Tripp Lite 2200XLT Power Supply User Manual
Contents
1. LAN Interface DIP Switches to D4 DIP Switches 1 and 2 activate or deactivate remote shutdown through the BASIC Contact Closure Ports See DB9 Port Con il nection on page 4 for which switch controls which port Note DIP Switch 3 has no function DIP Switch 4 serves as the UPS s System Enable Switch Storage amp Service Storage Turn your UPS OFF first engage the ON Standby Switch and release it to place your UPS in the Standby mode then set the System Enable Switch Jumper 4 UPS rear panel to DISABLE down finally disconnect the UPS power cord from the wall outlet If you plan on storing your UPS for an extended period of time recharge the UPS batteries once every three months Follow steps 1 and 3 in the Quick Installation section and allow the UPS to charge from 4 to 6 hours If you leave your UPS batteries discharged for an extended period of time they will suffer permanent loss of capacity Service If returning your UPS to Tripp Lite please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit Enclose a letter describing the symptoms of the problem If the UPS is within the 2 year warranty period enclose a copy of your sales receipt Specifications Smart 2200XLT Output Capacity VA Watts 2200 1750 Battery Runtime Half Load Full Load Minutes 274 11 Battery Recharge Time 2 4 hrs Approvals UL cUL Nominal Input Voltage Frequen
2. UPS is designed to support only computer equipment Connecting household appliances laser printers or surge suppressors is not recommended Turn your UPS ON Set the System Enable Switch DIP Figure DIP Switch 4 Switch 4 UPS back panel to the System Enable Switch ENABLE UP position See Figure 1 This switch activates the battery charger and microprocessor The light will flash until you engage the ON Standby Switch to activate the ON mode e Engage the momentary ON Standby Switch UPS front panel and release it to activate the ON mode and supply power to the UPS receptacles See Figure 2 Figure 2 ON Standby Switch DB9 Port Connection Optional On Next Page DB9 Port Connection Optional Using Tripp Lite cable connect your primary server s DB9 port to the single DB9 port labeled SMART LAN nee 4 1 which provides complete STEERER GG S intelligent RS 232 communications mS EREREED using the included cable labelled 5 73 743 Tt Lo meee 2 If you have additional computers a Connect them to the DB9 ports labeled BASIC LAN 2 2 which provide basic contact closure shutdown capabilities using the included i cables labelled 73 844 Thrrti i BERR ee _aeREEE E aoe b Set their corresponding LAN Interface SERRE DIP Switches to the ACTIVATE DOWN position See diagram for which switch controls w
3. TRIPP LITE SmartPro POWER PROTECTION 1111 W 35th Street Prep 4 LT Chicago IL 60609 USA Customer Support 773 869 1234 com www tripplite Line Interactive UPS Systems 230V Installation p 3 4 Basic Operation p 4 6 Storage amp Service p 7 Specifications p 7 Copyright 1999 Tripp Lite All rights reserved SmartPro is a registered trademark of Tripp Lite JN This manual contains important instructions and warnings that should be followed during the installation operation and storage of all Tripp Lite UPS systems UPS Location Warnings e Install your UPS indoors away from excess moisture or heat dust or direct sunlight e For best performance keep the indoor temperature between 32 F and 104 F between O C and 40 C e Leave adequate space around all sides of the UPS for proper ventilation UPS Connection Warnings e Connect your UPS to a properly grounded AC power outlet Do not remove or modify the UPS s plug e Do not use two prong adapters with the UPS s plug Do not plug your UPS into itself this will damage the UPS and void your warranty e If you are connecting your UPS to a motor powered AC generator the generator must provide clean filtered computer grade output Equipment Connection Warnings e Do not use Tripp Lite UPS Systems for life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alte
4. cy 208V 60 Hz On Line Input Voltage Range 173 250 volts Voltage Regulated Output Voltage Range 230V 9 On Battery Output Voltage Range 230V 5 Output Waveform Line Mode filtered sinewave Output Waveform Battery Mode PWM sine wave AC Surge Suppression exceeds IEEE 587 Cat A amp B standards AC Noise Attenuation gt 40 dB AC Protection Modes H to N H to G N to G Runtime can be extended with the connection of the appropriate Tripp Lite external battery packs With the addition of external battery packs battery recharge time will increase More Than Years Manufacturing Excellence Since 1922 TRIPP LITE POWER PROTECTION 1111 W 35th Street Chicago IL 60609 USA Customer Support 773 869 1234 www tripplite com r 93 1503 9911081
5. eptacles and Standby mode power OFF at the UPS receptacles Mute Test Switch Use this momentary switch to do two things Silence the blackout alarm Engage this switch and release it Note when the battery is nearly depleted the alarm resumes and cannot be silenced to alert you to immediately shut down connected equipment Test your UPS s battery charge Leave your connected equipment ON With your UPS plugged in and completely turned ON engage this switch hold it there for 5 seconds and release it The UPS will momentarily switch to battery to test its charge The light will turn ON and the alarm may sound if your UPS fails a self test and or the UPS battery is less than fully charged Let the UPS charge for 12 hours and perform a second self test If the light continues to stay on contact Tripp Lite for service CAUTION Do not unplug your UPS to test its batteries This will remove safe electrical grounding and may introduce a damaging surge into your network connections Indicator Lights All Indicator Light descriptions apply when the UPS is plugged into a wall outlet and turned ON This green light will shine constantly to indicate AC power is available at the receptacles It will flash to indicate AC power is not available See System Enable Switch and ON Standby Switch descriptions above This multi colored light displays 7 separate UPS battery charge conditions It will turn fro
6. equipment with AC line power during normal operation and battery power during blackouts and brownouts It also protects your equipment against damaging surges and line noise You can remotely reboot con nected equipment by turningthe UPS OFF and ON using Tripp Lite UPS software See software instructions for details SMART LAN 4 1 RS 232 Port The RS 232 port connects your UPS to any workstation or server Use with Tripp Lite software and cabling to monitor and manage network power and automatically save open files and shut down equipment during a blackout This port uses RS 232 communica tions to transmit UPS and power conditions Select models feature plug and play capability Contact Tripp Lite Customer Support for more information and a list of available SNMP network manage ment and connectivity products Py BASIC LAN 2 2 Contact Closure Ports 2 Also used to connect your UPS to any workstation or server Use with Tripp Lite software and cabling to automatically save open files and shut down equipment during a blackout These ports use contact closure signals to indicate line fail and low battery status External Battery Connector Use this to connect additional Tripp Lite battery packs for addi tional runtime Refer to the label next to the connector for appropriate Tripp Lite battery pack to connect Refer to instruc tions available with the battery pack for complete connection information and safety warnings
7. hich port DIP Switches 2 amp 1 Lan Interface Switches DEACTIVATE Sd z A Sa a i e 0000 e 0000 00000 0000o Y ji bi SS Ji NN i 2b Back Panel Load software and run the installation program appropriate for your operating system Serial port connections are optional Your UPS will function properly without these connections The SMART LAN 4 1 port is always enabled and is not controlled by the LAN Interface DIP Switches If you do not connect a computer to either of the BASIC LAN 2 2 ports set their corresponding LAN Interface DIP Switches to the DEACTIVATE UP position Note DIP Switch 3 has no function Basic Operation Switches System Enable Switch DIP Switch 4 432 4 This switch is located in the set of 4 switches next to the UPS s DB9 wil ports It activates the battery charger and intelligent microproces sor Always leave it in the ENABLE UP position when your UPS is plugged in Set the switch to DISABLE DOWN only if you store or ship your UPS to reduce battery drain Note the V light will flash until you engage the ON Standby Switch to activate the ON mode power ON at the UPS receptacles ON Standby Switch This momentary switch controls power to the UPS receptacles Engage it momentarily and release it to toggle between the ON mode power ON at the UPS rec
8. m red low to yellow medium to green full to show you the level of battery charge If the light is constant then your UPS is operating from line power and the battery is charging If the light is flashing then your UPS is operating from battery power and the battery is discharging When the light flashes red close any files you are working on and shut down your computer Whenever your UPS is automatically correcting high or low AC line voltage this green light will turn ON and the UPS will gently click The more the UPS has to correct voltage the more the green light will turn ON and the more the UPS will click These are both normal automatic operations of your UPS and no action is required on your part This red light will turn ON if your UPS fails a self test and or the UPS battery is less than fully charged Let the UPS charge for 12 hours and perform a second self test If the light continues to stay on contact Tripp Lite for service This multi colored light displays 4 separate UPS load conditions It will turn from green low to yellow medium to red high as you connect equipment to show you the load level your UPS is support ing When the light is red your UPS is supporting a load above 85 of its capacity If the red light begins flashing your UPS is severely overloaded Remove overload immediately until light stops flashing Other UPS Features L6 20 AC Receptacle This locking receptacle provides your connected
9. r the performance of a life support device e Do not connect surge suppressors to the output of your UPS This may damage your UPS and will void both the surge suppressor and UPS warranties Battery Warnings Your UPS does not require routine maintenance Do not open your UPS for any reason There are no user serviceable parts inside Battery replacement must be performed by qualified service personnel Because the batteries present a risk of electrical shock and burn from high short circuit current observe proper precautions Unplug and turn off the UPS before performing battery replacement Use tools with insulated handles and replace the existing batteries with the same number and type of new batteries Sealed Lead Acid Do not open the batteries Do not short or bridge the battery terminals with any object The UPS batteries are recyclable Refer to local codes for disposal requirements or call 1 800 SAV LEAD 1 800 728 5323 for complete recycling information Do not dispose of the batteries in a fire Connect only Tripp Lite battery packs with the correct voltage see voltage requirements label on the rear of your UPS and the correct connector color to match your UPS s External Battery Connector Do not plug UPS in or operate without batteries Installation D Plug your UPS into an electrical outlet The SmartPro 2200XLT should be connected to a 15 amp dedicated circuit Plug your equipment 2 into your UPS Your
Download Pdf Manuals
Related Search
Related Contents
Descripción Datos técnicos Modo de empleo 本編ダウンロードする(PDF) - 一般財団法人関西情報センター Targus 15” Koskin Standard Laptop Case Hardware Maintenance Manual maison creative - Forestier Paris PeakTech_4960 Spektrum SPMAR636 MÁQUINA DE COSER ESTIMADO CLIENTE ÍNDICE EBA 21 - GEASS Pentair PLDE36 User's Manual Copyright © All rights reserved.