Home

Majestic Appliances 360DVSR Indoor Fireplace User Manual

image

Contents

1. 10006326 5 360 DVS Series Direct Vent Fireplaces Fireplace Dimensions 360DVS3 306DVSL 360DVSR Rear Vent Configuration ZWN Access J Gas Line 5 iari o Top Vent Configuration Electrical Access J Gas Line Access H 2 HS cee Fig 1b Fireplace specifications 360DVS3 360DDVSL 360DVSR Appliance Dimensions vent Configuration Top Vent Configuration Bs Geemm 38 968 mm B 4 t02mm 4097 1032 mm 27 610mm D 2f 6mm 24 610mm 37 949 mm F 5 imm 35 911 mm 7 178 12 305 80mm 70mm 83mm 6 10006326 360DVS Series Direct Vent Fireplaces Framing Dimensions 360DVS2 Rear Vent Configuration asa CFM121 Top Vent Configuration CFM122 Fig 2a Fireplace framing dimensions 360DVS2 Framing Dimensions Ref Rear Vent Configuration Top Vent Configuration 24 610 mm
2. YES UNPLUG IGNITION LEAD AND CHECK SPARK SPARK ACROSS AT MODULE IGNITOR SENSOR GAP 24VAC NORMAL YES SPARK OK REPLACE MODULE YES CHECK IGNITION CABLE GROUND WIRING CERAMIC INSULATOR AND GAP CORRECT AS NECESSARY CHECK BOOT OF IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING TAKE PROTECTIVE ACTION TO SHIELD CABLE AND BOOT FROM EXCESSIVE TEMPERATURES TURN GAS ON PILOT BURNER LIGHTS CHECK THAT ALL MANUAL GAS VALVES ARE OPEN SUPPLY TUBING AND PRESSURES ARE GOOD AND PILOT BURNER ORIFICE IS NOT BLOCKED CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL CHECK FOR 24VAC ACROSS PV MVPV TERMINALS ON MODULE IF VOLTAGE IS OKAY REPLACE GAS CONTROL IF NOT REPLACE MODULE YES SPARK STOPS WHEN PILOT IS LIT YES NOTE IF S8600B GOES INTO LOCKOUT RESET SYSTEM CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE CLEAN FLAME ROD CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD amp MODULE CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY BLUE ADJUST PILOT FLAME IF PROBLEM PERSISTS REPLACE MODULE CHECK FOR 24VAC ACROSS MV MVPV TERMINALS IF NO VOLTAGE MAIN BURNER LIGHTS REPLACE MODULE CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS YES CONTROL IF OKAY REPLACE GAS CONTROL OR GAS CONTROL OPERATOR SYSTEM RUNS UNTIL NOTE IF S8600B GOES INTO LOCKOUT RESET SYSTEM ON OFF SWITCH IS IN OFF POSI
3. 4 Fig 30 Support straps for horizontal runs FP1185 Up to two 45 elbows may be used within the hori Fig 32 Maximum termination to roof clearance zontal run For each 45 elbow used on the hori zontal level the maximum horizontal length must be reduced by 18 457 mm Example Maximum horizontal length Zero elbows 10 3 1x 45 elbows 8 2 6 2 45 elbows 7 2 1 of an 8 ft 2 43 vertical rise Two 2 sets of 45 elbow offsets may be used within the vertical sections From zero to max 8 ft 2 43 m vent pipe can be used between elbows Fig 30 7DVCS supports offsets Fig 33 This application will require you first determine the roof pitch and use the appropriate starter kit See Venting Components List Page 22 The maximum angular variation allowed in the sys tem is 270 Fig 31 The minimum height of the vent above the highest point of penetration through the roof is 2 610mm Fig 32 10006326 21 360 DVS Series Direct Vent Fireplaces Vertical Through the Roof Installation 1 Locate your fireplace 2 Plumb to center of the 4 flue collar from ceiling above and mark position 3 Cut an opening equal to 9 x 9 240 x 240mm 4 Proceed to plumb for additional openings through the roof In all cases the opening must provide a minimum of 1 25 mm clearance to the vent pipe i e the hole must be at least 9 x 9
4. 10 x 9 W 265 x 240 mm through the exterior wall and frame Frame in the opening per Figure 18 Noncombustible walls Cut a round hole measuring 7 190 mm diameter through the exterior wall and frame Fig 18 STEP2 For combustible walls Measure wall thickness and cut zero clearance sleeve parts to proper length Max length is 12 305 mm Assemble sleeve to its maximum opening of 10 x 9 265 x 240 mm and attach to firestop with 8 sheetmetal screws supplied Install firestop assembly Fig 19 NOTE Zero clearance sleeve is required only for com bustible walls 10006326 Vent Opening for Combustible Wall 9 240mm 10 25 265mm Zt Framing Detail Vent Opening for Noncombustible Wall VO584 100 Fig 18 Locate vent opening on rear wall Maximum Length 12 305mm 8 Screws 2 gt Clearance 7 Side View CFM135a Sleeve Zero Clearance Sleeve Fig 19 Adjustable zero clearance sleeve STEP 3 Measure the horizontal length requirement for the vent ing including a 2 51 mm overlap i e from the elbow to the outside wall face plus 2 51 mm or the distance required if installing a second 90 elbow Fig 20 STEP 4 Install the 4 102 mm vent to the appliance collar and secure with three 3 sheetmetal screws Install the 7 178 mm vent pipe to the appliance collar and secure wi
5. 458mm 18 458mm distance of 2 610mm from the center line of the terminal E Clearance to unventilated soffit 12 305mm 12 305mm F Clearance to outside corner G Clearance to inside corner see next page H Clearance to each inside of center line 3 91cm within a height of 15 5m 3 91cm within a height of 15 extended above meter regulator assembly above the meter regulator assembly 5m above the meter regulator assy J Clearance to nonmechanical air supply inlet 6 15cm for appliances lt 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 other appliances appliances gt 10 000 Btuh 3kW and 23cm for appliances 10 000 100 000 Btuh 30kW 36 91cm Btuh 3kW and 50 000 Btuh for appliances gt 100 000 Btuh 30kW 15kW 12 30cm for appliances gt 50 000 Btuh 15kW feet 3m horizontall driveway located on public propert 7 Bacony N Clearance above a roof shall extend a minimum of 24 610mm above the highest point when it passes through the roof surface any other obstruction within a horizontal distance of 18 450mm 1 In accordance with the current CSA B149 Installation Codes 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Codes T A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings an
6. Allow to cool before proceeding This conversion procedure must be carried out by an authorized service provider gt Disconnect power to unit and shut off the gas supply Remove window frame assembly see Window Frame Assembly Removal Section Carefully remove the logs and lava rock material Remove the screws holding the burner housing as sembly in place Remove the burner housing assembly On some models you may need to loosen the pilot bracket retaining screw nut and tilt the pilot and bracket assembly to gain sufficient clearance to remove the burner housing assembly Remove front and rear orifice and replace with orifice supplied in the conversion kit NOTE On 360DV S2 S3 SL SR both burner orifices are the same size 7 Remove the screws holding the air shutter to the burner tubes Fig 47 Note the alignment of the air shutter on the tubes Remove the air caps and re place them with the new air shutters supplied in the conversion kit ABO N Air Shutter Retain ing Screws Air Shutters FP1447 Fig 47 Air shutter adjustment 8 SIT Top Convertible Pilot Gently lift off pilot hood from the pilot NOTE Do not remove the spring clip holding the hood in place Us ing a correctly sized Allen key unscrew the exposed orifice Insert the new orifice supplied in the kit do not overtighten the orifice Replace the pilot hood ensuring the index tab aligns with the notch o
7. position 10006326 5 6 Turn the remote switch if used OFF Turn the wireless remote if used OFF Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow instructions B in the safety warnings above If you do not smell gas go onto the next step Close the access door Turn ON all electrical power to the appliance Turn remote switch or wireless remote to ON If the appliance will not operate follow the instructions Turning Off the Gas to the Appliance below and call your service technician or gas supplier Gas Supply 4 2 NPT x 1 2 Flare d Bge PIE E Flex NN NOTE Shutoff valve is shown in position 29 360 DVS Series Direct Vent Fireplaces Troubleshooting the Gas Control System SIT NOVA 820 MILLIVOLT VALVE NOTE Before troubleshooting the gas control system be sure external gas shut off is in the position WARNING REMOVE GLASS FRONT BEFORE DOING ANY GAS CONTROL SERVICE WORK SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION 1 Spark ignitor will not light 2 Pilot will not stay lit after carefully following lighting instructions 3 Pilot burning no gas to main burner 4 Frequent pilot outage problem 30 A Defective or misaligned electrode at pilot B Defective ignitor Push Button A Defective pilot generator thermocouple remote wall switch B D
8. 10006171 10006174 10006171 Flue Pipe Plate Assembly 10002554 10002554 10002554 10002554 FluePipe Plate Gasket 10002237 10002237 10002237 1000223 Flue Cover Plate 10002298 10002298 10002298 10002298 Flue Cover Plate Gasket 10002233 10002233 10002233 10002233 Relief Plate with gasket 10002429 10002429 10002429 10002429 Deflector Cabinet Top Short N A 10002260 10002260 10002260 Corner Post left N A 10006190 10006190 10006190 Corner Post right N A 10006191 10006191 10006191 Corner Post Mounting Bracket N A 10006195 10006195 10006195 Deflector Cabinet Top Long 54364 54364 54364 54364 31a Pilot Assembly SIT Top Convertible EN 10002387 10002387 10002387 10002387 31b Pilot Assembly SIT Top Convertible EP 10002388 10002388 10002388 10002388 32 lgnitor Electrode SIT 52465 52465 52465 52465 33 Cable Ignitor SIT EN EP 10000696 10000696 10000696 10000696 34a SIT822 Gas Control Valve EN 57884 57884 57884 57884 34b SIT822 Gas Control Valve 57883 57883 57883 57883 35 Sensing Electrode w Cable EN EP 57885 57885 57885 57885 36 Transformer 24V EN EP 7522409 7522409 7522409 7522409 37 l gnition Module Honeywell 20000005 20000005 20000005 20000005 Wire Harness Honeywell 10001979 10001979 10001979 10001979 38 10006326 FK24 Fan Assembly This auxiliary fan system increases the efficiency of the circulation of the heated air The FK24 fan kit allows variable speed control of the
9. 240 x 240mm 5 Place fireplace into position 6 Place firestop s 7DVFS or Attic Insulation Shield 7DVAIS into position and secure Fig 35 7 Install roof support Fig 33 and roof flashing making sure upper flange is below the shingles Fig 34 8 Install appropriate pipe sections until the venting is above the flashing Fig 34 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 32 11 Apply high temperature sealant to 4 and 7 collars of vertical vent termination and install Typical Roof Sup port Application Typical Ceiling Sup port Application CFM110 Sheet Metal Screws 5 3 per joint Sealant Storm Collar TWL101a Fig 34 Roof flashing 22 If there is a room above ceiling level a A firestop spacer must be installed on both the bottom and the top sides of the ceiling joists Fig 35 If an attic is above ceiling level a 7DVAIS Attic Insulation Shield must be installed NOTE The enlarged ends of the vent sections are to always face downward Attic Insulation Shield Ji Ceiling In stallation 11 278mm 7 279 mm Upper Floor Firestop Spacer pe Nails 4 CFM100 Fig 35 Firestop and attic insulation shield 10006326 360DVS Series Direct Vent Fireplaces Twist Lock Venting Components 7TDVRVT Through the Wall Rear Vent Termination Starter Kit Model 7TDVSK S
10. be included with the appliance or equipment installation instructions and The special venting systems shall be Product Approved by the Board and the instructions for that system shall include a parts list and detailed installation instructions A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment all venting instructions all parts lists for venting instructions and or all venting design instructions shall remain with the appliance or equipment at the completion of the installation 10006326 360DVS Series Direct Vent Fireplaces Fireplace Dimensions 360DVS2 Rear Vent Configuration Electrical Al A Electrical Access Access Y Gas Line Gas Line Access IN Access Lf ite Le l Ho 2 D LES C _ yl Electrical AI Electrical Access Access Gas Line S al Gas Line f sAeenss JN T Appliance Dimensions Top Vent Configuration 38 968 mm 38 968 mm 43 1099 mm 24 610 mm 24 610 mm 37 949 mm 35 7 911 mm 7 178mm 12 305 mm 3 80mm 29 70 mm 14 33 14 33
11. box 3 Connect the white wire from the wall switch to the black wire from the transformer using an approved wire nut Connect the black wire from the wall switch to the black wire running from the 6 position of the ignition module also using an approved wire nut 360DVS Series Direct Vent Fireplaces HONEYWELL IGNITION MODULE 24V MVAP PV GRD 24V SENSE SPARK 1 2 3 56 um ORANGE ORANGE L POWER CORD W FEMALE SPADE 24 VAC 120 VAC ON WHITE BLACK H WHITE BLACK YELLOW o GREEN L 120 VAC Lo 24 VAC RET 40VA TRANSFORMER WALE SWITCH FP1225 Fig 12 Honeywell ignition module General Venting Your fireplace is approved to be vented either through the side wall or vertically through the roof e Only CFM Corporation venting components specifi cally approved and labeled for this fireplace may be used e Venting terminals shall not be recessed into a wall or siding e Horizontal venting must be installed on a level plane without an inclining or declining slope There must not be any obstruction such as bushes 10006326 garden shed fencing deck or utility building within 24 610mm from the front of the termination hood Do not locate the termination hood
12. box Pt ZA1200 be hard wired into the house supply The fan lead is then plugged into the box 10006326 360DVS Series Direct Vent Fireplaces FK12 This auxiliary fan system increases the efficiency of the circulation of the heating air Optional Accessories The FK12 Fan Assembly is a fixed speed fan system and does not allow for variable speed control It does not use the speed control unit or the heat sensor in cluded with the FK24 Kit Specifications 115 Volts 60 Hz 56 Watts Maintenance The fan itself does not require regular maintenance however periodic cleaning of the fan and the surround ing area is required Check the area under the control door lower louvre assembly and in front of the fan Wipe or vacuum this area at least once a month during the operating season Installation The fan assembly is supplied fully wired eliminating the need for a licensed electrician to carry out the installa tion 1 Open the lower Louvre assembly Maneuver the fan and bracket assembly around the gas valve and lines to locate the unit against the back wall of the appliance resting on the base 2 With the protective cover removed from the self ad hesive Velcro strips apply mild pressure to the fan amp bracket unit to secure the strips to the metal panels No further securing is required 3 Power to the fan can be supplied by plugging the supplied lead into a convenien
13. circulation fan and also incorporates a heat sensor in the circuit Specifications 115 Volt 60Hz 56 Watts Maintenance The fan itself does not require regular maintenance however periodic cleaning of the fan and the surround ing area is required Check the area under the control door lower louvre as sembly and in front of the fan and wipe or vacuum this area at least once a month during the operating season Installation The fan assembly and other components are supplied fully wired eliminating the need for a licensed electri cian to carry out the installation If hard wiring the fan in using Method B following we strongly recommend the use of a licensed electrician 1 Open the lower louvre assembly Maneuver the fan and bracket assembly around the gas valve and lines to locate the unit onto the screw studs on the back of the fireplace Install the thermal sensor under the bottom of the firebox locating it over the two 2 10 mm studs and secure it with nuts Locate the fan speed control unit This can be fit ted behind the lower louvre assembly as in Figure 51 or located remotely in a conveniently located wall mounted electrical box Remote location of the speed control will require suitable extension of the component wiring 4 The power supply may be connected in two ways Method A Route the 6 lead fitted to the unit to a conveniently located wall socket Method B receptacle
14. for SIT valve a F584 703 Flame Characteristics Fig 45 Correct pilot flame appearance It is important to periodically perform a visual check of the pilot and burner flames Compare them to the pictorials illustrated below Figs 45 amp 46 If the flame patterns appear abnormal contact a qualified service provider for service and adjustment Fig 46 Correct log flame appearance 10006326 27 360 DVS Series Direct Vent Fireplaces 28 Lighting Operating Instructions FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This heater has a pilot light which must be lit manually When lighting the pilot follow these instructions exactly BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions f you cannot reach your gas supplier call the Fire Department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand do not try to repair it call a qualifi
15. horizontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of the fire place to the face of the outer wall NOTE When installing the appliance as a rear vent unit the 90 transition elbow attached directly to the rear of the unit is not included in the following criteria and calculations Unless it is specifically mentioned this elbow should be ignored when calculating venting layouts Bo 1 1 s Fig 20 Maximum three 3 90 elbows per installation 17 360 DVS Series Direct Vent Fireplaces Horizontal plane means no vertical rise exists on this portion of the vent assembly The maximum number of 90 elbows per side wall installation is three 3 e 90 elbow is fitted directly on top of the fireplace flange the maximum horizontal vent run before the termination or a vertical rise is 36 914mm Max 20 508mm 36 914mm N Fig 21 Maximum horizontal run w no rise fa 90 elbow is used in the horizontal vent run level height maintained the maximum horizontal vent length is reduced by 36 914 mm Fig 21 This does not apply if the 90 elbows are used to increase or redirect a vertical rise Example According to the vent graph Fig 16 the maximum horizontal vent length in a system with a 7 191mm vertical rise is 20 ft 6 1m but if a 90 is required in the horizontal vent it
16. in step 3 to clamp the top trim piece in place With the trim piece in place along the top edge refit and secure the top deflector plate 7 Reattach the lower louvre panel to the hinges and re place the top louvre assembly protective plastic wrap must be removed A from the trim pieces before the appliance is put into service If plastic wrap is not re moved a health or fire hazard may develop 10006326 360DVS Series Direct Vent Fireplaces 10006326 41 360 DVS Series Direct Vent Fireplaces 42 10006326 LIMITED LIFETIME WARRANTY PRODUCT COVERED BY THIS WARRANTY All Vermont Castings gas stoves gas inserts and gas fireplaces and all Majestic brand gas fireplaces equipped with an Insta Flame Ceramic Burner or standard steel tube burner BASIC WARRANTY CFM Corporation hereinafter referred to collectively as the Company warrants that your new Vermont Castings or Majestic Gas Fireplace Stove is free from manufacturing and material defects for a period of one year from the date of purchase subject to the following conditions and limitations EXTENDED LIFETIME WARRANTY The heat exchanger where applicable and combustion chamber of every Vermont Castings or Majestic gas product is warranted for life against through wall perforation All appliances equipped with an Insta Flame Ceramic Burner have limited lifetime coverage on the ceramic burner plaque Warrantees are made to the original owner subject to proof o
17. must be reduced to 17 ft 5 2m NOTE The sum of Dim A and Dim B must not be greater than 17 ft 5 2m Fig 22 5 2m Max 7 6 2 3m Fig 22 Horizontal run reduction 18 The maximum number of 45 elbows permitted side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run Foreach 45 elbow installed in the horizontal run the length of the horizontal run MUST be reduced by 18 45 cm This does not apply if 45 elbows are installed on the vertical part of the vent system The maximum number of elbow degrees in a system is 270 Example shown in Figure 23 Elbow1 90 Elbow 2 45 Elbow3 45 Elbow4 90 Total angular variation 270 1 2 3 4 270 gt FP1438 Fig 23 Maximum elbow usage Vertical Side Wall Installation STEP 1 Locate and cut vent opening in the side wall It may be necessary to first position the fireplace and measure to obtain the hole location Depending on whether the wall is combustible or noncombustible cut the opening to size per Figure 24 Combustible walls Cut a rectangular hole measuring 9 H x 9 W 240 x 240mm through the exterior wall and frame Frame in the opening per Figure 24 Noncombustible walls Cut a round hole measuring 7 190 mm diameter through the exterior wall and frame Fig 24 STEP 2 For combustible walls Measure wall t
18. of the log is to be placed over the center of the grate The inner end of the log ensures that the bottom hole is located on the pin of the support 4 Place the log front left B121 on the grate The square hole located on the underside of the log is to place over the corner leg of the grate The inner end of the log ensures the bottom holes are located on the pin of the support 5 Place the log front right B122 Once more the square hole fits over the corner leg of the grate The inner end of this log maintains a recess on the underside which locates over the knob on the top of the log front left B121 to secure the inner end in place 6 Place the log rear left B123 The bottom back of the log rests on the grate The notch at the back of the log locates over the knob on the top of the log rear B120 The bottom of the log rests on top of the log front left 121 7 Place the log bottom left B124 The log maintains a step on the outer end which rests against the prong of the grate The alternate end rests on the side floor refractory panel 8 Place the log rear right B125 The log maintains a hole on the underside which rests over the knob on the top of the log rear B120 The bottom of the log rests against the side floor refractory panel and the side rests against the last prong of the grate 9 Place the log center B126 The log maintains a hole on the underside which rests over the knob on the top of th
19. wall 3 914mm Z Minimum distance between edge of a glass panel and an adjacent wall 3 76mm B Island Location Fig 3 X Maximum length of horizontal venting 20 6 1m Refer to the venting section in this manual for specific dimen sions Top of unit to 36 914 mm Front of unit to combustibles 36 914 mm Appliance 0 0 mm to standoff T 0 0 mm Vent End 1 2 13 mm to rear panel Nonvent End DVS2 0 0 mm Venting Concentric sections of DV Vent Top bottom amp sides 1 25 mm Nonconcentric sections of DV Vent Side and 1 25 mm 2 51 mm The height at which a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel This also applies to the distance between the mantel leg if so fitted and the fireplace For correct mounting height and width refer to Fig 4a and 4b and the Mantel Chart below The fitting of a bay window trim kit does not affect the distances and reference points referred to in the dia gram and chart Noncombustible mantels and legs may be installed at any height and width around the appliance When using paint or lacquer to finish the mantel such paint or lacquer must be heat resis
20. where excessive snow or ice buildup may occur Be sure to check the vent termination area after snow falls clear it to prevent accidental blockage of the venting system When using a snow blower make sure snow is not directed toward the vent termination area Location of Vent Termination It is imperative the vent termination be located observ ing minimum clearances as shown on the following page 13 360 DVS Series Direct Vent Fireplaces General Venting Information Termination Location INSIDE CORNER DETAIL Fixed Closed Ry DG CFM145a VENT TERMINATION AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED Canadian Installations US Installations Clearance above grade veranda porch 12 30cm 12 30cm deck or balcony B Clearance to window or door that may be 6 15cm for appliances 6 15cm for appliances opened lt 10 000Btuh 3kW 12 30cm lt 10 000 Btuh 3kW 9 for appliances gt 10 000 Btuh 3kW and 23cm for appliances gt 10 000 lt 100 000 Btuh 30kW 36 91cm Btuh 3kW and lt 50 000 Btuh for appliances gt 100 000 Btuh 30kW 15kW 12 30cm for appliances gt 50 000 Btuh 15kW C Clearance to permanently closed window 12 305mm recommended to 12 305mm recommended to prevent window condensation prevent window condensation D Vertical clearance to ventilated soffit located above the terminal within a horizontal 18
21. 00 360DVS3EN 26 600 360DVS3EP 28 500 360DVSLRN 26 600 360DVSLRP 28 500 360DVSRRN 26 600 Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installations must be in accordance with the current ANSI Z223 1 NFPA 54 and or local codes having jurisdiction Canada please consult provincial and or local authorities having jurisdiction for installations above 4 500 feet 1 370 m Gas Line Installation When purging the gas lines the window frame assembly must be removed The gas pipeline can be brought in through the vent end of the fireplace as well as the bottom Knockouts to allow gas pipe installation and testing any gas con nection are provided on the bottom behind the valve It is most convenient to bring the gas line in from the vent end of the valve as this allows fan installation or removal without disconnecting the gas line The gas line connection can be made with properly tinned 3 8 copper tubing 3 8 rigid pipe or an ap proved flex connector Since some municipalities have additional local codes it is always best to consult your local authority and the CSA B149 1 installation codes For USA installations consult the current National Fuel Gas Code ANSI Z223 1 NFPA 54 Always check for gas leaks with a mild soap and water solution Do not use an open flame for le
22. 0006326 360DVS Series Direct Vent Fireplaces Installation amp Operating Instructions This gas appliance should be installed by a qualified installer 11 When the fireplace is installed directly on carpeting vinyl preferably NFI or WETT Canada certified in accordance tile or any combustible material other than wood it must be with local building codes and current CSA B 149 1 Installation installed on a metal or wood panel extending the full width Codes for Gas Burning Appliances and Equipment If the unit is being installed in a mobile home the installation should comply with the current CAN CSA Z 240 4 code For U S A Installations follow local codes and or the current National Fuel Gas Code ANSI Z223 1 NFPA 54 FOR SAFE INSTALLATION AND OPERATION PLEASE NOTE THE FOLLOWING 1 This fireplace gives off high temperatures and should be located out of high traffic areas and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperatures of this fireplace and should stay away to avoid burns or ignition of clothing CAUTION Due to high glass surface temperature chil dren should be carefully supervised when in the same room as fireplace HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS 9 Under no circumstances should this fireplace be modified Parts removed for servicing should be rep
23. 22 10001822 10001822 Orifice Pilot PSE Prop 10001823 10001823 10001823 10001823 Orifice Pilot SIT Top convertible Nat 10002268 10002268 10002268 10002268 Orifice Pilot SIT Top conv Prop 10002269 10002269 10002269 10002269 Pilot tube amp fittings Top convertible 10001296 10001296 10001296 10001296 Manifold Tube amp Fittings 5 318 5 318 5 318 5 318 A Flexible Gas Line 18 with fittings 20002500 20002500 20002500 20002500 9 Thermocouple PSE 10001828 10001828 10001828 10001828 10 Thermocouple SIT Top Convertible 53373 53373 53373 53373 11 Thermopile 51827 51827 51827 51827 12 lgnitor electrode with cable SIT 10001297 10001297 10001297 10001297 13 Ignitor Piezo SIT 820 valve 52464 52464 52464 52464 14 lgnitor Piezo Honeywell Valve 20000062 20000062 20000062 20000062 15a Valve SIT 820 Nat 52677 52677 52677 52677 15b Valve SIT 820 Prop 52678 52678 52678 52678 16a Valve Honeywell Nat 10001782 10001782 10001782 10001782 16b Valve Honeywell Prop 10001759 10001759 10001759 10001759 17 Fan amp Bracket FK12 optional ZA1110 ZA1110 ZA1110 ZA1110 18 Fan amp Bracket FK24 optional 54103 54103 54103 54103 Temperature Sensor optional 51704 51704 51704 51704 Fan Speed Control optional 51738 51738 51738 51738 Speed Control Knob optional 51882 51882 51882 51882 Electric Cord 51865 51865 51865 51865 19 Remote ON OFF switch RN RP models 51842 51842 51842 51842 Wiring Ha
24. ASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS Louvre Removal The top side and top end Figure 36 louvres are removed by simply lifting the louvre assembly and 2 pulling the assembly away wan from the fireplace Fig 36 The lower side louvres are hinged along there lower edge and are folded down for He access to components in the base cavity of the fireplace The lower end louvre assembly on the 360DVS3 SL SR units is removed in the same man ner as the top louvre assem blies Louvre Glass Panel P1227 Window Frame Assembly Removal Side Window Frame Assemblies WN Shut off the gas supply Allow the fireplace to cool if it has been in operation Remove the top louvre assembly Lower the bottom louvre assembly Release the two clamps along lower edge of the frame by pulling down on clamp handles Fig 37 Tilt lower edge of frame out slightly and lift window frame assembly up and away from the fireplace 7 To reinstall the window frame assembly reverse this procedure Front Window Frame Assembly 1 Remove the top and bottom louvre assembly 2 Remove the lower window trim held in place with magnets 3 Remove both lower retaining screws Access to these screws is gained through the holes along the lower edge of the frame behind the trim Fig 38 4 Tilt lower edge of frame out slight
25. Multisided Top Rear Vent Convertible Direct Vent Fireplaces 360DVS2 360DVS3 360DVSL 360DVSR MAJESTIC FIREPLACES INSTALLER CONSUMER SAFETY INFORMATION PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE F tt gt IMPORTANT Read all instructions and warnings carefully before 21711 50 starting installation Failure to follow eee lt gt these instructions may result ECC possible fire hazard and will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY Installation and service must be formed by a qualified installer service Homeowner s Installation Do not store or use gasoline or other and Operating Manual flammable vapors and liquids in the vicinity of this or any other appliance If you smell gas Open windows Do not touch electrical switches Do not try to light any appliance Extinguish any open flame Do not use any telephone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas supplier s instructions If you cannot reach your gas supplier call the fire department NA 00 Nw Y y A N v D CERTIFIED 10006326 4 08 Rev 5 360 DVS Se
26. TION CHECK FOR CONTINUITY OF IGNITION CABLE AND GROUND WIRE NOTE IF GROUND IS POOR OR ERRATIC SHUTDOWN MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT THE TIME OF CHECKOUT CHECK THAT THE PILOT FLAME COVERS FLAME ROD AND IS STEADY TROUBLESHOOTING AND BLUE ENDS IF CHECKS ARE OKAY REPLACE MODULE 10006326 31 360 DVS Series Direct Vent Fireplaces Troubleshooting Honeywell VS8421 START Gas Supply On NO gt Supply Line Hooked Up Shutoff Valve Open YES Lockout Has Engaged Wait 60 Seconds And Try Again For Spark At Electrode While Pilot Lights With Piezo Depressing Piezo Ignitor 1 8 Gap To Pilot Hood Needed All Wiring Connections Replace Piezo Ignitor For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connections PILOT STAYS LIT Replace Thermopile Thermocouple Needs A Min Of 14mv Valve Is Turned On Wall Switch Is Not Turned On PILOT LIGHTS MAIN Watch For Grounded Wires BURNER Thermopile Needs A Min 325mv Plugged Burner Orifice Defective Valve Turn To Pilot YES Meter Should Read Greater Than 100mv If Not Replace SYSTEM OK 32 10006326 Fuel Conversion Instructions To convert this appliance from gas type to another fol low these instructions Before proceeding turn control knob to OFF and turn gas supply OFF Turn OFF any electricity that may be going to the appliance CAUTION Logs may be HOT
27. ak testing The gas control is equipped with a captured screw type pressure test point therefore it is not necessary to pro vide a 1 8 test point upstream of the control 10006326 1 2 Gas Supply E d gt NPT X 1 2 Flare Shut Off Valve 5 2 3 8 Flex Line FP297a Fig 5 Gas shutoff valve and flex connector When using copper or flex connector use only ap proved fittings Always provide a union when using black iron pipe so that the gas line can be easily discon nected for burner or fan servicing Refer to the gas specification for pressure details and ratings Isolate or disconnect this or any other gas appli ance control from the gas line when pressure test ing DO NOT subject the fireplace valve to test pressures exceeding 1 2 psi EB 1 Electrical Junction Box Connection The fireplace when installed must be electrically connected and grounded in ac cordance with local codes in the absence of local codes use the current CSA C22 1 Canadian Electrical Code For USA installations follow the local codes and National Electrical Code ANSI No 70 It is strongly suggested the wiring of the EB 1 Electrical Junction Box be carried out by a licensed electrician Ensure power to the supply line has been disconnected before commencing with this procedure The EB 1 electrical junction box has been supplied standard on this model to allow for easy connection of the opt
28. am Method B For instruction on wiring the EB 1 Electrical Junction Box see section EB 1 Electrical Junction Box Connection on Page 10 Remote Controls Optional remote control units are available to control dif ferent functions of the appliance CFM105 Model Function s Controlled RC1 ON OFF RC2 ON OFF amp Temperature IMTFK Wall mounted thermostat control 40 Decorative Trim Frame Kit The DV360TKMP Medium Trim Kit in polished brass is available for the 360DVS2 model only Each kit contains 4 polished brass trim pieces and the necessary attaching screws to frame one side window of the unit Installation Refer to Fig 53 1 Remove the top louvre assembly 2 Lower the bottom louvre assembly to expose the lou vre hinges Unscrew the retaining screws and remove the louvre assembly from the hinges 3 Remove the retaining screws that secure the top deflector plate above the top louvre opening and remove the plate Trim top Screws 4 lt Trim right Trim left Screws ARM Trim bottom Top trim piece FP4449 Top deflector plate Fig 53 Decorative trim frame installation 4 Using the screws provided attach the lower trim piece to the predrilled holes in the lower edge of the bottom louvre opening 5 Using the screws provided attach the two side trim pieces to the predrilled holes in the vertical side frames 6 Use the top deflector plate and the screws removed
29. anty is limited to the repair of or replacement of part s found to be defective in material or workmanship provided that such part s have been subjected to normal conditions of use and service after said defect is confirmed by the Company s inspection The company may at its discretion fully discharge all obligations with respect to this warranty by refunding the wholesale price of the defective part s Any installation labor construction transportation or other related costs expenses arising from defective part s repair replacement or otherwise of same will not be covered by this warranty nor shall the Company assume responsibility for same Further the Company will not be responsible for any incidental indirect or consequential damages except as provided by law SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIRCUMSTANCES THIS WARRANTY GIVES YOU SPECIFIC RIGHTSAND YOU MAY HAVE OTHERRIGHTS WHICH VARY FROM STATE TO STATE All other warranties expressed or implied with respect to the product its components and accessories or any obligations liabilities on the part of the Company are hereby expressly excluded The Company neither assumes nor authorizes any third party to assume on its behalf any other liabilities with respect to the sale of this Vermont Castings or Ma
30. burner compartment Remove and refit the logs per the instructions in this manual Always handle the logs with care as they are fragile and may also be hot if the fire place has been in use FK24 FK12 Fan Assembly The fan unit requires periodic cleaning At least once per month in the operating season open the lower lou vre panels and wipe or vacuum the area around the fan to remove any build up of dust or lint Brass Trim Clean the brass trim pieces using a soft cloth lightly dampened with lemon oil Do not use water or house hold cleaners on any brass components Cleaning the Standing Pilot Control System The burner and control system consists of burner tube gas orifice pilot assembly thermopile millivolt gas valve Most of these components may require only an occa sional checkup and cleaning and some may require ad justment If repair is necessary it should be performed by a qualified technician 1 Turn off pilot light at gas valve side 2 Let fireplace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal section Remove logs Vacuum burner compartment especially around orifice primary air openings Visually inspect pilot Brush or blow away any dust or lint accumulation Reinstall logs Ignite pilot refer to Lighting Instructions Reinstall window frame assembly A O Oo N 10006326 To obtain proper operation it is i
31. complete 10006350 10006350 10006350 10006350 1a Log Rear B120 10006315 10006315 10006315 10006315 1b Log Front Left B121 10006316 10006316 10006316 10006316 1c Log Front Right B122 10006317 10006317 10006317 10006317 1d Log Rear Left B123 10006318 10006318 10006318 10006318 1e Log Bottom Left B124 10006319 10006319 10006319 10006319 1f Log Rear Right B125 10006320 10006320 10006320 10006320 1g Log Center Right B126 10006321 10006321 10006321 10006321 2 Grate Assembly 10006014 10006014 10006014 10006014 Burner Housing Assembly Nat 10006148 10006148 10006148 10006148 3b Burner Housing Assembly Prop 10006299 10006299 10006299 10006299 Ceramic Burner Tile 10002165 10002165 10002165 10002165 A Orifice s Main burner Nat Refer to the rating plate for specific orifice information Orifice s Main Burner Prop Refer to the rating plate for specific orifice information 4a Pilot assembly PSE Nat 10001741 10001741 10001741 10001741 4b Pilot assembly PSE Prop 10001742 10001742 10001742 10001742 Pilot assembly SIT Top Conv Nat 10002264 10002264 10002264 10002264 5b Pilot assembly SIT Top Conv Prop 10002265 10002265 10002265 10002265 6 Pilot PSE with cable amp electrode 10001824 10001824 10001824 10001824 7 Pilot SIT Top Convertible 10002266 10002266 10002266 10002266 8 Pilot Hood SIT Top Convertible 10002385 10002385 10002385 10002385 Orifice Pilot PSE Nat 10001822 100018
32. d serves both dwellings t only permitted if veranda porch deck or balcony is fully open on a minimum 2 sides beneath the floor NOTE 1 Local codes or regulations may require different clearances 2 The special venting system used on Direct Vent Fireplaces are certified as part of the appliance with clearances tested and approved by the listing agency 3 CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements Fig 13 Vent termination clearances 14 10006326 Termination Clearances 360DVS Series Direct Vent Fireplaces Termination clearances for buildings with combustible and noncombustible exteriors Inside Corner Outside Corner Combustible 6 152 mm Noncombustible 2 51 mm Balcony Balcony Combustible 6 152 mm Noncombustible 2 51 mm with no side wall with perpendicular side wall 52504070 M KK Combustible amp Noncombustible Combustible amp Noncombustible ME 24 610 mm 12 305 mm P 20 508 mm 5066690 ERR wed Alcove Applications CWA Q 23 V E Min 6 152 mm for non vinyl sidewalls Min 12 305 mm for vinyl sidewalls 8 2 4 m Min No of Ca
33. e discarded however if the unit is converted back to rear vent a new piece of insulation material approved by CFM Corporation must be used for this purpose NOTE When converting appliance to top vent 1432 ensure the insulation material referred to step 3 is completely removed 4 Remove the 4 screws securing the flue cover plate to the top of the intake box and remove the cover Flue Cover and gasket Fig 11 5 Remove 4 screws securing the flue pipe to back of the intake box and remove pipe and gasket Fig 11 6 Secure the plate and gasket removed in step 4 over the flue opening in the back of the intake box En sure the gasket is in place and undamaged 7 Install the flue pipe and gasket removed in step 5 over the flue opening in the top of the intake box 8 Refit the outer collar adapter and gasket to the unit with the round collar on the top Secure the adapter with the 10 screws removed in step 1 Fig 11 Flue pipe removal 12 10006326 Electronic Gas Control Valve This appliance may be fitted with a Honeywell ignition module Installation of the remote ON OFF starter switch on electronic ignition units Fig 12 1 Thread the wiring through the holes on the side panels of the appliance Take care not to cut the wire or insulation on metal edges Route the wire to a conveniently located receptacle box 2 Attach the wire to the ON OFF switch and install the switch into the receptacle
34. e log front right B122 The alternate end rests against the side floor refractory panel and positions between the two 2 prongs of the grate 25 360 DVS Series Direct Vent Fireplaces Side of Fireplace B120 125 Fig 41 360DVS log placement Lava Rock and Ember Material Placement Your log set contains Ember Material and two types of Lava Rocks Set these materials in place after the logs have been installed Ember Material Pt 51915 Remove ember material from the bag and separate it into small pieces then scatter it over burner tiles in a random fashion Do not pack down ember material leave it in a fluffy state Lava Rock Pt 10001454 Remove lav rock material from packaging and spread it over ceramic floor panels outside log stack Do not place this lava rock material on burner tiles 26 B126 LG320 epis BugueA Flame amp Temperature Adjustment RN RP Models For units equipped with HI LO valves the flame adjust ment is accomplished by rotating the HI LO adjustment knob located near the center of the gas control valve Fig 42 and Fig 43 Turn H counterclockwise Turn clockwise to decrease to increase flame height flame height Fig 42 Flame adjustment knob for Honeywell valve 10006326 360DVS Series Direct Vent Fireplaces Turn counterclockwise Turn clockwise to increase to decrease flame height flame height Fig 43 Flame adjustment knob
35. ed service technician Applying force or any attempted repair may result in a fire or explosion Do not use this fireplace if any part has been under water Immediately call a qualified service techni cian to inspect the heater and to replace any part of the control system and any gas control which has been under water Lighting Instructions STOP Read the safety information above Turn off all electrical power to the fireplace For MN MP TN TP appliances ONLY go on to Step 4 For RN RP appliances turn the On Off Switch to OFF position or set thermostat to lowest level Open control access panel Push in gas control knob slightly and turn clockwise 7 to Euro SIT SIT NOVA Honeywell Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow in the safety infor mation above If you do not smell gas go to the next step Remove glass door before lighting pilot See Glass Frame Removal section Visibly locate pilot by the main burner Turn knob on gas control counterclockwise X to PILOT 10 Push the control knob all the way in and hold Immediately light the pilot by repeatedly depress ing the piezo spark igniter until a flame appears Continue to hold the control knob in for about one 1 minute after the pilot is lit Release knob and it will pop back up Pilot should remain lit If it goes out r
36. ee tL re P I eis 24 Louvre Removal ee 24 Window Frame Assembly 24 Glass Clean in EE 25 Ceramic Refractory Installation 25 urrilulenee c TL 25 Lava Rock amp Ember Material Placement saaa 26 Flame amp Temperature Adjustment i Renan kn nb 26 Flame Characteristics M P 27 Lighting amp Operating Instructions 28 Lighting amp Operating Instructions 29 Troubleshooting the Gas Control System 30 FUG Conversion Instrueliolis s oer i Erie vr aaae a Da ANa 33 Maintenance tnn dread pan aen dd 35 CITED uua E 36 Optional Accessories Fan Aree eA ene Remote Controls Decorative Tim Frame veel petere rrr red green 40 Warranty Mt X 43 M trey 44 2 1
37. efective automatic valve A Wall switch or wires defective B Thermopile may not be generating sufficient millivoltage C Plugged burner orifice D Defective automatic valve operator A Pilot flame may be too low or blowing high causing the pilot safety to drop out B Possible blockage of the vent terminal Using a match light pilot If pilot lights turn off pilot and push the red button again If pilot will not light check the gap at electrode and pilot it should be 1 8 to have a strong spark Push piezo Ignitor Button Check for spark at electrode and pilot If no spark to pilot and electode wire is properly connected replace ignitor Check pilot flame Must impinge on thermocouple thermopile NOTE This pilot burner assembly utilizes both a thermocouple and a thermopile The thermocouple operates the main valve opera tion ON OFF Clean and or adjust pilot for maxi mum flame impingement on thermopile and thermo couple Turn valve knob to Pilot Maintain flow to pilot millivolt meter should read greater than 10 mV If the reading is okay and the pilot does not stay on replace the gas valve NOTE An interrupter block not supplied must be used to conduct this test Check wall switch and wires for proper connections Jumper wires across terminals at wall switch if burner comes on repalce defective wall switch If okay jumper wires across wall switch wires at valve if burner comes on wire
38. epeat steps 5 through 8 f knob does not pop up when released stop and immediately call your service technician or gas supplier If after several tries the pilot will not stay lit turn the gas control knob to OFF and call your service technician or gas supplier 11 Replace glass door 12 Turn gas control knob to ON position 13 For RN RP appliances turn the On Off switch to position or set thermostat to desired setting 14 Turn on all electrical power to the fireplace To Turn OFF Gas to Heater Turn the On Off switch to Off position or set the thermostat to lowest setting Turn off all electric power to the fireplace if service is to be performed 3 Open control access panel 4 Push in gas control knob slightly and turn clockwise to OFF Do not force 5 Close control access panel 10006326 360DVS Series Direct Vent Fireplaces Lighting Operating Instructions For Fireplaces equipped with SIT822 Gas Valve EN or EP Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury and loss of life For your safety read the following warnings before lighting the appliance A This fireplace is equipped with an ignition device which automatically lights the pilot DO NOT try to light the pilot by hand BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next
39. f purchase and the conditions and limitations listed on this Warranty Document COMPONENT WARRANTY CAST IRON All external and internal cast iron parts are warranted for a period of three years Note On porcelain enamel finished external parts and accessories The Company offers no Warranty on chipping of enamel surfaces Inspect all product prior to accepting it for any damage to the enamel The salt air environment of coastal areas or a high humidity environment can be corrosive to the porcelain enamel finish These conditions can cause rusting of the cast iron beneath the porcelain enamel finish which will cause the finish to flake off Dye lot variations with replacement parts and or accessories can occur and are not covered by warranty GLASS DOORS Glass doors are covered for a period of one year Glass doors are not warranted for breakage due to misuse or accident Glass doors are not covered for discoloration or burned in stains due to environmental issues or improper cleaning and maintenance BRASS PLATED PARTS AND ACCESSORIES Brass parts should be cleaned with Lemon oil only Brass cleaners cannot be used Mortar mix and masonry cleaners may corrode the brass finish The Company will not be responsible for nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions GAS VALVES Gas valves are covered for a period of one year ELECTRONIC AND MECHANICAL COMPONENTS Electronic and mec
40. g 27 Horizontal length requirement STEP 6 Use appropriate length of pipe section telescopic or fixed and install The 20 508 mm section of pipe which goes through the wall is packaged with the 7DVSK starter kit and can be cut to suit if necessary Seal vent pipe and firestop gaps with high temperature sealant to restrict cold air being drawn in around the fireplace STEP 7 Apply high temperature sealant to 4 102 mm and 7 178 mm collars or to the termination 1 25 mm away from the crimped end Guide 4 and 7 collars of vent terminations into respective vent pipes Double check vent pipes to see that they overlap the collars by 19 360 DVS Series Direct Vent Fireplaces 2 51 mm Secure termination to the wall with screws provided and caulk around the wall plate to weather proof One alternative to screwing the termination directly to the wallis the use of expanding plugs or an approved exterior construction adhesive Or you may attach the termination with screws through the inner body into the 4 102 mm vent pipe however for this method you must extend the 4 102mm pipe approximately 6 153 mm beyond the outer face of the wall Support the horizontal pipes with metal pipe straps every 36 914mm Below Grade Installation When it is not possible to meet required vent terminal clearances of 12 305 mm above grade level we rec ommend using a starter kit It allow
41. gether align the beads of the male end with the grooves of the female end While bringing the pipes together twist the pipe until the flange on the female end contacts the external flange on the male end It is recommended that you secure the joints with three 3 sheet metal screws however this is not mandatory with twist lock pipe NOTE For ease of assembly use a lubricant Vaseline or similar substance on male end of twist lock pipe prior to assembly Male End E 2 Screw Holes TWL100 Fig 15 Twist lock pipe joints 15 360 DVS Series Direct Vent Fireplaces to Use the Vent Graph The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimension on the Sidewall Vent Graph bellow locate the point intersecting with slanted graph line 2 From the point of this intersection draw a vertical line to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example A If vertical dimension from floor of the fireplace is 11 3 4 m horizontal run to the face of outer wall must not exceed 14 4 3 m Example B If vertical dimension from floor of the unit is T 2 14 m h
42. hanical components of the burner assembly are covered for one year All steel tube burners are warranted for one year ACCESSORIES Unless otherwise noted all components and CFM Corporation company supplied accessories are covered for a period of one year CONDITIONS AND LIMITATIONS This new Vermont Castings or Majestic product must be installed by a competent authorized service contractor A licensed technician as prescribed by the local jurisdiction must perform any installation service work It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product Any alteration willful abuse accident or misuse of the product shall nullify this warranty This warranty is non transferable and is made to the original owner provided that the purchase was made through an authorized supplier of the Company The customer must pay for any Authorized Dealer in home travel fees or service charges for in home repair work It is the dealers option whether the repair work will be done in the customer s home or in the dealer s shop fuponinspection the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor 10006326 Any part and or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty whichever is longest This warr
43. hickness and cut zero clearance sleeve parts to proper length Max length is 12 305mm Assemble the sleeve and attach it to the firestop with 8 sheet metal screws supplied Install the firestop assembly Fig 25 Zero clearance sleeve is required only for combustible walls 10006326 Vent Opening for Combustible Wall 9 240mm Framing Detail Vent Opening for Noncombustible Wall VO584 100 Maximum Length 12 305mm Zero Clearance Sleeve N Zero Clearance Sleeve Side View Fig 25 Adjustable zero clearance sleeve STEP 3 Place fireplace into position Fig 26 Measure the verti cal height X required from the base of the flue collars to the center of the wall opening Fig 26 Vertical height requirement 10006326 360DVS Series Direct Vent Fireplaces STEP 4 Apply a bead of silicone to the inner and outer flue collars of the fireplace and using appropriate length of pipe section s attach to fireplace with three 3 screws Follow with the installation of the inner and outer elbow again secure joints as described in Connecting Vent Pipes section STEP 5 Measure the horizontal length requirement including a 2 51 mm overlap i e from the elbow to the outside wall face plus 2 51 mm or the distance required if installing a second 90 elbow Fig 27 Always install horizontal venting on a level plane ij ij Fi
44. idewall Starter Kit Model 7TDVSKV Vertical Venting for 7TDVSKV A order 1 12 to 6 12 roof pitch for 7TDVSKV B order 7 12 to 12 12 roof pitch for 7TDVSKV F order flat roof Starter Kit Model 7TDVSKS Snorkel Kit Snorkel Termination 7TDVSNORK for Below Grade Installation 45 Elbow 7TDVT45 for Rear Vent to Vertical Vent or Vertical Horizontal Offsets 90 Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic Vent Sections 7TDVP1218 12 to 18 adjustable length 7TDVP3564 35 to 64 adjustable length Pipe Sections for vertical or horizontal venting Model 7TDVP8 4 per box Model 7TDVP12 4 per box Model 7TDVP24 4 per box Model 7TDVP36 Model 7TDVP48 Firestop Spacer Model 7DVFS Attic Insulation Shield Model 7DVAIS Vertical Horizontal Combination Offset Support Model 7DVCS 10006326 23 360 DVS Series Direct Vent Fireplaces Operating Instructions Glass Information Only glass approved by CFM Corporation should be used on this fireplace The use of any non approved replacement glass will void all product warranties Care must be taken to avoid breakage of the glass Do not operate appliance with glass front removed cracked or broken Replacement glass complete with gasket is available through your Majestic Fireplaces dealer and should only be installed by a licensed qualified service person HOT GL
45. ional fan kits Fig 6 To connect the EB 1 box to the house electrical supply follow the steps below 1 Remove the front cover of the EB 1 box 2 Remove the plug socket assembly from the EB 1 box Feed the supply line in from the out through the elec trical knockout Connect the ground wire of the supply line to the green screw of the socket assembly Connect the white wire of the power line to the chrome screw of the socket assembly Connect the black wire of the power supply line to the brass screw polarized of the socket assembly O 10006326 360DVS Series Direct Vent Fireplaces 7 Refit the socket assembly back into the electrical box and replace the cover plate 8 The EB 1 electrical junction box is now ready to sup ply power to the FK12 or FK24 fan kit if used Electrical Inlet Hole Gas Inlet Hole EB 1 Electrical box Depend ing on the specific model this box may be installed on either side of the appliance Fig 6 EB 1 attachment Remote ON OFF Switch Installation Do not wire the remote ON OFF wall switch for this gas appliance into a 120V power A supply 1 Thread the wiring through the holes on the end panels of the appliance Take care not to cut the wire or insulation on metal edges Route the wire to a conveniently located receptacle box Attach the wire to the ON OFF switch and install the switch into the receptacle box Connect the othe
46. jestic product The warranties as outlined within this document do not apply to chimney components or other non CFM Corporation accessories used in conjunction with the installation of this product Damage to the unit while in transit is not covered by this warranty but is subject to claim against the common carrier Contact the dealer from whom you purchased your fireplace stove do not operate the appliance as this might negate the ability to process the claim with the carrier The Company will not be responsible for a Down drafts or spillage caused by environmental conditions such as near by trees buildings roof tops hills or mountains b Inadequate ventilation or negative air pressure caused by mechanical systems such as furnaces fans clothes dryers etc This warranty is void if a The fireplace has been operated in atmospheres contaminated by chlorine fluorine or other damaging chemicals b The fireplace has been subjected to prolonged periods of dampness or condensation c Anydamages tothe fireplace combustion chamber heat exchanger or other components due to water or weather damage which is the result of but not limited to improper chimney venting installation d Any alteration willful abuse accident or misuse of the product has occurred IF WARRANTY SERVICE IS NEEDED Contact your supplier Make sure you have your warranty your sales receipt and the model serial number of your CFM Corporatio
47. laced prior to operating this fireplace again Installation and any repairs to this fireplace must be per formed by a qualified installer service agency or gas sup plier A professional service person should be contacted to inspect this fireplace annually Make it a practice to have all of your gas fireplaces checked annually More frequent cleaning may be required due to excess lint and dust from carpeting bedding material etc Control compartments burners and air passages in this fire place should be kept clean and free of dust and lint Make sure the gas valve and pilot light are turned off before you attempt to clean this fireplace The venting system chimney of this fireplace should be checked at least once a year and if needed your venting System should be cleaned Keep the area around your fireplace clear of combustible materials gasoline and other flammable vapor and liquids This fireplace should not be used as a drying rack for cloth ing nor should Christmas stockings or decorations be hung on or around the fireplace Under no circumstances should any solid fuels wood coal paper or cardboard etc be used in this fireplace 10 The flow of combustion and ventilation air must not be ob structed in any way 10006326 and depth of the fireplace 12 This fireplace requires adequate ventilation and combustion air to operate properly 13 This fireplace must not be connected to a chimney flue serving a separa
48. ly and lift window frame assembly up and away from the fireplace 5 To reinstall the window frame assembly reverse the process Lower Clamps Window Frame Window Assembly Frame lt Assembly Pull Clamp A_ Push Hook Clamp Han Fig 37 Window frame assembly removal Location of Lower Retaining Screws FP1445 Fig 38 Retaining screw 10006326 Glass Cleaning It is necessary to periodically clean glass During start up condensation which is normal forms on the inside of the glass This condensation causes lint dust and other airborne particles to cling to glass surface Also initial paint curing may deposit a slight film on the glass It is therefore recommended glass be cleaned two or three times with a based house hold cleaner and warm water The use of fireplace glass cleaner is recommended within the first few weeks of operation After the initial cleaning process the glass should be cleaned two or three times during each operating sea son depending on the environment in the house Do not strike or slam the glass Ceramic Refractory Installation The vertical refractory panels are installed in the unit prior to shipment For assembly procedures refer to Figure 39 1 Unpack the ceramic refractory panels from the car ton Handle the refractory material carefully the panels are fragile 2 Place the two end floor
49. minus two times finishing material thickness to be even with face of unit L ROD 38 981 mm Not to be framed until unit is set in place due to 3 79 mm allowance for flue collar ROW Not to be framed until unit is set in place 43 1111 mm due to 3 79 mm allowance for flue collar 10006326 360 DVS Series Direct Vent Fireplaces Framing Dimensions 360DVS3 360DVSL 360DVSR Rear Vent Confiration 360DVSL 360DVS 3 L R 360DVS3 360DVSR 123 Top Vent Configuration YY 360DVS3 360DVSR CFM124 aming Dimension Rear Vent Configuration Top Vent Configuration 360DVS3 360DVSL R 360DVS3 360DVSL R See Note 1 See Note 2 See Note 1 See Note 2 38 981 mm Not to be framed until unit is set in place due to 3 79 mm allowance for flue collar 40 1032 mm minus one time 1x finishing material thickness to be even with face of unit NOTE 1 24 610 mm minus two times 2x finishing material thickness to be even with face of unit NOTE 2 24 629 mm minus one time 1x finishing material thickness to be even with face of unit 8 10006326 Locating Your Fireplace LU584 2 Fig 3 Locating your gas fireplace A Wall Location Fig 3 Y Minimum distance between a glass panel and a parallel
50. mperative that the pilot burner s flame characteristics are steady not lifting or floating Typically the top 3 8 1 2 10 13 mm of the thermo pile should be engulfed in the pilot flame Page 26 Fig 46 To adjust pilot burner to be done by a qualified service technician 1 Remove pilot adjustment cap 2 Adjust pilot screw to provide properly sized flame 3 Replace pilot adjustment cap The primary air shutter is set at factory and should be adjusted if necessary only by a qualified service tech nician Cleaning Electronic Ignition System The Electronic Ignition burner control system consists of main burner gas orifice pilot burner 24VAC valve with transformer The process for taking care of Electronic Ignition units is identical to that for taking care of Standing Pilot models 35 360 DVS Series Direct Vent Fireplaces CFM Corporation reserves the right to make changes in design materials specifications prices and discontinue colors and products at any time without notice 360DVS Series Units H63H00 H63100 H63A00 GFSM2L0 H63B00 93 00 H93A00 H93B00 H83A00 H83B00 H73A00 H73B00 36 10006326 360DVS Series Direct Vent Fireplaces 360 DVS Series Items marked are not shown the parts illustration Ref Description 360DVS2 360DVS3 360DVSL 360DVSR 1 Log Set
51. n product DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF 43 Canada ENER QUIDE Look for the EnerGuide Gas Fireplace Energy Efficiency Rating in this brochure Based on CSA 4 1 02 Efficiency Ratings Fireplace Efficiency Fan OFF Fan ON AFUE 360DVS2RN 360DVS2RP 360DVS2EN 360DVS2EP 360DVS3RN 360DVS3RP 360DVS3EN 360DVS3EP 360DVSLRN 306DVSLRP 360DVSLEN 360DVSLEP 360DVSRRN 360DVSRRP 360DVSREN 360DVSREP NATIONAL We recommend that our gas INSTITUTE hearth products be installed and serviced by profes sionals who are certified in the U S by the National Fireplace Institute NFI as CERTIFIED Gas Specialists www nficertified org CFM Corporation 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com
52. n the hood 10006326 360DVS Series Direct Vent Fireplaces PSE Pilot Using a suitable wrench on hexagonal body un screw the pilot hood assembly from the pilot Do not twist the hood itself Remove the orifice and replace it with the new orifice supplied in the kit Refit the pi lot hood assembly Do not overtighten the pilot hood The hood must return to its original alignment Take care not to damage the thermocouple thermopile or igniter 9 SIT 820 NOVA Gas Control Valve Fig 48 a Using a Torx T20 or slotted screwdriver remove and save three 3 pressure regulator mounting screws A pressure regulator tower B and dia phragm C b Ensure the rubber gasket D is properly posi tioned and install the new HI LO pressure regulator to the valve using the new screws E supplied with the kit Tighten the screws securely Reference torque 25 in Ib C Install the enclosed identification label F to the valve body where it can be easily seen Fig 48 Remove mounting screws pressure regulator tower and diaphragm assembly 33 360 DVS Series Direct Vent Fireplaces Regulator Cap Conversion Screw Pressure Regu lator Housing Fig 50 Honeywell conversion screw replacement Fig 49 Replace regulator 10 Reassemble fireplace in the reverse order except Honeywell Gas Control Valve Fig 50 for the window frame assembly Leave this off until The Honeywell val
53. nection sarisari sirviani edadia 11 Remote ON OFF Switch Installation 11 Alternate SwitGhLOGAathOn si cerei ee eri recur a ees ee 11 Optional Top Vent Application 12 Electronic Gas Control VAIN Gaz 25 Pee xe extet iex eb rene re iere tee 13 Venting Installation Instructions General Vening LII IL IEEE 13 General Venting Information Termination Location 14 Termination ClArANCS iss code Gated ne RA AUR DeC a Ra PEDE RE 15 General Information for Assembling Vent Pipes 15 TWISt LOCK PIPE e c ch advances 15 How Use the Vent Graph 16 Rear Wall Application amp Installation 2 16 Vertical Side Wall Application amp Installation 17 Below Grade Installation sssssssssssssssssseseessesee nennen nennen then nnns nnns nnne 20 Vertical Through the Roof Application amp Installation sssssssssm 21 Twist Lock Venting COMPONENTS Leti teneros 23 Operating Instructions Glass Information tee d t
54. or nails Holes to secure the unit to the floor are located behind the access door grille on the left and right sides of the unit Frame in the fireplace with a header across the top It is important to allow for the finished wall face when setting the depth of the frame Drywall sheetrock or wood material may be placed with a zero clearance to the top edges of the appli ance when finishing walls above sides of the appli ance with glass windows NOTE Attach wall finish ing to constructed frame not the appliance On 360DVSL and 360DVSR drywall wood or wood molding may be placed with zero clearance to the rear wall of the unit along the vertical edge formed by the standoffs to intersection of the rear wall to the side wall having the small glass window NOTE Attach wall finishing to constructed frame not the appliance Noncombustible materials such as brick or tile may be extended over the edges of the face of the appliance DO NOT cover any vent or grille panels A If a Trim Kit is going to be installed on the fireplace the brick or tile will have to be installed flush with the edges of the appliance Gas Inlet amp Manifold Pressures LP Propane Inlet Minimum Inlet Maximum 10 Gas Specifications Max Min Input Input Gas Control BTU h BTU h Nat 26 600 360DVS2RP 28 500 360DVS2EN 26 600 360DVS2EP 28 500 360DVS2RN 360DVS3RN 26 600 360DVS3RP 28 5
55. orizontal run to the face of outer wall must not exceed 8 2 6 lt O4 8 2 o T3 z 7 25 3 0 N H3 za 48 Q o 9 2 Lt my 95 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DV Graph Horizontal dimension from outside of the wall to the center of the fireplace vent flange Sidewall vent graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system Fig 16 Sidewall vent graph 16 Rear Wall Application When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance Specific rear vent starter kits must be used in these applications see venting components The appli ance has been approved for installation flat against a rear wall Fig 17 Maximum horizontal distance between the rear of the appliance and the outside face of the rear wall is 20 508 mm Fig 17 Minimum clearances between any combustible ma terial and the vent pipe sections are JOD 2 51 IDES sciiicet 1 25 BOOM an 1 25 20 508 1434 Fig 17 Rear vent application Rear Wall Installation Step 1 Locate and cut vent opening in the rear wall Combustible walls Cut a rectangular hole measuring
56. ound i 24 610mm Minimum A minimum of 24 610mm vertical pipe must be installed when using the 7TDVSNORK Kit The 22 559mm vertical rise center to center of the snorkel may be included for calculation of maximum horizontal run Fig 28 Below grade installation Do not backfill around the snorkel A clear ance of at least 4 102mm must be main tained between the snorkel and the soil If the foundation is recessed use recess brackets not supplied for securing lower portion of the snorkel Fas ten brackets to wall first then secure to snorkel with self drilling 8 x 1 2 sheetmetal screws It will be necessary to extend vent pipes out as far as protruding wall face Fig 29 Snorkel Foundation Wall 4 Wall Screws Watertight Seal Sheet Metal Screws Around Pipe CFM139 Fig 29 Snorkel installation recessed foundation 10006326 360DVS Series Direct Vent Fireplaces Vertical Through the Roof Application This Gas Fireplace has been approved for 1 2 3 4 270 Vertical installations up to 40 12 m in height Up to a 10 3 m horizontal vent run can be installed within the vent system using a maximum of two 90 elbows Fig 30 Max Height 40 12 2m Min Height 8 2 4m FP1444 Fig 31 Maximum elbow usage Min 2 610 mm Max 10 3m Max Height 40 12 2m Min Height 8 2 4m
57. ps Dn C ax 1 3 914 mm 2x D 6 1 8 m 1 x D cus 9 2 7 m 2 3x D 2 3 7 m 1 2xD Actual Actual Actual of Termination caps x 3 2 termination caps x D Dy NOTE Termination in alcove space spaces open only side and with an overhang is permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be a 3 914 mm minimum between termination caps 2 All mechanical air intakes within 10 1 m of a termination cap must be a minimum of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be a minimum of 1 305 mm below the termination cap Fig 14 Termination clearances General Information Assembling Vent Pipes Canadian Installations Venting system must be installed in accordance with the current CSA B149 1 installation code USA Installations The venting system must conform with local codes and or current National Fuel Gas Code ANSI Z223 1 NFPA 54 Only venting components manufactured by CFM Corpo ration can be used in Direct Vent systems Twist Lock Pipes When using twist lock pipe it is not necessary to use sealant on the joints The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of telescopic vent sections used in the system 10006326 To join the twist lock pipes to
58. r ends of the wire to the gas control valve as shown in Figure 7 99 Remote ON OFF Switch Control TH Valve TP TH Fig 7 Remote switch wiring diagram for R models Alternate Switch Location The remote switch can be installed on the front or the side of the access door Simply mount the switch to the bracket provided and screw the bracket to either side of the frame lining up the screws with the prepunched holes Fig 8 11 360 DVS Series Direct Vent Fireplaces Remove These Screws R P AEN KEN These Screws S SAI FP1430 Fig 8 Alternate switch location Optional Top Vent Application This appliance is shipped as a rear vent unit If the installation layout requires the unit to be a top vent con figuration the appliance can be converted by following the steps below Insulation Pad When removing and refitting the plates and Outer Collar Adapter Fig 9 Remove screws from outer collar adapter adapter be sure the associated gasket is undamaged and refitted as required 1 Remove the ten 10 screws securing the outer col lar adapter to the fireplace body Fig 9 2 Set the collar aside complete with the gasket NOTE Do not damage the gasket as the adapter and gasket must be refitted 3 Remove the insulation material exposed in Step 2 from the top of the unit Fig 10 This material can b
59. refractory panels on the base of the fireplace 3 Place both side panels along the side of the base NOTE 360DVS2 is the only 360DV unit that is fitted with two 2 end vertical panels as shown in Figure 39 360DVSL and 360DVSR units are each fitted with one end vertical panel and two side vertical panel The 360DVS3 has only one end vertical panel Clean the glass after the first two weeks of operation Do not clean the glass when hot Do not use an abrasive cleaner Vertical Panels in Place When Shipped Floor Panels Placed During Installation Fig 39 Ceramic panel installation 10006326 360DVS Series Direct Vent Fireplaces Installation Refer to Figures 40 and 41 for log location align ment Because of the log stack design these instructions can be followed from either side of the fireplace To follow these instructions identify the logs by the number cast into the underside For correct operation of the fireplace the logs must be correctly placed in the sequence described below 1 Unpack the logs from the shipping carton The logs are fragile handle them carefully Handle and dispose of plastic bags in A which logs were shipped in a safe manner As with all plastics they are not toys and should be kept away from infants 2 Remove both sides of the window frame assembly where applicable 3 Place the log rear B120 on the grate The square hole located on the underside
60. ries Direct Vent Fireplaces 1 lt Thank you and Congratulations on your purchase of a CFM Corporation Fireplace PLEASE READ THE INSTALLATION amp OPERATING INSTRUCTIONS BEFORE USING APPLIANCE IMPORTANT Read all instructions and warnings carefully before starting installation Failure to follow these instructions fully may result in a possible fire hazard and will void the warranty Installation and Operating Instructions 3 Important Curing Burning Instructions 3 5 Framing DIMENSIONS s cuoco peine 7 Locating Your erede ra Poe da Rhe EET ER EE 9 Clearance to Combustibles eon itte ente e aaraa so d 9 MERIT EE 9 ar EccL E 10 Eraimirige 2 eh reete tis uL met CDM eed 10 EE 10 Ier Seren M 10 Gas Inlet and Manifold Pressures 10 Gas Line IMStallatam cs svat s3eee ASEA 11 EB 1 Electrical Junction Box Con
61. rness remote switch 55923 55923 55923 55923 Remote ON OFF Switch Kit incls bracket 53875 53875 53875 53875 20 Louvre Assembly side top 10000039 10000039 10000039 10000039 10006326 37 360 DVS Series Direct Vent Fireplaces 360DVS Series continued Items marked are not shown in the parts illustration Ref Description 360DVS2 360DVS3 360DVSL 360DVSR 21 Louvre Assembly side bottom 10000040 10000040 10000040 10000040 22 Louvre Assembly end top N A 10002411 10002411 10002411 23 Louvre Assembly end bottom N A 10002412 10002412 10002412 24 Hinge lower louvre assemblies 52356 52356 52356 52356 25 Trim Window Top Bottom w Magnets PB 57483 57483 57483 57483 26 Trim Window Top Bottom w Magnets PB n a 10006197 10006197 10006197 Window Frame Assembly side 10002483 10002483 10002483 10002483 Window Frame Assembly end N A 10002484 10002484 10002484 Window Glass complete with gasket side 10002533 10002533 10002533 10002533 Window Glass complete with gasket end N A 10002534 10002534 10002534 Gasket Kit glass replacement 1x11 length 57317 57317 57317 57317 27 Window Frame Clamp 54174 54174 54174 54174 28 Refractory Lining vertical end walls 10006254 10006254 10006254 10006254 29 Refractory Lining vertical side wall N A N A 10006285 10006285 30 CR Bottom Kit w out Rear 10006257 10006257 10006257 10006257 Air Inlet Cover Plate Assembly 10006174 10006174 10006174 10006174 A Air Inlet Cover Plate Gasket 10006171
62. s are faulty or connections are bad Be sure wire connections from thermopile at gas valve terminals are tight and thermopile is fully inserted into pilot bracket One of the wall switch wires may be grounded Remove wall switch wires from valve terminals if pilot now stays lit trace wall switch wiring for ground May be grounded to fireplace or gas supply Check thermopile with millivolt meter Take reading at thermopile terminals of gas valve should read 250 300 millivolts minimum 150 while holding valve knob depressed in pilot position and wall switch OFF Replace faulty thermopile if reading is below specified minimum Check burner orifices for debris and remove Turn valve knob to ON place wall switch to ON millivolt meter should read greater than 100 mV If the reading is okay and the burner does not come on replace the gas valve Clean and or adjust pilot flame for maximum flame impingement on thermopile and thermocouple Check the vent terminal for blockage recycling the flue gases 10006326 360DVS Series Direct Vent Fireplaces Troubleshooting the Gas Control System SIT 822 Valve with a Honeywell Electronic Igniter START NOTE Remove glass before servicing v TURN GAS SUPPLY OFF NO CHECK LINE VOLTAGE 120VAC e TURN ON OFF SWITCH e LOW VOLTAGE TRANSFORMER 19 5 MINIMUM VAC TO CALL FOR HEAT e ON OFF SWITCH POWER TO MODULE e WIRING CONNECTIONS 24V NORMAL
63. s installation depth down to 7 178 mm below grade level Measure 7 178 mm from the center of the horizontal vent pipe as it penetrates through the wall NOTE Ensure sidewall venting clearances are ob served If venting system is installed below ground we recommend a window well with adequate and proper drainage If installing a snorkel a minimum 24 610 mm vertical rise is necessary The maximum horizontal run with 24 610 mm vertical pipe is 36 914mm The measurement is taken from the collar of the fireplace or transition elbow to the face of exterior wall See sidewall vent graph Page 15 for extended horizontal runs if the vertical exceeds 24 610 mm 1 Establish vent hole through the wall Fig 24 2 Remove soil to depth of about 16 406 mm below base of snorkel Install window well not supplied Refill hole with 12 305 mm of coarse gravel leav ing a clearance of about 4 102 mm below snorkel Fig 28 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking supplied around 4 in and 7 in snorkel collars 6 Slide snorkel into vent pipes and secure to wall 7 Level the soil so as to maintain a 4 102 mm clear ance below snorkel Fig 29 20 Zero Clearance Sleeve if required S E 7TDVSNORK H lt Snorkel Firestop WEAN RSS Min 4 102mm Clearance Gr
64. sionals for the installation of hard wired carbon monoxide detectors In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adjacent floor level In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon mono
65. tant to prevent dis coloration 10006326 360DVS Series Direct Vent Fireplaces Fireplace Louvre Assembly of Combustion Chamber y Y TF Bottom of Door Trim E CFM146 Mantel Chart Mantel Shelf Mantel from Top or Breast Plate of Comb Chamber A 10 254 mm A 19 483 mm W 8 203 mm 17 432 mm X 13 330 mm 11 297 mm Fig 4a Combustible mantel minimum installation 6 152 mm 15 381 mm 4 D 1 Top View Mantel Leg Front View Side of Combustion Chamber Mantel Leg CFM170 Mantel Mantel Leg From Side negem of Comb opening 1172 292 mm 6 152mm M 7ve f91mm 4 002mm N 5 140mm LJ 2 51mm O 3 89mm Fig 4b Combustible mantel leg minimum installation 360 DVS Series Direct Vent Fireplaces A hearth is not mandatory however for aesthetic purposes we recommend installing a noncombustible hearth that projects out 12 305mm or more from the front of the fireplace Cold climate installation recommendation When installing this unit against a noninsu A lated exterior wall or chase it is mandatory the outer walls be insulated to conform to applicable insulation codes Framing amp Finishing Choose the unit location 2 Place the unit into position and secure it to the floor with 112 38mm screws
66. te solid fuel burning fireplace 14 When the fireplace is not in use it is recommended the gas valve be left in the OFF position WARNING Check with your electronics manufacturer before installing a television or other electronic de vice above this fireplace 360DVS2 360DVS3 360DVSL 360DVSR CERTIFIED TO ANSI Z21 88 2005 CSA 2 33 2005 Vented Gas Fireplace Heaters This appliance may be installed in an aftermarket per manently located manufactured home or mobile home where not prohibited by local codes This appliance is only for use with type of gas indicated on the rating plate This appliance is not con vertible for use with other gases unless a certified kit is used IMPORTANT PLEASE REVIEW THE FOLLOWING CAREFULLY Remove any plastic from trim parts before turning the fireplace ON It is normal for fireplaces fabricated of steel to give off some expansion and or contraction noises during the start up or cool down cycle Similar noises are found with your furnace heat exchanger or car engine It is not unusual for your gas fireplace to give off some odor the first time it is burned This is due to the curing of the paint and any undetected oil from the manufacturing process Please ensure that your room is well ventilated open all windows Itis recommended that you burn your fireplace for atleast ten 10 hours the first time you use it If the optional fan kit has been installed place the fan switch in
67. th three 3 sheetmetal screws It is not neces sary to seal this connection It is critical there be no downward slope away from the appliance when connecting the vent or elbow 10006326 360DVS Series Direct Vent Fireplaces STEP 5 Guide vent through the vent hole as you place the appli ance in its installed position Guide the 4 102 mm and 7 178 mm collars of the vent termina tion into the outer ends of the venting Do not force the termination If the vent pipes do not align with the termination remove and realign the vent ing at the appliance flue collars Attach the termination to the wall as outlined in the instruction sheet supplied with the termination Vertical Sidewall Application It is very important the venting system maintain its bal ance between the combustion air intake and the flue gas exhaust certain limitations concerning vent con figurations must be strictly adhered to The vent graph Fig 16 showing relationship be tween vertical and horizontal side wall venting will help determine allowable dimensions Minimum clearance between vent pipes and com bustible materials is 1 25 mm on top bottom and sides unless otherwise noted When the vent termination exits through foundations less than 20 508 mm below siding outcrop the vent pipe must flush up with the siding e Itis best to locate the fireplace in such way that minimizes the number of offsets and
68. the OFF position during this time Proposition 65 Warning Fuels used in gas wood burning or oil fired appliances and the products of combustion of such fuels contain chemicals known to the State of California to cause cancer birth defects and other reproductive harm California Health amp Safety Code Sec 25249 6 360 DVS Series Direct Vent Fireplaces Requirements for the Commonwealth of Massachusetts All gas fitting and installation of this heater shall only be done by a licensed gas fitter or licensed plumber For all side wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied Installation of Carbon Monoxide Detectors At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling building or structure served by the side wall horizontal vented gas fueled equipment It shall be the responsibility of the property owner to secure the services of qualified licensed profes
69. tly located wall socket by using a hard wired receptacle box FK24 Fan Electrical Inlet Hole Fan Speed Control Box Gas Inlet Hole Heat Sensor Electrical Box EB 1 FP 1448 Fig 51 Fan installation 39 360 DVS Series Direct Vent Fireplaces Wiring Instructions The fireplace when installed must be elec A trically connected and grounded in accor dance with local codes or in the absence of local codes with the current CSA C22 1 Canadian Electric Code For USA installa tions follow local codes and the National Electrical Code ANSI NFPA 70 Any electrical rewiring of this fan must be done by a licensed electrician Should this fan require servicing or repair A the power supply must be disconnected For rewiring of any replacement parts refer to Figure 51 Method A Not using EB 1 Fig 52 1 Connect the ground wire to the power supply line to ground stud located on the base of the firebox 2 Connect the black wire of the supply line to either terminal of the speed control unit 3 The second terminal of the speed control unit is attached to either terminal of the thermal sensor 4 The second terminal of the thermal sensor is con nected to either terminal of the fan motor 5 The second fan motor terminal is connected to the white wire of the supply line A Speed Control B Temperature Sensor C Fan A Black White Ground Fig 52 Method wiring diagr
70. to the floor because some gas is heavier than the air and will settle on the floor What to do if you smell gas Do not try to light any appliance Do not operate any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions e If you cannot contact your gas supplier call the Fire Department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand do not try to repair it call a qualified service technician Force or attempting repair may result in a fire or explosion Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and any gas control that has been under water Lighting Instructions STOP Read the safety information above before continuing Turn off all electrical power to the appliance This appliance is equipped with an ignition device which automatically lights the pilot DO NOT try to light the pilot by hand Access the gas control by lowering the lower access door louvre assembly Turn the remote switch to the OFF position Turn OFF all electrical power to the fireplace if service is required Open the lower access panel Turn the shutoff valve on the flexible gas line to the OFF
71. ve fitted to this unit is suitable for use after unit has been checked for leaks and the gas with LP or Natural Gas It is converted to the required supply has been bled gas application by installing a color coded conversion 11 After bleeding the gas line and checking for leaks screw with a soap solution replace the window frame as a Using a suitable small screwdriver lift out the cen sembly tral regulator cap from the HI LO knob on the valve 12 Fire up the unit Check for flame impingement on b Unscrew the exposed conversion screw the logs adjusting as necessdiy C Insert the new color coded conversion screw Do TARER and supply pressures against the not overtighten the screw it must be finger tight appliance specifications d Refit the regulator cap procedure for converting from one gas Mount ion label lied with th to another is the same regardless of the 8 AUNE or eps initial gas used only variations sion screw to the valve in a visible position in orifice sizes and component part num bers Your authorized service provider will ensure correct parts are used 34 10006326 360DVS Series Direct Vent Fireplaces Maintenance Burner and Burner Compartment It is important to keep the burner and the burner com partment clean At least once per year remove the logs and lava rock ember material Vacuum and wipe out the
72. xide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a 1 through 4 Exemptions The following equipment is exempt from 248 CMR 5 08 2 a 1 through 4 The equipment listed in Chapter 10 entitled Equipment Not Required Be Vented in the most current edition of NFPA 54 as adopted by the Board and Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling building or structure used in whole or in part for residential purposes MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instructions provided by the manufacturer for installation of the equipment and the venting system shall include Detailed instructions for the installation of the venting System design or the venting system components and Acomplete parts list for the venting system design or venting system Gas Equipment Venting System NOT Provided When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirements shall be satisfied by the manufacturer The referenced special venting system instructions shall

Download Pdf Manuals

image

Related Search

Related Contents

Fisher-Price 75547 Motorized Toy Car User Manual  FT_Pieri Epolith SBR e1 - técnicas de hormigón y morteros  B E D I E N U N G S A N L E I T U N G M A N U A L  Mode d`emploi pour accéder aux photos de vos enfants.  LEDD-09112WK  China  telecharger la notice d`emploi  intext:Betriebsanleitung filetype:pdf    SD 320 Con  

Copyright © All rights reserved.
Failed to retrieve file