Home
        White Rodgers 1F85-0422 Thermostat User Manual
         Contents
1.  Carefully line the thermostat up with the base and snap  into place     Batteries   2    AA    alkaline batteries are included with the thermostat    To install the batteries  pull the battery door as shown by the  arrow and lift open  Using the polarity indicated inside the bat   tery door  insert the batteries  To close the battery door  swing  the door down while pulling in the direction of arrow  Once  fully down  snap the door back into position  To replace the  batteries  set system to OFF     WIRING CONNECTIONS       Figure 1     Battery door shown open       AA    Alkaline Batteries       Thermostat can be powered by system AC power or Battery   If Gm is displayed  the thermostat is battery powered  If mm  is not displayed  thermostat is system powered with optional  battery back up  When battery power remaining is approxi   mately half  the    will be displayed  When    Change     gt    is displayed  install fresh    AA    alkaline batteries immediately   For best results  replace all batteries with new premium brand  alkaline batteries such as Duracell   or Energizer    We recom   mend replacing batteries every 2 years  If the home is going  to be unoccupied for an extended period  over 3 months  and  fir is displayed  the batteries should be replaced before  leaving  When less than two months of battery life remain  the  setpoint temperature will offset by 10 degrees  10 degrees  cooler in Heat mode   10 degrees warmer in Cool mode   If  offset occurs  the normal 
2.  and temperatures are set for all program periods on  that day    10  Press SCHEDULE to the next day and repeat steps 2  through 9    11  When programming is complete and all of the times and  temperatures match your desired heating schedule  press  RUN  The thermostat will now run your program     Enter the Cooling Program   1  Press SYSTEM button to select    Cool    in the system  switch area indicating the active mode being pro   grammed    2  Follow Enter Heating Program instructions for entering  cooling times and temperatures     Energy Saving ENERGY STAR   Factory Pre Program  The programmable thermostats are programmed with the energy saving settings shown in the table below for all days of the  week  If this program suits your needs  simply set the thermostat clock and press the RUN button  The table below shows the    factory set heating and cooling schedule for all days of the week                          Wake Up Leave For Work Return Home Go To Bed   Period 1   Period 2   Period 3   Period 4   Heating    gt  og AM   70  F   8 00AM   62  F   5 00PM   70  F   10 00PM   62  F  Program  Cooling      i o   o   o  Program   6 00AM   75  F   8 00AM   83    5 00PM   75  F   10 00 PM   78  F                      Planning Your Program     Important   The Heating and Cooling Program schedules below allow you  to pencil in your own program times and temperatures    The thermostat comes configured for 7 day programming   and can also be configured for 5 1 1 day programming  
3.  default setting is  medium  ME   For Emer  Aux  the default setting is fast  cycle  FA   To change cycle rate  press the or  key     Cycle rate differentials for different settings are     Fast Medium Slow  MODE FA ME SL  Heat  SS1  MS2  0 4  F 06F 1 7  F  Cool  SS1  MS2  0 9  F 1 2  F 1 7  F  Heat Pump  HP1  HP2  0 9  F 1 2  F 1 7  F  Emer  HP1  HP2  0 6  F   12  F    8     9     10     11     12     Select Compressor Lockout CL OFF or ON     Select   ing CL ON will cause the thermostat to wait 5 minutes  between cooling cycles  This is intended to help protect  the compressor from short cycling  Some newer com   pressors already have a time delay built in and do not  require this feature  Your compressor manufacturer can  tell you if the lockout feature is already present in their  system  When the thermostat compressor time delay oc   curs  it will flash the setpoint for up to five minutes     System Mode Configuration     This thermostat is  configured for Heat and Cool  SYSTEM switch with Cool   Off  Heat  default  It can also be configured for Heat and  Cool with Auto changeover  Heat  Auto  Cool  Off   Heat  only with fan  Off  Heat   Heat only without fan  Auto only   Auto  Off   and Cool only  Cool  Off      Select Backlight Display     The display backlight im   proves display contrast in low lighting conditions  When  the    C    terminal is powered  selecting backlight CdL ON  will keep the light on continuously  Select backlight OFF  will turn the light on momen
4.  menu will be skipped     16  amp  17  Select Automatic Schedule     With just one touch    of the AUTO SCHEDULE button this feature allows   you to program a desired comfort temperature into all  the program periods along with a 6   set back for night  periods of both Heat and Cool programs  Factory default  is    On    for both  When Heat AS On and Cool AS On   are activated while in Heat or Cool mode  select desired  setpoint temperature and press AUTO SCHEDULE  This  value will be copied into all the morning  day and evening  program periods  The night program periods will have a  6  F set back     18  amp  19  Select Fast Second Stage ON or OFF     Heat    pump or Multi stage only  in the run mode  with the fast  Heat feature enabled  FA Heat On   if the Heat setpoint  temperature is manually raised by 3  F  2  C  or more  above the actual temperature using the second  stage will energize immediately  With FA OFF  second  stage will not energize until the setpoint temperature is  1  F or more above actual temperature for more than ten  minutes  The Fast Cool feature  FA Cool  provides the  same controls when the setpoint temperature is lowered     7    INSTALLER CONFIGURATION MENU    20  Select Daylight Saving Time Calculation     This feature  will allow the thermostat to calculate the DST automati   cally and apply it to the Real Time Clock display  Default  On  Use or buttons to select the feature OFF    21  Select Filter Replacement Reminder and Set Run  Time     Sel
5.  service person can instruct you on how  to test the Heat Cool system for correct operation  If the  system operates correctly  replace the thermostat        Thermostat Setting  amp   Thermostat Thermometer  Disagree      Thermostat thermometer setting    requires adjustment     The thermometer can be adjusted     4 degrees  See  Temperature Display Adjustment in the Configuration Menu  section        Furnace  Air Conditioner   Cycles Too Fast or Too  Slow  narrow or wide  temperature swing          The location of the thermostat and or    the size of the Heating System may  be influencing the cycle rate        Digital thermostats provide precise control and cycle faster  than older mechanical models  The system turns on and off  more frequently but runs for a shorter time so there is no  increase in energy use  If you would like an increased cycle  time  choose SL for slow cycle in the Configuration menu   step 6  heat   7  cool  or 8  heat pump   If an acceptable  cycle rate is not achieved  contact a local HVAC service  person for additional suggestions     11    HOMEOWNER HELP LINE  1 800 284 2925    White Rodgers is a division White K  of Emerson Electric Co  Rodgers  S    The Emerson logo is a  trademark and service mark EM ERSO N     of Emerson Electric Co  www white rodgers com    
6.  setting for two hours minimum  or until the next programmed time  To cancel the temporary  setting at any time and return to the program  press RUN  If  the SYSTEM button is pressed to select AUTO the thermostat  will change to Heat or Cool  whichever ran last  If it switches  to heat but you want cool  or it changes to cool but you want  heat  press both and buttons simultaneously to  change to the other mode        5  Additional presses of TIME will advance the display to  show the year  month and date of month  Press the  or button to change the display to the correct set   ting for each    6  Press RUN to exit the TIME mode     PROGRAMMING    Enter the Heating Program   1  Press SYSTEM button to select    Heat    in the system  switch area indicating the active mode being pro   grammed    2  Press the MENU button and then press SCHEDULE    3  The top of the display will show the day s  being pro   grammed  The time and temperature  flashing  are also  displayed     1    will also be displayed to indicate the pe   riod    4  Press or button to change the temperature to  your selected temperature for the 1st heating period    5  Press TIME button  time will flash    6  Press or button to adjust the start time for the  1st period    7  The time will change in 15 minute increments    8  After you have set the time and the temperature for  the period to begin  press SCHEDULE to advance to the  next program period     9  Repeat steps 2 through 8 until all of the program times 
7.  temperature and turn  off  The room temperature will actually be higher than  the thermostat displays but the reduction in humidity will  allow comfort at the slightly higher temperature     To turn this feature on in the Cool mode press Cool  Savings  The display will show    Save    next to the  setpoint temperature  When Cool Savings is making ad   justments to the room temperature display    Save    will be  flashing and the displayed room temperature may vary  within the adjustment range you selected     If    Save    is not displayed and this feature is OFF  no  change will occur when the cooling system is continu   ously running during periods of high demand     Energy Management Recovery  Energy Management  Recovery  E  On enables the thermostat to start heating  or cooling early to make the building temperature reach  the program setpoint at the time you specify  Heating will  start 5 minutes early for every 1   of temperature required  to reach setpoint     Example  E On is selected and your heating is pro   grammed to 65   at night and 70   at 7 AM  If the build   ing temperature is 65    the difference between 65   and  70   is 5    Allowing 5 minutes per degree  the thermostat  setpoint will change to 70   at 6 35 AM  Cooling allows  more time per degree  because it takes longer to reach  set temperature     5  6  amp  7  Cycle Rate Selection     The factory default setting    for Heat and Cool modes  SS1  MS2  is medium cycle   ME   For Heat Pump  HP1  HP2  the
8. STALLER CONFIGURATION MENU                         MENU PRESS DISPLAYED Press or to  REF    HP   SS  BUTTON   FACTORY DEFAULT  select from listed options COMMENTS  1 l1 1   MENU  MS 2  HP 1  HP 2  SS 1 Selects Multi Stage  MS 2 No Heat Pump    Heat Pump 1  HP 1  1 compressor    or Single Stage  SS 1   Heat Pump 2  HP 2  2  compressor or 2 speed compressor   2 2   2   MENU    GAS  for SS or MS ELE GAS setting  furnace controls the blower   ELE  for HP ELE setting  thermostat controls the blower  3 3   3   MENU CS  0  1 2 3 4 5 6 Selects Cool Savings   Disabled  Value 1  low  to 6  high   Value 0 Disables Feature  4 4   4   MENU E  On  OFF Selecis Energy Management Recovery  EMR   On or OFF   5       5   MENU CR Heat  ME  SL  FA Adjustable Anticipation   Selects heating cycle rate for MS or SS  6 5         MENU CR Heat Pump SL  FA Adjustable Anticipation  Heat Pump   only   ME  when heat pump selected in  1   7 6   6   MENU CR Cool  ME  SL  FA Adjustable Anticipation  Selects the cycle rate for  or cooling  only when MS 2 or SS 1 is selected in  CR Emer  FA  SL item 1   or Selects the cycle rate for Emergency  mode and Auxiliary stage if Heat Pump is  selected in item 1   8 7   7   MENU CL  OFF  CL On Compressor Lockout Time  9 8   8   MENU Heat Auto Heat Cool Off  System Mode Configuration  Cool Off Heat Off with Fan icon  with Automatic Changeover capability    Heat Off without Fan icon  Cool Off  Auto Off                                  10   9   9   MENU dL  On  dL OFF Sele
9. White y  Rodgers     Save these instructions for future use     FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS                                                 Blue 4    Universal Thermostat with    Automatic Heat Cool Changeover Option    Single Stage  Multi Stage or Heat Pump  Installation and Operating Instructions for Model        Model    Programming Choices                   CAREFULLY BEFORE INSTALLING OR OPERATING 1F85 0477 7 Day 5 1 1 Day  THIS CONTROL COULD CAUSE PERSONAL INJURY  AND OR PROPERTY DAMAGE   APPLICATIONS  THERMOSTAT APPLICATION GUIDE  D   1F85 0477 Thermostat  escription  Heat Pump  No Aux  or Emergency Heat  Yes  Heat Pump  with Aux  or Emergency Heat  Yes  Systems with up to 2 Stages Heat  2 Stages Cool Yes  Heat Only Systems  with optional fan switch  Yes  Millivolt Heat Only Systems     Floor or Wall Furnaces Yes OO  Cool Only Systems Yes   n   Gas or Oil Heat Yes  Electric Furnace Yes i          EMERSON  Hydronic  Hot Water  Zone Heat     2 Wires Yes    Hydronic  Hot Water  Zone Heat     3 Wires Yes  SPECIFICATIONS  Electrical Rating   Battery Power            0  0  00ee0eennna renna mV to 30 VAC  NEC Class II  50 60 Hz or DC  Input  210 TS pe 20 to 30 VAC    Terminal A ska aan    1 5 A per terminal  2 5A maximum all terminals combined    Setpoint Rah Gekregen es 45   to 90  F  7   to 32  C     Differential  Single Stage                  0 20000ernr  Differential  Heat Pump        Heat 0 6  F  Cool 1 2  F  adjustable   Heat 1 2  F  Cool 1 2  F  adjustab
10. ccurs  If the heat works intermittently  contact the furnace manufacturer or local HVAC service  person for assistance   3  Heating system requires service or Diagnostic  Set SYSTEM Switch to HEAT and raise the  thermostat requires replacement  setpoint above room temperature  Within a few seconds  the thermostat should make a soft click sound  This sound  usually indicates the thermostat is operating properly  If  the thermostat does not click  try the reset operation listed  above  If the thermostat does not click after being reset  contact your heating and cooling service person or place  of purchase for a replacement  If the thermostat clicks   contact the furnace manufacturer or a HVAC service  person to verify the heating is operating correctly   No Cool 1  Cooling system requires service or Same as diagnostic for No Heat condition except set the    Heat  Cool or Fan  Runs Constantly     gt  OO        thermostat requires replacement       Possible short in wiring      Possible short in thermostat      Possible short in heat cool fan system     FAN Switch set to Fan ON     thermostat to COOL and lower the setpoint below the room  temperature  There may be up to a five minute delay before  the thermostat clicks in Cooling     Check each wire connection to verify they are not shorted  or touching together  No bare wire should stick out from  under terminal block  Try resetting the thermostat as  described above  If the condition persists the manufacturer  of your system or
11. cts Display Light On or OFF  11   10  10  MENU 0 1 HI  2 HI  3 HI  4 HI  Adjustable Ambient Temperature Display   current temperature    1LO 2LO 3LO 4LO  12   11  11  MENU oF GC Selects Fahrenheit Celsius Temperature Display  13   12   12  MENU L Heat L 62 to L 89 Selects Limited HEAT Range   90   14   13  13  MENU L Cool L 46 to L 82 Selects Limited COOL Range   45   15   14  14  MENU P7 P3 Defaults for 7 day programming  P7  or 5 1 1  day programming  P3  is available  16   15 15   MENU Heat AS  On  OFF Automatic Schedule for heat mode   17   16  16  MENU Cool AS  On  OFF Automatic Schedule for cool mode   18  17        MENU Heat FA  On  OFF Fast Heat option may be disabled by  selecting OFF  NA to SS config   19  18        MENU Cool FA  On  OFF Fast Cool option may be disabled by    selecting OFF  NA to SS config   NA to Heat only system              20   19  17  MENU dS  On  OFF Selects Automatic daylight Savings Time option  On or OFF   21  20  18  MENU   Change Filter  OFF  On Selects Filter Change out Indicator On or OFF   MENU   Change Filter  200 h  25 1975 h Change Filter time in 25 hour increments  This  menu only appears if On is selected in above   22   21 19  MENU Cool On  o  Heat On  b  Selects operation of the reversing valve terminal   O B  output as an O or B terminal   23  22  20  RUN Returns to Normal Operation                               INSTALLER CONFIGURATION MENU    1     2     3     4     This control can be configured for     MS 2     Multi Stage S
12. ect the    Change Filter    reminder On or  OFF  If selected On  press MENU to select the time  period from 25 to 1975 hours in 25 hours increments    In a typical system  200 hours  default  of run time is  approximately 30 days  After the selected time of blower  operation  the thermostat will display    Change Filter     as a reminder to change or clean your air filter  When     Change Filter    is displayed  press MENU or RUN but   ton to clear the display and restart the time to the next  filter change     OPERATING YOUR THERMOSTAT    Choose the Fan Setting  Auto or On    Press the FAN button to Auto or On    Fan Auto is the most commonly selected setting and runs the  fan only when the heating or cooling system is on    Fan On runs the fan continuously for increased air circulation  or to allow additional air cleaning     Choose the System Setting    Heat  Off  Cool  Auto  Emer    Press the SYSTEM button to select    Heat  Thermostat controls only the heating system    Off  Heating and Cooling systems are off    Cool  Thermostat controls only the cooling system    Auto  Auto Changeover is used in areas where both heating  and cooling may be required on the same day  AUTO allows  the thermostat to automatically select heating or cooling  depending on the indoor temperature and the selected heat  and cool temperatures  When using AUTO  be sure to set the  Cooling temperatures more than 1   Fahrenheit higher than  the heating temperature    Em   Heat Pump models  Thermosta
13. ermostat is reset  installer configuration menu    settings and programming will reset to factory settings        function correctly contact your heating cooling service person  or place of purchase     Symptom    If a voltage spike or static discharge blanks out the display  or causes erratic thermostat operation  you can reset the  thermostat by removing the wires from terminals R and C   do not short them together  and removing batteries for 2  minutes  After resetting the thermostat  replace the wires and  batteries  If the thermostat has been reset and still does not    Note  Be sure to review the installer configuration menu    Possible Cause    settings     To reset the programming  clock and configuration settings   press and and the FAN button simultaneously  The  thermostat should go blank and then all segments will be  displayed momentarily     Correction Action       No Heat No Cool No Fan   common problems     i   2   3     Blown fuse or tripped circuit breaker   Furnace power switch to OFF   Furnace blower compartment door or  panel loose or not properly installed     Replace fuse or reset breaker    Turn switch to ON    Replace door panel in proper position to engage safety  interlock or door switch           4  Loose connection to thermostat or Tighten connections   system   No Heat 1  Pilot light not lit  Re light pilot   2  Furnace Lock Out Condition  Heat Many furnaces have safety devices that shut down when  may also be intermittent  a lock out condition o
14. gures 4 6   Refer to equipment manufacturers    instructions for specific    system wiring information     You can configure the thermostat for use with the following    heat pump systems                      Heat Pump 1  et  Fault Indicator  or System  Malfunction  Switch  Heat Pump 2   HP2                       System Malfunction  Module          Energized in  Cool Mode    B  Energized in  Heat  Off   Emergency  Mode       HEAT PUMP TYPE 1  HP 1   Single stage compressor    system  gas or electric backup   HEAT PUMP TYPE 2  HP 2   Multi stage compressor or two    compressor system with gas or electric backup     proper thermostat configuration     Figure 3     Heat Pump Systems    Heat and  Cool Mode    Output    Heat Mode  2nd Stage   Emergency  Mode 2nd  Stage    Blower   Circulator  Fan Energized    Emergency on Call for       1st Stage   Compressor        Single Stage and Multi Stage Connections    Refer to equipment manufacturers    instructions for specific    system wiring information     This thermostat is designed to operate a single transformer    or two transformer system     2nd  Stage   Com   pressor           Mode  1st Stage    Heat or Cool   Set Elect Gas  Option for  Emergency    Heat Mode  3rd Stage   Emergency  Mode 2nd             Jumper    After wiring  see INSTALLER CONFIGURATION section for    NOTE  If your system does  not provide an E connection   jumper W2 to W E to use  the Auxiliary Heat in the  Emergency Mode       Common connection    required f
15. l system shall conform to Class Il circuits per  the NEC code        Remove Old Thermostat   A standard heat cool thermostat consists of three basic parts    1  The cover  which may be either a snap on or hinge type    2  The base  which is removed by loosening all captive  screws    3  The switching subbase  which is removed by unscrewing  the mounting screws that hold it on the wall or adapter  plate  Before removing wires from old thermostat   label each wire with the terminal designation from  which it was attached  Disconnect the wires from the  old thermostat one at a time  Do not let wires fall back  into the wall     Installing New Thermostat   1  Pull the thermostat body off the thermostat base  Forcing  or prying on the thermostat will cause damage to the unit    2  Place base over hole in wall and mark mounting hole  locations on wall using base as a template    3  Move base out of the way  Drill mounting holes  If you  are using existing mounting holes and the holes drilled  are too large and do not allow you to tighten base snug   ly  use plastic screw anchors to secure the base    4  Fasten base snugly to wall using mounting holes shown  in Figure 2 and two mounting screws  Leveling is for  appearance only and will not affect thermostat operation    5  Connect wires to terminal block on base    6  Push excess wire into wall and plug hole with a fire re   sistant material  such as fiberglass insulation  to prevent  drafts from affecting thermostat operation    7 
16. le     Operating AMDbIeNt          ec eeeeeeeseeeeeeeeeseeeeeeeeneeeenees 32   to  105  F  0   to  41  C   Operating Humidity   20 0 0    eee sseeeeseeeseeteseeeneetenees 90  non condensing max   Shipping Temperature Range     40   to  150  F   20   to  65  C   Dimensions Thermostat           ccceesseeeeeseeeeesneeeeneees 3 7 8 H x 5 1 8 W x 1 1 4   D    A CAUTION    To prevent electrical shock and or equipment damage     disconnect electric power to system at main fuse or  circuit breaker box until installation is complete        Index Page       Installation 2       Wiring Connections       Wiring Diagrams  Thermostat Quick Reference       Installer Configuration Menu       Operating Your Thermostat           CO  OD  oO  WP    Programming                     Troubleshooting             ATTENTION  MERCURY NOTICE  This product does not contain mercury  However  this product  may replace a product that contains mercury     Mercury and products containing mercury must not be  discarded in household trash  Do not touch any spilled  mercury  Wearing non absorbent gloves  clean up any spilled  mercury and place in a sealed container  For proper disposal  of a product containing mercury or a sealed container  Refer  to www white rodgers com for location to send product  containing mercury                 s  EMERSON   Clima    te Technologie    PART NO  37 7050A    www white rodgers com    0933    INSTALLATION  A WARNING    Thermostat installation and all components of the    contro
17. onstantly Heat if mon   Multi  in Heat  Off  Heat Mode   configured  Stage 2 Emergency 2nd Stage   for Electric   MS2  Mode Heat                       e  NEUTRAL 120VAC  120VAC         e COOLING   _  HOT  CLASS II  HEATING TRANSFORMER  CLASS II  TRANSFORMER  Figure 6     3 Wire  SPDT  Heat Only Zone Valve Wiring  Jumper  Single Stage 24 Volt Constant  3 wire tae   Blower Circulator  Hot  ar 24 Volt  Zone Valve  6  Fan Energized Heat se    Com   application  5  og mon   120VAC        CLASS II  TRANSFORMER    THERMOSTAT QUICK REFERENCE    Home Screen Description    Figure 7     Home Screen Display    Battery Level Indicator  Indicating the current power  level of the 2    AA    batteries   Full power remaining   E gt  Half power remaining   Change  gt  The batteries  should be replaced at this time  with 2 new premium brand     AA    Alkaline batteries     See page 2 for more details     wt  ws    Programming and Configuration Items     System On    indicates when heating or cooling stage  is energized     System On  2    indicates when a second  stage is energized   The word    Hold    is displayed when the thermostat is in  the Hold mode     Temp Hold    is displayed when  the thermostat is in a Temporary Hold mode         Displays    Change Filter    when the system has run for  the programmed filter time period as a reminder to  change or clean your filter       Displays    Set    for setpoint when in Run Program mode       Displays System Mode  Heat  Em  Auto  Cool  Off   
18. or    Time    in Menu Mode       Displays Fan Mode  On  Auto  in Menu Mode       Displays    Set Schedule        Schedule     or    Menu       Displays    Save    when Cool Savings    is working       Displays    Heat Pump    when system is configured  as Heat Pump thermostat    Displays    Hold    in programmable mode  When not in  Hold mode  displays    Run    in program run mode        Initially displays    Auto Sched     If Auto Schedule had  been used or disabled  then it displays    Cool Savings  when in the Cool Mode if Cool Savings has been ena   bled in the menu      9            Room Setting    Temperature Temperature     gM  ca    n  Oe  Ve  _    Fan  Indicator    System  Indicator       Figure 8     Programming  amp  Configuration Items       Change  Hi   Filter     3           Heat Pump    System On  2    q Mo Tu W wi  fp Date  Set    TE  LONI    nod FAY o    Month Call For  Service Save    O Year    haosa  Coe a                           SYSTEM   FAN    l moa Em Auta  On Auto        Cool OffTime          Set      Schedule       Menu                                Call For Service    indicates a fault in the heating   cooling system  it does not indicate a fault in the    thermostat     INSTALLER CONFIGURATION MENU    With thermostat in Heat  Cool or Auto  in normal operation  press the Menu button for at least 5 seconds  The display will show  item  1 in the table below  Press Menu button to advance to the next menu item  Press or to change an item option     IN
19. or fault or  malfunction indication     120VAC    CLASS II  TRANSFORMER    SINGLE STAGE  SS 1  gas  oil or electric     MULTI STAGE  MS 2  gas  oil or electric     After wiring  see INSTALLER CONFIGURATION section for    You can configure the thermostat for use with the following    fossil fuel systems     proper thermostat configuration     Figure 4     Single Stage or Multi Stage System  No Heat Pump  with Single Transformer    System    Jumper                 Single  Fault  Indicator  or  System  Malfunction    Switch in             System Malfunction  Module                Emergency    o    Energized Constantly  in Cool Mode    B    Energized Constantly    Heat  Off        Cool Mode  1st Stage                                    Heat  Mode    1st Stage   Heat Mode        Blower   Circulator  Fan Energized  on Call for  Cool  and  Heat if  configured  for Electric       No Output       2nd Stage              Optional   24 Volt   Com    mon          Common connection  required for fault or  malfunction indication     120VAC    CLASS II  TRANSFORMER       WIRING DIAGRAMS    Figure 5     Single Stage or Multi Stage System  No Heat Pump  with Two Transformers    Remove Jumper Wire  Jumper between RH 8 RC    System              Indicator   NOT       Energized Constantly  in Cool Mode    B       Cool Mode  1st Stage    Blower   Circulator  Fan Energized  on Call for  Cool  and                               24 Volt   Hot   Cool       Optional  24 Volt   Com     A USED  Energized C
20. see  configuration section      Factory settings are listed on Monday through Friday  Satur   day and Sunday  If you are re programming a 7 day schedule   pencil in all lines with the times and temperatures you want     If you are re programming a 5 1 1 fill in your own times and  temperatures directly below the factory times and tempera   tures    Keep the following guidelines in mind when planning your  program    e In Heating  lower temperatures will save energy     e In Cooling  higher temperatures will save energy   e If you plan on using Auto Changeover  do not program  the heating higher than the cooling     PROGRAMMING    10    Worksheet for Re Programming 7 Day and 5 1 1 Day Program                                                                                     Heating Wake Up Leave For Work Return Home Go To Bed  Program  Period 1   Period 2   Period 3   Period 4   6 00 AM 70  F 8 00 AM 62  F 5 00 PM 70  F 10 00 PM 62  F  MON  TUE  WED  THU  FRI  6 00 AM 70  F 8 00 AM 62  F 5 00 PM 70  F 10 00 PM 62  F  SAT  6 00 AM 70  F 8 00 AM 62  F 5 00 PM 70  F 10 00 PM 62  F  SUN  Cooling Wake Up Leave For Work Return Home Go To Bed  Program  Period 1   Period 2   Period 3   Period 4   6 00 AM 75  F 8 00 AM 83  F 5 00 PM 75  F 10 00 PM 78  F  MON  TUE  WED  THU  FRI  6 00 AM 15  F 8 00 AM 83  F 5 00 PM 75  F 10 00 PM 78  F  SAT  S  N 6 00 AM 75  F 8 00 AM 83  F 5 00 PM 75  F 10 00 PM 78  F                                  TROUBLESHOOTING    Reset Operation    Note  When th
21. setpoint can be manually reset with  or CY   Another offset will occur within two days if batter   ies are not replaced              Figure 2     Thermostat base and rear view of thermostat                                           Mounting Mounting  Hole      Hole  Place Level      gt    ir a     Place Level  across    j across  Mounting Tabs Mounting Tabs   for appearance only   for appearance only                                                       Refer to equipment manufacturers    instructions for specific system wiring information  After wiring  see CONFIGURATION section  for proper thermostat configuration  Refer to figure 3 through 6 for wiring diagram specifications     TERMINAL DESIGNATION DESCRIPTIONS       Terminal  Designation Description   Listar Heat pump malfunction indicator for systems  with malfunction connection   O T Changeover valve for heat pump energized  constantly in cooling   Bassein Changeover valve for heat pump energized  constantly in heating   Varena Compressor Relay   N Qa ccsreseirs 2nd Stage Compressor       Terminal  Designation Description    Heat Relay Emergency Heat Relay  Stage 1    2nd Stage Heat  3rd Stage Heat in HP 2    Fan Relay   Power for Heating   Power for Cooling   Common wire from secondary side of cooling system  transformer or heat only system transformer   Bassi 3 Wire Zone Valve     Energized when no call for Heat             WIRING DIAGRAMS    Heat Pump Connections    If you do not have a heat pump system  refer to fi
22. t controls only backup  heating system     PROGRAMMING    Set Current Time and Date   1  Press MENU and then TIME button once  The display  will show the hour only    2  Press and hold either the or button until you  reach the correct hour and AM PM designation  AM  begins at midnight  PM begins at noon     3  Press TIME once again  The display window will show  the minutes only    4  Press and hold either the or button until you  reach the correct minutes     22  Select Reversing Valve Output     The O B option is  factory set at    O    position  This will accommodate the  majority of heat pump applications  which require the  changeover relay to be energized in COOL  If the  thermostat you are replacing or the heat pump being  installed with this thermostat requires a    B    terminal  to  energize the changeover relay in HEAT  the O B option  should be set at    B    position     IMPORTANT     Manual Operation  Bypassing the Program   Programmable Thermostats   Press or and then the HOLD button and adjust the  temperature wherever you like  This will override the program   The HOLD feature bypasses the program and allows you   to adjust the temperature manually  as needed  Whatever  temperature you set in HOLD will be maintained 24 hours a  day  until you manually change the temperature or press RUN  to cancel HOLD and resume the programmed schedule     Program Override  Temporary Override    Press or buttons to adjust the temperature  This   will override the temperature
23. tarily after any key is pressed   When the    C    terminal is not powered  the light will be on  momentarily after any key is pressed no matter whether  the backlight is selected ON or OFF     Select Temperature Display Adjustment 4 LO to 4 HI       Allows you to adjust the room temperature display up  to 4   higher or lower  Your thermostat was accurately cali   brated at the factory  but you have the option to change  the display temperature to match your previous thermo   stat  The current or adjusted room temperature will be  displayed    Select F   or C   Readout     Changes the display readout  to Celsius or Fahrenheit as required     13  amp  14  Temperature Limit Range Heat or Cool     This    15     selection sets the maximum HEAT  13  or minimum  COOL  14  temperature for the setpoint range  Select the  limit temperature using the or keys  In the Run  mode  the setpoint temperature will not adjust past the  limit temperature selected  When the limit temperature is  reached  trying to raise or lower the setpoint past the limit  will cause    L    to be displayed in the times digits for about 6  seconds  This feature not available on earlier models     Program Options  Configured for 7 day or 5 1 1 day pro   gramming or non programmable mode  The default set   ting is P7  indicating 7 day programming  The programs  per week can be changed to P3 by pressing the or  keys  A selection of 0 Days for non programmable  will eliminate the need for EMR  and that step in the 
24. ystem  no heat pump    HP 1     Heat Pump with one stage of compressor   HP 2     Heat Pump with two stage compressor or two  compressor system  Gas or Electric backup   SS 1     Single Stage System    GAS or Electric  ELE  fan operation  If the heating sys   tem requires the thermostat to energize the fan  select  ELE  Select GAS if the heating system energizes the fan  on a Call for heat     Select Cool Savings    value     Selects the amount   of adjustment for the Cool Savings    feature in Cool  mode with 1  1    being the least amount of adjustment  and 6  6    being the most amount of adjustment  Default  value is 0 which disables this feature  Selecting a value  greater than 0 will display Cool Savings on the screen  and enable the key for Cool Savings feature  Cool Sav   ings is an optional energy saving feature that can reduce  your cooling costs  It is based on the principal that lower  indoor humidity makes a slightly higher temperature   feel more comfortable  Cool Savings operates during  periods of high demand which normally occur on the  hottest summer days when a cooling system may run   for hours to reach the thermostat setting  Long cooling  run times also lower the indoor humidity  Cool Savings   very slowly  adjusts the setpoint temperature to make the  setpoint closer to the displayed room temperature  to a  maximum of the number of degrees you select  Adjust   ing the setpoint temperature over a long cooling run time  allows the system to reach your set
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
FCS-320-TM Ansaugrauchmelder  Series R Chiller Model RTWD  información pinchar aquí  Mode d`emploi chaudière    ファイアウォールオプション YSL-MC120カタログ  User interface having movable sheet with click  Funny Or Die Presents    Copyright © All rights reserved. 
   Failed to retrieve file