Home
        Carrier 38CKB Air Conditioner User Manual
         Contents
1.    460 4 14 3 8 365 1 3 4 19 1  048  060 30 762 0 6 1 2 A   596 9 20 508 0 7 8 22 2   Fig  2   Unit Reference Drawing  3  Run refrigerant tubes as directly as possible by avoiding A CAUTION    unnecessary turns and bends     4  Leave some slack between the structure and the unit to absorb Towpieyent compressor damage  DO NOT bury morethan 36    in   914mm  of refrigerant tubing  If ANY tubing is buried   provide 6 in   152mm  vertical rise at service valve     vibration        5  When passing refrigerant tubes through the wall  seal the    opening with RTV or other pliable silicon based caulk   See OUTDOOR UNITS CONNECTED TO FACTORY APPROVED  Fig  3   INDOOR UNITS     Outdoor unit contains correct system refrig   6  Avoid direct lineset contact with water pipes  ductwork  floor erant charge for operation with indoor unit of the same size when  joists  wall studs  floors  and walls  connected by 15 ft  4 55m  of field supplied or factory accessory    7  Do not suspend refrigerant tubing from joists and studs with a tubing  Check refrigerant charge for maximum efficiency     rigid wire or strap which comes in direct contact with the REFRIGERANT TUBING     Connect tubing to fittings on out   tubing   See Fig  3   door unit vapor and liquid service valves   See Fig  2      8  Ensure that tubing insulation is pliable and completely sur        rounds the vapor tube  A WARNING   9  When necessary  use hangar straps which are   in   25mm  Relieve pressure and recover all refrigerant 
2.    Ca       Carrier    ee        HEATING  amp  COOLING    38CKB   50 Hz  Air Conditioning Unit       Installation and Start Up Instructions    NOTE  Read the entire instruction manual before starting the  installation   SAFETY CONSIDERATIONS   Improper installation  adjustment  alteration  service  maintenance   or use can cause explosion  fire  electrical shock  or other  conditions which may cause death  personal injury  or property  damage  Consult a qualified installer  service agency  or your  distributor or branch for information or assistance  The qualified  installer or agency must use factory authorized kits or accessories  when modifying this product  Refer to the individual instructions  packaged with the kits or accessories when installing     Follow all safety codes  Wear safety glasses  protective clothing   and work gloves  Use quenching cloth for brazing operations   Have fire extinguisher available  Read these instructions thor   oughly and follow all warnings or cautions included in literature  and attached to the unit  Consult local building codes and national  electric codes for special requirements     Recognize safety information  This is the safety alert symbol  N    When you see this symbol on the unit and in instructions or  manuals  be alert to the potential for personal injury     Understand the signal word DANGER  WARNING  or CAU   TION  These words are used with the safety alert symbol  DAN   GER identifies the most serious hazards which will resu
3. COMMENDATIONS  1  Locate the unit away from windows     2  Ensure that vapor and liquid tube diameters are appropriate to  the capacity of the unit   See Table 1         Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations     Book  1  4 PC 101    Catalog No  013 862  Tab  3a  2a    Printed in U S A  Form 38CKB C1SI    Pg 1 12 94 Replaces  New    AIR IN    NOTES   DIeCHARGE 1  Allow 30 in   762  clearance to service sides of unit  48 in    1219 2  above unit  6 in   152 4  on one side  12 in   304 8  on remaining   side  and 24 in   609 6  between units for proper airflow   2  Minimum outdoor operating ambient in cooling mode is 55 F  12 8 C     max 115 F  46 1 C  AIR 3  Dimensions in parenthesis are in millimeters    4  Series designation is the 13th position of the unit model number           AIR IN    AIR  DISCHARGE  AIR IN    AIR Pree 4 AIR DISCHARGE    RATING LABEL 5  FIELD POWER P P  SUPPLY CONN    i IN  DIA  22 22  HOLE WITH  114 IN  DIA  28 57  KNOCKOUT a ars  AND 134 IN  DIA  34 92  KNOCKOUT  P  Cc           O  4 KO FIELD CONTROL    SUPPLY CONN  7  IN  DIA  22 22  HOLE  3  IN  DIA  9 53  LIQUID LINE CONN                   F DIA SUCTION LINE CONN S                                           A91173   UNIT SIZE abe   F  In  mm In    mm In  mm In  mm  018 18 457 2 3   381 0 10 3 16 258 8 5 8 15 9  024 22 1 2 571 5 3 11 16     460 4 14 3 8 365 1 5 8 15 9  036 22 1 2 571 5 3 11 16  
4. OR     4s      LIQUID LINE SOLENOID TRANS  TRANSFORMER  IFR     INDOOR FAN RELAY    A94331  Fig  5   24 v Control Circuit Connections    Copyright 1994 CARRIER Corp    7310 W  Morris St  e Indianapolis  IN 46231 38ckbc1s       Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations     reek x k  PC 101 Catalog No  013 862 Printed in U S A  Form 38CKB C1SI Pg 6 12 94 Replaces  New  al aj 2a    
5. RING     Route 24 v control wires  through control wiring grommet and connect to brown and blue  pigtails supplied in unit splice box   See Fig  5      Use furnace transformer  fan coil transformer  or accessory trans   former for control power  24 v 40va minimum     NOTE  Use of available 24 v accessories may exceed the mini   mum 40 va power requirement  Determine total transformer load   ing and increase the transformer capacity or split the load with an  accessory transformer as required     Step 6   Compressor Crankcase Heat    When equipped with a crankcase heater  energize heater a mini   mum of 24 hrs before starting unit  To energize heater only  set  thermostat to OFF position and close electrical disconnect to  outdoor unit    A crankcase heater is required if the refrigerant tubing is longer  than 50 ft  15 24m      Step 7   Install Electrical Accessories  If Any    Refer to the individual instructions packaged with the kit or  accessory when installing     Step 8   Start Up and Check Charge    A CAUTION    To prevent compressor damage or personal injury  observe  the following      Do not overcharge system with refrigerant    e Do not operate unit in a vacuum or at negative pressure    e Do not disable low pressure switch     In scroll compressor applications    e Dome temperatures may be hot    e In 3 phase application  incorrect phasing will cause reverse  rotation  resulting in elevated noise levels  equalized pres   sures and reduced current draw  Correct by 
6. before system  wide and conform to the shape of the tubing insulation   See repair or final unit disposal to avoid personal injury or death   Fig  3   Use all service ports and open all flow control devices     10  Isolate the hangar straps from the insulation by using metal including solenoid valves     sleeves bent to conform to the shape of the insulation        If refrigerant tubes or indoor coil is exposed to atmospheric  conditions for longer than 5 minutes  it must be evacuated to 500  microns to eliminate contamination and moisture in the system     Table 1   Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters                   LIQUID VAPOR  UNIT SIZE Connection Dia  Tube Dia  Connection Dia  Tube Dia   In  mm In  mm In  mm In  mm  018  024 3 8 9 53 3 8 9 53 5 8 15 88 5 8 15 88  036 3 8 9 53 3 8 9 53 3 4 19 05 3 4 19 05  048 3 8 9 53 3 8 9 53 7 8 22 23 7 8 22 23  060 3 8 9 53 3 8 9 53 7 8 22 23 1 1 8 28 58                            1  Tube diameters are for lengths up to 50 ft  15 24m   For tube sets over 50 ft  15 24m   consult Long Line Application Guideline     2  Do not apply capillary tube indoor coils to these units     A CAUTION    To prevent damage to unit or service valves observe the  following     e Use a brazing shield   e Wrap service valves with wet cloth or use a heat sink  material     SWEAT CONNECTION     Use refrigerant grade tubing  Service  valves are closed from factory and ready for brazing  After  wrapping the service valve 
7. g  1   Model 38CKB    For proper airflow  a 6 in   152mm  clearance on 1 side of unit and  12 in   305mm  on all remaining sides must be maintained   Maintain a distance of 24 in   610mm  between air conditioners   Position so water  snow  or ice from roof or eaves cannot fall  directly on unit    On rooftop applications  locate unit 6 in   152mm  above roof  surface  Where possible  place unit above a load bearing wall   Arrange supporting members to adequately support unit and  minimize transmission of vibration to building  Consult local  codes governing rooftop applications    Step 3   Replace Indoor AccuRater   Piston  if Required  Check indoor coil piston to see if it matches the required piston  shown on unit rating label  If it does not match  replace indoor coil  piston with piston shipped with this unit  The piston shipped with  outdoor unit is correct for any approved indoor coil combination     4 CAUTION    Remove indoor coil piston if unit is to be installed on system  with a TXV metering device        Step 4   Make Piping Connections   Outdoor units may be connected to indoor sections using accessory  tubing package or field supplied refrigerant grade tubing of correct  size and condition  For tubing requirements beyond 50 ft  15 24m    consult Long Line Application Guideline which is available at  your local distributor    NOTE  In some cases  noise in the living area has been traced to  gas pulsations from improper installation of equipment     INSTALLATION RE
8. le from unit per local codes     A WARNING       To avoid personal injury or death  do not supply power to unit  with compressor terminal box cover removed           A WARNING    The unit cabinet must have an uninterrupted or unbroken  ground to minimize personal injury if an electrical fault  should occur  The ground may consist of electrical wire or  metal conduit when installed in accordance with existing  electrical codes  Failure to follow this warning can result in an  electric shock  fire  or death              ROUTE GROUND AND POWER WIRES     Remove access  panel and control box cover to gain access to unit wiring  Extend  wires from disconnect through power wiring hole provided and  into unit control box   See Fig  2   Size wires per local codes  but  not smaller than minimum wire size shown on unit rating label     CONNECT GROUND AND POWER WIRES     Connect ground  wire to ground connection in control box for safety  Connect  power wiring to contactor as shown in Fig  4     DISCONNECT  PER N E C  AND OR  LOCAL CODES       CONTACTOR    O  a oe  FIELD POWER  a OO  _3 PHASE ONLY BLUE 7  gee eee E    WIRING  GROUND  LUG                   a          A94025  Fig  4   Line Power Connections    NOTE  Use No  18 AWG  American Wire Gage  color coded   insulated  35   C minimum  wire  If thermostat is located more than  100 ft  30 5m  from unit as measured along the control voltage  wires  use No  16 AWG color coded wires to avoid excessive  voltage drop     CONNECT CONTROL WI
9. lt in severe  personal injury or death  WARNING signifies hazards which  could result in personal injury or death  CAUTION is used to  identify unsafe practices which would result in minor personal  injury or product and property damage     A WARNING    Before installing  modifying  or servicing system  main elec   trical disconnect switch must be in the OFF position  There    may be more than 1 disconnect switch  Lock out and tag  switch with a suitable warning label  Electrical shock can  cause personal injury or death     INSTALLATION  Step 1   Check Equipment and Jobsite  UNPACK UNIT     Move to final location  Remove carton taking  care not to damage unit     INSPECT EQUIPMENT     File claim with shipping company  prior to installation if shipment is damaged or incomplete  Locate  unit rating label on unit service panel   See Fig  2   It contains  information needed to properly install unit  Check rating label to  be sure unit matches job specifications     Step 2   Install on a Solid  Level Mounting Pad       If conditions or local codes require the unit be attached to pad   tiedown bolts should be used and fastened through knockouts  provided in unit base pan  Refer to unit mounting pattern in Fig  2  to determine base pan size and knockout hole location     When installing  allow sufficient space for airflow clearance   wiring  refrigerant piping  and service  Allow 30 in   762mm   clearance to service end of unit and 48 in   1219mm  above unit              A94356  Fi
10. reversing power  connection L1 and L2 on contactor        A CAUTION    To prevent personal injury wear safety glasses  protective  clothing  and gloves when handling refrigerant and observe  the following     e Back seating service valves are not equipped with Schrader  valves  Fully back seat  counter clockwise  valve stem before  removing gage port cap    e Front seating service valves are equipped with Schrader  valves        A CAUTION       Do not vent refrigerant to atmosphere  Recover during system  repair or final unit disposal     1  Fully back seat  open  liquid and vapor tube service valves     2  Unit is shipped with valve stem s  front seated and caps  installed  Replace stem caps after system is opened to refrig   erant flow  back seated   Replace caps finger tight and tighten  additional 1 6 turn with wrench     3  Close electrical disconnects to energize system     4  Set room thermostat at desired temperature  Be sure set point  is below indoor ambient temperature     5  Set room thermostat at COOL and fan switch at FAN or  AUTO  as desired  Operate unit for 15 minutes  Check system  refrigerant charge     6  Factory charge is shown on unit rating label  Adjust charge by  following procedure shown on charging tables located on unit     Step 9   Leave User   s Manual with Owner    For continued high performance and to minimize possible equip   ment failure  periodic maintenance MUST be performed on this  equipment    Leave User   s Manual with owner  Explain sy
11. stem operation and  periodic maintenance requirements outlined in manual  Frequency  of maintenance may vary depending on geographic areas  such as  coastal applications which require more frequent maintenance     THERMOSTAT THERMOSTAT FURNACE                                                                                                                                                                                                                                                                                                                                                                                     Apes s25  i R H H  R  TLA MOTOR   m  i   POWER   c H     ames     M   SUPPLY    Gps   Cs 46  c   m     TRANS    Y H    c    4 IU AERES Breva rere EE   Aa          Wire ee  COOLING ONLY ONE STAGE COOLING   GAS HEATING  THERMOSTAT FAN COIL THERMOSTAT INDOOR UNIT  R H       4   R R H 4  R  c H        a NAE  F m    ea o     Vaa E 4yY bs Lape on Y 4 Y Len L  w          4  we Ww  4         W  ONE STAGE COOLING   ELECTRIC HEAT ONE STAGE COOLING   HEATING    ACCESSORY LIQUID LINE SOLENOID    NOTES     1  Wiring must conform to local codes    2  LLS required on some units  See specific unit instructions    3  Transformer required is 24 v  40 va minimum  A 60 va or external power source may  be necessary when installing accessories    4  When installing electronic thermostat  connect transformer common to thermostat C     LEGEND    c      COMPRESSOR CONTACTOR  m      INDOOR FAN MOT
12. with a wet cloth  the tubing set can be  brazed to the service valve using either silver bearing or non silver  bearing brazing material  Consult local code requirements  Refrig   erant tubing and indoor coil are now ready for leak testing  This  check should include all field and factory joints     NOTE  Avoid contact between tubing and structure                                OUTDOOR WALL  INDOOR WALL  CAULK    A      y F LIQUID TUBE   amp    3     AN E VAPOR TUBE  INSULATION  THROUGH THE WALL  g sT  HANGER STRAF   AROUND VAPOR    TUBE ONLY  INSULATION  VAPOR TUBE  fe   fe   fe   a TE 3  1   MIN ee ee  X   25 mm  LIQUID TUBE    SUSPENSION    A94330  Fig  3   Piping Installation    Step 5   Make Electrical Connections    Be sure field wiring complies with local and national fire  safety   and electrical codes  and voltage to system is within limits shown  on unit rating label  Contact local power company for correction of  improper voltage  See unit rating label for recommended circuit  protection device        NOTE  Operation of unit on improper line voltage constitutes  abuse and could affect unit reliability  See unit rating label  Do not  install unit in system where voltage or phase imbalance may  fluctuate above or below permissible limits    NOTE  Use copper wire only between disconnect switch and  unit    NOTE  Install branch circuit disconnect per local codes of  adequate size to handle unit starting current  Locate disconnect  within sight from and readily accessib
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
MODE D`EMPLOI  Panasonic Toughbook Y7 User's Manual    Copyright © All rights reserved. 
   Failed to retrieve file