Contents

1. CFC LED red LED OFF CFC may be removed reset button CFC slot ATTENTION Never unscrew and dismount the inner metallized cover while the XL Web is powered Danger of short circuiting LON eeeeaee senesan eenen aeaea o 7 oo000 Oloooo JUDO O paz o o fees o LonWorks interface 8 position unshielded RJ45 connector jack Ethernet interface 8 position USB interface RS232C serial interface port 3 shielded RJ45 connector jack CAT5 lower terminal block removable terminals 1 thru 6 upper terminal block removable terminals 7 thru 12 EN1B 0256GE51 R0909 standard male 9 position sub D RS232C serial interface port 2 standard male 9 position sub D RS232C serial interface port 1 standard male 9 position sub D Fig 1 Hardware features top and front view EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS Terminal Blocks The Excel Web features two rows of removable terminal blocks located at the front left hand side see Fig 1 on page 2 for the connection of cables to the two binary outputs and the binary inpu
2. BINARY INPUT AND OUTPUTS Wiring When wiring the two binary outputs and the binary input use a min size of 20 AWG 0 5 mm and a maximum of 14 AWG 2 5 mm The max length of all cables is 400 m Two wires with a total thickness of 14 AWG can be twisted together and connected using a wire nut include a pigtail with this wire group and attach the pigtail to the individual terminal block Deviations from this rule can result in improper electrical contact Local wiring codes may take precedence over this recommendation EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS Binary Input The Excel Web controller s binary input a normally open contact is not galvanically isolated It is suitable for con nection with signalling via 0 36 Vdc voltage or external resistor or dry contact Table 6 Binary input specifications resistance at A voltage a purpose assigned to oe binary con binary input by user using bina tact ext info CARE 7 in eN resistor or p dry contact high level detection i e 3 8 to gt 10 kO or voltage at detection that binary input 36 Vde open input open ter has opened P P minals 5 V low level detection i e lt 400kQor Curent from p h 0 to 0 8 P shorted detection that binary input when binary a Vde terminals has closed input shorted 2 mA The binary input is protected against miswiring Specifically it is protected against voltages of up to 29 Vac
3. slots for DIN rails center to center distance 100 3 mm as a o A HOY fastening LOH apor ala POHD Fig 9 Housing base view from below The Excel Web can be mounted onto DIN rails as follows refer also to Fig 10 1 Hang the upper slot onto the upper DIN rail 2 Swing the unit down until it is flush with the lower DIN rail 3 Slide the fastening plate and corresponding screw in the oval hole up against and behind the bottom edge of the lower DIN rail and screw it firmly into place 4 If necessary the swivel cover can be locked by inserting a small string lock lead seal or screw into either one of the two openings provided The unit is dismounted by loosening the fastening plate and lifting the unit out of place 100 Al lo fastening ky Plate i c Fig 10 Mounting the Excel Web on to two DIN rails Wall Panel Mounting Dismounting The Excel Web can be mounted on walls or in panels in any desired orientation However mounting the Excel Web upside down on ceilings should be avoided insofar as the swivel cover would then swing open EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS y l 4 4 I 0 3 190 Se 141 5 0 3 1 36 5 gt N gt Q5 0 3 e 29 220 0 3 429 gt
4. Excel Web controller rather than having your PC and the Excel Web controller both connected to a LAN In any case your PC s IP address must match the Excel Web controller s default IP address subnet We recommend using 192 168 253 21 and Network Mask 255 255 255 0 NOTE In order to subsequently operate on your standard Ethernet network again you will have to change the configuration back to the previous settings Engineering Downloading and commissioning Procedure The user must first create on a Windows compatible platform using CARE 7 the application data for the Excel Web controller Before downloading the application it can be tested using the simulator called LIVE CARE OFFLINE 2 The user then downloads from the Windows compatible platform the application data created in step 1 into the Excel Web controller typically via the USB interface After the very first set up the Excel Web controller gets the final IP address which you assigned offline during the engineering process using CARE You can use this final IP address for further application firmware downloads provided all of the Excel Web controllers are powered up 3 Typically testing and debugging using the LIVE CARE functionality of CARE 7 is then performed in a simulated environment i e with the Excel Web controller connected to a test board EN1B 0256GE51 R0909 EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS The Excel Web is th
5. is 278 4 Fig 11 Drilling template view from above Swivel Cover Lock The swivel cover can be locked by inserting a small string lock lead seal or screw into either one of the two openings provided see Fig 10 POWER SUPPLY Wiring NOTE All wiring must comply with applicable electrical standards and ordinances Refer to job or manu facturers drawings for details Local wiring guide lines e g VDE 0100 may take precedence over recommendations provided in these installation instructions e Power supply 24 Vac 20 50 or 60 Hz or 24 38 Vdc galvanically isolated Power consumption max 10 VA USB unloaded Excel Web and 24 Vac field devices can obtain their power from the same transformer e Several Excel Web controllers can share a single common transformer In this case you must ensure that terminal 1 of each of the Excel Web controllers is connected to 24 V and terminal 2 is connected to the minus pole optionally terminal 2 can additionally be connected to the earth see also Fig 12 e The power supply LED see section Power Supply LED on page 5 indicates whether power is being supplied e In the event you wish to connect one of the 24 Vac pins to the earth ground not recommended connect it via terminal 2 of the lower removable terminal plug see also Fig 12 Table 3 Cable sizing use only copper cables type of signal lt 300 ft lt 550 ft lt 1300 ft 100 m 1
6. transfer of data onto the card NOTE Upon inserting a CF into a running Excel Web the CF will be reformatted if necessary Specifically If the CF already has the format EXT3 it will not be formatted otherwise it will be formatted and any data already present on it will be irretrievably lost USB Interface Downloads The Excel Web is equipped with a USB port into which a standard USB type A connector can be inserted This USB interface is the recommended interface for downloading applications and firmware via CARE 7 and for operating the Excel Web via Internet Browser in parallel to an Ethernet connection The following USB host networking adapter has EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS been approved BELKIN DIRECT CONNECT BELKIN order no F5U104 or F5U104G at www belkin com Fig 7 USB interface Alternatively either of the following three adapters can also be used SMC 2208USB ETH SMC 2209USB ETH or D Link DUB E100 See section Option 1 USB recommended on page 9 LEDs and Buttons LonWorks Service LED and Service Button The Excel Web is equipped with a LoNWoRrks service LED and a LONWORKs service button together marked LON see also Fig 1 on page 2 They are used for commissioning the Excel Web and for troubleshooting LonWorks Service Button When the LonWoRks service button is pressed the service pin message is broadcast on the LoNWoRrks network and all LONWORKS tools currently co
7. 70 m 400 m 24 Vac power 16 AWG 14 AWG supply 1 5 mm 2 5 mm low voltage 14 18 AWG 2 5 0 75 mm 0 10 V sensors totalizers binary inputs 0 10 V signals for actuators etc Power is supplied via terminals 1 and 2 of the lower re movable terminal plug The removable terminal plug permits individual Excel Web controllers to be disconnected from the power supply without disturbing the operation of other devices powered by the same source NOTE Do not reverse the polarity of the power connection cables and avoid ground loops i e avoid connecting one field device to several controllers as this may result in short circuiting Transformer Data Table 4 1450 series transformers data Die secondary side 120 Vac 24 Vac 50 VA 2 x 24 Vac 40 VA and 002 120 Vac 100 VA from separate transformer 24 Vac 100 VA and 24 Vdc 003 120 Vac 600 mA 240 220 Vac 24 Vac 50 VA 2 x 24 Vac 40 VA and 240 220 Vac 100 VA from separate transformer 24 Vac 100 VA and 24 Vdc 240 220 Vac 600 mA Table 5 Overview of CRT Series AC DC current max AC current 005 max DC current 0 5 A 500 mA 1 3 A 1300 mA 2 5 A 2500 mA primary voltage 230 Vac Excel Web 120 Vac EN controller transformer e NOT NI RECOMMENDED Fig 12 Connection of Excel Web EN1B 0256GE51 R0909 EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS Lightning Protection Please contact your loca
8. Honeywell Excel Web XL1000B C HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION INSTRUCTIONS TABLE OF CONTENTS Overview of Hard Ware iii A a a id a diana 2 Terminal BlockS oz tdo TI E Mona te ccs 3 LonWorks Interface ooooimcicci nic a E Ed RRA 3 Ethernet Interface aseinani an a a tiene 3 RS232C Serial Interface POMS Annina a ii Renate ete 4 CF Port LED Request Button and Slot ccccccccccceceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeseseseseseeeeeseeeseeeees 4 USBilnterface DOWNIOAS 25 22 sacs EET A lnea celia E T 4 LEDs aNd BUUONS A iii 5 Power Supply LE Dives nnk Maken an han Man die ev iawn cea enn ees 5 Binary Input terminals 344 LE Dice ccc dana Se sone bees Saban eh e a ad 5 Binary Output terminals 7 8 LED ooo ride 5 Binary Output terminals 9 10 LED coin iaa 5 Ethemet LEDS cardio 5 LEDS MIO li A dla bien heed died ier dined ene 5 Reset Button aris NN 6 MOU NG oso eco ao coo E A T 6 Before Installation isnin iaa ete A a 6 DIMENSIONS ate opaca 6 POWER SUPpIY sii ice eter eee cece ct bie eater cide Sah caters A tae Lecter cht de a ac a rennet tae Seva dave a a 7 WINING nee eee A oie A ee a een ees 7 Transformer Dita o a ct ito tadas 7 Lightni g Protection ii A da 8 RINFARU 24 ua a lies 8 LonWorks COMMUNICATIONS 0 a a a dia 8 General Informatica ida 8 Connecting to the LONWORKS Network oooooccccconocccccococcnononcnonano nono nono nnnn ntun nc nano nn rn nn r
9. ction as needed or per manently of a portable platform which must host an Internet Explorer compatible internet browser for the purpose of operating the Excel Web This requires the establishment of a remote connection via RS232 on the PC plus a null modem cable RS232 cross over cable Because it offers a much higher speed we recommend instead using the USB interface Port 3 Modem Interface Port 3 is intended for the permanent connection if needed of a modem e g an analog modem an ISDN adapter or a GSM adapter for the purpose of communicating with other front ends e g 3 party BACnet front ends via modem EN1B 0256GE51 R0909 CF Port LED Request Button and Slot The Excel Web features a slot type I socket into which type ll Compact Flash Cards CF cards but also type I CF cards can be inserted Inserting a CF card allows the Excel Web controller s internal memory for storing trend records to be increased CF cards having a variety of storage sizes are available from wholesale and retailer dealers NOTE Insert the CF card carefully and make sure that it has the proper orientation see Fig 6 narrow notch 98 98 98 90 98 98 98 98 98 98 OQ 98 38 Fig 6 Inserting a CF card into the slot NOTE Before removing a CF card always first push the CF request button and wait usually just a few seconds until the CF LED turns OFF Violating this rule could interrupt the
10. ecifically an RJ45 jack permitting communication on LONWORKs networks LonWorks Fig 3 LonWorks interface RJ45 jack There are two methods of connecting the Excel Web to the LonWorks networks both or either connection method can be used e via terminals 5 6 and 11 12 of the terminal blocks see Fig 1 on page 2 and or e via the corresponding jack located to the right of the terminal blocks see Fig 3 See also section LonWorks Service LED and Service Button on page 5 for details on the corresponding LONWoRKS service LED and one LONWoRKS service button Ethernet Interface The Excel Web is equipped with a 10 100 Mbaud Ethernet interface specifically an RJ45 jack permitting com munication as per IEEEC 802 3 on BACnet IP networks i Fig 4 Ethernet interface 8 2 WARNING Risk of equipment damage gt If the Ethernet Interface is connected thus earth grounding the Excel Web ensure that the Excel Web is not also earth grounded gt If an additional earth grounding is indispensable ensure that the Excel Web is earth grounded only via terminal 2 of the lower removable terminal plug see also Fig 12 EN1B 0256GE51 RO909 EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS Via the Ethernet Interface the user sitting at a platform hosting EBI can e g view and edit the time programs trend values etc of the other devices in the BACnet IP network The RJ45 jack conforms to
11. ed twisted pair solid conductor wire When possible use Honeywell AK3781 AK3782 AK3791 or AK3792 cable US part numbers See Excel 50 5000 LonWorks Mechanisms ENOB 0270GE51 for details including maximum lengths Use wire with a minimum size of 20 AWG 0 5 mm and a maximum size of 14 AWG 2 5 mm EN1B 0256GE51 R0909 xL Web termination Fig 13 Connection to LonWorks network and termination module here daisy chain network configuration The Excel Web controller can be connected to the LONWORKS network via terminals 5 6 and 11 12 of the removable terminal plug or via the LONWoRKSs jack see also section LonWorks Interface on page 3 This permits individual Excel Web controllers to be connected disconnected from the LonWorks network without disturbing the operation of other devices Depending upon the chosen network configuration one or two terminations may be required Two different LonWorks termination modules are available e LONWonRKS termination module order no 209541B e LONWoRKS connection termination module mountable on DIN rails and in fuse boxes order no XAL Term 0 Honeywell XAL Term 1 shield 0 plug in Mole termination jumper y FIT LPT Bus ETT LPT Free Park Position removable Screw type 3 pole terminal block Fig 14 LONWorRKS connection and termination module
12. en physically installed in the wall wiring cabinet etc In the course of doing this the Excel Web controller s terminal blocks are wired and the corresponding RJ45 jacks are inserted into its LONWORKS interface and the Ethernet interface If desired i e if the Excel Web controller is to later communicate by modem too the corresponding jack can be inserted into the corresponding RS232C interface namely Port 3 The user must now commission the Excel Web and the field devices to which it is connected via LONWoRKS i e their NV s must be bound and configured This is per formed with the same platform hosting CARE 7 as in step 3 via any LONWoRKS access e g terminals 5 6 and 11 12 or via the RJ45 LONWonrks jack Typically the user again tests and debugs the Excel Web controller this time in its actual working environment Testing and debugging is again performed using the LIVE CARE functionality of CARE 7 Optionally testing can be performed using an Internet browser on a laptop or PC with 800x600 resolution or higher The tester debugger can now perform audio visual checking to see if the field devices are responding as predicted desired 7 Engineering installation and commissioning are now complete The corresponding jack can now be removed from the USB port The Excel Web controller begins operation Protocolling In the context of the Excel Web controller protocolling means creating a log of the
13. g the Excel Web using the reset button Please contact Honeywell if this does not solve the problem Ethernet LEDs The Excel Web is equipped with two Ethernet LEDs see also Fig 1 on page 2 Ethernet Link LED The LED marked indicates the Ethernet link s status Specifically it is lit whenever an Ethernet jack has been inserted into the corresponding port and the software has established the Ethernet link It is dark when the link has been disabled Ethernet Activity LED The LED marked lt gt indicates whether or not the Ethernet link is currently active Specifically when it flashes this means that signals are being transmitted received on the Ethernet network when it is dark no messages are being transmitted received LEDs L1 and L2 At present these LED s are not in use EN1B 0256GE51 R0909 EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS Reset Button The reset button can be pressed only using a long thin tool e g a screwdriver Pressing it reboots the Excel Web controller s operating system and restarts the application MOUNTING Before Installation IMPORTANT To allow the evaporation of any condensation resulting from low shipping storage temperatures keep the controller at room temperature for at least 24 h before applying power US requirement only This device must be installed in a UL listed enclosure offering adequate space to maintain the segregation of line volta
14. ge field wiring and Class 2 field wiring In order to meet the criteria for CE certification the XL1000 controller must be mounted inside an electrical panel Dimensions _ _ ALLOW 30 mm CLEARANCE FOR OPENING SWIVEL COVER 7 N 190 Mo oF BO HA E t O E BG EC E LON _ 101011 191012 _ 91013 E 8 P OE AE 4 q N i 278 7 0 6 60 6 ALLOW 30 mm CLEARANCE FOR ALL ACCESSING INTERFACES 4 4 0 3 e o o co E a P i m S o A i ie 15 TE 12 1 7 t 290 0 3 5 0 3 Fig 8 Dimensions in mm The Excel Web has the following dimensions W x L x H 278 x 190 x 61 mm Its housing conforms to IP20 Its pollution degree 2 makes it suitable for use in residential controls commercial controls in a clean environment or non safety controls for installation on or in appliances The Excel Web is suitable for mounting on a standard rail DIN EN 50022 35 x 7 5 on walls or in panels as well as for installation in appropriately sized wiring cabinets or fuse boxes Allow sufficient clearance approx 30 mm to access the interfaces and to open the swivel cover see Fig 8 EN1B 0256GE51 R0909 DIN Rail Mounting Dismounting 4 o 1 jam o A
15. l Honeywell representative for information on lightning protection RIN APU24 The RIN APU24 Uninterruptable Power Supply can be directly wired to an Excel Web See RIN APU24 Uninterruptable Power Supply Mounting Instructions ENOB 0382GE51 for a detailed wiring diagram LONWORKS COMMUNICATIONS General Information The Excel Web controller is equipped with a free topology transceiver FTT10A or FT X1 for communication at a data transmission rate of 78 Kbaud on LONWoRKS networks using the LonTalk protocol The LONWorks network is insensitive to polarity eliminating the possibility of installation errors due to miswiring Different network configurations daisy chain loop and star configurations or any combination thereof are possible see also Excel 50 500 LonWorks Mechanisms Interface Description ENOB 0270GE51 Connecting to the LonWorks Network IMPORTANT Do not bundle wires carrying field device signals or LonWorks communications together with high voltage power supply or relay cables Specifically maintain a min separation of 3 inches 76 mm between such cables Local wiring codes may take precedence over this recommendation IMPORTANT Try to avoid installing in areas of high electromagnetic noise EMI Cable Types The unit must be wired to the LONWorks network using either e level IV 22 AWG Belden part number 90220150 or e plenum rated level IV 22 AWG Belden part number 9H2201504 non shield
16. nnected to the LONWORKS network will receive this message LonWorks Service LED The LONWoRKS service LED can display various behaviors having different meanings see Table 2 Power Supply LED The LED marked indicates whether or not the Excel Web is currently under power Specifically when it is lit the is under power when it is dark the is not under power Binary Input terminals 3 4 LED The LED marked indicates the state of the binary input which is a normally open contact located at terminals 3 and 4 Specifically when it is lit the binary input is closed when it is dark the binary input is open Binary Output terminals 7 8 LED The LED marked A indicates the state of the binary output watchdog relay at terminals 7 and 8 which is a normally closed contact Specifically when it is lit the alarm contact is open when it is dark the alarm contact is closed For a detailed description of the watchdog relay behavior see Excel Web User Guide EN2B 0289GE51 Binary Output terminals 9 10 LED The LED marked indicates the state of the binary output at terminals 9 and 10 which is a normally open contact Specifically when it is lit this means that the application has closed the relay when it is dark the relay is open Table 2 LonWorks service LED behaviors meanings LED behavior meaning LED remains OFF after power up Defective Excel Web hardware e g power supply p
17. re rre 8 Binary Input and Outputs aa enana noia aa aama ci nce coun epee cine ai diia A Ad A lina 8 A O RO A 8 Binary plata li da soda Heed 9 Bilary US A irse 9 Engineering COMMISSIONING ici A a subzadeacseevuascddencuauvgesuaeedzacessvecuseas Required Preparations Engineering Downloading and Commissioning PrOCedUre oococccccccccccococococoncnocanononcnnncnnnnnnnnnnnnnnncnnnnnn nn nr nncnnann nn 9 ProtocoliNg eiere A A e ada 10 UpAAtiNg FiMWAare iii A cada 10 U S Registered Trademark Copyright O 2009 Honeywell Inc EN1B 0256GE51 R0909 All Rights Reserved EXCEL WEB CONTROLLER INSTALLATION INSTRUCTIONS OVERVIEW OF HARDWARE binary output terminals 9 10 LED yellow LED ON application has closed contact binary output terminals 7 8 LED red LED ON watchdog has closed contact power supply LED green LED ON power supplied binary input terminals 3 4 LED yellow LED ON input closed LED ON Ethernet link is enabled Ethernet link LED yellow Ethernet activity LED yellow LED ON Ethernet active LonWorks service LED yellow for meaning of LED behavior see Table 1 LonWorks service button pushing broadcasts service pin message LED2 currently unused LED1 currently unused Compact Flash Card CFC release button push before removing CFC
18. rk Mask 255 255 255 0 Option 2 Dedicated Ethernet Interface For access via Ethernet the Excel Web has a permanent default IP address 192 168 253 20 and Network Mask 255 255 255 0 Your PC s IP address must match the Excel Web controller s default IP address subnet We recommend using 192 168 253 21 and Network Mask 255 255 255 0 If the laptop or PC with which you wish to access the Excel Web via Ethernet IP is not already equipped with an integrated Ethernet Card or if you want to leave the IP settings of the integrated network card unchanged buy and install into your laptop or PC an external Ethernet network card e g Devolo MicroLink LAN USB Network Adapter typical retail price 30 Option 3 Standard Ethernet Interface For access via Ethernet the Excel Web has a permanent default IP address 192 168 253 20 and Network Mask 255 255 255 0 Your PC s IP address must match the Excel Web controller s default IP address subnet We recommend using 192 168 253 21 and Network Mask 255 255 255 0 Change the factory set configuration of the integrated Ethernet card so as to match the Excel Web IP address and IP subnet When using this default address you must ensure that you have only one powered up Excel Web controller on your Ethernet otherwise communication will fail because all Excel Web controllers have the same permanent default IP address Alternatively you can use an Ethernet cross over cable between your PC and the
19. roblems clock problems or defective Neuron Chip LED is lit continuously after first power up Defective Excel Web hardware LED flashes at power up 3 goes OFF and then is lit con tinuously LED flashes briefly Neuron chip lacks LONWORKS interface program Remedy Use Excelon or LonMaker set Excel Web online Excel Web probably experiencing continuous watchdog resets or periodically external memory or EEPROM is corrupt Excel Web is unconfigured but 5 LED repeatedly blinks ON for has an application Remedy 1 s and OFF for 1 s OFF for approx 10 s After wards the service LED turns 6a ON and remains ON indicating completion of the blanking process Commission Excel Web using CARE 7 Return Excel Web to factory OFF for approx 1 s 6b Afterwards the service LED is lit continuously Return Excel Web to factory OFF for 1 15 s depending on application size and sys 6c tem clock Afterwards ser vice LED repeatedly flashes ON for 1 s and OFF for 1 s Excel Web is unconfigured but has an application Remedy Commission Excel Web using CARE 7 LED remains OFF after a short ON duration Excel Web is configured and running normally 8 LED flashes ON Excel Web received a WINK command from LONWORKS other physical outputs are unaffected In case of a problem check if the LonWorks service LED s behavior is changed by resettin
20. t as well as for connecting LoNWoRrks and the power supply A nearby sticker provides an overview of the terminal assignment see Fig 2 24Vac dc 20 10VA 50 60Hz IP 20 D 71101 Schoenaich Made in Germany CE Fig 2 Terminal assignment sticker Maximum torque for fastening the wiring terminal screws is 0 5 Nm 4 5 Ib in Table 1 provides a more detailed explanation of the terminals and their functions Table 1 Overview of terminals and functions term function 1 2 power supply 24 Vac 20 19 2 to 38 Vdc a binary input normally open 36 Vdc pin 4 is the signal ground freely configurable using CARE 7 to read input from either 1 a field device or 2 a collective alarm input or 3 a 2 Excel Web controller whose duties it could then assume in the event of its failure 5 6 LONWORKS 3 4 a binary output watchdog relay SPDT normally closed 24 Vac max 2 A permanent load per 7 8 manently configured to write output to an alarm device which can then signal that Excel Web is malfunctioning a binary output potential free contact SPST normally open 24 Vac max 2 A permanent load freely configurable using CARE 7 to write output to either 1 a field device or 2 a 2 Excel Web controller which could then assume the 1 Excel Web s duties in the event of its failure 11 12 LonWorks 9 10 LonWorks Interface The Excel Web is equipped with a LonWorks interface sp
21. the specifications of the following two Ethernet sub standards e 100Base TX twisted pair star wiring 100 Mbaud Ethernet based on Manchester signal encoding over category 5 or better twisted pair cable max segment length 100 meters and e 10Base T twisted pair star wiring 10 Mbaud Ethernet based on Manchester signal encoding over category 3 or better twisted pair cable max segment length 100 meters RS232C Serial Interface Ports The Excel Web is equipped with three male 9 pin sub D jacks into which corresponding female 9 pin sub D plugs can be inserted for various different purposes see following sub sections These ports allow data transmission rates of 9 6 19 2 76 8 or 115 2 kBaud the default 00000 O 0000 O Fig 5 RS232C serial interface Using CARE 7 the user can configure the specific desired data transmission rate of each individual RS232C port it is thus possible for the three ports to operate simultaneously at three different rates Port 1 Factory Service Interface Port 1 is intended for the connection as needed of a plat form for the purpose of servicing in the factory only the Excel Web In this context servicing comprises a group of different activities including e updating portions of the Excel Web controller s Operating System namely LINUX BACstack Apache Web Server and e diagnostics Linux firmware Port 2 Browser Interface Port 2 is intended for the conne
22. values or states of the data points which have been assigned to this particular Excel Web controller Using the browser interface the user must place the corresponding data points into trend If at some later point in time i e after lengthy operation a protocol of the Excel Web controller s history is desired the corresponding trend data can be generated viewed and downloaded in CSV format via the browser interface For the storage of larger amounts of trend data more than 64 000 trend entries corresponding to approx 2 MB a CF card see section CF Port LED Request Button and Slot can be used Updating Firmware If at some later point in time i e after the release of a new version of the firmware the user wishes to download the new firmware into the Excel Web this can be done using CARE 7 via either USB or Ethernet or using EBI via Ethernet Honeywell Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sarl Rolle Z A La Pi ce 16 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell GmbH B blinger Strasse 17 71101 Sch naich Germany Phone 49 7031 63701 Fax 49 7031 637493 http ecc emea honeywell com Subject to change without notice Printed in Germany EN1B 0256GE51 R0909
23. when miswired the Excel Web controller is unable to detect a valid input signal Binary Outputs The Excel Web controller is equipped with two binary outputs Hardware Limits e Amin current of 50 mA is required to ensure a reliable contact e The binary outputs are designed for a max continuous current of 2 A e Switching voltage 24 Vac 20 NOTE If inductive components are to be connected to the binary outputs and if these binary outputs switch more often than once every two minutes these components must be prevented from causing harmful interference to radio or television reception conformance with EN 45014 ENGINEERING COMMISSIONING Please refer also to CARE 7 User Guide Product Literature No EN2B 0182GE51 for more information Required Preparations In order to access with a laptop or PC the Excel Web via Ethernet IP for the first time you may employ any one of the following three options Option 1 USB recommended This USB interface is the recommended interface for downloading applications and firmware via CARE 7 The following USB host networking adapter has been approved BELKIN DIRECT CONNECT BELKIN order no F5U104 or F5U104G at www belkin com For access via USB the Excel Web has a permanent default IP address 192 168 252 20 and Network Mask 255 255 255 0 Your PC s IP address must match the Excel Web controller s default IP address subnet We recommend using 192 168 252 21 and Netwo