1. If the SPD remains in an alarm condition once the electrician is satisfied that the electrical system and its connections are normal the unit should be repaired Atthis point consult the factory having available the following information Unit identification number refers to the model and serial numbers detailed on the data label and is located on the front of the enclosure Installation Operation and Maintenance Manual Surge Protective Devices Nature of problem including status of all status indicators and alarms Servicing The Liebert SH Series comes with a ten year parts and five year labor warranty see Warranty Information For servicing assistance contact your local Liebert Sales Representative or Emerson Network Power Surge Protection at 800 288 6169 or 607 721 8840 ONLY QUALIFIED PERSONNEL SHOULD MAINTENANCE ON THE SYSTEM HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT DURING NORMAL OPERATIONS ELECTRICAL SAFETY PRE CAUTIONS MUST BE FOLLOWED WHEN SERVICING THIS UNIT TO PREVENT RISK OF ELECTRICAL SHOCK TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE SERVICING UNIT Corrective Maintenance The Liebert SPD is designed for years of trouble free operation However even the most reliable equipment may fail under abnormal conditions Diagnostic indicators are provided to indicate when the unit needs repair or replacement To ensure continuity of surge protection failed units should
2. In the case of lightning whose potential is developed with respect to the earth the SPD diverts the surge current to the grounding electrode earth connection However for most transient surges that are developed by switching loads the SPD diverts the surge current back to its source without involving the grounding electrode Installation Operation and Maintenance Manual For proper SPD performance the service entrance grounding electrode system must comply with the NEC by having all available electrodes building steel metal water pipe driven rods concrete encased electrodes etc properly bonded together and connected to the power system grounding The use of a separate grounding electrode to ground the SPD defeats the effectiveness of the SPD is a potential safety hazard may cause equipment damage is an NEC violation reference NEC 250 51 and 250 54 and is not recommended Neutral Connection FOR PROPER AND SAFE A CAUTION OPERATION THE SPD s NEUTRAL MUST BE RELIABLY CONNECTED TO THE NEUTRAL OF THE SOURCE FAILURE TO PROVIDE A RELIABLE NEUTRAL CONNECTION MAY RESULT IN FAILURE Liebert SPDs SL 22075 Rev 0 9 2010 Liebert Surge Protective Devices INSTALLATION INSTRUCTIONS The Liebert SH Series Hybrid Surge Protective Devices SPDs are high quality high energy surge current diversion systems designed to protect sensitive equipment from damaging transient voltage surges Proper installation is required
3. be repaired or replaced at the earliest convenient service opportunity When replacing surge modules other components should be inspected for damage and replaced if necessary Standard electrical troubleshooting procedures should be used to isolate problems otherthan failed surge current diverter modules When replacing components for continued proper operation and safety replace only with identically rated components Please contact factory for information on replacement parts PERFORM Preventative Maintenance Inspection and Cleaning Periodic system inspections cleaning and connection checks are recommended to ensure reliable system performance and continued surge transient protection It is difficult to establish a schedule for preventative maintenance since conditions vary from site to site Inspections for failed surge modules using available diagnostics should be done routinely weekly or monthly Liebert SPDs SL 22075 Rev 0 9 2010 Liebert Surge Protective Devices Limited Warranty This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser s business General Liebert Corporation products and systems are in our opinion the finest available We take pride in our products and are pleased that you have chosen them Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship Please read
4. if desired Service Clearances Service clearance is needed for units with hinged doors on the front that are capable of being opened Thirty six inches 36 in 914 mm minimum is recommended Mounting Unit is intended to be wall mounted Refer to installation instructions for mounting dimensions and weight Warnings Defined Danger Indicates an imminently ADANGER hazardous situation that if not avoided will result in death or serious injury This signal word is to be limited to the most extreme situations Warning Indicates a potentially hazardous situation that if not avoided could result in death or serious injury Caution Indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices A CAUTION Liebert SPDs SL 22075 Rev 0 9 2010 Liebert Surge Protective Devices ELECTRICAL CONNECTIONS All electrical connections should be installed by a qualified licensed electrician only All wiring must comply with the National Electrical Code NEC and applicable local codes VERIFY THAT ALL POWER CIRCUITS ARE DE ENERGIZED AND LOCKED OUT BEFORE MAKING ELECTRICAL CONNECTIONS Voltage Ratings and Power Source Configurations Before making connections to the unit verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source See the chart on pa
5. verte RO Ride PbsstPs e CoU RGUF RUE TENERE ERUPRTEIDPRPQAPPUNU CIR eie rh 3 Voltage Protection Ratings 1i seeescsset E er iiine ne Ree EEEE EERE RE EE KESPDEEPEMPMIe E da ce PER 3 Circuit Ampacity LIMITATIONS 2 2 c rh naher eR EMME RET SG E E MERE EEOC eed CaaS EE RS 3 System Groundingand Bondihlg 2 vs eere ap PrRR E RES E ERRA EEE EEREROHEREPOFNTOERER EN EU RR ROO Ies 3 Parallel Connections eerie f E EE DD RS ER PIN EPITQU NU OEN T EE E V EN EN PII E Pea eee 5 Grounding Electrode 2 nter RENDER MERE UNUS DORMERREMIR DEN ES MEX EE Xx ICD EE EE 5 Neutral Connections sersan e RAPI pUPREP D e Re RF P PRE EE ER UTR AR RPG PROEUP CUP RE aee 5 INSTALLATION INSTRUCTIONS Product Installation sth y eesu ete Sp RRSPEPEN ROPOETRU Y P rPUT UNE BUM eT E EEEE eve qa gl E 6 Dimensional Information Chart nc preIt p cow Sees ea sen robe sea UPrenespPrE S E vir O RARER INNA Ts Na NE 6 Suggested Breaker and Wire Size Cliart 1 5 5 ore ce cease eoe t hune ee rur E RE E Y eh er X EE FE Erbe 7 MONITORING FEATURES External Status Indicators Standard 2 prre Re ERE ER ened dod p n E A EERE EERE MUEVE TERETE ERRES 8 AudibleAlarri Starndatrd sri ecitr t Ex eU PTRNUC ta OOIARGNE Rua bi ur d px RS dda ama m EetrCee n HE ene e 8 Summary Alarm Contact Standard ss cvcscsecaeii wed E TPTUOME ER Ya LINE FEL POR VR EE ARR PEDIR HER PETEE 8 Transient Counter Optlorial o I Rer knee ex IS XEXPET ROG EODERSONERPERKPPAN QN RES CURE EREE E Fae
6. 10 Emerson Electric Co
7. 14 841 6022 FAX Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco PD Italy 39 049 9719 111 Phone 39 049 5841 257 FAX Emerson Network Power Asia Pacific 7 F Dah Sing Financial Centre 108 Gloucester Road Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX Liebert com Technical Support 607 721 8840 Phone 607 722 8713 FAX 800 288 6169 Toll Free While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use ofthis information or for any errors or omissions 2010 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SL 22075 9 10 Rev 0 Printed in USA Emerson Network Power The global leader in enabling Business Critical Continuity Emerson Network Power com E AC Power E Embedded Computing Bl Outside Plant li Racks and Integrated Cabinets Bl Connectivity E Embedded Power Bl Power Switching amp Controls Bl Services E DC Power Bi Monitoring li Precision Cooling ll Surge Protection Emerson Network Power the Emerson Network Power logo and Business Critical Continuity are trademarks and service marks of Emerson Electric Co 20
8. 8 Swell Counter Optional 25 rere ROI FUE ved cu ERWIN RERUM MERI NU D RM Kd Te eL RO RF EAEE 8 TROUBLESHOOTING SERVICING MAINTENANCE Tro bleshootilig sea 59 yet Ehre TER EEXM PERI E decd des UEEMESES QN OD E RREE KIEL De QOEM T E M 8 SEMVICING pL 8 Corrective Malntenamnce ucceeeer rk EY EFE Ga CNN UEERRR ow eee ca aes eee SR aN ANE ER ETE CN esau 8 Preventative Maintenance sueco etre RR ER raw oid Re de e RO REUS NARI ROG EE eee ARO e e Res 8 WARRANTY INFORMATION TO Year Warranby 222xe rer m RR ESRRRODeE OR eA OR AEN ER RI RR X DIO MEER KI CURE TIR PE hors ae Fas 9 Installation Operation and Maintenance Manual 1 Liebert SPDs SL 22075 Rev 0 9 2010 Liebert UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection 1 Inspect the shipping crate s for damage or signs of mishandling before unpacking the unit 2 Remove any securing bands and cardboard packing and inspect the unit for any obvious shipping damages 3 Ifany damageasaresult of shipping is observed immediately file a claim with the shipping agency and forward a copy to your local Liebert Sales Representative Handling Considerations Larger units are bolted to a shipping pallet to facilitate handling by forklift or pallet jack Check the size and weight Refer to the cabinet data furnished with the unit Storage The unit should be stored in a clean dry environment Storage temperature range is 55 C 67 F to 85 C 185 F Care should be t
9. E Surge Protection For Business Critical Continuity Liebert SH Series Surge Protection Installation Operation and Maintenance Manual Liebert EMERSON Liebert Surge Protective Devices LIEBERT SURGE PROTECTIVE DEVICE INSTALLATION OPERATION AND MAINTENANCE MANUAL TABLE OF CONTENTS UNPACKING AND INSTALLATION U packing and Preliminary Inspectioli sarres ranem er RR RO RR hb DUCERE ERNRRRIRFRNE A E C ERER CR EN ER bes 2 Handling Considerations areco onin EU Ur se OLCHDUI OP PUOI deese sng S PEU M REP EEEE De der reese 2 Slordig Ci ci st die oes tube pias e gud Cab ED aehed ahs eyed dale era pee ent Kin NEN OE EDD Mehdi e Maegan aes ME 2 LOCATION CONSIDERATIONS EnvIFODITIeliEsoi S4 Fez Rae e Eque xx EE EPI cepe bea id aeq p duda odo M eee tede DUE M Rd pea 2 Fs H 2 Service clearances uid ose nae per vn oett e ae wes edere idco Up PEU e Teatre d EU NE 2 forte E PNEPCCRL E 2 Warnings Defined PC 2 ELECTRICAL CONNECTIONS Voltage Ratings and Power Source Configurations 0 0 cece cece cece cece eee eee he emere 3 Voltage Ratings and Power Source Configurations Chart sesesesssssesssessee e meme 4 Wire Connections cuius zu prx emensus EA EEA Reha eod eE dup QE RR Rar quete Feb DOE dear Nu das dame eke E 3 Over CUMENUPTOLECHON s usse emt EE RR Eur ODE ER RENE EQ REL CPP RE RERO E C ED ERE NES 3 NEC Colslderatiolis ccs rune rei
10. ED LED is illuminated check to ensure that power is applied to the SPD If an abnormal indication is present remove power to the SPD and contact Liebert Emerson Network Power Surge Protection at 1 800 288 6169 or 1 607 721 8840 7 Periodically monitor the status of the LEDs Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is illuminated Please contact Liebert Emerson Network Power Surge Protection at 1 800 288 6169 or 1 607 721 8840 8 The protection modules in these SPDs may be replaceable contact Liebert Emerson Network Power Surge Protection for replacement A CAUTION If the SPD model is a Wye configured unit 4W G and a Neutral connection is not available please contact factory SUGGESTED BREAKER AND WIRE SIZE Allowable Range Circuit Breaker Size suos SACO suo Aa 15A 175A Installation Operation and Maintenance Manual Connection Wire Size Circuit Breaker WR Disconnect Size 8 1 0 AWG 58 VOAWG 414 2 0 AWG 8 1 0 AWG 8 1 0 AWG Factory Suggested Size Connection Wire Size 6 AWG 4 AWG 4 AWG 2 AWG Liebert SPDs SL 22075 Rev 0 9 2010 Liebert MONITORING FEATURES External Status Indicators Standard These indicators provide a summary of the status of the surge SPD module For normal conditions the green OK LED is illuminated and the red Service LED is extinguished If the surge SPD module requires replacement the green OK L
11. ED is turned off and the red Service LED illuminated Audible Alarm Standard If the surge SPD module requires replacement an audible alarm is activated to draw attention to the fact that repair service is required to restore the system to normal operation An audible alarm disable is provided to silence the alarm The system will automatically reset itself after repair The audible alarm switch and Service LED can be tested by activating the Test switch on the system monitor panel Summary Alarm Contact Standard Two sets of summary alarm Form C relay contacts 2 N O and 2 N C are provided forremote indication ofthe failed surge SPD module Contacts are rated 5 amps at 250 VAC maximum with a power factor of 1 0 Access to the contacts is provided via contact terminals located on the printed circuit board mounted on the inside of the unit s cover Surge Counter Optional The surge counter is provided for transient voltage surge monitoring The counter totalizes line surges monitored since the last time the counter was reset The circuit counts all surges that deviate from the line sine wave The factory setting is 30 over nominal line voltage Other settings include 50 70 and 100 TROUBLESHOOTING SERVICING MAINTENANCE Troubleshooting If status failure indication occurs or summary alarm contacts has changed states a qualified electrician shall first determine if the systems voltage and proper phasing exists
12. FAULT CONDITIONS DURING THESE FAULT CONDITIONS ANY ELECTRICAL EQUIPMENT INCLUDING AN SPD MAY BE SUBJECTED TO VOLTAGES WHICH EXCEED THEIR DESIGNED RATINGS THIS INFORMATION IS BEING PROVIDED TO THE USER SO THAT AN INFORMED DECISION CAN BE MADE BEFORE INSTALLING ANY ELECTRICAL EQUIPMENT ON AN UNGROUNDED POWER SYSTEM CONTACT FACTORY FOR UNGROUNDED APPLICATIONS Aninsulated grounding conductor is required in addition to any metallic raceway which may be used as a grounding conductor For parallel connected SPDs the grounding conductor should be the same wire size as the associated power conductors continued on page 5 Liebert SPDs SL 22075 Rev 0 9 2010 Liebert VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS Source Configurations Nominal Operating Voltage L N L G Maximum Continuous Model Voltage Code Operating Voltage Found in part number Single Phase L N 2 W G L Single Phase L L 2 W G L1 L2 G Single Phase 3 W G Three Phase Delta 3 W G e 120 230 240 240 380 415 380 415 480 480 Three Phase Wye 4W G Three Phase Wye 3 W G No Neutral A B c G 220 240 220 240 380 415 220 240 380 415 Installation Operation and Maintenance Manual Liebert SPDs SL 22075 Rev 0 9 2010 Note 1 For other voltages or source configurations consult factory Liebert Surge Protective Devic
13. HETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT NEGLIGENCE STRICT LIABILITY TORT OR OTHERWISE Miscellaneous e NO SALESPERSON EMPLOYEE OR AGENT OF LIEBERT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY Warranty terms may be modified if at all only in a writing signed by a Liebert officer e Liebert obligations under this warranty are conditioned upon Liebert timely receipt of full payment of the product purchase price and any other amounts due Liebert reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others In the event that any provision of this Warranty should be or becomes invalid and or unenforceable during the warranty period the remaining terms and provisions shall continue in full force and effect This Warranty shall be governed by and construed under the laws of the State of Ohio without reference to the conflict of laws principles thereof e This Warranty represents the entire agreement between Liebert and User with respect to he subject matter herein and supersedes all prior or contemporaneous oral or written communications representations understandings or agreements relating tothis subject Installation Operation and Maintenance Manual 10 Liebert SPDs SL 22075 Rev 0 9 2010 Liebert Corporation 1050 Dearborn Drive P O Box 29186 Columbus OH 43229 800 877 9222 Phone US amp Canada Only 614 888 0246 Outside U S 6
14. aken to avoid condensation All packing and shipping materials should be left intact until the unit is ready for final installation If the unit has been stored for an extended period of time the unit should be cleaned and carefully inspected before placing into service Installation Operation and Maintenance Manual Surge Protective Devices LOCATION CONSIDERATIONS For optimum transient surge protection coordinated surge suppression should be applied at the service entrance and all other electrical connections to the building telephone CATV etc at known surge generating loads within the building large motors arc welders switched capacitors etc as well as at sensitive electronic loads such as computers electronic appliances solid state motor drives etc For interconnected electronicloads suchas by way of data cabling transient surge suppression should also be applied to the interconnecting wiring data cables Environment Unit is designed for operation indoors in ambient temperatures of 40 C 40 F to 60 C 140 F with a relative humidity of 0 to 95 non condensing The unit is provided in an industrial use enclosure which is dust tight and drip tight and should not be installed in areas with excessive dust corrosive vapors flammable materials or explosive atmospheres Audible Noise The audible noise of the unit is less than 40 dB at 5 feet which allows its placement within almost any room
15. assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components Drawings Descriptions Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the certified drawings if any applicable thereto to Liebert s final invoices and to applicable Liebert product brochures and manuals current as of the date of product shipment Descriptions Liebert does not control the installation and use of any Liebert product Accordingly it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE Obtaining Performance Under This Warranty Within a reasonable time but in no case to exceed thirty 30 days after User s discovery of a defect User shall contact Liebert at 1 800 LIEBERT 543 2378 and request a return authorization number User shall ship the product with proof of purchase to Liebert freight prepaid Liebert products shipped to Liebert without a return authorization number will be refused and returned freight collect to User at User s expense Liebert products shipped by User to Liebert which have incurred freight damage due to User s improper packaging of the product will not be covered by his Warranty and any repairs or replacement parts components or products needed will be invoiced in the full current p
16. es PARALLEL CONNECTIONS Typical Parallel Connections without Internal Rotary Disconnect e z 3 gp 2 5 E a 8 g i i M i IN Protected Loads 4 Neutral Liebert Surge t gt Phase s Protective Device Transient Protected Safety Panel Wire should be Seoul less than 5 feet and straight as possible Typical Parallel Connections with Internal Rotary Disconnect o 9 3 8 POP a ww NE 0 LA To Protected Loads t Neutral Liebert Rotary Surge Disconnect Phase s Protentive evice Transient j Ground Protected cem Panel Wire should be Ground less than 5 feet and straight as possible ELECTRICAL CONNECTIONS continued from page 3 Grounding conductors must be routed with the associated power conductors in the same raceway conduit When metallic raceways are used adequate electrical continuity must be maintained at all raceway connections particularly raceway terminations to the electrical enclosures The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety hazard and is not recommended Grounding Electrode Surge protective devices do not discharge all surges to ground earth Surge protective devices can also divert the surge current back to its source to complete the electrical circuit
17. for maximum system performance The installer should perform the following steps to assure a quality installation The entire installation manual should be read before starting installation These instructions do not replace national or local electrical codes Check applicable electrical codesto ensure compliance Installation ofthe Liebert SPD system should only be performed by qualified personnel 1 Insure that all power is removed before beginning installation A qualified licensed electrician shall install all electrical connections Summary Alarm Contacts X2 in 1 Normally Open in 2 Common in 3 Normally Closed Liebert SH Series Without Disconnect Weight Ibs Dimensions Inches Model 2 RIAs aes sHo25 16 16 8 17 25 9 5 0 44 35 sH032 16 16 8 1725 10 0 44 49 suo40 16 16 8 17 25 10 0 44 49 suoz5 20 20 8 2125 14 O44 85 Installation Operation and Maintenance Manual 7 SESTERCE SCR E EG sH025 20 16 8 21 25 10 0 44 45 SH032 20 36 8 2125 10 58 sHo40 20 16 8 SH075 20 24 8 21 25 2 The SPD is provided in NEMA 4 enclosures which are suitable for use in indoor or outdoor installations 3 Determine where the SPD is to be mounted allowing for minimum length of wire between itself and the input power terminals of the service panel Punch or cut the proper hole size in the side of the SPD closest to the knockout
18. ge 4 for voltage rating applications with typical power source configurations A CAUTION Wire Connections With parallel connection the size of the wiring to the SPD unit is independent of the protected circuit s ampacity NEC Article 285 21 B requires surge suppressor connecting conductors to be at least 14 copper or 12 aluminum To reduce the wiring impedance to surge currents it is recommended that the phase neutral if required and ground conductors are twisted together and routed in the same raceway conduit Avoid any sharp bends in the conductors Overcurrent Protection The SPD unit conducts practically no current under normal operation and only conducts very short duration transient surge currents NEC Considerations The following is from the National Electric Code 2008 Edition NEC 285 21 Connections NEC 285 23 Type 1 SPDs Shall be installed in accordance with 285 35 A and B A Installation Type 1 SPDs shall be installed as follows 1 Type 1 SPDs shall be permitted to be connected to the supply side of the service disconnect as permitted in 230 82 4 or 2 Type 1 SPDs shall be permitted to be connected in Type 2 locations as specified in 285 24 B At the service When installed at the services the grounding conductor of a Type 1 SPD shall be connected to one of the following Installation Operation and Maintenance Manual 1 Grounded service conductor 2 Grounded electrode conductor 3 Gr
19. ounding electrode for service 4 Equipment grounding terminal in the service equipment Voltage Protection Ratings To obtain the voltage protection ratings VPRs as obtained by Underwriters Laboratory Incorporated in accordance with the Standard for Safety Surge Protective Devices SPDs Standard 1449 Third Edition released 2009 marked on this product the wire size listed for each product must be utilized to connect the unit to your facilities power grid Connections made with conductors other than the wire size listed may result in different VPRs Circuit Ampacity Limitations Representative samples of these products have been investigated by Underwriters Laboratories Incorporated to withstand without exposing live circuits or components at system voltages and fault currents up to 200 000 AIC as described in the Standard for Safety Surge Protective Devices SPDs Standard 1449 Third Edition released 2009 System Grounding and Bonding The performance and safety of any SPD system is dependent on proper grounding and bonding Grounding is required for safety Correct implementation also enhances equipment performance Incorrect grounding can reduce or impede the SPD s operation All electrical circuits to the SPD must include an aaa grounding conductor A CAUTION oe by the NEC and local UNGROUNDED POWER SYSTEMS ARE INHERENTLY UNSTABLE AND CAN PRODUCE EXCESSIVELY HIGH LINE TO GROUND VOLTAGES DURING CERTAIN
20. rice amount and returned reight collect to User Subject to the limitations specified herein Liebert will repair or replace at its option without charge for Liebert labor or materials subsequent o its inspection F O B Liebert s facility the Liebert product warranted hereunder which does not conform to the Warranty Replacement parts components or products shipped to User prior to Liebert s receipt and inspection of the product claimed to be defective shall be invoiced in the ull current price amount and shipped freight collect F O B Liebert s facility Warranty coverage will be extended only after Liebert s receipt of he claimed defective product within thirty 30 days of shipment of any replacement parts components or products if applicable and only if Liebert s inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of his Warranty All defective products and component parts replaced under this Warranty become the property of Liebert Warranty Performance of Component Manufacturers It is Liebert s practice consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible to cooperate with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects in the product components Accordingly Liebert may utilize third parties in the performance of Wa
21. rranty work including repair or replacement hereunder where in Liebert s opinion such work can be performed in less time with less expense or in closer proximity to the Liebert product Installation Operation and Maintenance Manual 9 Liebert SPDs SL 22075 Rev 0 9 2010 Liebe rt Surge Protective Devices Items Not Covered By Warranty THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse improper application wrong or inadequate electrical current or connection negligence inappropriate on site operating conditions corrosive atmosphere repair by non Liebert designated personnel accident in transit tampering alterations a change in location or operating use exposure to the elements Acts of God theft or installation contrary to Liebert s recommendations or specifications or in any event if the Liebert serial number has been altered defaced or removed Notwithstanding the foregoing the following Acts of God are covered lightning induced surges which are transients spikes or other sub cycle discontinuous events impinging on normally applied voltage as defined by reference data in the latest version of IEEE C62 41 and the Liebert product performance specifications THIS WARRANTY DOES NOT COVER shipping costs installation costs circuit breaker resetting or maintenance or service items and further except as provided herein does NOT include labor costs or transportation charges arising from the replacement of the Lieber
22. t product or any part thereof or charges to remove a reinstall same at any premises of the User THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Liebert product in combination with any electrical or electronic components circuits systems assemblies or other materials not furnished by Liebert Liebert does NOT warrant the suitability for use or the results ofthe Liebert product in combination with the products of others THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT DESIGNED FOR USE IN THE FOLLOWING APPLICATIONS i ANY NUCLEAR OR RELATED APPLICATIONS AND ii LIFE SUPPORT AND PATIENT CONNECTED AND APPLIED MEDICAL AND DENTAL APPLICATIONS REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD Limitations e THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE e USER S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIEBERT PRODUCT AS SET FORTH HEREIN e IF USER S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION LIEBERT S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE e IN NO EVENT SHALL LIEBERT ASSUME ANY LIABILITY FOR INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER INCLUDING WITHOUT LIMITATION LOST PROFITS BUSINESS INTERRUPTION OR LOSS OF DATA W
23. to be utilized in the service panel Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the table below Mount surge suppressor to wall using 3 8 mounting hardware continued on page 7 Dimensional Information Liebert SH Series ge Service Panel for ase Loads to be Protected Phase L3 C Disconnect Main Breaker for Panel Dedicated Neutral Buss Disconnect Optional Ground Buss Recommended Wire Entrance Liebert SH Series With Disconnect Dimensions Inches Weight Ibs 044 21 25 Liebert SPDs SL 22075 Rev 0 9 2010 Liebert Surge Protective Devices INSTALLATION INSTRUCTIONS continued from page 6 4 Connect black wires line or phase marked L1 A L2 B or L3 C the white wire neutral marked N and the green wire ground marked G of the SPD using the wire range listed below To yield the best performance of the SPD within the electrical distribution system keep all conductors as short as possible and avoid sharp bends 5 Connection to the unit s summary alarm contacts shall be with 18 22 AWG The ratings of the Form C contacts are 5 amps at 250 VAC maximum with a power factor of 1 0 For additional information see Monitoring section 6 Apply power The surge protector is fully operational when the GREEN LEDs onthe modules and the front door of enclosure are illuminated If the GREEN LEDs are extinguished or a R
24. your Warranty carefully This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty TEN YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP LIEBERT PRODUCTS COVERED Liebert SH Series Interceptor Terms of Warranty As provided herein the Liebert product is warranted to be free of defects in material and workmanship for a period of ten 10 years from the date of product shipment from Liebert The shipment date will be determined only from the Liebert bill of lading If any part or portion of the Liebert product fails to conform to the warranty within the warranty period Liebert at its option will furnish new or factory remanufactured parts for repair or replacement of that part or portion Warranty Extends to First Purchaser for Use Non transferable This Warranty is extended to the first person firm association or corporation for whom the Liebert product specified herein is originally installed for use the User in the fifty United States excluding territories or Canada This Warranty is not transferable or assignable without the prior written permission of Liebert Assignment of Warranties Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of the Liebert product and which are assignable but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties