Home

Samsung WA422PRHDWR Flat Panel Television User Manual

image

Contents

1. 6 If prompted to save the selection press the Enter button to either confirm or save the selection See the table on page 16 for a complete listing of the user settable parameters 7 Tf there is no user input for ten seconds the UPS will exit the configuration mode and return to normal mode displaying Line mode 23 TOSHIBA UPS Manual Test Manual UPS and Battery tests may be performed from the UPS configuration screen Tests may be performed when the battery is not being charged To run the battery test scroll to the Manual Bat Test parameter press the Enter button twice Note In order for the UPS to operate normally Manual Bypass should always be set to OFF because the load will not be protected by the unit when Manual Bypass is ON Note Turn off the UPS and keep the AC power on to use the Generator function go to normal mode for Generator OFF 5 5 Interpreting UPS Messages Troubleshooting procedures described here provide instructions to be used to isolate UPS malfunctions Start the troubleshooting procedure in the event of a control panel alarm Audible Alarms e While operating on battery power ON BAT LED is on the UPS will beep once at 5 second intervals e While operating on battery power and the battery power is low ON BAT LED is flashing the UPS will beep twice at 5 second intervals e In the event of an internal fault with an active alarm ALARM LED is on the UPS will provide a
2. from the LCD display and can be changed if necessary 1200 Backup min 80 37 21 19 is 15 3 8 6 19 TOSHIBA 5 User s Guide to Operations Normal ongoing UPS operation requires little or no user input Startup and shutdown requirements of the user are discussed in this section 5 2 UPS Startup and Shutdown Starting the UPS Ensure that installation is correct and that the input power cable is connected to a properly grounded outlet Start the UPS by pressing the On Off button on the front panel The UPS will start the inspection of internal functions main synchronization and inverter startup successful completion allows for output power via the outlets During the startup inspection the LCD will display Ready On The LED will light up when output power has started and the LCD display will show Line Mode Switch on the load Shutting Down the UPS Shut off and disconnect the load Press and hold the UPS On Off button for five seconds The alarm will sound and the UPS will shut down The LCD will momentarily display UPS OFF Note In emergency situations the EPO should be used 5 3 Button Operation 1 is the Load ON OFF button a Press and hold the Load ON OFF button for at least 3 seconds to turn on the UPS b While the UPS is operating press and hold the Load ON OFF button for at least 3 seconds to turn off the UPS 20 TOSHIBA is the Enter but
3. Indicates a hazard that may cause injury from an electrical shock or burn The symbol is comprised of an equilateral triangle enclosing a lightning bolt 2 EXPLOSION HARZARD SYMBOL Indicates a hazard that may cause injury from exploding parts It is comprised of an equilateral triangle enclosing an explosion image TOSHIBA Important Safety Instructions This manual contains important instructions that should be followed during the installation maintenance and operation of the UPS and its batteries to assure safe and proper operation 1 5 6 Turn off lockout and tagout all power sources before connecting the power wiring to the equipment or when performing maintenance Hardwire type UPS units are not equipped with an over current protection device nor do they have an output disconnect for the ac output Therefore user installed circuit breaker should be provided between the UPS output and the load input The maximum ambient operating temperature is 104 40 Battery servicing should be performed by a qualified Toshiba Representative only Unauthorized personnel should not service batteries Contact your nearest Toshiba authorized service center for battery replacement Qualified Personnel ONLY Qualified Personnel is one that has the skills and knowledge relating to the construction installation operation and maintenance of the electrical equipment and has received safety training o
4. Technology On line double conversion topology with automatic bypass Input Phase Single phase with ground Bypass Voltage 184VAC 265VAC Input Voltage range 160VAC 276VAC Frequency 50 60 Hz Auto selection Frequency window from main supply 45 65 Hz Synchronization window 3Hz Input current 1000 VA 4A Input Power factor 0 97 Output Output Voltage 208 220 230 240 VAC selectable from LCD panel Voltage regulation 2 Voltage distortion lt 5 THD at full non linear load lt 3 THD at full linear load Frequency regulation 0 25 Hz battery or free running mode Dynamic response 9 max from 100 to 20 or from 20 to 100 linear load Overload capacity 100 125 1 min 125 150 10 sec Efficiency greater than 86 Environmental Ambient temperature 0 C to 40 C Recommended temperature 15 C to 25 C Storage temperature 15 C to 50 C Cooling Forced air cooling Humidity 0 95 non condensing Audible noise lt 45 db normal and battery mode 1000 VA lt 50 db normal and battery mode 1200 VA Standard Safety 50091 1 1 Emissions EN50091 2 Immunity EN50091 2 1000 1200V A 30 TOSHIBA Tower HV Model OUTPUT POWER 1000VA 700W 1200VA 840W Connection Input IEC 320 10A IEC 320 10A Connection Output 4 x IEC 320 10A 4 x IEC 320 10A Battery type Lead acid 9Ah 12V Lead ac
5. 420x152x239 420x152x239 Ship Dimensions WxDxH mm 546x280x356 546x280x356 Dimensions W x D x H inch 16 5x6x 9 4 16 5x6x 9 4 Ship Dimensions WxDxH inch 21 5x11x14 21 5x11x14 Weight kg Ib 16 2 35 6 17 37 4 Ship Weight kg 16 18 2 40 19 3 42 5 19 Rack mount LV Model OUTPUT POWER 1000VA 700W 10 1000VA 700W 2U Connection Input 5 15R 5 15R Connection Output 3 x 5 15R US 5 15R US Battery type Lead acid 9Ah 6V Lead acid 9Ah 12V Number of batteries 4 3 Backup time full load 4 min 7 min Recharge time lt 4 hours to 90 lt 4 hours to 90 Dimensions W x Dx Hmm 525x428x45 425x429x 89 Ship Dimensions WxDxH mm 645 546 206 553x546x206 Dimensions W x D x H inch 20 7x16 85x1 75 16 73 16 9 3 5 Ship Dimensions WxDxH inch 25 4x21 5x6 6 21 75x21 5x8 11 Weight kg Ib 15 5 34 1 17 0 37 6 Ship Weight kg Ib 17 5 38 5 19 3 42 5 32 TOSHIBA 8 Warranty Information TOSHIBA INTERNATIONAL CORPORATION LIMITED WARRANTY POLICY 48 contiguous U S States Canada Mexico UNINTERRUPTIBLE POWER SUPPLIES UPS TOSHIBA INTERNATIONAL CORPORATION TIC warrants that the 1000 Series Uninterruptible Power Supplies UPS and Uninterruptible Power Supply Battery BATTERY sold by TIC to the end user User shall be free of defects in material and workmanship UPS Unit Battery Series Capacity Dispatch War
6. tee set mens EREA 6 4 Installation situ 7 4 1 ENVIO Metas tai oia 7 4 3 Front Panel Settings ensais instant 16 5 Computer and Alarm Connections 18 6 User s Guide to Operations 20 6 1 UPS Startup and Shutdown ss 20 6 2 Button Operations tresse rencia 20 6 3 Control Panel functions 21 6 4 Interpreting UPS Messages 24 6 5 25 Te 26 8 Technical Specifications 27 8 1 Power Range 1000 1200 LV 27 8 2 Power Range 1000 19 Rack mount model LV 10 amp 2U 28 8 3 Power Range 1000 1200 VA HV 29 8 4 Power Range 1000 VA 19 Rack mount model 1U 2U 30 9 Warranty Information ss 33 TOSHIBA Manual s Purpose and Scope This manual provides information on how to safely install operate and maintain your TIC power electronics product This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual Read the manual completely before installing operating or performing maintenance on this equipment This manual and the accompanying drawings should be considered a permanent part of the equipment an
7. LV General Rated power 1000 VA 1200 VA at power factor 0 7 Technology On line double conversion topology with automatic bypass Input Phase Single phase with ground Bypass Voltage 96VAC 138 VAC user selectable Input Voltage range 80VAC 144 VAC Frequency 50 60 Hz Auto selection Frequency window from main supply 45 65 Hz Synchronization window 3Hz Input current 1000 VA 8 2A 1200 VA 10 0A Input Power factor 0 97 Output Output Voltage 100 110 115 120 127 VAC selectable from LCD panel Voltage regulation 2 Voltage distortion lt 5 THD at full non linear load lt 3 THD at full linear load Frequency regulation 0 25 Hz battery or free running mode 27 TOSHIBA 7 3 Power Range 1000 VA 19 Rack mount model LV 10 4 20 General Rated power 1000 VA at power factor 0 7 Technology On line double conversion topology with automatic bypass Input Phase Single phase with ground Bypass Voltage 96VAC 138VAC user selectable Input Voltage range 80VAC 144VAC Frequency 50 60 Hz Auto selection Frequency window from main supply 45 65 Hz Synchronization window 3Hz Input current 1000 VA 8 2A Input Power factor 0 97 Output Output Voltage 100 110 115 120 127 VAC selectable from LCD panel Voltage regulation 2 Voltage distortion lt 5 THD at full non linear load lt 3 THD at full linear load Frequency regulation 0 25 Hz battery or free running mode Dynamic r
8. a requirement when working with batteries To be performed by Qualified Personnel only 1 Verify that the UPS is off and that the power cord is disconnected from the power source Remove watches rings or other metal objects Use tools with insulated handles to prevent inadvertent shorts Wear rubber gloves and boots Do not place tools or any metal parts on top of batteries Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground Contact with any part of a grounded battery can result in electrical shock The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance XIV TOSHIBA Instructions Importantes Concernant LA S CURIT CONSERVER CES INSTRUCTIONS Cette notice contient des instructions importantes concernant la s curit ATTENTION Une battery peut pr senter un risque de choc lectrique de br lure par transfert d nergie ATTENTION L limination des batteries est r glement e Consulter les codes locaux cet effet XV TOSHIBA Inspection Storage Disposal CAUTION Inspection Upon receipt of the UPS an inspection for shipping damage should be performed Use caution when removing the unit from the pallet Refer to labels or documentation attached to packing material Uncrating Check the unit for loose broken bent or otherwise damaged parts If damage has o
9. is lt 40 C If the problem persists call your service representative Output Short Constant Beep Output short circuit Call the service rep High output Voltage Constant Beep High output voltage Call the service rep Low Output Constant Beep Low output voltage Call the service rep Voltage Bus Fault 2 Beeps sec High internal DC bus Turn off loads Turn off UPS Voltage and call the service representative Site Wiring Fault 1 Beep sec Voltage detected UPS main connector wrong between neutral and polarity Rotate the connector ground Schuko electric contact UPS installed to main supply without ground See section 4 3 for information on how to disable the Site wiring alarm Wrong AC Line Line Abnormal 1 up during auto restart 25 TOSHIBA EE 6 Maintenance With a minimal amount of maintenance you can expect years of satisfactory operation from the UPS unit The most critical issues for the reliability of the UPS are environmental issues Ensure that the temperature and humidity are always in accordance with the specifications and keep the area around the unit clean and dust free The typical battery lifetime is 4 years when operated at 25 C Check the back up time capability of the UPS battery at 6 to 12 month intervals to ensure adequate support for the application 26 TOSHIBA 7 Technical Specifications 7 2 Power Range 1000 1200 VA
10. operates in free run mode when the input frequency is outside of the selected input frequency range When starting the UPS the targeted frequency is 50 or 60 Hz 0 25Hz Refer to section 4 3 Front Panel Settings to set up bypass availability while running in free run mode Diagnostic Tests When the UPS is started a diagnostic test is executed automatically that checks the electronics and battery and reports any problems on the LCD display The advanced battery management system monitors the performance of the battery and will indicate if battery replacement is required The battery management system tests the battery every 30 days of normal mode operation A battery discharge test is performed and reports any problems on the LCD display Except during the first 24 hours after startup while the UPS is in charging mode diagnostic tests can be performed manually from the front panel when required TOSHIBA 2 2 System Configuration The UPS device and the internal backup battery make up the system Depending on the site and load requirements of the installation available options may be utilized to create a tailored solution Planning a UPS system should include the following considerations e The total demand of the protected system shall dictate the output power rating VA Allow a margin for future expansion or calculation inaccuracies from measuring power requirements e Backup time needed will determine the battery size needed If t
11. price 35 TOSHIBA Procedure for Defective Product Screening and Disposition User must contact TIC via e mail upsservice tic Toshiba com or phone 1 877 867 8773 outside the U S call 713 466 0277 to report a defect a UPS UPS part and or BATTERY Subject to the limitations of TIC policy and product type TIC service or TIC service representative shall repair replace the UPS part warranted hereunder without charge for material or labor If TIC determines that the requested repair is not covered under this limited warranty policy TIC shall advise customer and quote cost of repair Repair charges shall be based on service parts price and prevailing service charges at the time of repair In no event after the expiration of the respective warranty period will warranty work be performed In the event of a defective BATTERY claim stand alone and or cabinet TIC will use its published Battery Diagnostic Document to evaluate warranty applicability TIC will confirm that the storage maintenance installation and operating conditions were met The BATTERY capacity will be tested in accordance with the performance test guidelines IEEE STD 450 Should the BATTERY fail to deliver 70 of its rated capacity it shall be deemed defective and will be replaced Either float or cyclic service will be used to determine the warranty credit as per published Battery Diagnostic Document The typical credit applied will be as listed in the foll
12. runs on 4 FREE RUN SET ON OFF unsynchronized Mode For example if input frequency 55Hz output frequency will stay at 60Hz If OFF disable UPS runs on unsynchronized mode For example if input frequency 55Hz UPS will go to Battery mode If ON enable UPS runs on high efficiency mode 5 HE MODE SET ON OFF Bypass mode is on when power flows at 95 or lower If OFF disable UPS runs on high efficiency mode Bypass mode is on when power flows at 85 or lower If ON enable UPS switch to 6 MANUAL BYPASS Bypass mode immediately 16 TOSHIBA 7 OUTLET SETTING GROUP 1 GROUP 2 This is load shed feature Option 1 1 On 2 Option 2 1 Off 2 Option 3 1 Off 2 Off Option 4 1 On 2 Off Perform battery test 8 BATTERY TEST TEST CE a 9 SILENCE SET ON OFF 10 BAT CABINET SET 0 EXT B PACKS options when battery 1 EXT PACKS cabinets are connected 2 EXT B PACKS Alarm on main connector connected at wrong polarity 11 SITE FAULT SET ENABLE DISABLE or installation to main supply without group 12 LANGUAGE ENGLISH GERMAN FRENCH SPANISH ITALIAN If ON UPS will work with a very large range of voltages and frequencies without 13 GENERATOR ON OFF switching back and forth from Line mode battery mode Option to enable and disable the RS232 port USB share the communication line with 14 RS232 CONTROL ENABLE DISABLE RS232 Only one option may be us
13. the power on only after attaching ALL of the covers Do Not remove any covers of the UPS when the power is on If the UPS should emit smoke or an unusual odor or sound turn the power off immediately The heat sink and other components may become extremely hot to the touch XX TOSHIBA Allow the unit to cool before coming in contact with these items 13 Warning signs should be placed on or near the load as a notification that the load 18 being powered by the UPS 14 Additional warnings and notifications shall be posted at the equipment installation location as deemed required by Qualified Personnel While operating the inverter mode placing the breaker the OFF position will switch the UPS to the battery backup mode The output of the UPS will continue uninterrupted to the load The unit must be in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown power to the load caution After an Emergency Power Off EPO do not reset the breaker until the UPS has been fully discharged The UPS could be damaged if the unit is not fully discharged before the breaker is reset XXI TOSHIBA 1 Introduction The information provided in this manual covers single phase 1000 1200 uninterruptible power systems Included in this manual is information on the installation operation safety precautions shipping and storage of
14. their descriptions and associated symbols When the words DANGER WARNING and CAUTION are used in this manual they will be followed by important safety information that must be carefully adhered to 1 Danger The word DANGER in capital letters preceded by the safety alert symbol indicates that an imminently hazardous situation exists that if not avoided will result in death or serious injury to personnel J N DANGER TOSHIBA Warning The word WARNING in capital letters preceded by the safety alert symbol indicates that a potentially hazardous situation exists that if not avoided could result in death or serious injury to personnel N WARNING Caution Attention The word CAUTION or ATTENTION in capital letters preceded by the safety alert symbol indicates that a potentially hazardous situation exists that if not avoided may result in minor or moderate injury ANCAUTION ATTENTION The word CAUTION without the safety alert symbol indicates a potentially hazardous situation exists which if not avoided may result in equipment and property damage CAUTION IX TOSHIBA Special Symbols Other warning symbols may appear in conjunction with the Danger Warning and Caution symbol and are used to specify special hazards These warnings describe particular areas where special care and or procedures are required in order to prevent serious injury and possible death 1 ELECTRICAL HAZARD SYMBOL
15. 212 The email address is toshibaups tic toshiba com You may also contact Toshiba International Corporation by writing to Toshiba International Corporation 13131 West Little York Road Houston Texas 77041 9990 Attn UPS Product Manager For further information on Toshiba International Corporation s products and services please visit our website at www tic toshiba com TOSHIBA Statements FCC Part 15 NOTICE Pursuant to section 15 of FCC rules this product has been tested and complies with the conditions of a Class B digital device The product has been established as offering sufficient protection against dangerous interference for installations in a residential area Installation and use of the equipment should comply with the instructions provided in order to avoid interference due to the amount of radio frequency energy that is radiated and generated by the equipment TIC cannot assure that no interference will occur Turn the unit on and off to help determine if the radio or television reception is found to be influenced by harmful interference from the equipment If required use one of the following measures to minimize the negative effects of interference e Place the receiving antenna in a separate location or orientation e Increase the distance between the receiver and the equipment Ensure that your equipment and the receiver on separate circuits e Contact a technician ex
16. IEC PROTECTOR 2 INPUT OY E _ CIRCUIT BREAKER 11 TOSHIBA 1000VA Rack mount 1U Rear Panel INPUT CIRCUIT PROTECTOR EPO RS232 INTERFACE OPTIONAL OUTLET Ne USB INPUT OPTIONAL RM 1U 110V 220V NEMA INPUT CIRCUIT PROTECTOR EPO RS232 INTERFACE OPTIONAL OUTLET 7 7 N LA NIN 4 Ne USB INPUT OPTIONAL RM 1U 220V IEC 12 TOSHIBA FE 1000VA Rack mount 2U Rear Panel FACE OUTLET 21 110V ave 3B TE INPUT OPTIONAL PTIONAL CIRCUIT BREAKER PROTI RM 2U 220V 2 13 3 3 TOSHIBA Connection to main supply and loads 1000 1200 Ensure that the UPS is disconnected from the main supply and loads while connecting the External Battery Cabinets Use the battery cable supplied with the External Battery Cabinet to connect the External Battery Cabinet to the UPS If more than one battery cabinet is required use the supplied cable A familiarity with the UPS parameter settings is required if changing the Battery pack quantity as when using the External Battery Cabinets section 4 3 Front Panel Sett
17. OUND XIX TOSHIBA Operating Precautions 9 10 11 12 The UPS should not be powered up until the entire operation manual has been read The voltage of the input power source must be within the range of 10 to 30 of the rated input voltage The input frequency must be within the rated input frequency range Voltages and frequencies outside of the permissible range may activate the internal protection devices The UPS should not be used with load that has rated input that is greater than the rated output of the UPS Do not use the UPS to provide power to motors that require high starting current or with motors that require a long starting time such as vacuum cleaners and machine tools over sizing the UPS for lock rotor current would be required Do not insert metal objects or combustible materials in the ventilation slots of the UPS Do not place hang or paste any objects on the exterior surfaces of the UPS The capacitors of the UPS maintain a residual charge for a while after turning the UPS off The required discharge time for each UPS typeform is provided via a cabinet label and a CHARGE LED Wait for at least the minimum time indicated on the label and ensure that the CHARGE LED has gone out before opening the door of the UPS once the UPS power has been turned off Do not attempt to disassemble modify or repair the UPS Call your Toshiba sales representative for repair information Turn
18. Uninterruptible Power Supplies 1000 Series Reliability in motion User Manual 1000 Series Uninterruptible Power Supplies UPS Single Phase 1000 1200 VA TOSHIBA IMPORTANT NOTICE The instructions contained in this manual are not intended to cover all of the details or variations in equipment or to provide for every possible contingency concerning installation operation or maintenance Should further information be required or if problems arise which are not covered sufficiently contact your Toshiba sales office at 713 466 0277 The contents of this instruction manual shall not become a part of or modify any prior or existing agreement commitment or relationship The sales contract contains the entire obligation of Toshiba International Corporation TIC s UPS Division The warranty contained in the contract between the parties is the sole warranty of Toshiba International Corporation s UPS Division and any statements contained herein do not create new warranties or modify the existing warranty Any electrical or mechanical modifications to this equipment without prior written consent of Toshiba International Corporation will void all warranties and may void the UL CUL listing Unauthorized modifications can also result in personal injury death or destruction of the equipment TOSHIBA UNINTERRUPTIBLE POWER SUPPLY Complete the information below for the UPS system received Unless otherwise specified on
19. atures of the UPS includes e Auto Restart and Cold Start features e Programmable Load Shed Receptacle e Intelligent Charger with Rapid Charge in only 3 5 hours to 90 e Wide Input Voltage Window e Wide Input Frequency Window for Complete Generator Compatibility e Input Power Factor greater than 0 97 e Output Power Factor 0 70 e Multiple Languages LCD Display e Free Run Mode See detail explanation on page 4 e Diagnostic Tests See detail explanation on page 4 e Optional Network Interface Card e Optional Environmental Monitoring Device In the event that a power failure lasts longer than the UPS backup time the UPS will shut down Upon power restoration the UPS will restart automatically which includes output power being restored to the load and the start of battery recharge See following figure for systemic applicable of the UPS system Figure 1 Block diagram TOSHIBA An input filter reduces transients on the main supply For maintaining full battery charge AC power is rectified and regulated in the rectifier feeding power to the inverter and battery converter DC power is converted to AC in the inverter and passes it on to the load Power to the load is maintained from the battery during a power failure The converter increases voltage for the inverter as required TOSHIBA EE Free Run Mode Free run mode is a mode of operation in which the output frequency does not match input frequency The UPS
20. ccurred during shipping keep all original crating and packing materials for return to the shipping agent The warranty does not apply to damage incurred during shipping Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications Storage During periods of non use the following guidelines are recommended for storage Storage Preparation 1 Power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries 2 Stop the unit 3 Place the MCCB switch in the Off position Storing Conditions e best results store the UPS in the original shipping container and place a wood or metal pallet e Storage temperature 20 40 4 104 e The optimum storage temperature is 21 C 70 F A higher ambient temperature will require recharging more frequently during storage Avoid the following storage locations XVI TOSHIBA AEE e Locations that are subject to extreme temperature changes or high humidity e Locations that are subject to high levels of dust or metal particles e Locations that are subject to excessive vibration e Inclined floor surfaces Storage Maintenance e If stored at an ambient temperature less than 20 68 F recharge the batteries every 9 months e If stored at an ambient temperature of 20 30 C 68 86 F recharge the batteries every 6 months e If stored at an ambien
21. ch behind and 50mm 2 inch on the sides of the UPS for ventilation Ensure that the front of the UPS remain supply clear for user access The External Battery Cabinets must be installed next to or underneath the UPS TOSHIBA Vertical and Wall mounted Installations with Accessories Install the vertical and wall mounted units as shown below Vertical Installation Wall mounted installation ppl sA ida INT gt Fa 7 j UN 5 2 gt y 222 TOSHIBA Rack mounted Installation with Accessories Install the rack mounted unit as shown below Installation with bottom bracket Screw M5 11 4 PCS ch 1 A TOSHIBA Stacked UPS Installation with accessories Install the stacked unit as shown below Stack installation Y in 10 TOSHIBA Rear Panel Views 1000VA 1200VA Tower Rear Panel RS232 Ph H NETWORK G TRANSIENT PROTECTOR _ CIRCUIT lt BREAKER INPUT 110V NEMA NETWORK TRANSIENT INTERFACE OP TIONAL MO USB OPTIONAL EXTERNAL BATTERY OPTIONAL T OUTLET e Kay INTERFACE OPTIONAL USB OPTIONAL R Nal e EXTERNAL BATTERY EOE OPTIONAL AU QUE D 220V
22. constant audible alarm and display an error message on the LCD display e While operating in the Bypass mode BYPASS LED is on the UPS will not beep Silencing an Alarm With the exception of a LOW BATTERY Alarm pressing any of the front panel buttons will turn off the alarm Select Silent Alarm Mode to disable all audible alarms 24 TOSHIBA 5 6 Troubleshooting Displayed on LCD Audible Alarm Alarm Description What You Should Do Output Overload Two The UPS is overloaded Remove loads from the UPS in Line Mode More least to most critical If this power required than the solves the problem the UPS UPS can provide The will return to normal operation UPS operates in bypass Battery Test No Beeps Battery test active No action needed User Notification only Over Charge Constant Beep Overcharged Batteries Turn off loads Turn off UPS and call your local dealer Low Battery 2 Beeps 5 sec UPS operating on The unit will restart Battery Power and will Automatically when acceptable shut down soon due to power returns low battery voltage On Battery 1 Beep 5 sec UPS operating on Save your data and perform a Battery Power controlled shutdown Charger Failure Constant Beep Failed Charger Phone service representative Over Temperature Constant Beep High ambient Ensure that the UPS fans and Temperature vents are not blocked and that the ambient temp
23. d should be readily available for reference and review Dimensions shown in the manual are in metric and or the English equivalent Toshiba International Corporation reserves the right without prior notice to update information make product changes or to discontinue any product or service identified in this publication TOSHIBA INTERNATIONAL CORPORATION is a registered trademark of the Toshiba International Corporation All other product or trade references appearing in this manual are registered trademarks of their respective owners Toshiba International Corporation TIC shall not be liable for direct indirect special or consequential damages resulting from the use of the information contained within this manual This manual is copyrighted No part of this manual may be photocopied or reproduced in any form without the prior written consent of Toshiba International Corporation Copyright 2005 Toshiba International Corporation All rights reserved Printed in the U S A IV TOSHIBA Contacting Toshiba International Corporation s Customer Support Center Toshiba International Corporation s Customer Support Center can be contacted to obtain help in resolving any Uninterruptible Power Supply system problems that you may experience or to provide application information The center is open from 8 a m to 5 p m CST Monday through Friday The Support Center s toll free number is US 800 231 1412 Fax 713 896 5
24. ed at a time Complete the installation entirely before changing the default settings or connecting a load to the UPS 17 TOSHIBA 4 Computer and Alarm Connections At the rear of the UPS is an interface that allows direct communication with a computer system see figure 2 There is a RS232 serial data interface a USB data interface and an emergency power off switch The RS232 port and the USB interface cannot be used simultaneously In addition there is an optional interface slot that allows for the installation of communications cards It may be used in parallel with either the RS232 or USB ports An SNMP WEB card is available for the optional interface slot that allows for the RemotEye to manage and monitor the system over a network or over the internet RS 232 Standard Interface Port Only the communication cable provided with the UPS may be used to connect the UPS to a computer when using the RS232 port of the UPS Ensure that the operating system of the computer supports RS232 communications Other advanced power protection solutions such as SNMP are available from your dealer The RS 232 interface uses a 9 pin D sub connector The names and functions of the port pins are listed in the following table 86000 SESE ES Pin Signal Direction re UPS Functions 2 TxD Output TxD Output 3 RxD Input RxD Inverter Off Input 5 Common Common 6 Output Ac Fail Output 8 Output Low Batte
25. esponse 9 max from 100 to 20 or from 20 to 100 linear load Overload capacity 100 125 1 min 125 150 10 sec Efficiency greater than 86 Environmental Ambient temperature 0 C to 40 C Recommended temperature 15 C to 25 C Storage temperature 15 C to 50 C Cooling Forced air cooling Humidity 0 95 non condensing Audible noise lt 45 db normal and battery mode 1000 1200 VA 28 TOSHIBA 7 4 Power Range 1000 1200 VA HV General Rated power 1000 VA 1200 VA at power factor 0 7 Technology On line double conversion topology with automatic bypass Input Phase Single phase with ground Bypass Voltage 184VAC 265V AC user selectable Input Voltage range 160VAC 276VAC Frequency 50 60 Hz Auto selection Frequency window from main supply 45 65 Hz Synchronization window 2 5Hz Input current 1000 VA 4A 1200 VA 5 2A Input Power factor 0 97 Output Output Voltage 208 220 230 240 VAC selectable from LCD panel Voltage regulation 2 Voltage distortion lt 5 THD at full non linear load lt 3 THD at full linear load Frequency regulation 0 25 Hz battery or free running mode Dynamic response 9 max from 100 to 20 or from 20 to 100 linear load Overload capacity 100 125 1 min 125 150 10 sec Efficiency greater than 86 29 TOSHIBA 7 5 Power Range 1000 VA 19 Rack mount model HV 1U amp 2U General Rated power 1000 VA at power factor 0 7
26. he load is less than the UPS nominal power rating then the actual backup time will be longer following options are available e External Battery Cabinets and e Connectivity options Remote Contact SNMP WEB card The following UPS models are available Model Backup time Internal Recharge time to 90 batteries capacity UPS 1000VA 7 min 4 hours UPS 1200VA 6 min 4 hours Additional External Battery Cabinets are available if more back up time is needed TOSHIBA 3 Storage Please adhere to the following instructions if the UPS is not installed when received e Store the equipment its original packing and shipping carton e Store the unit a temperature of 15 to 25 Ensure that the equipment is fully protected from wet or damp areas and from moist air In order to maintain the vitality of the batteries ensure that the UPS is recharged every 6 months for at least 8 hours during storage TOSHIBA 3 Installation 3 2 Environment To ensure safe and proper operation ensure that the installation conforms to the following specifications Ensure that the installation location is consistent with the following Avoid extreme temperature and humidity Maximal battery can be attained with a recommended temperature range of 15 C to 25 C e Protect the equipment from moisture e Space and ventilation requirements must be met Ensure there is at least 100mm 4 in
27. id 9Ah 12V Number of batteries 3 3 Backup time full load 7 min 6 min Recharge time lt 4 hours to 90 lt 4 hours to 90 Dimensions WxDxH mm 420x152x238 420x152x238 Ship Dimensions WxDxH mm 546x280x356 546x280x356 Dimensions W x D x H inch 16 5x6x9 4 16 5 6 9 4 Ship Dimensions WxDxH inch 21 5 11 14 21 5x11x14 Weight kg Ib 16 2 35 6 17 37 5 Ship Weight kg Ib 18 2 40 19 41 8 19 Rack mount HV Model OUTPUT POWER 1000VA 700W 1U 1000VA 700W 20 Connection Input TEC 320 10A TEC 320 10A Connection Output 4 x IEC 320 10A 4 x IEC 320 10A Battery type Lead acid 9Ah 6V Lead acid 9Ah 12V Number of batteries 3 Backup time full load 4 min 7 min Recharge time lt 4 hours to 90 lt 4 hours to 90 Dimensions WxDxH mm 525x428x44 425x428x84 Ship Dimensions WxDxH mm 645x546x206 553x546x206 Dimensions W x D x H inch Ship Dimensions WxDxH inch Weight kg 16 20 7x16 85x1 75 25 4x21 5x6 6 15 5 34 16 73x16 9x3 5 21 75x21 5x8 11 17 38 Ship Weight kg Ib 17 3 38 5 19 3 42 5 31 TOSHIBA Tower LV Model OUTPUT POWER 1000VA 700W 1200VA 840W Connection Input 5 15R 5 15R Connection Output 5 15R US 6 x 5 15R US Battery type Lead acid 9Ah 12V Lead acid 9Ah 12V Number of batteries 3 3 Backup time full load 7 min 6 min Recharge time lt 4 hours to 90 lt 4 hours to 90 Dimensions WxDxH mm
28. ing display may be accessed by pressing this button UPS Meters Display Listed below are the parameters available for viewing from the UPS meters display Press this button to scroll through the parameters LCD Message Description O P VOLT xxx xV Shows Output AC Voltage O P xx x Hz Shows Output Frequency I P VOL T xxx xV Shows Input AC Voltage FREQ xx x Hz Shows Input Frequency BAT VOLT xx xV Shows Battery Voltage O P LOAD xx Shows Load of Max Load O P W xW Shows Output Watts O P VA xVA Shows Output VA O P CURR xA Shows Output Current BACKUP TIME xx min Shows Estimated Backup Time in Minutes BAT xx Shows Approximate Percentage of Battery Capacity TEMPERATURE xxC Shows Approximate Ambient Temperature BAT PACK NUM x Shows External Battery Pack Number RATING xxxxVA Shows UPS Rating CPU VERSION xx x Shows CPU Version 22 TOSHIBA UPS Configurations 1 Parameter settings may be viewed from the UPS Settings display 2 To enter the configuration mode press and hold the Function button for one second The first configuration parameter will be shown on the LCD display 3 Press the Function button again to scroll through the remaining parameters 4 Press the Enter button to select a displayed parameter 5 Press the Function button to scroll through the options for the selected parameter Press the Enter button to select the setting
29. ings Connect the input cable to the UPS and connect the other end to a grounded outlet The batteries will charge automatically when connected to the main supply The UPS may be used immediately to power a load However the maximum battery back up time will not be available until the recommended 8 hour minimum charge time has completed If a Site Wiring Fault is displayed rotate the connector Schuko electric contact see section 5 6 Troubleshooting After charging the UPS connect the load to the UPS see the example in Figure 2 Example of Installation of Plug amp Play products Do not connect any devices to the UPS that may cause overloading of the UPS or that draws half wave rectified current such as hair dryers or vacuum cleaners See section 4 Computer and Alarm Connections if computer or alarm rear panel connections are used The installation is now complete 14 TOSHIBA COMMUNICATION CABLE POWER CORD IEC INTERCONNECTION CABLES Figure 2 of Installation of Plug amp Play products 15 TOSHIBA 4 3 Front Panel Settings Listed below are the default settings of the primary UPS parameters CS 1 O P VOLT SET 100V 110V 115V 120V 127V 120V 120V FOR LV 2 I P FREQ Input Frequency range Input Frequency Set in Free Run mode 3 VP BYPASS SET 10 10 15 Input Voltage range when Input Bypass Setting 10 15 Bypass mode is on 15 20 If ON enable UPS
30. n the hazards involved Refer to the latest edition of NFPA 70E for additional safety requirements Qualified Personnel shall 1 2 Have read the entire operation manual Be trained and authorized to safely energize de energize ground lockout and tag circuits and equipment and clear faults in accordance with established safety practices Be trained in the proper care and use of protective equipment such as safety shoes rubber gloves hard hats safety glasses face shields flash clothing etc in accordance with established safety practices Be trained in rendering first aid XI TOSHIBA 5 Be knowledgeable of batteries and the required handling and maintenance precautions For further information on workplace safety visit www osha gov XII TOSHIBA Important Safety Instructions cont d N warninG Misuse of this equipment could result in injury and equipment damage In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment Do not dispose of the batteries in a fire The batteries may explode ANCAUTION Do not open or mutilate the batteries Released electrolyte is harmful to the eyes and skin and could also be toxic Npancer battery can present risk of electrical shock and high short circuit current TOSHIBA Strict adherence to the following precautions is
31. owing table Credit for Replacement Battery When Approved Warranty Time from Shipment UPS Batteries Cost to Customer months Credit List Price 55 65 75 85 36 TOSHIBA aa MODIFICATIONS No representative salesperson agent distributor or employee of TIC is authorized to modify any of the terms of the warranty unless modifications are made in writing and signed by an authorized TIC officer 37 TOSHIBA TOSHIBA INTERNATIONAL CORPORATION INDUSTRIAL DIVISION 13131 West Little York Road Houston Texas 77041 Tel 713 4660277 Fax 713 466 8773 US 800 231 1412 Canada 800 872 2192 Mexico 01 800 527 1204 www tic toshiba com Copyright 6 2005
32. perienced with radio and TV or a dealer for further assistance ICES 003 This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe B respecte toutes les exigences du Reglement sur le mat riel brouilleur du Canada VI TOSHIBA Declaration of Conformity Request Units labeled with a CE mark comply with the following standards and directives Harmonic Standards EN 50091 1 1 and EN 50091 2 EU Directives 73 23 Council Directive on equipment designed for use within certain voltage limits 93 68 Amending Directive 73 23 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark TOSHIBA General Safety Instructions DO NOT attempt to install operate maintain or dispose of this equipment until you have read and understood all of the product safety information and directions that are contained in this instruction manual Safety Alert Symbol Signal Words The Safety Alert Symbol indicates that a potential personal injury hazard exists The symbol is comprised of an equilateral triangle enclosing an exclamation mark Sianal Words Listed below are the signal words that are used throughout this manual followed by
33. ranty On Site Warranty On Site 1000VA ai 1200VA Note 1 The warranty period begins from the shipment date The shipment date is determined by the date on the TIC Bill of Lading Note 2 For the 1000 Series the warranty applies if the unit is sent and returned paid for by the user to from the Toshiba International Corporation or a Toshiba International Corporation designated Authorized Service Center If any UPS part of UPS and or BATTERY fails to conform or is defective then TIC at this option will repair or replace defective component s 33 TOSHIBA EEE LIMITATIONS AND EXCLUSIONS This limited warranty shall not cover the UPS UPS part or BATTERY during their respective warranty periods if the following storage maintenance installation operating conditions are not met throughout the warranty periods 5 conditions below VALVE REGUALATED LEAD ACID VRLA BATTERIES FOR TOSHIBA INTERNATIONAL CORPORATION UPSREQUIRED OPERATING CONDITIONS Annual Average Temperature 25 C 77 F 89 F for more than 30 Temperature Temperature per cell lt 32 C days 2 Maximum number Discharge time Maximum Number of of full charge discharge Cycles 24 months cycles 30 minutes 69 15 minutes 86 10 minutes 5 minutes VALVE REGUALATED LEAD ACID VRLA BATTERIES FOT TOSHIBA INTERNATIONAL CORPORATION UPS INSTALLATION AND MAINTENANCE CONDITIONS While UPS is in transi
34. ry Output 9 Output 8 24 VDC Power Table 1 RS232 Pin Out Signal 18 TOSHIBA USB Port Connecting the UPS to a computer using the USB port of the computer requires USB compliant hardware PC operating system support and a UPS driver The RS232 serial port cannot be used when using the USB port The USB cable is standard cable and may be purchased separately EPO Port emergency power off A customer supplied switch located remotely may be used to open the EPO connection and force the UPS output receptacles to be switched off The EPO function shuts down the equipment immediately An EPO will not provide an orderly shutdown The UPS will have to be manually restarted in order to regain power to the outlets After an Emergency Power Off EPO do not reset the breaker until the UPS has been fully discharged The UPS could be damaged if the unit is not fully discharged before the breaker is reset Network Transient Protector The network transient protector located on the back panel has both IN and OUT RJ45 10 baseT jacks and will protect a single network connector Connect the input connector to the jack labeled IN and the output connector to the jack labeled OUT Load Segments The sets of receptacles known as load segments which provide organized shutdown and startup of the equipment Less critical equipment can be turned off during power outages saving battery power for critical loads The load group status can be viewed
35. t inside the UPS The UPS generates and can radiate radio frequency energy during operation Although RFI noise filters are installed inside of the unit there is no guarantee that the UPS will not influence some sensitive devices that are operating near by If such interference is experienced the UPS should be installed farther away from the affected equipment and or powered from a different source than that of the affected equipment The user should provide output over current protection for hardwired UPS systems After ensuring that all power sources are turned off and isolated in accordance with established lockout tagout procedures connect the power source wiring of the correct voltage to the input terminals of the UPS XVII TOSHIBA AEE 12 Connect the output terminals of the UPS to the load refer to NEC Article 300 Wiring Methods and Article 310 Conductors For General Wiring Size the branch circuit conductors in accordance with NEC Table 310 16 Conductor Routing and Grounding 1 Use separate metal conduits for routing the input power output power and control circuits 2 Follow the wire size and tightening torque specifications 3 Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise 4 A separate ground cable should be run inside the conduit with the input power output power and control circuits ANCAUTION THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GR
36. t or storage it must always be in Storage suitable temperature see condition 1 Parallel battery string applications must be approved 4 External Batteries by TIC in writing User must recharge the batteries if not in use Idle Batteries charged for more than 6 months 34 TOSHIBA The Warranty does not cover damage or defects caused by misuse improper application wrong or inadequate electrical current voltage frequency inadequate connections inadequate water or drain services user negligence repair by non Toshiba International Corporation designated personnel accident during shipment tampering alterations a change in UPS and or BATTERY location or application exposure to the elements acts of God theft sabotage installation contrary to TIC s recommendations or specifications Published Operation Manuals or if the serial numbers have been altered defaced or removed Repair or replacement of a defective UPS UPS part and or BATTERY does not extend the respective original warranty period All defective UPS UPS parts and or BATTERIES shall be the property of TIC upon replacement The sales contract contains the entire obligation of Toshiba International Corporation and constitutes the sole and exclusive remedy of all purchasers and users of the UPS UPS part and or BATTERY TIC s responsibility for UPS UPS Parts and or BATTERY shall not exceed one times the net UPS and or BATTERY purchase
37. t temperature of 30 40 86 104 F recharge the batteries every 3 months Disposal Please contact your local or state environmental agency for details on disposal of electrical components and packaging in your particular area It is illegal to dump lead acid batteries in landfills or dispose of improperly Please help our Earth by contacting the environmental protection agencies in your area the battery manufacturer or call Toshiba toll free at 800 231 1412 for more information about recycling XVII TOSHIBA Installation Precautions 199 10 11 N caurion Install the unit in a well ventilated location allow at least 10 cm 4 inches on all sides for air ventilation and for maintenance Install the unit in a stable level and upright position that is free of excessive vibration Install the unit where the ambient temperature is within the range specified Do not install the UPS in areas that are subject to high humidity Do not install the UPS in areas that allow exposure to direct sunlight Do not install the UPS in areas that allow exposure to high levels of airborne dust metal particles or flammable gases Do not install the UPS in areas near sources of electrical noise Ensuring a proper earth ground will reduce the effects of electrical noise and will reduce the potential for electrical shock Do not install the UPS in areas that would allow fluids or any foreign object to ge
38. the equipment Installation must be carried out in accordance with this manual Electrical installations must also follow local legislation and regulations Only qualified personnel should install this equipment Failure to comply with the warnings and precautions could prove to be fatal 2 System Description The purpose of the UPS is to protect sensitive systems from poor quality utility power complete loss of power or other associated problems System types include computers workstations process control systems telecommunications systems sales terminals or other critical instrumentation Electrical interference may occur causing problems in AC power Interference may come from lightning the power company radio transmissions or motors Normal operation of sensitive electrical equipment requires protection against power outages low or high voltage levels frequency variations differential and common mode noises and transients In order to prevent power line problems from reaching critical systems and causing damage to software hardware or causing equipment to malfunction the UPS helps by maintaining a constant voltage isolating critical load output and cleaning the utility AC power TOSHIBA 2 1 General Description As a double conversion on line UPS it is able to supply uninterrupted clean single phase power to your critical systems while keeping batteries charged continuously even if the utility power fails Other fe
39. the warranty card the warranty period for the UPS or UPS part is 36 months from the shipment date see TIC bill of lading Unless otherwise specified on the warranty card the warranty period for a UPS battery is 24 months from the shipment date see TIC bill of lading Please complete the following information and retain for your records Job Number Model Number Serial Number Application Shipment Date Installation Date Inspected By July 2005 Document Number 57723 001 TOSHIBA Table of Contents Manual s Purpose and Scope IV Contacting Toshiba International Corporation s Customer Support Center V CA General Safety Instructions Important Safety Instructions XI Important Safety Instructions cont d Instructions Importantes 2 2 XVI Installation Pr cautions lirica XVII Operating XX 6 unes nn 1 2 System Descriptions el ste at 1 2 1 General Description iio ir il ed 2 2 2 System Configuration ss 5 A
40. ton a Press and hold the Enter button for at least 2 seconds to read the parameter settings of the UPS Press the Enter button again to read the next parameter b Ten seconds of inactivity will return the display to the original status 3 LO is the Function button a Press and hold the Function button for at least 2 seconds to access the selectable parameters Press the Function button again to view the next parameter b Press the Enter button to view or change the displayed parameter c Ten seconds of inactivity will return the display to the original status 5 4 Control Panel functions The front panel is composed of five LED indicators an LCD screen and a speaker for audible alarms ON S gt is on when the UPS is turned on green ON LINE y is on when in the Normal or Static Bypass modes Also indicates that there is voltage at the output terminals green ON BAT is on while operating in the Battery mode BYPASS is on while operating in the Bypass mode yellow ALARM N is on during active UPS internal errors red FAULT is accompanied by an audible alarm Press any of the front panel buttons to cancel the alarm 21 TOSHIBA EOE Status of the UPS measurements and alarms are all indicated on the LCD screen 829 1000 Figure 3 Control panel Normal Display The UPS status is shown in the normal display mode The UPS Meters display and the Sett

Download Pdf Manuals

image

Related Search

Related Contents

2 - Manual und bedienungsanleitung.  取扱説明書1はこちら  安全データシート  Samsung SM-T235 User Manual  Installing PCIE-8120 into a Dell R720 server  InLine 1m, HDMI - HDMI    Samsung KING-2000 Kullanıcı Klavuzu  

Copyright © All rights reserved.
Failed to retrieve file