Minuteman Pro 320 Battery Backup (MMNPRO320) UPS System
Contents
1. Battery install Date of manufacture Date of battery re Enter the current date when date placement replacing batteries day month year XXIXXIXXXX Battery life in Up to 5 characters At first battery replacement days reset to reflect actual num ber of days experience in your environment or leave fac ory default Enable Enabled Enable or disable When enabled the UPS will Disable auto automatically restart from a resstart low battery shutdown when normal A C returns Enabled Enabled at low bat Enabled the UPS will emit Set audible tery disabled a short beep when in the alarm state battery mode At Low Bat tery the UPS will emit two tonesfrom low battery warning until shutdown Disabled Use only when software is controlling the UPS or to silence the alarm UPS output UPS output or UPS UPS Output When the UPS Shutdown is told to shut down it turns Type offthe UPS output only UPS Turns off the UPS which requires the UPS to be turned on manually Set low volt 85 VAC 170 for 230 85 or 80 or 75 VAC Changes the voltage point age Xfer point VAC cis 170 or 160 or 150 at which the UPS switches VAC for 230 VAC to battery power models 14 B MINUTEEEMAN UNINTERRUPTIBLE POWER SUPPLIES m PRODUCT WARRANTY LIMITED PRODUCT WARRANTY Para Systems Inc Para Systems warrants this equipment when properly applied and operated within specified conditions against faulty materials or
2. Para Systems Life Support Policy As a general policy Para Systems Inc Para Systems does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness Para Systems does not recommend the use of any of its products in direct patient care Para Systems will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Para Systems that a the risks of injury or damage have been minimized b the customer assumes all such risks and c the liability of Para Systems Inc is adequately protected under the circumstances Examples of devices considered to be life support devices are neonatal oxygen analyzers nerve stimulators whether used for anesthesia pain relief or other purposes auto transfusion devices blood pumps defibrillators arrhythmia detectors and alarms pacemak ers hemodialysis systems peritoneal dialysis systems neonatal ventilator incubators ventilators for both adults and infants anesthesia ventilators and infusion pumps as well as any other devices designated as critical by the United States FDA Hospital grade wiring devices and leakage current may be ordered as options on many PARA SYSTEMS UPS systems PARA SYSTEMS does not claim that units with this modification are
3. B MINUTEMAN UNINTERRUPTIBLE POWER SUPPLIES aum OF CONTENTS B H Pro Series Owner s Manual 1 Introduction 2 2 Controls and Indicators 4 3 Installation 5 4 Operation 7 5 Troubleshooting 9 6 Replacing the Battery 10 7 Obtaining Service 12 8 Specifications 13 9 Configurable Parameters amp Settings 14 10 Limited Product Warranty 15 11 Declaration of Conformity 31 Copyright Para Systems Inc 1998 MINUTEEMAN UNINTERRUPTIBLE POWER SUPPLIES aum oct EAN Thank you for purchasing a Minuteman power protection product It has been designed and manufactured to provide many years of trouble free service IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Please read the manual before installing your Pro Series UPS as it provides the information that should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance Included is information on customer support and factory service if it is required If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the Minuteman technical support department can rapidly assist you NOTICE This equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of F
4. REPAIRS CAN BE PERFORMED BY MINUTEMAN SERVICE PERSONNEL ONLY CAUTION DONOT OPEN OR MUTILATE BATTERIES RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES AND MAY BE TOXIC CAUTION DONOT DISPOSE OF BATTERIES IN A FIRE THE BATTERIES MAY EXPLODE THE BATTERIES IN THIS UPS ARE RECYCLABLE DISPOSE OF THE BATTERIES PROPERLY THE BATTERIES CONTAIN LEAD AND POSE A HAZARD TO THE ENVIRONMENT AND HUMAN HEALTH IF NOT DISPOSED OF PROPERLY REFER TO LOCAL CODES FOR PROPER DISPOSAL REQUIREMENTS OR RETURN THE BATTERY TO MINUTEMAN CAUTION ALTHOUGH BATTERY SYSTEM VOLTAGES ARE ONLY 12 VDC AND 24 VDC THE BATTERY SYSTEM CAN STILL PRESENT A RISK THE CURRENT CAPABILITY OF A BATTERY IS SUFFICENT TO BURN WIRE OR TOOLS N VERY RAPIDLY PRODUCING MOLTEN METAL OBSERVE THESE PRECAU TIONS WHEN REPLACING THE BATTERIES 1 REMOVE WATCHES RINGS OR OTHER METAL OBJECTS 2 USE HAND TOOLS WITH INSULATED HANDLES 3 DO NOT LAY TOOLS OR OTHER METAL PARTS ON TOP OF CAUTION aarrERIES REPLACE BATTERIES WITH THE SAME NUMBER AND TYPE AS ORIGI NALLY INSTALLED IN THE UPS THESE BATTERIES HAVE PRESSURE OPERATED VENTS 10 B MINUTEEEMAN UNINTERRUPTIBLE POWER SUPPLIES BATTERY REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS SECTION BEFORE ATTMPTING TO REPLACE THE BATTERIES 1 Lay the unit on its side or bring to the edge of a table Remove the retaining screw holding the battery door in place and slide the door towards the bottom of the unit 2 Gently pu
5. certified or listed as Hospital Grade by PARA SYSTEMS or any other organization Therefore these units do not meet the requirements for use in direct patient care 3 MINUTI POWER SUPPLIES EZMAN Arros ann PAN Noicators INDICATORS oost buck FRONT PANEL E replace fault overload battery MINUTESEMAN Pro 1400 front panel l Press and release the on off test button after one beep to turn the unit on or off O see section 4 y online on battery boost and buck The online on battery boost and buck LED illuminates in a steady state when the UPS is on and supplying AC power to the load blinks and sounds the audible alarm when supplying battery power to the load blinks with no audible alarm when the automatic voltage regulator is in operation The fault LED illuminates when the UPS has detected an internal fault contact Minuteman technical support The overload LED illuminates when the loads connected to the Ups exceed the UPS power rating see section 4 The replace battery LED illuminates when the UPS has detected that battery replacement is required see section 6 B MINUTEMAN UNINTERRUPTIBLE POWER SUPPLIES Interface Port Circuit Breaker Pro 1400 rear panel REAR PANEL 120 vac models shown The RJ 45 RJ 11 modular connectors are used for 10 Base T network single line telephone surge protection see section 3 The comput
6. 10 Base T surge protection let through as a percentage of an applied 6 kV 1 2 50 us 500 SPA a8 20 us test Telephone line surge protection let through as a percentage of an applied 6 kV 1 2 50 lt 1 us 500 a 8 20 us test Operating temperature 0 to 40 degrees C 32 to 104 degrees F Storage temperature see Section 11 15 to 45 degrees C 5 to 113 degrees F Operating and storage relative humidity 0 to 95 non condensing Operating elevation Oto 3 000 m 0 to 10 000 ft Storage elevation 0 to 15 000 m 0 to 50 000 ft Electromagnetic immunity IEC 801 2 level IV 801 4 level IV 801 5 level III Audible noise at 1 m 3ft 45dBA Size H x W x D 222x22 8x21 6cm 30 5x31 1x28 6 cm 1 12 0x12 25x 8 65 x 9 0 x 8 5 in 1125in 5 8 10 2 11 2 17 8 19 2 244 25 8 ight ippi 6 9 8 Kg 7 5 8 4 Kg Weight Net Shipping 154 176 16 4 18 6 Kg Kg Kg Lb Lb 224 39 3 42 4 537 24 7 Lb Lb 56 8 Lb Safety and approvals Listed to UL 1778 Compliance to CSA 22 2 EMC Verification FCC Class B certified 13 I ETIUTE MINUTEEMAN UNINTERRUPTIBLE POWER SUPPLIES FIGURABLE PARAMETERS KeU amp SETTINGS These items require optional software or hardware FUNCTION FACTORY DEFAULT USER CHOICES DESCRIPTION UPS ID Pro Series Up to 64 characters to Use this function to uniquely define the UPS identify the UPS in your net work configuration
7. 320VA s20VA 7oova 100VA h 400VA Acceptable input voltage 0 160 0 282 VAC Input voltage on line operation 85 152 170 285 VAC Output voltage 105 136 210 250 VAC Nominal input frequency 50 or 60 Hz autosensing Input protection Resettable circuit breaker Frequency limits on line operation 50 or 60 Hz 5 Transfer time 2 4 ms typical Maximum load 320VA 520VA 700VA 4000VA 1400VA 208W 338W 455W 670W 950W On battery output voltage 115 230 VAC On battery frequency 50 or 60 Hz 0 Hz unless synchronized to utility during brownout On battery waveshape Simulate sine wave one time 8 20 us waveform Protection Overcurrent and short circuit protected latching shutdown on overload Surge energy rating 500 J 440J 500 J 440J one time 10 1000 us waveform Surge current capability 19 5 kAmps total 39 kAmps total Surge response time Surge voltage let through percentage of applied ANSI C62 41 Cat A 6 V test waveform Ons instantaneous normal mode 5 ns common mode lt 5 lt 0 5 Noise filter Normal and common mode EMI RFI suppression Battery Type Spill proof maintenance free user replaceable sealed lead acid one 12v 11 two 12v Ah 11Ah two 12v 17 Ah one 12v 7 Ah Typical battery life 3to 6 years depending on the number of discharge cycles and ambient temp Typical recharge time 2 to 5 hours from total discharge
8. CC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Department of Communications These limits are designed to provide reasonable protection against such interference in a residential instal lation This equipment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equipment may cause interference to radio and television reception If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Re orient the receiving antenna Relocate the computer with respect to the receiver Move the computer away from the receiver Plug the computer into a different outlet so that the computer and receiver are on different branch circuits Shielded communications interface cables must be used with this product WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment Receiving Inspection After removing your Minuteman UPS from its carton it should be inspected for damage that may have occurred in shipping Immediately notify the carrier and place of purchase if any damage is found Warranty claims for dama
9. DED HEREIN PARA SYSTEMS MAKES NO WARRANTIES EX PRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation of implied warranties therefore the aforesaid limitation s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically Para Systems is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data cost of substitutes claims by third parties or otherwise The sole and exclusive remedy for breach of any warranty expressed or implied concerning Para Systems s products and the only obligation of Para Systems hereunder shall be the repair or replacement of defective equipment components or parts or at Para Systems s option refund of the purchase price or substitution with an equivalent replacement product This warranty gives you specific legal rights and you may also have other rights which vary from state to state Longer term and F O B job site warranties are available at extra cost Contact Para Systems 1 972 446 7363 for details 15
10. S via the screws on the connector housing Connect the other end of the cable to the device that will be monitoring controlling the UPS NOTE CONNECTING TO THE COMPUTER INTERFACE PORTIS OPTIONAL THE UPS WORKS PROPERLY WITHOUT A CONNECTION TELEPHONE NETWORK SURGE PROTECTION CONNECTION OPTIONAL Connect a single line telephone or a 10 Base T network line to the protection sockets on the rear of the UPS This connection will require another length of telephone or network cable The cable coming from the telephone service or networked system is connected to the port marked IN the OUT port is connected to the equipment to be protected NOTE CONNECTING TO THE TELEPHONE NETWORK SURGE PROTECTION CONNECTION IS OPTIONAL THE UPS WORKS PROPERLY WITHOUT A CONNECTION CHECKING THE SITE WIRING FAULT 120 VAC models only After plugging in the UPS check the site wiring fault SWF LED on the rear of the unit If the LED is illuminated the UPS is plugged into an improperly wired AC outlet CAUTION IF THE UPS INDICATES A SITE WIRING FAULT HAVE A QUALIFIED ELECTRICIAN CORRECT THE PROBLEM CHARGING THE BATTERY The PRO Series UPS s will charge the internal batteries whenever the unit is connected to an AC source It is recommended that the UPS batteries be charged for a minimum of 4 hours before use The UPS may be used immediately however the on battery run time may be less than normally expected CONNECTING YOUR EQUIPMENT P
11. ae Incorrect service wirin Have a qualified electrician The Site Wiring Fault g correct the service wiring LED is illuminated The Online On The UPS is being controlled via Disconnect the computer cable from the UPS and press the On i its computer port battery LED is CHR button momentarily If UPS works illuminated but there normally software has control of is no output the UPS UPS does not provide The batteries may be weak or Charge the batteries for 8 hours expected backup time at the end of useful service and retest If the backup time is still less than expected the batteries may need to be replaced even though the replace battery LED is not Replace battery LED is Weak or bad batteries bad bat eck battery connection and illuminated tery connection or replace the batteries Follow battery replacement procedures in section 6 The UPS occaisionally Normal operation The UPS is performing its intended emits a beep function MINUTEEMAN UNINTERRUPTIBLE POWER SUPPLIES Um uoc THE BATTERY REPLACING THE BATTERY The PRO Series UPS has an easy to replace hot swappable battery s Please read the following warning statements before attempting to service the battery s WARNING tnis UNINTERRUPTIBLE POWER SOURCE CONTAINS POTENTIALLY HAZARDOUS VOLTAGES DO NOT ATTEMPT TO DISASSEMBLE THE UNIT BEYOND BATTERY REPLACEMENT PROCEDURES BELOW EXCEPT FOR THE BATTERY THIS UPS CONTAINS NO USER SERVICABLE PARTS
12. er interface port is for UPS monitoring and control see section 3 The site wiring fault LED illuminates when the UPS detects an improperly wired AC power outlet 120 vac MODELS ONLY see section 3 The output power receptacles are NEMA 5 15R type IEC output sockets on 230 VAC models The input power cord has a NEMA 5 15P connector IEC input socket on 230 VAC models The input circuit breaker will trip in the event the load exceeds the UPS s power rating AE anon EW INSTALLATION PLACEMENT Install the UPS in a temperature controlled environment that is free of conductive contami nants Select a location which will provide good air circulation for the UPS at all times Avoid locations near heating devices water or excessive humidity or where the UPS is exposed to direct sunlight Route power cords so they cannot be walked on or damaged MINUTEEMAN UNINTERRUPTIBLE POWER SUPPLIES CONNECTING TO AN AC SOURCE Plug the UPS into a two pole three wire grounded receptacle only Do not use extension cords or adapter plugs COMPUTER INTERFACE CONNECTION OPTIONAL Minuteman Power Management software and interface cables kits can be used with the Pro 320 and larger units Use only Minuteman or Minuteman approved interface cables with these UPS s Connect the interface cable to the 9 pin computer interface port on the rear of the UPS Secure the connector to the UP
13. eset automatically to provide a warning at the next power failure COMMUNICATIONS PORT The communications port is a standard DB9 female with both RS232 and simulated contact closure capability The Pro series units will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port To change the port configuration requires the unit be turned off and restarted with the desired cable connected The pinout for the port is depicted per the chart below Pin 1 Not used Pin 2 TXD Pin 3 RXD and receive ups shutdown command Pin 4 Simulated contact closure AC fail NO Pin 5 Ground Pin 6 Simulated contact closure low battery warning NO Pin 7 Simulated contact closure AC fail NC Pin 8 AC fail signal high to low signal Pin 9 Instant off pull and hold this pin low to turn off output receptacles B MINUTEMAN UNINTERRUPTIBLE POWER SUPPLIES VA snoornc EW TROUBLESHOOTING CHART Symptom Possible Cause What To Do UPS will not t On Off Test button not Press On button momentarily WML UON pushed one beep to start UPS UPS operates in Input AC breaker is tripped Reset circuit breaker by pressing battery mode only the plunger back in If circuit even though there is breaker trips after UPS starts up normal AC present reduce the load on the UPS Fault LED is illuminated UPS has detected an internal Call for service fault
14. ge caused by the carrier will not be honored B MINUTEEEMAN UNINTERRUPTIBLE POWER SUPPLIES The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage In the unlikely case that the UPS needs to be returned to Minuteman please use the original packing material Since Minuteman is not responsible for shipping damage incurred when the system is returned the original packing material is inexpensive insurance PLEASE SAVE THE PACKING MATERIALS WARNING Risk OF ELECTRICAL SHOCK HAZARDOUS LIVE PARTS INSIDE THIS POWER SUPPLY ARE ENERGIZED FROM THE BATTERY EVEN WHEN THE AC INPUT POWER IS DISCONNECTED TO DE ENERGIZE THE OUTPUTS OF THE UPS 1 IF THE UPS IS ON PRESS THE ON OFF BUTTON FOR 1 SECOND 2 DISCONNECT THE UPS FROM THE AC POWER OUTLET 3 TODEENERGIZE THE UPS COMPLETELY DISCONNECT THE BATTERY SEE SECTION 6 FOR INSTRUCTIONS CAUTION TOREDUCE THE RISK OF ELECTRICAL SHOCK IN CONDI TIONS WHERE LOAD EQUIPMENT GROUNDING CANNOT BE VERIFIED DISCON NECT THE UPS FROM THE AC POWER OUTLET BEFORE INSTALLING A COM PUTER INTERFACE CABLE RECONNECT THE POWER CORD ONLY AFTER ALL SIGNALING CONNECTIONS ARE MADE CAUTION CONNECT THE UPS TO ATWO POLE THREE WIRE GROUND ING AC POWER OUTLET THE RECEPTACLE MUST BE CONNECTED TO APPROPRI ATE BRANCH PROTECTION CIRCUIT BREAKER OR FUSE CONNECTION TO ANY OTHER TYPE OF RECEPTACLE MAY RESULT IN A SHOCK HAZARD AND VIOLATE LOCAL ELECTRICAL CODES
15. he battery reserve runs low This continues until AC returns or the UPS shuts down from battery exhaustion MINUTEEMAN UNINTERRUPTIBLE POWER SUPPLIES Battery Backup Rear Panel Switch Functions USER NOTES Battery Backup During normal AC operation the rear panel switch may be used to change the low voltage transfer level This voltage is the voltage at which the unit switches from normal operation to battery mode operation The transfer point is changed by pressing and holding the switch until the switch level desired is achieved The factory default level is 85 VAC international version is 170VAC 1 Press and hold the switch until the unit sounds the audible alarm one time to change the level to 80 VAC 160vac 2 Press and hold the switch until the unit sounds the audible alarm twice sequentially to change the level to 75 VAC 150VAC 3 Press and hold the switch until the unit sounds the audible alarm three times sequentially to reset to default setting While operating in the battery backup mode the rear panel switch may be used to silence the audible alarm Press and hold the switch until the unit sounds the audible alarm once to silence the audible alarm The audible will reset and provide an alarm if the unit batteries are nearing depletion This is referred to as the low battery warning alarm When utility power returns and the unit switches to normal AC mode the audible alarm will r
16. le BEFORE calling technical support A Your Name and address Where and when the unit was purchased All of the model information on the rear of your Pro Series UPS Any information on the failure including LEDs that may be illuminated A description of the protected equipment including model numbers if possible A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Material Authorization Number RMA G If the UPS is under warranty the repairs will be done at no charge If not there will be a charge for repair mmoostu 4 Pack the UPS in its original packaging If the original packaging is no longer available ask the technical support technician about obtaining a new set It is important to pack the UPS properly in order to avoid damage in transit Never use Styrofoam beads for a packing material A Include a letter with your name address day time phone number RMA number a copy of your original sales receipt and a brief description of the trouble 5 Mark the RMA on the outside of all packages The factory cannot accept any package without the RMA marked on the outside 6 Return the UPS by insured prepaid carrier to Minuteman Para Systems Inc 1455 LeMay Drive Carrollton Tx 75007 CIFICATIONS NOTE 230VAC Specs Shown In
17. ll out the battery by grasping the battery removal tab 3 Disconnect the two wires disconnect the connector on the 1400 va unit connecting the battery to the UPS Pull back straight on the connector while wiggling the connector from side to side E m 4 Connect the new battery in place of the old one ensuring that black wire is connected to the negative terminal and the red wire is connected to the positive terminal the Pro 1400 connectors are keyed Small sparks at the battery connection are normal 5 Place the new battery in the case taking care not to pinch any wires 6 Slide the battery door back into its slot and replace the retaining screw 7 Dispose of the battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery See new battery instructions for more info Pro 1400 replace 11 MINUTEEMAN UNINTERRUPTIBLE POWER SUPPLIES opt Ns SERVICE FAV IF THE UPS REQUIRES SERVICE 1 Use the TROUBLESHOOTING section 5 to eliminate obvious causes 2 Verify that no circuit breakers are tripped A tripped circuit breaker is the most common problem 3 Call your dealer for assistance If you cannot reach your dealer or if he cannot resolve the problem call or FAX Minuteman Technical Support at the following numbers Voice phone 972 446 7363 FAX line 972 446 9011 Please have the following information availab
18. lug the equipment into the receptacles on the rear of the unit Insure that you do not exceed the maximum output rating of the UPS refer to UPS back panel or electrical specifications in this manual CAUTION DO NOT CONNECT A LASER PRINTER TO THE BATTERY BACKUP RECEPTACLES ON THE UPS UNLESS THE UPS IS RATED 2000VA OR N GREATER A LASER PRINTER DRAWS SIGNIFICANTLY MORE POWER WHEN PRINTING THAN AT IDLE AND MAY OVERLOAD THE UPS B MINUTEEEMAN UNINTERRUPTIBLE POWER SUPPLIES AOSERATION a AW TURNING THE UNIT ON OFF On Off TestSwitch Press and release the switch after one beep to turn the unit on and supply power to the load The load are immediately powered while the UPS runs a 5 second self test Press and release the switch to turn the unit off The UPS will continue to charge the batteries whenever it is plugged in and there is AC present SELF TEST On Off Test Switch The self test feature is useful to verify the correct operation of the UPS and the condition of the battery With the UPS plugged into normal AC press and hold the ON OFF TEST SWITCH for 4 seconds four beeps then release the switch The UPS will perform a five second self test Note The UPS will automatically perform a self test on startup and every two weeks During the self test the UPS will switch to battery power and the on line LED will blink and the audible alarm will sound as well The length of the test that automatically is performed eve
19. ry two weeks is longer than the start up or user invoked test This test will run for approximately fifteen seconds to measure the battery s capability to provide an acceptable amount of runtime If the UPS fails a self test one of the LED s will remain illuminated indicating the type of problem see section 5 Troubleshooting ALARMS ON BATTERY When the UPS is operating on the batteries the on line LED will blink and the audible alarm will sound every 10 seconds The alarm will stop once the UPS returns to on line operation UPS FAULT When the UPS detects a hardware fault the fault LED will illuminate and the UPS will emit a sustained tone The fault condition can be re set by turning the UPS off and then on see section 5 for more information OVERLOAD When the amount of load attached to the UPS exceeds its power rating the overload LED will illuminate and the UPS will emit a sustained tone This alarm will remain on until the excess load is removed or the UPS s self protection circuit shuts the UPS down REPLACE BATTERY The UPS automatically tests the battery s condition and will illuminate the replace battery LED and emit a short beep This tone will be repeated every hour until the battery passes a self test It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a replace battery condition LOW BATTERY WARNING The UPS will emit two consecutive beepsevery five seconds when t
20. workmanship for a period of three years from the date of manufacture For equipment sites within the United States and Canada this warranty covers repair or replacement of defective equipment at the discretion of Para Systems Repair will be from the nearest authorized service center Replacement parts and warranty labor will be borne by Para Systems For equipment located outside of the United States and Canada Para Systems only covers faulty parts Para Systems products repaired or replaced pursuant to this warranty shall be warranted for the unexpired portion of the warranty applying to the original product This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase The warranty shall be void if a the equipment is damaged by the customer is improperly used is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications b the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel or c has been used in a manner contrary to the product s operating manual or other written instructions Any technical advice furnished before or after delivery in regard to use or application of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances but it is used at the recipient s sole risk EXCEPT AS PROVI
Download Pdf Manuals
Related Search
Related Contents
LED BEAM Moving Head 4in1 MH StarTech.com 50 ft Premium Composite Video Cable Inspiration® 8 User`s Manual - White Plains Public Schools INFORMATIONEN ZUR EINHALTUNG MODEL MRG20 - Pentair Water Literature Whirlpool FGS385Y User's Manual Operating Instructions Submersible sewage pumps User manual Copyright © All rights reserved.