1. Catalog Number RSEN W12 Total Lighting Control Line voltage Wall Switch Occupancy Sensor DESCRIPTION AND OPERATION The RSEN W 12 is a self contained motion sensing lighting control which replaces a conventional wall switch for energy savings and convenience Lights turn off automatically after a room is vacated Built in sensors produce low intensity inaudible sound and detect changes in sound waves caused by motion such as walking into the room reaching for a telephone turning ina chair The sensor does not respond to audible sound In the Automatic ON mode the lights turn on automatically when a person enters the room In the M anual ON mode lights are turned on by pressing the touchplate on the switch Modes can be changed by flipping the concealed switch under the touchplate In either mode lights will remain on as long as motion is detected in the room When no motion is detected the lights will turn off automatically after the pre set time delay Following this a grace period of approximately ten seconds allows lights to be turned on again by motion At any time lights may be turned off while the room is occupied by pressing the touchplate The RSEN W 12 is fully self resetting lights turned off manually in Automatic ON mode will stay off while the room remains occupied After the room is vacated and the preset time delay and grace period have elapsed the lights will remain off until turned on automatically
2. LED goes off and stays off with no motion 6 If the sensor is activated by passers by in the hallway reduce the Entry Range setting 7 Set Time Delay to the desired setting for normal use If lights go out while the room is occupied increase setting slightly until an optimum interval is obtained Recom mended time delay is usually 6 8 minutes approximately 10 o clock People who remain very still for long periods may need a longer time delay 8 If preferred the RSEN W12 may be set to M anual ON for maximum energy savings by moving the M ode switch to the M position In this setting the occupant must push the touchplate to turn on lights upon entering the room Ww N Catalog Number RSEN W 12 Emergency Service or Support 888 852 2778 TROUBLESHOOTING Emergency Manual ON An override jumper is located underneath the touchplate This jumper should remain in place at all times except in the event of unit malfunction Remove the jumper to bypass the sensor and turn the lights on LED Will Not Go On Verify that the lighting circuit has power Verify that the sensor is properly adjusted Press the touchplate to turn on the lights manually If the LED does not light replace the RSEN W 12 Lights Will Not Turn ON If the lights will not turn on automatically after someone enters the room press the touchplate to see if lights will turn on If so the RSEN W 12 could be set to M anual ON mode Check
3. SEN W 12 must be verified Adjustments should be made with the HVAC system on Use only insulated tools to make adjustments 1 Adjustment controls are under the touchplate Time Delay ranges from 15 seconds for testing to 30 minutes Using a small screwdriver set Time Delay to 15 seconds by turning the control completely counterclockwise until it stops at minimum setting approximately 8 o clock Turn control for Area Range until flat edge of control is at 10 o clock Turn Entry Range until flat edge of control is at 9 o clock Move the Mode switch to the Auto or A position The area of coverage can be determined by watching the LED indicator on the front of the sensor while moving around the room The LED lights only when the sensor detects motion Adjust the Area Range control to the lowest setting that provides adequate motion detection of a person working in the room Do not set higher than necessary 4 Leave the room The lights should go out in approximately 15 seconds Wait at least 12 seconds after the lights go out Walk normally back into the room and verify that the lights turn on automatically If not the Entry Range should be increased slightly Do not set higher than necessary 5 If the LED blinks when there is no movement in the room it is possible that the sensor is being activated by air flow from the HVAC system Reduce the Area Range setting until the
4. arity sensitive One Circuit Two Lighting Loads The combination of Load 1 and Load 2 must not exceed the maximum load rating Consult with the building manager and occupant to determine which lights should be off Load 2 when the toggle switch adjacent to the RSEN W 12 is open OFF Caution If a room is wired for two circuits using two separate hot leads itis very important to connect only one circuit to the RSEN W12 Split one circuit into two switchlegs and cap the unused hot lead inside the box The RSEN W 12 must always control Load 1 while its control of Load 2 is selected manually by opening and closing the toggle switch Connect one wire to the switchleg for Load 1 and one side of the toggle switch for Load 2 Finally connect the other wire from the RSEN W 12 to the hot lead Connec tions are not polarity sensitive Catalog Number RSEN W 12 INSTALLATION CONTINUED Sensor Wiring 120 VAC OR 277 VAC NEUTRAL LOAD 2 LOAD 1 LOAD 2 SWITCH LEG SWITCH LEG TOGGLE SWITCH RSEN W12 OPTIONAL Sensor Adjustment Switch to M for Manual On Switch to A for Auto On Sensitivity Time Delay Adjustments Adjustment clockwise clockwise minimum 15 seconds to to maximum 30 minutes Checkout and Adjustment Once installation is complete restore power to the lighting circuit Proper operation of the R
5. the next time someone enters the room The RSEN W 12 can be used with a standard toggle switch to split the lighting load for rooms that are wired for two switches as shown in the wiring diagram FEATURES Replaces a conventional wall switch e For use in small rooms or offices up to 300 square feet One model for either 120 VAC or 277 VAC e Choice of automatic ON or manual ON modes e Separate time delay and sensitivity adjustments For indoor use only Before proceeding read the enclosed installation instructions For GE TLC Service call 1 877 584 2685 USA or 1 800 661 619 Canada Installation Instructions IMRSEN W12 Catalog Number RSEN W 12 INSTALLATION Coverage The RSEN W 12 is designed for offices or small rooms up to 300 square feet Although total coverage of minor motion is 450 square feet wall switches are normally mounted off center in a room which reduces the coverage attainable Basic Installation Steps 1 Turn off power at the circuit breaker 2 Wire and mount the switch in standard junction box 3 Restore power to the circuit 4 Adjust settings and test Location When installing the RSEN W 12 in a new junction box choose the switch location carefully to provide optimum coverage of the occupied area When replacing an existing wall switch bear in mind that there must be a clear line of sight between the sensor and the area to be covered Avoid pointing the switch directly in
6. to the hallway where it may detect passers by Mounting CAUTION Before installing or performing any service onan RSEN W 12 power must be turned off at the circuit breaker panel The RSEN W 12 can replace one switch in any standard single or double gang box It may be installed in the same manner as an ordinary wall switch Wire the RSEN W12 as described in the wiring section Ratings 120 VAC Ballast or Tungsten Maximum Load 800 Watts Minimum Load One ballast or one incandescent lamp 277 VAC Ballast only Maximum Load 1200 Watts Minimum Load One ballast Wiring CAUTION The RSEN W12 is designed for use with either 120 VAC or 277 VAC only Do not use with any other voltage Do not wire to control receptacle circuits Verify that the connected load does not exceed the RSEN W12 ratings Use twist on wire connectors for all connections All installations should be in compliance with the NEC and all state and local electrical codes The RSEN W 12 can be wired to control both an exhaust fan and lighting provided the total load does not exceed the maximum load rating in Amps for the automatic wall switch Sensor Coverage Y2 STEP WALK COVERAGE M OTION AT DESK COVERAGE SENSOR feet meters Sensor Location 10 x 15 OFFICE One Circuit One Lighting Load Connect one wire to the switchleg for the load Connect the other wire to the hot lead Connections are not pol
7. under the touchplate to verify the setting If set to Automatic ON mode the sensor may have been overridden by someone pressing the touchplate allow the RSEN W 12 to time out to verify normal operation If the lights do not turn on after pressing the touchplate confirm that no other switches or equipment are interrupt ing or bypassing power to the sensor or the load If lights still do not turn on replace the RSEN W 12 Lights Will Not Turn OFF If lights will not turn off after the set time delay and the LED has not lit during the time period press the touchplate to turn off the lights manually If lights turn off refer to items 5 and 6 under Checkout and Adjustment If lights do not turn off verify that the override jumper under the touchplate has not been removed Confirm that no other switches or equipment are interrupt ing or bypassing power to the RSEN W 12 or the load If lights still do not turn off replace the RSEN W 12 GE Lighting Controls 41 Woodford Ave Plainville CT 06062 Made in U S A