Contents
1. Two Beeps per second The UPS is overloaded in Battery Mode Your Shut off the least important equipment connected Two Beeps equipment needs more to the UPS If this solves the overload problem per second power than the UPS is rated the UPS will switch from bypass back to normal to provide The unit operation using either AC line or battery power switches to Bypass The UPS is doing a battery test The 4 operating mode lights flash counter clockwise in sequence No action needed The UPS will return to normal operation when it successfully completes the battery test No Audible Beep Five Beeps If the Battery LED is initially then No flashing this means replace Phone the nearest Best Power office Sound the battery Make sure the unit s fans and vent holes are not If the Battery LED is off this blocked and make sure the temperature at the Constant Beep is a High Ambient UPS location is not above 40 C 104 F If these Temperature alarm conditions did not cause the problem phone the nearest Best Power office Constant Beep 2 ee EE ara Phone the nearest Best Power office Constant Beep High DC bus voltage Phone the nearest Best Power office Bypass static transfer switch is shorte
2. A WARNING Clean only the external surfaces of the unit Use a cloth dampened not soaking with water only Allow the unit to completely dry before returning the unit to service UNINTERRUPTIBLE POWER SYSTEMS 13 Best Power 610 UPS Maintenance and Warranty 6 3 Troubleshooting The TROUBLESHOOTING CHART covers most of the difficulties that you may encounter under normal working conditions If the UPS fails to operate properly please review the following checks before calling the repair center els the circuit breaker turned on in the electrical panel supplying power to the UPS els the UPS plugged into a correctly working outlet ls the line voltage within the rating specified Has the fuse or the circuit protector protecting the loads tripped Please note the following information when you call for service Model number e Serial number Fuse or Circuit Date of problem Full description of problem Breaker BEST POWER Customer Service Locations are listed on the inside of the front cover Bypass LED When the UPS is providing power directly through the internal bypass switch the Bypass LED is on as shown This will happen if the BYPASS Switch on the front panel is pressed It also happens during an overload or if the UPS cannot run on battery power because of an inverter failure See the Alarm section and the table on the next page to find out the exact cause If the internal bypa
3. 610 2BAT 1500 1 5kVA 150 minutes 610 1BAT 3000 3 0kVA 16 minutes 610 2BAT 3000 3 0kVA 60 minutes 25 minutes Runtimes are approximate and depend on state of charge of batteries at time of power failure ambient temperature connected load age of battery etc Larger runtimes are available on request UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 UPS Optional Features 10 5 2 Best Relay AS400 Card Installation and Operation Output 2 ES 2 Pin connector A plug with link is supplied with the Best Relay AS400 card option This plug must be installed for normal operation If this plug is removed the load will be transferred to bypass The plug is removed only in applications where an external maintenance bypass switch is used When using an external bypass switch remove the link in the plug and connect the red and black wires from the cable routed out of the left side of the bypass switch cabinet Output 1 DB9 female connector To install the Best Relay AS400 card complete the following steps 1 Shut down your protected load Press the UPS or O Standby switch and remove the input line cord from the wall socket A CAUTION Even with the UPS switched off dangerous voltages may still be present at the UPS or its outlets 2 Remove the communications slot cover on the rear of the UPS by removing the two retaining screws Slide the Best Relay AS400 card option into t
4. accessible To de energize the UPS in an emergency press or O and unplug the power cord from the wall outlet The power cord is intended as the disconnect To reduce the risk of electric shock shut off and unplug the unit before making any connections to the UPS communication port 15 Refer to page 32 for important information regarding grounding connecting to earth and the UPS and protected equipment leakage current Models without Input Plugs Only 16 The UPS must be installed by a qualified service person The service person must install AC line input according to local and national codes and must be familiar with batteries and battery installation The Installation Manual that came with the UPS contains detailed information for the service person who installs the UPS 17 If a bypass switch is provided the bypass switch must be installed according to instructions in the Installation Manual that came with the UPS Follow standard safety practices and remove all power before installing the bypass switch 18 Before operating the bypass switch the service person must perform the phase check described in the UPS Installation Manual 19 DO NOT operate the bypass switch when the UPS is running from battery power AJ Best Power UNINTERRUPTIBLE POWER SYSTEMS 1 BEST POWER 610 UPS Installation 2 1 Introduction and Product Description An Uninterruptible Power System is designed to connect b
5. 1 Switching on the UPS BYPASS UPS ON Switch Switch Fault or Overload Load Level or Runtime Bypass Line Inverter Battery This symbol used on some models 3 2 When the Power Fails BEST POWER 610 UPS Operation 6 After completing the installation and battery recharge switch on the UPS by pressing and holding the front panel switch I for one second The unit will now commence a system check sequence before establishing its own inverter power At first all the Load Level LEDs will illuminate together and then one by one Within a few seconds the Inverter indicator will illuminate indicating the inverter has now started and the bypass indicator will extinguish indicating that the UPS is now in normal mode NOTE If the Line indicator flashes and the battery indicator illuminates at the same time your incoming utility AC source voltage and or frequency is out of the UPS specification The UPS is drawing energy from the batteries You may now start the equipment connected to the UPS If the load level indicator exceeds 100 and the audible alarm sounds twice per second you have plugged too many items into the UPS and overloaded it Remove the non critical items and check the load level indicators When the utility AC source fails the UPS will continue to deliver output to the UPS receptacles fro
6. 6636 MEXICO Phone 52 5 527 8009 Best Power Technology Limited 1 800 711 8978 13 Healey Road Fax 52 5 399 1320 Dandenong VIC 3175 AUSTRALIA Phone 61 3 9706 5022 Fax 61 3 9794 9150 BEST POWER Worldwide Manufacturers of Power Protection Conversion and Transformation Products AZ Best Power UNINTERRUPTIBLE POWER SYSTEMS 23 For Users in the United States only Note this equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct interference at his her own expense Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment For Users in Canada only This Class A interference causing equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil numerique de la Classe A respecte toutes les exigences du Reglement sur le materiel
7. Windows 95 Windows NT Windows 3 1x or OS 2 you must follow the instructions provided with the CheckUPS II v3 2x disk to remove the old software before installing v3 2x New Installation Instructions Step 1 System connection and startup Turn off the UPS and the PC to be protected If using the supplied cable look for the UPS label on one end Connect this end to the COM port on the UPS Connect the other end to a free serial port on your PC Turn the UPS power on and restart the PC Step 2 Install and run the software Note These instructions assume lt cd_rom gt is your CD ROM drive designation If not substitute the appropriate drive letter or mount point Windows 95 Release B and 98 Plug and Play Installation If the Update Device Driver Wizard Add New Hardware Wizard in Windows 98 appears insert the CheckUPS II Suite Version 3 2x CD ROM and click Next to continue with the Plug and Play installation process The wizard either automatically searches your floppy drive s and CD ROM drive or prompts you to select the drive to be searched for the applicable driver file The installation process requires the use of your internet browser Netscape 3 0 or Internet Explorer 3 0 or higher recommended The entire installation process and associated documentation is presented in the form of HTML pages which may be browsed from any operating system Follow the on screen instructions to complete the Windows 95 or
8. connected to the network can allow a network supervisor to monitor and control the UPS via SNMP protocol under such popular network management platforms like HP OpenView IBM NetView etc In addition the user may also manage the BestLink UPS through a web browser such as Netscape or Internet Explorer The BestLink SNMP Web adaptor card has a 10BASE T Ethernet interface built in The SNMP adaptor has a DIP switch to set the I P address assignments and two 2 LED indicators show power or network status plus error conditions In the BestLink SNMP Web Adaptor card option package you will find the following items e One SNMP adaptor card One 3 5 DOS formatted diskette containing the UPS SNMP Agent MIB One 3 5 tar formatted diskette containing the UPS SNMP Agent MIB One User Manual One Alternate mounting plate To install the BestLink SNMP Web adaptor card complete the following 1 Shut down your protected load Press the UPS or O Standby switch and remove the input line cord from the wall socket CAUTION Even with the UPS switched off dangerous voltages may still be present at the UPS or its outlets 2 Remove the communications slot cover on the rear of the UPS Slide the BestLink SNMP Web adaptor card option into the slot and secure it with supplied screws 3 Store the communications slot cover plate for recovery in case the BestLink SNMP Web adaptor card option is re
9. ee Sa mm in mm in mm in Kg Ib 7 0 AH 33 5 74 E 0610 2000 192 7 6 330 13 8 455 17 9 35 77 U 33 5 74 E 0610 3000 192 7 6 330 13 8 455 17 9 35 77 U 0610 3000 192 7 6 330 13 8 490 19 3 35 77 U AL Best Power UNINTERRUPTIBLE POWER SYSTEMS 19 Best Power 610 UPS Maintenance and Warranty 6 5 Warranty LIMITED TWO YEAR WARRANTY Standard Warranty For All Purchases BEST POWER a division of SPX Corporation hereinafter called BEST POWER warrants that each product sold by BEST POWER is compatible with existing commercially available computer equipment with enclosed power supplies and is free from defects in materials and workmanship under normal use and service This warranty is applicable only to the initial retail purchaser PURCHASER and is not transferable The duration of this warranty is two 2 years from the date of the first retail sale or the date of delivery to the PURCHASER whichever occurs first subject to the following conditions If the PURCHASER discovers within the duration of this warranty a failure of the product to perform compatibly with presently existing computer equipment or a defect in material or workmanship the PURCHASER must promptly notify BEST POWER in writing within the duration of the warranty or not later than one month after expiration of the warranty BEST POWER s obligation under this warranty is limited to the replacement or repair subject to the con
10. for 10 seconds inverter transfer to bypass for E models Greater than 110 to 130 for 10 seconds inverter transfer to bypass for U models Application of a short circuit will not damage the UPS All models 0 ms 700 1500 models 4 ms or less 2 5 ms typical 2000 3000 models 0 ms Returns to normal mode after overload condition is removed 83 at nominal input voltage under full load pf 0 7 battery fully charged 41 dB in line mode 45 dB in battery mode 50 dB in line mode 50 dB in battery mode 50 dB in line mode 50 dB in battery mode 52 dB in line mode 52 dB in battery mode Electronic overload and short circuit protection Automatic low battery shutdown High temperature shutdown When input mains power returns UPS starts automatically Two stage audible alarm The alarm sounds every 4 seconds after input mains failure When the battery discharge point is near the alarm sounds every second The alarm sounds once every second during an overload This continuous alarm sounds when there is an inverter short circuit output overvoltage DC bus overvoltage or high temperature Best Power 610 UPS Maintenance and Warranty _18 6 4 Model Specifications cont Battery Specifications DC Float DC Bus _ Battery Number of 2iScharge Recharge oi off Voltage Voltage Ratin Batteries Time Time to Voltage g g g FullLoad 90 g 12 VDC 7 0 AH 7 0 AH 7 0 AH All Models Physical amen ty amas
11. to the output receptacles The ON switch can apply AC to the output receptacles from the batteries without a live AC supply To remove AC from the output receptacles disconnect the input cord and press the STANDBY switch Hazardous voltage can be present at the unit s output any time AC input power or DC battery voltage is applied To avoid possible personal injury or equipment damage and to make certain there is no output voltage turn the unit off unplug the unit or disconnect AC input and disconnect all DC sources The installation and use of this product must comply with all national federal state municipal or local codes that apply To reduce the risk of fire or electric shock install the unit in a temperature controlled indoor area free of dust lint and conductive contaminants Do not place the unit near liquids or in an excessively humid environment To reduce the risk of overheating do not block the unit s ventilation panels Do not expose the unit to direct sunlight or other heat sources Do not allow liquids or foreign objects to enter the unit The unit does not contain any user serviceable parts The batteries are not user replaceable The user must not open the unit AY Best Power UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 UPS General Information v 1 4 Safety Notices and Warnings cont service personnel Remove rings watches and other jewelry before servicing th
12. 2 2 Sizing your Load NBR R Rhee eee eee eee BRE R Ree he eee eee Electrical equipment is often rated in VA volt amps This ah m a aa A E A E TEE represents the rated voltage times the rated current i e 230 Volts x 2 Amp 460VA Check your equipment for the manufacturer s label This label should state the equipment s desired operating voltage V and current A drawn by the equipment The manufacturer s label is usually found on the external rear or underside of the equipment or in the handbook or operator s manual Most computers and their related components are rated at worst case with all of the expansion slots or bays fully loaded at low line voltage so your actual load is probably less than the load indicated by the manufacturer Be Benar UNINTERRUPTIBLE POWER SYSTEMS BEST POWER 610 UPS Installation 2 2 3 Types of Loads The Best Power 610 UPS is designed to power all modern computer equipment loads The UPS output is specifically designed to work with switching power supplies found in today s microprocessor based equipment Laser Printers and your UPS Best Power does not recommend protecting laser printers with this UPS Laser printers have a heating cycle which provides adhesion of the toner to the paper This heating cycle draws large amounts of electrical current and will overload your UPS If your printer is mission critical and you want to protect it with a UPS the UPS must be siz
13. 98 installation of CheckUPS UNINTERRUPTIBLE POWER SYSTEMS 9 Best Power 610 UPS Optional features Windows 95 Release A Installation If a dialog box appears announcing that Windows 95 has found a Fortress Patriot Patriot Pro or SOLA 320 or 520 UPS follow these steps for a quick CheckUPS II installation When Windows 95 displays the New Hardware Found dialog box select the Driver from disk provided by hardware manufacturer option and click OK When the Install from Disk dialog box is displayed insert the CheckUPS II Suite Version 3 2x CD ROM and click Browse Under drives select lt cd_rom gt Make sure that the file name abestups inf is selected and click OK Return to the Install from Disk screen and click OK to start the installation process The installation process requires the use of your internet browser Netscape 3 0 or Internet Explorer 3 0 or higher recommended The entire installation process and associated documentation is presented in the form of HTML pages which may be browsed from any operating system Follow the on screen instructions to complete the Windows 95 installation of CheckUPS 5 1 External Battery Options External battery packs may be connected to the Best Power 610 1kVA 1 5kVA 2kVA and 3kVA models to give extended autonomy during power failure The standard battery packs available are listed below Battery pack UPS Rating Runtime with additional pack Part Number Half Load Full Load
14. ENT ALLOWED BY LAW ANY CLAIMS FOR LOSS ARISING OUT OF THE FAILURE OF PRODUCTS TO PERFORM FOR ANY PERIOD OF TIME OR SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES OR OTHER ECONOMIC LOSS ARE EXPRESSLY EXCLUDED Some states do not allow limitations on how long an implied warranty lasts so that the above limitation on duration of implied warranties may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state You are advised to consult applicable state laws N Best Power UNINTERRUPTIBLE POWER SYSTEMS 21 Best Power 610 UPS Maintenance and Warranty 6 6 Service Instruction and Service Locations Return Policy Most instances of initial failure to operate properly can be remedied through a telephone conversation between the user and BEST POWER Telephone and fax numbers for principal BEST POWER offices are on the inside of the front cover of this manual If during the course of your call it is determined that a product must be returned your service representative will provide you with instructions All returns to BEST POWER must have a Return Authority RMA Number The following information is required to obtain an RMA Number 1 Best Power part number 2 Serial number 3 Company name
15. INGAPORE 628584 Telephone 65 265 6866 FAX 65 265 6636 Best Power Technology Gmbh Am Weichselgarten 23 D 91058 Erlangen GERMANY Tele 49 9131 77700 Toll Free 0130 84 7712 in Germany Fax 49 9131 7770 444 Best Power Technology Mexico S A de C V Golfo de Riga 34 Colonia Tacuba Mexico D F 11410 MEXICO Telephone 52 5 527 8009 1 800 711 8978 FAX 52 5 399 1320 Borri Elettronica Industriale Srl Via de Lavatori 124 Milan ITALY Telephone 39 02 6600661 2 FAX 39 02 6122481 Best Power Technology Regional Offices Benelux Tel 31 0 10 4655803Fax 31 0 10 4662993 Croatia Tel 38554101414 Fax 38554101414 Czech Rep Tel 42 26845038 Fax 42 2 825 153 Hungary Tel 36 1 1534606 Fax 36 1 1534606 Russia Tel 7095 2433595 Fax7501 2586792 Copyright 1999 Best Power All rights reserved AY Best p ower UNINTERRUPTIBLE POWER SYSTEMS 1 1 Table of Contents Best Power 610 UPS General Information i Page Number 1 General Information 1 1 Table of Contents 200 2 cece e cece eeeceeeeeeneeeeeeaaeeeeeaeeeeeneeeeeeaaeeeeas i 1 2 Notice to UPS Owners 00 eee eee eecee cece eee eeeaeeeeeaeeeteeeeeeeaaeeteee ii T3 Preface nirna aaia A R eerie ili 1 4 Safety Notice and WarningS ccccccceeeeeeeeeeeeeeeeeeeceeeeeeeeaeeeees iV 2 Installation 2 1 Introduction and Product Description eeeeeeeeeeeeeeeeeenteeeeeees 1 22 Sizing yourLoad ss hassel eiiseiesivntieenieeieeiesi
16. POWER also makes Single Phase UPS systems up to 15kVA e Three Phase UPS systems to 400kVA Parallel Three Phase UPS Systems to 2MVA Plug in Power Conditioners to 3kVA Hardwired Single Phase Power Conditioners to 22 5kVA Constant Voltage Transformers to 7 5kKVA e CVDC Constant Voltage Ferroresonant Power Supplies BEST POWER products are available through an extensive distribution network These distributors offer literature technical assistance and a wide array of off the shelf products for the fastest possible delivery Best Power is a world wide organization and as well as the offices detailed on the inside cover of this manual Best Power is also located BEST POWER OFFICES BEST POWER Technology Ltd Best Power Technology Germany GmbH BEST House Am Weichselgarten 23 Moorside Road Winchester D 91058 Erlangen Hampshire GERMANY ENGLAND S023 7RX Phone 49 9131 77700 Phone 44 1962 844414 Toll Free 0130 84 7712 Fax 44 1962 841846 Fax 49 9131 7770 444 Best Power Borri Elettronica Industriale Srl PO Box 280 Via dei Lavoratori 124 Necadah Wisconsin 54646 20092 Cinisello Balsamo Mi USA MILAN ITALY Phone 1 608 656 7200 Phone 39 02 6600661 2 Fax 1 608 565 2221 Fax 39 02 6122481 Toll Free 1 800 356 5794 US and Can Best Power Technology Pte Ltd Best Power Technology Mexico S A de C V 19 Neythal Road Golfo de Riga 34 SINGAPORE 628584 Colonia Tacuba Phone 65 265 6866 Mexico D F 11410 Fax 65 265
17. a Best Power Best Power 610 Installation and Operation Manual for 700VA 1 0KVA 1 5KVA 2 0KVA and 3 0KVA LTM 1312E AJ Best TAUPTIBLE SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR YOUR UPS db WARNING This unit has an internal battery and is capable of generating dangerous voltages Do not open the unit by removing the outer case Please read the SAFETY WARNINGS on pages iv and v The unit can generate power even when disconnected from the utility supply Ensure you read this manual carefully and are aware of the correct operating parameters How to talk to us If you have any problem a question or require any information on Best Power s extensive range of UPS and power protection equipment this is where to contact us Best Power Technology LTD Best House Moorside Rd Winchester Hants S023 7RX ENGLAND Freephone Main Tele No Help Desk Service Fax Sales Fax Main Fax 0800 378444 44 0 1962 844414 44 0 1962 829050 44 0 1962 840108 44 0 1962 844353 44 0 1962 841846 E mail info bestpower emea com http www bestpower emea com Best Power P O Box 280 Necedah Wisconsin 54646 U S A Telephone 1 608 565 7200 Toll Free 1 800 356 5794 US and Can 20092 Cinisello Balsamo Mi FAX 1 608 565 2221 International FAX 1 608 565 7675 E mail info bestpower com Best Power Technology Pte Ltd 19 Neythal Road S
18. address phone number and contact person 4 Proof of purchase 5 Special instructions if any 6 Description of problem Shipments must be made in the original packing container Damage resulting from shipment in a non original container will void this warranty For proper handling upon receipt at BEST POWER the RMA Number must be clearly placed on the outside of the package BEST POWER will not be responsible for damage to returned goods that have not been properly packaged or damage exceeding normal wear and tear Service Telephone Numbers In the U S and Canada 1 800 356 5737 or 1 608 565 2100 Worldwide Service Fax 1 608 565 7642 or 1 608 565 2509 For Service in UK 44 0 1962 829050 Fax 44 0 1962 840108 For Service in Germany 49 9131 77700 Fax 49 9131 777051 For Service in Latin America 52 5 399 0369 Fax 52 5 399 1320 ae Best Power UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 UPS Maintenance and Warranty 22 You have purchased a UPS that will provide you with many years of service protecting your equipment from surges sags and blackouts This product incorporates the highest quality standards in engineering manufacturing and testing and carries a 2 year warranty against defects in material and workmanship This product is backed by over 75 years of pride and integrity We are sure you will agree there is no substitute for a BEST POWER Power Protection device Did you know that BEST
19. battery and inverter will light alternatively until the test is completed Each UPS is supplied with a package of CHECKUPS pees Pe Receive Data Rs232 II Advanced UPS communications software See Note 1 transmit Data This package includes the correct interconnection R5232 G d cable for your Best Power 610 UPS If your computer S roum does not have a DB9 connector on the serial port use O O 6 7 8 9 5 a standard DB9 DB25 adaptor available at most computer accessory stores The CD ROM provided with O O O 1 op 3 4 your UPS includes software for many standard operating systems Refer to section 4 1 for more details of CheckUPS II and its capabilities N O N C es If you are adding the optional Best Relay Card nak Closes AS40089 refer to Section 5 2 for instructions to install Input Input on the card Be careful to connect your Best Relay Mains Mains Low AS4008 interface cable to the correct DB9 connector ree rere Refer to Section 5 2 for more details of the Best Relay AS400 card option Note 1 Remote shutdown is available in battery mode only If you are adding the BestLink SNMP Web option card with no mains input power refer to Section 5 3 for instructions to install the card Keeping pin 6 at 5 to 12 VDC Only one 1 card either Best Relay AS400 or ee will turn off the UPS SNMP can be fitted into the slot at any one time Be ewer UNINTERRUPTIBLE POWER SYSTEMS 3
20. brouileur du Canada 24 Leakage Current Information The UPS ground earth conductor carries leakage current from the loads in addition to any leakage current generated by the UPS Maximum UPS Leakage Current generated by the various UPS models is shown in Table 1 below Table 1 To limit the total leakage current to 3 5 mA the load leakage must be limited to the value shown under Load Leakage Current for each UPS model as shown in Table 2 below If you do not know the load leakage current replace the UPS power cord with a power cord that uses an industrial style locking plug such as IEC 309 If you do not have a matching receptacle have an electrician install the correct receptacle The three wire receptacle that you plug the UPS into must have a good low impedance ground protective earth connection to provide a safe path for leakage current Table 2 UPS Model Load Leakage Current WARRANTY REGISTRATION Fill out the information listed below and retain this page for your records Send a photocopy of this page by mail or by fax to your nearest Best Power office if you can t register your warranty information online We recommend that you register your product by using the online registration form To enter your warranty information online go to http www bestpower com and select Warranty Registration on the Best Power home page Use the information you have recorded on this page to complete the online registratio
21. d The bypass static Constant Beep transfer switch was shorted Phone the nearest Best Power office when the line breaker was turned on Inverter static transfer switch is shorted The Constant Beep inverter static transfer switch Phone the nearest Best Power office was shorted when the UPS was started AL Best Power UNINTERRUPTIBLE POWER SYSTEMS 15 Troubleshooting Table No AC In Out or Battery Problems Possible Cause What you should do The green Line LED is noton 1 No input power may be available 1 Make certain the UPS is plugged into even though AC line input to the UPS a receptacle with power applied seems to be available and the 2 The input circuit breaker or fuse 2 Reset the breaker or replace the UPS beeps every few on the back of the UPS has been fuse and restart the UPS seconds tripped or opened 1 Make certain the loads are plugged The UPS operates normally es Bader ehcoue dias into the receptacles on the UPS but some or all of the 2 Reset the circuit breaker for the protected loads won t operate 2 ir t pe cupu fecepiacle has a receptacle by pressing the button or circuit breaker it has been tripped i resetting the switch Recharge the battery for at least 10 hours by connecting the UPS to a The am
22. ditions specified below of such product returned intact to BEST POWER which shall appear to BEST POWER upon inspection to have been either incompatible or defective Replacement or repair will be made at BEST POWER s Worldwide Service Highway 80 Necedah Wisconsin 54646 U S A Such repair or replacement shall be at BEST POWER s expense This warranty does not cover any taxes which may be due in connection with replacement or repair nor any installation removal transportation or postage costs These expenses will be paid by PURCHASER If BEST POWER is unable to repair or replace the product to conform to this warranty after a reasonable number of attempts BEST POWER will refund the purchase price Remedies under this warranty are expressly limited to those specified above TO THE EXTENT ALLOWED BY LAW BEST POWER DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AND ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ON THIS PRODUCT IS LIMITED IN DURATION TO THE DURATION OF THIS WARRANTY TO THE EXTENT ALLOWED BY LAW BEST POWER SHALL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LOSS OF PROFITS INJURIES TO PROPERTY LOSS OF USE OF THE PRODUCT OR ANY ASSOCIATED EQUIPMENT Some states do not allow limitations on how long an implied warranty lasts so that th
23. e above limitation on duration of implied warranties may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state You are advised to consult applicable state laws No warranty is made with respect to other products sold by BEST POWER which do not bear the name BEST POWER and no recommendation of such other product shall imply or constitute any warranty with respect to them This warranty does not cover repair or replacement because of damage from unreasonable use for example only damage from road hazard accident fire or other casualty misuse negligence or incorrect wiring and any use or installation not in conformance with instructions furnished by BEST POWER or repairs or replacements needed because of modifications or parts not authorized or supplied by BEST POWER ae Best Power UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 UPS Maintenance and Warranty 20 LIMITED WARRANTY Transient Voltage Surge Suppression Circuitry For U S and Canadian Purchasers Only BEST POWER a division of SPX Corporation BEST POWER hereby warrants the transient voltage surge suppression circuitry in each FERRUPS FORTRESS PATRIOT UNITY I CITADEL or SPIKEFREE product hereinafter called Produc
24. e package In case of damage notify the delivering carrier at once regardless of the external condition of the boxes After your claim has been established with the carrier damaged merchandise may be returned for repair see Page 19 for Return Policy Do not destroy packing material or boxes until the carrier s agent has examined them Save all packaging materials in case reshipment of the UPS is required Any damage sustained in transit when shipped from the user especially in an incorrect container will not be covered under warranty Best Power 610 UPS General Information jii 1 3 Preface Best Power makes no warranty of any kind with regard to this document including but not limited to the implied warranties of merchantability and fitness for a particular purpose Best Power shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing performance or use of this material This document contains proprietary information which is protected by copyright All rights are reserved No part of this document may be photographed reproduced or translated to another language without the prior written consent of Best Power This manual contains technical information about the 700VA 1 0kVA 1 5KVA 2 0kVA and 3 0kVA Best Power 610 family of uninterruptible power systems Also available in the 610 family with single phase inputs are the 6 0kVA and 10kVA The technical informati
25. e unit Always wear protective clothing and eye protection and use insulated tools when working near batteries M 9 All servicing of this equipment including battery replacement must be performed by qualified 10 Before maintenance repair or shipment the unit must be completely switched off and unplugged or disconnected from AC line all DC sources must be disconnected and all connections must be removed For units with no input plug switch the unit off and disconnect AC line input at the service panel 11 The sealed lead acid battery ies contained in this unit must be disposed of properly according to local regulations The batteries contain toxic lead and battery acid that pose environmental and human health hazards if not disposed of properly Do not dispose of batteries in a fire batteries could explode For battery disposal assistance call your local BEST Power office 12 A battery can present a risk of electrical shock and high short circuit current Keep unauthorized personnel away from batteries Only a qualified service person familiar with battery systems should service the batteries 13 Do not open or mutilate batteries Released electrolyte or battery acid is harmful to the eyes and skin and may be toxic If acid is spilled on skin or in the eyes flush with fresh water and contact a physician immediately Plug in Models Only 14 The AC outlet which supplies power to the unit must be near the unit and must be easily
26. ed to accommodate the high peak current surge of the printer 2 4 UPS Locations Your UPS should be in a controlled environment A controlled environment is one that is indoor temperature controlled and free of conductive or semiconductive contaminants The Best Power 610 is intended for indoor use only There should be adequate ventilation and the location should be free of dust and CAUTION fumes Do not install the unit next to open windows where uncontrolled environmental conditions could affect the unit Do not install the unit in any type of enclosure without first calling Best Power Technical Support The unit must have unrestricted air flow The environmental shown in Table 1 ENVIRONMENTAL SPECIFICATIONS right show the temperature and Ambient Operating lt 1500 m 4 900 feet 0 C to 40 C 32 F to 104 F Temperature 1500 3000 m 0 C to 35 C 32 F to 95 F humidity limits of the UPS Do not exceed these limits Ambient Storage All Models 15 C to 50 C 5 F to 122 F 4 900 9 800 feet Humidity All Models 0 to 95 noncondensing Altitude All Models 3000 m 9 800 feet max Table 1 2 5 Installation and Startup If your UPS unit has an AC inlet plug plug the unit into a wall socket If you have a hardwired unit refer to the separate Installation and Wiring Instructions shipped with hardwire units Be ower UNINTERRUPTIBLE POWER SYSTEMS 3 BEST POWER 610 UPS Insta
27. ediecis 1 2 3 Typesof Loads 2 sccccccisceecesst it eccdeee sins eteeeettdttteceensitiaeceecseiniens 2 24 UPSEOCALONS tis ect eau ecient 2 2 5 Installation and Startup c cceccccececeeeeeeeeeceeeeeeeeeeeseeeeeeeeeeeeeaees 2 2 6 Recharging the UPS Battery 0 eccceccceeeeeeeeeeseeeeeeeeeeeeteaeeeeeaees 3 2 7 External Battery Connection 0 eceececeeeeeeeeeeeeeeteeeeeeeeeeteaaeeeeaes 4 2 8 Voltage Selection Switch 0 0 cececceeeeeeeeeeeeteeeeceeeeeeeeeeesenaeeeeeaes 4 2 9 Setting up the UPS Monitoring from your Computer 05 5 3 UPS Operation 3 1 Switching on the UPS 0 000 eee cece ee eeeeeeeeee sees eeeeeeeeeeaaeeneneees 6 3 2 When the Power Falls eireta 6 3 3 When the Power Returns 0 0 0 ceeeeceeeeeeeeecneeeeeeeaaeeeeeeenaaeeeeee 7 3 4 Front Panel INGICAONS ssrin a a aa 7 4 CheckUPS Software Suite 4 1 Installing the CheckUPS II Software 0 ccccceceeeeteeeesteeeeeees 8 5 Optional Features 5 1 External Battery Options 00 0 2 eeccecceceeeeeceeeeeeeeeeseeaeeseeeeeeennaeees 9 5 2 Best Relay AS400 0 Card Installation and Operation 10 5 3 BestLink SNMP WEB Card Installation and Operation 11 6 Maintenance and Warranty 6 1 Storage irinin eceadveseai a deupecve let cay seseteaat Geecahstn degen iusteds 12 6 2 Maintenance and Cleaning cccceceeeeceeeeeeneeeeeceeeeeneeeeesaeees 12 6 3 Troubleshooting cceceeceeeceeeeeeneeeeccaee
28. eeeneeeeseaeeeesaaeeseceeeeeeaeees 13 6 4 Model Specifications ecccecceeeeeeccececeeeeseeeeeeeeeseaeeeseceeeseaeees 16 G5 WAMGUINY E cet eecseetcckve E 19 6 6 Service Instruction and Service Locations ccceeeeeeeeereees 21 AJ Best Power UNINTERRUPTIBLE POWER SYSTEMS ii Best Power 610 UPS General Information 1 2 Notice to UPS Owners ae EFF Lee r AY Best Power UNINTERRUPTIBLE POWER SYSTEMS Thank you for choosing a Best Power product your answer in power protection Over many years Best Power has built a reputation for designing and manufacturing top quality reliable power products Your Best Power unit is designed to provide trouble free operation in a normal commercial environment We encourage you to read this manual carefully in order to get full benefit from the features included in your Best Power product Please see the last page of this manual for online warranty registration Or you may complete the Warranty registration card and return it to us This will enable us to ensure you get immediate service for your system both in the warranty period and beyond WARNING A This unit has an internal battery and is capable of generating dangerous voltages Do not open the unit by removing the outer case Please read the SAFETY WARNINGS on pages iv and v Check your unit for damage that may not be apparent by the outside appearance of th
29. etween your utility supply wall outlet and your critical load Its function is to continually monitor the availability and quality of the electrical supply and to recreate the mains voltage to remain within the UPS specifications as detailed for each model Your Best Power 610 is an advanced true on line sine wave UPS with bypass line using double conversion technology The utility power enters the UPS where it is rectified to a DC voltage which will float charge the battery as well as run the DC to AC inverter The inverter generates the true sine wave output recreating the utility supply voltage A bypass path is provided through a transfer switch in case the UPS becomes overloaded or an inverter fault occurs Because the UPS is an on line design conditioned power is provided continuously to your load During an electrical power failure the unit employs its internal maintenance free battery to supply continuous power for as long as the battery is capable The UPS autonomy after a power failure will depend on a the size of the UPS and the load of your equipment b the size of the battery used either the standard internal battery or external battery pack options and c the state of the battery and battery charge when the power failure occurs Batteries have a finite life that can be affected by excessive use and or high ambient temperatures Under normal operation you should expect a 3 5 year life from your UPS battery
30. he slot and secure it with supplied screws 3 Store the communications slot cover plate for reinstallation in case the Best Relay AS400 card option be removed and decommissioned in the future 4 The Best Relay AS400 card will now be operational when the UPS is turned on and returned to service AS400 DB9 Pin out connections UPS Fail Normally open active will close po Relay contact Summary alarm Normally open active will close Active Relay contact when UPS fails bypass activated utility power and low battery status Remote Shutdown Activated by 5 12V for 1 sec duration La a 5 Common Common connection for pins Relay common 1 2 6 7 8 amp 9 Bypass Normally open will close when UPS is in bypass mode Relay contact 7 Battery Low Normally open will close when Relay contact battery is almost discharged UPS ON Normally open will close when Relay contact UPS is on Utility line failure Normally open will close when Relay contact ac input fails AJ Best Power UNINTERRUPTIBLE POWER SYSTEMS 11 Best Power 610 Optional Features 5 3 BestLink SNMP WEB Card Installation and Operation You may wish to connect your UPS to a network management system using SNMP This will require the purchase of the Bestlink SNMP WEB Adaptor card option Part No 0610 SNMP 00 which will install in the communications slot on the rear of the UPS This device when plugged into the UPS communications slot and
31. llation 2 6 Recharging the UPS Battery To optimize the performance of your UPS be sure the battery is fully charged before using the UPS to support your critical load To recharge the battery place the UPS close to a wall outlet and connect the matching line cord to the UPS receptacle then plug it into the wall socket If hardwired turn the breaker on at the service panel supplying power to the UPS When power is supplied to the UPS without operating any front panel switches the UPS will go through a short test sequence and the cooling fan will start ONG On the front panel the line indicator and the bypass indicator willilluminate At this time there is power available at the output sockets Note The battery backup feature of the UPS is not available in this mode See section 3 1 Switching on the UPS to enable the battery backup mode In this mode and normal UPS operating mode recharging occurs automatically and will take 10 hours if the batteries are completely discharged As UPS units are normally delivered with charged batteries providing the UPS has not been in storage for a long time it will not take long for the battery to reach full capacity CAUTION IN ALL CONDITIONS if the UPS is connected to a live supply AC POWER IS PRESENT AT THE UPS OUTPUT TERMINALS OR RECEPTACLES The front panel ON and 4 or O STANDBY switches do NOT control the delivery of power
32. ltage 2 1 Voltage 2 1 by the arrows for the inverter output voltage you need 208 v 100 Hiv l l 220 M 110 M M For Hardwire Models Make sure the UPS and its input breaker are off If you have an optional 230 viv 120 IYA nae a n bypass switch make sure it is turned to Bypass 240 NV M 27 v or Off 2 1 Note When the UPS is in bypass mode l or the optional maintenance bypass switch is set to Maintenance or i Bypass the voltage selection switches Voltage Selection Switch do NOT control the output voltage N Benar UNINTERRUPTIBLE POWER SYSTEMS 4 BEST POWER 610 UPS Installation 2 9 Setting up the UPS Monitoring from your Computer Model Shown 0610 3000U soft wired version Your UPS is fitted with a DB9 communications connector on the rear panel From this connector you can access opto coupled outputs indicating mains failure or low battery The contact ratings are 30 VDC at 10 mA The diagram below shows DB9 contact connections Alternatively RS232 serial communication is available This RS232 provides a proprietary command sequence for the computer to monitor the utility and the UPS status and to control the UPS output The data format of the RS232 is 2400 bps 8 bit data 1 stop bit and no parity DBI The battery test mode is also available through the RS232 command sequence when the UPS is operating and the power is normal During the test the 4 LED s line bypass
33. m the internal or external batteries and the UPS inverter When this occurs an audible alarm will sound every 4 seconds and the line indicator will extinguish The battery indicator will be illuminated to show that the battery is now being discharged The audible alarm can be silenced by pressing the I ON push button switch on the front panel and holding it momentarily If the battery continues to discharge until the low battery charge point is reached the audible alarm will sound again At any time the audible alarm can be reactivated by pressing the ON switch on the front panel Be ower UNINTERRUPTIBLE POWER SYSTEMS 7 Best Power 610 UPS Operation 3 3 When the Power Returns When the utility AC Line returns after a power failure the Line indicator will illuminate again the audible alarm will silence and the UPS will automatically commence the recharging of the battery The battery indicator will go out and the UPS will return to normal operation 3 4 Front Panel Indicators BYPASS UPS ON Switch Switch Your Best Power 610 UPS is fitted with 10 LED indicators to provide you with a simple but comprehensive explanation of the UPS status The functions of these indicators are detailed below o Fault will illuminate when a fault condition occurs in Fault or the UPS At this time the audible ala
34. moved and decommissioned in the future 4 Follow the detailed set up instructions found in the User Manual that came with the BestLink SNMP WEB Adaptor Card option package ae Best Power UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 Maintenance and Warranty 12 6 1 Storage The UPS must be kept at reasonable temperatures to obtain maximum battery life 15 to 21 C is ideal Note While in storage the unit MUST be plugged into AC power for 10 hours every six months This is necessary to recharge its internal batteries The unit must be recharged more frequently if it is stored above 35 C 95 F to obtain maximum battery life The warranty on this product will be affected if the unit is improperly stored 6 2 Maintenance and Cleaning Turn off and disconnect loads before performing maintenance work Your BEST POWER 610 UPS requires little or no maintenance Occasionally the input and output connections should be inspected for signs of damage and repaired if necessary If you would like to clean the unit first remove all power to the unit by pressing or O Standby and unplugging the unit from the wall outlet For units with no input plug switch the unit off and disconnect AC line input at the service panel or the maintenance bypass switch If the unit is operating in an unusually dusty or dirty area carefully vacuum any dust from the input vents as well as the chassis holes located on the sides of the UPS
35. n Best Power Standard Warranty Registration Best Power Model Number Best Power Serial Number I acknowledge that the above product has been properly installed and grounded in accordance with instructions supplied by Best Power signature installation date Please print the following information Contact Person Company Street Address City State Country Postal Zip Code Telephone E mail Address
36. on for these products is detailed in a separate manual The family is further enhanced by units with a three phase input and single phase output at 7 5KVA 10kVA 15kVA and 20kVA Again technical information on these products is detailed in a separate manual AL Best Power UNINTERRUPTIBLE POWER SYSTEMS iV Best Power 610 UPS General Information 1 4 Safety Notices and Warnings Important Please read this before installing your UPS Warnings Cautions and Notes appear throughout this manual Please familiarize yourself with them as they are essential for your safety and will enable you to maximize longevity of your UPS WARNING A Denotes a procedure or practice which if not performed correctly or adhered to may result in personal injury Do not proceed beyond a Warning sign until the indicated conditions are fully understood and met CAUTION Denotes a procedure or practice which if not performed correctly or adhered to may result in damage to equipment Do not proceed beyond a Caution sign until the indicated conditions are fully understood and met Note Denotes an essential procedure or practice A Safety Warnings 1 2 Do not use the unit for other than its intended use If the UPS is connected to a live AC supply AC is ALWAYS present at the UPS receptacles The front panel ON and or O STANDBY switches do not control the delivery of power
37. ount of time that the The battery may not be fully charged source of AC line input Then retest the UPS can run on battery is less _ or it may be bad or the charger may battery backup time If the problem has than the rated time have failed not been solved by recharging the batteries phone the nearest Best Power office Recharge the battery for at least 10 hours by connecting the UPS to a The battery voltage is low source of AC line input If the problem continues phone the nearest Best Power office The yellow Battery LED is flashing 16 6 4 Model Specifications Rating Model rh Pai Input Output VA W Number p p Connector Socket Type Voltage Voltages B610 0700E 230 208 220 230 240 IEC 320 C14 4 a 700 VA 3 490 W IEC 320 C14 4 NEMA B610 0700U 120 100 110 120 127 NEMA 5 15P 5 15R B610 1000E 230 208 220 230 240 IEC 320 C14 a o 1000 VA 3 700 W IEC 320 C14 4 NEMA B610 1000U 120 100 110 120 127 NEMA 5 15P 5 15R B610 1500E 230 208 220 230 240 IEC 320 C14 a T 1500 VA 3 1050 W IEC 320 C14 4 NEMA B610 1500U 120 100 110 120 127 NEMA 5 15P 5 15R B610 2000E 230 208 220 230 240 IEC 320 C14 4 T 1400 W e B610 2000U 100 110 120 127 NEMA a shel L5 20P 2 5 20R B610 3000E 230 208 220 230 240 IEC 320 C20 4 Paes 2100 W To 5 15R and B610 3000U 100 110 120 127 2 NEMA 5 20R Also available as a hardwired unit Frequency E and U models Input Range 50 60 Hz 5 Autosensing Output Frequenc
38. r or replacement because of damage from unreasonable use damage from road hazards accident fire or other casualty misuse negligence incorrect wiring and any use or installation not in conformance with instructions furnished by BEST POWER or repairs or replacements needed because of modifi cations or parts not authorized or supplied by BEST POWER This warranty is operable only upon the written acceptance by BEST POWER of an application by the PUR CHASER on BEST POWER s standard form for the above warranty coverage for the Product sold In such application the PURCHASER shall represent that the Product sold has been properly installed and grounded in accordance with instructions received from BEST POWER and the PURCHASER shall also specify the computer equipment to which the Product sold has been connected and the location of the computer equipment This warranty will not apply to any equipment not specified in the application by the PURCHASER as protected equipment EXCEPT AS EXPRESSLY SET FORTH IN THIS WARRANTY AND BEST POWER S LIMITED TWO YEAR WARRANTY BEST POWER MAKES NO OTHER WARRANTIES AND TO THE EXTENT ALLOWED BY LAW BEST POWER DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE REMEDIES UNDER THIS WARRANTY ARE EXPRESSLY LIMITED TO THE REPAIR OR REPLACEMENT OF PRODUCTS AND THE REIMBURSEMENT SPECIFIED ABOVE AND TO THE EXT
39. rm will sound vetoed continuously C Overload will illuminate when the UPS is overloaded ee N ev or Runtime j za Load Level and Runtime perform two functions during different operating modes of the UPS When utility AC Bypass mains is present Load Level will show the equipment load connected as a percentage of the UPS capacity in oe AG increments See LED Indications Percent of Full Load below Inverter Ta When the UPS is in battery mode Runtime lights will Battery show the amount of battery capacity remaining as a percentage of the full battery capacity in increments See Percent of Battery Charge under LED Indications x _ This symbol used on some models The Bypass light illuminates when the bypass line is in use and the UPS power is being sourced directly LED Indications from the utility AC supply When the UPS starts the Percent of Full Load bypass line will always be in service with the light 0 35 35 55 55 75 75 95 95105 Overload illuminated until the inverter has started and accepted the load si The Line light will illuminate when there is normal AC a voltage entering the UPS from the utility supply _ aa mm i ll The Inverter light should be on during normal utility available or mains failure mode When OFF the UPS cannot p
40. rovide battery backup power Percent of Battery Charge 0 35 35 55 55 75 75 95 95 100 The Battery light illuminates during mains failure showing that the battery is discharging UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 CheckUPS SoftwareSuite 8 4 1 Installing the CheckUPS II Software Each Best Power 610 UPS is supplied with CheckUPS II ene software a sophisticated UPS Monitoring and orderly unattended CheckUPS II system shutdown utility for most popular operating systems The CheckUPS II Suite is contained onthe CD ROM in the Crhware cuiteVersiona 21 software pack along with a special cable for use with your Best Power Management Monitoring and Control Software Power 610 On the CD ROM you will find versions of the 7 CheckUPS II software to operate on Windows v3 11 Now includes N etW atch software for the Windows 95 and 98 Windows NT OS 2 Novell and BestLink SN MPYW EB Adapter various UNIX platforms ri WINDOWS 95 98 WINDOWSNT WINDOWS 3 1x os 2 NOVELL NETWARE Installation par UNINTERAUPTIBLE A SYSTEMS The CheckUPS II Suite CD ROM is now completely browsable using your internet browser Netscape Navigator 3 0 or Internet Explorer 3 0 or higher recommended SFT 0543E If you previously installed CheckUPS for
41. ss operates because of an overload the UPS can transfer back to normal operation after the overload has been removed Fault or Overload Alarm LED BYPASS UPS ON and Alarm Whenever the red Fault or Overload LED at the top of the front Switeh Switch panel is on or flashing the UPS has detected a problem The UPS will also sound an alarm tone beep to notify you of the problem When this happens use the table on the next page to determine the cause of the problem and how you should react _ Fault or Overload To silence the alarm press the Alarm Switch also called UPS On Note that silencing the alarm will not solve the problem that caused it Bypass If you need to contact Best Power because of the alarm make Line sure that you have your unit s model number and serial number Inverter available when you call Battery oO This symbol used on some models for Bypass Switch ae Best Power UNINTERRUPTIBLE POWER SYSTEMS Best Power 610 UPS Maintenance and Warrant 14 Troubleshooting Table If LEDs are Lit LEDs Lit Audible Alarm What You Should Do The UPS is overloaded Your equipment needs more power than the UPS is rated to provide The UPS operates in bypass Shut off the least important equipment connected to the UPS If this solves the overload problem the UPS will switch from bypass back to normal operation using either AC line or battery power
42. t sold by it for installation in the United States of America and Canada to be free from defects in material and workmanship under normal use and service for the lifetime of the Product beginning with the date of sale to the initial retail purchaser subject to the following conditions This warranty is applicable only to the initial retail purchaser hereinafter called PURCHASER is not transferable and is limited to the following remedies 1 The replacement or repair of the transient voltage surge suppression circuitry in each Product that is returned intact to BEST POWER and which shall appear to BEST POWER upon inspection to have been defective in material or workmanship or to have been damaged through normal use 2 The reimbursement to the PURCHASER of up to 25 000 per occurrence of documented physical damage to specified computer equipment connected to a Product where such damage could have been prevented by transient voltage surge suppression circuitry as detailed in BEST POWER s specification for the Product sold This warranty is made in addition to BEST POWER s Limited Two Year Warranty This warranty does not include any taxes which may be due in connection with replacement or repair nor any installation transportation or postage costs These expenses will be paid by PURCHASER Replacement or repair will be made at BEST POWER s Worldwide Service Highway 80 Necedah Wisconsin 54646 U S A This warranty does not cover repai
43. to the output receptacles Be wer UNINTERRUPTIBLE POWER SYSTEMS BEST POWER 610 UPS Installation 2 7 External Battery Connection i All units excluding the 700VA model can be fitted with Battery an external battery option to increase the runtime on Connection batteries when the UPS is operating during an input utility line mains failure Refer to Section 5 1 for selection of external battery options for your specific UPS On the rear of each of the 1 3kVA capacity UPS units you will find an external battery receptacle If you have purchased an external battery option it will be supplied with an interconnecting cable to connect into this receptacle Use only the matching battery option for your UPS rating Using the incorrect battery option may cause damage to your UPS system After you make the connection between the external battery and the UPS switch ON the circuit breaker on the external battery pack Once connected your UPS will maintain the charge in the external battery providing the utility mains is available 2 8 Voltage Selection Switch The voltage selection switch is in the upper left corner beside the communication port on the back of the UPS Output Voltage The chart above the switch shows the proper settings for each voltage E Model U Model High Voltage Low Voltage Set the voltage selection switch in the direction shown Vo
44. y Automatic conforms to input Output Regulation 0 5 inverter free running Phase locked to input under normal conditions Nominal Input Voltage Typical for E models 230 VAC 10 20 Typical for U models 120 VAC 10 20 Nominal Output Voltages selected by DIP switches on back panel Values for E models 208 220 230 or 240 VAC 3 under all input mains and battery charge conditions Values for U models 100VAC 30A 110 VAC 27A 120 VAC 25A or 127 VAC 24A 3 under all input mains and battery charge conditions 17 6 4 Output Power Factor Waveform Overload Capacity Battery Transfer Time BypassTransfer Time UPS to from bypass Auto Reverse Efficiency AC to AC All Models Acoustic Noise at one meter from the front panel 700 1000 VA E and U 1500 VA E and U 2000 and 3000 VA E 2000 and 3000 VA U Protection Output Low Battery Thermal Automatic Restart Following Battery Discharge or Remote OFF Signal Audible Alarms Battery Discharge Overload UPS Fault Best Power UNINTE RRUPTIBL POWER SYSTEMS Best Power 610 UPS Maintenance and Warranty Model Specifications cont 0 7 lagging to unity the unit operates with up to 50 ufarad capacitive load Less than 4 THD at full linear load less than 7 THD at full nonlinear load Greater than 130 10 for 1 5 seconds 20 ms inverter transfer to bypass Greater than 110
Download Pdf Manuals
Related Search
Related Contents
Le phénomène des abductions est quelque chose de si étrange, si VL-CM260/240(設置説明書) (3.52 MB/PDF) MANUEL D`INSTALLATION ET D`UTILISATION DU N1 Migration with the NIE Technical Bulletin AgfaPhoto PRECISA 1430 Doro Congress 150 Samsung M1817N manual de utilizador Naim R-Com Copyright © All rights reserved.