serviced by www PelletKing com   603 424 1183    SHELLED CORN    SATISFACTORY PERFORMANCE  Shelled corn must be 15  or less moisture content  The keys  to satisfactory performance are  proper operation of the Furnace  diligent maintenance and burning  only dry  clean  quality corn  Corn dust must be screened prior to using     NOTE  Corn with excessive grain dust must be screened  by sifting with 3 16  mesh screening   Large pieces of cob may plug the auger     Clinkers and Ash are a by product of burning corn and are not caused by your Furnace  Furnace  performance can be quickly and severely reduced if poor quality corn is used   See section covering  the    Clinker Removal    on page 35 for more information  A CONTINUOUS BURN  MAINTENANCE SHEDULE IS PROVIDED AS AN EXAMPLE ON PAGE 36 IN THE DAILY  MAINTENA
42. fuel burns at the same rate   The moisture content of corn greatly influences how it burns  Burning Pellets requires  adjustments to the low burn to prevent Creosote from forming  Following is a description of the  function of the Feed Trim button    Solution  The Feed Trim button on the control board allows the feed rate on  1  Pilot  setting  to be increased or decreased  Different types of fuel and the way the Furnace is installed  will affect the low burn and needs attention during the break in period of the Furnace     SCF 050 Manual  51    Sold and serviced by www PelletKing com   603 424 1183    ALWAYS DISCONNECT APPLIANCE  POWER BEFORE SERVICING    THERMOSTAT MANUAL    a  The default Pilot setting has an On Time of 2 5 seconds   The  1 LED light indicates the default pilot setting  This  setting requires little fine tuning     b  Pressing the Feed Trim button once will turn the  1 and   4 LED lights on at the same time  This reduces the On  Time to 2 0 seconds  reducing the fuel on the pilot setting  Less Fuel may require more adjusting of the draft     See the figure to the right for details        ALWAYS DISCONNECT APPLIANCE  POWER BEFORE SERVICING    THERMOSTAT MANUAL Figure 27    c  Pressing the Feed Trim button again will turn  on the  1 and  5 light at the same time This  reduces the On Time to 1 5 seconds  Again   less Fuel may require more adjusting of the  draft     See figure to the left for more details    Using the auger trim button is also helpful  when t
43. haust system  These tees are to assist in  periodically cleaning the pipe  Single or double clean out tees may be used  The exhaust system  must be installed so the entire system can be cleaned without disassembly     NOTE  ADHERE TO THE PL VENT CLEARANCES TO COMBUSTIBLES AS REQUIRED   STRICTLY OBSERVE THE PL VENT MANUFACTURER   S SAFETY SPECIFICATIONS     QUANTITY OF MATERIALS     1  It is recommended that the vent system be installed with a minimum of three feet  3     of  vertical rise above the exhaust port on the back of the furnace     FAILURE TO PROVIDE THE NATURAL DRAFT THAT RESULTS FROM A VERTICAL  RISE MAY RESULT IN SMOKE BEING RELEASED INTO THE HOUSE WHEN  ELECTRICITY TO THE UNIT IS INTERRUPTED WHILE BURNING OR SMOLDERING  CORN REMAINS IN THE BURN GRATE   See    Battery Backup    on page 9    2 It is not recommended to run vertical venting outside the heated environment where the  furnace is installed  Running a venting system in a cold environment may cause the flue  temperatures to cool down too much for adequate drafting  See figures 5  amp  6 on pages 13  amp  14   Additional vertical exhaust venting should be provided when using    a  More than one  1  elbow or tee  and or   b  Horizontal runs of over three  3  feet   Horizontal runs over 10 feet not recommended    3  For a venting system ending in a horizontal run  the exhaust pipe must be terminated by a  listed end cap or a PL vent elbow  45 or 90 degrees   Note  End caps or elbows must vent  exhaust gases 
44. he control board again  Many times  the cause of this is a change in the  vacuum inside the Furnace  This may be caused by excessive wind  opening the Firebox door  or opening the Ash Pan door  The control board will monitor the vacuum switch and resume  normal operation if the vacuum returns to normal     Safety Features    WARNING  These safety features are designed to protect life and property     Bypassing these features voids all warranties and the safety listing of the Furnace        1     High Limit    switch     an overheat safety switch will shut off the fuel feed if the  Furnace reaches temperatures above normal operating temperature  This is a     Normally Closed    switch and is part of the Fan limit control  If the High limit  switch trips several times  the problem in the Furnace must be diagnosed before    SCF 050 Manual  29    Sold and serviced by www PelletKing com   603 424 1183    the Furnace is put back in service   Defective Room Fan  dirty Room Fan  dirty  Return Air Filter  defective Fan Limit Control or possibly a bad Control Board     2  Proof of Fire switch also called the P O F  This senses the temperature rise in the  exhaust system  The switch is    Normally Open    and closes the circuit at 110  degrees  The Furnace will shut down if temperatures above 110 degrees F are not  sensed during start up or if the temperature drops below 110 degrees during  normal operation     3  Vacuum switch also called the Negative pressure switch  When the Furnace 
45. he firebox and under the hopper should be vacuumed  annually     NOTE  UNPLUG THE FURNACE  Remove the access panels of the Furnace  Carefully  clean or vacuum any dust  cobwebs and household dust  Carefully vacuum around the fan  motors  If electrical wires become disconnected call your dealer for service         REMOVE FAN      AND CLEAN  EXHAUST  DUCT                REMOVE CONVECTION  BLOWER AND CLEAN  AND OIL YEARLY                           CLEAN OR REPLACE  FILTER REGULARLY    Figure 24    SCF 050 Manual  43    Sold and serviced by www PelletKing com   603 424 1183    4  The exhaust fan should be removed  may require a new gasket  and cleaned with  compressed air annually  Call dealer for this service  Annual oiling of the motors  is not needed     5  The Convection Blower should be removed and cleaned with compressed air  annually  There are 2 oil ports on the motor     Fall Startup  Prior to lighting the first fire check the outside area around the exhaust and air  intake systems for obstructions  Try all controls to see that they are working prior to lighting  a fire     SAFE OPERATION     1  Disposal of Ashes  Ashes should be placed in a metal container with a tight  fitting lid  The closed container of ashes should be placed on a non combustible  floor or on the ground  well away from all combustible materials  pending final  disposal  If the ashes are disposed of burial in soil or otherwise locally dispersed   they should be retained in the container until all cind
46. imes to keep the tubes clean  If the Tube Scraper feels sticky  and difficult to move  check for the presence of creosote on the tubes  If creosote  is present a damper adjustment may be needed or the Furnace has become  plugged and needs a thorough cleaning  Call Dealer for assistance  To pull the  tube scraper back and forth use the Rod Handle tool shown in Fig  21 on page 40     7  Use a dry paper towel to clean the glass  Quickly open the door and wipe the  glass  The rate of burn will determine how often the window needs cleaning   Prolonged burning at a slow burn rate will result in the need for more frequent  window cleaning  Cooling the Furnace and wiping the window daily with a cloth  or paper towel will normally keep the window from accumulating difficult to  clean residue  Use of a glass cleaner ONLY permitted when the Furnace is cold     CAUTION  Do not slam the door  Do not operate the Furnace with a broken or cracked  glass  Replace only with heat resistant ceramic glass supplied by the manufacturer     There are 2 things to keep an eye on during the cleaning process     1  If the ash pan door or firebox door were left open for more than 90 seconds the  Furnace will go into safety shutdown  You will notice that the Furnace quits augering  corn into the burn pot  Toggle the On Off switch off and back on  This will reset the  board  You will need to use the auger button   3  to manually feed corn into the pot  for a couple of minutes until the program resumes     
47. ing start up  If the Exhaust temperature does not reach 110 degrees F  or  if during use the temperature drops below 110 degrees F  the Furnace will go into     Internal Alarm    and the Auger will quit feeding fuel  Once the Furnace  completes the safety shutdown  the  3 LED will start blinking   See Figure 14 on  Page 25     2  The High Limit switch  This sensor will sense if the unit reaches temperatures  that are too high for normal operation  If this happens the Auger will quit feeding  and the  2 and  3 LED lights will flash simultaneously  See Figure 14 on Page  25     3  The Vacuum switch  For the Furnace to operate correctly the firebox needs to be  sealed  During the first 30 seconds after the Furnace has been turned on the  control board will check to see if the switch senses negative pressure  Vacuum  in  the firebox of the Furnace  If there is no negative pressure  the Furnace will go  into    Safety shutdown    and the  2 LED will start blinking   See Figure 14 on  Page 25        Power Reset     If all the lights on the control board are lit up and the board is  unresponsive you must unplug the Furnace  wait 10 seconds and plug the Furnace back in  to reset the board        Internal Alarm     When the control board becomes unresponsive  the control board is in  Internal Alarm  The control board has sensed one of the Safety sensors  This may cause the  furnace to go out  In some cases  after waiting approximately 45 seconds the furnace will  start responding to t
48. is  turned on the Exhaust fan will create a negative pressure in the firebox  The  control board continually checks to see if Negative Pressure  vacuum  is present  during operation of the Furnace  If the exhaust venting system becomes clogged  or obstructed  the firebox door or ash pan door are left open or the exhaust fan  quits working the control board will go into    Safety shutdown     There is a 60  second window to allow for cleaning the glass and removing the clinker before  then Furnace shuts down  This is sufficient for the Daily Maintenance    The St  Croix corn Furnace has been Safety Tested by an accredited  independent  laboratory     Combustion Air Damper    Do not neglect to adjust the  Combustion Air damper during the  break in period of your new  Furnace  See Figure 15 to the left    Your Furnace is equipped with an  air inlet damper  The purpose of  this damper is to adjust combustion  airflow to match the characteristic  of each specific air inlet and  chimney configuration  The  damper is preset at the factory with  a setscrew  The damper will most  likely only need a small adjustment  during the break in period  To  know if the damper needs to be  adjusted you should learn to  recognize how Corn or Pellets burn  in this furnace system           AIR  DAMPER    Figure 15    SCF 050 Manual  30    Sold and serviced by www PelletKing com   603 424 1183    When burning corn the burn pot should be    BALANCED     This means the corn that is  being augered into
49. k for 90   of the most common installations   Long horizontal runs might need the damper opened  Tall vertical runs might need the  damper to be closed a little  etc  To adjust the damper  use the setscrew to make the  adjustments  To make an adjustment turn the screw 1   2 turn clockwise to open the damper  or   2 turn counter clockwise to close the damper  Turning the setscrew counterclockwise  will not move the damper  so remember to use the damper handle to bring the damper up  to the screw  After making an adjustment wait at least 15 minutes to see how the burn pot  reacts to the change     SCF 050 Manual  32    Sold and serviced by www PelletKing com   603 424 1183    Terminology used when burning Corn    1  Balanced burn pot  This means the corn rapidly turns into red hot coals once it is  in the burn pot     2  Lag time  This is the time it takes for the corn to start burning and the burn pot to  become balanced  Corn will tend to stick together in a clump in the burn pot if the  corn feeds in faster than it   s burning     3  Overloaded burn pot  Once the corn has formed a clump in the burn pot the pot  will overload and slowly the fire will die out     Procedure for adjusting the damper when burning Corn     a  Once the Furnace is burning  leave the control board on the  1 setting for Lo an  hour  This will allow the Furnace to warm up before any adjustments to the  damper are made  After 1   2 an hour look in the burn pot to see if the burn pot is  balanced  Unless
50. me noticeable  If this build up is noticed  close the damper 50  to  start out with  and place the setscrew against the damper blade  Use this as the  starting point to make additional adjustments with the setscrew  Some build up is  normal and may be removed during the maintenance schedule     Once the adjustment has been made for the pilot setting slowly advance the Furnace  to the  5 Heat Level and observe the flame  If black soot  wipes off easily  builds up  on the glass and black smoke is visible at the tips of the flames turn the setscrew one  Y turn counterclockwise and bring the damper blade up against the screw  Wait 5      10 minutes before attempting another adjustment  An occasional wisp of black smoke  is normal every now and then     SCF 050 Manual  34    Sold and serviced by www PelletKing com   603 424 1183    Thermostat Control    Pilot Settings    The Furnace may be controlled with a thermostat to help maintain a more constant  temperature  A Corn or Pellet furnace will be a little slower in reacting to a thermostat than  the typical Gas  Electric or Oil fired furnace  With this in mind we have incorporated 3 Pilot  settings on the control board  See Point 5 on Page 26   This will allow the heat output during  the pilot stage to be matched to the size of the home  A larger home will require more heat  than a small one  Keep in mind that the furnace is constantly producing some heat that helps  heat the home while the furnace is in pilot mode  If the home se
51. nections must be sealed with RTV silicone to assure a gas tight seal   Any leaks into a confined area caused by faulty installation or improper operation of the furnace  could produce dizziness  nausea and in extreme cases  death     8  Under certain circumstances an outside source of combustion air may be needed and is required on  all mobile home installations  If room air is used to supply combustion air  room air starvation   operation of exhaust fans and icing of air vents can adversely affect proper furnace operation     9  Smoke detectors  installed in the same general area as the Furnace  may be activated if the Furnace  door is left open and smoke is allowed to enter the area     CAUTION  NEVER ADD FIRE STARTER TO A HOT FURNACE   CAUTION   Hot Surfaces      Keep Children away     Do not touch during Operation     SCF 050 Manual  24    Sold and serviced by www PelletKing com   603 424 1183    Control Board Features    The Control Board controls all functions of  the furnace by monitoring sensors that are in        the system  These sensors serve 2 purposes     ALWAYS DISCONNECT APPLIANCE    POWER BEFORE SERVICING  a  General Operation of the Furnace     THERMOSTAT MANUAL    b  Safety Features  to shut the unit  down in the event the sensors detect  a problem in the unit     The Control Board also has Diagnostic  Capabilities to help in diagnosing 3 areas in  the furnace  These areas are     1  High Temperature Limit   2  Proof of Fire Sensor  3  Vacuum in the Firebox 
52. ney flue serving another appliance     BUILDING PERMIT  Contact the local building officials to obtain a permit and information on any local installation  restrictions and inspection requirements     DEFINITION OF    FURNACE       The word    Furnace    as used in this manual is interpreted to mean a corn or wood pellet burning  Add On Furnace  This model is not intended as the sole source of heat     SAFETY TESTING    The furnace has been independently tested and listed by Warnock Hersey Laboratories in  accordance with the proposed ASTM Standards and the applicable portions of UL 1482 and  ULC 5627 B366 2  and Oregon Administrative Rules 814 23 901 through 814 23  909  stating  requirements for installation as a shop heater or Add On Furnace and for mobile home  installations  The safety listing label is located on the inside of the removable front panel of the  unit  Please refer to label for pertinent information     DISCLAIMER OF WARRANTY    Since Even Temp Company has no control over the installation of the furnace  Even Temp  Company grants no warranty  implied or stated  for the installation of the furnace and assumes  no responsibility for any special  incidental or consequential damages     MANUFACTURED BY   Even Temp Inc    Hwy 34  Waco  NE  68467    SCF 050 Manual  4    BEFORE INSTALLATION THOROUGHLY  READ AND UNDERSTAND THIS MANUAL    SAFETY NOTICE    PLEASE READ THE ENTIRE MANUAL BEFORE INSTALLING AND USING YOUR NEW FURNACE  FAILURE  TO FOLLOW INSTRUCTIONS MAY R
53. nse P O F  it will repeat the last step and continue feeding  corn or pellets on the  1 setting for 5 minutes     e  The board will check for P O F  again  If the board still fails to sense the Proof of  Fire switch the Furnace will go into    Safety shutdown     See section on    Diagnostic Features on page 27      If this happens  repeat steps 1 through 4 from the section on Lighting Your Furnace     Shutting The Furnace Off  Refer to Figure 14     1  Press the On Off switch  2  once  the lights will go off and the fire will go out in a  few minutes  The board essentially goes into    Safety shutdown        2  As long as the temperature within the Furnace remains above 110  F the Combustion   Exhaust  Fan will continue to run  When the P O F  switch drops out the Combustion fan    will run for another 10 minutes and finally shut down completely     4  NEVER unplug the Furnace to shut it off  Doing so may cause a  significant amount of smoke to enter the room     Diagnostic Features of the Control Board    The  2 LED and the  3 LED lights on the LED Light bar as show in figure14 will flash  to give a diagnostic code to help in diagnosing problems that may occur     These conditions fall into 2 categories   a  Heat related issues     b  Vacuum related issues     SCF 050 Manual  28    Sold and serviced by www PelletKing com   603 424 1183    The Diagnostic Lights flash as follows     1  The Proof of Fire switch  This switch will sense the temperature of the Exhaust  rising dur
54. o many changes in a  short period of time will not             Y A d allow for an accurate adjustment     EXAMPLES OF DAMPER SETTINGS                                                    Figure 16    SCF 050 Manual  31    Sold and serviced by www PelletKing com   603 424 1183    If you experience problems adjusting the Furnace during the Break In Period   contact your dealer  The figure below may be used to gage the approximate damper  setting when making an adjustment  Some chimney systems will fall outside the norm   for example  a chimney with excessive draft or one with a long horizontal run  In dealing  with technical support  the terminology listed in figure 17 may be used to clarify where  your damper needs to be set     5    mmm        3 O Clock Position   lt p Fully Open       4 O Clock Position  Approximately  50  closed                  O Clock Position  Approximately    6 O Clock Position 80  Closed  Fully Closed  Figure 17    Damper Adjustment Procedure     Once the Furnace has been lit for the first time  the damper will need to be adjusted  The  process is different for Corn than Pellets  This may take some time  so please be patient  during this process  This Damper Adjustment process only needs to be done once  After  the damper has been adjusted to the unique installation in your home  the control board  will do the rest     As was Stated earlier there is a setscrew in the damper and the damper has been preset at  the factory  This setting will most likely wor
55. rown Pin Out on  Not Used Molex Connector    80P301 38    Figure 25    The Electrical Rating of this furnace is  120 Volt  60 Hz  4 AMP  The minimum  recommended circuit is 15 Amp  A dedicated circuit for the furnace is recommended     SCF 050 Manual  45    Sold and serviced by www PelletKing com   603 424 1183    CAUTION  The electrical components of the Furnace are not owner serviceable  Call your  dealer for proper diagnosis of electrical problems and service to those components     Electrical Layout       Figure 26  l  Fan Limit Control 6  Control Board  Ze Convection Blower Ta Thermostat Wiring Terminal  3  Combustion Blower 8  Wiring Terminal Block  Inside Cabinet   4  Proof of Fire Switch 9  2 Speed Blower Rocker Switch  5  Vacuum Switch 10  Auger Motor    SCF 050 Manual  46    Sold and serviced by www PelletKing com   603 424 1183    Additional Canadian Installation requirements     1     The fans of this Furnace may cause a negative pressure area in the room where this  Furnace is installed  If the Furnace is not connected to a Return Air duct system in the  house  provision should be made to provide make up air to the unit  It is  recommended to provide opening equal to 120 Square inches for Return Air to the  Furnace room    Outside Combustion Air may be needed if     a     b     The unit does not vent steadily  smell  experiences smoke rollout  burns poorly  or  back drafts whether or not there is combustion present    Any of the symptoms listed above are alleviat
56. rticles of fly  ash  The fly ash will collect in the exhaust vent and restrict the flow of the flue gases   Judge the frequency of cleaning by checking the amount of ash that accumulates in  the elbows or tee   s of the exhaust system  Ask the dealer for suggested frequency of  cleaning  equipment needed and procedures for cleaning  Check the Exhaust system  and Ash Traps at least once every two months during the heating season     6  Gaskets  Periodically inspect the condition of the rope gasket around the door   window and ash door  Replace as needed     7  Air Filter  Check the Return Air Filters at least once a month and replace when  needed  The size of the filter is 1    X 12    X 25        SCF 050 Manual  42    Sold and serviced by www PelletKing com   603 424 1183    Many dealers offer a Service Contract that will cover Yearly Maintenance  Contact  your St  Croix Dealer for assistance in maintaining your Furnace in top condition     Yearly Maintenance    Yearly maintenance is designed to assure safe operation  prolong the life of the Furnace  and help preserve its aesthetic appeal     1  Spring Shutdown  After the last burn in the spring  cool the Furnace  Remove all  corn from the hopper and the auger  Thoroughly clean the burn pot  burn pot box   ash pan and ash traps behind the ash pan   To locate the ash traps see figure 4     2  The exhaust system should be thoroughly cleaned at least annually  Call your  dealer for this service     3  The motor fan area behind t
57. rying to keep the glass cleaner when  burning on the  1 setting  The more fuel on  low will usually mean less build up on the  glass        Figure 28    SCF 050 Manual  52    Sold and serviced by www PelletKing com   603 424 1183    12  How do I adjust the draft for the Pilot settings   1 setting      Not all fuel burns at the same rate  The moisture content of corn  greatly influences how it burns  Burning Pellets requires  adjustments to the low burn to prevent Creosote from forming   Following is a description of the function of the Fan Trim button     ALWAYS DISCONNECT APPLIANCE  POWER BEFORE SERVICING    THERMOSTAT MANUAL    z  ZS    The Draft Trim button will adjust the combustion fan voltages on  the  1 pilot setting  There are 2 adjustments that can be made  To  adjust the Combustion fan voltages  push the Draft Trim button  and you will notice all of the LED lights on the light bar flash  once     The first adjustment  Lights flash once  will lower the combustion  fan voltages approximately 5 volts  Using this draft adjustment  will be common when burning Pellets     The second adjustment  Lights flash twice  will raise the voltage  approximately 5 volts  This may be used in a venting situation that  is restrictive  a long horizontal run or a venting system with  excessive elbows for instance        Figure 29  13  Is there a Cycle Time adjustment on the Control Board for Pellets and Corn     Located on the back of the control board are 4 Jumper Pins that control the 
58. system allows the corn to be burned  efficiently and completely in a relatively small burn pot  Very little residue ends up in the  ash pan     When burning Pellets in the standard pot in the furnace  ash will build up in a similar manner  as the clinker does when burning corn  The pot is maintained the same way as described in  the following section covering the removal of the clinker  The time it takes the pot to fill up  with ash depends on the quality of the pellets and on the quantity of pellets burned  The  interval of dumping the ash is directly related to the rate of burn  A Furnace running on a  thermostat cycling at a moderate rate will generally last approximately 24 hours  However if    SCF 050 Manual  35    Sold and serviced by www PelletKing com   603 424 1183    the Furnace is running continuously on the highest setting the Ash will need dumping every  10 to 12 hours  It is the responsibility of the Owner User of the furnace to determine the  frequency of dumping the Ash  based on the rate of burn and the quality of pellets  ash  content      Clinker Ash Removal     Once a clinker ash has formed in the burn pot  it must be removed or the Furnace will go  out  The St  Croix Burn system is designed to remove the clinker ash without loosing the  fire in the burn pot  It is a 3 part system     1  The coal rake  This is a    fork    shaped device that will allow the Furnace operator  to    shave    the burning coals off the top of the clinker  separating the 2 areas
59. ts above the default setting  Pushing the button a 3  time will  reset the voltage to the default setting  This adjustment is available to fine tune the  1  Heat Level draft setting  This would only be used in the case the furnace was hooked up  to a tall Vertical Chimney  to decrease the draft if needed  or if it was connected to a  Chimney with a long Horizontal run  to increase the draft if needed      5  The Feed Trim button  5  will allow the Fuel feed rate to be adjusted on Heat Level 1  only  Heat Level 1 should be seen as the Pilot setting of the furnace  when operating on a  Thermostat  Pushing the Feed Trim button  5  will switch between the different  adjustments  Heat Level one can be adjusted in the following ways     a  The first LED only indicates the Normal  1 setting   2 5 second on time   This is  the highest Pilot setting and may be used when heating a larger size home     b  The first and fourth LED lights indicate the  1 Low setting   2 0 second on time   This is the medium Pilot setting and may be used when heating a medium size  home where less heat is needed when the unit is running in pilot mode     c  The first and fifth LED lights indicate the  1 High setting   1 50 second on time   This is the lowest Pilot setting and may be used when heating a small size home  where minimal heat is needed when the unit is running in pilot mode     The adjustments described in points 4 and 5 remain in effect as long as the unit is  plugged in  If the unit gets unpl
60. ugged or if there is a power failure the settings are  lost and the adjustments would need to be reset     Pre Lighting Instructions    When lighting your Furnace for the first time or any time you have run out of corn or  pellets fill the hopper  The auger tube will be empty and it helps to hold the    Auger  Button    in until you hear corn or pellets drop into the burn pot  Corn is fed from the  hopper to the burn pot by a high torque motor that is capable of doing SERIOUS harm to  fingers  Keep fingers and other objects away from the auger     SCF 050 Manual  26    Sold and serviced by www PelletKing com   603 424 1183    WARNING    Risk of Fire    Do not operate with the Firebox door or Ash Removal doors open   Do not store Fuel or other Combustible material within marked Installation  Clearances    Inspect and Clean Flues and Chimneys regularly     Danger  Risk Of Fire or Explosion   Do not burn Garbage  Gasoline  Drain Oil or other Flammable Liquids     WARNING  The auger can start at any time while the Furnace is running    CAUTION  The Coal Rake must be pulled out and the Slide Out Bottom pushed in  to Operate the Furnace   See Furnace layout on page 1     REMEMBER  If burning pellets in the standard Burn pot  be sure to remove the  side shields of the burn pot first     Lighting Your Furnace   1  Make sure there is Corn or Pellets in the hopper     2  Add one cup of Pellets to the burn pot  not more and not less   Do not try to start  your Furnace with corn  Add a g
61. umulate on a  regular basis  Once a month or sooner  depending on the quality of fuel being used   See Figure 23 on Page 42     Figure 23 shows how the baffle is removed from the Furnace  Clean the baffle on a  regular basis  Frequency of cleaning depends on amount of fuel being burnt and the  quality of the pellets  Fuel with low ash content is recommended  Failure to clean the  baffle can cause the Furnace to become plugged with fly ash     SCF 050 Manual  41    Sold and serviced by www PelletKing com   603 424 1183       Baffle Removal                                          STEP 2  ALLOW THE 2 SCREWS  TO DROP OUT OF THE  KEYHOLE SLOTS  To remove the baffle  lift the back of the  baffle up to clear the inner back of the  Furnace and slide towards the front of the  Furnace  The baffle will slide out of the  STEP 1 keyhole slots and drop down  When  SIDE VIEW putting the baffle back in the Furnace   OF BAFFLE    make sure the screws are in the keyhole    slots and the back of the baffle is lifted  up over the inner back to keep the  LIFT UP THE Baffle locked in place   BACK SIDE OF  BAFFLE  amp  SLIDE  TOWARDS FRONT  OF FURNACE Figure 23                   5  Exhaust System  Periodic cleaning of the exhaust system is required  Under certain  conditions chimneys may plug up rapidly  Dirty High moisture content Corn and poor  installations require more frequent chimney cleanings  See Page 20    Preventing  Chimney Fires     The products of combustion will also contain small pa
62. vailable that offers less maintenance  If the furnace is used primarily  as a pellet furnace it is recommended to replace the standard burn pot with this Retro Fit  Pellet pot  See figure 13 on page 23 for details     SCF 050 Manual  22    Sold and serviced by www PelletKing com   603 424 1183    STEP4    LIFT POT UP  STEP 1        _      os TO REMOVE  ek  nl ON  neg FURNACE  REMOVE       STEP     LOOSEN SCREW  TWO TURNS          _    STEP 3      PULL COAL RAKE POD AA OZ  TOWARDS THE FRONT Se     ae     OF THE STOVE UNTIL  IT STOPS Le  s    x   h THE SLIDE OUT BOTTOM  STEP 5 REMAINS IN THE STOVE  AFTER REMOVING THE BURN POT AND SHOULD BE CLOSED  UNSCREW THE COAL RAKE ROD WHILE USING THE NEW  FROM THE COAL RAKE AND REMOVE RETRO FIT PELLET POT  IT FROM THE FURNACE  REACH INSIDE  THE POT WRAP AREA AND REMOVE  THE COAL RAKE    RETRO FIT POT  INSTALLATION  PART   80P53831R    INSERT THE NEW POT INTO   THE BURN POT AREA OF THE  FURNACE  PLACE THE POT  SCRAPER INTO THE POT AS  SHOWN  SLIDE THE SCRAPER  ROD THROUGH THE HOLE IN  THE FRONT OF THE FURNACE  AND SCREW INTO POT SCRAPER       Figure 13    The Maintenance of this pot consists of using the pot scraper to clean the grate in the bottom of the pot  when needed  The pot clinkering shut over a short period of time would be considered unusual and an  adjustment will need to be made to the draft or the cycle time of the board may need to be lengthened   For information on adjusting the Cycle Time see point 13 on page 53  If you have
63. when needed  The Fan Limit Control is also located on the left side     Supply Air  The SC 050 Furnace may be connected to a gas  oil or Electric Heat pump system  with existing duct work     Return Air  The furnace does not need to be connected directly to the existing cold air return  system  but it is recommended     Venting  The location should be as close as possible to an outside wall for venting purposes  The  furnace requires 4    PL Vent pipe  The shortest vent system with minimal elbows is the best     SCF 050 Manual  7    Sold and serviced by www PelletKing com   603 424 1183    Clearances  amp  Access for Service  amp  Maintenance    LE    MOSSY    E    i    A  1   j  f  j         LIL       Figure 3  FLOOR PROTECTION   The furnace should be installed on a non combustible surface  extending 16    in front of the unit   LEFT SIDE     Minimum clearance to combustibles on the right side of the furnace is 2     ACCESS FOR SERVICE AND MAINTENANCE   The remaining clearances shown above    are required to allow access to components during service and maintenance     SCF 050 Manual  8    Sold and serviced by www PelletKing com   603 424 1183    Caution    INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER OR  DEALER     ADHERE TO ALL CLEARANCES SPECIFIED BY THE MANUFACTURER OF THE  VENTING SYSTEM USED     ADHERE TO ALL CLEARANCES SPECIFIED IN THE INSTALLATION  INSTRUCTIONS OF THIS FURNACE     THIS FURNACE USES A POSITIVE PRESSURE VENTING SYSTEM  DO NOT  INSTALL A FLU
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
QP019 Manual  GXV670 Suplemento    PROGRAMME - Théâtre de Grasse  DROIT SOCIAL  Sony PCWA-C100 User's Manual  Consulter le document en PDF - Bureau de la sécurité des  INFORMATION, INSTRUCTION & USER MANUAL  HoMedics HHP-250-CA Downloadable Instruction Book  catalogo_residenziale    Copyright © All rights reserved. 
   Failed to retrieve file