Home

Harman Stove Company PF 100 Furnace User Manual

image

Contents

1. dm on left See page 14 Fig 24 and 26 for larger images See NOTES EZ LAE j 56250 may The sections of pipe lock together to form an air ZZ Z DIN a 222222 221 tight seal in most cases however in some cases a pag 227 2 A fect seal is not achieved For this reason and the fact Yh Zo SG q S lt DE that the PF100 operates with a positive vent pressure 9 we specify that all joints within the structure should x also be sealed with clear silicone i NOTE Use only 4 diameter type L or PL t venting system Be sure to inspect and clean exhaust venting system frequently 4 PF100 Assembly Filter Box Cold Air Return Solid Side Panel Blower access Panel Blower access Panel Cover Ban NOTE Read and follow all of the vent pipe manufacturers instructions on the proper installation and support of the vent pipe Adhere to all clearances bw ta Solid Side Panel SS 4 This Edg Toward DON p Furnace 4 Tek screw from outside Fig 4 Top same as bottom gt Filter Frame Panel Bottom same as top Fig 3 Assembling Filter Box Th
2. Low Fuel Light Fig 43 Lul NORMAL SETTING 17 1 Fig 44 29 7 Low Fuel Sensor Fig 45 Wall Control The wall control acts like a thermostat however what is actually going on is a thermister in the wall con trol is sending temperature information back to the mi cro processor on the furnace This information is used to increase or decrease the size ofthe fire according to the needs ofthe home Setting The Room Temperature To set the room temperature simply turn the tem perature dialto the desired setting The control and the furnace will then perform to achieve the set tempera ture Note The minimum temperature you can set with a full counter clockwise knob position is 58 degrees The maximumtemperature you can set with a full clock wise knob position is 90 degrees Wall Control calibration The Normal Setting on the Temp Dial ofthe Furnace Control See Fig 44 cali brates the Wall Control temperature span Ifthe Temp Dial is not pointing to the Normal Setting the tem perature span could vary by 3 degrees up or down de pending on the Temp Dial knob setting Low Fuel Sensor There is a low fuel sensor in the hopper that tells the control that the fuel level in the hopper has dropped below the sensor When this happens the Low Fuel light on the Wall Control will start to blink You then know that it is time to fill the hopper with pellets Note
3. L ou PL Le Harman PF100 peut tre connect une fournaise ou un syst me de pompe de chauffage d j existants Model Fuel Chimney Connector Size BTUH Kw Input Pellet Electrical Rating Maximum Overcurrent Protection Modele Combustible Grandeur du Tuyau de Chemin e Rendement des Boulettes BTUH Kw Classitication lectrique Protection Maximum du Courant Pellet 100 112 625 BTUH 33 Kw 120V 9 3A 60 Hz Clearances to Combustibles Espaces Libres aux Combustibles combusts 1o Fier Box on Appronee Des combustibles bla boite devitation de combustibies 19 Connector Pipe 2st mmy Des combustibles au tuyau connecteur combustibles o Appance 12 20smmy Des combustibles Supply air Plenom to Galing Provision air pl numauplafond Ss Supiy Air Plenum to Combuatibie Chase Provision plenum au chassis du combusubi At 16 of pipe length distance from fiue collar while maintaining listed clearances from appliance body Un tuyau de grandeur de distance de 16 de l ouverture du ventitateur doit tre en accord avec l espace libre mentionn d l appareil m me A Harman PF 100 may be connected to an existing furnace or heat pump duct system Essential parts and subassemblies provided for field assembly are as foliows Pi ces essentielles et sous assembl es procur es pour l assemblage sont les suivantes Thermostat Thermostat
4. dINV I S 054 WAI 0007 8 dV t 054 0061 S 9 ejod peus WAO 0001 z EO L euondo xne p lt 0 onuoo mE ET juouio o 1OPUSI Inoy Jad spunod 10 0W Jasne Jod punod wing dINV FI uonsnquioo Udy 9 sruiojs s 0 09 OVA 07I UPATA 000 II 03 0058 0 SULY 3ndu NLA 36 PF100 91780 06 E YIMOTE NOLLSNAWDI CX 931 SOLOW 0303 IA lt gt 83 11812 1510 IDANINA 3GISNI gt LNAWS 13 2311ND51 NOILOISNNOD 3 VvW34 3vW 39IA AOLOW MOLOW 330334 x INANI OVA 021 L37DIA oe NOLLIINND 319W33 3 WW N aa sms a 3018 A3IA WDIIDS LINGNOD X314 8 SLOVINO9 je LINGNOD X314 8 4 00 6 Taw A07 30718 C3W 0v48 1IH HOLIAS JessJeg ADT p i HILIMS 3AU18 013345 Et r LAdLAD 5 ANAH YAMOd LOSNNOO G NDIL3 3NNDO 3VN34 31vN
5. Wiring Diagram Owners Manual Hopper Lid Label Chain Shaker Gasket Low Fuel Sensor Combustion Blower Inner Ash Door Gasket Circuit Breaker Harness 10 Amp Circuit Breaker 4 Pole Thermostat Extension 3 Speed Switch 20 X 20 X 1 Air filter 3 Position Terminal Block Junction Box Harness Fan Limit 2 Pair Twisted Cat 3 Cable 100 Options 5 Double Fan Blade high altitude 1500 CFM Blower 2000 CFM Blower Outside Air Assembly 12 1 2 Flex Pipe 2 3 4 ID 25 Flex Pipe 2 3 4 ID 0 88 00248 1 10 06620 1 10 73403 2 00 73418 2 00 733 14 2 00 773850 3 00 08534 3 44 35263 3 20 00744 3 20 08101 3 20 03100 3 20 9301 3 20 40985 3 20 36648 1 10 01007 3 31 00534 3 31 00968 3 31 00982 3 40 86125 1 10 5555 1 10 73351 3 44 00409 3 90 73370 3 90 08101 3 90 08415 3 44 08100 4 20 03835 3 21 08639 2 00 00539 3 20 04947 3 20 334110 3 20 04946 3 20 70020 3 40 20201 3 20 03018 3 20 04948 3 20 23139 3 20 02583 3 20 502221 1 00 00682 3 21 52092 1 10 09542 2 00 08544 2 00 08545 HARMAN CENTRAL HEAT WARRANTY HARMAN 5 YEAR LIMITED WARRANTY Residential 5 YEAR LIMITED 1 YEAR LIMITED WARRANTY Commercial WARRANTY Harman Stove Company warrants its central heat products to be free from defects in material or workmanship in normal use and service for a period of 5 years from the date of sales invoice and for mechanical and electrical failures in normal use and service for a pe
6. To install power to the furnace first remove the cover on the circuit breaker junction box shown Inside you will find the main terminal block See wir ing diagram on page 36 for location of main terminal block and proper power connections In the bottom ofthe box a knockout hole is provided for the incoming wire The minimum recommended circuit is 15 Amp 120 V A C 60 Hz This furnace should be the only appliance on the circuit This furnace should never be powered by the use of an extension cord The recommended high and low voltages are 130 V A C 60 Hz maximum high voltage and 113 V A C 60 Hz minimum low voltage The furnace will continue to operate at voltages as low 105 V A C although it can not be guaranteed that automatic ignition will occur Also there is the possibility of a distribution blower motor overload NOTE If other sources of electrical power are to be used such as a generator for normal opera tion or emergency operation this source should be checked before installation Many generators and inverters may not supply 120V A C 60Hz power stable enough to operate the control board properly Control board damage could occur Checking amp Re cording the Low Draft After the venting is completed the firebox low draft will need to be checked and possibly adjusted After re moving the 3 8 bolt from the draft hole shown in Fig 38 insert the draft meter tube The inner ash door and the hoppe
7. whether x a5 LI 60 Hz or not it is interconnected Sa HITE WHITE E z re a 3 AUTOMATIC z3 PEER VIOLET V ae ED ize 2 THE ORIGINAL SKY BLUE SKY BLUE YELLOW 0 SPLICE WILL NEED TO BE SPLIT b Cya TO MAKE THESE NEW CONNECTIONS M ROUND mi DO NOT DISCONNECT os CD THIS SPLICE Eh d a T D WHITE SPARE IS PROVIDED ah mi uj m hh FOR TRANSFORMER HOOK UP Fr TO FAN MOTOR Fig 34 N 18 PF100 Throw Installation High Limit Setpoint CONTROL i WWI gt if Locknuts outside and inside Fig 36 NOTE KEEP THE FAN LIMIT CONTROL INSTRUCTIONS WITH THE OWNERS MANUAL FOR FUTURE REFERENCE NOTE If fans are used in the fuel storage area they should be installed so as not to create negative pressures in the room where the solid fuel burning appliance is located FAN HIGH LIMIT CONTROL Installation amp Set up 1 The Fan Control must be placed in the discharge plenum approximately 11 inches above the discharge open ing of the furnace as close to center as possible Note The best place is on the same side as the ash door because of ease of access See Fig 35 Note Care must be taken when installing the Fan Control when an air conditioning A Coil is used The Fan Control must always be installed below the A Coil in low plenum installations 2 Install the flex and wiring 3 Make sure that the
8. 8 ceiling height The PF100 furnace can be fitted with an air condi tioning coil mounted in the supply air plenum The Harman Stove Co is not responsable for sizing duct placement or interconnections However we have made adding A C to the furnace easier with the information listed below There is a factory installed junction box ready to accept your A C relay The A C fan control center with 40 va transformer must have a DPDT relay STEVECO 90 112 Harman part 3 20 38056 Other brands are available at local supply houses The wiring should be done as per Fig 34 Thelow voltage wiring to the outside condensing unit and the cooling thermostat are not shown see condensing unit diagrams for that information This style relay is used to lock out the feeder sys tem ofthe furnace when the A C unit is calling for cool ing This is a fail safe against both units operating at the same time See the NOTE in the lower left corner THE SIZE OF THESE WIRENUTS WILL NEED TO BE CHANGED TO ACCEPT THE ADDED WIRES FROM THE CIRCUIT Doe Gol ARR an On tro ela NOTE BREAKER J BUX x It is highly recomended that the wg furnace control be turned to the SPLICE via Ha Ew ae m OFF position whenever air bl VIOLET VIOLET E ae E BLACK conditioning is being used
9. Testing the low fuel sensor can be done by turning the FEED ADJUSTER knob to Test The POWER light will go off when the sensor is uncovered and will light when the sensor is covered again Note The LOW FUEL light on the Furnace Con trol will light at the same time Only the LOW FUEL light on the Furnace Control will remain lit for three min utes after the sensor is covered with pellets See Note below Note The Low Fuel light indicates that there is power going to the auxiliary leads in the circuit breaker junction box 120 VAC 60 Hz Max 1 Amp The auxiliary power leads would be used if an optional bulk hopper and auger system were installed see wiring diagram on page 36 Type of Fuel Pelletized wood only Note The lower the ash content ofthe pellets the less cleaning that will be needed ofthe heat exchanger surfaces The cleaner these surfaces are kept the more efficient the furnace will be PF100 23 Starting Fire Automatically 1 Turn Mode Selector to OFF This resets the control in addition to turning it off Fig 46 2 Fill hopper with pellets When filling the hopper check for excessive fines in the bottom ofthe hopper Fines are small pieces of broken pellets sawdust Fines do not flow easily and often build up on the hopper funnel bottom angles These fines can be pushed into the feeder opening and then fill the hopper with pellets As the system works they will be bur
10. can be gained through the blower access panel cover and the filter opening See Fig 14 Note Two pieces of 2x4 stacked laying flat on Fig 14 the floor 12 inches from the blower opening will support the filter box during installation 8 PF100 Assembly Firebrick Firebrick installation required The firebrick is shipped in the ashpan It will need to be placed on the brick shelf as shown in Fig 15 It can be installed with either face to the fire Hold the brick longways and slide it down into the slot on the shelf There is a stop at the rear ofthe shelfto stop the rearward travel The brick just sits on the shelf in the upright position Baffle installation The upper heat exchanger baffle comes shipped along side the ashpan Remove the ashpan and the baffle This upper baffle needs to be installed before operating the furnace The baffle has a long 45 degree bend on the bot tom of the firebox side See Fig 17 The top has a 90 degree bend on the same side to 1 use as a handle On the opposite side there are four hooks that will LA support the baffle Baffle support bracket Fig 16 On the front and rear ofthe firebox walls there are brackets that these hooks fit into See Fig 16 Slide the upper baff
11. increases as the duct decreases in size with the same CFM blower The sound of air flowing through the duct increases as the velocity increases Therefore the largest size duct practial should be used The velocity to sound level must be taken into con sideration when connecting this furnace into an existing duct sustem As a primary source furnace the duct system can be installed to fit the customers needs These are recommended Supply Air duct sizes in square inches for the different CFM blowers that may be used with this furnace Velocity 500fpm 700fpm 900fpm Static LW C 3 min to 6 max 1000CFM 270sq in 21059 10 160sq in 1500CFM 360sq in 290sq in 220sq in 2000CFM 470sq in 360sq in 290sq in These duct sizes are only recommendations The Return Air duct system should be sized aprox 10 percent larger for heating only systems and 20 per cent larger ifairconditioning is installed CAUTION Regardless of the supply air duct size installed the Distribution Blower Motor MUST be checked for running Amperage Check the motor name plate for the full load AMPS Ifthe amperage is running higher than that listed a supply air restricting damper may be required to increase the supply plenum positive static pressure Adding Air Conditioning to the PF100 furnace An easy rule of thumb for A C CFM blower size is 75 to 1 CFM for each square foot of conditioned space std
12. it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote makes an extremely hot fire The pellet vent pipe should be inspected at least twice monthly during the heating season to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire Guidance on minimizing creosote formation and the need for periodic creosote removal The chimney should be inspected during the heating season to determine if a creosote build up has occurred If a significant layer of creosote has accumulated 3mm or more it should be removed to reduce the risk of a chimney fire 14 PF100 Installation Outside Air Outside air is optional although it may be required by some building codes The benefit of outside air is higher efficiency and reduced venting restrictions mainly noticed in small and very tight houses To install outside air use 2 3 4 I D galvinized steel flex pipe part 2 00 08544 12 6 length or part 2 00 08545 25 length There is a break away hole on the rear panel which must be removed before con necting the flex pipe See Fig 28 The pipe should be Inlet Cover partt Fig 27 run outside and terminate 3 feet or more below or
13. of the vent pipe Adhere to all clearances WARNING Keep combustible materials such as grass leaves etc at least 3 feet away from the point directly under the vent termination between the vent and the ground WARNING DO NOT INSTALL IN SLEEPING ROOM CAUTION KEEP COMBUSTIBLES AWAY FROM FLUE OUTLET 61 S914 pasn s apojg epnih v y ueuw 3294 OZ O 59509425 0 0 X9 j pisino eui Jo iubue LUNLUIXDW au ILON 59509420 epnji v ay so OF JON PINOYS 199834 DSUN 19191 SespoJoe 1994 j Deur 010 0 1994 10391 BY JION 5 0 G G G _ LZZZOS OZ a pelinbey si eppig ud y jo abuoud p P9P99N 2 mg uonsnquior 01 01 E eur ubj Jewo g mu gj 8 91 9 y neo 1994 JO Spubsnou ul 7 GZ 06 yder SunuoA PF100 11 Requirements for Terminating the Venting WARNING Venting terminals must not be recessed into a wall or siding NOTE Only PL vent pipe wall pass throughs and fire stops should be used when venting through com bustible materials NOTE Always take into consideration the effect the prevailing wind direction or other wind cur
14. provides specific legal rights and the consumer may have other rights that vary from state to state PLEASE READ LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DEVICES THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES NOT HARMAN STOVE COMPANY OR THEIR WARRANTY ADMINISTRATOR FURTHERMORE THESE ACCESSORY DEVICES MUST BE INSTALLED AND USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER Remedies The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale or anything done in connection therewith whether in contract in tort under any warranty or otherwise shall not except as herein expressly provided exceed the price of the equipment or part of which such liability is based CLARIFY The above represents the complete warranty which is given in connection with central heat manufactured by Harman Stove Company No other commitments verbal or otherwise shall apply except by a written addendum to this warranty PF100 39 Testing Label Harman PF 100 LISTED PELLET FUEL CENTRAL OR SUPPLEMENTARY FURNACES FOR RESIDENTIAL USE APPAREIL DE CHAUFFAGE CENTRAL OU SUPPLEMENTAIRE ENREGISTRE DE BOULETTES c COMBUSTIBLES POUR USAGE DANS LES RESIDENCES Tested and Listed By Beaverton Oregon USA OMNH Test Laboratories Inc Report Rapport 135 S 02 2 Certified for U S A and Canada Certifi pour les Etats Unis et le Canada Serial No Num ro de S rie Tested June 200
15. 023000 993 WINE 8 8010395 p4 0 Yq 1935 poo uni L 1030 A pue J240 g uonsnquto 42945 9 s ASAL 03 poo sjojd ou p xx 10duanq aY ur 5 AY xx SIGN 1IBUBYIXA JU9U 991 UBILI 0 ALYS AAO 0 10323125 apong aang YINO SAL 1014000 10139196 IPON dur ONLLLAS TVWHON OLLVKOLOV LHOTT TVANYN m O NOILSQHWOO TANA SALVIS EDS 9 e sapag W3A40d 12402 Suruada samod j uuo3std 35VLIOA HDIH DNINAVA
16. 1 foot or more to the side of the vent pipe outlet Never terminate the outside air above the vent pipe outlet The maximum length of this pipe is 25 feet Inlet cover part number 1 10 09542 should be used to keep birds ro Outside Air Pipe Knockout dents etc out of the inlet pipe See Fig 27 NOTE If outside air is installed the inlet cover should not be placed in an area where drifting of snow or ice will build up blocking the intake air supply The Outside Air knockout is located on the face of the Feeder Cover It is pre cut except for several small tabs There is also a filler plate screwed to the inside to cover the top of the hole after the Outside Air Pipe has been installed This will allow for removal of the Feeder Cover without disconnecting the Outside Air Pipe See Fig 28 Only metal Intake Flex should be used for the Outside Air Supply connection Only ascreened or rodent protected Outside Air Intake cover should be used as an outside weather cover The Outside Air Intake Pipe is inside the Feeder Cover and to the right of the feeder motor The 2 3 4 steel flex pipe is made to slide over the outside of the Air Intake Pipe See Fig 29 It should be held into place with some silicone foil tape or a hose clamp not sup plied HRV When installing in a house with a Heat Reclaiming Ventilation System HRV be sure the system is balan
17. 1 to CAN CSA B366 1 M91 UL 391 ASTM E 1509 95 amp ULC C1482 M1990 Install and use only in accordance with the manufacturer s installation operating instructions Refer to authorities having jurisdiction for proper installation Contact local building or fire officials about restrictions and installation inspection in your area If there are no applicable local codes follow 211 and CAN CSA B365 Special precautions are required for passing the Chimney through combustible wall or ceiling Inspect and clean exhaust venting system frequently in accordance with manufacturer s instructions Use a 4 diameter type L PL venting system HARMAN S m E COMPANY Test en Juin 2001 CAN CSA B366 1 M91 UL 391 ASTM 1509 95 a ULC C1482 M1990 Installez et utilisez en accord avec les instructions d installation et d op ration du fabricant R f rez vous des professionnels avec autorit dans l installation Contactez le bureau de la construction ou le bureau des incendies au sujet des restrictions et de l inspection d installation dans votre voisinage S il n y a pas de codes locaux suivez alors ANSI NFPA211 et CAN CSA B365 Prenez des pr cautions sp ciales lorsque vous faites passer une chemin e travers un mur ou un plafond combustible Inspectez ct nettoycz le systeme de ventilation fr quemment en accord avec les instructions du fabricant Utilisez un syst me de ventilation de 4 de diam tre de type
18. 4 MUST be installed between the plenum and the floor regis ter The register size MUST have an area of at least 240 square inches The minimum ceiling height is 6 6 This is set by the clearance to combustibles 28 from the top of the of the furnace See Fig 22 NOTE Install vent at clearances gp nsn specified by the vent manufacturer CAUTION When installing a floor 28 register the temperature of the discharge air MUST be taken into 65 5 consideration The discharge temperature may be high enough to cause burns if not properly operated and maintained eight Ceiling MIN 78 CAUTION The Blower Motor full load AMPS MUST be checked A plenum damper may be required to adjust the motor full load AMPS to the motor nameplate rating L I Fig 22 PF100 13 Venting and Installation See NOTES on page 13 Fig 23 Chimneys taller than 20 above the connection will re quire a draft test to determine if the draft is too high Note The Hi
19. 9 Troubleshooting 34 Feeder Parts 35 Specifications 36 Wiring Diagram 37 Parts List amp Options 38 Warranty 39 Testing Label 40 Quick Reference Start Up 41 Please read this entire manual before you install and use your new furnace Failure to follow instructions may result in property damage bodily injury or even death DO NOT INSTALL IN A MOBILE HOME SAVE THESE INSTRUCTIONS Harman Stove Company 352 Mountain House Road Halifax PA 17032 PF100 3 Assembly Design The first thing that needs to be done is deciding where and how the furnace will be installed Things that need to be taken into consideration are VENTING SUPPLY amp RETURN DUCTING ELEC TRICAL and Condensation drainage if A C is in stalled Don t forget access to the furnace for service When the return air inlet position is known the filter box and distribution blower can be installed See pages 5 6 7 8 When the furnace is set into place venting can be done Venting Use 4 pellet vent pipe to vent your PF 100 A combustion blower is used to extract the com bustion gases from the firebox This creates a negative pressure in the firebox and a positive pressure in the venting system as shown in fig 2 The longer the vent pipe and more elbows used in the system the greater the flow resistance Because of these facts we recom mend using as few elbows as possible and 30 feet or l
20. Blocked or partially blocked flue 2 Blocked or partially blocked inlet air a Backdraft damper on the inlet pipe may be stuck closed b If outside air is installed the inlet cover may be blocked 3 The air chamber under the burnpot may be filled with fines and small bits of ash 4 The holes in the burnpot may be getting filled with ash or carbon buildup 5 Combustion blower fan blades may need cleaned 6 There is no fuel in the hopper SMOKE SMELL Seal the vent pipe joints and connection to stove with silicone FIRE HAS GONE OUT 1 Nopellets in hopper 2 Draft setting is too low 3 Something is restricting fuel flow 4 Feed motor or combustion blower has failed 5 Power failure or blown fuse 34 PF100 SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fuel ratio is too rich A Feed rate too high B Draft too low caused by a gasket leak LOW HEAT OUTPUT 1 Feed rate too low 2 Draft too low because of gasket leak 3 Poor quality or damp pellets 4 Combination of 1 and 2 Cleaning Burn Pot Whenever your stove is not burning take the opportunity to scrape the burn pot to remove carbon buildup A vacuum cleaner is handy to remove the residue Be sure the stove is cold if you use a vacuum Carbon buildup can be scraped loose with the fire burning using the special tool provided with your stove Scrape the floor and sides of the burn pot The carbon will be pushed out by the incoming fuel Always wear gloves to do this
21. Burnpot Scraper Graltoir de la chaudi re de chauffage Datacom Wire Fit datacom 1000 CFM Blower Standard Ventilateur 1000 Standard Fan Control High Limit Contr le du ventilateur haute limite 1400 Blower Optional Ventilateur CFM 1400 Optionnel Fire Brick Brique de feu Return Air Filter Box Boite dc filtration pour retour d air Heat Exchanger Baffles D flecteurs d change de chaleur DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Do not operate with fire chamber or ash removal doors open WARNING Do not store fuel or other combustible material within installation clearance area CAUTION Hot while in operation DO NOT touch Keep children clothing furniture and other combustible mater al out of the installation clearance area DO NOT connect this unit to a chimney flue that serves another appliance Flooring must be a non combustible material coveririg the installation clearance area and 18 in front of and 8 to either side of the fuel loading doors In the event of loss of electrical power Consult owner s manual for restarting your furnace after power is restored Manufactured by Fabriqu par Ash Pan Bassin des cendres NE PAS CONNECTER CET APPAREIL UN TUYAU DE CHEMINEE SERVANT UN AUTRE APPAREIL ATTENTION pas op rer si la port du combustible ou la porte de l cuvette des cendres sont ouvertes Ne pas placer le combustible et les matieres combustibles l
22. E Cleanout Tee s should always be used on the transitions to horizontal pipe to allow easy access for cleaning The venting gragh allows for one 90 deg or Tee fitting in any configuration If more 90 s T s or 45 s are needed the total length must be adjusted to allow for the added restriction Up to four 4 additional 90 s Tee s or equivalent 45 s can be added as long as the overall length is ad justed in accordance with the values listed below See the venting graph on page 12 Fach Vertical 90 deg or T subtract 2 5 feet Each Vertical 45 deg subtract 1 5 feet Each Horizontal 90 deg or T subtract 5 0 feet Each Horizontal 45 deg subtract 2 5 feet Any exterior venting vent pipe exposed to out side ambiant temperatures should be kept to a minimum due to potential condensation problems This is especially important in high humidity cold weather climates such as maritime areas lake shores and low river valleys 10 PF100 INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE INSTALL VENT WALL PASS THROUGHS AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER NOTE All installation clearnaces and restrictions must be adhered to NOTE Read and follow all of the vent pipe manufacturers instructions on the proper installation and support
23. IANINIM 91 8 yIOE IE 1109 DNIN WAY NIHSNd P NVI IN 1 8091 1 0 O2rEL Pr Q3 171089 9NINV38 Wyo Qs 133899 LIYH amp 59800 05 8 ASSY YIYNY a BEN 6800 01 1 C 0v0 00 2 9 93419135 ONINV38 9819 lee Ce LAN L 91 S J3IDNY 01600 01 1 LNJAC TIM AGUE 830334 ATENASSY ESAOO 2807 DNISV38 A014 2105620808 c ITITS SINAN UNIA Nav adHsfld PF100 35 Specifications Wn 969 06 6972 70882 nami oos e 101 9 t 5 5 0 N CN o ag i J E d Jr NG i ES i 09612 Y i H NG 1 1 E EE a 27081 zl E ME E di 00011 J d 090 v 1 996 SZ 1 Q3TIVISNI HIMOTE 8r C9 S sroSesn eonnoo poSRIOAV Hi i 9
24. Installation amp Operating Manual The Harman PF 100 Pellet Pro Furnace Ce manuel est disponible en Fran ais sur demande SAFETY NOTICE PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALLAND USE YOUR NEW ROOM FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH FOR USE IN THE U S AND CANADA SUITABLE FOR INSTALLATION IN MOBILE HOMES IF THIS HARMAN PELLET FURNACE IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDING DEPARTMENT FIRE DEPARTMENT FIRE PREVENTION BUREAU ETC TO DETERMINE THE NEED FORAPERMIT CETTE GUIDE D UTILISATION EST DISPONIBLE EN FRANCAIS CHEZ VOTRE CONCESSIONNAIRE DE HARMAN STOVE COMPANY SAVE THESE INSTRUCTIONS 2 PF100 Parts Fan Control Hopper Lid Latches Vent Pipe Combustion Blower cover Heat Exchanger Shaker Handle Combustion Blower E 3 Speed Switch pu Control Cover d Outer Door Latches Outer Door a Viewing Glass Filter Box PF100 Table of Contents Assembly Venting Installation 15 Operation 21 Maintenance 2
25. Removing Ashes Turn the Temp Dial to number 1 approxi mately 30 minutes before removing ashes This will result in a cooler stove and ash pan Maximum Feed Adjuster settings are not needed in most cases Operating in the normal range 4 is recommended when maximum heat output is not required The ESP probe prevents the stove from being over fired Keep the stove free of dust and dirt Pellet fuels are put into 3 categories in terms of ash content Premium at 1 or less Standard at 3 or less and all others at 3 or more The P68 is capable of burning all 3 categories of pellets due to a patented feeder and burn pot system It should be noted however that higher ash content will require more frequent ash removal scraping of the burn pot and may provide less BTU s per pound Normally standard and high ash pellets cost less than premium pellets and can be cost effective when burned in the P68 The moisture content must not exceed 8 Higher moisture will rob BTU s and may not burn properly 0 n LL 20660 06 8 AULUWAV 39 CGI00 00 c AIN TA vIG 00CGeT 0E E 108 839fv 8 05 8 lt 1104 33509 pEGT0 00 e LNAOW SOLOW 70180 01 1 e LININT TIM WAY JAHSNd LIWNDND 539905 181518 05 5 ETOGO02Ge1 0E E p
26. W NIOTA TVNINAAL NIVIA i x 450 7 H 5 annoa S C m S ody zz TOYINOD Nv4 31V383d3S HLIM e SA AE am gu D 71091405 3 SN390N 3lIHM x c H V 59 2 NOLLONAP NI sors P k gt aN E5 J avo N gt gt T 7 HHH 4981 2 m m LINANDI X314 8 E UD i c Q 4addou ui gt BSN3S TANI 309 IA HOIH 0 453 i ANIM Q31SIAL 3 NOILVadd0 VASUN SZ SIIYM 006 7 8pou 1591 5 SdWV OT SIIVM 0021 E3A9OSN1G H I MOOT TWNIWYSL LVLSOWNSHL 310d 7H 09 2V SIDA 021 dS3 sde P 1991790 MOT WVADVIC ONINIM SJOVNANS 11771134 00114 NYWAYH 55 T eng eenia ouum ang 9 98 aavog y M M pH AAO DES pay PF100 37 Parts List Rubber Grommet 7 5 Hopper lid gasket 38 PF100 Igniter Element Assembly Burn Pot Weldment Exchanger Baffle Top Exchanger Baffle Bottom Arrow Scraper Flame Guide Flame Guide Insulator Thermister Probe Thermostat Circuit Board G4941 Differential Switch 5 Single Fan Blade standard 1000 CFM Distribution Blower Motor 1000 CFM Distribution Blower Complete Black Control Knobs 2 White Black Control Knob Control Knob Shaft 12 X 6 X 1 25 Firebrick Glass With Gasket Ash Pan Burn Pot Gasket
27. ced and is not creating a negative pressure in the house Note Ifthe furnace is installed with the outside air system no adjustments to the HRV should be necessary PF100 15 Installation Low FUEL O Fig 30 Orange D White Orange Blue TH White Blue D Fig 31 Datacom Wall Control Cable Orange Red LED Blue White Blue Tstat Orange White White or Black LED Blue Blue Tstat Fig 32 16 PF100 Wall Control Wiring The Wall Control sends and receives it s informa tion from the control board through a 4 wire Datacom cable There is a 100 length of this cable supplied with the furnace 100 lengths of this cable can also be or dered separately part 3 20 02583 Or any Datacom cable CAT 3 2 twisted pair 24ga solid wire can be acquired at a local electrical supply house Also any CAT 3 24ga solid wire 2 3 or 4 pair cable can be used because they all have the same pair color combinations The maximum length of wall control wiring is 200 feet The furnace connecting point is a 4 pole screw ter minal block on the side of the hopper just around the corner to the right ofthe control Follow the wiring instructions on the label alongside the terminal block See Fig 31 CAUTION With this small of wire gauge car
28. d push inward several strokes Third with the handle all the way out turn the handle right to left the full sweep several times End with the handle pushed inward and pointing down PF100 33 Troubleshooting FEEDER DOES NOT FEED 1 No pellets in hopper 2 Firebox draft may be too low for low draft pressure switch in feeder circuit to operate Check for closed doors loose or missing gasket on doors or hopper lid or a faulty pres sure switch 3 Feed motor will not run until ESP senses 165 deg F Maybe you did not put enough pellets in the burn pot before lighting the fire manually 4 Something is restricting flow in the hopper or causing the slide plate to stick 5 Feed motor has failed PARTIALLY BURNED PELLETS 1 Feed rate too high 2 Draft too low Check burn pot clean out slide and door gasket 3 Burn pot or heat exchanger tubes may need to be cleaned 4 Combination of all the above 5 6 status blink A6 blink control board status indication is caused by poor or incomplete combustion The Automatic Ignition circuit board has the ability to track the combustion through feed settings and ESP temperatures When the control board has calculated poor or incomplete combustion it will shut down the unit as a safety feature Poor or incomplete combustion is a contributer of creosote which may cause a chimney fire A 6 blink status may be caused by several things 1
29. e must be taken not to overtighten the terminal screws thus breaking the wire There are tie wrap holes in the face ofthe hopper aprox every 6 to keep the cable secure and out ofthe way The Wall Control is made to fit on a standard wall case electrical box It could also be mounted directly to a stud using 2 drywall screws In either case the screws should be turned in and tested for a snug fit when the Wall Control is slid down over the screws The Wall Control only hangs on the screws so a good fit is impor tant Remove the Wall Control and make the Datacom cable connections with the UY auto splicers provided DO NOT STRIP THE WIRES Following the wiring diagram on the inside of the Wall Control make each splice See Fig 32 Insert the two matching color wires fully into the two holes ofone ofthe UY connectors A pair of standard Channel lock pliers works ideally to squeeze the raised button down into the UY connector body Extra UY connectors can be purchased Part 3 20 00200 NOTE A pair of needle nose pliers may be nec essary to insert the BLUE T stat wires fully into the con nector Visually inspect to see that the wires are fully inserted before squeezing the UY splicer NOTE The PF100 furnace Can Not be installed with any other brand or type of wall thermostat Installing Duct RETURN EXISTING UNIT Fig 33 The Harman PF100 may be connected to a gas or oil fired central furnace or heat pu
30. e cold air return filter box can be assembled with the filter frame on either side or the back pro vided there is access to the combustion blower and flue area It is not recomended that the filter frame be installed on the same side as the ash door due to the need to access the combustion blower filter and flue pipe for service 1 Place the bottom on the floor The edge closest to the knockouts will be the edge towards the furnace See Fig 4 2 Place the desired vertical panel inside the bot tom tray and hold into place with one Tek screw in the bottom middle hole solid panel shown See Fig 4 PF100 5 Assembly Filter opening must be up SS Filter Frame Panel LE lt VA a NIN bd LS DS 2 D pa LEE P VA d Tis E sA gt 2 7 2 P LA Ue Fig 6 Open Side Panel bp a 6 PF100 Assembling Filter Box Cont d 3 Place the filter frame panel inside the bottom and inside the solid panel corner See Fig 6 for corner detail Make sure that the filter opening is up See Fig 5 Hold the filter panel to the solid panel with a Tek screw in the middle hole of the solid panel and one in the bot tom middle hole under the filter opening NOTE Do not put any screws into any of the top holes at this time 4 Place the remaining panel in this case the blower access panel in the bottom pan
31. el and into the corner of the solid panel See Fig 7 Make sure that the panel is inthe upright position There are no cover mount ing holes in the bottom edge of this panel Hold the panel into place with one Tek screw in the middle hole of the solid panel and one in the bottom middle hole of the blower access panel Assembly Assembling Filter Box Cont d 5 Place the top on the filter box as shown in figure 8 At this time all Tek screws can be inserted around the filter box Note Except for the 6 screws that attach the blower access panel in place There should not be any screws protruding from the box on the side toward the furnace Also DO NOT put a screw into the top center of the filter panel as a screw in this location will interfere with the filter access cover 6 Pry out the two knockouts in the top of the box and install the flex connector and the switch See Fig 9 Note Don t forget the HI MED LO switch label on the switch before the locknut Make sure that the set screw on the flex connector is not pointing toward the furnace end of the box when the locknut is fully tightened The filter box is now ready to install onto the furnace Follow the Blower mounting instructions on page 8 before continuing to step 7 Note The blower should be mounted on the fur nace before the filter box for ease of distribution blower installation Note It is best to wait until the blower filter bo
32. er 4 consecutive 8 minute attempts To reset Turn the Mode Selector to OFF and then back to Automatic 6 Blinks Indicates that the control has calculated poor or incomplete combustion occurring for more than 50 minutes A six blink status may be set if the stove is allowed to run out of pellets To reset turn mode selector to OFF then back on to the desired mode If the unit was not out of pellets see Troubleshooting section Page 35 for more details Manual reset disconnect power at the circut breaker for few seconds and reconnect If error still occurs call your Dealer 22 PF100 Mode Selector Allows you to choose between Automatic Mode Service Mode or OFF Automatic Mode Automatic mode switches operational control of the furnace to the wall mounted control This is the mode to use whenever the furnace is burning in a normal heating application Service Mode Service mode switches control of the furnace to the temp dial The temp dial can be set from 1 to 7 to allow a steady furnace temperature at the desired level The main purpose of this mode is to operate the furnace without having to go back to the wall mounted control OFF Mode Turning the mode selector to OFF will shut down the furnace The Distribution Blower is not controlled by the Test operation The Distribution Blower has it s own Manual Test Switch on the Fan High Limit Control cover Operation Temperature Dial Low FUEL
33. erature dial setting on the wall control 14 Return air filter Check the condition of the return air filter periodically and replace as needed Solid fuel burning appliances need to be cleaned frequently because soot creosote and ash may accu mulate If you suspect a chimney vent pipe fire 1 Call the fire department 2 Remove fuel from the burn pot using the burnpot scraping tool to scrape the pellets into the ash pan 3 Remove the ash pan from the unit and take outside Do not place ash pan on a combustible material 4 Turn off circuit breaker at unit 5 Do not use the unit until a qualified person has inspected your appliance and venting 28 PF100 Maintenance 5 ie cleanout cover Possible pellet fines build up area Fig 61 Scrape burnpot to remove any carbon build up that may have occured operation Scraping can be done while in Fig 62 Burnpot cleaning The burnpot should be cleaned no less than once a week For best operation the burnpot should be cleaned every time the hopper is filled with pellets The fire does not have to be out to scrape the burnpot although it is recomended the furnace be on minimum burn at the time of cleaning Note The furnace can easily be turned to mini mum burn regardless of present opera
34. es that may have accumulated NOTE ALWAYS REMEMBER TO CLOSE THE CLEANOUT COVERAFTER CLEANING Feeder Chamber Fig 61 This chamber may get a buildup of fines from the feeder mechanism movement This area should be checked and cleaned at least once a year To remove the feeder cover Remove the 5 16 wing nut Slide the cover off of the threaded stud e Inspect and clean the inner chamber if necessary See Fig 61 Reinstall the cover making certain it is centered on the feeder body and tighten as tightly as you can by hand PF100 29 Maintenance Ash Removal It is recommended to remove the ashes when the furnace is not in operation This lessens the chances of coming in contact with hot surfaces Ashes can be re moved while in operation but extra care must be taken Open Outer Ash Door Lift the two latches shown in figure 63 and open the outer door as shown in figure 64 If the Distribution Blower is running when the outer door is open some air will escape around the door opening This is not a prob lem however any dust that is caused in the ash removal process can potentially be blown around Outer Door Latches Fig 63 Open Inner Ash Door Lift latches shown in figure 64 and open the inner door as shown in figure 65 NOTE Keep hopper lid and ash pan doors closed during operation and maintain all seals in good condition Remove Ash Pa
35. ess of vent pipe The maximum horizontal run should not exceed 18 feet Pez Be sure to use wall and ceiling pass through fittings which are approved for pellet vent pipe when going through combustible materials Be sure to use a starting collar to attach the venting system to the stove The starting collar must be sealed to the stove flue collar with high temp silicone caulking or aluminum tape and screwed into the stove flue Fig 2 collar at least three 3 places Vent Pipe 4 pellet venting pipe also known as PL vent is The shaded areas are the clear constructed of two layers with air space between the ances for the PL vent pipe that must oe be maintained at 3 After the vent layers This air space acts as an insulator and reduces ing leaves the shaded area it may be installed outside surface temperature to allow a clearance to Only UL listed wall pass throughs combustibles of only 2 inches This 2 inch clearance is Posed also approved by the pipe manufacturers See images Clearances and Venting
36. ets being used Keep in mind that the cleaner the heat ex changer surface is kept the higher the heat transfer effi ciency will be Due to it s ease of restarting it is recommended that the furnace be OFF and COOL before cleaning Before starting to clean the inside of the firebox area it is recomended that all of the baffling be removed Start with the upper heat exchanger baffle See Fig 66 Push straight upward on the lower ash slide angle aprox 1 2 This will release the baffle from the positioning brackets and allow it to be tilted toward the burnpot and removed from the furnace Fig 66 Note Observe the positioning tabs and bracket system on the rear of the upper baffle as it is being removed for easier replacement later Remove the lower baffle plate This baffle is a flat plate that sits on the furnace floor Tip the top edge to ward the burnpot and lift up and out of the furnace Note how the baffle bottom edge sits behind the ash pan guide and against the heat exchanger See Fig 67 Ash Pan Guide r 5 d With all of the baffling removed the entire firebox area and the accordion heat exchanger can be cleaned Use the pointed end ofthe scraper supplied to clean the accordion heat exchanger A small wisp br
37. etting Remember if your feed rate is too high you may waste fuel due to overshooting the Wall Control setting 6 Flip the Igniter Switch up into the AUTO LIGHT position 7 Turn the Temperature Dial on the wall control to desired room temperature Note The set temperature on the dial must be higher than the room temperature for the fire to light WARNING HOT WHILE IN OPERATION KEEP CHILDREN CLOTHING AND FURNITURE AWAY CONTACT MAY CAUSE SKIN BURNS PF100 25 DA 6 i 8 Turn the Temperature Dialon the furnace SR control to NORMAL SETTING NORMAL C SETTING a i VH Fig 53 9 Turn Mode Selector to AUTOMATIC AUTOMATIC This will start the lighting process ifthe tempera ture at the wall control is less than the set temperature on the dial The PF100 is more than just an automatic ignition pellet furnace The automatic system will allow the fire size to be adjusted to match the heating needs and even put the fire out if necessary If heat is needed after the fire is out the PF100 will automatically re ignite and adjust the fire size to match the heating need Fig 54 10 Fill hopper with pellets and remove AUTOMATIC ashes as required Type of Fuel Use pelletized wood only Note The lower the Temp Dial Mode Selector ash content ofthe pellets the less cleaning that will be This is the Cont
38. flue venting will not interfere with the flex to the Fan Control 4 Pry out one of the bottom knockouts of the Fan Control Install the 90 degree flex connector as shown in Fig 36 One of the locknuts stays on the outside of the box and one goes on the inside to tighten the connector into place This allows for maximum room for the wires around the switches 5 REMOVE THE COPPER JUMPER BE TWEEN THE LIMIT AND CONTROL SWITCHES It is not needed Figure 36 shown with copper jumper that has already been removed 6 Connect the two VIOLET wires to the FAN CONTROL switch It doesn t matter which wire is on which screw See Fig 36 7 Connect the WHITE and SKY BLUE wires to the LIMIT switch It doesn t matter which wire is on which screw See Fig 36 8 Make sure that all of the wires are out of the way when closing the cover Excess twisting and pinching of the wires could cause a short circuit 9 HIGH LIMIT setup is simple just rotate the high limit pointer clockwise until it is against the tamper proof screw Never adjust this screw 10 FANCONTROL setup Move both fan control pointers together until they touch then rotate both pointers together until the gap between them is directly over the middle 0 of 100 See Fig 36 Note This is the best fan control position we have found during factory testing These fan control limits can be adjusted if desired PF100 19 Installation Installing Electrical Power
39. gh Burn Draft should not exceed 85 IWC Some form ofa restrictor plate may be required at the top ofhigh chimneys to reduce the draft See page 20 for the Draft Test procedure el Fig 24 The shaded areas are the clearances for the PL vent pipe that must be maintained at 3 After the venting leaves the shaded area it may be installed at 2 to combustibles Only listed 4 pellet vent wall pass throughs and fire stops must be used See Fig 23 amp 25 18 18 7 7777 I WG 16 N V Fig 25 The PF100 furnace may be used and installed into an existing masonary or Class A metal chimney Certain Canadian and Local Codes may require that the chimney be fully relined See Fig 24 It Can Not be installed in a chimney serving another appliance The chimney should be cleaned and or inspected be fore installation 44 mp a l Fig 26 Creosote Formation and Need for Removal When wood is burned slowly
40. ht Indicates power to the ignitor Temp dial LOW C FU BLOWE MOTO O MANUAL LIGHT Feed adjuster Sets the maximum feed rate Test Runs all motors at full speed for one minute to check operation After one minute the furnace will go to minimum burn and the combustion EL blower will alternate from high to low every minute to remind you that you are still in Test Mode AUTO LIGHT Lighting Mode Selector Switched between Auto and Manual lighting AUTOMATIC Mode Selector See explanation below Dealer Diagnostic Port For dealer maintenance only Requires special DDM monitor supplied to Harman Dealers exclusively The Temp Dial should be in the Normal Setting position except when service work is being done It also allows you to adjust the fire temperature when the Mode Selector is in Service Mode using the scale marked from I to 7 Status light error messages 1 Blink Indicates control board self diagnostic failure This requires a manual reset 3 Blinks Indicates ESP Exhaust Sensing Probe failure This requires a manual reset 4 Blinks Can occur only in the Automatic Mode and indicates the Wall Control has failed or is not installed If a Wall control is then installed the status light will automatically reset Note only after the unit has warmed up 5 Blinks In Auto Light Mode Only Indicates that the igniter has failed to light the fire aft
41. intericur de l espace d sign e pour l installation ATTENTION Chaud lors de l op rat on NE PAS toucher Gardez les enfants les v tements les meubles et les mat riaux combustibles loin de l espace d sign e pour l installation NE PAS connecter cet apareil un tuyau de chemin e servant un autre appareil Le plancher de l espace d sign pour l installation doit tre fait de mati re non combustible de 18 en avant et de 8 de chaque c t des portes d entr e du combustible Dans le cas d un manque d lectricit Consultez le manuc du propri taire pour remettre la fournaise en marche lorsque l lectricit est revenue Harman Stove Co 352 Mountain House Rd Halifax PA 17032 Date of Manufacture Date de Fabrication 2004 2005 2006 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Made in U S A Fait aux Etats Unis 40 PF100 Do Not Remove or Cover This Label Ne pas enlever ou recouvrir cette tiquette SUIUBOTD oqe S IVJOP 929u U9jUI A UO 298 AY IIG z x TIMOG Supnpusr enue A 3noqe uo uonoos IY IIS z 10 5000 992 uo 395 u utu 5591 SI AY AY IYL AN YOyIMs 3u3rT oiny ou dili OT x UMOYS 58013395 9Y 0 sqou 013u0 IY Jo UINL 6 IY 0
42. le down on to the brackets while you hold the baflle against the heat exchanger You will notice that the upper baffle will hold the lower baffle plate into position See Fig 17 Note how the upper and lower baffles are held into position because they will need to be removed during heat exchanger cleaning PF100 9 4 Type L or u PL Vent pipe DAADAAAAA WATA VAVAVAVAVAVAYAYA KANA Fig 18 This is the minimum venting configuration NOTE This would only be allowed with non combustible walls NOTE Use only 4 diameter type L or PL venting system Be sure to inspect and clean exhaust venting system frequently The minimum vent configuration 15 a 90 or Tee on a starter collar and a 24 length horizontal through an exterior wall A cap or other bird screen on the end should direct the flue gasses down and away from the structure See Fig 18 The maximum horizontal length is 18 feet The mini mum termination height above the exterior grade 15 18 The maximum total length of any configuration is 30 feet see venting graph on page 13 for exceptions NOT
43. lue gasses into the combustion blower inlet hole A flashlight may be necessary Fig 72 Inspect the chain shaker mechanism for proper operation Note Fly ash can build up to the top edges of the heat exchanger tubes without affecting operation The chain shaker will cause any excess to fall down into the chamber under the tubes where it can be cleaned out f through the fire box See Fig 73 IT CAUTION Inspect flue pipes flue pipe joints and flue pipe seals regularly to ensure that smoke and flue gases are not drawn into and circulated by the air circulation system Cleaning the Tube heat exchangers The heat exchangers tubes have anexternal handle that operates the cleaning mechanism See Fig 74 This cleaning should be done at least once a week although it can be done as often as desired The cleaner the heat exchangers are the more efficient the furnace will be This cleaning can be done at any time and in any mode of operation Lower cleanout chamber Fig 73 The handle has two directions ofmovement Right to Left and In and Out All inside surfaces of these rect angular tubes can be cleaned with this range of motion First with the handle pushed in turn the handle right to left the full sweep several strokes Second with the handle pointing straight down pull out an
44. mp duct system Prior to installation determine whether all requirements for installation including all clearnaces can be met The PF100 warm air supply and the cold air return must be installed in a parallel arrangement EXAMPLE The warmair supply duct from the PF100 is to be con nected to the warm air supply ofthe existing furnace Also the cold air return duct from the existing furnace is to beconnected to the cold air return duct ofthe PF100 Isolation dampers 2 should be installed in the ductwork 1 in the warm air supply duct for the existing furnace and 1 in the warm air supply duct ofthe PF100 after or downstream ofthe high limit fan control These dampers can be manually operated or fully automatic In either case the unit that is not being used must be prevented from being operated This also can be done manually or automatically NOTE Any control wiring power wiring needed should be performed by a quali fied installer and or electrician The warm air supply outlet ofthe PF100 shall not be connected to the cold air return inlet ofthe central furnace because a possibility exists of components of the central furnace overheating and causing the central furnace to operate other than as intended We recommend that the warm air supply plenum be constructed of sheet metal PF100 17 Installing Duct Recommendations for Supply Airand Return Air duct sizing The speed or velocity of air moving through duct systems
45. n Always wear gloves to remove ash pan Grab the ash pan by the handle and pull it out of the furnace Lift the handle and use it for carrying the ash pan Close the inner door before disposing of the ashes Disposal of Ashes Ashes should be placed in a metal container with a tight fitting lid The closed container ofashes should be placed on a non combustible floor or on the ground well away from all combustible materials pending final disposal If ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all cinders have thoroughly cooled Soot and Flyash Formation and Need for Removal The products of combustion will contain small particles of flyash The flyash will collect in the exhaust venting system and restrict the flow of the flue gases Incomplete combustion such as occurs during startup shutdown or incorrect operation ofthe room heater will lead to some soot formation which will collect in the exhaust venting system The exhaust venting system Fig 65 should be inspected at least twice monthly to determine if cleaning is necessary 30 PF100 Maintenance Cleaning the accordion heat exchanger firebox This cleaning should be done after each ton of pel lets used The frequency ofthis cleaning will be directly related to the quality and the ash content ofthe pell
46. ned 3 Clean burnpot with scraper if necessary This is usually a weekly maintenance procedure Cleaning the burn pot with the scraper witha small amount of new fuel in the bottomis not a problem First scrape the ashes on the front of the burn pot into the ash pan Then scrape the hole grid surface downward into the burn pot When the stove is ignited these scrapings will be pushed out by the feeder Note Ifthe Distribution Blower is running when the outer door is open some air will escape around the door opening This is not a problem however any dust that is caused in the process can potentially be blown around Fig 48 24 PF100 Fig 49 Fig 50 AUTO LIGHT MANUAL LIGHT Fig 51 O Fig 52 4 If starting after an empty hopper turn Feed Adjuster to TEST for one 60 second cycle This will purge pellets into the auger tube and also allow you to check the motors for operation NOTE The auger motor will not operate with the ash door open 5 Turn Feed Adjuster to 4 If this is your first fire or you are trying different pellets set the feed adjuster to 74 Fig 50 This is a conservative number and will probably need to be increased 1f maxi mum BTU output is desired After you know a feed rate setting that works well for your application use that s
47. nufacturer giving the model and serial numbers the date of purchase your dealer s name and address plus a simple explanation of the nature of the defect Extra costs such as labor mileage and overtime are not covered Nuisance calls are not covered by these warranties THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS REPAIR AND OR REPLACEMENT AT HARMAN STOVE COMPANY S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL DAMAGES CONNECTED THEREWITH WARRANTY EXCLUSIONS Failure due but not limited to fire lightning acts of god power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to filters fuses knobs glass door packing paint batteries or battery backup and related duct work are not covered Also excluded from this warranty are consumable or normal wear items including but not limited to grates fire brick gaskets Additional or unusual utility bills incurred due to any malfunction or defect in equipment and the labor cost of gaining access to or removal of a unit that requires special tools or equipment are not covered Maintenance needed to keep the stove in good operating condition is not covered This includes but is not limited to cleaning adjustment of customer controls and customer education Labor material expenses and or equipment needed to comply with law and or regulations set forth by any governmental agencies are not covered This warranty
48. ombustion Blower 3 Speed Switch Control Cover Outer Door Latches l Outer Door L ss Viewing Glass Filter Box d Fig 40 The Control The control can be covered as shown above or uncovered as shown at left There is a pair of slots pro vided for each position Simply move the cover to the desired position by placing the tabs on the cover in the proper slots CAUTION Hot while in operation Do not touch Keep children clothing furniture and other combustible material out of the installation clearance area WARNING Do not operate with fire chamber or ash removal doors open WARNING Do not store fuel or other combustible material within installation Fig 41 clearance area PF100 21 WARNING HIGH VOLTAGE Disconnect power before opening cover Power Light Indicates power to the control and is also used during Test to check the Low Fuel Sensor operation STATUS POWER Status Light Will be lit in either automatic or service mode when pointer is not within off position band except after normal shut down It FEED also blinks to indicate errors listed below COMBUSTION IGNITOR Low Fuel Light Indicates that fuel in the hopper is low and needs to be refilled Combustion Blower Light Indicates Power to combustion blower Feed Motor Light Indicates Power to the feed motor IgnitEr Lig
49. oo much time is allowed to pass before lighting the starting gel CAUTION Care must be taken not to get starting gel on your hands or clothing Serious burns could occur during the lighting process CAUTION Never tryto apply more starting gelto an already burning fire or a fire with smoldering pellets NEVER USE GASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS FUR NACE KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE FURNACE WHILE IN USE PF100 27 11 Turn Mode Selector to SERVICE This will start the combustion blower and allow the ESP to control the fire in relation to the Temp Dial set ting 1 through 7 Once the fire is well established the Temp Dial can remain on any number setting desired or changed to the AUTOMATIC setting If you change to AUTOMATIC remember to set the Temp Dial to Normal Setting for proper Wall Control calibration Fig 59 NOTE When the Switch is setto Manual Lite in the AUTOMATIC mode the Wall Control will func tion as in Auto Lite except the fire will not be allowed to go out It will only be allowed to go to a minimum burn rate between the times the Wall Control is calling for heat This rate is about 1 pound of fuel per hour 12 Light The Starting Gel With A Match 13 Close The Doors The fire willlight and the PF100 will adjust the fire to proper level according to the temp
50. or this is heat build up and required space for service and normal operation This is the minimum size of the room even ifit is built of non combustible material High and low air vents MUST be installed between the roomand the remaining living space Each vent should be at least 72 square inches in area The vent size will need to be increased if there is no return air ducting sys tem The striped areas are the minimum clearances to com bustibles which is 36 from stove body not hopper or blower The shaded area indicates the required floor protec TITLE tion area The PF100 requires 48 x 52 of floor protec VU My IA ai qt tion centered around the skidplate footprint Flooring should 7 S To I 7 4 8 W be aminimum of 26 gauge sheet metal covering the instal Z lation clearance area and 18 in front of and 8 to either Ly 22 22 97 7 side ofthe ash pan door CA The 18 ch the h di factur 18 clearance on hopper end is manufactur cag ers recommendation for adding pellets and or servicing the feeder mechanism The minimum clearance to the top ofthe plenum 15 4 Note the minimum height to the bottom ofthe supply Le 96 MIN duct if it crosses the hopper Fig 21 The minimum duct configuration to a living space above the furnace is as shown in below An offset ofat least 2
51. paved driveway located on public property must be a minimum of 7 feet M The clearance under a veranda porch deck or balcony must be a minimum of 12 inches NOTE The clearance to vegetation and other exterior combustibles such as mulch is 36 as measured from the center of the outlet or cap This 36 radius continues to grade or a minimum of 7 feet below the outlet Certain Canadian and Local codes or regula tions may require different clearances A vent shall not terminate directly above a side walk or paved driveway which is located between two single family dwellings and serves both dwellings 3Only permitted if veranda porch deck or bal cony is fully open on a minimum of 2 sides beneath the floor NOTE Where passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 if in Canada Inside Corner B Fixed Closed Area where terminal is not permitted Fig 20 Venting and Clearances m 64 5 VIT TI LI TINTS 1 COME Z 12 YA 2 Floor Protector 2 PF100 EE 1 Skidplate eve i Footprint Clearances to combustibles If installing the furnace in a room separated from the remaining living spaces the minimum size of the room must be no smaller than 8 x 8 See Fig 21 The reason f
52. r lid must be latched during this test It is recom mended that the draft meter have a scale of 0 to 1 WC Turn the Furnace Control to Test this will start the Fig 38 combustion blower and allow you to check and record the High Draft IWC date There is no adjustment for the High Draft After the first 60 seconds the Test mode lowers the combustion blower voltage to the Low Burn voltage The Test mode cycles the voltage from high to low every 60 seconds During this lowered voltage cycle the Low Burn Draft must be checked and adjusted if necessary The la cw recommended low draft setting should be between 25 amp Mi 35 IWC Depending on the amount of vertical rise it may Low Draft Adjustment Pot not be possible to get a low draft reading in this range In this case a maximum low draft of 55 is acceptable The adjustment screw is through the small hole to the Fig 39 right of the Igniter Light See Fig 39 Adjusted the Low Draft to IWC 20 PF100 Don t forget to turn the control back to 4 Draft meter bolt Furnace Control Fan Control Hopper Lid Latches Vent Pipe Combustion Hopper blower cover Heat Exchanger Shaker Handle C
53. rents will cause with flyash and or smoke when placing the termi nation In addition the following must be observed A The clearance above grade must be a minimum of 18 B The clearance to a window or door that may be opened must be a minimum of 48 to the side 48 below the window door and 12 above the window door with outside air installed 18 12 clearance to a permanently closed win dow is recommended to prevent condensation on the window D The vertical clearance to a ventilated soffit lo cated above the terminal within a horizontal distance of 2 feet 60 cm from the center line of the terminal must be aminimum of 18 E The clearance to an unventilated soffit must be aminimum of 12 The clearance to an outside corner 15 11 from center of pipe G The clearance to an inside corner is 12 O Air supply inlet Vent terminal 12 PF100 H A vent must not be installed within 3 feet 90 cm above a gas meter regulator assembly when mea sured from the horizontal center line ofthe regulator I The clearance to service regulator vent outlet must be a minimum of 6 feet J The clearance to a non mechanical air supply inlet to the building or the combustion air inlet to any other appliance must be a minimum 01487 K The clearance to a mechanical air supply inlet must be a minimum of 10 feet with outside air installed 6 feet L The clearance above a paved sidewalk or a
54. rews on each side where shown in Fig 11 Start with the two center screws NOTE There are two small holes in the discharge end ofthe blower that matchthe two center holes on the small angle of the blower bracket The two 2 outer holes are drilled by theTek screws 2 Mount blower with brackets installed on the furnace as shown in Fig 12 Each side will require 6 Tek screws NOTE The furnace blower opening is made large enough for the use of a 1500 or 2000 CFM blower The blower mounting brackets will fit either blower The inner hole pattern is for the 1000 CFM blower and the outer pattern is for the 1500 or 2000 CFM blower NOTE These Blower Motors are not designed to be operated without any positive static back pressure OPERATION WITHOUT SUPPLY DUCTWORK OR IN FREE AIR WILL CAUSE MOTOR OVERLOAD AND PREMATURE FAILURE CAUTION Regardless of the supply air duct size installed the Distribution Blower Motor MUST be checked for running Amperage Check the motor name plate for the full load AMPS Ifthe amperage is running higher than that listed a supply air restricting damper may be required to increase the supply plenum positive static pressure 3 Mount the filter box on the furnace with 8 10 x 3 4 Tek screws 3 on each side Visually locate these holes so you are familiar with their location on the filter box and the furnace Access to the mounting holes
55. riod of 1 year from the date of sales invoice If defective in material or workmanship during the warranty period Harman Stove Company will at its option repair or replace the product as described below The warranty above constitutes the entire warranty with respect to Harman Stove Company HARMAN STOVE COMPANY MAKES NO OTHER WARRANTY EXPRESSED OR IMPLIED INCLUDING ANY WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE No employee agent dealer or other person is authorized to give any warranty on behalf of Harman Stove Company This warranty does not apply if the product has been altered in any way after leaving the factory Harman Stove Company and its agents assume no liability for resultant damages of any kind arising from the use of its products In addition the manufacturer and its warranty administrator shall be held free and harmless from liability from damage to property related to the operation proper or improper of the equipment THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the operators manual THESE WARRANTIES WILL NOT APPLY if abuse accident improper installation negligence or use beyond rated capacity causes damage HOW TO MAKE A CLAIM any claim under this warranty should be made to the dealer from whom this appliance was purchased Then contact is made with ma
56. rol setting that will allow the Wall needed ofthe heat exchanger surfaces The cleaner these Control to function surfaces are kept the more efficient the furnace will be NOTE Do not burn garbage gasoline naphtha engine oil or other inappropriate materials in the PF100 Store pellets in the manufacturer s wrapping until needed to prevent pellets from absorbing moisture Do not store fuel within the appliance installation clearances or within the space required for fueling ash removal and other routine maintenance operations 26 PF100 AUTO LIGHT MANUAL LIGHT Fig 57 Fig 58 Lighting A Fire Manually Lighting the fire manually will not be necessary unless the igniter in the burnpot fails Follow steps 1 through 5 of the instructions for automatic lighting 6 Flip the Igniter Switch Down into the MANUAL LIGHT position See Fig 55 7 Open inner and outer ash doors as shown in figs 63 64 65 on page 30 8 Fill burnpot with pellets as shown See Fig 57 Only fill level with the front edge DO NOT OVERFILL 9 Have matches or other ignition source ready 10 Apply starting gel as shown in Fig 58 NOTE Stirring the starting gel into the pellets usually allows the fire to become established quicker CAUTION A vapor flash could occur ift
57. se about 1 8 turn This will allow the complete assembly to be removed from the blower chamber Clean the blower fan blades and the blower plate sealing overlap See Fig 71 Note Be carefull not to bend the fan blades this will throw the fan blade out of balance or it may rub the inner chamber which may affect the performance ofthe furnace Any horizontal and vertical flue pipe directly above the unit should be cleaned at this time Note The horizontal flue pipe directly above the furnace is the first place fly ash will settle due to the slowing of flue gas velocity through horizontal pipe Cleaning of horizontal venting pipes is very important to the efficiency of this furnace Sealing Overlap Fig 71 32 PF100 Maintenance Clean the flue outlet throat this is the hole that W 4 goesupinto the flue pipe See Fig 72 a Note The ESP probe sensing tip extends into this same area CARE MUST BE TAKEN NOT TO bn d DAMAGE THE ESP PROBE DURING CLEAN ING Bending of the ESP probe will make it difficult to 1 remove should become necessary See Fig 72 Clean the inner chamber of the blower See Fig 72 Clean the furnace blower plate sealing overlap See Fig 72 Inspect the tops of the heat exchanger tubes where the chain shaker mechanism is located Make sure there are no fly ash buildups that may block the easy flow of f
58. tion Simply turn the Mode Selector to SERVICE Then turn the Temp Dial to the 1 setting If this is done before starting to refill the hopper the furnace willnot be as hot when scrap ing the burnpot When the burnpot cleaning is completed don t forget to turn the control back to the Wall Control positions See Fig 61 Use the flat end of the scraper provided to scrape down over the holed surface of the burnpot grate See Fig 62 It is not necessary to clean out the scrapings from this cleaning because they will be pushed out the next time the auger operates Note Make a special effort to scrape the bottom inside corners of the burnpot where the auger tube en ters the burnpot Carbon deposits can build up over time in this area that may cause a restriction to the flow of pellets into the burnpot Note An old long shank screwdriver with the end sharpened is an ideal aid in the removal of these deposits Cleaning the burnpot air chamber This area only needs to be cleaned twice a heating season unless excessive buildup is noticed during sched uled cleanings There is a cover on the front of the burnpot to gain access to the air chamber and igniter The cover is held into place by two thumb screws Loosen the thumb screws and remove the cover See Fig 60 The air cham ber can be cleaned of any ash that has fallen through the holes during operation and cleaning Also at this time remove the feeder assembly cover and remove any fin
59. ush wire brush or an old stiff bristled paint brush works best for cleaning the firebox walls All of the fly ash removed during cleaning will fall to the bottom ofthe furnace where there is an unobstructed access for cleaning Even the bottom ends of the chains can be seen and accessed easily from the door opening See Fig 68 CAUTION Cleanout of the heat exchanger flue pipe chimney and combustion blower fan housing is especially important at the end of the heating season to minimize corrosion during the summer months caused by accumulated ash PF100 31 Maintenance Combustion Blower Cleaning Remove the combustion blower heat shield There are two latches that hold the shield in place See Fig 69 Flip the latches up and pull the shield away from the furnace It can not be fully removed it can only be moved down over the wire until it hangs on the junction box The furnace MUST be OFF and COOL before you should attempt to clean the combustion blower The wire to the combustion blower doesn t need to be disconnected during the cleaning process Loosen the three 3 thumb screws about 4 turns each See Fig 70 Hold the motor head with one hand and the blower plate handle with the other hand Pull outward on the plate handle until the complete unit comes loose Now rotate the plate counter clockwi
60. x and cold air return duct work is installed before install ing the filter and side panel 3 Speed Switch Access Panel Cover opening 7 Afterthe Filter Box is installed on the furnace the electrical wiring to the three speed switch needs to be completed WHITE to WHITE VIOLET to the center terminal ofthe switch and the BLACK RED BLUE to the terminals shown Note The optional 1500 CFM blower is a single speed blower therefore the three speed switch will not be used The optional 2000CFM blower is a 4 speed Yellow on 2000 CEM molor only hook up the three colors shown and tape off the orange wire See Fig 10 VIEW BLUE ngg apy RED 8 Install the access panel cover by hooking the lip A at the bottom ofthe cover over the edge in the filter box BLACK 7 Use 6 Tek screws to secure the access panel Violet 120VAC 9 To install the filter insert the filter into the filter slot and slide completely into the frame Take note to the air flow arrow on the filter when installing Slide the filter access cover over the opening with the upright angle Fig 10 toward the filter box Ifa Tek was put into the middle hole by mistake remove the screw to allow the access cover to fit properly PF100 7 Assembly Blower Assembly Install the blower mounting brackets on the blower as shown in Fig 11 1 Install 4 Tek sc

Download Pdf Manuals

image

Related Search

Related Contents

  manual de instrucciones del programador pg master 6001    Multiquip DCA400SSI Portable Generator User Manual  CombiVapeurExpert-BD-VDEF 11 08 2011  保存用 取扱説明書  取扱説明書  Miele B 995 D  

Copyright © All rights reserved.
Failed to retrieve file