1.      If the SPD remains in an alarm condition once the electrician  is satisfied that the electrical system and its connections are  normal  the unit should be repaired     Atthis point consult the factory  having available the following  information       Unit identification number    refers to the model and serial  numbers detailed on the data label and is located on the front  of the enclosure      Installation  Operation and Maintenance Manual    Surge Protective Devices      Nature of problem    including status of all status indicators  and alarms      Servicing   The Liebert SH Series comes with a ten year parts and five  year labor warranty  see Warranty Information   For servicing  assistance  contact your local Liebert Sales Representative or  Emerson Network Power  Surge Protection at 800 288 6169  or 607 721 8840     ONLY QUALIFIED PERSONNEL SHOULD  MAINTENANCE ON THE SYSTEM     HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT  DURING NORMAL OPERATIONS     ELECTRICAL SAFETY PRE CAUTIONS MUST BE FOLLOWED  WHEN SERVICING THIS UNIT     TO PREVENT RISK OF ELECTRICAL SHOCK  TURN OFF AND  LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE  SERVICING UNIT     Corrective Maintenance   The Liebert SPD is designed for  years of trouble free operation  However  even the most  reliable equipment may fail under abnormal conditions   Diagnostic indicators are provided to indicate when the unit  needs repair or replacement  To ensure continuity of surge  protection  failed units should
2.    In the case of lightning whose potential is developed with  respect to the earth  the SPD diverts the surge current to  the grounding electrode  earth connection   However  for  most transient surges that are developed by switching loads   the SPD diverts the surge current back to its source without  involving the grounding electrode     Installation  Operation and Maintenance Manual    For proper SPD performance  the service entrance grounding  electrode system must comply with the NEC by having all  available electrodes  building steel  metal water pipe  driven  rods  concrete encased electrodes  etc   properly bonded  together and connected to the power system grounding    The use of a separate grounding electrode to ground the SPD  defeats the effectiveness of the SPD  is a potential safety hazard   may cause equipment damage  is an NEC violation  reference  NEC 250 51 and 250 54   and is not recommended     Neutral Connection    FOR PROPER AND SAFE  A CAUTION OPERATION  THE     SPD s  NEUTRAL  MUST BE RELIABLY  CONNECTED TO THE NEUTRAL OF THE SOURCE  FAILURE TO    PROVIDE A RELIABLE NEUTRAL CONNECTION MAY RESULT IN  FAILURE     Liebert SPDs SL 22075 Rev 0  9 2010    Liebert     Surge Protective Devices    INSTALLATION INSTRUCTIONS    The Liebert SH Series Hybrid Surge Protective Devices  SPDs   are high quality  high energy surge current diversion systems  designed to protect sensitive equipment from damaging  transient voltage surges  Proper installation is required 
3.  be repaired or replaced at the  earliest convenient service opportunity  When replacing surge  modules  other components should be inspected for damage  and replaced if necessary  Standard electrical troubleshooting  procedures should be used to isolate problems otherthan failed  surge current diverter modules  When replacing components   for continued proper operation and safety  replace only with  identically rated components  Please contact factory for  information on replacement parts     PERFORM    Preventative Maintenance  Inspection and Cleaning     Periodic system inspections  cleaning  and connection checks  are recommended to ensure reliable system performance and  continued surge transient protection     It is difficult to establish a schedule for preventative  maintenance since conditions vary from site to site  Inspections  for failed surge modules using available diagnostics should be  done routinely  weekly or monthly      Liebert SPDs SL 22075 Rev 0  9 2010    Liebert  Surge Protective Devices    Limited Warranty    This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser s business     General    Liebert Corporation products and systems are in our opinion the finest available  We take pride in our products and are pleased that you have chosen  them  Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship   Please read 
4.  if desired     Service Clearances    Service clearance is needed for units with  hinged doors on the front that are capable of being opened   Thirty six inches  36 in 914 mm  minimum is recommended     Mounting     Unit is intended to be wall mounted  Refer to  installation instructions for mounting dimensions and weight     Warnings Defined       Danger  Indicates an imminently  ADANGER hazardous situation that  if not  avoided  will result in death or  serious injury  This signal word  is to be limited to the most    extreme situations     Warning  Indicates a potentially  hazardous situation that  if not  avoided  could result in death or  serious injury        Caution  Indicates a potentially  hazardous situation that  if not  avoided  may result in minor or  moderate injury  It may also be used  to alert against unsafe practices     A CAUTION    Liebert SPDs SL 22075 Rev 0  9 2010    Liebert     Surge Protective Devices    ELECTRICAL CONNECTIONS    All electrical connections should be installed by a qualified   licensed  electrician only  All wiring must comply with the  National Electrical Code  NEC  and applicable local codes     VERIFY THAT ALL POWER CIRCUITS ARE  DE ENERGIZED AND LOCKED OUT BEFORE MAKING  ELECTRICAL CONNECTIONS     Voltage Ratings and Power Source Configurations      Before making connections to the unit  verify that the unit  model number and nameplate voltage rating are appropriate  for connection to the intended power source  See the chart  on pa
5.  verte RO Ride PbsstPs e CoU RGUF RUE TENERE ERUPRTEIDPRPQAPPUNU CIR eie rh 3  Voltage Protection Ratings 1i seeescsset E er iiine ne Ree EEEE EERE RE EE KESPDEEPEMPMIe E da ce PER 3  Circuit Ampacity LIMITATIONS    2 2 c rh naher eR EMME RET SG E E MERE EEOC eed CaaS EE RS 3  System  Groundingand Bondihlg      2 vs eere ap PrRR E RES E ERRA EEE EEREROHEREPOFNTOERER EN EU RR ROO Ies 3  Parallel Connections   eerie f E EE DD RS ER PIN EPITQU NU OEN T EE E V EN EN PII E Pea eee 5  Grounding Electrode  2  nter RENDER MERE UNUS DORMERREMIR DEN ES MEX EE Xx ICD EE EE 5  Neutral Connections sersan e RAPI pUPREP D e Re RF P PRE EE ER UTR AR RPG PROEUP CUP RE aee 5  INSTALLATION INSTRUCTIONS  Product Installation sth y eesu ete Sp RRSPEPEN ROPOETRU Y P rPUT UNE BUM eT E EEEE eve qa gl E 6  Dimensional Information  Chart      nc preIt p cow Sees ea sen robe sea  UPrenespPrE S E vir O RARER INNA Ts Na NE 6  Suggested Breaker and Wire Size  Cliart  1 5 5    ore ce cease eoe t hune ee rur E RE E Y eh er X EE FE Erbe 7  MONITORING FEATURES  External Status Indicators  Standard         2 prre Re ERE ER ened dod p n E A EERE EERE MUEVE TERETE ERRES 8  AudibleAlarri Starndatrd     sri ecitr t Ex eU PTRNUC ta  OOIARGNE Rua bi  ur d px RS dda ama m EetrCee n HE ene e 8  Summary Alarm Contact  Standard    ss cvcscsecaeii wed E TPTUOME ER Ya LINE FEL POR VR EE ARR PEDIR HER PETEE 8  Transient Counter  Optlorial              o I Rer knee ex IS XEXPET ROG EODERSONERPERKPPAN QN RES CURE EREE E Fae 
6. 10 Emerson Electric Co     
7. 14 841 6022 FAX    Via Leonardo Da Vinci 8  Zona Industriale Tognana  35028 Piove Di Sacco  PD   Italy   39 049 9719 111 Phone  39 049 5841 257 FAX    Emerson Network Power Asia Pacific  7 F   Dah Sing Financial Centre   108 Gloucester Road  Wanchai  Hong Kong   852 25722201 Phone   852 28029250 FAX    Liebert com    Technical Support  607 721 8840 Phone  607 722 8713 FAX   800 288 6169 Toll Free    While every precaution has been taken to ensure the accuracy and  completeness of this literature  Liebert Corporation assumes no  responsibility and disclaims all liability for damages resulting from use  ofthis information or for any errors or omissions        2010 Liebert Corporation All rights reserved throughout the world   Specifications subject to change without notice        Liebert and the Liebert logo are registered trademarks of Liebert  Corporation  All names referred to are trademarks or registered  trademarks of their respective owners     SL 22075  9 10  Rev  0 Printed in USA    Emerson Network Power     The global leader in enabling Business Critical Continuity   Emerson Network Power com  E AC Power E Embedded Computing Bl Outside Plant li Racks and Integrated Cabinets  Bl Connectivity E Embedded Power Bl Power Switching  amp  Controls Bl Services   E DC Power Bi Monitoring li Precision Cooling ll Surge Protection    Emerson Network Power  the Emerson Network Power logo and Business Critical Continuity are trademarks and service marks of Emerson Electric Co     20
8. 8  Swell Counter  Optional   25  rere ROI FUE ved cu ERWIN RERUM MERI NU D RM Kd Te eL RO RF EAEE 8    TROUBLESHOOTING SERVICING MAINTENANCE    Tro  bleshootilig sea 59 yet Ehre TER EEXM PERI E decd des UEEMESES QN OD E RREE KIEL De QOEM T E M 8  SEMVICING pL 8  Corrective Malntenamnce    ucceeeer rk EY EFE Ga CNN UEERRR ow eee ca aes eee SR aN ANE  ER ETE CN esau 8  Preventative Maintenance sueco etre RR ER raw oid Re de e RO REUS NARI  ROG EE eee ARO e e Res 8  WARRANTY INFORMATION   TO Year Warranby       222xe rer m RR ESRRRODeE OR eA OR AEN ER RI RR X DIO MEER KI CURE TIR PE hors ae Fas 9    Installation  Operation and Maintenance Manual 1 Liebert SPDs SL 22075 Rev 0  9 2010    Liebert     UNPACKING AND INSTALLATION  Unpacking and Preliminary Inspection  1  Inspect the shipping crate s  for damage or signs of  mishandling before unpacking the unit     2 Remove any securing bands and cardboard packing and  inspect the unit for any obvious shipping damages     3  Ifany damageasaresult of shipping is observed  immediately  file a claim with the shipping agency and forward a copy to  your local Liebert Sales Representative     Handling Considerations   Larger units are bolted to a shipping pallet to facilitate handling  by forklift or pallet jack  Check the size and weight  Refer to  the cabinet data furnished with the unit     Storage   The unit should be stored in a clean  dry environment   Storage temperature range is  55  C   67  F  to  85  C    185  F   Care should be t
9. E Surge Protection  For Business Critical Continuity     Liebert SH Series Surge Protection    Installation  Operation and Maintenance Manual                Liebert  EMERSON     Liebert  Surge Protective Devices    LIEBERT SURGE PROTECTIVE DEVICE  INSTALLATION  OPERATION AND MAINTENANCE MANUAL    TABLE OF CONTENTS  UNPACKING AND INSTALLATION  U  packing and Preliminary Inspectioli sarres ranem er RR RO RR hb DUCERE ERNRRRIRFRNE A E C ERER CR EN ER bes 2  Handling Considerations  areco onin EU Ur se OLCHDUI OP PUOI deese sng S PEU M REP EEEE De der reese 2  Slordig Ci ci st die oes tube pias e gud Cab ED  aehed ahs eyed dale era pee ent Kin NEN OE EDD Mehdi e Maegan aes ME 2  LOCATION CONSIDERATIONS  EnvIFODITIeliEsoi S4 Fez Rae e Eque xx EE EPI cepe bea id aeq p duda odo M eee tede DUE M Rd pea 2  Fs                                                     H   2  Service clearances uid ose nae per vn oett e ae wes edere idco Up PEU e Teatre d EU NE 2  forte E PNEPCCRL              E 2  Warnings Defined PC                    2  ELECTRICAL CONNECTIONS  Voltage Ratings and Power Source Configurations          0 0 cece cece cece cece eee eee he emere 3  Voltage Ratings and Power Source Configurations  Chart             sesesesssssesssessee e meme 4  Wire Connections cuius zu prx emensus EA EEA Reha eod eE dup QE RR Rar quete Feb DOE dear Nu das dame eke E 3  Over CUMENUPTOLECHON s   usse emt EE RR Eur ODE ER RENE EQ REL CPP RE RERO E C ED ERE NES 3  NEC Colslderatiolis    ccs rune rei
10. ED  LED is illuminated  check to ensure that power is applied to  the SPD  If an abnormal indication is present  remove power to  the SPD and contact Liebert Emerson Network Power Surge  Protection at 1 800 288 6169 or 1 607 721 8840     7  Periodically monitor the status of the LEDs  Reduced  protection exists if the GREEN LEDs are extinguished or the  RED LED is illuminated  Please contact Liebert Emerson  Network Power Surge Protection at 1 800 288 6169 or  1 607 721 8840     8  The protection modules in these SPDs may be replaceable   contact Liebert Emerson Network Power Surge Protection for  replacement     A CAUTION    If the SPD model is a Wye configured unit  4W G   and  a Neutral connection is not available  please contact  factory     SUGGESTED BREAKER AND WIRE SIZE    Allowable Range    Circuit Breaker Size     suos   SACO     suo   Aa      15A  175A       Installation  Operation and Maintenance Manual    Connection Wire Size Circuit Breaker  WR Disconnect Size   8  1 0 AWG  58  VOAWG   414 2 0 AWG   8  1 0 AWG   8   1 0 AWG         Factory Suggested Size    Connection  Wire Size   6 AWG   4 AWG   4 AWG   2 AWG    Liebert SPDs SL 22075 Rev 0  9 2010    Liebert     MONITORING FEATURES    External Status Indicators  Standard      These indicators  provide a summary of the status of the surge SPD module   For normal conditions  the green  OK  LED is illuminated and  the red  Service  LED is extinguished  If the surge SPD module  requires replacement  the green  OK  L
11. ED is turned off and  the red  Service  LED illuminated     Audible Alarm  Standard      If the surge SPD module requires  replacement  an audible alarm is activated to draw attention  to the fact that repair service is required to restore the system  to normal operation  An audible alarm disable is provided to  silence the alarm  The system will automatically reset itself  after repair  The audible alarm switch and  Service  LED can be  tested by activating the  Test  switch on the system monitor  panel     Summary Alarm Contact  Standard      Two sets of summary  alarm Form C relay contacts  2 N O  and 2 N C   are provided  forremote indication ofthe failed surge SPD module  Contacts  are rated 5 amps at 250 VAC maximum with a power factor of  1 0  Access to the contacts is provided via contact terminals  located on the printed circuit board mounted on the inside of  the unit s cover     Surge Counter  Optional    The surge counter is provided for  transient voltage surge monitoring  The counter totalizes line  surges monitored since the last time the counter was reset   The circuit counts all surges that deviate from the line sine  wave  The factory setting is 30  over nominal line voltage   Other settings include 50   70   and 100      TROUBLESHOOTING  SERVICING   MAINTENANCE    Troubleshooting   If status failure indication occurs or summary alarm contacts  has changed states  a qualified electrician shall first determine  if the systems voltage and proper phasing exists
12. FAULT CONDITIONS   DURING THESE FAULT CONDITIONS ANY ELECTRICAL  EQUIPMENT  INCLUDING AN SPD  MAY BE SUBJECTED TO  VOLTAGES WHICH EXCEED THEIR DESIGNED RATINGS  THIS  INFORMATION IS BEING PROVIDED TO THE USER SO THAT  AN INFORMED DECISION CAN BE MADE BEFORE INSTALLING  ANY ELECTRICAL EQUIPMENT ON AN UNGROUNDED  POWER SYSTEM  CONTACT FACTORY FOR UNGROUNDED  APPLICATIONS     Aninsulated grounding conductor is required in addition to any  metallic raceway  which may be used as a grounding conductor   For parallel connected SPDs  the grounding conductor should  be the same wire size as the associated power conductors     continued on page 5     Liebert SPDs SL 22075 Rev 0  9 2010    Liebert     VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS       Source Configurations    Nominal Operating Voltage       L N    L G    Maximum Continuous Model Voltage Code  Operating Voltage  Found in part number        Single Phase L N  2 W   G  L    Single Phase L L  2 W   G  L1    L2  G    Single Phase  3 W  G    Three Phase Delta  3 W   G    e    120       230                   240    240       380 415    380 415       480    480       Three Phase Wye  4W  G         Three Phase Wye  3 W   G No Neutral    A  B  c  G       220 240    220 240    380 415          220 240    380 415          Installation  Operation and Maintenance Manual                   Liebert SPDs SL 22075 Rev 0  9 2010    Note 1  For other voltages or source configurations  consult factory     Liebert     Surge Protective Devic
13. HETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT  NEGLIGENCE  STRICT LIABILITY   TORT OR OTHERWISE     Miscellaneous     e NO SALESPERSON  EMPLOYEE OR AGENT OF LIEBERT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS  WARRANTY  Warranty terms may be modified  if at all  only in a writing signed by a Liebert officer     e Liebert obligations under this warranty are conditioned upon Liebert timely receipt of full payment of the product purchase price and any  other amounts due  Liebert reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to  User or others       In the event that any provision of this Warranty should be or becomes invalid and or unenforceable during the warranty period  the  remaining terms and provisions shall continue in full force and effect       This Warranty shall be governed by  and construed under  the laws of the State of Ohio  without reference to the conflict of laws principles  thereof     e This Warranty represents the entire agreement between Liebert and User with respect to he subject matter herein and supersedes all prior or  contemporaneous oral or written communications  representations  understandings or agreements relating tothis subject     Installation  Operation and Maintenance Manual 10 Liebert SPDs SL 22075 Rev 0  9 2010    Liebert Corporation    1050 Dearborn Drive   P O  Box 29186   Columbus  OH 43229   800 877 9222 Phone    US  amp  Canada Only    614 888 0246  Outside U S    6
14. aken to avoid condensation  All  packing and shipping materials should be left intact until  the unit is ready for final installation  If the unit has been  stored for an extended period of time  the unit should be  cleaned and carefully inspected before placing into service     Installation  Operation and Maintenance Manual    Surge Protective Devices    LOCATION CONSIDERATIONS    For optimum transient surge protection  coordinated surge  suppression should be applied at the service entrance and all  other electrical connections to the building  telephone  CATV   etc    at known surge generating loads within the building   large motors  arc welders  switched capacitors  etc    as well  as at sensitive electronic loads  such as computers  electronic  appliances  solid state motor drives  etc    For interconnected  electronicloads  suchas by way of data cabling   transient surge  suppression should also be applied to the interconnecting  wiring  data cables      Environment     Unit is designed for operation indoors in  ambient temperatures of  40  C   40  F  to  60  C   140  F  with  a relative humidity of 0  to 95   non condensing      The unit is provided in an industrial use enclosure  which is  dust tight and drip tight and should not be installed in areas  with excessive dust  corrosive vapors  flammable materials or  explosive atmospheres     Audible Noise     The audible noise of the unit is less than  40 dB at 5 feet  which allows its placement within almost any  room
15. assumes NO RESPONSIBILITY for any  matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components        Drawings  Descriptions    Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the certified drawings  if any   applicable thereto  to Liebert   s final invoices  and to applicable Liebert product brochures and manuals current as of the date of product shipment      Descriptions      Liebert does not control the installation and use of any Liebert product  Accordingly  it is understood that the Descriptions are  NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE     Obtaining Performance Under This Warranty    Within a reasonable time  but in no case to exceed thirty  30  days  after User   s discovery of a defect  User shall contact Liebert at 1 800 LIEBERT   543 2378  and request a return authorization number  User shall ship the product  with proof of purchase  to Liebert freight prepaid  Liebert  products shipped to Liebert without a return authorization number will be refused and returned freight collect to User at User   s expense  Liebert  products shipped by User to Liebert which have incurred freight damage due to User   s improper packaging of the product will not be covered by  his Warranty and any repairs or replacement parts  components or products needed will be invoiced in the full current p
16. es    PARALLEL CONNECTIONS    Typical Parallel Connections   without Internal Rotary Disconnect                                                                          e z  3 gp 2  5   E   a 8 g     i i  M i  IN Protected  Loads     4 Neutral  Liebert  Surge     t  gt  Phase s  Protective  Device    Transient  Protected Safety  Panel Wire should be Seoul  less than 5 feet  and straight  as possible          Typical Parallel Connections   with Internal Rotary Disconnect           o  9 3 8  POP  a ww NE     0        LA To    Protected  Loads                                                                         t Neutral  Liebert  Rotary Surge    Disconnect Phase s  Protentive  evice  Transient  j Ground  Protected cem  Panel Wire should be Ground  less than 5 feet  and straight  as possible          ELECTRICAL CONNECTIONS  continued from page 3     Grounding conductors must be routed with the associated  power conductors in the same raceway  conduit   When  metallic raceways are used  adequate electrical continuity  must be maintained at all raceway connections  particularly  raceway terminations to the electrical enclosures     The use of isolating bushings or other means to interrupt  a metallic conduit run is a potential safety hazard and is not  recommended     Grounding Electrode     Surge protective devices do not  discharge all surges to ground  earth   Surge protective  devices can also divert the surge current back to its source to  complete the electrical circuit  
17. for  maximum system performance     The installer should perform the following steps to assure a  quality installation  The entire installation manual should be  read before starting installation  These instructions do not  replace national or local electrical codes  Check applicable  electrical codesto ensure compliance  Installation ofthe Liebert  SPD system should only be performed by qualified personnel     1  Insure that all power is removed before beginning  installation  A qualified licensed electrician shall install all  electrical connections     Summary Alarm Contacts  X2     in 1   Normally Open  in 2   Common    in 3   Normally Closed       Liebert SH Series  Without Disconnect     Weight   Ibs     Dimensions  Inches     Model  2 RIAs aes     sHo25   16   16   8  17 25  9 5  0 44  35     sH032   16   16   8  1725  10  0 44  49     suo40   16   16   8  17 25  10  0 44  49     suoz5  20   20   8  2125  14  O44  85         Installation  Operation and Maintenance Manual     7     SESTERCE SCR E EG   sH025  20   16   8  21 25  10  0 44  45    SH032  20   36   8 2125   10     58    sHo40  20   16   8    SH075   20   24   8  21 25    2  The SPD is provided in NEMA 4 enclosures which are suitable  for use in indoor or outdoor installations     3  Determine where the SPD is to be mounted  allowing for  minimum length of wire between itself and the input power  terminals of the service panel  Punch or cut the proper hole  size in the side of the SPD closest to the knockout 
18. ge 4 for voltage rating applications with typical power    source configurations   A CAUTION    Wire Connections     With parallel connection  the size of the  wiring to the SPD unit is independent of the protected circuit s  ampacity  NEC Article 285 21 B  requires surge suppressor  connecting conductors to be at least  14 copper or  12  aluminum  To reduce the wiring impedance to surge currents   it is recommended that the phase  neutral  if required    and ground conductors are twisted together and routed in  the same raceway  conduit   Avoid any sharp bends in the  conductors     Overcurrent Protection     The SPD unit conducts practically  no current under normal operation and only conducts very  short duration transient surge currents   NEC Considerations     The following is from the National  Electric Code 2008 Edition   NEC 285 21 Connections  NEC 285 23 Type 1 SPDs  Shall be installed in accordance with  285 35 A  and  B     A  Installation  Type 1 SPDs shall be installed as follows    1  Type 1 SPDs shall be permitted to be connected to  the supply side of the service disconnect as permitted in  230 82 4  or   2  Type 1 SPDs shall be permitted to be connected in  Type 2 locations as specified in 285 24    B  At the service  When installed at the services  the  grounding conductor of a Type 1 SPD shall be connected to  one of the following     Installation  Operation and Maintenance Manual     1  Grounded service conductor    2  Grounded electrode conductor    3  Gr
19. ounding electrode for service    4 Equipment grounding terminal in the service equipment    Voltage Protection Ratings     To obtain the voltage  protection ratings  VPRs   as obtained by Underwriters  Laboratory  Incorporated  in accordance with the Standard  for Safety  Surge Protective Devices  SPDs   Standard 1449  Third  Edition  released  2009   marked on this product  the wire size  listed for each product must be utilized to connect the unit to  your facilities  power grid  Connections made with conductors  other than the wire size listed may result in different VPRs     Circuit Ampacity Limitations     Representative samples  of these products have been investigated by Underwriters  Laboratories  Incorporated to withstand  without exposing  live circuits or components at system voltages and fault  currents up to 200 000 AIC  as described in the Standard for  Safety  Surge Protective Devices  SPDs   Standard 1449  Third  Edition  released  2009      System Grounding and Bonding     The performance and  safety of any SPD system is dependent on proper grounding  and bonding  Grounding is required for safety  Correct  implementation also enhances equipment performance   Incorrect grounding can reduce or impede the SPD s  operation     All electrical circuits to the SPD must include an aaa  grounding conductor    A CAUTION oe by the NEC and local    UNGROUNDED POWER SYSTEMS ARE INHERENTLY  UNSTABLE AND CAN PRODUCE EXCESSIVELY HIGH LINE TO   GROUND VOLTAGES DURING CERTAIN 
20. rice amount and returned  reight collect to User           Subject to the limitations specified herein  Liebert will repair or replace  at its option  without charge for Liebert labor or materials  subsequent  o its inspection F O B  Liebert s facility  the Liebert product warranted hereunder which does not conform to the Warranty  Replacement parts   components or products shipped to User prior to Liebert   s receipt and inspection of the product claimed to be defective shall be invoiced in the  ull current price amount and shipped freight collect F O B  Liebert   s facility  Warranty coverage will be extended only after Liebert s receipt of  he claimed defective product within thirty  30  days of shipment of any replacement parts  components or products  if applicable  and only if  Liebert s inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of  his Warranty  All defective products and component parts replaced under this Warranty become the property of Liebert           Warranty Performance of Component Manufacturers    It is Liebert s practice  consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible  to cooperate  with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects  in the product components  Accordingly  Liebert may utilize third parties in the performance of Wa
21. rranty work  including repair or replacement  hereunder  where  in Liebert   s opinion  such work can be performed in less time  with less expense  or in closer proximity to the Liebert product     Installation  Operation and Maintenance Manual 9 Liebert SPDs SL 22075 Rev 0  9 2010    Liebe rt  Surge Protective Devices    Items Not Covered By Warranty     THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse  improper application  wrong or inadequate electrical  current or connection  negligence  inappropriate on site operating conditions  corrosive atmosphere  repair by non Liebert designated personnel   accident in transit  tampering  alterations  a change in location or operating use  exposure to the elements  Acts of God  theft or installation  contrary to Liebert s recommendations or specifications  or in any event if the Liebert serial number has been altered  defaced or removed   Notwithstanding the foregoing  the following Acts of God are covered  lightning induced surges  which are transients  spikes or other sub cycle   discontinuous events impinging on normally applied voltage as defined by reference data in the latest version of IEEE C62 41 and the Liebert  product performance specifications        THIS WARRANTY DOES NOT COVER shipping costs  installation costs  circuit breaker resetting or maintenance or service items and further   except as provided herein  does NOT include labor costs or transportation charges arising from the replacement of the Lieber
22. t product or any part  thereof or charges to remove a reinstall same at any premises of the User     THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Liebert product in combination with any electrical  or electronic components  circuits  systems  assemblies  or other materials not furnished by Liebert  Liebert does NOT warrant the suitability for  use or the results ofthe Liebert product in combination with the products of others     THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT DESIGNED FOR USE IN THE FOLLOWING APPLICATIONS   i  ANY  NUCLEAR OR RELATED APPLICATIONS  AND  ii  LIFE SUPPORT AND PATIENT CONNECTED AND APPLIED MEDICAL AND  DENTAL APPLICATIONS     REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY  PERIOD     Limitations     e THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES  EXPRESS OR IMPLIED  INCLUDING  MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE     e USER S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIEBERT PRODUCT AS SET FORTH  HEREIN     e IF USER S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION   LIEBERT S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE  PRICE     e   IN NO EVENT SHALL LIEBERT ASSUME ANY LIABILITY FOR INDIRECT  SPECIAL  INCIDENTAL  OR CONSEQUENTIAL  DAMAGES OF ANY KIND WHATSOEVER  INCLUDING WITHOUT LIMITATION  LOST PROFITS  BUSINESS INTERRUPTION  OR LOSS OF DATA  W
23. to be  utilized in the service panel  Drill mounting holes in wall at  location picked for SPD next to service panel using mounting  dimensions shown in the table below  Mount surge suppressor  to wall using 3 8  mounting hardware      continued on page 7     Dimensional Information  Liebert SH Series             ge  Service Panel for ase  Loads to be Protected Phase L3 C    Disconnect Main  Breaker for  Panel    Dedicated Neutral Buss    Disconnect     Optional  Ground Buss    Recommended Wire  Entrance    Liebert SH Series  With Disconnect     Dimensions  Inches  Weight     Ibs      044    21 25    Liebert SPDs SL 22075 Rev 0  9 2010    Liebert     Surge Protective Devices    INSTALLATION INSTRUCTIONS  continued from page 6     4  Connect black wires  line or phase  marked L1 A  L2 B or  L3 C  the white wire  neutral  marked N  and the green wire   ground  marked G  of the SPD using the wire range listed  below  To yield the best performance of the SPD within the  electrical distribution system  keep all conductors as short as  possible and avoid sharp bends     5  Connection to the unit s summary alarm contacts shall be  with  18     22 AWG  The ratings of the Form  C  contacts are  5 amps at 250 VAC maximum with a power factor of 1 0  For  additional information  see  Monitoring  section     6  Apply power  The surge protector is fully operational when  the GREEN LEDs onthe modules and the front door of enclosure  are illuminated  If the GREEN LEDs are extinguished or a R
24. your Warranty carefully  This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain  performance under this Warranty     TEN YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP    LIEBERT PRODUCTS COVERED   Liebert SH Series  Interceptor      Terms of Warranty    As provided herein  the Liebert product is warranted to be free of defects in material and workmanship for a period of ten  10  years from the date  of product shipment from Liebert  The shipment date will be determined only from the Liebert bill of lading  If any part or portion of the Liebert  product fails to conform to the warranty within the warranty period  Liebert  at its option  will furnish new or factory remanufactured parts for  repair or replacement of that part or portion           Warranty Extends to First Purchaser for Use  Non transferable    This Warranty is extended to the first person  firm  association or corporation for whom the Liebert product specified herein is originally installed  for use  the    User     in the fifty United States  excluding territories  or Canada  This Warranty is not transferable or assignable without the prior  written permission of Liebert        Assignment of Warranties    Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of the Liebert product and which are  assignable  but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties  
    