Contents

1. must be 600V 1 5 mm rated minimum 2 Double insulate all mains wiring Chassis 1 O o o 0 O O e SISI E o 3 O O O CD c A ls O DF 0 0 0 Ra El EI El E E o o O O o O O O o e O Jo oj o O gt ES 38 8 88 38 88 83 a8 E a e Ko o D 1 o eg o a a a 5 POs OTTO O ola me O DO rT SISS gt O O TEI ll O O O O O 6 wires Chassis 2 o JO n O O O O O SERE D o L O O O ON A A _ L B amp e O e O LC a O e 2 O a O 2 88 a8 83 38 E E a8 manj 888 She aa a er Q Oi Q o O O O o O D o ojo o 38 8 83 38 3 83 a8 z EEE EE EE ma taa gt Q o O o e a a O o o O o ola O O Bo rT SS O O o il T O O O G O POWERWIRINGO1 CDR 4 wires NON Battery 1 Battery 2
2. CISPRB CDR LEE A lt l 00008220392 09429068290 Ferrite sleeve Ferrite sleeve Typical cabinet wire routing A Ferrite sleeve Knockout Ground P 2 Proper shielding method for field wiring Figure 1 3 Typical wiring for CISPR Class B systems 1 10 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation Installing E series cabinets E series cabinets are available in two basic models the 3 CABx E and 3 RCCx E E series cabinets use the same back boxes as those available in the United States and Canada and accommodate 1 2 or 3 rail chassis Refer to Table 1 1 fora list of available cabinets The doors for 3 CABx E cabinets are specific to LPCB EN 54 3 CAB E series cabinets doors allow level 1 access to the panel without the aid of any special tools To provide level 1 access to the panel the inner door incorporates a flexible mylar film across the top opening When closed persons having the general responsibility for safety supervision may still access the panel control and fire function annunciator strips The outer door assembly incorpora
3. Figure 1 1 Typical routing diagram for mains and battery wiring 1 6 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation Pull field wiring for low voltage circuits through knockouts on either side of the enclosure Chassis 1 o Y e ssl A o E L ED e He amp EE o O 7 TE Il E E Se E e i O o q O o O ii ii II l gt Qr o TIS o ela Frye QO ae O G TI BEI N S lbacvea00edq O o li
4. 1 All wiring supervised 000 O O A An isolator base or module must be installed LY LY WW 2 for every 32 continuous devices on the loop An isolator may be installed anywhere on the loop but no more than 32 devices can be installed between isolators SSDC_EURO_01 CDR Figure 1 6 3 SSDC installation and wiring EST3 International Installation Supplement Manual 1 17 Technical Manuals Online http www tech man com European Marketplace Installation Installing the 3 AADC Addressable Analog Device Controller module Caution This product contains components that are sensitive ke to static electricity Failure to follow proper handling procedures will result in equipment damage Assembling the 3 AADC device controller Assemble the 3 AADC device controller according to the instructions provided on the 3 AADC installation sheet with the following additions e Attach a Kapton label over the communication LEDs See Figure 1 7 Wiring the 3 AADC device controller Make the field wiring connections as indicated in the 3 SSDC installation sheet with the following exceptions e Loop the end of the Class A primary wire pair and the Class A return wire pair and clamp a ferrite sleeve ordered separately P N RFK1 around each loop See Figure 1 7 Note Field wiring should be thoroughly checked before making connections to reduce the possibility of wiring faults 1 18 EST3 International Installation Supplement Manual
5. 1 Relays shown in energized state 2 SIGA CT2 defined as Monitor device type o o o 3 Do not wire earth ground to TB1 EGND SIGA CT2 4 EOL relays must be installed inside the remote control panel EOL relays and SIGA CT2 only required in 43 2 1 remote control panels Do not install in repeater panels DOOD terminals on previous CPU module 24 Vdc Riser 2 24 Vdc Riser 1 m all European Marketplace Installation N N N WN N N N 6 N BEER PITT ARA NE AI To NETWORK A A CPU Remote control unit 3 ANNCPU1 E G G A A B B G 2 N 2 N N 4 D 4 D D Vv V NETWORK TB1 EOL Relay ANNCPU1_EURO_01 CDR From DATA IN DATA IN Signature controller or previous device DATA OUT DATA OUT Figure 1 4 3 ANNCPU1 power supervision wiring for remote control units EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com terminals on next module To next device European Marketplace Installation Installing the 3 LCD display module Caution This product contains components that are sensitive ke AN to static electricity Failure to follow proper handling procedures will result in equipment damage Install the 3 LCD displ
6. installed outside the United States and Canada EST3 Smoke Management Application Manual P N 270913 This manual provides information for designing programming and testing an EST3 smoke control system EST3 Users Self Study Course P N 270684 This course contains a self paced manual and accompanying video The course 1s designed for building personal security guards firefighters and similar individuals that may be required to operate the system Signature Series Intelligent Smoke and Heat Detectors Applications Bulletin P N 270145 This manual provides additional applications information on the Signature series smoke and heat detector applications Signature Series Component Installation Manual P N 270497 This manual provides detailed mounting and wiring information for all Signature series devices Speaker Application Guide P N 85000 0033 This manual provides information on the placement and layout of speakers for fire alarm signaling and emergency voice communications Strobe Applications Guide P N 85000 0049 This manual provides information on the placement and layout of strobes for fire alarm signalings IV EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Related documentation ENS4 Part 2 1997 ENS4 Part 4 1997 73 23 EEC 89 336 EEC as amended by 9 3 1 EEC EN50130 4 1995 EN55022 1995 EST3 International Installation Supplement Manual
7. Ea lo o o 8 wires 4 wires oE olo CD 009990968 CEE SN R O o L y M fpodaaobreaod DD E e ana O 6 o O O o o O eo eo O 8 E r LE r y E qi E F q tz as a3 33 28 35 88 3 59 66 EE 990 E r _____ k 0 I E OO SO E E E e O o O o Q 9 Q Q Q PA PA of O O TLT a Hr m TLT DGH 33 33 E 85 E 8 LS o e A AP a a o De A st pi de o 5 OTT O_o 90 l E O il rT 9 S B aeoea00ea EH 4 O O POWERWIRING02 CDR 24 Vdc auxiliary power circuit Bundle low voltage wiring in neat fashion using nylon cable ties Keep wiring towards Notes the front of the enclosure 1 There are no
8. Technical Manuals Online http www tech man com Content Control and Indicating Equipment Power Supply Equipment Low Voltage Directive Electromagnetic Compatibility Directive Immunity Requirements for Components of Fire Intruder and Social Alarm Systems Limits and Methods of Measurement of Radio Disturbance Characteristics of Information Technology Equipment Content vi EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation Summary This chapter provides information required for certified technicians to properly assemble and install components in order to meet requirements for the European marketplace Content General system requirements and special considerations 1 2 LPCB EN 54 compliant systems 1 2 CE compliant systems 1 8 Installing E series cabinets 1 11 Installing a Repeater Remote Control Unit 1 12 Assembling the repeater remote control unit e 1 12 Wiring the repeater remote control unit 1 12 Installing the 3 LCD display module 1 14 Installing the 3 SSDC Signature Device Controller module 1 16 Assembling the Signature device controller 1 16 Wiring the Signature device controller 1 16 Installing the 3 AADC Addressable Analog Device Controller module 1 18 Assembling the 3 AADC device controller 1 18 Wiring the 3 AADC device controller 1 18 Installing the 3 ASU FT Audio Source Unit with Firefight
9. an event is in the Fire bin Press the Fault switch to display events placed in the Fault bin Pressing the switch once selects the bin and displays the first event pulled up in the queue Pressing the switch again displays the next event in the queue The switch s LED flashes when an event is in the Fault bin Press the Sounder Off On switch to turn off all active sounder circuits Pressing the switch a second time turns all the sounder circuits back on The switch s LED indicates that the sounder circuits have been silenced Activating the Sounder Off On function requires an access level 2 password Notes e This switch may also be used to cancel the drill signal Project configuration settings affect Alarm Silence function operation Pressing the Sounder Off On and Panel Silence switches at the same time activates the panel lamp test function Press the Reset switch to restore the system to normal The switch s LED indicates the status of the Reset function The LED flashes quickly during the smoke power down phase flashes slowly during the power up phase and is on steady during the restoral phase Activating the Reset function requires an access level 2 password Notes e The Reset switch is disabled as long as the alarm silence inhibit timer is running The Reset switch does not affect disabled points or manually overridden functions EST3 International Installation Supplement Manual 2 1 Technical Manual
10. es ee 11 A N Previous V Next aL TT 12 ajajaja Command eje L 3LCDE CDR 16 15 14 13 Figure 2 4 3 LCD display module with European marketplace inserts 2 4 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Index Control or Indicator Power LED Test LED CPU Fault LED Sounder LED Disable LED Drill Switch LED Panel Silence Switch LED Liquid crystal display screen Disable Switch LED European Marketplace Operation Functional Description The Power LED indicates that mains ac or battery power is applied to the panel The Test LED indicates that a part of the system is in the test mode Test mode must be exited manually The CPU Fault LED indicates that the CPU module has detected a processor failure Processor failures must be reset manually The Sounder LED indicates the status of the sounder circuits The LED flashes when a fault exists on a sounder circuit The LED is on steady when a sounder circuit has been disabled Disabled conditions have priority over fault conditions The Disable LED indicates that a point or zone has been disabled using the Disable command Press the Drill switch to activate the Drill function The LED indicates that the Drill function is active Pressing this switch a second time cancels the Drill function and turns off the LED Activating the Drill function requires an access level 2 password Press
11. EST3 International Installation Supplement Manual P N 270925 Rev 1 0 24JANOO Technical Manuals Online http www tech man com DEVELOPED BY COPYRIGHT NOTICE TRADEMARKS CREDITS DOCUMENT HISTORY Date Revision 24JANOO 1 0 Edwards Systems Technology 6411 Parkland Drive Sarasota FL 34243 941 739 4300 Copyright 2000 All rights reserved This manual and the products it describes are copyrighted by Edwards Systems Technology Inc EST and others under separate licensing agreements You may not reproduce translate transcribe or transmit any part of this manual without express written permission from EST This manual contains proprietary information intended for distribution to authorized persons or companies for the sole purpose of conducting business with EST If you distribute any information contained in this manual to unauthorized persons you have violated all distributor agreements and we may take legal action IBM is a trademark of International Business Machines Corporation Microsoft and MS DOS are registered trademarks and Microsoft Mouse Windows Word and Wordpad are trademarks of Microsoft Corporation This manual was designed and written by EST Technical Services Documentation Department Sarasota Reason for change Original release Technical Manuals Online http www tech man com Content Important information ii About this manual iii The EST3 library iv R
12. Panel Silence switch to silence the panel s trouble buzzer The LED indicates that the buzzer has been silenced and there is at least one active point on the panel A new active point into the panel turns off the LED and re sounds the trouble buzzer By default the trouble buzzer re sounds every 15 seconds after being silenced as a reminder that an active point still exists on the panel The trouble reminder period can be changed in the project configuration 168 character backlit alohanumeric display of system status Press the Disable switch to display events placed in the Disable bin Pressing the switch once selects the bin and displays the first event pulled up in the queue Pressing the switch again displays the next event in the queue The switch s LED flashes when an event is in the Disable bin CAUTION Depending on the size of the system the panel may not reset points in a zone that go active while the zone is in test as quickly as desired after re enabling the zone Always reset the panel after re enabling zones Note Only one message is displayed regardless of how many zones are in test To view zones in test highlight the common zones in test message and press Details then Next to view each zone in test EST3 International Installation Supplement Manual 2 5 Technical Manuals Online http www tech man com European Marketplace Operation Index 10 11 12 13 14 15 16 17 2 6 Control o
13. Technical Manuals Online http www tech man com European Marketplace Installation Class A Primary QU A US II O MOMO Mo Mo Mo zo OO ii Class A Return P1 LOOP1 LOOP1 o Ly g Place Kapton label over bus communication LEDs Red wire Black wire A comms U clamps gt 1 All wiring supervised 00000 oo A An isolator base or module must be installed J UL VJ U J U B for every 32 continuous devices on the loop An isolator may be installed anywhere on the loop but no more than 32 devices can be installed between isolators SSDC_EURO_01 CDR Figure 1 7 3 AADC installation and wiring EST3 International Installation Supplement Manual 1 19 Technical Manuals Online http www tech man com European Marketplace Installation Installing the 3 ASU FT Audio Source Unit with Firefighter s Telephone Caution This product contains components that are sensitive to static electricity Failure to follow proper handling procedures will result in equipment damage Assembling the 3 ASU FT Assemble the 3 ASU FT as indicated on the 3 ASU FT installation sheet with the following exceptions e Clamp a ferrite sleeve ordered separately P N RFK 1 to each ribbon cab
14. al WARNING In this configuration this is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures CISPR Class B systems CISPR Class B systems can only be configured using 3 RCC E series cabinets Wiring inside the cabinet must meet the same requirements as LPCB EN 54 systems with the following additions e All low voltage wiring entering the cabinet must be shielded and terminated inside the cabinet to studs provided immediately at the point of entry See Figure 1 3 e Clamp a ferrite sleeve ordered separately P N RFK 1 around each cable entering the cabinet close to the point of entry 1 8 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation Note Mains ac conductors do not require shielding or attaching ferrite sleeves In addition take extra care to avoid damaging the RF gasket on the back box and cabinet door EST3 International Installation Supplement Manual 1 9 Technical Manuals Online http www tech man com European Marketplace Installation Ferrite sleeve Of FO JAN 000000000
15. al certification report for a list of compatible products High and low voltage cabinet wiring Figure 1 1 shows a typical routing scheme for mains and battery wiring Figure 1 2 shows typical wiring for all other wiring EST3 International Installation Supplement Manual 1 5 Technical Manuals Online http www tech man com European Marketplace Installation Bundle mains wiring in neat fashion using nylon cable ties Position and maintain wiring towards the rear of the enclosure 3 wires Bundle battery wiring in neat fashion using nylon cable ties Position and maintain wiring towards the rear of the enclosure D 2 wires Notes 1 All mains and battery wiring Pull mains ac power conductors through designated knockout on re back box top of enclosu
16. ay module as indicated on its installation sheet with the following exception e Insert the 3 LKE European label kit before attaching the 3 LCD to the CPU module To insert the 3 LKE labels 1 Remove the slide locks from right side of the display module See Figure 1 5 2 Insert the 3 LKE labels 3 Replace the slide locks 1 14 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation meri He i Panel controller Panel operator interface SH Side view O O Power Test i Sounder Disable Sounder Panel A Reset Off On Silence Drill og C LD 9 1 E Yo e l e P P n Fire Fault Disable Monitor A Previous V Next UO 0009 OCS C d ti UL O O 3LKE_INSTALL CDR Figure 1 5 3 LCD Display module installation EST3 International Installation Supplement Manual 1 15 Technical Manuals Online http www tech man com European Marketplace Installation Installing the 3 SSDC Signature Device Controller module Caution This product contains components that are sensitive ho AN to static electricity Failure to follow pr
17. d audible may be used interchangeably All sounder circuits shall be configured as audibles e A dedicated disconnect device must be provided for each installation Caution The fault event message Network panel xx off line could indicate a serious failure such as CPU Failure of the CIE panel Repeater Caution The fault event message Power Supply could indicate a serious fault such as battery charger failure or loss of ac power gt gt 1 2 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation The EST3 life safety system has been approved certified to EN 54 2 4 1997 by LPCB along with the following options with requirements e output to fire alarm devices e alarm counter e fault signals from points e test conditions e standardized input output interface The products that were found compliant are listed in Table 1 1 Table 1 1 LPCB EN 54 compliant products Models 3 CAB7B E 3 CAB D R E 3 CAB14 E 3 CAB14D R E 3 CAB21 E 3 CAB21D R E 3 RCC7R E 3 RCC14R E 3 RCC21R E 3 6ANN E R 3 10ANN E R 3 LCDANN E 3 PPS M 230 E 3 BPS M 230 E EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Description 1 chassis wall box with E series inner and outer doors Available in surface or semi flush mounting 2 chassis wall box w
18. elated documentation iv Chapter 1 European Marketplace Installation 1 1 General system requirements and special considerations 1 2 LPCB EN 54 compliant systems 1 2 CE compliant systems 1 8 Installing E series cabinets 1 11 Installing a Repeater Remote Control Unit 1 12 Assembling the repeater remote control unit e 1 12 Wiring the repeater remote control unit 1 12 Installing the 3 LCD display module 1 14 Installing the 3 SSDC Signature Device Controller module 1 16 Assembling the Signature device controller 1 16 Wiring the Signature device controller 1 16 Installing the 3 AADC Addressable Analog Device Controller module 1 18 Assembling the 3 AADC device controller 1 18 Wiring the 3 AADC device controller 1 18 Installing the 3 ASU FT Audio Source Unit with Firefighter s Telephone 1 20 Assembling the 3 ASU FT 1 20 Wiring the 3 ASU FT 1 20 Installing a 3 1DC8 4 Initiating Device Circuit module 1 22 Chapter 2 European Marketplace Operation 2 1 Introduction 2 2 3 LCD display controls and indicators 2 4 Chapter 3 Chinese Marketplace Installation 3 1 Wiring requirements for China systems 3 2 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Content Important information Limitation of liability This product has been designed to meet the requirements of various international standards Installation in accordance with this
19. er s Telephone 1 20 Assembling the 3 ASU FT 1 20 Wiring the 3 ASU FT 1 20 Installing a 3 IDC8 4 Initiating Device Circuit module 1 22 EST3 International Installation Supplement Manual 1 1 Technical Manuals Online http www tech man com European Marketplace Installation General system requirements and special considerations LPCB EN 54 compliant systems To achieve compliance with EN 54 2 4 1997 per LPCB the following considerations must be taken into account e There are no user serviceable parts within the CIE Control and Indicating Equipment Contact your distributor for assistance e The battery size is limited to 17 Ah and shall be manufactured by GS Battery Inc type PE 12V Series e To eliminate the possibility of rail communication LEDs from being misinterpreted as events blank Kapton labels supplied with the PPS M 230 E must be applied over the rail communication LEDs for every LRM installed in a rail slot e To invoke the correct functionality that complies with EN 54 2 4 1997 the project must be configured with the Market Place setting set to European and the Primary Language setting set to English U K e The term used for zones in test throughout the EST3 documentation is Service Groups Points within a Service group must exactly match the points defined for each Zone The messages and zone numbers must also match e The 3 LKE insert must be installed in the 3 LCD e The terms sounder an
20. he 3 IDC8 4 installation sheet with the following exceptions e Attach a Kapton label over the communication LEDs See Figure 1 9 e Place a 1 5 KQ resistor in series with each initiating device on the return side of the circuit Kapton label IDC84SOFTSHORT CDR N N N N N N N N O OS MA e EI IDC NAC IDC NAC IDC IDC NAC IN 1 2 3 4 1 2 de tees TB1 3 IDC8 4 Typical initiating device circuit wiring Figure 1 9 3 IDC8 4 typical installation 1 22 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Chapter 2 European Marketplace Operation Summary This chapter provides instructions for operating the 3 LCD when the system is programmed for the European market place For information not covered in this chapter refer to the EST3 Systems Operation Manual Content Introduction 2 2 3 LCD display controls and indicators 2 4 EST3 International Installation Supplement Manual 2 1 Technical Manuals Online http www tech man com European Marketplace Operation Introduction When configured for the European market place there is no requirement to acknowledge each individual event Each event can be viewed using the Previous and Next message switches Fire events do not automatically restore and are removed from the Fire event bin only after the panel is reset Syste
21. ilter e The ground conductor must be secured to the back box ground stud closest to where power enters the cabinet then to the power supply ground terminal e Attach the ac line filter in the top left corner of the cabinet From mains ac ei n Oe ee CAB E series or Ferrite sleeve gt RCC E series back box Brown wire Green wire ll Back box Blue wire ground stud Filter O Brown wire Blue wire y oll G L1 L2 3 PPS MON 230 CHINASYS01 CDR Figure 3 1 Wiring diagram showing high voltage wiring for China systems 3 2 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com
22. ith E series inner and outer doors Available in surface or semi flush mounting 3 chassis wall box with E series inner and outer doors Available in surface or semi flush mounting 1 chassis wall box with solid door same as US model Available in surface or semi flush mounting 2 chassis wall box with solid door same as US model Available in surface or semi flush mounting 3 chassis wall box with solid door same as US model Available in surface or semi flush mounting 6 position base annunciator includes door CPU 2 annunciator support modules and 5 blank filler plates 10 position base annunciator includes door CPU 2 annunciator support modules and 9 blank filler plates Remote command module annunciator includes door LCD and CPU IEC950 compliant Primary Supply with Power Distribution IEC950 compliant Booster Supply European Marketplace Installation Models 3 CPU1 3 ANNCPU 1 3 RS232 3 RS485A B R 3 LCD 3 IDC8 4 3 SSDC 3 AADC 3 LDSM 3 ANNSM 3 24Y 3 24R 3 12RY 3 LRMF Description Main CIE Central Processing module Remote CIE Repeater Central Processing module RS 232 serial communication card RS 485 serial communication card Display module for both CIE and Remote Repeater Sounder circuits and traditional device module Signature Driver Controller module Addressable Analog Device Controller LED card Driver Support Module for Main CIE LED card Driver Su
23. le P N 250190 going from the 3 CHAS7 to the 3 RCIC close to the 3 RCIC Do not loop the ribbon cable See Figure 1 8 e Attach a Kapton label over the communication LEDs on the 3 ASU controller module e Attach a Kapton label over the communication LEDs on the 3 FTCU controller module Wiring the 3 ASU FT Make field wiring connections as indicated on the 3 ASU FT installation sheet 1 20 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com CATE e i Zi eZ a 7 B CHAS7 O R Top rail a 33 FI _ TI 250190 O Y 250191 Bottom rail oo ooo si 000 SS Pl L Ll 250192 CD 250190 cs eee DE PO 3 CHASS t mo a T A O ee Ey From FTCU J2 3 RCIC COUT J9 3FTCU_EURO_01 CDR Figure 1 8 3 FTCU cabling diagram EST3 International Installati
24. limitations on wire types used for low voltage wiring to meet LPCB EN 54 approval Figure 1 2 Typical routing diagram for low voltage wiring EST3 International Installation Supplement Manual 1 7 Technical Manuals Online http www tech man com European Marketplace Installation CE compliant systems In CE compliant systems special consideration must be given regarding RF emissions The standard EN55022 CISPR 22 includes two basic categories Class B and Class A Class B systems are intended primarily for use in a domestic environment and may include e Equipment with no fixed place of use For example portable equipment powered by built in batteries e Telecommunications terminal equipment powered by a telecommunications network e Personal computers and auxiliary connected equipment Class A systems are all other systems that satisfy the Class A limits but not the Class B limits EST3 systems can be configured to meet both Class A and Class B requirements for emissions Refer to CISPR 22 for information on Class A and Class B limits Please contact your authorized distributor for the Declaration of Conformity and a current list of compliant modules CISPR Class A systems CISPR Class A systems meet the same requirements as LPCB EN 54 systems Refer to Table 1 1 and Table 1 2 for a list of the required hardware Install according to the instructions provided in their respective installation sheets and this manu
25. m events that automatically restore are removed from their respective event bins once they are restored The 3 LCD display operates as described in the EST3 System Operations Manual with the following notable exceptions e By default the date is displayed in date month year format as shown in Figure 2 1 The panel s date format can be changed regardless of the market place setting e The event bins shown in Figure 2 2 are designated as follows in order from highest to lowest priority F for fire alarm events For example smoke detector or fire call point activations f for fault events For example open or shorted circuits D for disable events M for monitor events The expanded message area occupies the top half of the display screen when an operator presses the Details switch This allows the most recent highest priority event to always be displayed as shown in Figure 2 3 e The panel does not automatically silence after all the events have been reviewed Time 11 03 12 25 01 1999 Date ACME CORPORATE Custom HEADQUARTERS BUILDING Banner Alarm Alarm History 0002 History 3SCRN1E CDR Figure 2 1 3 LCD display screen when panel is in normal state 2 2 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Operation Number of active points a oo Number of disabled points System time 14 19 32 A00003 D0000 0001 Fire Call Pt Oldest highest prio
26. manual applicable codes and the instructions of the Authority Having Jurisdiction is mandatory EST shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of EST products beyond the cost of repair or replacement of any defective products EST reserves the right to make product improvements and change product specifications at any time While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents EST assumes no responsibility for errors or omissions ii EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Content About this manual This manual only contains information specific to systems installed outside the United States and Canada It is intended to supplement the ES73 Installation and Service Manual which should be the primary source of information Chapter 1 provides special procedures for the installation and electrical wiring of system components as required for LPCB approval certification Chapter 2 provides special procedures for the operation of systems installed in the European market place Chapter 3 provides special installation and electrical wiring of system components as required for the Chinese marketplace Safety information Important safety admonishments are used throughout this manual to warn of
27. on Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation AIN BIN 000 000 000 Top rail 909 AOUT BOUT CIN DIN Bottom rail Sep 000 COUT DOUT AIN CIN BIN DIN oy col fr olloloj lolo O lololo y O Notes 1 All wiring supervised A Ferrite clamps not required on a 3 ASU or 3 ASU 4 1 21 European Marketplace Installation Installing a 3 IDC8 4 Initiating Device Circuit module N N N N NN NN N X IDC NAC IDC NAC IDC IDC NAC IN 1 2 3 4 1 2 I l I 1 i Q JP2 o o JP1lolo olo J1 JP4 o o JP3 olo olo O ni IDC NAC IDC NAC IDC IDC NAC IN 5 6 7 8 5 6 I l i I YEN oe cee EN ee PAIA 0 ooo 0 O Caution This product contains components that are sensitive ko to static electricity Failure to follow proper handling procedures will result in equipment damage Install the 3 IDC8 4 as indicated on t
28. oper handling procedures will result in equipment damage Assembling the Signature device controller Assemble the Signature device controller according to the instructions provided on the 3 SSDC installation sheet with the following additions e Attach a Kapton label over the communication LEDs See Figure 1 6 Wiring the Signature device controller Make the field wiring connections as indicated on the 3 SSDC installation sheet with the following exceptions e Loop the end of the Class A primary wire pair and the Class A return wire pair and clamp a ferrite clamp ordered separately P N RFK 1 around each loop See Figure 1 6 Note Field wiring should be thoroughly checked before making connections to reduce the possibility of wiring faults 1 16 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation Class A Primary to first device on the loop N N N N N N N Poe A A A P pO0o00o00o00oooOo III B B A ASPB B A mwt sica KR sica Class A Return from last device on the loop Place Kapton label over bus communication LEDs Red wire Black wire de a F ere IL HH T clamps gt
29. possible hazards to persons or equipment WARNING Warnings are used to indicate the presence of a hazard that will or may cause personal injury or death or loss of service if safety instructions are not followed or if the hazard is not avoided gt Caution Cautions are used to indicate the presence of a hazard that will or may cause damage to the equipment if safety instructions are not followed or if the hazard is not avoided gt EST3 International Installation Supplement Manual lil Technical Manuals Online http www tech man com Content The EST3 library A family of documents and multi media presentations supports the EST3 network A brief description of each document is provided below EST3 Installation Manual and Service Manual P N 270380 This manual provides complete information on how to install and service the EST3 hardware This manual also includes installation information on selected Signature Series components EST3 Programming Manual P N 270381 This manual provides quick reference information for defining and labeling individual system components using the Systems Definition Utility SDU and for writing rules to govern system operation EST3 System Operations Manual P N 270382 This manual provides detailed information on how to operate the system and System components EST3 International Installation Supplement Manual P N 270925 This manual provides information specific to systems
30. pport Module for Remote Repeater Control display module consisting of 24 yellow light emitting diodes Control display module consisting of 24 red light emitting diodes Control display module consisting of 12 red and 12 yellow light emitting diodes Local rail module filler plate As arequirement of LPCB approval certification to EN 54 2 4 1997 the assemblies listed in Table 1 2 were investigated as ancillary to the EN 54 function These products may be installed in the same cabinet as the main CIE however separation must be provided between control display modules designated as fire related functions and the ancillary control display modules Table 1 2 LPCB EN 54 compliant ancillary products Model 3 ASU 3 FTCU 3 RCIC 3 ZA20 3 ZA40 Description Audio Source Unit Firefighters Telephone Control Unit Rail Chassis Interface for ASU and FTCU 20 watt Audio Amplifier 40 watt Audio Amplifier EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com European Marketplace Installation Model Description 3 12Sx Control display module consisting of 12 switches and 24 light emitting diodes of various colors 3 12 Sx Control display module consisting of 12 switches and 12 light emitting diodes of various colors 3 6 351xx Control display module consisting of 6 sets of 3 switches 3 light emitting diodes of various colors Compatible products Refer to the LPCB approv
31. r Indicator Monitor Switch LED Previous Message Switch Next Message Switch Command Menus Switch Details Switch Enter key Delete Backspace key Numeric keypad Functional Description Press the Monitor switch to display events placed in the Monitor bin Pressing the switch once selects the bin and displays the first event pulled up in the queue Pressing the switch again displays the next event in the queue The switch s LED flashes when an event is in the Monitor bin Press the Previous switch to display the event with the next lower event number When the first event is displayed pressing this switch pulls up the last event in the queue Press the Next switch to display the event with the next higher event number When the last event is displayed pressing this switch pulls up the first event in the queue Press the Command Menus switch to access a list of commands from which an operator can select in order to control system operations Pressing the switch a second time exits operator control of the system The 3 LCD automatically exits operator control of the system after the user timeout period has expired Pressing the Details switch displays additional information about the event highlighted on the display screen For Zone Groups pressing the Details switch displays a list of the active devices in the zone group e For Instruction Text Groups pressing the Details switch displays the entire instr
32. rity PULL ADMIN BLDG event or last reviewed 14 lA 1ST FLR WEST event in selected event queue 0002 Fire SMOKE ADMIN BLDG dio de as IST FER WEST priority even XPA FOOO DOOO M001 Monitor event queue Disable event queue Fire event queue Fault event queue 0001 Fire Call Pt Event type icine E E ezio Device message 1ST FLR WEST 0002 Fire SMOKE ADMIN BLDG IST FLR WEST 000 DOOO M001 3SCRN2E CDR Highlight indicates which event queue is displayed in the shaded Total number of events area of the display screen in the queue Figure 2 2 3 LCD display screen when panel is in off normal state Expanded Message S1 TOO1 PO1 C02 D0008 Active device s logical NO DATA TO REPORT AARS 001 001 0002 Fire SMOKE ADMIN BLDG Most recent highest LST FLR WEST priority event 000 D000 M001 3SCRN7E CDR Figure 2 3 Expanded message display EST3 International Installation Supplement Manual 2 3 Technical Manuals Online http www tech man com European Marketplace Operation 3 LCD display controls and indicators 1 2 3 4 5 E g B L L Power Test CPU Sounder Disable Fault Sounder Panel 21 D 6 20 7 8 19 9 18 10 A ey ae
33. s Online http www tech man com European Marketplace Operation Control or Index Indicator Functional Description Trouble buzzer The trouble buzzer alerts the operator to any off normal located on CPU system conditions such as module e Active alarms e Active test or disabled zones e Active fault conditions Active monitor conditions Internal software self checks When an event is placed into one of the bins the trouble buzzer sounds a pattern associated with that bin The pattern is determined by the project marketplace settings When multiple events of different types come into the panel the buzzer sounds the pattern for the highest priority event 2 8 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Chapter 3 Chinese Marketplace Installation Summary This chapter provides information required for certified technicians to properly assemble and install components in order to meet requirements for the Chinese marketplace Content Wiring requirements for China systems 3 2 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com 3 1 Chinese Marketplace Installation Wiring requirements for China systems Wire high voltage conductors as shown in Figure 3 1 Note the following e Clamp a ferrite sleeve ordered separately P N RFK 1 around all three conductors inside the cabinet before the f
34. tes a protective gasket around the upper door opening to prevent debris from entering the enclosure To install an E series cabinet 1 Install the cabinet back box Refer to the applicable back box installation sheet 2 Install the cabinet doors Refer to the applicable cabinet door installation sheet EST3 International Installation Supplement Manual 1 11 Technical Manuals Online http www tech man com European Marketplace Installation Installing a Repeater Remote Control Unit Caution This product contains components that are sensitive to static electricity Failure to follow proper handling procedures will result in equipment damage Assembling the repeater remote control unit To assemble the repeater remote control unit 1 Install the cabinet back box Refer to the back box installation sheet 2 Install the cabinet doors Refer to the cabinet door installation sheet 3 Install the 3 ANNCPUI Refer to the 3 ANNCPUI installation sheet Wiring the repeater remote control unit Make the field wiring connections as indicated in the 3 ANNCPUI installation sheet with the following exceptions e Do not attach a wire from earth to TB1 EGND e fused as a remote control unit only user interface power for remote control units must be supervised as shown in Figure 1 4 1 12 EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com From NETWORK B B Notes
35. uction text e For Maintenance Alerts pressing the Details switch displays a list of the dirty devices e For Common Troubles pressing the Details switch displays a list of the specific troubles for the selected device e For Guard Patrols pressing the Details switch displays the offending station and indicates whether the activation was caused because of an early late or out of sequence condition Press the Enter key to select the highlighted menu option or to start processing the information shown in the display Press the Delete Backspace key to move the cursor to the left of the current position and remove the character from the display The Delete Backspace key is also used to cancel functions and move the operator back through the menus Press a number key to select the menu option of the same number or enter the number for use in conjunction with other system functions EST3 International Installation Supplement Manual Technical Manuals Online http www tech man com Index 18 19 20 21 Control or Indicator Fire Switch LED Fault Switch LED Sounder Off On Switch LED Reset Switch LED European Marketplace Operation Functional Description Press the Fire switch to display events placed in the Fire bin Pressing the switch once selects the bin and displays the first event pulled up in the queue Pressing the switch again displays the next event in the queue The switch s LED flashes when